TC - Rcue 40 - 240 WG2 (TCGB0045 (12-06)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 88
At a glance
Powered by AI
The document discusses water-cooled water chillers, their components, operation instructions, installation and testing procedures.

The main components of the chiller include the compressor, condenser, water cooler, control system and expansion valve.

The refrigerant is compressed in the compressor and condenses in the condenser by transferring heat to the water. It then expands through the expansion valve and evaporates in the water cooler by absorbing heat from the water before returning to the compressor.

Technical Catalog

Installation, Operation and Maintenance Instructions.


Design Information

WATER COOLED
WATER CHILLERS
-SCREW TYPERCUE40WG2-240WG2 (R407C)
Capacity 134 kW-696 kW
Heat Pump Option
Heating Capacity 161 kW-824 kW

TABLE OF CONTENTS
1. IMPORTANT NOTICE................................................................................................................. 1
2. FEATURES AND BENEFITS...................................................................................................... 1
2.1. NEW CHILLER PICTURE.....................................................................................................................1
2.2. COMPRESSOR ....................................................................................................................................2
2.3. CONTROL ............................................................................................................................................3
2.4. HEAT EXCHANGER.............................................................................................................................4
2.5. NEW ELECTRONIC EXPANSION VALVE ...........................................................................................4

3. OPERATION INSTRUCTIONS ................................................................................................... 4


3.1. HITACHI WATER COOLED WATER CHILLER MODELS: RCUE 40-240 WG2 ..................................4

4. COMPONENTS OF CHILLER .................................................................................................... 5


4.1. STRUCTURE DRAWING .....................................................................................................................5

5. PREPARATION INITIAL CHECK ............................................................................................... 6


5.1. INITIAL CHECK ....................................................................................................................................6
5.2. PLACING THE UNIT.............................................................................................................................6
5.3. CENTRE OF GRAVITY ........................................................................................................................7
5.4. SERVICE SPACE AND FOUNDATION................................................................................................8
5.5. TRANSPORTATION BY RIGGING.......................................................................................................9

6. INSTALLATION .......................................................................................................................... 10
6.1. ELECTRICAL WIRING .........................................................................................................................10
6.2. WATER PIPING....................................................................................................................................12
6.3. MINIMUM INTERNAL SYSTEM WATER VOLUME .............................................................................13
6.4. WATER CONTROL ..............................................................................................................................13
6.5. BMS CONNECTION .............................................................................................................................15
6.6. CSC-5S.................................................................................................................................................21
6.7. INSTALLATION FINAL CHECK............................................................................................................24

7. TEST RUNNING.......................................................................................................................... 25
7.1. PREPARATION ....................................................................................................................................25
7.2. TEST RUNNING ...................................................................................................................................25
7.3. INSTRUCTIONS AFTER TEST RUNNING ..........................................................................................26

8. CONTROLLER ADJUSTMENT .................................................................................................. 26


8.1. CONTROL SYSTEM.............................................................................................................................27
8.2. CONTROLLER ADJUSTMENT ............................................................................................................28

9. SELF-INSPECTION FUNCTIONS .............................................................................................. 30


9.1. ALARM INDICATION............................................................................................................................30
9.2. NORMAL INDICATION.........................................................................................................................31
9.3. FUNCTION FOR INDICATION OF OPERATION CONDITION ............................................................31

10. CONTROL SYSTEM ................................................................................................................. 36


11. MAINTENANCE ........................................................................................................................ 39
11.1. COMPONENTS ..................................................................................................................................39
11.2. LUBRICATION....................................................................................................................................39
11.3. DEPOSITS..........................................................................................................................................39
11.4. CLEANING METHOD .........................................................................................................................40
11.5. WINTER SHUTDOWN........................................................................................................................41
11.6. SPRING START-UP ...........................................................................................................................41
11.7. PART REPLACEMENT ......................................................................................................................41
11.8. REFRIGERATION CYCLE..................................................................................................................42
11.9. REFRIGERANT CYCLE DIAGRAM OF HITACHI WATER COOLED CHILLER.................................42
11.10. COMPRESSOR REMOVAL..............................................................................................................44
11.11. SAFETY AND PROTECTION CONTROL ........................................................................................44
11.12. NORMAL OPERATING PRESSURE................................................................................................46
11.13. TEST RUNNING AND MAINTENANCE RECORD ...........................................................................47
11.14. DAILY OPERATING RECORDS.......................................................................................................48
11.15. SERVICING FOR R407C REFRIGERANT SYSTEM .......................................................................48

12. TROUBLESHOOTING .............................................................................................................. 49

13. GENERAL SPECIFICATIONS .................................................................................................. 51


13.1. GENERAL DATA ................................................................................................................................51
13.2. OPTION LINE UP ...............................................................................................................................54

14. DRAWINGS ............................................................................................................................... 55


14.1. DIMENSIONAL DRAWINGS ..............................................................................................................55
14.2. WIRING DIAGRAMS ..........................................................................................................................60

15. MODEL SELECTION ................................................................................................................ 70


15.1. SELECTION EXAMPLE .....................................................................................................................70
15.2. PERFORMANCE TABLE ...................................................................................................................71
15.3. ELECTRICAL DATA ...........................................................................................................................77
15.4. SOUND DATA ....................................................................................................................................78

16. APPLICATION DATA ............................................................................................................... 79


16.1. WORKING RANGE ............................................................................................................................79
16.2. PART LOAD PERFORMANCE ..........................................................................................................79
16.3. ETHYLENE GLYCOL APPLICATION.................................................................................................80

17. COMPONENTS DATA .............................................................................................................. 81


17.1. COMPRESSOR..................................................................................................................................81
17.2. CONDENSER AND WATER COOLER ..............................................................................................81

IMPORTANT NOTICE

1/1

1. IMPORTANT NOTICE
HITACHI pursues a policy of continuing improvement in
design and performance of Products. The right is therefore
reserved to vary specifications without notice.
HITACHI cannot anticipate every possible circumstance
that might involve a potential hazard.
No part of this manual may be reproduced without written
permission.
Signal words (DANGER, WARNING and CAUTION) are
used to identify levels of hazard seriousness. Definitions
for identifying hazard levels are provided below with their
respective signal words.

DANGER:

Immediate hazards which WILL result in severe


personal injury or death.

WARNING:

Hazards or unsafe practices which COULD result


in sever personal injury or death.

 CAUTION:

Hazards or unsafe practices which COULD result


in minor personal injury or product or property
damage.
NOTE:
Useful information for operation and/or maintenance.

If you have any questions, contact your contractor or


dealer of HITACHI.
This instruction gives a common description and
information for this water cooled water Chiller which you
operate as well as for other models.
This water cooled water Chiller has been designed for
the following temperatures. Operate the water cooled
water Chiller within this range.
Working Range
Maximum
Condenser Water
Outlet
Temperature
Chilled Water
Outlet
Temperature

C
Minimum

45
*(55)

22

15

5
**(-10)

(*) In case of High Condensing option and Heat Pump


operation option.
(**) In case of low water temperature option.
This instructions should be considered as a permanent
part of the water cooled water Chiller equipment and
should remain with the water cooled water Chiller
equipment.

2. FEATURES AND BENEFITS


2.1. NEW CHILLER PICTURE

HITACHI is a world leader in technology and with


continual research and product development, now offers
a screw type Water Cooled Chiller.

A wide range of capacities are available from 134 kW to


696 kW.
Heating operation is available for option. Heating
Capacities are available from 161 kW to 824 kW.

2/2

FEATURES AND BENEFITS

2.2. COMPRESSOR
THE SAMURAI RANGE

INCORPORATES THE LATEST


DEVELOPMENT OF HITACHIS
SCREW COMPRESSOR
TECHNOLOGY FOR THE NEW
MILLENNIUM.

Highly Reliable HITACHI Two-Pole


Motor

Built-in Oil Separator (Cyclone oil


separator)

Oil Sight Glass


Oil Heater
High precision Twin Screw Rotors
Suction Filter

-LOW VIBRATION-

TWIN SCREW COMPRESSOR

Reciprocating

Screw

AMPLITUDE (m)

By having so few moving parts, it has become highly reliable


with very low noise level and low vibration

Time (second)
PRINCIPLE OF COMPRESSION
Discharge Port

Suction Port

HITACHIs Continuous Capacity Control system uses


advanced electronic controls to position the infinitely
variable slide valve within each compressor.
This modulation allows exact load control and accurate
chilled water temperature without the need for
expensive inverters.

COOLING LOAD %

CONTINUOUS CAPACITY CONTROL

Cooling load = continuos capacity control


Step
control

TIME (Hour)

FEATURES AND BENEFITS

2/3

-PART LOAD PERFORMANCE-

ENERGY SAVING

MOTOR INPUT (%)

Thanks to Continuous Capacity Control, 15~20% energy


saving is possible compared with current step control
systems due to the following:
-The cooling load can be more closely matched
-Continuous Capacity Control takes advantage of high
efficiency part load performance.
-Frequent compressor starts and stops are eliminated.

Continuous
Capacity
Control

COOLING CAPACITY (%)

2.3. CONTROL
MANY FUNCTIONS
Newly developed Control Board has many functions
shown below as standard.
Forced compressor load control
2 Different temperature setting
Memory data in alarm
Automatic restart after power failure
Heating operation (Heat pump operation option)

etc...

-CONTINUOUS CAPACITY CONTROL-

PRECISE TEMPERATURE

CONTROL
WATER TEMPERATURE

Start
Outlet Water Temperature

Load Up 1
(Quick cooling)
Load Up 2
Neutral =2qC Standard
(Minimum 0.5C)
Load Down
TIME

-CONVENTIONAL STEP CONTROLRestart


WATER TEMPERATURE

Combination of "Continuous Capacity


Control Compressor" and "HITACHIs
unique electronic controls" enable the
Chiller to control outlet water temperature
precisely, independent of cooling load.
This control benefits not only airconditioning but also industrial process
use.

Outlet
Temperature

1st step

Final step

Temperature
Band 7qC
(normally)

1/4
2.4. HEAT EXCHANGER
Less Refrigerant (Small Internal Volume)
-Clean (Stainless Steel)
-High efficiency (closer approach temperature)
Plate type heat exchanger can provide improved cooling
capacity for R407C

PLATE TYPE HEAT EXCHANGER


The new Samurai Chillers are equipped with plate type
Heat Exchangers, which have many advantages when
compared with conventional Shell & Tube heat
exchanger as described beside:

PLATE

CAPACITY (%)

SHELL & TUBE

2.5. NEW ELECTRONIC EXPANSION VALVE

This unit is equipped with an electronic expansion valve to


provide sophisticated control under any temperature
condition.
The electronic expansion valve provides reduced electrical
power consumption compared to the classical system.

3. OPERATION INSTRUCTIONS
3.1. HITACHI WATER COOLED WATER CHILLER MODELS: RCUE 40-240 WG2
To Start the Unit.
1.Open the water inlet and outlet valves.
2.After assuring that all control switches have been cut
OFF, and the LOCAL/REMOTE switch on the
printed circuit board is in the LOCAL position, turn
ON the power switch.
3.Confirm that phases R, S and T are correctly
connected. The correct phase connection can be
checked by a phase sequence indicator. If not
correctly connected, the compressor does not start
due to activation of a reversal phase protection
device. Cut the main switch and interchange two of
three terminals, R, S and T at the main power source
terminals.
4.Set the changeover switch to cool or Heat (In case
of Heat Pump operation option)
5.Fully open the liquid line stop valves.
6.Operate the cooling (Hot) and chilled water pump.
7.Set the Dip SW at the desired temperature
8.Depress the ON push button of the operation Switch
To Stop the Unit
1.Depress the OFF push button of the operation
switch.
2.Switch OFF the main power source when the unit is
shut down for a long period of time.
Pilot Lamp
The red LED indicates the normal operation.
When the orange LED is activated, any one of the
safety devices may be functioning.

Please contact your service shop, if this condition is


detected.
Daily Checking
1.Check the power supply to ensure that it is proper.
2.Check for abnormal sounds and vibration.
3.Check the unit amperage.
4.Check the operating pressure.
Troubleshooting
Unit Does Not Start
1.Is the main switch ON?
2.Is the main fuse OK?
3.Is the cooling (Hot) and chilled water running?
4.Are the setting temperature calling for the cooling
operation?
Poor Cooling (Heating) Operation
1.Is there sufficient water supplied to the condenser
and the cooler?
2.Is the setting temperature correct?
3.Is the operating pressures normal?
Maintenance
1.Replace the oil, if it has been deteriorated
2.Clean the unit with a cleaner.
3.Clean the condenser and the water cooler . (It is
recommended that a specialist will be contacted for
this type of work.)

