Vol-II (B) Edited
Vol-II (B) Edited
TRANSMISSION DIRECTORATE
.
ICB-TD-TKTLP073/74 - 01
ICB-TD-TKTLP073/74 - 01
Nepal Electricity Authority
Nepal
VOLUME II(B) OF III
August 2016
Tamakoshi-Kathmandu 220/400 kV Transmission Line Project
Transmission Directorate, NEA Training Center Complex
Kharipati, Bhaktapur, Nepal
Telephone: +977-1-6620016
Fax: +977-1-6620016
Section 9 - OPGW
Contents
Chapter 01 : Specification for OPGW cabling & associated hardware & fittings
Chapter 02 : Inspection & Testing Requirement
Chapter 03 : Installation for OPGW Cabling
Appendix :
Appendix A :
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-1
Chapter-01
Specification for OPGW cabling & associated hardware & fittings
Table of Content
1.0
1.1
1.1.1
1.1.2 ATTENUATION........................................................................................................................... 3
1.2
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-2
1.4
1.5
1.9
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-3
Section-01
Specification for OPGW cabling and associated hardware & fittings
The broad scope of this specification include the survey, planning, design, engineering, manufacturing,
supply, transportation, insurance, delivery at site, unloading, handling, storage, , installation, splicing,
termination, testing, demonstration for acceptance and commissioning and documentation for:
a)
b)
c)
d)
e)
f)
OPGW fibre optic cable including all associated hardware, accessories & fittings
Fibre Optic approach cable including installation material
Fibre Optic Distribution Panels (FODP) & Joint Box
Supply of spares
Supply of test equipments
All other associated work/items described in the technical specifications.
This section of the technical specification describes the functional and technical specifications of
OPGW cabling and associated hardware and fittings.
1.0 Fibre Optic Cabling
In this section of the technical specification, the functional & technical specifications of OPGW cable,
associated hardware & fittings for the requirements for G.652D Dual-window Single mode (DWSM)
telecommunications grade fibre optic cable is mentioned. Bidders shall furnish with their bids, detailed
descriptions of the fibres & cable(s) proposed.
All optical fibre cabling including fibre itself and all associated installation hardware shall have a
minimum guaranteed design life span of 25 years. Documentary evidence in support of guaranteed life
span of cable & fibre shall be submitted by the Contractor during detailed engineering.
1.1 Required Optical Fibre Characteristics
The optical fibre to be provided should have following characteristics :
1.1.1 Physical Characteristic
Dual-Window Single mode (DWSM), G.652D optical fibres shall be provided in the fibre optic cables.
DWSM optical fibres shall meet the requirements defined in Table 1-1(a).
1.1.2 Attenuation
The attenuation coefficient for wavelengths between 1525 nm and 1575 nm shall not exceed the
attenuation coefficient at 1550 nm by more than 0.05 dB/km. The attenuation coefficient between 1285
nm and 1330 nm shall not exceed the attenuation coefficient at 1310 nm by more than 0.05 dB/km.
The attenuation of the fibre shall be distributed uniformly throughout its length such that there are no
point discontinuities in excess of 0.10 dB. The fibre attenuation characteristics specified in table 1-1
(a) shall be guaranteed fibre attenuation of any & every fibre reel.
The overall optical fibre path attenuation shall not be more than calculated below :
Bidding Document for ICB-TD-TKTLP 073/74-01
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-4
Maximum attenuation @ 1550 nm : 0.21 dB/km x total km + 0.05 dB/splice x no. of splices + 0.5
dB/connector x no. of connectors.
Maximum attenuation @ 1310 nm : 0.35 dB/km x total km + 0.05 dB/splice x no. of splices + 0.5
dB/connector x no. of connectors.
Table 2-1(a)
DWSM Optical Fibre Characteristics
Fibre Description:
Dual-Window Single-Mode
Cladding Diameter:
125.0 m 1 m
0.6m
Cladding non-circularity
1260
As per G.652 D
0.69 Gpa
Attenuation Coefficient:
@ 1310 nm
@ 1550 nm
Chromatic Dispersion;
Maximum:
nm
0.35 dB/km
0.21 dB/km
1300 to 1324 nm
0.092 ps/(nm2xkm) maximum
Temperature Dependence :
Bend Performance :
0.2 ps/km^
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-5
Tower span details shall be collected by the contractor during survey. To meet the overall
requirement of the transmission line(s), the contractor may offer more than one design without
any additional cost to Employer, in case single design is not meeting the requirement. OPGW cable
to be designed to meet transmission line sag-tension parameters and other details to be provided by
Transmission Line contractor. Any other details, as required for cable design etc. shall be collected
by the Contractor during survey.
1.2.1 Optical Fibre Cable Link Lengths
The estimated optical fibre link lengths are provided in Appendices as transmission line route length.
However, the Contractor shall supply the OPGW cable as required based on the tower schedule. The
Contractor shall verify the transmission line route length during the survey and the Contract price
shall be adjusted accordingly.
For the purpose of payment, the optical fibre link lengths are defined as transmission line route
lengths from Gantry at one terminating station to the Gantry in the other terminating station. The
actual cable lengths to be delivered shall take into account various factors such as sag, service loops,
splicing, working lengths & wastage etc. and no additional payment shall be payable in this regard.
The unit rate for FO cable quoted in the Bid price Schedules shall take into account all such factors.
1.2.2
All optical fibres shall be individually coated. Individual optical fibres within a fibre unit and fibre
units shall be identifiable in accordance with EIA/TIA 598 or IEC 60304 or Bellcore GR-20 colourcoding scheme.
Colouring utilized for colour coding optical fibres shall be integrated into the fibre coating and shall
be homogenous. The colour shall not bleed from one fibre to another and shall not fade during fibre
preparation for termination or splicing.
Each cable shall have traceability of each fibre back to the original fibre manufacturer's fibre number
and parameters of the fibre. If more than the specified number of fibres is included in any cable, the
spare fibres shall be tested by the cable manufacturer and any defective fibres shall be suitably
bundled, tagged and identified at the factory by the vendor.
1.2.3
Buffer Tube
Loose tube construction shall be implemented. The individually coated optical fibre(s) shall be
surrounded by a buffer for protection from physical damage during fabrication, installation and
operation of the cable. The fibre coating and buffer shall be strippable for splicing and
termination. Each fibre unit shall be individually identifiable utilizing colour coding. Buffer tubes
shall be filled with a water-blocking gel.
1.2.4
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-6
The OPGW cable shall be designed and installed such that the optical fibres experience no strain
under all loading conditions of transmission lines. Zero fibre strain condition shall apply even after a
25 year cable creep.
For the purpose of this specification, the following definitions shall apply:
Maximum Working Tension (MWT) is defined as the maximum cable tension at which there is
no fibre strain.
The no fibre strain condition is defined as fibre strain of less than or equal to 0.05%, as
determined by direct measurements through IEC/ ETSI (FOTP) specified optical reflectometry
The Cable strain margin is defined as the maximum cable strain at which there is no fibre
strain.
The cable Maximum Allowable Tension (MAT) is defined as the maximum tension
experienced by the Cable under the worst case loading condition.
The cable max strain is defined as the maximum strain experienced by the Cable under the
worst case loading condition.
The cable Every Day Tension (EDT) is defined as the maximum cable tension on any span
under normal conditions.
The Ultimate /Rated Tensile Strength (UTS/ RTS/ breaking strength) is defined as the
maximum tensile load applied and held constant for one minute at which the specimen shall
not break.
While preparing the Sag-tension charts for the OPGW cable the following conditions shall be met:
The Max Allowable Tension (MAT) / max strain shall be less than or equal to the MWT/
Strain margin of the cable.
The sag shall not exceed the earth wire sag in all conditions.
The Max Allowable Tension shall also be less than or equal to 0.4 times the UTS.
The 25 year creep at 25% of UTS (creep test as per IEEE 1138) shall be such that the 25 year
creep plus the cable strain at Max Allowable Tension (MAT) is less than or equal to the
cable strain margin.
The everyday tension (EDT) shall not exceed 20% of the UTS for the OPGW cable.
The Sag-tension chart of OPGW cable indicating the maximum tension, cable strain and sag shall
be calculated and submitted along with the bid under various conditions as per tower design of the
transmission line.
The size of OPGW shall be selected such that max. tension and sag at specified temperature and
wind condition remains within the limits of transmission line tower design.
1.2.5 Cable Materials
The materials used for optical fibre cable construction, shall meet the following requirements:
1.2.5.1 Filling Materials
The interstices of the fibre optic unit and cable shall be filled with a suitable compound to prohibit
any moisture ingress or any water longitudinal migration within the fibre optic unit or along the fibre
Bidding Document for ICB-TD-TKTLP 073/74-01
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-7
optic cable. The water tightness of the cable shall meet or exceed the test performance criteria as per
IEC 60794-1-F-5.
The filling compound used shall be a non-toxic homogenous waterproofing compound that is free of
dirt and foreign matter, non-hygroscopic, electrically nonconductive and non-nutritive to fungus. The
compound shall also be fully compatible with all cable components it may come in contact with and
shall inhibit the generation of hydrogen within the cable.
The waterproofing filling materials shall not affect fibre coating, colour coding, or encapsulant
commonly used in splice enclosures, shall be dermatologically safe, non-staining and easily
removable with a non-toxic cleaning solvent.
1.2.5.2 Metallic Members
When the fibre optic cable design incorporates metallic elements in its construction, all metallic
elements shall be electrically continuous.
1.2.6
This section describes the requirements for marking, packaging and shipping the overhead fibre optic
cable.
(a) Drum Markings: Each side of every reel of cable shall be permanently marked in white lettering
with the vendors' address, the Purchasers destination address, cable part number and
specification as to the type of cable, length, number of fibres, a unique drum number including
the name of the transmission line & segment no., factory inspection stamp and date.
(b) Cable Drums: All optical fibre cabling shall be supplied on strong drums provided with lagging
of adequate strength, constructed to protect the cabling against all damage and displacement
during transit, storage and subsequent handling during installation. Both ends of the cable shall
be sealed as to prevent the escape of filling compounds and dust & moisture ingress during
shipment and handling. Spare cable caps shall be provided with each drum as required.
The spare cable shall be supplied on sturdy, corrosion resistant, steel drums suitable for long
periods of storage and re-transport & handling.
