Hitachi WJ200 Genric Mill Programming Parameters
Hitachi WJ200 Genric Mill Programming Parameters
Hitachi WJ200 Genric Mill Programming Parameters
FROM
TO
Remove this jumper by pressing on the little orange tab and pulling on the wire ferule. Relocate the jumper by inserting
the pins into L to PLC logic terminals. Connect the pins on the VFD cable to the VFD input logic terminals by just pushing
the pins into the labeled logic input hole, give a slight tug when inserted to make sure it is locked in. Red wire labeled 24
to P24, connect the remaining wires to terminals as shown below and per the wire numbered labels (1, 2, 3, etc.) for the
respective input.
The VFD will need to be programmed to accept commands from the terminal inputs and to set all the parameters. It will not operate until this is done. Load
the Hitachi software and driver to your computer. Remove the little rubber port and connect the USB cable to the port on the WJ200, . Do not connect the
USB cable to the computer yet, you must first power up the WJ200 and the computer, then connect the cable to your computer. It should show the USB
driver is loaded under your devices. See the separate PDF file for the specific programming via a computer.
http://www.hitachi-america.us/ice/inverters/products/ac_variable_speed_drives/wj200/
Software is available at no cost from the Hitachi website site:
http://www.hitachi-america.us/ice/inverters/support_service_sales/software_dloads
You must install BOTH the Then ProDriveNext (2.1.1) AND the USB driver software. The USB driver must be installed before connecting a computer to the VFD.
With the WJ200 turned on and the USB cable connected to your computer, check in Windows under "Devices and Printers" the your Hitachi shows up in the pop
up window. Then run the ProDriveNext software program. The ProDriveNext software program has FOUR separate modules that are sequentially installed, so
continue the installation until it says it is completed.
1. The software in NOT intuitive until you have used it for awhile. When you load the software, click on the "File" tap at the top menu, then select "New
Solution" each time when connecting to the VFD. Otherwise it tries to load old saved VFD files that are saved on your computer. There may be a way to edit
them and download back to the VFD, but haven't been able to do this.
2. In the window tab "Add device" check the lower two check boxes, "Read Items:....", then click the "Online&Read" button below. A pop-up screen should
indicate that the VFD is on-line and connected, hit the OK button, and this will start the download of the VFD programmed parameters to the computer
program.
3. In the left Toolbox pane you will see the VFD is connected. Click on the Parameter Data, a series of tabs and screen should come up in the right viewing pane.
Note the series if Taps for each Parameter Group (F, A B, C, H and P). Each Group Tab is a separate list of programmable functions, so you need to click on that
tab to see the parameter group.
4. On any one Group Page, you can modify each parameter by clicking on the "Set Value" cell and entering the new numerical value. The parameter line will be
highlighted with any changes you make, you can do one or many changes on multiple lines. Note: the value is not changed in the VFD memory until you either
hit the "Program" tab at the top and select "Download (PC->Device), or you can place your cursor over the changed parameter, hit the "right " mouse key, and a
pop-up menu will give you the same options. I recommend changing a few parameters, downloading them to the VFD and checking that everything is working.
Then doing a few more within a group. Also for tweaking values once you get familiar with the effects.
5. There is a software Auto-tune motor function, used to determine your motor's parameters H031-H034. You need to run the Auto-Tune to load the motor
2
parameters, if doing this with motor rotation, you must remove the motor drive belt. Once you run Auto-tune set H002 to 02:(Auto tuned data) to run the
VFD off of your motor data.
6. The WJ200 may need to be programmed before it will work using the terminal commands and external speed control. Some of the software operated motor
controls may change some of the VFD programming and it may stop responding to command (they change A001 and A002, so recheck these if the terminal block
commands and external pot speed control stop working). Keep a hard copy of the program changes so you make. Be sure that the "Logic input" wiring
connections match up with their assigned programmed functions "C001-C007".
READ THIS: If you manually program the WJ200 via the keypad you must first:
1. Change B037 to "00" for full display of all functions. You must press both the up and down arrows to access single-digit edit mode since this feature is not
accessible in the default basic display. You must change B037 before you can change B031.
AND THEN
2. Change B031 to "10". This unlocks all the high level program functions for editing. Then make the following program changes that are highlighted.
WJ200
Type: Parameter Set
ProDriveNext
Version:2.3.1.0
KEY:
-------------High
Importance
F
Group
Data
ID
F001
0 Hz
F002
3 s
10
F202
10 s
10
F003
3 s
10
Data Name
Set value
Unit
Default value
Range
Comments
0
Set by VFD
Acceleration time of 3 seconds with an S
acceleration curves works well
10 s
10
0.01 ...