Remote/Local Changeover
Switch is Rear Side.

o
p
q
r
s
t
u
v

Operation Switch

Oil Sight Glass

Check valve

Power Wiring Supply

Electrical Box

Water Condenser

Water Cooler

Compressor

Name

w
x
y
z
{
|
}
~

Pressure Relief Valve

High Pressure Switch

Economizer (only for 80, 150, 240 HP)

Solenoid Valve (only for 80, 150, 240 HP)

Liquid Sight Glass

Drier

Liquid Line Stop Valve

Electronic Expansion valve

Name

STRUCTURE DRAWING OF HITACHI WATER COOLED-WATER CHILLER UNIT (Example: RCUE80WG2)

COMPONENTS OF CHILLER

4. COMPONENTS OF CHILLER

4.1. STRUCTURE DRAWING

HITACHI Water cooled Water Chiller (Example of 1 Compressor Chiller)

4/5

5/6

PREPARATION INITIAL CHECK

5. PREPARATION INITIAL CHECK


5.1. INITIAL CHECK
Required Materials
Measure and Architectural Information Regarding
Installation Location
Installation Location
Confirm that the final installation location is provided
with convenient piping and wiring work. Strong water
runoff should be avoided.
Installation Space
Check for obstacles which hamper maintenance work in
the space specified in Fig.1.
Foundation
Check to ensure that the foundation is flat, level and
sufficiently strong, taking into account the maximum
foundation gradient (Fig. 2) and the unit weight balance.
Confirm elevation provision for the unit on a solid base
with an iron frame or concrete curbs shown in chap. 5.4.

In order to obtain proper clearance beneath the unit for


on-the-ground installation, where foundation bolts
should be sunk into concrete.
Unit
Check to ensure that the unit has been transported
without damage. File a damage claim with the
transportation companies if mishandling due to
transportation company negligence is suspected.
Transportation
Secure the route to the final installation location by
confirming the dimensions, (Refer to the Unit General
Data in Catalogue).

5.2. PLACING THE UNIT

DANGER:

-Do not install the unit outdoors. If installed outdoor,

an electrical leakage will occur, since the unit has


not been designed for dew protection
-If leakage is detected, stop the unit and contact the
installer or a service shop. Do not use a naked fire
near the refrigerant gas. If a naked fire is utilised
near the refrigerant gas, refrigerant is turned into a
harmful phosgene compound.

Chiller
Unit

WARNING:

This unit is operated with refrigerant R407C, which


is non-flammable and non-poisonous. However,
refrigerant itself is heavier than the atmosphere so
that a floor is covered with refrigerant gas if
refrigerant is leaked. Therefore, keep good
ventilation to avoid choke during servicing.

 CAUTION:

Check to ensure that valves are correctly opened. If


not opened, serious damage will occur to the
compressor due to an abnormally high pressure.

Fig. 1

Maximum Foundation Gradient

The unit should be installed in an upright


position within the gradient shown in below Fig.

Tools And Instruments

Pincers, Wrenches, Facilities to Transport and


Place The Unit.
Transportation

Transportation the unit as close to the final


installation location as practical before
unpacking is accomplished. Provide adequate
facilities to place the unit on the foundation, with
sufficient consideration given to those
individuals performing the installation.
Unpacking

10 mm
5 mm

Follow the instructions marked on the packing.


Fig. 2

PREPARATION INITIAL CHECK

5/7

5.3. CENTRE OF GRAVITY


Centre of Gravity

Centre of Gravity

4
Control Panel

Model

40

50

60

80

Location

RCUE - WG2
100
120

150

180

200

240

Weight Distribution (kg)

1
2
3
4

225
175
215
165

230
175
225
170

245
190
250
190

275
410
215
415
285
415
225
415
Operating Weight

430
440
445
450

445
465
470
485

600
700
625
730

610
710
645
750

620
735
675
795

(kg)

780

800

875

1000

1765

1865

2655

2715

2825

1655

Location of Center of Gravity (mm)


Dimension
A
Dimension
B

538

531

522

509

521

516

509

511

508

501

490

490

490

482

815

813

803

1262

1263

1259

5/8

PREPARATION INITIAL CHECK

5.4. SERVICE SPACE AND FOUNDATION

RCUE 40, 50, 60, 80WG2

RCUE 100, 120, 150WG2

RCUE 180, 200, 240WG2

Detail Of Foundation

N
1
2
3
4
5
6

Name
4- 26 (Mounting Holes)
Bottom Frame
Vibration proof Rubber Mat (4 positions)
Vibration proof Rubber Mat (8 positions)
Vibration proof Rubber Mat (12 positions)
Vibration proof Rubber Mat (1 mat per position) OPTION

N
7
8
9
10
11
12

Name
Washer
Nut
Foundation bolt (M20)
Rubber Bush (OPTION)
Steel Plate (1 mm)
Concrete

PREPARATION INITIAL CHECK

5/9

5.5. TRANSPORTATION BY RIGGING


5.5.1. TRANSPORTATION BY RIGGING
Hook wire cables and apply field-supplied spreader bars
on the top of the unit (see below figure) to prevent the
unit from damage due to cable scratches. The unit
should remain in an upright position even during rigging.
The wire cable to rig the unit shall be three times
stronger than the unit weight. Check to ensure that the
rigging bolts are tightly fixed to the unit. The rigging
angle shall be greater than 60 as shown. The weight of
the unit is indicated on the unit label.

DANGER:

Do not stand below the unit when rigging.

 CAUTION:

Put clothes between wires and the unit to avoid


damages.

N
1
2
3
4
5

5.5.2. TRANSPORTATION BY ROLLER


When rolling the unit, put at least 6 equal-sized rollers
under the base frames. Each roller must carry both the
outer frames, and must be suited to balance the unit
(see the centre of gravity in page 5/7).

Name
60 (or more)
Electrical Box
4 x 30 Rigging Holes
Spreader Bar (Field supplied)
Lifting Bracket (Field supplied)

5.5.3. DECLINING THE UNIT DURING


TRANSPORTATION

WARNING:

Do not decline the unit more than an angle of 15


as shown in the figure during transportation. If
declined more than an angle of 15, the unit may
fall down.

Smaller than 15

6/10 INSTALLATION

6. INSTALLATION
6.1. ELECTRICAL WIRING
Tools and Instruments

One Set of Wiring tools and Electrical Tester


(Clamp Meter)
Schedule Check

WARNING:

- Confirm that the field-selected electrical

components (main power switch, fuses, wires,


conduit connections, wire terminals and others)
are properly selected according to the Electrical
Data in this Technical Catalogue, and ensure that
they comply with national and local codes.
- It is recommended that the main power switch be
locked in the OFF position, to prevent against
accidental supply of power during equipment
servicing.
- Check to ensure that an earthling wire is correctly
connected to the unit. This wire protects from an
electric shock. Utilisation of an earth leakage
breaker is necessary.

4.Firmly connect the wires with wire terminals to unit


screw terminals R, S, T and N according to below
figure.
5.Connect the wires between the power source and the
field-supplied magnetic switches.
6.Consider that the main power source will not be left
turned OFF, easily, because it is necessary to
energise the oil heater even during unit stoppage.

Main Power Wiring Procedures

Confirm that electrical power is not being


supplied to the installation location prior to any
electrical installation work.
1.Install the field-supplied main switch box (es) at a
properly selected location.
2.Install conduit connectors in the hole for the power
wiring.
3.Lead main power wires and the earthling wire
through the connector to the screw terminals for
main power and earthling in the magnetic switch box.
The neutral wires for 380/50 Hz and 415 V/50 Hz
power supply should also be led through the
connector.

N
1
2
3
4
5

Name
Main Power/Terminal Board (R,S,T,N)
Electrical Box
Main Power Switch
Main Power Wiring
Earth Wiring

Control Wiring
Connect the interlock wiring and control wiring between
the unit terminals and the magnetic switches for the
water pumps, according to the wiring label. The main
connection to terminal N is required.

INSTALLATION

N
1
2
3
4
5
6
7
8
9
10
11
12

Name
In case of remote control operation this wire
shall be removed.
R Phase
Neutral
Low Voltage / Remote Control
Run/Stop Signal
Alarm Signal
Alarm Lamp
Pump Interlock
Pump operation
Remote Control Switch (RSW-A) (OPTION)
2,3 cycles
3 cycles

N
13
14
15
16
17
18
19
20
21
22

6/11

Name
2 nd. Setting Temperature
External Thermostat Operation
Operation Mode (OPTION)
Only used for:
-Diff. Water Pressure switch (OPTION)
-Flow Switch (OPTION)
Force Compressor
Load Operation
Free Cooling
Output signal (Only cycle N 1)
In case of individual indication without Remote
Control Switch
Customer wiring
Force compressor load
Setting of low voltage control

NOTE:
1.All the setting shall be performed before Power ON.
2.Remote / Local Change over Switch on Operation
Switch shall be set, to Remote.
3.Terminals 1 ~/21 are for AC220-240V,Terminals
A ~D  are for DC24V. Terminals E ~F  are
H-link (Low signal)

6/12 INSTALLATION
6.2. WATER PIPING
When piping connections are performed:
1. Connect all pipes as close as possible to the unit, so
that disconnection can be easily performed when
required.
2. Connect the condenser and water coolers in the
same unit to the same common water piping.
3. It is recommended for the piping of the chilled water
inlet and outlet that flexible joints be utilised, so that
vibration will not transmit.
4. Whenever permissible, sluice valves should be
utilized for water piping, in order to minimize flow
resistance and to mantain sufficient water flow.
5. Proper inspection should be performed to check for
leaking parts inside and outside the system, by
completely opening the condenser and chilled water
inlet and outlet valves to the condenser and water
cooler.Additionally, equip valves to the inlet and outlet
piping.Equip an air purge cock and a drain cock on
the water piping. The cock handle should be removed
so that the cock can not be opened under normal
circumstances. If this cock is opened during
operation, trouble will occur due to water blow-off.

6. Sufficiently perform insulation to keep the chilled


water piping cool and to prevent sweating of the
piping.
7. Under the condition where the ambient temperature
is low in winter, there is a case where equipment and
piping will become damaged during the shutdown
periods at night, because the water in the pump or
piping will be frozen. To prevent freezing of the water,
it is effective to operate the pumps even during
shutdown period.
HITACHI Chiller has the pump ON/OFF operation
control (see Wiring Diagram) water from piping.
Additionally, in a case where measures such as water
draining are difficult, utlize antifreeze mixture of
ethylene glycol type or propylenen glycol type.
8. The common water pipes (Inlet/Outlet of condenser
and cooler, field supplied, should be connected to
condenser and cooler directly.

 CAUTION:

-Never use an antifreeze mixture of the salt type,

because it possesses strong corrosion


characteristics, and water equipment will be
damaged
-This product is equipped with plate type heat
exchangers. In the plate heat exchanger, water
flows through a narrow space between the plates.
Therefore, there is a possibility that freezing may
occur if foreign particles or dusts are clogged. In
order to avoid this clogging, provide a. 20 mesh
water strainer at the inlet of condenser and chilled
water piping near the product. A 20 mesh water
strainer is available as an option.

Condensing (Hot) Water Outlet

Condensing (Hot) Water Inlet

Chiller

Cooled Water Inlet

Cooled Water Outlet

NOTE:
HITACHI chiller has the pump ON/OFF operation control (see wiring diagram)

N
1
2
3
4

Name
Pressure Gauge
Strainer
Flexible Joint
Valve

INSTALLATION

6/13

 CAUTION:

In case of connecting some units to the same


water piping, design the water piping so that the
water distribution to each unit is equal (refer to
figure below) Imbalance of water distribution may
cause a serious damage like a water freezing in
the heat-exchanger.

Chiller Unit

Water Pump

Heat Load
Side

6.3. MINIMUM INTERNAL SYSTEM WATER VOLUME


To ensure the cooling operation at least 5 minutes
without interruption, the internal chilled water volume in
the piping system should be greater than the minimum
volume as shown below.

MODEL RCUE WG2


Condenser Water
Flow Range

NOTE:
Minimum internal system water volume written below
is for standard ON/OFF differential, minimum internal
system water volume shall be increased by the
setting of differential
.

40

50

60

80

100

120

150

180

200

240

Max.

m /h

48.1

57.4

69.8

82.3

114.9

139.6

157.8

186.2

214.9

246.8

Min.

m3/h

14.3

17.1

20.7

24.7

38.0

41.4

47.4

56.0

64.0

74.2

Max.