There shall be no factory splices allowed within a continuous length of cable. Only one continuous
cable length shall be provided on each drum. The lengths of cable to be supplied on each drum shall
be determined by a "schedule" prepared by the Contractor and approved by the owner.
1.3. Optical Ground Wire (OPGW)
OPGW cable construction shall comply with IEEE-1138, 2009. The cable provided shall meet both
the construction and performance requirements such that the ground wire function, the optical fibre
integrity and optical transmission characteristics are suitable for the intended purpose. The cable
shall consist of optical fibre units as defined in this specification. There shall be no factory splices
within the cable structure of a continuous cable length.
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-8
The composite fibre optic overhead ground wire shall be made up of multiple buffer tubes embedded
in a water tight aluminium/aluminium alloy protective central fibre optic unit surrounded by
concentric-lay stranded metallic wires in single or multiple layers. Each buffer tube shall have
maximum 12 no. of fibres. All fibres in single buffer tube or directly in central fibre optic unit is not
acceptable. The dual purpose of the composite cable is to provide the electrical and physical
characteristics of conventional overhead ground wire while providing the optical transmission
properties of optical fibre.
1.3.1
The central fibre optic unit shall be designed to house and protect multiple buffered optical fibre
units from damage due to forces such as crushing, bending, twisting, tensile stress and moisture. The
central fibre optic unit and the outer stranded metallic conductors shall serve together as an integral
unit to protect the optical fibres from degradation due to vibration and galloping, wind and ice
loadings, wide temperature variations, lightning and fault current, as well as environmental effects
which may produce hydrogen.
The OPGW design of dissimilar materials for stranded wires and tubes are not allowed. Central fibre
optic unit may be of aluminium / aluminium alloy tube. There shall be no exposed areas of tubing
that can make electrical contact either directly or indirectly through moisture, contamination,
protrusions, etc with the surrounding stranded wires. The tube may be fabricated as a seamless tube,
seam welded, or a tube without a welded seam.
1.3.2
Basic Construction
The OPGW cable construction shall conform to the applicable requirements of this specification,
applicable clauses of IEC 61089 related to stranded conductors and Table 1.2(a) OPGW Mechanical
and Electrical Characteristics. In addition, the basic construction shall include bare concentric-laystranded metallic wires with the outer layer having left hand lay. The wires may be of multiple layers
with a combination of various metallic wires within each layer. The direction of lay for each
successive layer shall be reversed. The finished wires shall contain no joints or splices unless
otherwise agreed to by the Employer and shall conform to all applicable clauses of IEC 61089 as
they pertain to stranded conductors.
The wires shall be so stranded that when the complete OPGW is cut, the individual wires can be
readily regrouped and then held in place by one hand.
1.3.3
Breaking Strength
The rated breaking strength of the completed OPGW shall be taken as no more than 90 percent of the
sum of the rated breaking strengths of the individual wires, calculated from their nominal diameter
and the specified minimum tensile strength.
The rated breaking strength shall not include the strength of the optical unit. The fibre optic unit shall
not be considered a load bearing tension member when determining the total rated breaking strength
of the composite conductor.
1.3.4
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-9
Table 1-2(a) provides OPGW Electrical and Mechanical Requirements for the minimum
performance characteristics. Additionally, the OPGW mechanical & electrical characteristics shall be
similar to that of the earthwire being replaced such that there is no or minimal consequential increase
in stresses on towers. OPGW installation sag & tension charts shall be as per transmission line
requirement. For the OPGW cable design selection and preparation of sag tension charts, the limits
specified in this section shall also be satisfied. The Bidder shall submit sag-tension charts for the
above cases with their bids.
Table 1.2(a)
OPGW Electrical and Mechanical Requirements
(1)
Everyday Tension
(2)
(3)
Bidder may offer separate design for each short circuit rating however OPGW design with higher
short circuit level shall be acceptable.
1.3.5 Operating conditions
Since OPGW shall be located at the top of the transmission line support structure, it will be
subjected to Aeolian vibration, Galloping and Lightning strikes. It will also carry ground fault
currents. Therefore, its electrical and mechanical properties shall be same or similar as those required
of conventional ground conductors.
1.4 Installation Hardware
The scope of supply includes all required fittings and hardware such as Tension assembly,
Suspension assembly, Vibration dampers, Reinforcing rods, Earthing clamps, Downlead clamps,
splice enclosure etc. The Bidder shall provide documentation justifying the adequacy and suitability
of the hardware supplied. The quantity of hardware & fittings to meet any eventuality during site
installation minimum@ 1% shall also be provided as part of set/km for each transmission line
without any additional cost to Employer.
The OPGW hardware fittings and accessories shall follow the general requirements regarding design,
materials, dimensions & tolerances, protection against corrosion and markings as specified in clause
4.0 of EN 61284: 1997 (IEC 61284). The shear strength of all bolts shall be at least 1.5 times the
maximum installation torque. The OPGW hardware & accessories drawing & Data Requirement
Sheets (DRS) document shall consist of three parts: (1) A technical particulars sheet (2) An assembly
drawing i.e. level 1 drawing and (3) Component level drawings i.e. level 2 & lower drawings. All
component reference numbers, dimensions and tolerances, bolt tightening torques & shear strength
and ratings such as UTS, slip strength etc shall be marked on the drawings.
The fittings and accessories described herein are indicative of installation hardware typically used for
OPGW installations and shall not necessarily be limited to the following:
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-10
(a) Suspension Assemblies: Preformed armour grip suspension clamps and aluminium alloy
armour rods/ reinforcing rods shall be used. The suspension clamps shall be designed to carry
a vertical load of not less than 25 KN. The suspension clamps slippage shall occur between
12kN and 17 kN as measured.
The Contractor shall supply all the components of the suspension assembly including
shackles, bolts, nuts, washers, split pins, etc. The total drop of the suspension assembly shall
not exceed 150 mm (measured from the centre point of attachment to the centre point of the
OPGW). The design of the assembly shall be such that the direction of run of the OPGW
shall be the same as that of the conductor.
(b) Dead End Clamp Assemblies: All dead end clamp assemblies shall preferably be of
performed armoured grip type and shall include all necessary hardware for attaching the
assembly to the tower strain plates. Dead end clamps shall allow the OPGW to pass through
continuously without cable cutting. The slip strength shall be rated not less than 95% of the
rated tensile strength of the OPGW.
(c) Clamp Assembly Earthing Wire: Earthing wire consisting of a 1500 mm length of
aluminium or aluminium alloy conductor equivalent in size to the OPGW shall be used to
earth suspension and dead end clamp assemblies to the tower structure. The earthing wire
shall be permanently fitted with lugs at each end. The lugs shall be attached to the clamp
assembly at one end and the tower structure at the other.
(d) Structure Attachment Clamp Assemblies: Clamp assemblies used to attach the OPGW to the
structures, shall have two parallel grooves for the OPGW, one on either side of the
connecting bolt. The clamps shall be such that clamping characteristics do not alter adversely
when only one OPGW is installed. The tower attachment plates shall locate the OPGW on
the inside of the tower and shall be attached directly to the tower legs/cross-members without
drilling or any other structural modifications.
(e)
Vibration Dampers: Vibration dampers type 4R Stockbridge or equivalent, having four (4)
different frequencies spread within the Aeolian frequency bandwidth corresponding to wind
speed of 1m/s to 7 m/s, shall be used for suspension and tension points in each span. The
Contractor shall determine the exact numbers and placement(s) of vibration dampers
through a detailed vibration analysis as specified in technical specifications.
One damper minimum on each side per OPGW cable for suspension points and two
dampers minimum on each side per OPGW cable for tension points shall be used for
nominal design span of 400 meters. For all other ruling spans, the number of vibration
damper shall be based on vibration analysis.
The clamp of the vibration damper shall be made of high strength aluminum alloy of type
LM-6. It shall be capable of supporting the damper and prevent damage or chaffing of the
conductor during erection or continued operation. The clamp shall have smooth and
permanent grip to keep the damper in position on the OPGW cable without damaging the
strands or causing premature fatigue failure of the OPGW cable under the clamp. The clamp
groove shall be in uniform contact with the OPGW cable over the entire clamping surface
except for the rounded edges. The groove of the clamp body and clamp cap shall be smooth,
free from projections, grit or other materials which could cause damage to the OPGW cable
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-11
when the clamp is installed. Clamping bolts shall be provided with self locking nuts and
designed to prevent corrosion of threads or loosening in service.
The messenger cable shall be made of high strength galvanised steel/stain less steel. It shall
be of preformed and post formed quality in order to prevent subsequent droop of weight and
to maintain consistent flexural stiffness of the cable in service. The messenger cable other
than stainless steel shall be hot dip galvanised in accordance with the recommendations of
IS: 4826 for heavily coated wires.
The damper mass shall be made of hot dip galvanised mild steel/cast iron or a permanent
mould cast zinc alloy. All castings shall be free from defects such as cracks, shrinkage,
inclusions and blow holes etc. The surface of the damper masses shall be smooth.
The damper clamp shall be casted over the messenger cable and offer sufficient and
permanent grip on it. The messenger cable shall not slip out of the grip at a load less than
the mass pull-off value of the damper. The damper masses made of material other-than zinc
alloy shall be fixed to the messenger cable in a suitable manner in order to avoid excessive
stress concentration on the messenger cables which shall cause premature fatigue failure of
the same. The messenger cable ends shall be suitably and effectively sealed to prevent
corrosion. The damper mass made of zinc alloy shall be casted over the messenger cable and
have sufficient and permanent grip on the messenger cable under all service conditions.
The contractor must indicate the clamp bolt tightening torque to ensure that the slip strength
of the clamp is maintained between 2.5 kN and 5 kN. The clamp when installed on the
OPGW cable shall not cause excessive stress concentration on the OPGW cable leading to
permanent deformation of the OPGW strands and premature fatigue failure in operation.
The vibration analysis of the system, with and without damper and dynamic characteristics
of the damper as detailed in Technical Specification, shall have to be submitted. The
technical particulars for vibration analysis and damping design of the system are as follows:
Sl. No.
1
Description
Technical Particulars
400 meters
1100 meters
100 meters
Configuration:
As per Specifications
Standard preformed
rods/AGS
Procurement of Plant
armour
Single-Stage: Two-Envelope
Section 9 - OPGW
9-12
The damper placement chart for spans ranging from 100m to 1100m shall be submitted by
the Contractor. Placement charts should be duly supported with relevant technical
documents and sample calculations.