3600.00
F004
00:(Forward)
A
Group
Data
ID
A001
Data Name
Set value
Frequency source
01:(Control terminal)
02:(Function F001
setting)
A201
A002
02:(Function F001
setting)
01:(Control terminal)
02:(Function F001
setting)
02:(Run key on
keypad, or digital
operator)
A202
02:(Run key on
keypad, or digital
operator)
02:(Run key on
keypad, or digital
operator)
A003
Base frequency
60 Hz
60
A203
A004
60 Hz
75 Hz
60
60
A204
60 Hz
60
00:(Forward)
Unit
Default value
Range
THIS MUST BE SET TO "01" IF YOU USE AN
EXTERNAL POT CONNECTED TO
TERMINALS "H, O & L" TO SET YOUR RPM
SPEED CONTROL.
THIS MUST BE SET TO "01" IF YOU USE
COMMANDS SENT TO THE VFD VIA
CONTROL BLOCK TERMINAL "1-7", THIS
MAY GET RESET TO "02" WHEN YOU DO
THE MOTOR AUTOTUNE AND THE VFD
WILL NO LONGER RESPONDS TO THE
TERMINALS, SO MAY NEED TO BE RESET
BACK TO "02". WHEN SET TO "01" VFD
RUN KEY WILL NOT WORK, ONLY STOP
KEY.
A005
[AT] selection
A011
A015
A016
A017
A038
A039
EzSQ selection
Jog frequency
Jog stop mode
00:(disabling)
04:(Controlled
deceleration (valid
during run))
04:(Controlled
deceleration (valid
during run))
A041
A241
00:(Manual torque
boost)
00:(Manual torque
boost)
A042
A242
01:(Automatic torque
boost)
00:(Manual torque
boost)
1 %
1 %
A012
A013
A014
A043
00:(Select between
[O] and [OI] at [AT]
(ON=OI, OFF=O))
00:(Select between
[O] and [OI] at [AT]
(ON=OI, OFF=O))
0 Hz
0 Hz
0 %
0.00 ...
400.00
0.00 ...
400.00
0 ... 100
100 %
100
0 ... 100
01:(Use 0Hz)
01:(Use 0Hz)
31
1 ... 30, 31
1
1
00:(disabling)
6 Hz
5 %
5
A243
A044
A244
5 %
03:(Sensorless vector
(SLV))
00:(Constant torque)
5
00:(Constant
torque)
00:(Constant
torque)
A051
A052
DC braking frequency
0.5 Hz
0.5
A053
A054
0 s
80 %
0
50
A061
A261
A045
A245
A046
A246
A047
A247
A055
A056
A057
A058
A059
100 %
100 %
100
100
100
100
20 ... 100
20 ... 100
0 ... 255
100
100
0 ... 255
100
100
0 ... 255
100
100
0 ... 255
00:(Disable)
00:(Disable)
0 s
0.5
01:(Level detection)
0
0
5
0 ... 100
0.0 ... 60.0
2.0 ... 15.0
75 Hz
0 Hz
0.00 ...
80.00
0.00 ...
01:(Level detection)
0 %
0 s
8 kHz
A062
0 Hz
A262
0 Hz
A063
0 Hz
A064
0.5 Hz
0.5
A065
0 Hz
A066
0.5 Hz
0.5
A067
0 Hz
A068
0.5 Hz
0.5
A069
0 Hz
A070
A071
A072
0 s
A073
00:(PID Disable)
00:(PID Disable)
1
1 s
A074
0 s
A075
PV scale conversion
A076
PV source
A077
A078
A079
01:([O] terminal
(voltage in))
00:(PID input = SP-PV)
0.00 ...
25.00
0.0 ...
3600.0
0.00 ...
100.00
0.01 ...
99.99
00:([OI] terminal
(current in))
00:(PID input = SPPV)
0 %
00:(Disabled)
60.00
0.00, 0.50 ...
80.00
0.00, 0.50 ...
60.00
0.00 ...
400.00
0.00 ...
10.00
0.00 ...
400.00
0.00 ...
10.00
0.00 ...
400.00
0.00 ...
10.00
0.00 ...