3
m /h

38.6

45.9

55.8

66.6

91.9

111.4

127.8

150.8

172.3

199.9

0.42

0.51

0.61

0.73

1.01

1.23

1.41

1.66

1.89

2.20

Chilled Water Flow Range


Minimum Internal
System Water Volume

Internal Volume in Water Cooler

Liter

15.1

16.7

21.5

23.9

44.8

44.8

44.8

64.4

64.4

71.6

Internal Volume in Condenser

Liter

14.8

18.6

23.9

27.6

40.2

49.4

49.4

71.6

71.6

82.7

6.4. WATER CONTROL

 CAUTION:

When industrial water is applied for chilled water


and condenser water, industrial water rarely
causes deposits of scales or other foreign
substances on equipment. However, well water or
river water may in most cases contain suspended
solid matter, organic matter, and scales in great
quantities. Therefore, such water should be
subjected to filtration or softening treatment with
chemicals before application as chilled water.

It is also necessary to analyse the quality of water by


checking pH, electrical conductivity, ammonia ion
content, sulphur content, and others, and to utilise
industrial water only if problem is encountered through
these check.
The following is the recommended standard water
quality.

6/14 INSTALLATION

Item

Standard Quality
pH (25 C)
Electrical Conductivity (mS/m) (25C)
(2)
{S/cm} (25 C)
Chlorine Ion (mg CI/I)
2
Sulphur Acid Ion (mg SO4 /I)
The Amount of Acid Consumption (pH 4.8)
(mg CaCO3/I)
Total Hardness (mg CaCO3 /I)
Calcium Hardness (mg CaCO3 /I)
Silica L (mg SIO2 /I)
Reference Quality
Total Iron (mg Fe/I)
Total Cupper (mg Cu/I)
Sulphur Ion (mg S2/I)
Ammonium Ion (mg NH4+/I)
Remaining Chlorine (mg CI/I)
Floating Carbonic Acid (mg CO2/I)
Index of Stability

Chilled Water System


Circulating
Water
Supply Water
(20 C Less
than)

Tendency (1)
Corrosion

Deposits
of Scales

6.8 ~ 8.0

6.8 ~ 8.0

Less than 40
Less than 400

Less than 30
Less than 300

Less than 50
Less than 50

Less than 50
Less than 50

Less than 50

Less than 50

Less than 70
Less than 50
Less than 30

Less than 70
Less than 50
Less than 30

Less than 1.0

Less than 0.3

Less than 1.0


Less than 0.1
It shall not be detected.
Less than 1.0
Less than 0.1
Less than 0.3
Less than 0.3
Less than 4.0
Less than 4.0
6.8 ~ 8.0
-

NOTE:
1. The mark in the table means the factor concerned with the tendency of corrosion or deposits of scales.
2. The value showed in {} are for reference only according to the former unit.

INSTALLATION

6.5. BMS CONNECTION

6.5.1. SYSTEM
BMS connection is available by using
HARC70-CE1(OP), optional BMS interface unit.
Upper Monitoring Device
Upper Monitoring Device

LonWorks
HARC70-CE1 OP

LonWorks

H-Link

HARC70-CE1

H-Link

Chiller 1

Chiller 1

Chiller 2

Chiller 3

Chiller 4

One interface HARC70-CE1 can connect up to 4


Chillers from a remote place using H-Link connection
(Hitachi communications protocol).
Protocol used by HARC70-CE1 (OP) is LonWorks. It can
connect only one Chiller.
Physical channel connection with interface is FTT-10

6.5.2. SIGNAL
Control Operation

State Monitoring

ON/OFF Chiller

All HARCS

Outlet Water Setting

All HARCS

ON/OFF

All HARCS

Chilled Water Outlet Setting

All HARCS

Chilled Water Outlet Temperature

All HARCS

Chilled Water Inlet Temperature.

All HARCS

Alarm Codes

All HARCS

Operation Status
Discharge Pressure 1,2

All HARCS
Only HARC OP

Suction Pressure 1,2

Only HARC OP

Discharge Temperature 1,2

Only HARC OP

Suction Temperature 1,2

Only HARC OP

Compressor Status (ON/OFF) 1,2

Only HARC OP

Outlet Water Temp. 1

Only HARC OP

Water Temp. In Evap. Backside 1

Only HARC OP

6/15

6/16 INSTALLATION

6.5.3. CAUTION ON USE HARC70-CE1 (OP)


Please use it correctly according to the following
"CAUTION ON USE.
As for the following:
HARC indicate HARC70-CE1 or
HARC70-CE1 OP
Monitoring Device indicate upper connecting
device for supervise , and Control Panel indicate
Control panel of Chiller unit.
SNVT Indicate Standard Network Variables Types
1.Install HARC in a grounded metal box.
2.Install a short circuit breaker in the power supply of
HARC.
3.The transmission line between HARC and Chiller unit
should be 0.75mm2 twisted-Pair cable. If it is not
used, then it cannot communicate between HARC and
Chiller unit, and it does not work properly.
4.After an abnormal transmitting occurs between HARC
and Chiller unit, and Chiller unit stops, in the case of
operation starting by the hand operation, then once
turn off Chiller units power supply, and turn on the
power supply. If it isnt carried out, then Chiller unit
keeps the condition of transmission alarm.
5.After an abnormal transmitting occurs between HARC
and Chiller unit, and Chiller unit stops, in the case of
operation starting by Monitoring Device, then transmit
an operation order after you transmit a stop order
once. If it isnt carried out, it can't start.
6.After Chiller unit, under control by HARC, is stopped
by the control panel, and operation is done from the
Monitoring Device, then transmit an operation order
after you transmit a stop order once. If it isnt carried
out, it cant start.
7.Don't set the setting temperature to Chiller unit, under
control by HARC, by the control panel. If it is done, the
setting temperature is changed. And, as for the setting
temperature, which changed in this case, transmit to
Monitoring device.
8.After the setting temperature is changed by Monitoring
Device, in the case of turned off Chiller units power
supply, set the setting temperature by Monitoring
device again. If it isnt carried out, then the setting
temperature becomes to the temperature by setting
control panel.
9.If power failure occurs in Chiller unit, under control by
HARC, it may not revert to the condition before the
power failure. Try to detect that the operation
condition of Chiller unit changed, by the Monitoring
Device. If Chiller unit stopped due to the power failure,
then transmit an operation order from the Monitoring
Device after the power supply restoration. And,
transmit the setting temperature, mode from the
Monitoring device. If it isnt carried out, and then
Chiller unit is stopping, and the setting temperature,
mode is the initialisation value by Chiller unit.
10.When SNVT, which is transmitted from HARC, is
used by other control device, premise that there is
two minutes delay between the transmitting SNVT
and the movement Chiller unit . If it isnt premised,
then a problem may occurs in the control system.

11.Don't interrupt the power supply of HARC when you


use SCPT in HARC. Even if it exceeds
MaxSendTime, when SNVT is not transmitted from
HARC, and SNVT is transmitted below with the
setting value of MinSendTime, then transmit SCPT
again . If it isnt carried out, SCPT value continues
maintaining 0.
12.If the setting of control panel change Remote to
Locally, and set Remote again, then set the setting
temperature and mode from the Monitoring Device
again. If it does not set, then the setting temperature
and mode continue maintaining the initialisation value
by Chiller unit.
13.When the abnormal transmitting occurs between the
Monitoring Device and HARC, then the condition of
the Monitoring Device may not correspond with the
condition of HARC. Set MaxSendTime and try that
the condition of the Monitoring Device corresponds
with the condition of HARC in the interval of
MaxSendTime .
14.It can't be used with the except for stop signal of
input terminal of Chiller unit .

6.5.4. DIMENSIONAL DRAWING AND


SPECIFICATIONS OF HITACHI GATEWAY
(MODEL HARC70-CE1/HARC70-CE1 0P)
Structural Drawing

Terminal Cover
After Open

Down

After Open
ID number of NEURON CHIP
On Rear Side of Cover

Mounting Dimensions
Mounting by Screw

Mounting on DIN Rail

Center Line of DIN Rail

INSTALLATION

System Wiring

Gateway

Chiller Unit
n1

Description

Wire Size

Power Supply
Power Wire AC 220/240V
(Field Supplied)

2mm shielded

Connection Wiring Between Chiller Signal Wiring DC 5V


(Field Supplied)

0.75mm twisted-pair cable


Max. length 1000m

Ground Earth Wire


(Field Supplied)

Connection Wire Between LonWorks Signal Wire DC 5V


(Field Supplied)

Marking of Terminals

Mark
POW

Indication
Red: Power Supply (AC220/240V)
Green: Lighted During
Transmission Between LONWORKS
Yellow: Lighted During
Transmission Between Chiller

IRP
PAC

Wiring Procedures

Power Line

Section

1220-240V Power
Source HARC70-CE1(OP)

Wiring Method

Remark

AC / AC / E

AC / AC / E

Earthing Wire

Control Circuit

LON / H-LINK

Upper System HARC70-CE1(OP)

Non-polar

LON / H-LINK

HARC70-CE1(OP) Water Chillers

Non-polar

6/17

6/18 INSTALLATION
Network Variables and Setting (HARC70-CE1)
Chiller
Number

Water
Cooled

Condenser
less

Air
Cooled

Air
Heat
Pump

SVNT
Number

Name

Type

LONMARK
SNVT No

Description

Contents

nv0

nviChillerEnable_0

SNVT_switch

95

On/Off Order

Byte 1: Value 0 (Fixed)


Byte 2: State 0/1 = STOP/RUN

nv1

nviCoolSetpt_0

SNVT_temp_p

105

Cool Water Temperature


Setting

2 Bytes: -2000 ~ 2500 = -20 ~ 25 C

nv2

nviMode_0

SNVT_hvac_mode

108

Operation Mode Setting

nv3

nviHeatSetpt_0

SNVT_temp_p

105

Hot Water Temperature Setting

nv4

nvoOnOff_0

SNVT_switch

95

On/Off state

nv5

nvoActiveSetpt_0

105

105

Temperature Setting
Operation Capacity (Not used
for continous capacity)
Chilled outlet temperature

1 byte:
1 = HVAC_HEAT (Heating)
3 = HVAC_COOL (Cooling)
2 bytes: 3000 ~ 6000 = 30 ~ 60 C
Byte 1: Value 0 (Fixed)
Byte 2: State 0/1 = STOP/RUN
2 Bytes: -2000 ~ 6000 = -20 ~ 60 C

nv6

nvoActualCapa_0

nv7

nvoLvgCHWTemp_0

nv8

nvoEntCHWTemp_0

SNVT_temp_p

105

Chilled inlet temperature

nv9

nvoAlarmDescr_0

SNVT_str_asc

36

Alarm code

nv10

nvoChillerStat_0

SNVT_chlr_status

127

Chiller Status

nv11

untest_0

nv12

untest_1

nv13

untest_2

SNVT_press (Not
Available)

30

NOT USED

NOT USED

nv14

untest_3

nv15

nviChlrEnable_1

SNVT_switch

95

nv16

nviCoolSetpt_1

SNVT_temp_p

105

nv17

nviMode_1

SNVT_hvac_mode

108

On/Off Order
Cool Water Temperature
Setting
Operation Mode Setting

Same than nv0

Same than nv2


Same than nv3

Same than nv1

nv18

nviHeatSetpt_1

SNVT_temp_p

105

Hot Water Temperature Setting

nv19

nvoOnOff_1

SNVT_switch

95

On/Off state

Same than nv4

nv20

nvoActiveSetpt_1

105

Same than nv5

105

Temperature Setting
Operation Capacity (Not used
for continous capacity)
Chilled outlet temperature

Same than nv7


Same than nv8

nv21

nvoActualCapa_1

nv22

nvoLvgCHWTemp_1

SNVT_temp_p
SNVT_lev_percent
(Not Available)
SNVT_temp_p

nv23

nvoEntCHWTemp_1

SNVT_temp_p

105

Chilled inlet temperature

nv24

nvoAlarmDescr_1

SNVT_str_asc

36

Alarm code

Same than nv9

nv25

nvoChillerStat_1

SNVT_chlr_status

127

Chiller Status

Same than nv10

nv26

untest_4

nv27

untest_5

nv28

untest_6

SNVT_press (Not
Available)

30

NOT USED

NOT USED

nv29

untest_7

nv30

nviChlrEnable_2

SNVT_switch

95

nv31

nviCoolSetpt_2

SNVT_temp_p

105

nv32

nviMode_2

SNVT_hvac_mode

108

On/Off Order
Cool Water Temperature
Setting
Operation Mode Setting

Same than nv0

Same than nv2


Same than nv3

81

NOT USED

Same than nv1

nv33

nviHeatSetpt_2

SNVT_temp_p

105

Hot Water Temperature Setting

nv34

nvoOnOff_2

SNVT_switch

95

On/Off state

Same than nv4

nv35

nvoActiveSetpt_2

105

Same than nv5

105

Temperature Setting
Operation Capacity (Not used
for continous capacity)
Chilled outlet temperature