The damper placement charts shall include the following
(1) Location of the dampers for various combinations of spans and line tensions clearly
indicating the number of dampers to be installed per OPGW cable per span.
(2) Placement distances clearly identifying the extremities between which the distances are
to be measured.
(3) Placement recommendation depending upon type of suspension clamps (viz Free center
type/Armour grip type etc.)
(4) The influence of mid span compression joints, repair sleeves and armour rods (standard
and AGS) in the placement of dampers
1.5 Fibre Optic Splice Enclosures (Joint Box)
All splices shall be encased in Fibre Optic Splice Enclosures. Suitable splice enclosures shall be
provided to encase the optical cable splices in protective, moisture and dust free environment. Splice
enclosures shall comply with ingress protection class IP 66 or better. The splice enclosures shall be
designed for the storage and protection of required number of optical fibre splices and equipped with
sufficient number of splice trays for splicing all fibres in the cable. No more than 12 fibres shall be
terminated in a single splice tray. They shall be filled with suitable encapsulate that is easily
removable should re-entry be required into the enclosures.
Splice enclosures shall be suitable for outdoor use with each of the cable types provided under this
contract. Splice enclosures shall be appropriate for mounting on transmission line towers above anticlimb guard levels at about 10 metres from top of the tower and shall accommodate pass-through
splicing. The actual mounting height and location shall be finalised after Survey. Contractor shall be
responsible for splicing of fibres and installation of splice enclosures.
1.5.1
Splicing of the optical fibre cabling shall be minimized through careful Contractor planning. There
shall be no mid-span splices allowed. All required splices shall be planned to occur on tower
structures. All optical fibre splicing shall comply with the following:
(a) All fibre splices shall be accomplished through fusion splicing.
(b) Each fibre splice shall be fitted with a splice protection sheath fitted over the final splice.
(c) All splices and bare fibre shall be neatly installed in covered splice trays.
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-13
(d) For each link, bi-directional attenuation of single mode fusion splices, shall not average more
than 0.05 dB and no single splice loss shall exceed 0.1 dB when measured at 1550 nm.
(e) For splicing, fibre optic cable service loops of adequate length shall be provided so that all
splices occurring at tower structures can be performed at ground level.
1.6 Fibre Optic Approach Cables
For purposes of this specification, a fibre optic approach cable is defined as the Armoured
underground fibre optic cable required to connect Overhead Fibre Optic Cable (OPGW) between the
final in line splice enclosure on the gantry / tower forming the termination of the fibre cable on the
power line and the Fibre Optic Distribution Panel (FODP) installed within the building. The
estimated fibre optic approach cabling length requirements are indicated in the appendices. However,
the Contractor shall supply & install the optical fibre approach cable as required based on detailed
site survey to be carried out by the Contractor during the project execution and the Contract price
shall be adjusted accordingly.
1.6.1
Basic Construction
The cable shall be suitable for direct burial, laying in trenches & PVC/Hume ducts, laying under
false flooring and on indoor or outdoor cable raceways.
1.6.2
The Approach Cable shall be a UV resistant, rodent proof, armoured cable with metallic type of
armouring. The outer cable jacket for approach cable shall consist of carbon black polyethylene resin
to prevent damage from exposure to ultra-violet light, weathering and high levels of pollution. The
jacket shall conform to ASTM D1248 for density.
1.6.3
Approach cable shall contain fibres with identical optical/ physical characteristics as those in the
OPGW cables. The cable core shall comprise of tensile strength member(s), fibre support/bedding
structure, core wrap/bedding, and an overall impervious jacket.
1.7 Fibre Optic Distribution Panel
Fibre Optic Distribution Panels is required for each location for termination of fibres in a manner
consistent with the following:
(a) FODPs shall be suitable for use with each of the cable types provided as part of this contract.
FODPs shall accommodate pass-through splicing and fibre terminations.
(b) FODPs for indoor use shall be supplied in suitable cabinets/racks with locking arrangement
(c) All FODPs shall be of corrosion resistant, robust construction and shall allow both top or bottom
entry for access to the splice trays. Ground lugs shall be provided on all FODPs and the
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-14
Contractor shall ensure that all FODPs are properly grounded. The FODP shall meet or exceed
ingress protection class IP55 specifications.
1.7.1 Optical Fibre Connectors
Optical fibres shall be connectorised with FC-PC type connectors preferably. Alternatively connector
with matching patch cord shall also be acceptable. Fibre optic couplings supplied with FODPs shall
be appropriate for the fibre connectors to be supported. There shall be no adapters.
1.8 Service Loops
For purposes of this specification, cable and fibre service loops are defined as slack (extra) cable and
fibre provided for facilitating the installation, maintenance and repair of the optical fibre cable plant.
(a) Outdoor Cable Service Loops: In-line splice enclosures installed outdoors and mounted on the
utility towers shall be installed with sufficient fibre optic cable service loops such that the
recommended minimum bend radius is maintained while allowing for installation or
maintenance of the cable to be performed in a controlled environment at ground level.
(b) Indoor Cable Service Loops: FODPs shall provide at least three (3) metres of cable service
loop. Service loops shall be neatly secured and stored, coiled such that the minimum
recommended bend radius' are maintained.
(c) Fibre Units Service Loops: For all fibre optic cable splicing, the cable shall be stripped back a
sufficient length such that the fan-out of fibre units shall provide for at least one (1) metre of
fibre unit service loop between the stripped cable and the bare fibre fan-out.
(d) Pigtail Service Loops : Connectorised pigtails spliced to bare fibres shall provide at least 1
metre of service loop installed in the FODP fibre organizer and at least one (1) metre of service
loop to the couplings neatly stored behind the FODP coupling panels.
(e) Fibre Service Loops : At least 0.5 metre of bare fibre service loop shall be provided on each
side of all fibre splices. The bare fibre service loops shall be neatly and safely installed inside
covered splice trays.
1.9 Test Equipment
The table 1.3 below provides mandatory test equipment requirements, to be provided as applicable as
per BoQ. The parameters / features of the mandatory equipments are enumerated as follows :
Table 1.3
S. No.
A.
1
2
Test equipment
Parameter
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-15
1310/1550nm).
3
4
5
6
7
8
9
In case the offered make/model of test equipment has multiple options for the parameters, the option of
higher range shall be acceptable. The supplied test equipment shall be suitable for use in the high
EMI/EMC environment. The Contractor shall submit performance certificate for offered test
equipment from at least one customer. The Contractor shall offer only reputed make test equipment
such as Acterna (JDSU)/Anritsu/Sumitomo/Agilent/EXFO etc.
Definitions and test methods for the relevant parameters of singlemode fibres
Characteristics of a single-mode optical fibre cable
(4) IEEE
IEEE-1138
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-16
EIA/TIA-455-169
EIA/TIA-455-170
EIA/TIA-455-174
EIA/TIA-455-175
EIA/TIA-455-176
EIA/TIA-598
(6)
IEC-60793-1 series
IEC-60794-1-1
IEC-60794-1-2
IEC-60794-3
IEC-60794-4
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-17
IEC-61089
IEC-61232
IEC-61284
IEC-61395
Specifications and codes shall be the latest version, inclusive of revisions, which are in force at the
date of the contract award. Where new specifications, codes, and revisions are issued during the period
of the contract, the Contractor shall attempt to comply with such, provided that no additional expenses
are charged to the Employer without Employers written consent.
In the event the Contractor offers to supply material and/or equipment in compliance to any standard
other than Standards listed herein, the Contractor shall include with their proposal, full salient
characteristics of the new standard for comparison.
In case values indicated for certain parameters in the specifications are more stringent than those
specified by the standards, the specification shall override the standards.
I.10 References
(1)
(2)
(3)
(4)
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-18
Chapter - 02
Inspection & Testing Requirement
Table of Content
2.1
2.2.1
2.2.2
2.2.3
2.2.4
2.2.5
2.2.6
2.2.7
2.2.8
2.3
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-19
Section - 02
Inspection & Testing Requirement
All materials furnished and all work performed under this Contract shall be inspected and
tested. Deliverables shall not be shipped until all required inspections and tests have been
completed, and all deficiencies have been corrected to comply with this Specification and
approved for shipment by the Employer.
Except where otherwise specified, the Contractor shall provide all manpower and materials
for tests, including testing facilities, logistics, power and instrumentation, and replacement of
damaged parts. The costs shall be borne by the Contractor and shall be deemed to be included
in the contract price.
The entire cost of testing for factory, production tests and other test during manufacture
specified herein shall be treated as included in the quoted unit price of materials, except for
the expenses of Inspector/Employers representative.
Acceptance or waiver of tests shall not relieve the Contractor from the responsibility to
furnish material in accordance with the specifications.
All tests shall be witnessed by the Employer and/or its authorized representative (hereinafter
referred to as the Employer) unless the Employer authorizes testing to proceed without
witness. The Employer representative shall sign the test form indicating approval of
successful tests.
Should any inspections or tests indicate that specific item does not meet Specification
requirements, the appropriate items shall be replaced, upgraded, or added by the Contractor
as necessary to correct the noted deficiencies at no cost to the Employer. After correction of a
deficiency, all necessary retests shall be performed to verify the effectiveness of the
corrective action.
The Employer reserves the right to require the Contractor to perform, at the Employer's
expense, any other reasonable test(s) at the Contractor's premises, on site, or elsewhere in
addition to the specified Type, Acceptance, Routine, or Manufacturing tests to assure the
Employer of specification compliance.
2.1 Testing Requirements
Following are the requirements of testing :
1. Type Testing
2. Factory Acceptance Testing
3. Site Acceptance Testing
2.3.1 Type Testing
Bidding Document for ICB-TD-TKTLP 073/74-01
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-20
"Type Tests" shall be defined as those tests which are to be carried out to prove the design,
process of manufacture and general conformity of the materials to this Specification. Type
Testing shall comply with the following:
(a)
All cable & equipment being supplied shall conform to type tests as per
technical specification.
(b)
The test reports submitted shall be of the tests conducted within last seven (7)
years for OPGW cable prior to the date of proposal/offer submitted. In case the
test reports are older than seven (7) years for OPGW cable on the date of
proposal/offer, the Contractor shall repeat these tests at no extra cost to the
Employer.