400.00
0.0 ... 60.0
0
00:(Disabled)
7
A081
02:(AVR enabled
except during
deceleration)
02:(AVR enabled
except during
deceleration)
A281
02:(AVR enabled
except during
deceleration)
02:(AVR enabled
except during
deceleration)
A082
03:(230)
00:(200)
A282
A083
00:(200)
V
1 s
00:(200)
A084
A085
A086
A092
A292
A093
A293
A094
A294
A095
A295
A096
0.3
100 %
00:(Normal
operation)
100
0.000 ...
10.000
50 ... 200
00:(Normal
operation)
0 %
5 s
10 s
10
3 s
10
10 s
10
0.01 ...
3600.00
0.00 ...
400.00
0 0.00 ...
400.00
0
0.00 ...
400.00
0 Hz
0 Hz
8
A296
A097
01:(S-curve)
01:(S-curve)
A098
00:(linear)
01:(S-curve)
A101
A102
A103
A104
A105
A131
A132
A141
A142
A143
Calculation symbol
A145
ADD frequency
A146
A150
A151
0 Hz
0 0.00 ...
400.00
Acceleration is default S curve, seems to
work well
Deceleration is linear. S curve may be
more likely to trip the overvoltage error.
0 Hz
0 Hz
20 %
20
0.00 ...
400.00
0.00 ...
400.00
0 ... 100
100 %
100
20 ... 100
1 ... 10
1 ... 10
0.00 ...
400.00
10
0 ... 50
10 %
10
0 ... 50
A152
A153
A154
A155
A156
A157
A161
A162
A163
A164
A165
B
Group
Data
ID
b001
b002
b003
b004
b005
01:(Use 0Hz)
Data Name
Set value
00:(Alarm output
after trip, no
automatic restart)
10 %
10
0 ... 50
10 %
10
0 ... 50
0 Hz
0 s
0 Hz
0
0
0 s
0.00 ...
400.00
0.0 ... 60.0
0.00 ...
400.00
0.0 ... 25.5
0 Hz
0 Hz
0 %
100 %
0
100
0.00 ...
400.00
0.00 ...
400.00
0 ... 100
0 ... 100
01:(Use 0Hz)
Unit
Default value
Range
00:(Alarm output
after trip, no
automatic restart)
1 s
1 s
00:(Disable)
00:(Disable)
00:(Restart 16 times)
00:(Restart 16
times)
10
b007
b008
b010
b011
b012
b212
b013
b213
b015
b016
b017
b018
b019
b020
b021
0 Hz
0.00 ...
400.00
3 times
1 ... 3
1 s
00:(Alarm output
after trip, no
automatic restart)
00:(Alarm output
after trip, no
automatic restart)
100 %
100
100 %
100
01:(Constant torque)
01:(Constant
torque)
01:(Constant
torque)
01:(Constant torque)
01:(Enabled for
acceleration and
constant speed)
20.0 ...
100.0
20.0 ...
100.0
0 Hz
0 %
0 Hz
0 %
0 Hz
0 ... 400
0 %
01:(Enabled for
acceleration and
constant speed)
11
b221
b022
160 %
b222
150 %
b023
b223
b024
01:(Enabled for
acceleration and
constant speed)
01:(Enabled for
acceleration and
constant speed)
1 s
00:(Disabled)
b026
b031
b033
b034
b035
0 hr
b036
b037
b030
150 %
150
1 s
01:(Enabled)
20.0 ...
200.0
0.1 ...
3000.0
01:(Enabled)
100 %
100
0.5 s
0.5
00:(freq at previous
shutoff)
10:unlock high level
program parameters
00:(No restriction)
20.0 ...
200.0
0.1 ...
3000.0
00:(freq at previous
shutoff)
01:(all parameters except B031
and output frequency F001 are
locked when [SFT] terminal is ON)
10
5 ... 20
0 ... 65535
0 ... 255
00:(No restriction)
2
00:(Full display)
01:(Enabled for
acceleration and
constant speed)
b029
20.0 ...
200.0
150 20.0 ...
200.0
1
0.1 ...
3000.0
1 0.1 ...
3000.0
1 s
b025
b027
b028
150
04:(Basic display)
12
display.
b038
b039
b040
b041
200 %
200
b042
200 %
200
b043
200 %
200
b044
200 %
200
b045
b046
00:(Disable)
01:(Reverse rotation
is protected)
00:(Disable)
01:(Reverse rotation
is protected)
b049
b050
00:(CT mode)
01:(Decelerates to a
stop)
220 V
00:(CT mode)
00:(Trips)
b053
b054
b060
b051
b052
b061
b062
001:(d001)
00:(Disable)
001:(d001)
00:(Disable)
00:(Quadrant-specific
setting mode)
00:(Quadrantspecific setting
mode)
0 ... 200,
255
0 ... 200,
255
0 ... 200,
255
0 ... 200,
255
360 V
360
1 s
0 Hz
100 %
100
0.0 ...