Same than nv7


Same than nv8

nv36

nvoActualCapa_2

nv37

nvoLvgCHWTemp_2

SNVT_temp_p
SNVT_lev_percent
(Not Available)
SNVT_temp_p

nv38

nvoEntCHWTemp_2

SNVT_temp_p

105

Chilled inlet temperature

nv39

nvoAlarmDescr_2

SNVT_str_asc

36

Alarm code

Same than nv9

nv40

nvoChillerStat_2

SNVT_chlr_status

127

Chiller Status

Same than nv10

nv41

untest_8

SNVT_press (Not
Available)

nv42

untest_9

30

NOT USED

NOT USED

nv43

untest_10

30

nv44

untest_11

30

nv45

nviChlrEnable_3

SNVT_switch

95

nv46

nviCoolSetpt_3

SNVT_temp_p

105

nv47

nviMode_3

SNVT_hvac_mode

108

On/Off Order
Cool Water Temperature
Setting
Operation Mode Setting

Same than nv0

Same than nv2


Same than nv3

81

Provide an interval of
5 seconds of more
between each setting

Those values are


updated each 60
seconds.
When setting points
are changed from
NOT USED
HARC change to
2 Bytes: -2000 ~ 6000 = -20 ~ 60 C
related point is
detected not waiting
60 seconds.
If no water chiller is
2 Bytes: -2000 ~ 6000 = -20 ~ 60 C
connected these
values are set to 0
31 Bytes: 4 first bytes alarm description as shown in chiller.
5th byte always 0. Others undefined
3 bytes:
Byte 1: Chiller Run Mode
0: Chlr_Off (OFF Mode) 2:Chlr_Run (Run Mode)
Byte 2: Chiller Operation Mode
1: HVAC_HEAT (Heating) 3:HVAC_COOL (Cooling)
A: HVAC_FREE_COOL (Cooling Thermostat Off)
Byte 3: Chlr State
bit 0: 0/1 (no alarm / alarm)
bit 1: 0/1 (run not available / run available)
bit 2: 0/1 (central / local)
bits 3 ~ 7: Not used

SNVT_temp_p
SNVT_lev_percent
(Not Available)
SNVT_temp_p

81

Remarks

NOT USED

Not used

Provide an interval of
5 seconds of more
between each setting
Those values are
updated each 60
seconds.
When setting points
are changed from
HARC change to
related point is
detected not waiting
60 seconds.
If no water chiller is
connected these
values are set to 0

Not used

Provide an interval of
5 seconds of more
between each setting
Those values are
updated each 60
seconds.
When setting points
are changed from
HARC change to
related point is
detected not waiting
60 seconds.
If no water chiller is
connected these
values are set to 0

30

Same than nv1

nv48

nviHeatSetpt_3

SNVT_temp_p

105

Hot Water Temperature Setting

nv49

nvoOnOff_3

SNVT_switch

95

On/Off state

Same than nv4

nv50

nvoActiveSetpt_3

105

Same than nv5

105

Temperature Setting
Operation Capacity (Not used
for continous capacity)
Chilled outlet temperature

Same than nv7


Same than nv8

nv51

nvoActualCapa_3

nv52

nvoLvgCHWTemp_3

SNVT_temp_p
SNVT_lev_percent
(Not Available)
SNVT_temp_p

nv53

nvoEntCHWTemp_3

SNVT_temp_p

105

Chilled inlet temperature

nv54

nvoAlarmDescr_3

SNVT_str_asc

36

Alarm code

Same than nv9

nv55

nvoChillerStat_3

SNVT_chlr_status

127

Chiller Status

Same than nv10

nv56

untest_12

nv57

untest_13

nv58

untest_14

NOT USED

NOT USED

nv59

untest_15

nv60

nciMaxSendTime

nv61

nciMinSendTime

81

NOT USED

Not used

Provide an interval of
5 seconds of more
between each setting
Those values are
updated each 60
seconds.
When setting points
are changed from
HARC change to
related point is
detected not waiting
60 seconds.
If no water chiller is
connected these
values are set to 0

30
SNVT_press (Not
Available)

30
30
30

NOT USED

INSTALLATION

6/19

Network Variables and Setting (HARC70-CE1 OP)


Water Condenser
Air
Air Heat
Cooled
less
Cooled Pump

SVNT
Number

Name

Type

LONMARK
SNVT No

Description

Contents

nv0

nviChillerEnable_0

SNVT_switch

95

On/Off Order

Byte 1: Value 0 (Fixed)


Byte 2: State 0/1 = STOP/RUN

nv1

nviCoolSetpt

SNVT_temp_p

105

Cool Water Temperature


Setting

2 Bytes: -2000 ~ 2500 = -20 ~ 25 C

nv2

nviMode

SNVT_hvac_mode

108

Operation Mode Setting

1 byte:
1 = HVAC_HEAT (Heating)
3 = HVAC_COOL (Cooling)
2 bytes: 3000 ~ 6000 = 30 ~ 60 C
Byte 1: Value 0 (Fixed)
Byte 2: State 0/1 = STOP/RUN
2 Bytes: -2000 ~ 6000 = -20 ~ 60 C

nv3

nviHeatSetpt

SNVT_temp_p

105

Hot Water Temperature Setting

nv4

nvoOnOff

SNVT_switch

95

On/Off state

nv5

nvoActiveSetpt

105

nv6

nvoActualCapa

nv7

nvoLvgCHWTemp

SNVT_temp_p
SNVT_lev_percent
(Not Available)
SNVT_temp_p

105

Temperature Setting
Operation Capacity (Not used
for continous capacity)
Chilled outlet temperature

nv8

nvoEntCHWTemp

SNVT_temp_p

105

Chilled inlet temperature

nv9

nvoAlarmDescr

SNVT_str_asc

36

Alarm code

nv10

nvoChillerStat

SNVT_chlr_status

127

Chiller Status

n11

nvoDpress1

SNVT_press

30

Discharge Pressure 1

n12

nvoDpress1

SNVT_press

30

Discharge Pressure 2

2 Bytes:0~30000 = 0~3,000 kPa

n13

nvoDpress1

SNVT_press

30

Discharge Pressure 3

2 Bytes:0~30000 = 0~3,000 kPa

81

NOT USED

2 Bytes: -2000 ~ 6000 = -20 ~ 60 C


31 Bytes: 4 first bytes alarm description
as shown in chiller. 5th byte always 0.
Others undefined
3 bytes:
Byte 1: Chiller Run Mode
0: Chlr_Off (OFF Mode) 2:Chlr_Run (Run
Mode)
Byte 2: Chiller Operation Mode
1: HVAC_HEAT (Heating)
3:HVAC_COOL (Cooling)
A: HVAC_FREE_COOL (Cooling
Thermostat Off)
Byte 3: Chlr State
bit 0: 0/1 (no alarm / alarm)
bit 1: 0/1 (run not available / run
available)
bit 2: 0/1 (central / local)
bits 3 ~ 7: Not used
2 Bytes:0~30000 = 0~3,000 kPa

n14

nvoDpress1

SNVT_press

30

Discharge Pressure 4

2 Bytes:0~30000 = 0~3,000 kPa

n15

nvoDpress1

SNVT_press

30

Discharge Pressure 5

2 Bytes:0~30000 = 0~3,000 kPa

n16

nvoDpress1

SNVT_press

30

Discharge Pressure 6

2 Bytes:0~30000 = 0~3,000 kPa

n17

nvoSpress1

SNVT_press

30

Suction Pressure 1

2 Bytes:0~30000 = 0~3,000 kPa

n18

nvoSpress2

SNVT_press

30

Suction Pressure 2

2 Bytes:0~30000 = 0~3,000 kPa

n19

nvoSpress3

SNVT_press

30

Suction Pressure 3

2 Bytes:0~30000 = 0~3,000 kPa

n20

nvoSpress4

SNVT_press

30

Suction Pressure 4

2 Bytes:0~30000 = 0~3,000 kPa

n21

nvoSpress5

SNVT_press

30

Suction Pressure 5

2 Bytes:0~30000 = 0~3,000 kPa

n22

nvoSpress6

SNVT_press

30

Suction Pressure 6

2 Bytes:0~30000 = 0~3,000 kPa

n23

nvoDtemp1

SNVT_temp_p

105

Discharge Temp 1

2 Bytes: -12700 ~12700 = -127 ~ 127 C

n24

nvoDtemp2

SNVT_temp_p

105

Discharge Temp 2

2 Bytes: -12700 ~12700 = -127 ~ 127 C

n25

nvoDtemp3

SNVT_temp_p

105

Discharge Temp 3

2 Bytes: -12700 ~12700 = -127 ~ 127 C

n26

nvoDtemp4

SNVT_temp_p

105

Discharge Temp 4

2 Bytes: -12700 ~12700 = -127 ~ 127 C

n27

nvoDtemp5

SNVT_temp_p

105

Discharge Temp 5

2 Bytes: -12700 ~12700 = -127 ~ 127 C

n28

nvoDtemp6

SNVT_temp_p

105

Discharge Temp 6

2 Bytes: -12700 ~12700 = -127 ~ 127 C

n29

nvoSTemp1

SNVT_temp_p

105

Suction Temp 1

2 Bytes: -12700 ~12700 = -127 ~ 127 C

n30

nvoSTemp2

SNVT_temp_p

105

Suction Temp 2

2 Bytes: -12700 ~12700 = -127 ~ 127 C

n31

nvoSTemp3

SNVT_temp_p

105

Suction Temp 3

2 Bytes: -12700 ~12700 = -127 ~ 127 C

n32

nvoSTemp4

SNVT_temp_p

105

Suction Temp 4

2 Bytes: -12700 ~12700 = -127 ~ 127 C

n33

nvoSTemp5

SNVT_temp_p

105

Suction Temp 5

2 Bytes: -12700 ~12700 = -127 ~ 127 C

n34

nvoSTemp6

SNVT_temp_p

105

Suction Temp 6

2 Bytes: -12700 ~12700 = -127 ~ 127 C

n35

nvoODtemp

SNVT_temp_p

105

Outdoor Temperature

2 Bytes: -12700 ~12700 = -127 ~ 127 C

n36

nvoCompOnOff1

SNVT_state x 16

83

Compressor Information

32 Bytes: Byte 1: b0: 0/1 = STOP/RUN

n37

nvoCompOnOff2

SNVT_state x 16

83

Compressor Information

32 Bytes: Byte 1: b0: 0/1 = STOP/RUN

n38

nvoCompOnOff3

SNVT_state x 16

83

Compressor Information

32 Bytes: Byte 1: b0: 0/1 = STOP/RUN

n39

nvoCompOnOff4

SNVT_state x 16

83

Compressor Information

32 Bytes: Byte 1: b0: 0/1 = STOP/RUN

n40

nvoCompOnOff5

SNVT_state x 16

83

Compressor Information

32 Bytes: Byte 1: b0: 0/1 = STOP/RUN

n41

n42

n43

n44

n45

n46

n47

n48

nvoCompOnOff6
nvoLvgCHWTemp
1
nvoLvgCHWTemp
2
nvoLvgCHWTemp
3
nvoLvgCHWTemp
4
nvoLvgCHWTemp
5
nvoLvgCHWTemp
6
unused 1

n49

Provide an interval of 5
seconds of more between
each setting

2 Bytes: -2000 ~ 6000 = -20 ~ 60 C

Remarks

SNVT_state x 16

83

Compressor Information

32 Bytes: Byte 1: b0: 0/1 = STOP/RUN

SNVT_temp_p

105

Outlet Water Temp 1

2 Bytes: -12700 ~12700 = -127 ~ 127 C

SNVT_temp_p

105

Outlet Water Temp 2

2 Bytes: -12700 ~12700 = -127 ~ 127 C

SNVT_temp_p

105

Outlet Water Temp 3

2 Bytes: -12700 ~12700 = -127 ~ 127 C

SNVT_temp_p

105

SNVT_temp_p

105

SNVT_temp_p

105

SNVT_temp_p

unused 2

n50

Those values are updated


each 60 seconds.
When setting points are
changed from HARC change
to related point is detected
not waiting 60 seconds.
If no water chiller is
connected these values are
set to 0

105

Water Temp in Cooler BackSide


1
Water Temp in Cooler BackSide
2
Water Temp in Cooler BackSide
3
NOT USED

NOT USED

NOT USED

SNVT_temp_p

105

NOT USED

NOT USED

NOT USED

unused 3

SNVT_temp_p

105

NOT USED

NOT USED

NOT USED

n51

unused 4

SNVT_temp_p

105

NOT USED

NOT USED

NOT USED

n52

unused 5

SNVT_temp_p

105

NOT USED

NOT USED

NOT USED

n53

unused 6

SNVT_temp_p

105

NOT USED

NOT USED

NOT USED

n54

unused 7

SNVT_temp_p

105

NOT USED

NOT USED

NOT USED

n55

unused 8

SNVT_temp_p

105

NOT USED

NOT USED

NOT USED

n56

unused 9

SNVT_temp_p

105

NOT USED

NOT USED

NOT USED

nv57

nciMaxSendTime

nv58

nciMinSendTime

2 Bytes: -12700 ~12700 = -127 ~ 127 C


2 Bytes: -12700 ~12700 = -127 ~ 127 C
2 Bytes: -12700 ~12700 = -127 ~ 127 C

NOTE:
Set and use the variables in accordance with the above tables. (The variables based on "Chiller Part of LonMarkFunction
Profile", however, some function and setting range have limitation)

6/20 INSTALLATION
Space Requirements

Specifications
Item

NOTE:
1.Before operating this gateway, initial settings by a
system integrator for the local LonWorks system
are necessary.
2.This gateway is designed to be connected with
LonWorks network, and will not function by itself
when it is not connected.
3.The power lines and the signal lines shall be
separated with a minimum distance of 15cm.
4.It is necessary to set and adjust the Chillers and
gateway before operating the system.
5."LonWork" "LonMark" are trademarks of Echelon
Corporation registered in the USA and other
countries.