(c)
The Contractor shall submit, within 30 days of Contract Award, copies of test
reports for all of the Type Tests that are specified in the specifications and that
have previously ( before Contract award) been performed. These reports may be
accepted by the Employer only if they apply to materials and equipment that are
essentially identical to those due to be delivered under the Contract and only if
test procedures and parameter values are identical to those specified in this
specifications carried out at accredited labs and witnessed by third party /
customers representatives.
In the event of any discrepancy in the test reports or any type tests not carried
out, same shall be carried out by Contractor without any additional cost
implication to the Employer.
In case the Type Test is required to be carried out, then following shall be
applicable:-
(d)
(e)
The Contractor shall provide a detailed schedule for performing all specified
type tests. These tests shall be performed in the presence of a representative of
the Employer.
(f)
The Contractor shall ensure that all type tests can be completed within the time
schedule offered in his Technical Proposal.
(g)
In case of failure during any type test, the Supplier is either required to
manufacture a fresh sample lot and repeat all type tests successfully or repeat
that particular type test(s) at least three times successfully on the samples
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-21
selected from the already manufactured lot at his own expenses. In case a fresh
lot is manufactured for testing then the lot already manufactured shall be
rejected.
2.1.1 Type Test Samples
The Contractor shall supply equipment/material for sample selection only after the Quality
Assurance Plan has been approved by the Employer. The sample material shall be
manufactured strictly in accordance with the approved Quality Assurance Plan. The
Contractor shall submit for Employer approval, the type test sample selection procedure. The
selection process for conducting the type tests shall ensure that samples are selected at
random. For optical fibres/ Fibre Optic cables, at least three reels/ drums of each type of
fibre/cable proposed shall be offered for selection. For FO cable installation hardware &
fittings at least ten (10) samples shall be offered for selection. For Splice enclosures at least
three samples shall be offered for selection.
2.1.2 List of Type Tests
The type testing shall be conducted on the following items
(a) Optical fibres
(b) OPGW Cable
(c) OPGW Cable fittings
(d) Vibration Damper
(e) Splice Enclosure (Joint Box)
(f) Approach Cable
2.1.2.1 Type Tests for Optical Fibres
The type tests listed below in table 2-1 shall be conducted on DWSM fibres to be supplied as
part of overhead cables. The tests specific to the cable type are listed in subsequent sections.
Table 2-1
Type Tests For Optical Fibres
S. No.
Test Name
Acceptance Criteria
Test procedure
Attenuation
As per Section-01 of TS
IEC 60793-1-40
Or EIA/TIA 455-78A
As per Section-01 of TS
IEC 60793-1-40
Or EIA/TIA 455-78A
IEC 60793-1-40
Or EIA/TIA 455-78A
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-22
Table 2-1
Type Tests For Optical Fibres
S. No.
Test Name
Acceptance Criteria
Test procedure
Temp. Cycling
(Temp dependence of
Attenuation)
As per Section-01 of TS
IEC 60793-1-52
Or EIA/TIA 455-3A, 2
cycles
As per Section-01 of TS
IEC 60793-1-47
Or EIA/TIA 455-62A
IEC 60793-1-45 Or
EIA/TIA 455164A/167A/174
As per Section-01 of TS
IEC 60793-1-42 Or
EIA/TIA 455168A/169A/175A
Chromatic Dispersion
Cladding Diameter
As per Section-01 of TS
IEC 60793-1-20 Or
EIA/TIA 455-176
Point Discontinuities of
attenuation
As per Section-01 of TS
IEC 60793-1-40 Or
EIA/TIA 455-59
10
As per Section-01 of TS
IEC 60793-1-20 Or
EIA/TIA 455-176
11
As per Section-01 of TS
IEC 60793-1-30
Or EIA/TIA 455-31B
-End Of table-
Test Name
Water Ingress
Test
Test
Description
IEEE 11382009
Test Procedure
IEEE 1138-2009
(IEC 60794-1-2 Method F5 or EIA/TIA 455-82B)
: Test duration : 24 hours
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-23
Table 2-2
Type tests for OPGW Cable
S. No.
Test Name
Test
Description
Test Procedure
Seepage of
filling
compound
IEEE 11382009
IEEE 1138-2009
(EIA/TIA 45581B)
Preconditioning period:72
hours.
Test duration: 24 hours.
Short Circuit
Test
IEEE 11382009
IEEE 1138-2009
IEEE 1138-2009
Or
IEC60794-410 /
IEC 60794-1-2
(2003)
Method H1
4
Aeolian
Vibration
Test
IEEE 11382009
Or
IEC60794-410 /
IEC 60794-12, Method E19
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-24
Table 2-2
Type tests for OPGW Cable
S. No.
Test Name
Test
Description
Test Procedure
clamps shall be visually
inspected for mechanical
damage and photographed
after the test.
Galloping test
IEEE 11382009
IEEE 1138-2009
Cable Bend
Test
Sheave Test
IEEE 11382009
IEEE 1138-2009
IEEE 1138-2009
OR
IEC 60794-1-2
(2003)
Method E1B
Crush Test
IEEE 11382009
(IEC 60794-1-2,
Method E3/
EIA/TIA 455-41B)
Bidding Document for ICB-TD-TKTLP 073/74-01
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-25
Table 2-2
Type tests for OPGW Cable
S. No.
Test Name
Test
Description
Test Procedure
400-metre length of fibre
optic cable shall be applied
for a period of 10 minutes. A
permanent or temporarily
increase
in
optical
attenuation value greater
than 0.1 dB change in
sample shall constitute
failure. The load shall be
further increased in small
increments
until
the
measured attenuation of the
optical waveguide fibres
increases and the failure load
recorded along with results.
Impact Test
IEEE 11382009
IEEE 1138-2009,
(IEC 60794-1-2
E4/ EIA/TIA 45525B)
10
Creep Test
IEEE 11382009
IEEE 1138-2009
As
per
Aluminium
Association Method, the
best-fit straight line shall be
fitted to the recorded creep
data
and
shall
be
extrapolated to 25 years. The
strain margin of the cable at
the end of 25 years shall be
calculated. The time when
the creep shall achieve the
strain margin limits shall
also be calculated.
11
Fibre Strain
Test
IEEE 11381994
IEEE 1138-1994
12
Strain Margin
Test
IEEE 11382009
IEEE 1138-2009
Stress strain
IEEE 1138-
IEEE 1138-2009
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-26
Table 2-2
Type tests for OPGW Cable
S. No.
Test Name
Test
Description
2009
Test Procedure
13
Test
14
Cable Cut-off
wavelength
Test
IEEE 11381994
IEEE 1138-1994
15
Temperature
Cycling Test
IEEE 11382009
IEEE 1138-2009
Or IEC 60794-1-2, Method F1
16
Corrosion
(Salt Spray)
Test
EIA/TIA 455-16A
17
Tensile
Performance
Test
18
Lightning
Test
IEC 60794-4-10 /
IEC 60794-1-2 (2003)
19
DC
Resistance
Test
(IEC 60228)
-End Of Table-
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-27
Part 1:
The tension assembly (excluding tension clamp) shall be increased at a constant rate up to a
load equal to 50% of the specified minimum Failure Load increased at a constant rate and
held for one minute for the test rig to stabilise. The load shall then be increased at a steady
rate to 67% of the minimum Failure Load and held for five minutes. This load shall then
remove in a controlled manner and the Tension Assembly disassembled. Examination of the
Tension Dead-End and associated components shall be made and any evidence of visual
deformation shall be documented.
Part 2:
The Tension Dead-End and associated components shall then be reassembled and bolts
tightened as before. The tensile load shall gradually be increased up shall gradually be
increased up to 50% of the specified Minimum Failure Load of the Tension Assembly and
Bidding Document for ICB-TD-TKTLP 073/74-01
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-28
held for one minute for the Test Rig to stabilise and the load shall be further increased at a
steady rate until the specified minimum Failure Load is reached and held for one minute. No
fracture should occur during this period. The applied load shall then be increased until the
failing load is reached and the value shall be documented.
Acceptance Criteria for Tension/Suspension Assembly:
- No evidence of binding of the Nuts or Deformation of components at end of Part 1 of Test.
- No evidence of Fracture at the end of one minute at the minimum failure load during Part 2
of the Test.
Any result outside these parameters shall constitute a failure.
(ii) Clamp Slip Strength Test for Suspension Assembly
The suspension assembly shall be vertically suspended by means of a flexible attachment. A
suitable length fibre optical cable shall be fixed in the clamps. Once the Suspension Clamp
has been assembled, the test rig is tensioned to 1 kN and the position scale on the recorder
zeroed. The test rig is then tensioned to 2.5 kN and the relative positions of the Reinforcing
Rods, Armour Rods and Suspension Clamp shall be marked by a suitable means to confirm
any slippage after the test has been completed. The relative positions of the helical Armour
Rods and associated Reinforcing Rods at each end shall be marked and also 2 mm relative
position between clamp body and Armour Rods shall be marked on one side. The load shall
be increased to 12 kN at a loading rate of 3 kN/min and held for one minute. At the end of
this one minute period, the relative displacement between clamp body and the armour rods
shall be observed. If the slippage is 2 mm or above, the test shall be terminated. Otherwise, at
the end of one minute the position of the clamp body and 2 mm. relative positions between
clamp body and armour rods shall be marked on the other side. After the one minute pause,
the load shall be further increased at a loading rate of 3 kN/min, and recording of load and
displacement shall continue until either the relative Position displacement between clamp
body and armour rods reaches more than 2 mm or the load reaches the maximum slip load of
17 kN. On reaching either of the above values the test is terminated. Visual examination of
all paint marks shall be recorded, and a measurement of any displacement recorded in the
Table of Results.
Acceptance Criteria:
The Suspension Clamp has passed the Slip Test if the following conditions are met:
Slippage shall occur between the specified maximum and minimum slip load of 12 17 kN.
There shall be no slippage of the Reinforcing Rods over the cable, and no slippage of
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-29
The relative movement (i.e. more than 2 mm between Armour Rods & Clamp body)
between minimum 12 kN and maximum slip 17 kN, shall be considered as slip.
The Armour Rods shall not be displaced from their original lay or damaged**.
** Definition of no damage in accordance with convention expressed in IEC 61284:
1997 no damage, other than surface flattening of the strands shall occur.