1000.0
0.0 ...
1000.0
0.01 ...
3600.00
0.00 ...
10.00
0 ... 100
0 %
0 ... 100
0 %
0 ... 10
13
b063
b064
b065
b070
b071
b075
b078
b079
b082
b083
b084
0 ... 100
0 %
0 ... 100
0 %
0 ... 10
255 %
255
255 %
255
40 C
40
0 ... 100,
255
0 ... 100,
255
-10 ... 50
1
0.5
2
1 ... 1000
0.10 ... 9.99
2.0 ... 15.0
00:(OFF)
1
0.5 Hz
12 kHz
00:(Initialization
disabled)
00:(Standard)
b089
01:(Enabled,
depending on the
output current)
b090
b091
b087
b088
100
00:(OFF)
b085
b086
100 %
00:(Initialization
disabled)
00:(Standard)
28
00:(Enabled)
00:(Restart from 0Hz)
0.01 ...
99.99
00:(Enabled)
00:(Restart from
0Hz)
01:(Enabled,
depending on the
output current)
10 %
00:(DEC (decelerate
to stop))
00:(DEC (decelerate
to stop))
14
b092
01:(Fan is ON during
run, OFF during stop
(5 minute delay from
ON to OFF))
01:(Fan is ON during
run, OFF during stop
(5 minute delay
from ON to OFF))
b093
b094
00:(Count)
00:(All parameters)
00:(Count)
00:(All parameters)
b095
b096
01:(Enable during
run only)
360
b097
b100
b101
b102
b103
b104
b105
b106
b107
b108
b109
b110
b111
b112
b113
b120
b121
b122
b123
50 Ohm
0
0
0
0
0
0
0
0
0
0
0
0
0
0
50
Hz
V
Hz
V
Hz
V
Hz
V
Hz
V
Hz
V
Hz
V
00:(Disable)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
50.0 ...
600.0
0
0.0 ... 800.0
0
0.0 ... 800.0
0
0.0 ... 800.0
0
0.0 ... 800.0
0
0.0 ... 800.0
0
0.0 ... 800.0
0 ... 400
0.0 ... 800.0
0
0
0
00:(Disable)
0 s
0 s
0 s
15
b124
b125
b126
b127
b130
b131
Deceleration overvoltage
suppression enable
Decel. overvolt. suppress level
b132
b133
0 s
0 Hz
0
0
100 %
0 Hz
100
0
01:(Enabled)
00:(Disabled)
390 V
380
1 s
1 times
0.2
1
b145
0.10 ...
30.00
0.00 ... 5.00
b150
b160
b161
b163
b164
b134
b165
b166
b171
b180
1 s
00:(No trip (Hardware
shutoff only))
00:(No trip
(Hardware shutoff
only))
d001
d001
d002
00:(Freq. set disabled)
00:(Disable)
d001
d001
d002
00:(Freq. set
disabled)
00:(Disable)
02:(Ignore)
00:(R/W enable)
00:(Disabling)
00:(Initialization
disable)
02:(Ignore)
00:(R/W enable)
00:(Disabling)
00:(Initialization
disable)
16
C
Group
Data
ID
C001
INPUTS FOR 2 WIRE CONTROL USING A SINGLE 3 POSITION ON-OFF-ON SUSTAINED SWITCH. THE
MACHINE COULD RESTART IF LEFT IN A RUN POSITION WHEN THE VFD IS TURENED ON, THE MACHINE
SHOULD BE WORRIED TO USE THE USP:UNATTENDED START PROTECTION.