Specifications

Connection
Capacity
Power Supply
Power
Consumption
Ambient Condition
Temperature
Relative Humidity
Net weight
Colour
Material of Box
Mounting Method
Mounting Location
Accessories
Transceiver

Warranty

Maximum 4H-Link PCBs of Hitachi


Chiller
AC 1-PH, 220~240V10% 50/60Hz
Maximum 10W
0-45C
10-80% (with condition of no
condensation)
0.6kg
Grey (Munsell 5Y7/1 or similar)
ABS resin molding material
Wall Mount (By 2 x M4 Screws), or on
DIN Rail (35mm)
In Weather and Dust-Proofed Control
Panel
Core x 1, Capacitor x 1
Using FTT-10A
No warranty shall be applied for the
control and operation of the upper
"LonWorks" side.
Hitachi's liability shall cover only Hitachi
Chillers, this gateway, and accessibility
by "LonWorks"

Transmitting Setting (On Chiller Control PCB)


Operation
Before shipment, No. 1 pin of DSW10 is set at
ON side
In case that Chiller Unit quantity in the same HLink is 2 or more, set No. 1 pin of DSW10 at the
OFF side from 2nd Unit. If only one Chiller Unit
is used, no setting is required.
In case of applying high voltage to the terminal
TB1 (E,F), the fuse on the PCB is cut.
In such a case, first connect the wiring to TB1
(E,F) and then turn ON DSW-2

DSW
ON
OFF

ON
OFF

ON
OFF

INSTALLATION

6/21

6.6. CSC-5S
CSC-5S is a remote controller for Hitachi Water Chillers

6.6.1. SYSTEM
CSC-5S allows the individual control of a Chiller Unit as well as it allows a centralized and grouped controls of a maximum
number of 8 chillers.
8 Chillers (Maximum)
CSC-5S

6.6.2. SIGNAL
Indication code

Indication Content

Unit

ON/OFF unit operation


Setting Temperature COOL

Setting Temperature HEAT

Remark

Control Data

C1Pd ~ C2Pd
C1Ps ~ C2Ps

Operation Mode
Discharge Pressure
Suction Pressure

C1td ~ C2td

Discharge Gas Temperature

C1ts ~ C2ts

Suction Gas Temperature

C1tr ~ C2tr

Liquid Refrigerant Temperature

CEL

Inlet Water Temperature

CoL

Outlet Water Temperature

CcoL

Individual Water Piping Outlet Temperature

tSC

Setting Temperature of Chilled Water

tSH

Setting Temperature of Hot Water

tSCd

Setting Analog Temperature of Chilled Water

Not available

tSHd

Setting Analog Temperature of Hot Water

Not available

dF

Differential Setting

tA

Ambient Temperature (Not available)

Crno
CvEr
rno

ROM No. of Chiller Unit


Version No. of Chiller Unit
ROM No. of Controller (CSC-5S)

MPa
MPa

Control
Monitoring

Indicate Max. 6
Refrigerant Circuit
Data

The display contents


depend on chiller
unit.

Monitoring Data

6/22 INSTALLATION
6.6.3. CAUTION ON USE OF CSC-5S
Follow strictly instructions of CSC-5S Installation Manual. This controls requires power supply ~1 220-240 V.

6.6.4. DIMENSIONAL DRAWING AND SPECIFICATIONS OF CSC-5S


Structural Drawing

Mounting Dimensions

System Wiring
Max. 8 Chiller Units

Chiller Unit

Chiller Unit

Power Supply
To TB2 of other Controller

Twist Pair Cable 1P-0.75mm2

INSTALLATION

CSC-5S LAYOUT

SPACE REQUIREMENTS

More than 50 mm

Do not run the power line and the control line


through the same conduit tube.

PowerLine
Power Supply Part
Screw
(x2)

Control
Line
Switch Box with Cover
(Field-Supplied)

TRANSMITTING SETTING (ON CHILLER CONTROL PCB)


Operation

DSW

Before shipment, No. 1 pin of DSW10 is set at ON side

ON
OFF

In case that Chiller Unit quantity in the same H-Link is 2 or more, set No. 1 pin of
DSW10 at the OFF side from 2nd Unit. If only one Chiller Unit is used, no setting is
required.

ON
OFF

In case of applying high voltage to the terminal TB1 (E,F), the fuse on the PCB is cut.
In such a case, first connect the wiring to TB1 (E,F) and then turn ON DSW-2

ON
OFF

6/23

6/24 INSTALLATION

6.7. INSTALLATION FINAL CHECK


Inspect the installation work according to all documents and drawings. Table below shows the minimum check points.

6.7.1. INSTALLATION WORK CHECK LIST


1. Is the unit solidly mounted and levelled?
2. Is the installation location adequate?

4. Is the electrical wiring system adequate?


Wire Size

Tightened Connections

Indoor Installation

Switch Size

Operation Control Devices

Space for Maintenance Work

Fuse Size

Safety Devices

Noise and Vibration

Voltage and Hz

Interlock

Sunshine and other Heat Sources


Appearance
3. Is the water piping system adequate?
Tube Size

Water Drain

Length

Water Control

Flexible Joint

Air Purge

Insulation

Pressure Control

Strainer
Common Pipes (for 3 cycles)

5. Have the R, S and T phases of the water Chiller


correctly been connected to the R, S and T phases of
the main power source?
6. Are the stop valves for the condenser liquid line open?
7. Have the packing glands and the cap nuts for the stop
valves been tightened?
8. Is BMS connected correctly and operate as decided?

TEST RUNNING

7/25

7. TEST RUNNING
7.1. PREPARATION
Tools and instruments

High Pressure Compound Gauge. Low


Pressure Compound Gauge. Electrical Tester
and General Tools.

 CAUTION:

- Switch On the main power switch, and energise the

oil heater for 12 hours before start-up, to sufficiently


warm the oil.
- Check to ensure that valves are correctly opened. If
not opened, serious damage will occur to the
compressor due to an abnormally high pressure.
- Remove the foreign particles and substances from
the water piping without going through the water
coolers and condensers, and cleaning the water
strainer filter before test runningg. Check to ensure
that no foreign particle and substance exists in the
water piping

7.2. TEST RUNNING


Test running should be performed as follows, when the unit
is wired according to the HITACHI standard wiring label.
1. Switch ON the field-supplied pump and the cooling
tower, and the pump and cooling tower will be started
immediately. Check the condition and operation state of
these components
2. Fully open the liquid line stop valve.
3. Set the operation switch to "ON", and the compressor
will be started in a few minutes after this operation,
according to the following Operation Sequence Chart
(Refer to pages 36 to 38).

Test running should be accomplished as follows.

 CAUTION:

When the unit is wired according to the HITACHI


standard wiring shown on the wiring label. Switch ON
the main power switch, and energize the oil heater for
12 hours before start-up to sufficiently warm the oil.
Each rotation direction of two rotors in the compressor
is fixed so that a reversal phase protection device is
equipped.
However, the rotation direction should be checked with
a following method:
Confirm that phases R, S and T for the compressor is
correctly connected. The correct phase connection
can be checked by a phase sequence indicator. If
not, the compressor does not start due to activation of
the reversal phase protection device.

- Cut the main switch and interchange two of three

terminals, R, S and T on the main terminals at the field


connection side in the unit.
1. Operate the pump for chilled water and other
auxiliary equipment such as fan coil units and air
handling units.Check to ensure that the chilled water
flows sufficiently and that other auxiliary equipment
operate properly.
2. Set the switch at the desired temperature.
3. Depress the ON push button, the compressor will
be started.
4. After system operation becomes stabilized, check the
discharge and suction pressures by 7-segment on
control panel.
5. Check to ensure that the thermostat functions
properly.
6. Check to ensure that the control and protective
devices function properly.
7. Starting timer and unload-starting timer are set at five
(5), thirty (30) seconds, respectively, in accordance
with operation characteristics. Therefore, local
adjustment should be avoided.

NOTE:

- A loud sound occurs when this compressor is

stopped after the normal operation. However, this


sound indicates no abnormalities and stops within a
few seconds by the activation of the check valve.
This sound is due to the reverse rotation of the
screw rotors, resulting from the pressure difference
between the discharge and the suction pressure.
- Each compressor may show the different values of
running current due to individual capacity control for
each compressor. This is not abnormal.

8/26 CONTROLLER ADJUSTMENT

7.3. INSTRUCTIONS AFTER TEST RUNNING


When the test running is completed, please instruct
customers about operation and periodic maintenance
methods before leaving the unit, by using Installation,
Operation and Maintenance Manual. A special attention is
required to the following caution:

 CAUTION:

-Do not cut off the power source switch during the

operating season. When the power source switch is


cut off, the oil heater for screw compressor is not
energised, and the compressor might be damaged
due to oil foaming at starting.
-When the operation season starts after long
disconnection of the power source switch, please turn
on the power source switch 12 hours before starting
operation.

8. CONTROLLER ADJUSTMENT

LED

PUSH
BUTTON
SWITCH

7 SEGMENTS

SWITCH POSITION
ON
OFF

ON
OFF
ON
OFF

High Cut Check (Fan Stop for Checking)


(NOT AVAILABLE)

Chilled Water Temperature Setting


(STANDARD: "+07")

Defrosting Set by Ambient Temperature (Heat Pump)


(NOT AVAILABLE)

Continuous Capacity Control Setting


(STANDARD)

Compressor starting Delay Time


(STANDARD: 3 min)

Mode Set Switch A / H-LINK address


(DEPEND ON MODEL)

Manual Defrost (Heat Pump)


(NOT AVAILABLE)

Optional Function B
(STANDARD: ALL OFF)

Optional Function C
(STANDARD: ALL OFF)

Mode Set Switch B


Local/Remote Changeover Switch
(STANDARD: "Local")

Cool/Heat Changeover Switch


(STANDARD: "Cool", Heat is available only for Heat Pump
operation Option)

Current Limitation
(Not Available)

Neutral Zone Setting


(STANDARD: "3")

Hot Water Temperature Setting for Heat Pump


(STANDARD: "45", Available only for Heat Pump operation
option)

Optional Function A (Outernals signals, Self-Checking mode)


(STANDARD: ALL OFF)

Pump Operation (STANDARD: OFF)

CONTROLLER ADJUSTMENT

8/27

8.1. CONTROL SYSTEM


Electrical Operation Control advanced HITACHI Water
Chillers are as follows.

Capacity Control

Printed Circuit Board

All models are equipped with an unloading system for each


compressor, in order to adjust the cooling capacity and to
provide precise temperature control for the chilled water,
coupled with electronic thermostats.

A micro-processor, relays and electronic components are


mounted on the Printed Circuit Board. Increased reliability
is assured due to the elimination of mechanical parts and
wires. This board contains various function by applying
micro-processor as follows:

Control Panel
ON switch, OFF switch, Power Supply Lamp, Operation
Lamp, Alarm Lamp, Operation/Alarm Indicator for each
refrigerant cycle and check switch are mounted in the
Control Panel. The Control Panel is located at a position
where easy access is available. Operation/Alarm indicator
can display individual alarm codes such as High-Cut, LowCut etc. this function is very useful for detecting what alarm
has occurred. Check switches are for checking chilled
water temperature and alarm occurrence data. Chilled
water temperature setting switches, ON/OFF Differential
Setting Switches, Remote-Local Switch and so on are
located at the rear side of Control Panel, in order not to
access during operation.