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-30
optic cable and examine all its components for distortion, crushing or breaking. Also the fibre
optic cable shall be checked to ensure free movement within the core using dial callipers to
measure the diameter of the core tube. The material shall be defined as failed if any visible
distortion, crushing, cracking or breaking of the core tube is observed or the fibre optic cable
within the core tube is not free to move, or when the diameter of the core tube as measured at
any location in the clamped area is more than 0.5 mm larger or smaller of the core diameter
as measured outside the clamped area.
(v) Structure Mounting Clamp Strength Test
The clamp and mounting assembly shall be assembled on a vertical 200 mm x 200 mm angle
and a short length of fibre optic cable installed. A vertical load of 200 kg shall be applied at
the end of the mounting clamp and held for 5 minutes. Subsequently, the load shall be
increased to 400 kg and held for 30 seconds. Any visible distortion, slipping or breaking of
any component of the mounting clamp or assembly shall constitute failure.
2.1.2.4
The testing standard of vibration damper for OPGW shall be as per applicable international
standard i.e. IEC 61897.
(a) Dynamic Characteristic Test
The damper shall be mounted with its clamp tightened with torque recommended by the
manufacturer on shaker table capable of simulating sinusoidal vibrations for Critical Aeolian
Vibration frequency band ranging from 0.18/d to 1.4/d where d is the OPGW cable
diameter in meters. The damper assembly shall be vibrated vertically with a 1 mm
amplitude from 5 to 15 Hz frequency and beyond 15 Hz at 0.5 mm to determine following
characteristics with the help of suitable recording instruments.
(i)
Force Vs frequency
(ii)
(iii)
The Force Vs frequency curve shall not show steep peaks at resonance frequencies and deep
troughs between the resonance frequencies. The resonance frequencies shall be suitably
spread within the Aeolian vibration frequency-band between the lower and upper dangerous
frequency limits determined by the vibration analysis of fibre optic cable without dampers.
Acceptance criteria for vibration damper:
(i) The above dynamic characteristics test on five damper shall be conducted.
(ii) The mean reactance and phase angle Vs frequency curves shall be drawn with
the criteria of best fit method.
(iii) The above mean reactance response curve should lie within following limits:
Bidding Document for ICB-TD-TKTLP 073/74-01
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-31
The analysis shall be done for single fibre optic cable without armour rods. The
tension shall be taken as 25% of RTS of fibre optic cable for a span ranging
from 100 m to 1100 m.
(ii)
The self damping factor and flexural stiffness (EI) for fibre optic cable shall be
calculated on the basis of experimental results. The details to experimental
analysis with these data shall be furnished.
(iii)
The power dissipation curve obtained from Damper Characteristics Test shall
be used for analysis with damper.
(iv)
Examine the Aeolian Vibration level of the fibre optic cable with and without
vibration damper installed at the recommended location or wind velocity
ranging from 0 to 30 Km per hour, predicting amplitude, frequency and
vibration energy input.
(v)
From vibration analysis of fibre optic cable without damper, antinode vibration
amplitude and dynamic strain levels at clamped span extremities as well as
antinodes shall be examined and thus lower and upper dangerous frequency
limits between which the Aeolian vibration levels exceed the specified limits
shall be determined.
(vi)
From vibration analysis of fibre optic cable with damper(s) installed at the
recommended location, the dynamic strain level at the clamped span extremities,
damper attachment point and the antinodes on the fibre optic cable shall be
determined. In addition to above damper clamp vibration amplitude and
antinodes vibration amplitudes shall also be examined.
The dynamic strain levels at damper attachment point, clamped span extremities
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-32
and antinodes shall not exceed the specified limits. The damper clamp vibration
amplitude shall not be more than that of the specified fatigue limits.
(c) Fatigue Tests
(i) Test Set Up
The fatigue tests shall be conducted on a laboratory set up with a minimum effective span
length of 30m. The fibre optic cable shall be tensioned at 25% of RTS of fibre optic cable and
shall not be equipped with protective armour rods at any point.
Constant tension shall be maintained within the span by means of lever arm arrangement.
After the fibre optic cable has been tensioned, clamps shall be installed to support the fibre
optic cable at both ends and thus influence of connecting hardware fittings are eliminated
from the free span. The clamps shall not be used for holding the tension on the fibre optic
cable. There shall be no loose parts, such as suspension clamps, U bolts, on the test span
supported between clamps mentioned above. The span shall be equipped with vibration
inducing equipment suitable for producing steady standing vibration. The inducing
equipment shall have facilities for step less speed control as well as step less amplitude
arrangement. Equipment shall be available for measuring the frequency, cumulative number
of cycles and amplitude of vibration at any point along the span.
(ii) Fatigue Test
The vibration damper shall be installed on the test span with the manufacturer's specified
tightening torque. It shall be ensured that the damper shall be kept minimum three loops away
from the shaker to eliminate stray signals influencing damper movement.
The damper shall then be vibrated at the highest resonant frequency of each damper mass.
For dampers involving torsional resonant frequencies, tests shall be done at torsional modes
also in addition to the highest resonant frequencies at vertical modes. The resonance
frequency shall be identified as the frequency at which each damper mass vibrates with the
maximum amplitude on itself. The amplitude of vibration of the damper clamp shall be
maintained not less than 25/f mm where f is the frequency in Hz.
The test shall be conducted for minimum ten million cycles at each resonant frequency
mentioned above. During the test, if resonance shift is observed, the test frequency shall be
tuned to the new resonant frequency.
The clamp slip test as mentioned herein shall be repeated after fatigue tests without
retorquing or adjusting the damper clamp, and the clamp shall withstand a minimum load
equal to 80% of the slip strength for a minimum duration of one minute.
After the above tests, the damper shall be removed from fibre optic cable and subjected to
dynamic characteristics test. There shall not be any major deterioration in the characteristics
of the damper. The damper then shall be cut open and inspected. There shall not be any
broken, loose, or damaged part. There shall not be significant deterioration or wear of the
Bidding Document for ICB-TD-TKTLP 073/74-01
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-33
damper. The fibre optic cable under clamp shall also be free from any damage.
For purposes of acceptance, the following criteria shall be applied:
(1)
There shall not be any resonant frequency shift before and after the test by
more than 20%
(2)
The power dissipation of the damper before and after test at the individual
resonant frequencies do not differ by more than 20%
Beside above tests, the type tests listed below in the table shall also be conducted on
Vibration Damper
Sl
No.
1
2
3
4
5
6
Test Name
Test Procedure
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-34
The sealed splice enclosure, with fibres spliced and looped inside, must be subjected to a
temperature of +55C 2C with a relative humidity rate of between 90% and 95% for 5
days. The attenuation variation of the fibres during the duration of the test shall be less than
0.05dB, and the internal humidity rate measured, less than 2%.
(iii) Rain Withstand Test / Water Immersion test
The splice enclosure with optical fibres cable installed and fibres spliced fixed, shall be
subjected to 24 hours of simulated rain in accordance with IEC 60060 testing requirements.
No water seepage or moisture shall be detected in the splice enclosure. The attenuation
variation of the fibres after the test shall be less than 0.05dB.
(iv) Vibration Test
The splice enclosure, with fibres united inside, shall be subjected to vibrations on two axes
with a frequency scanning of 5 to 50 Hz. The amplitude of the vibrations shall be constant at
0.450mm, peak to peak, for 2 hours, for each of the vibrations' axes. The variation in
attenuation, of the fibres, shall be less than 0.05dB. The splice enclosure shall be examined
for any defects or deformation. There shall be no loosening or visible damage of the FO cable
at the entry point.
(v) Bending and Torsion test
The splice enclosure, with fibres spliced inside, shall be firmly held in place and be subjected
to the following sequence of mechanical stresses on the cable:
a)
3 torsion cycles of 180 shall be exercised on the cable. Each cycle shall be less than
one minute.
b)
3 flexure cycles of the cable, of 180 with one cycle less than one minute.
The variation in the attenuation, of the fibres, shall be less than 0.05dB. The cables
connection ring shall remain securely fixed to the box with the connection maintained firmly.
No defects/fissures shall be noted on the joint ring or on the splice enclosure
(vi) Tensile test
The splice enclosure with cable fixed to the boxes shall be subjected to a minimum tension of
448 N for a period of two minutes. No fissure shall be noted in the connections or on the
box.
(vii)
Drop Test
With 2 lengths of 11 metres of cable fixed to the box, it shall be dropped five times from a
height of 10 metres. There shall be no fissure, at all, of the box, and the connections shall
remain tight. The test surface shall be carried out in accordance with IEC 60068-2-32.
2.1.2.6 Type Tests for Fibre Optic Approach Cable
Bidding Document for ICB-TD-TKTLP 073/74-01
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-35
The type tests to be conducted on the Fibre Optic Approach cable are listed in Table 2-3:
Type Tests for Fibre Optic Approach Cable. Unless specified otherwise in the technical
specifications or the referenced standards, the optical attenuation of the specimen, measured
during or after the test as applicable, shall not increase by more than 0.05 dB/Km.
Table 2-3:
Type Tests Fibre Optic Approach Cable
S.NO.
Test Name
Test Procedure
(IEC 60794-1-F5 /
EIA 455-82B) Test duration : 24
hours
Seepage of filling
compound
(EIA 455-81A)
Preconditioning : 72 hours,
Test duration : 24 hours.
Crush Test
Impact Test
(EIA 455-33A)
Cable Cut-off
wavelength Test
(EIA 455-170)
Temperature Cycling
Test
(IEC60794-1-F1/EIA-455-3A) 2
cycles
-End Of Table-
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-36
constitute final acceptance of the system or any portion thereof. These tests shall be carried
out in the presence of the Employer's authorised representatives unless waiver for witnessing
by Employers representatives is intimated to the contractor.
Factory acceptance tests shall not proceed without the prior delivery to and approval of all
test documentation by the Employer.
The factory acceptance tests for the supplied items shall be proposed by the Contractor in
accordance with technical specifications and Contractor's (including Sub-Contractor's /
supplier's) standard FAT testing program. In general the FAT for other items shall include at
least: Physical verification, demonstration of technical characteristics, various operational
modes, functional interfaces etc.
For Test equipment FAT shall include supply of proper calibration certificates, demonstration
of satisfactory performance, evidence of correct equipment configuration and manufacturers
final inspection certificate/ report.
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-37
him. The production tests to be carried out at each stage of production shall be based on the
Contractors standard quality assurance procedures. The production tests to be carried out
shall be listed in the Manufacturing Quality Plan (MQP), alongwith information such as
sampling frequency, applicable standards, acceptance criteria etc.