Data Name
Set value
Unit
Default value
Range
Input [1] function
00:(FW:FORWARD
Run/Stop)
01:(RV:Reverse
Run/Stop)
06:(JG:Jogging)
00:(FW:FORWARD
Run/Stop)
01:(RV:Reverse
Run/Stop)
02:(CF1:Multi-speed
Select,Bit 0 (LSB))
C002
C003
C004
13:(USP:Unattended
Start Protection)
03:(CF2:Multi-speed
Select,Bit 1)
C005
09:(2CH:2-stage
Acceleration and
Deceleration)
09:(2CH:2-stage
Acceleration and
Deceleration)
C006
255:No function
18:(RS:Reset
Inverter)
C007
255:No function
13:(USP:Unattended
Start Protection)
17
C
Group
Data
ID
C001
INPUTS FOR 3 WIRE CONTROL REQUIRES A MOMENTARY STOP SWITCH, MOMENTARY RUN SWITCH
AND A 2 POSITION SUSTAINED DIRECTION SWITCH
Data Name
Set value
Unit
Default value
Range
Input [1] function
STA code=20; ON
momentary starts
motor
STP code=21; ON no
change, Momentary
Off stops rotation
00:(FW:FORWARD
Run/Stop)
01:(RV:Reverse
Run/Stop)
02:(CF1:Multi-speed
Select,Bit 0 (LSB))
C002
C003
F/R code=22 ; ON
selects reverse
direction
C004C007
255:No function
C011
C012
C013
C014
C015
C016
00:normally open
[NO]
00:normally open
[NO]
00:normally open
[NO]
00:normally open
[NO]
00:normally open
[NO]
00:normally open
[NO]
00:normally open
[NO]
00:normally open
[NO]
00:normally open
[NO]
00:normally open
[NO]
00:normally open
[NO]
00:normally open
[NO]
18
C017
00:normally open
[NO]
01:(FA1:Frequency
Arrival Type 1Constant Speed)
00:normally open
[NO]
01:(FA1:Frequency
Arrival Type 1Constant Speed)
C021
C022
00:(RUN:Run Signal)
00:(RUN:Run Signal)
C026
05:(AL:Alarm Signal)
05:(AL:Alarm Signal)
C027
07:(LAD frequency
(PWM))
07:(LAD frequency)
07:(LAD frequency
(PWM))
07:(LAD frequency)
C031
[EO] terminal
selection(Pulse/PWM output)
[AM] terminal selection(Analog
voltage output 0...10V)
Digital current monitor reference
value
Output [11] active state
C032
C036
C038
C028
C030
100 %
100
20.0 ...
200.0
00:normally open
[NO]
00:normally open
[NO]
01:normally closed
[NC]
01:(During constant
speed only)
00:normally open
[NO]
00:normally open
[NO]
01:normally closed
[NC]
01:(During constant
speed only)
C039
C040
100 %
01:(During constant
speed only)
100
01:(During constant
speed only)
C041
C241
115 %
115 %
115
115
0 Hz
0 Hz
C042
C043
19
0.00 ...
400.00
0.00 ...
C044
C045
C046
C047
C052
C053
C054
C055
C056
C057
C058
C059
deceleration
PID deviation level
Frequency arrival setting 2 for
acceleration
Frequency arrival setting 2 for
deceleration
Pulse train input/output scale
conversion
PID FBV output high limit
PID FBV output low limit
Over-torque/under-torque
selection
Over/under-torque level(Forward
powering mode)
Over/under-torque level(Reverse
regen. mode)
Over/under-torque level(Reverse
powering mode)
Over/under-torque level(Forward
regen. mode)
Signal output mode of
Over/under-torque
C061
C063
C064
C071
C072
C074
C075
C076
C077
C078
100
0
400.00
0.0 ... 100.0
0.00 ...
400.00
0.00 ...
400.00
0.01 ...
99.99
0.0 ... 100.0
0.0 ... 100.0
100 %
100
0 ... 200
100 %
100
0 ... 200
100 %
100
0 ... 200
100 %
100
0 ... 200
3 %
0 Hz
3
0
0 Hz
100 %
0 %
00:(Over-torque)
00:(Over-torque)
01:(During constant
speed only)
01:(During constant
speed only)
90 %
0 Hz
90
0
100
0 ... 100
0.00 ...
100.00
0 ... 110
1 ... 247
0 s
0 ms
0.00 ...