Operation Hour-Meter
This hour-meter indicates the sum of the compressor
operation

Screw Compressor Cycling Protection Circuit.


The electronic timer of the screw compressor cycling
protection (ccp) connected in the compressor control circuit
delays the screw compressor restarting period for
approximately three (3) minutes for No.1 compressor, four
(4) minutes for No.2 compressor, five (5) minutes for No.3
compressor.
Electronic Thermostat Circuit.
The electronic thermostat senses chilled water outlet
temperature, and operate capacity control solenoid valves
of HITACHI screw compressor.
Screw Compressor Reversing Protection Circuit.
This circuit is composed of a reverse-phase protection
devices, preventing reverse operation of the screw
compressor, because the screw compressor definitely
cannot be operated in the wrong direction, due to the
misconnection of the main power phases.
Restart after Short Period Power-Failure.
In the case that a power failure shorter than 2 seconds
occurred, compressors can be restarted automatically
within 3 minutes after power supply.
If power failure longer than 2 seconds occurres,
compressor also can be restarted by selection switch
setting.
Power Supply
All models need only single power supply . Control circuit is
powered from main power circuit. For remote control, pump
interlock and pump operation, see the diagram of
"Customer Wiring".

8/28 CONTROLLER ADJUSTMENT


8.2. CONTROLLER ADJUSTMENT
Layout of control panel of printed circuit board is shown in
the Figure of the last page.
Setting functions are followings:

Continuos Capacity Control Setting


Switch=DSW5

Chilled Water Outlet Temperature Setting


Switch = RSW1 and RSW2

Temperature Band for Stop Setting Switch


= 1 degree is standard. The figure 1 and 2 of the DSW5
switch are already set at figure 1 = ON side, 2 = OFF side.
The locations at the figure 1 and 2 of the DSW5 mean as
follows.

= 7C for chilled water outlet temperature is


recommended. The RSW1 and RSW2 dials are already
set at 7 and 0.
Setting at the figures from 3 to 9 of the RSW2 dial
should not be permitted.

Hot Water Outlet Temperature Setting


Switch = RSW3 and RSW4 (Available only for Heat
Pump operation option) = 45C for hot water Outlet
temperature is recommended. The RSW3 and RSW4
dials are already set at 5 and 4.

Current limitation = RSW5, 6, 7

Figure
1
2
1
2
1
2
1
2
Location
ON ON ON OFF OFF ON OFF OFF
Band(degree)
0.5
1.0
1.5
2.0
Temperature Band for Restart Setting Switch
= 2 degree is standard. The figure 3 and 4 of the DSW5
switch are already set at figure 3 = ON side, 4 = OFF side.
The locations at the figure 3 and 4 of the DSW5 mean as
follows.
Figure
3
4
3
4
3
4
3
4
Location
ON ON ON OFF OFF ON OFF OFF
Band(degree)
1.0
2.0
3.0
4.0

= The RSW5, RSW6 and RSW7 should not be


permitted.

Neutral Zone Setting Switch = RSW8


= 2 degrees is standard. The RSW8 dial is already set at
3 = 2 degrees.
The figures at the RSW8 dial means as follows:
Figure
0 1 2 3 4 5 6 7 8 9
Band(degree) 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0
Continuous Capacity Control Setting Switch =

DSW5Definition of Special Terms.


Water
Temperature
Load Up 1 Mode

Load Up 2 Mode
9C

Water Outlet
Temperature
Set by
RSW8
Neutral Zone

Water Inlet
Temperature
Inlet Water Temp.
when system is
stopped with
Thermos Off mode

7C

Setting Temperature
Set by
DSW5,
1&2 pin

Load Down Mode


6C
Thermo Off
Standard
Setting

Figure
5
5
Location
ON OFF
Band(degree) 1.0 3.0
Output Signal Time for Load-up 1 Mode Setting Switch
= 12 seconds is standard. The figure 6 of the DSW5 switch
is already set at ON side.
The locations at the figure 6 of the DSW5 mean as follows.
Figure
6
6
Location
ON OFF
Time(second) 12 24

10C

Set by
DSW5,
5 pin

Differential Temperature of Load-up 2 Mode Setting Switch


= 1 degree is standard. The figure 5 of the DSW5 switch is
already set at ON side.
The locations at the figure 5 of the DSW5 mean as follows.

Set by
DSW5,
3&4 pin

Output Signal Time for Load-up 2 and Load-down Mode


Setting Switch
= 2 seconds is standard. The figure 7 and 8 of the DSW5
switch are already set at figure 7 = ON side,
8 = ON side.
The locations at the figure 7 and 8 of the DSW5 means as
follows.
Figure
7
8
7
8
7
8
7
8
Location
ON ON ON OFF OFF ON OFF OFF
Time(second)
2
4
6
8
Interval of Output Signal Time for Load-up 2 and Loaddown Mode Setting Switch.
=60 seconds is standard. The figure 9 and 10 of the DSW5
switch are already set at figure 9=ON side, 10=ON side.
The locations at the figure 9 and 10 o f the DSW5 mean as
follows.
Figure
9
10
9
10
9
10
9
10
Location
ON ON ON OFF OFF ON OFF OFF
Time(second)
60
90
120
30

CONTROLLER ADJUSTMENT

Setting of Compressor Cycling Protection


Start = DSW2
* Time Delay Starting for Compressor Setting Switch *
The compressor will be started after this setting time.
= 3 minutes is standard. The figure 1 and 2 of the DSW2
switch are already set at figure 1 = OFF side, 2 = OFF side.
The locations at the figure 1 and 2 of the DSW2 mean as
follows.
Figure
Location
Time(minute)

1
2
1
2
1
2
1
2
ON ON ON OFF OFF ON OFF OFF
0.5
6
10
3

Manual Set Switch A = DSW3


* Compressor Forcedly Stop Mode Setting Switch *
Switches "DSW3-1" is for No.1 compressor, "DSW3-2" for
No.2, and "DSW3-3" for No.3.
If necessary to stop any compressors, turn these switches
(DSW3-1, DSW3-2 and DSW3-3 to the OFF side, the
compressors corresponding to these switches are turned to
the OFF side will be stopped).
The figures of the DSW3 switch are initially set as follows
depend on the compressor quantity.
This switch is for servicing, therefore, all the compressors
shall be ON for normal operation.
Figure
Location
Model

1
2
3
ON
OFF OFF
1 Comp. System

Figure
Location
Model

1
2
3
ON
ON
ON
3 Comp. System

1
2
3
ON
ON
OFF
2 Comp. System

Setting at the figures from 4 to 10 of the DSW3 switch


should not be permitted (always at OFF side).
Note: The figures 2 and 3 of DSW3 which are Not
corresponding to the equipped compressor number are
always turned to the OFF side.

Manual Set Switch B = DSW4


The figure 2, 6 and 7 of the DSW4 switch must be turned to
the ON side.
Setting at the figures 1,3, 4, 5 and 8 of the DSW4 switch
should not be permitted (always at OFF side).

8/29

The figures 9 and 10 of DSW4 switch are for compressor


size setting as follows.
Figure
Location
Compressor

9
10
OFF ON
40 HP

9
10
ON OFF
50 HP

9
10
ON ON
60 HP

9
10
OFF OFF
80 HP

Selection Switch for Cooling/ Heating


Operation = SW8
The SW8 selection SW is used for selecting cooling or
heating operation. However, Standard model in this series
are for cooling only. So that Heating function is available
only for Heat Pump operation option.
Turn SW8 to the upper side for cooling operation or lower
side for heating operation.

Selection Switch for Local/ Remote Operation


= SW6
= Local operation is standard. So that the SW6 selection
switch is turned to the upper side.
If Remote operation is required, the SW6 selection switch
is turned to the upper side.

Selection Switch for Local/ Remote Pump


Operation = SW7
= The SW7 selection switch is turned to the lower ("OFF")
side as remote setting.
If local operation is required, the SW7 selection switch is
turned to the upper side.

Other Switches = SW5, DSW6, RSW9 and


DSW1
This control panel is equipped with other switches:
The SW5 selection switch for chilled water/brine water, so
that this switch must be turned to the upper side
(water). DSW6 and RSW9 for operation mode and
setting change of these switches are not available.
The figure 2 of DSW6 must be turned to the upper side.
It is recommended that the setting is not changed at site.
Also, the DSW1 switch is equipped with. This switch is
used for only checking, resulting in easy troubleshooting.

9/30 SELF-INSPECTION FUNCTIONS

9. SELF-INSPECTION FUNCTIONS
9.1. ALARM INDICATION
SEG1

Alarm Indication
If the unit is operated under abnormal conditions, an alarm
code(refer to the table below) is indicated and the "Alarm"
LED is lighted.
Function of 7-Segment Light Emitted Diode on Control
Panel is as shown in the table below.
Code
No.2
Cycle

No.1
Cycle

SEG2

 .  .

7 Segments on
Control Panel

Content

No.3
Cycle
Activation of High Pressure Switch
Activation of Low Pressure Control

Activation of Thermal Relay for Compressor or Malfunction of Auxiliary Relay Arn


Activation of Discharge Gas Thermistor
Activation of Compressor Internal Thermostat
Excess Low Temperature of Cooler Inlet Refrigerant
Activation of Suction Gas Thermistor
Phase Abnormally (Only for 3 cycle unit)
Failure of Water Outlet Thermistor (Only for 3 cycle unit)
Activation of Freeze Protection Control (Only for 3 Cycle Unit)
Failure of Cooler inlet Refrigerant Thermistor (Open / Short)
Failure of Discharge Gas Thermistor (Open / Short)
Failure of Thermistor set before Expansion Valve
Failure of Water Outlet Thermistor (Rear side of Water Cooler)
Failure of Suction Gas Thermistor (Open / Short)
Failure of Discharge Gas Pressure Sensor (Open / Short)
Failure of Suction Gas Pressure Sensor (Open / Short)
Failure of Hot Water Outlet Temperature Thermistor (Only for 3 Cycle Unit of Heat Pump
Operation Option)
Phase Abnormally (Only for 1 and 2 Cycle Unit)
Failure of Water Inlet Temperature Thermistor
Failure of Water Outlet Thermistor. (Only for 1 and 2 Cycle Unit)
Activation of Freeze Protection Control (Only for 1 and 2 Cycle Unit)
Failure of Hot Water Inlet Temperature Thermistor (Only for Heat Pump Operation Option)
Failure of Hot Water Outlet Temperature Thermistor (Only for 1 and 2 Cycle Unit of Heat
Pump Operation Option)
No Feedback Signal from Water Pump
Incorrect Operation
Error Communication between Expansion Valve PCB and Control PCB

Alarm of Excessively High Water Temperature


Alarm of Water Failure for Water Cooler (Differential Pressure Switch or Flow Switch
Option)
Alarm of Water Failure for Condenser (Differential Pressure Switch or Flow Switch Option)
Activation of Additional Protection Device
Error Communication between Chiller and Remote Controller (If CSC-5S is connected.)
Retry Operation (by Alarm Cx-9x or Cx-Lx, x: Cycle No.)

- : Flickering

SELF-INSPECTION FUNCTIONS

9/31

9.2. NORMAL INDICATION


If the unit is operated under a normal operation condition,
the operation code (refer to the table below) is indicated on
7-Segment LEDs of the control panel.

No.1
Cycle

Code
No.2
Cycle

Content

No.3
Cycle
Power Supply, After Stoppage
Cooling Operation

Heating Operation (Only for Heat Pump Operation Option)


Stoppage by Thermo-OFF or Retry by Alarm Cx-5x
Pump Operation, Warning of Pump Feedback
Initializing Electronic Expansion Valve

9.3. FUNCTION FOR INDICATION OF OPERATION CONDITION


Function for Indication of Operation Condition
The setting temperature, chilled water temperature sensed
at the thermistor, the setting differential temperature and
the last alarm code are digitally indicated on the control
panel.
The Alarm Code
Occurrence Data

Memory Data
Indication in alarm
(Latest Data only)

Normal Operation
Condition
"88" "Co" "oF"

o Press the check "" and "" switches


Checking
Indication

simultaneously for more than 3 sec.