The production tests would normally not be witnessed by the Employer. However, the
Employer reserves the right to do so or inspect the production testing records in accordance
with Inspection rights specified for this contract.
Test Name
Acceptance Criteria
Test procedure
Attenuation Coefficient
T S,Table 1-1(a)
Point Discontinuities of
attenuation
EIA/TIA 455-59
TS ,Table 2-1(a)
Chromatic Dispersion
EIA/TIA 455168A/169A/175A
EIA/TIA 455-/176
Cladding diameter
EIA/TIA 455-176
EIA/TIA 455-31B
-End of table-
The test report for the above tests for the fibers carried out by the Fiber Manufacturer and
used in the OPGW cables shall be shown to the inspector during OPGW cable FAT and shall
be submitted along with the OPGW cable FAT report.
2.2.4 Factory Acceptance Test on OPGW Cable
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-38
The factory acceptance tests for OPGW cable specified below in Table follow the
requirements set forth in IEEE standard 1138 / IEC 60794. The FAT shall be carried out on
10% of offered drums in each lot as specified in technical specifications and the optical tests
shall be carried out in all fibres of the selected sample drums. The Rated Tensile Strength test
shall be carried out on one sample in each lot.
Table 2-5
Factory Acceptance Tests on OPGW
Applicable standard: IEEE 1138 / IEC 60794
S.
No.
2.2.5
The factory acceptance tests for OPGW Fittings as specified below in Table 2-6. The
sampling plan shall be as per relevant standard:
Table 2-6
Factory Acceptance Tests On OPGW Fittings
S. No.
3
4
Galvanising test
Tension Assembly
7
8
Galvanising Test
Vibration Damper
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-39
Table 2-6
Factory Acceptance Tests On OPGW Fittings
S. No.
10
11
12
13
14
15
16
17
18
19
20
21
22
Table 2-7
Factory Acceptance Tests On Approach Cable
S. No.
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-40
Visual check of Quantities and Specific Component Number for each component
of Splice Enclosure/FODP and dimensional checks against the approved drawings.
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-41
SAT shall be carried out link by link from FODP to FODP. SAT may be performed in parts
in case of long links.
The tests, checks, adjustments etc conducted by the Contractor prior to offering the
equipment for SAT shall be called Pre-SAT activities. The Pre-SAT activities shall be
described in the installation manuals and Field Quality Plan documents.
Sag and tension of OPGW shall generally be as per approved sag-tension chart and during
installation, sag and tension of OPGW shall be documented. Upon completion of a
continuous cable path, all fibres within the cable path shall be demonstrated for acceptance of
the cable path. Fibre Optic cable site testing minimum requirements are provided in Table 29(a) through 2-9(c) below:
Table 2-9(a)
Fibre Optic Cable Pre-Installation Testing
Item:
Description:
1.
2.
3.
Table 2-9(b)
Fibre Optic Cable Splicing Testing
Item:
Description:
1.
2.
3.
Table 2-9(c)
Fibre Optic Cable Commissioning Testing
Item:
2.
Description:
End to End (FODP to FODP) bi-directional average attenuation of each fibre at
1310 nm and 1550 nm by OTDR.
End to End (FODP to FODP) bi-directional average attenuation of each fibre at
1310 nm and 1550 nm by Power meter.
3.
Bi-directional average splice loss by OTDR of each splice as well as for all
1.
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-42
Proper termination and labelling of fibres & fibre optic cables at FODP as per
approved labelling plan.
-End of Table-
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-43
Chapter-03
Installation for OPGW Cabling
Table of Content
3.1
3.3
3.4
3.5
3.6
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-44
Section-03
Installation of OPGW Cabling
3.1 Installation requirements
The OPGW cable shall be installed at the top of the tower in place of earthwire (only one of the
earthwire peaks in case of 400kV & above lines, if applicable) for under construction transmission
lines as envisaged.
The OPGW cable sections shall normally be terminated & spliced only on tension towers. In
exceptional circumstances, and on Employer specific approval, cable may be terminated on suspension
towers, but in this case tower strength shall be examined to ensure that tower loads are within safe
limits and if required, necessary tower strengthening shall be carried out by the Contractor.
For OPGW Cable to be installed on new line transmission line, the stringing shall be carried by the
Transmission Line Contractor as per the stringing chart/procedure submitted by them and approved by
Employer. The Contractor shall install OPGW as per approved stringing procedure.
The Contractor shall follow precautions including proper location of drum site, installation of stringing
blocks/pulleys, proper sagging, proper installation of hardware, proper tension as per Sag-Tension
chart, provision of service loops of OPGW in jointing locations etc.
3.1.1 Installation of OPGW cable
The OPGW cable sections shall normally be terminated & spliced only on tension towers. In
exceptional circumstances and on Employer specific approval, cable may be terminated on Suspension
towers, but in this case tower strength shall be examined to ensure that tower loads are within safe
limits and if required, necessary tower strengthening shall be carried out by the Contractor. In such a
case, the jointing of OPGW on suspension tower if required, shall be acceptable subject to its
suitability.
3.1.2 Installation Hardware Fittings
All required hardware fittings shall be installed alongwith OPGW Cable.
3.2 Installation of Approach Cable
The existing cable trenches/ cable raceways proposed to be used shall be identified in the survey
report. The Contractor shall make its best effort to route the cable through the existing available cable
trenches. Where suitable existing cable trenches are not available, suitable alternatives shall be
provided after Employer approval. However, the approach cable shall be laid in the HDPE pipe in all
condition.
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-45
Suitable provisions shall be made by the Contractor to ensure adequate safety earthing and insulated
protection for the approach cable.
All required fittings, supports, accessories, ducts, inner ducts, conduits, risers and any item not
specially mentioned but required for laying and installation of approach cables shall be supplied and
installed by the Contractor.
3.3 Optical Fibre Termination and Splicing
Optical fibre terminations shall be installed in Fibre Optic Distribution Panels (FODP) designed to
provide protection for fibre splicing of preconnectorized pigtails and to accommodate connectorized
termination and coupling of the fibre cables. The Contractor shall provide rack /wall mounted Fibre
Optic Distribution Panels (FODPs) sized as indicated in the appendices and shall terminate the fibre
optic cabling up to the FODPs. The location of FODP rack shall be fixed by the Contractor, with the
Employers approval.
3.4 Fibre Optic Distribution Panel
At each location requiring the termination of at least one fibre within a cable, all fibres within that
cable shall be connectorized and terminated in Fibre Optic Distribution Panels in a manner consistent
with the following :
(a) All fibre optic terminations shall be housed using FODPs provisioned with splice organizers and
splice trays. All fibres within a cable shall be fusion spliced to pre-connectorized pigtails and
fitted to the "Back-side" of the provided fibre optic couplings.
(b) Flexible protection shall be provided to the patch cord bunches going out from FODP to other
equipment.
3.5 Methodology for Installation and Termination
All optical fibre cable termination, installation, stringing and handling plans, guides and procedures,
and engineering analysis (e.g. tension, sag, vibration etc.) shall be submitted to the Employer for
review and approval in the engineering/design phase of the project, prior to establishing the final cable
lengths for manufacture. Installation procedures including details of personnel and time required shall
be documented in detail and submitted to Employer for approval. All installation practices shall be
field proven and ISO accredited.
All cable segments shall include service loops as specified in this specification .The maximum
allowable stringing tension, maximum allowable torsional shear stress, crush strength and other
physical parameters of the cable shall not be exceeded. The preventative measures to be taken shall be
documented in detail and submitted to Employer in advance of installation.
Optical fibre attenuation shall be measured after installation and before splicing. Any increase in
attenuation or step discontinuity in attenuation shall not be acceptable and shall constitute a cable
segment failure. In the event of cable damage or any fibre damage, the complete section (tension
Bidding Document for ICB-TD-TKTLP 073/74-01
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-46
location to tension location) shall be replaced as mid-span joints are not acceptable.
Any or all additional steel work or modifications required to attach the fibre cabling to the overhead
transmission/ distribution line towers shall also be carried out by the Contractor. It shall be the
Contractors responsibility to provide adequate communications among all crew members and support
staff to ensure safe and successful installations.
3.6 Cable Raceways
To the extent possible, existing cable raceways shall be utilised. The Contractor is required to provide
and install any additional indoor cable raceways which may be required for proper implementation of
the fibre optic cabling system. This requirement shall be finalised during survey. The cable raceways
shall conform to the following:
(a) All cable raceways shall be sized to support full loading requirements plus at least a 200% safety
loading factor.
(b) Indoor cable raceways shall be fabricated from construction grade aluminium, galvanized iron or
anodized sheet metal or any other suitable material approved by the Employer. Suitable anticorrosion measures shall be provided. Steel fabricated raceways shall be finished inside and out,
treated to resist rust and to form a metal-to- paint bond.
(c) Mechanical construction drawings of the cable raceways shall be submitted for Employers
information & review.
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-47
Appendix-A
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-48
Appendix-B
Data Requirement Sheets
The following sets of Data Requirement Sheets are required to be filled up by the bidders to aid
in the evaluation process. The response shall be brief and to the point and shall be supported by
the printed product description and other literature. The DRS duly filled and the relevant
drawings shall also be submitted during the detailed engineering along with the relevant technical
brochures.
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-49
DRS Form 1
DATA REQUIREMENTS SHEETS for
OVERHEAD FIBRE OPTIC CABLE
Manufacturer:
Part #:
_______________________________
Configuration:
_______________________________
CABLE CONSTRUCTION
Seq
1.
Parameter:
As per Technical
Specification
No. of Fibres
Dual Window Single-Mode:
48
2.
Buffer Type:
Loose Tube
3.
Non-metallic
4.
5.
Maximum Twelve(12)
6.
25 Year
Procurement of Plant
Single-Stage: Two-Envelope
Section 9 - OPGW
9-50
DRS Form 2
DATA REQUIREMENTS SHEETS for OPTICAL FIBRE
DUAL-WINDOW SINGLE MODE (DW-SM)
OPTICAL PARAMETERS
Seq
As per Technical
Specification
Parameter:
1.
2.
3.
4.
5.
6.
7.
Cutoff wavelength:
8.
9.
10.
11.