99.99
0 ... 1000
100 C
05:(9600bps)
05:(9600bps)
1
00:(No parity)
01:(1bit)
02:(Disable)
00:(No parity)
01:(1bit)
02:(Disable)
20
C081
C082
C085
C091
C096
C098
C099
C100
100 %
100 %
100 %
00:(Disable)
00:(Modbus-RTU)
100
100
100
00:(Disable)
00:(Modbus-RTU)
1
1
1
1
00:(Input
terminal(485RUN))
00:(Input
terminal(485RUN))
C101
00:(Clear last
frequency (return to
default frequency
F001))
00:(Clear last
frequency (return to
default frequency
F001))
C102
Reset selection
C103
C104
C105
C106
C109
C111
C130
C131
C132
C133
C140
C141
00:(0Hz)
00:(0Hz)
100
100
0
115
0
0
0
0
0
0
%
%
%
%
s
s
s
s
s
s
100
100
0
115
0
0
0
0
0
0
21
1 ... 8
1 ... 8
50 ... 200
50 ... 200
0 ... 100
0.0 ... 200.0
0.0 ... 100.0
0.0 ... 100.0
0.0 ... 100.0
0.0 ... 100.0
0.0 ... 100.0
0.0 ... 100.0
C142
00:(RUN:Run Signal)
00:(RUN:Run Signal)
C143
00:(RUN:Run Signal)
00:(RUN:Run Signal)
C144
00:([LOG] = A AND B)
C145
00:(RUN:Run Signal)
00:([LOG] = A AND
B)
00:(RUN:Run Signal)
C146
00:(RUN:Run Signal)
00:(RUN:Run Signal)
C147
00:([LOG] = A AND B)
C148
00:(RUN:Run Signal)
00:([LOG] = A AND
B)
00:(RUN:Run Signal)
C149
00:(RUN:Run Signal)
00:(RUN:Run Signal)
C150
00:([LOG] = A AND B)
00:([LOG] = A AND
B)
C160
C161
C162
C163
C164
C165
C166
C169
H
Group
Data
ID
H001
1
1
1
1
1
1
1
0
Data Name
Set value
Auto-tuning selection
00:(Disabled)
1
1
1
1
1
1
1
0
Unit
Default value
00:(Disabled)
22
0 ... 200
0 ... 200
0 ... 200
0 ... 200
0 ... 200
0 ... 200
0 ... 200
0 ... 200
Range
Use the autotune feature to determine
H002
H202
kW
06:(1.5)
01:(4P)
01:(4P)
kW
H003
H203
H004
H204
H005
H205
H006
H206
H020
H220
H021
H221
H022
H222
H023
H223
H024
H224
00:(Hitachi standard
motor )
00:(Hitachi standard
motor )
06:(1.5)
ASSUMES
1.5 HP
06:(1.5)
01:(4P)
01:(4P)
100 %
100 %
100
1 ... 1000
100 1 ... 1000
100
100
100
0 ... 255
100 0 ... 255
1.477 Ohm
1.477
1.477 Ohm
1.477
0.801 Ohm
0.801
0.801 Ohm
0.801
12.8 mH
12.8
12.8 mH
12.8
4.16 A
4.16
4.16 A
4.16
0.017 kgm2
0.017
0.017 kgm2
0.017
23
0.001 ...
65.535
0.001 ...
65.535
0.001 ...
65.535
0.001 ...
65.535
0.01 ...
655.35
0.01 ...
655.35
0.01 ...
655.35
0.01 ...
655.35
0.001 ...
9999.000
0.001 ...
9999.000
H030
H230
H031
H231
H032
H232
H033
H233
H034
H234
H050
H051
1.477 Ohm
1.477
1.477 Ohm
1.477
0.801 Ohm
0.801
0.801 Ohm
0.801
12.8 mH
12.8
12.8 mH
12.8
4.16 A
4.16
4.16 A
4.16
0.017 kgm2
0.017
0.017 kgm2
0.017
0.2 times
0.2
2 s
24
0.001 ...
65.535
0.001 ...
65.535
0.001 ...
65.535
0.001 ...
65.535
0.01 ...
655.35
0.01 ...
655.35
0.01 ...
655.35
0.01 ...
655.35
0.001 ...
9999.000
0.001 ...
9999.000
0.00 ...
10.00
0 ... 1000
Programming the WJ200 via the computer. Load Hitachi VFD Software AND USB Driver first before connecting the VFD. Turn on
VFD and connect to PC, verify USB Driver is working as shown.
Run Hitachi VFD Software program, click on File and choose new project. Click to download Parameter and Program data and then
click on Online&Read.
Verifies that it is connected to the WJ200 VFD, click n OK to continue and upload parameters to your PC.
25
Click on Parmater as shown to pull up Parameter setting WJ200 window. Click on Group tab you want to edit.
26
You make changes in the 'Set value" Column, the line(s) will be highlighted to indicate a change(s). The change(s) must then be sent
to the VFD.
Program variable changes must be sent from the PC to the VFD, either Left click on the "Program" pull down menu tab, or Right click
on the highlighted parameter to pull up the menu.
27
C Group Tab pulls up the program variables for the Input functions
Motor Auto-tune determines your motors actual operating parameters, which can be enetered in the VFD program variables
28