As per Bidder
offering
0.35 dB/km
0.21 dB/km
0.05 dB
0.05 dB
8.6 to 9.5 m
( 0.6 m )
3.5 ps/(nmxkm)
5.3 ps/(nmxkm)
18 ps/(nmxkm)
1300 to 1324 nm
1260 nm
0.05 dB
0.05 dB
0.50 dB
Cladding Diameter
(nominal deviation):
Polarisation mode dispersion
coefficient
Proof test level
125.0 m 1 m
0.2 ps/km1/2
0.69 Gpa
Procurement of Plant
Single-Stage: Two-Envelope
10-1
SECTION- 10
DETAIL SURVEY REPORT
Detailed survey including route alignment, profiling, have been carried out by the
Employer and is attached herewith only for the reference. Though these are not
expected to vary substantially, however, certain quantity of detailed survey
including route alignment, profiling, tower spotting, optimization of tower
locations etc. have been kept in the scope of the Bidder for the changes in the
route if any needed during execution stage.
Procurement of Plant
Single-Stage: Two-Envelope
Section 11 - Drawings
11-1
SECTION-XI
DRAWINGS
Procurement of Plant
Single-Stage: Two-Envelope
SHEET No 1 OF 2
OF INDIA LIMITED
DRG No
/DES
WIND ON TOWER
1) FOR RELIABILITY CONDITION FULL WIND HAS TO BE APPLIED
2) FOR SECURITY CONDITION 75% OF FULL WIND HAS TO BE APPLIED
3) FOR SAFETY CONDITION NO WIND HAS TO BE APPLIED
438 (-418 )
438 (-418)
702
689
JA0
PEAK
JA0
1370 ( -1100)
1370 ( -1100)
1416
1370 ( -1100
)
1416
1370 ( -1100
)
1387
1387
CE0
CF0
CE0
CF0
1370 ( -1100)
1370 ( -1100)
882 ( -612)
1370 ( -1100
)
1416
1416
CC0
CD0
1370 ( -1100)
1370 ( -1100)
MXM
1416
1387
CD0
882 ( -612)
1370 ( -1100
)
1416
CA0
BXM
842
CC0
11
49
TXM
842
CB0
1387
CA0
11
49
CB0
RELIABILITY CONDITION
1029 ( -836 )
266 (-246 )
36
406
JA0
1370 (-1100)
21
69
JA0
3249 ( -1842 )
1370 (-1100)
1387
1387
3249 (-1842 )
87
87
CE0
CF0
CE0
CF0
1370 (-1100)
1370 (-1100)
3249 ( -1842 )
3249 (-1842 )
1387
1387
87
87
CC0
CD0
CC0
CD0
882 ( -612)
1370 (-1100)
3249 (-1842 )
3249 (-1842 )
842
1387
CB0
87
CA0
11
87
CB0
49
CA0
SAFETY CONDITION
TRMX-LOMN MXWSPN (MNWSPN)
NO WIND ON TOWER
SHEET No 2 OF 2
OF INDIA LIMITED
DRG No
/DES
WIND ON TOWER
1) FOR RELIABILITY CONDITION FULL WIND HAS TO BE APPLIED
2) FOR SECURITY CONDITION 75% OF FULL WIND HAS TO BE APPLIED
3) FOR SAFETY CONDITION NO WIND HAS TO BE APPLIED
686 ( -493)
1029 ( -836 )
18
36
3249 ( -1842 )
51
0
JA0
JA0
3249 (-1842 )
87
3249 ( -1842 )
87
CE0
CF0
3249 ( -1842 )
3249 (-1842 )
87
87
87
CE0
CF0
2273 (-713)
87
3249 ( -1842 )
44
CD0
87
CC0
CD0
2273 ( -713)
10
20
CC0
3249 ( -1842 )
3249 (-1842 )
44
87
3249 ( -1842 )
44
CB0
CA0
87
CB0
10
10
20
20
CA0
2273 (-713)
SHEET No 1 OF 3
OF INDIA LIMITED
DRG No
/DES
WIND ON TOWER
1) FOR RELIABILITY CONDITION FULL WIND HAS TO BE APPLIED
2) FOR SECURITY CONDITION FULL WIND HAS TO BE APPLIED
3) FOR SAFETY CONDITION NO WIND HAS TO BE APPLIED
438 (-418)
438 ( -418)
3187
PEAK
3187
JA0
JA0
1819 ( -739 )
1819 ( -739 )
6847
CE0
CF0
1819 ( -739 )
1819 ( -739 )
6847
MXM
3668
CF0
1331 (-251 )
1331 (-739 )
1819 ( -739 )
1819 ( -739 )
3668
6847
CC0
CD0
1331 (-251 )
1331 (-739 )
6847
BXM
54
30
CD0
6847
CE0
6847
CC0
1331 (-739 )
54
30
6847
TXM
1331 (-251 )
6847
CA0
3668
CB0
6847
CA0
CB0
54
30
RELIABILITY CONDITION
266 (-246)
1029
1655
1028
JA0
1819 ( -739)
25
21
JA0
1819 ( -739)
6847
4149
6847
CE0
CF0
1331 (-251 )
1819 ( -739)
3668
2493
1331 (-251 )
1819 ( -739)
CF0
4149
4149
2493
2493
CC0
CD0
54
30
CD0
2493
CE0
6847
CC0
4149
3668
6847
CB0
4149
2493
2493
CA0
CB0
54
30
CA0
4149
SHEET No 2 OF 3
OF INDIA LIMITED
DRG No
/DES
WIND ON TOWER
1) FOR RELIABILITY CONDITION FULL WIND HAS TO BE APPLIED
2) FOR SECURITY CONDITION FULL WIND HAS TO BE APPLIED
3) FOR SAFETY CONDITION NO WIND HAS TO BE APPLIED
686
1029
514
1028
JA0
4149
77
1
10
28
JA0
4149
3173
2493
4149
2493
CE0
1246
CF0
2493
CF0
4149
1246
18
69
93
3173
24
18
69
18
69
CE0
3173
4149
2493
CC0
1246
CD0
2493
CD0
4149
18
69
3173
24
93
69
18
24
93
CC0
3173
1246
4149
2493
CA0
1246
CB0
2493
CB0
69
24
18
69
93
18
24
93
CA0
NO WIND ON TOWER
224 (-204)
331 (-311)
972
PEAK
497
JA0
24
87
JA0
1210 ( -130 )
1210 ( -130 )
2243
2243
2243
1571 ( -491 )
2243
2243
CD0
2243
52
52
45
45
CC0
1210 ( -130 )
1571 ( -491 )
2243
1571 ( -491 )
2243
CB0
2243
CA0
CB0
0
52
45
CA0
45
1571 ( -491 )
CD0
1210 ( -130 )
52
CF0
52
45
52
2243
2243
CE0
1210 ( -130 )
CC0
BXM
2243
CF0
1210 ( -130 )
MXM
1571 ( -491 )
45
CE0
TXM
1571 ( -491 )
OF INDIA LIMITED
SHEET No 3 OF 3
DRG No
/DES
WIND ON TOWER
1) FOR RELIABILITY CONDITION FULL WIND HAS TO BE APPLIED
2) FOR SECURITY CONDITION FULL WIND HAS TO BE APPLIED
3) FOR SAFETY CONDITION NO WIND HAS TO BE APPLIED
972 [*61]
497 [*344]
JA0
24
87
[*0
]
JA0
722 ( 358)
1210 (-130 )
373
1259 (-179 )
2243
910
CF0
1200
CE0
CF0
373
2243
1210 (-130 )
373
CD0
1259 (-179 )
2243
1454 (-374 )
910
CB0
1200
CA0
CB0
DEAD-END (with slack span) SECURITY CA0 & CC0 & CE0
267 (-247)
514
10
28
JA0
1332 ( 252 )
1332 ( 252 )
1247
1247
CF0
24
24
93
93
CE0
1332 ( 252 )
1332 ( 252 )
1247
1247
24
24
93
CD0
93
CC0
1332 ( 252 )
1332 ( 252 )
1247
1247
93
CB0
24
93
CA0
24
54
25
CA0
1200
CC0
722 ( 358)
1454 (-374 )
910
CD0
54
25
CC0
1259 (-179 )
1210 (-130 )
722 ( 358)
54
25
CE0
1454 (-374 )
ANTICASCADING CONDITION
TRMX-LOMN MXWSPN (MNWSPN)
360 [127]
1020
360 [127]
GA0
1020
882 [364]
1864
882 [364]
CE1
1864
882 [364]
1864
CC1
1864
882 [364]
1864
CF1
882 [364]
CD1
882 [364]
CA1
1864
882 [364]
1739
CE0
CB1
882 [364]
1739
CF0
GA0
882 [364]
882 [364]
1418
CE1
1418
882 [364]
1418
CC1
1418
882 [364]
1418
CD1
882 [364]
CA1
1418
CB1
882 [364]
882 [364]
1323
CF1
882 [364]
CE0
1323
CF0
882 [364]
882 [364]
1739
CC0
1739
882 [364]
1739
CD0
882 [364]
CA0
1739
CB0
882 [364]
1323
882 [364]
CC0
1323
589 [242]
820
CD0
882 [364]
CA0
1323
CB0
5196
RELIABILITY
SECURITY
(Bottom ckt)
220 [68]
360 [127]
1020
882 [364]
882 [364]
1418
CE1
1418
CF1
882 [364]
1418
1418
CC1
1418
CD1
1418
878
CB1
3166
CC1
1418
CA1
882 [364]
1418
882 [364]
1418
882 [364]
882 [364]
CA1
CE1
GA0
882 [364]
882 [364]
882 [364]
1418
455
882 [364]
GA0
882 [364]
1418
5432
882 [364]
882 [364]
1323
CE0
1323
882 [364]
1323
1323
882 [364]
CC0
1323
882 [364]
1323
CF0
882 [364]
CD0
1323
Security
(top ckt)
1323
CB0
CE0
1323
882 [364]
1323
1323
882 [364]
CC0
882 [364]
882 [364]
CA0
882 [364]
CA0
Security
(Ground wire)
882 [364]
1323
873
49
2273
87
873
GA0
49
CE1
2273
87
2273
87
CC1
87
CD1
CA1
87
2273
CB1
87
CE0
87
2273
CC0
87
CF0
87
CD0
87
CB0
87
CC1
87
CD1
2273
CA1
87
CB1
2273
CE0
87
87
2273
CC0
87
CF0
2273
1688
43
CF1
2273
2273
2273
CA0
CE1
87
2273
2273
2273
2273
2273
87
2273
2273
87
87
87
2273
2273
87
CF1
2273
GA0
CD0
2273
87
CA0
CB0
1020
RELIABILITY
SAFETY
(Bottom ckt)
593
873
49
1688
43
CE1
1020
2273
87
CC1
24
GA0
0
2273
87
CA1
87
87
87
CB1
CE0
CF0
2273
CC0
87
2273
CA0
SAFETY
(Top ckt)
87
CD0
87
CB0
2273
87
CC1
CA1
87
87
CE0
87
2273
CC0
87
CF0
2273
2273
SAFETY
(GWR)
CB1
2273
87
CA0
CD1
2273
2273
87
CF1
2273
87
2273
87
510
2273
2273
87
2273
87
CD1
CE1
2273
2273
2273
87
2273
87
2273
2273
87
CF1
GA0
CD0
2273
87
CB0
Section 11 - Drawings
132 kV Drawings
Procurement of Plant
Single-Stage: Two-Envelope
BASIC BODY
+9.0
Shoretest Leg
-3.0
-1.5
0
+1.5
+3.0
+4.5
+6.0
+7.5
+9.0
-3.0, -1.5, 0
-1.5, 0, +1.5
0, +1.5,
+1.5
+3.0, +4.5, +6.0
+4.5, +6.0, +7.5
+6.0, +7.5, +9.0
+7.5, +9.0
+9.0
DATE :
DRAWING NO. :
T-K/132KV/LEGSCHEME
LEG SCHEME FOR TOWER TYPES DA, DB, DC, DD, DBH, DDH
PRAPARED BY:
APPROVED BY:
CHECKED BY:
T-K/132KV/SINGLESUSPENSION
PRAPARED BY:
DATE :
DRAWING NO. :
APPROVED BY:
CHECKED BY:
TECHNICAL DATA:
T-K/132KV/SINGLETENSION
PRAPARED BY:
DATE :
DRAWING NO. :
APPROVED BY:
CHECKED BY:
Section 11 - Drawings
400 kV Drawings
Procurement of Plant
Single-Stage: Two-Envelope
3 m for Tower DA
-4.5, -3.0, -1.5
+1.5, +3.0
+3.0
+4.5, +6.0, +7.5
+6.0, +7.5, +9.0
+7.5, +9.0
+9.0
+1.5, +3.0
+3.0
+4.5, +6.0, +7.5, +9.0
+6.0, +7.5, +9.0
+7.5, +9.0
+9.0
LEG SCHEME FOR TOWER TYPES DA, DB, DC, DD, DBH, DDH
PRAPARED BY:
CHECKED BY:
DRAWING NO. :
APPROVED BY:
DATE :
T-K/400KV/LEGSCHEME
COMPONENT DETAILS
TECHNICAL DETAILS:
DATE :
DRAWING NO. :
PROJECT
TITLE
CONSULTANT
PRAPARED BY:
CHECKED BY:
APPROVED BY:
Sr.No.
DESCRIPTION
U.T.S.
COMPONENT DETAILS
MATERIAL
WEIGHT
QTY.
FINISH
COMPONENT NO.
DATE :
DRAWING NO. :
400 KV. QUADRUPLE TENSION STRING SUITABLE FOR QUADRUPLE ACSR MOOSE CONDUCTOR
PROJECT
TITLE
CONSULTANT
PRAPARED BY:
CHECKED BY:
APPROVED BY:
Sr.No.
DESCRIPTION
U.T.S.
COMPONENT DETAILS
MATERIAL
WEIGHT
QTY.
FINISH
COMPONENT NO.
DATE :
DRAWING NO. :
400 KV. QUADRUPLE TENSION STRING SUITABLE FOR QUADRUPLE ACSR MOOSE CONDUCTOR
PROJECT
TITLE
CONSULTANT
PRAPARED BY:
CHECKED BY:
APPROVED BY:
PROJECT
TITLE
DRAWING NO. :
DATE :
PRAPARED BY:
APPROVED BY:
COMPONENT DETAILS
PROJECT
DATE :
DRAWING NO. :
400 KV SINGLE I SUSPENSION PILOT STRING SUITABLE FOR QUADRUPLE ACSR MOOSE CONDUCTOR
TITLE
CONSULTANT
PRAPARED BY:
CHECKED BY:
APPROVED BY:
NOTES
300X300X8
3
8
5
10
925
SECTION A-A
TITLE
10
S.NO.
PROJECT
CONSULTANT
T-K/400KV/DACSR
PRAPARED BY:
DATE :
DRAWING NO. :
APPROVED BY:
CHECKED BY:
NOTES
10
10
9
8
7
6
5
4
3
2
1
S.NO.
8
5
6
3
700
STEEL TAPE
MS
MS
WOOD
MS
MS
MS
WOOD
WOOD
WOOD
Qty Material
2
24
3
6
2
8
1
2
1
SECTION A-A
BUSH PLATE
SLOT FOR INNER END OF EARTHWIRE
WASHER
BARREL SUPPORT
TIE RODS
MILD STEEL BUSH
BARREL STUD
BARREL
FLANGE
PROTECTIVE EXETRNAL LAGAING
DESCRIPTION
DATE :
DRAWING NO. :
T-K/400KV/DEW
PRAPARED BY:
APPROVED BY:
CHECKED BY:
Section 11 - Drawings
Common Drawings
Procurement of Plant
Single-Stage: Two-Envelope
SEC- B-B
BARBED WIRE
C.L. OF TOWER
TITLE
CONSULTANT
PRAPARED BY:
APPROVED BY:
CHECKED BY:
DATE :
DRAWING NO. :
PROJECT
LINE DIRECTION
NOTES
1 : ALL DIM. ARE IN MM
2 : M.S. PLATE 1.6 mm THICK (MIN)
3 : WHITE ENAMELLED BACKGROUND AND RED ENAMELLED LETTERING
PROJECT
CIRCUIT PLATE
CONSULTANT
PRAPARED BY:
DATE :
DRAWING NO. :
APPROVED BY:
CHECKED BY:
NOTES
1 : ALL DIM. ARE IN MM
2 : 10.97mm GALVINISED WIRE WITH G.S LUG FORGED AT ONE END
OTHER END FREE FOR A REQUIRED LENGTH OF COUNTERPOISE WIRE
3 : FOUR G.S. LUG WILL BE REQUIRED PER TOWER . THREE LUGS WILL BE
CONNECTED ON 3 LEGS & FOURTH LUG WILL BE CONNECTED WITH FLAT
TYPE 'C' PROVIDED FOR PIPE TYPE EARTHING .
4 : 10.97 MM WIRE SHALL BE OUTSIDE COPPING .
5 : ONE SET COMPRISING OF FOUR NUMBERS OF REQUIRED LENGTH OF
COUNTERPOISE WIRE
TITLE
PROJECT
CONSULTANT
PRAPARED BY:
DATE :
DRAWING NO. :
APPROVED BY:
CHECKED BY:
NOTES
1 : ALL DIM. ARE IN MM
2 : LETTER AND FIGURE SHALL IN RED ENAMEL & BACKGROUND SHOULD BE WHITE ENAMELLED.
3 : BACK : BLACK VITREOUS ENAMELD
6 : FASTENERS & WASHERS : 2 NOS. 16 mm PER PLATE WITH FOUR NOS. 2mm THICK LEAD WASHERS
PROJECT
CONSULTANT
T-K/132kV/DPL
PRAPARED BY:
DATE :
DRAWING NO. :
APPROVED BY:
CHECKED BY:
NOTES
1 : ALL DIM. ARE IN MM
2 : LETTER AND FIGURE SHALL IN RED ENAMEL & BACKGROUND SHOULD BE WHITE ENAMELLED.
3 : BACK : BLACK VITREOUS ENAMELD
6 : FASTENERS & WASHERS : 2 NOS. 16 mm PER PLATE WITH FOUR NOS. 2mm THICK LEAD WASHERS
PROJECT
CONSULTANT
T-K/400kV/DPL
PRAPARED BY:
DATE :
DRAWING NO. :
APPROVED BY:
CHECKED BY:
NOTES
PER TOWER
TITLE
CONSULTANT
PRAPARED BY:
DATE :
DRAWING NO. :
APPROVED BY:
CHECKED BY:
PROJECT
REMARKS
M 16 x 45 LG.
QTY.
M 16 x 35 LG.
SIZE
M 12 x 30 LG.
S.NO.
TITLE
PROJECT
CONSULTANT
PRAPARED BY:
DATE :
DRAWING NO. :
APPROVED BY:
CHECKED BY:
NOTES
PROJECT
DATE :
DRAWING NO. :
CONSULTANT
PRAPARED BY:
APPROVED BY:
CHECKED BY:
END FLATED
50
135
SEC. S-S
STUB ANGLE
FLAT
25
GALVD. FLAT
B
TWISTED
STUB ANGLE
S
16 BOLTS
25
DETAIL AT 'B'
300
DETAIL X
12 BOLTS
25
30
TITLE
CONSULTANT
PRAPARED BY:
APPROVED BY:
CHECKED BY:
DATE :
DRAWING NO. :
T-K/400KV/PE01
PROJECT
150
2850
45
6.5 HOLES
25 PIPE
DETAIL AT 'A'
NOTES
150
140
150
1000
25
40
25
c'
4
b' 3
a'
c 2
1 b
a
X c/a
X b'/a'
X c'/a'
X b/a
TITLE
PROJECT
CONSULTANT
PRAPARED BY:
DATE :
DRAWING NO. :
APPROVED BY:
CHECKED BY:
NOTES
1 : ALL DIM. ARE IN MM
2 : STEP BOLT SHALL BE HOT DIPPED GALVNISED
3 : WEIGHT / PIECE WITH TWO NUTS 0.41 K.G.
1
0
DATE :
DRAWING NO. :
APPROVED BY:
CHECKED BY:
PRAPARED BY:
CONSULTANT
TITLE
PROJECT
1
0
NOTES
G.L.
PROJECT
TITLE
DATE :
DRAWING NO. :
PRAPARED BY:
APPROVED BY:
CHECKED BY:
NOTES
10
PROJECT
CONSULTANT
PRAPARED BY:
DATE :
DRAWING NO. :
APPROVED BY:
CHECKED BY:
Annexure
ANNEXURE
Procurement of Plant
Single-Stage: Two-Envelope