It is changed to the normal mode by
pressing the "" and "" switches
simultaneously for more than 3 sec.
again.

p Press the check "" switch for more than

3 sec.
It is changed to the normal mode by
pressing the "" switch for more than 3
sec. again.

q Press the check "" switch for more than

Second Water
Temperature Setting

3 seconds at the time to display latest


alarm coad.

r Press the check "" switch for more than


3 seconds.

Note:Each indication mode shall be changed from the normal mode.

Indication Mode of Alarm Occurrence Data o


The content of abnormal stoppage including activation of
safety devices is memorised and indicated on the
control panel
Alarm Occurrence Data (Max.10 data)

2 3

In case of No. 1 cycle high


pressure alarm occurrence

 

2 3

 

In case of No. 2 cycle high


pressure alarm occurrence

It is changed to the normal mode by


pressing the "" switch for more than 3
sec. Again.

NOTE:
If an abnormal operation is occurred under this
indication mode, this indication mode is changed to
the alarm indication mode.

9/32 SELF-INSPECTION FUNCTIONS


Checking Indication q

Back to "CPU ROM numbre"

Alarm Code Occurred Last

(no alarm)

Discharge Pressure (MPa)

Discharge Pressure (MPa)

Discharge Pressure (MPa)

Suction Pressure (MPa)

Suction Pressure (MPa)

Suction Pressure (MPa)

Discharge Gas Temperature (Option) (C)

Discharge Gas Temperature (Option) (C)

Discharge Gas Temperature (Option) (C)

Suction Gas Temperature (C)

Suction Gas Temperature (C)

Suction Gas Temperature (C)

Evaporating Temperature (C)

Evaporating Temperature (C)

Evaporating Temperature (C)

Water Inlet Temperature (C)

 4 +

(N 1 Cycle $+ = 1.92 MPa)

 4 +

 4 +

 4 6

(N 1 Cycle $6 = 0.42 MPa)

 4 6

 4 6

 7 +

(N 1 Cycle 7+ = 82C)

 7 +

 7 +

 7 6

(N 1 Cycle 76 = -2C)

 7 6

 7 6

 7 5

(N 1 Cycle 75 = -2C)

 7 5

 7 5

  "

Average Water Outlet Temperature (C)

Water Outlet 1 Temperature (C)

Water Outlet 2 Temperature (C)

Water Outlet 3 Temperature (C)

Setting Water Outlet Temperature (C) (Cooling)

Setting Water Outlet Temperature (C) (Heating)

Second Setting Water Outlet Temperature (C) (Cooling)

Second Setting Water Outlet Temperature (C) (Heating)

 3 "

 3 "

 3 "

7 6 

7 6 

 

7 6  +

7 6  +


& $

 " +

2 &
Hold

 " +

Compressor Capacity Control (C)

Load up

Compressor Capacity Control (C)

 3 "

 " +

Compressor Capacity Control (C)

9/33

+ -

Setting Neutral Zone Temperature Difference (C)

SELF-INSPECTION FUNCTIONS

+ #
Load down


Thermo-off
Alarm Control Status



Control Status

Control Status

Discharge Pressure Control

Not available

Suction Pressure Control

Not available

Different Pressure Control

Load Down Control (Water


Outlet Temp.)

Freeze Protection Control

Not Available

Compressor Start Control

Discharge Temperature
Control

Discharge Temperature Retry

Liquid Bypass (Not Available)

Not available

Not Available

Control Status

ux

sw

 $ 

 3
Compressor start control

 $ 

 3

Suction pressure control activated

 4 

 3

Discharge pressure control activated

9/34 SELF-INSPECTION FUNCTIONS

Memory Data Indication in Alarm

Data is indicated same as Checking Indication.


In addition the checking data, below data is added.

Evaporating Temperature (C)

Water Outlet Temperature (Cooler Backside) (C)

Water Outlet Temperature (Cooler Backside) (C)

Water Outlet Temperature (Cooler Backside) (C)

Control status

Expansion Valve Pulse

Expansion Valve Pulse

Expansion Valve Pulse

 7 5

  3

  3

  3

 $ 

 3

 , 3

 #

 , 3

 

 , 3

SELF-INSPECTION FUNCTIONS

Second Water Temperature Setting

9/35

This temperature setting can provide another setting value for water temperature.
It can be changed by external signal
Second Water Temperature Setting Procedure
1)Press the check switch for more than 3 seconds.
Then, display shows the current setting value.

7   +

#
:

* This shows the setting value is 6C.


If press the check or in this mode, the display is changed to either Hot Water Temperature Setting or
Chilled Water Temperature Setting alternatively.

7   +

7  +
:

2)Press the check and switches simultaneously for more than 3 seconds.The mode is changed to setting mode.
Then, the setting value can be changed by pressing the check and switches.
However, the setting value shown on display, is not available in this moment.
Press


:

#
:

Press


:

3)Press the check and


switches simultaneously for more than 3 seconds. At the same time, the setting value
shown on display is memorized and available.

7   +

.
:

* The setting is changed to 9.5C.


* Hot water temperature setting change is performed by same procedure mention above.
When the wiring connection shown below, this second temperature setting is available.

Available

Not

Solenoid Valve

Time Schedule

SV11
SV12
SV13

OFF
OFF
OFF

OFF

OFF

MC1

Motor for
Compressor

OFF
OFF
OFF

ON
OFF
OFF
CLS
ON
OFF
OFF
ON

OFF
CLS
OFF
OFF
OFF
OFF

Main Power Switch


Chilled Water Pump
Condenser Water Pump
Operation Switch (ON/OFF)
Load Up
Neutral
Controller
Load Down
Safety Devices
N 1
Power Supply Lamp
Operation Lump
Alarm Lumpr
Oil Heater
CH1

Control Devices

Control Stage

9/36 SELF-INSPECTION FUNCTIONS

OFF
OFF
OFF

OFF

ON
ON
ON
CLS
ON
OFF
OFF
ON

3min.

ON
OFF
OFF

OFF

ON
ON
ON
ON
CLS
ON
ON
OFF
ON

15%

15%

30sec.

ON
ON
OFF
OFF
OFF
OFF
5sec.

ON
ON
ON
CLS
ON
ON
OFF
OFF
DLT
(ULD)

ON
ON
ON
CLS
ON
ON
OFF
OFF
STA
(ULD)

Starting Control
ON
ON
ON
O
CLS
ON
ON
OFF
OFF
DLT
(FLD)
CLS
ON
ON
OFF
OFF
DLT
(FLD)

ON
ON
ON
O

ON
ON
ON
O
CLS
ON
ON
OFF
OFF
DLT
(ULD)
15%99%
OFF
ON
OFF

ON
ON
ON
O
CLS
ON
ON
OFF
OFF
DLT
(ULD)
15%99%
OFF
OFF
OFF
OFF
ON
OFF

15%

ON
ON
ON
O
CLS
ON
ON
OFF
OFF
DLT
(ULD)

ON
OFF
OFF

OFF

ON
ON
ON
O
CLS
ON
ON
OFF
ON

ON
ON
ON
O
CLS
ON
ON
OFF
OFF
DLT
(ULD)
15%99%
OFF
OFF
OFF
OFF
OFF
OFF

OFF

ON
ON
ON
O
OPN
ON
ON
ON
ON

OFF
OFF
OFF

OFF

ON
ON
ON
OFF
CLS
ON
OFF
OFF
ON

Safety Devices

CLS: Close, OPN: Open, STA: Star, DLT: Delta


ULD: Unload, FLD: Full Load

Minimum 3min.

15%- 100% 100%


99%
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF

ON
ON
ON
O
CLS
ON
ON
OFF
OFF
DLT
(ULD)

Capacity Control

OFF
OFF
OFF

100%

ON
ON
ON
O
CLS
ON
ON
OFF
ON
DLT
(FLD)

OFF
OFF
OFF

OFF

ON
OFF
OFF
OFF
CLS
ON
OFF
OFF
ON

Shut Down

OFF
OFF
OFF

OFF

CLS
OFF
OFF
OFF
OFF

OFF
OFF
OFF
-

10/36
CONTROL SYSTEM

10.CONTROL SYSTEM
Standard Operating Sequence for RCUE 40WG2, RCUE 50WG2, RCUE 60WG2 and RCUE 80WG2

Time Schedule

Solenoid Valve

Motor for
Compressor

SV11
SV12
SV13
SV21
SV22
SV23

MC2

MC1

Main Power Switch


Chilled Water Pump
Condenser Water Pump
Operation Switch (ON/OFF)
Load Up
Controller
Neutral
Load Down
N 1
Safety Devices
N 2
Power Supply Lamp
Operation Lump
Alarm Lumpr
CH1
Oil Heater
CH2

Control Devices

Control Stage

OFF
OFF
OFF
OFF
OFF
OFF

OFF

OFF

OFF
CLS
CLS
OFF
OFF
OFF
OFF
OFF

OFF
OFF
OFF
OFF
OFF
OFF

OFF

OFF

ON
OFF
OFF
CLS
CLS
ON
OFF
OFF
ON
ON

OFF
OFF
OFF
OFF
OFF
OFF

OFF

OFF

ON
ON
ON
CLS
CLS
ON
OFF
OFF
ON
ON

ON
OFF
OFF
ON
OFF
OFF

OFF

15%

ON
ON
ON
CLS
CLS
ON
ON
ON
OFF
ON
DLT
(ULD)

ON
ON
ON
O
CLS
CLS
ON
ON
ON
OFF
OFF
DLT
(FLD)
ON
ON
ON
O
CLS
CLS
ON
ON
ON
OFF
OFF
DLT
(FLD)

15%100% 100%
99%
DLT
DLT
DLT
(ULD) (FLD) (FLD)
15%100% 100%
99%
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF

ON
ON
ON
O
CLS
CLS
ON
ON
ON
OFF
OFF
DLT
(ULD)
15%99%
DLT
(ULD)
15%99%
OFF
ON
OFF
OFF
ON
OFF

ON
ON
ON
O
CLS
CLS
ON
ON
ON
OFF
OFF
DLT
(ULD)

OFF
ON
OFF
OFF
ON
ON

15%

DLT
(ULD)

15%

ON
ON
ON
O
CLS
CLS
ON
ON
ON
OFF
OFF
DLT
(ULD)

ON
OFF
OFF
ON
OFF
OFF

OFF

0FF
15%99%
DLT
(ULD)
15%99%
OFF
OFF
OFF
OFF
OFF
OFF

ON
ON
ON
O
CLS
CLS
ON
ON
ON
OFF
OFF
DLT
(ULD)

DLT
(ULD)
15%99%
OFF
OFF
OFF
OFF
OFF
ON

OFF
OFF
OFF
OFF
OFF
OFF

OFF

OFF

ON
ON

ON
OFF
OFF

ON
ON
ON
O
OPN
OPN
ON
ON

ON
ON
ON
O
OPN
CLS
ON
ON

Safety Devices

CLS: Close, OPN: Open, STA: Star, DLT: Delta


ULD: Unload, FLD: Full Load

15%99%
DLT
(ULD)
15%99%
OFF
OFF
OFF
OFF
OFF
OFF

ON
ON
ON
O
CLS
CLS
ON
ON
ON
OFF
OFF
DLT
(ULD)

ON
ON
ON
O
CLS
CLS
ON
ON
ON
ON
ON

9/37

Capacity Control

The compressor which started finally will be started first.

ON
OFF
OFF
ON
OFF
OFF

15%

DLT
(ULD)

15%

ON
ON
ON
CLS
CLS
ON
ON
ON
OFF
OFF
DLT
(ULD)

30sec.

ON
OFF
OFF
ON
OFF
OFF
5sec.

15%

STA
(ULD)

ON
ON
ON
CLS
CLS
ON
ON
ON
OFF
OFF
STA
(ULD)
15%

Minimum 3min.

60sec.

ON
OFF
OFF
ON
OFF
OFF
5sec.

ON
OFF
OFF
ON
OFF
OFF

3min.

OFF

ON
ON
ON
CLS
CLS
ON
ON
ON
OFF
ON
STA
(ULD)
15%

OFF

OFF

ON
ON
ON
ON
CLS
CLS
ON
ON
ON
ON
ON

Starting Control

SELF-INSPECTION FUNCTIONS

OFF
OFF
OFF
OFF
OFF
OFF

OFF

OFF

ON
ON
ON
OFF
CLS
CLS
ON
OFF
OFF
ON
ON

OFF
OFF
OFF
OFF
OFF
OFF

100%

DLT
(FLD)

100%

ON
ON
ON
O
CLS
CLS
ON
ON
ON
ON
ON
DLT
(FLD)

OFF
OFF
OFF
OFF
OFF
OFF

OFF

OFF

ON
OFF
OFF
OFF
CLS
CLS
ON
OFF
OFF
ON
ON

Shut Down

OFF
OFF
OFF
OFF
OFF
OFF

OFF

OFF

OFF
OFF
OFF
CLS
CLS
OFF
OFF
OFF
OFF
OFF

CONTROL SYSTEM

Standard Operating Sequence for RCUE 100WG2, RCUE 120WG2 and RCUE 150WG2

10/37

SV11
SV12
SV13
SV21
SV22
SV23
SV31
SV32
SV33

MC3

MC2

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

OFF

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

OFF

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

OFF

OFF

OFF

OFF
ON
ON
ON

ON
ON
ON
CLS
CLS
CLS
OFF
OFF

3 min.

ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF

OFF

OFF

OFF

OFF
ON
ON
ON

ON
ON
ON
ON
CLS
CLS
CLS
ON
ON

ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF

OFF

OFF

OFF
OFF
ON
ON
STA
(ULD)
15%

ON
ON
ON
CLS
CLS
CLS
ON
ON

ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF

OFF

OFF

OFF
OFF
OFF
OFF
DLT
(ULD)
15%
DLT
(ULD)
15%

ON
ON
ON
CLS
CLS
CLS
ON
ON

60 sec.

ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
5 sec.

OFF
OFF
OFF
OFF
DLT
(ULD)
15%
STA
(ULD)
15%

ON
ON
ON
CLS
CLS
CLS
ON
ON

ON
ON
ON
CLS
CLS
CLS
ON
ON

30 sec.

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
DLT
DLT
(ULD)
(ULD)
15%
15%
DLT
DLT
(ULD)
(ULD)
15%
15%
STA
DLT
(ULD)
(ULD)
15%
15%
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
5 sec.

ON
ON
ON
CLS
CLS
CLS
ON
ON

DLT
(FLD)
100%
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON

DLT
(ULD)
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON

15%-99%

15%-99%

OFF
OFF
OFF
OFF
DLT
(FLD)
100%
DLT
(ULD)

ON
ON
ON
O
CLS
CLS
CLS
ON
ON

15%-99%

DLT
(ULD)

15%-99%

OFF
OFF
OFF
OFF
DLT
(ULD)

ON
ON
ON
O
CLS
CLS
CLS
ON
ON

Minimun 3min.
The Compressor which started finally will be restarted first.

60 sec.

ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
5 sec.

OFF

OFF

OFF
OFF
ON
ON
DLT
(ULD)
15%

ON
ON
ON
CLS
CLS
CLS
ON
ON

Starting Control

DLT
(FLD)
100%
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

15%-99%

OFF
OFF
OFF
OFF
DLT
(FLD)
15%
DLT
(ULD)

ON
ON
ON
O
CLS
CLS
CLS
ON
ON

OFF
ON
ON
OFF
ON
OFF
OFF
ON
OFF

15%-99%

DLT
(ULD)

15%-99%

OFF
OFF
OFF
OFF
DLT
(ULD)
15%
DLT
(ULD)

ON
ON
ON
O
CLS
CLS
CLS
ON
ON

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

15%-99%

DLT
(ULD)

15%-99%

OFF
OFF
OFF
OFF
DLT
(ULD)
15%
DLT
(ULD)

ON
ON
ON
O
CLS
CLS
CLS
ON
ON
OFF
OFF
OFF
OFF
DLT
(ULD)
15%
DLT
(ULD)
15%
DLT
(ULD)
15%
OFF
ON
ON
OFF
ON
OFF
OFF
ON
OFF

ON
ON
ON
O
CLS
CLS
CLS
ON
ON

Capacity Control

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

15%-99%

DLT
(ULD)

15%-99%

DLT
(ULD)

15%-99%

OFF
OFF
OFF
OFF
DLT
(ULD)

ON
ON
ON
O
CLS
CLS
CLS
ON
ON

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

15%-99%

DLT
(ULD)

15%-99%

DLT
(ULD)

OFF

ON
ON
OFF
OFF

ON
ON
ON
O
OPN
CLS
CLS
ON
ON

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON

15%-99%

DLT
(ULD)

OFF

OFF

ON
ON
ON
OFF

ON
ON
ON
O
OPN
OPN
CLS
ON
ON

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

OFF

OFF

OFF

ON
ON
ON
ON

ON
ON
ON
O
OPN
OPN
OPN
ON
ON

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

OFF

OFF

OFF

OFF
ON
ON
ON

ON
ON
ON
OFF
CLS
CLS
CLS
ON
OFF

DLT
(FLD)
100%
DLT
(FLD)
100%
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

ON
OFF
OFF
OFF
DLT
(FLD)

ON
ON
ON
O
CLS
CLS
CLS
ON
ON

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

OFF

OFF

OFF

OFF
ON
ON
ON

ON
OFF
OFF
OFF
CLS
CLS
CLS
ON
OFF

Shut Down

CLS: Close, OPN: Open, STA: Star, DLT: Delta


ULD: Unload, FLD: Full Load

ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF

OFF

OFF

OFF

OFF
ON
ON
ON

ON
ON
ON
O
CLS
CLS
CLS
ON
ON

Safety Devices

OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF

OFF

OFF

OFF

OFF
OFF
OFF
OFF

OFF
OFF
OFF
CLS
CLS
CLS
OFF
OFF

CONTROL SYSTEM

Time Schedule

Solenoid Valve

Motor for
compressor

OFF

OFF

OFF

Oil Heater

OFF

OFF
ON
ON
ON

CH1
CH2
CH3
MC1

OFF
OFF
OFF
OFF

Operation Lump

Alarm Lump

ON
OFF
OFF
CLS
CLS
CLS
OFF
OFF

OFF
CLS
CLS
CLS
OFF
OFF

Main Power Switch


Chilled Water Pump
Condenser Water Pump
Operation Switch (ON/OFF)
Controller
Load up
Neutral
Load down
No. 1
Safety Devices
No. 2
No. 3
Power Supply Lamp

Devices

Control Stage

9/38 SELF-INSPECTION FUNCTIONS

10/38
CONTROL SYSTEM

Standard Operating Sequence for RCUE 180WG2, RCUE 200WG2, and RCUE 240WG2

MAINTENANCE 11/39

11. MAINTENANCE
The unit should be periodically inspected according to the
same items as those described in the paragraph titled
Test Running. In order to ensure dependable
performance and long life operation, the following
additional items should be given for particular attention.

WARNING:

If a fire accidentally occurs, turn OFF the main switch


and use an extinguisher for an oil fire and an electric
fire.
Do not operate the unit near flammable gases such
lacquer, paint oil, etc. to avoid a fire or an explosion.
Turn OFF the main switch when electrical box covers
are removed for setting the temperature. Do not
operate the unit without fixing panels.

DANGER:

 CAUTION:

Perform periodical maintenance according to the


INSTRUCTIONS to maintain the unit in a good
condition.
Do not touch the parts at the discharge gas side by
hand, since the pipes at the discharge side are
heated by refrigerant and the temperature becomes
higher than 100 C.
Do not utilize this unit for cooling or heating of
drinking water or food. Comply with local codes and
regulations.
Turn OFF all the main switches if refrigerant leakage
or chilled / hot water leakage occurs. Also, if the unit
can not be stopped by the control switch, turn OFF all
the switches for power source.

Switch OFF main interruptor (MI) for any work inside


electrical box.

11.1. COMPONENTS
Compressor

Control and Protective Devices

The semi-hermetic screw compressor requires periodic


maintenance, including replacement of parts. See the
HITACHI Service Handbook for Screw Compressors, for
details.

Do not readjust the settings in the field unless the setting is


maintained at the point other than the point listed in the
table on chapter 11.

Electrical Equipment
Always pay careful attention to working voltage, amperage
and phase balance. Check for faulty contact caused by
loosened terminal connections, oxidised contacts, foreign
matter, and others.

11.2. LUBRICATION
Compressor
The compressors are charged at the factory with the
correct oil listed in Component Data and the compressor
nameplate. It is not necessary to add oil, if the refrigerant
cycle remains sealed.

11.3. DEPOSITS
Slime and other minerals in the condenser water or chilled
water tend to deposit on inside surfaces of plates over a
long period of operation. As deposits of these minerals
increase, excessive high discharge pressure or lower
operation pressure are detected, indicating evidence of
deposits on the condenser or the water cooler. The figure
in page 41 indicates the range where cleaning is required.

 CAUTION:

-Cleaning of plate type heat exchangers shall be

performed by specialists. Please contact your


contractor or dealer of HITACHI.
-Clean the water strainer filter periodically according to
its clogging degree. If not cleaned periodically, the
water strainer will be broken due to an excessive
pressure to the strainer screen.

strainer at the inlet of the chilled water piping near the


product. If clogging in the plate type heat exchanger
occurs seriously, this will cause insufficient cooling
performance or local freezing in the plate type heat
exchanger. It is strongly recommended that the heat
exchanger be cleaned at the same time when the
filter is cleaned.
Pay attention to the following caution and normal
cleaning method. For details, contact your Hitachi
installer.

Water

WARNING:

-This product is equipped with plate type heat

exchangers. In the plate type heat exchanger, water


flows through a narrow space between plates.
Therefore, there is a possibility that freezing may
occur if foreign particles or dusts are clogged. In
order to avoid this clogging, provide a 20 mesh water

Refrigerant

11/40 MAINTENANCE

 CAUTION:

-In the case that a cleaning agent is used adjust

-Correctly select cleaning agent depending on scales in

concentration of the cleaning Agent, cleaning period


and temperature according to the scale degree.
-In the case that acid cleaning is performed,
neutralisation treatment is required after cleaning.
Treatment for neutralisation fluid should be performed
by a waste fluid contractors.
-The cleaning agent and neutralizing agent are erosive
and stimulative against eyes, skin, mucous membrane
etc. Therefore use protection tools (protection glasses,
protection gloves, protection shoes, protection cloth,
protection mask, etc.) in order not to absorb or touch
these agents during this cleaning work.

the plate type heat exchangers. The cleaning


chemicals are different depending on fouling degree.
-This plate type heat exchanger is made of stainless
steel. Do not use a cleaning agent containing
hydrochloric acid or fluorine compound. If used, the
heat exchanger will be damaged, resulting in
refrigerant leakage.
-After cleaning with cleaning agent, clean inside of
water piping including the heat exchangers by using
clean water. Perform water treatment (preventive
treatment) in order to prevent the water circuit from
corrosion or re-adhering of scales after cleaning.

11.4. CLEANING METHOD

q
p

r
s

o
r
u

t
N
1
2
3
4

Name
Chiller Unit
Chilled Water / Inlet Piping
Acid-resistant Type Water Pump
Hose

1. Installation of Cleaning Circuit


-Stop the water Chiller unit.
-Stop the circulating water pump.
-Disconnect the connections at the chilled water inlet or
cooling water inlet and install a circulating water circuit by
using an acid-resistant type water pump.
2. Check of Circulating Circuit
Pour water in the cleaning tank and operate the acidresistant type water pump.
-Check to ensure that no water leakage exists.
-Check to ensure that the water hose is firmly fixed.
-Check to ensure that the cleaning Agent will not damage
equipment near the water Chiller even if bubbles occur
and touch them.
-Check to ensure that good ventilation is available.
-Check to ensure that no abnormal sound occurs.
3. Cleaning Work
-Discharge water in the water circuit of the air conditioning
system.
-Supply diluted cleaning fluid from the cleaning water tank
by operating the acid-resistant pump.
-Circulate the cleaning fluid for an appropriate period of
time (the operating time should be determined according
to the type of cleaning Agent, concentration and fouling
degree).

N
5
6
7
8

Name
Diluted Cleaning Fluid
Chilled Water / Outlet Piping
Cleaning Water Tank
Waste Fluid Tank
4. Waste Fluid
-Stop the acid-resistant pump.
-Put the waste fluid into the waste fluid tank.
-Supply water into the cleaning tank and operate the pump
for water cleaning.
-Put the cleaning water into the waste fluid tank as same as
the waste fluid.
-Measure pH degree by using a pH test sheet and
neutralize the waste fluid by gradually adding neutralizing
agent.
-After neutralization ask a waste fluid treatment contractors
to handle it.
5. Neutralisation Treatment in the Water Piping
-Put water into the cleaning tank.
-Operate the acid-resistant pump after air-purging.
-Measure the pH degree and gradually add neutralizing
agent until the pH reaches pH = 7.
-Operate the pump for a specified period of time for
neutralization.
-Discharge the used water.
-Operate the circulating pump and clean the circuit with
water until no fouling fluid is observed.
6. Re-starting
-Reconnect the water piping as they were so that the water
Chiller can operate.
-After cleaning, perform water treatment (preventive
treatment) in order to prevent the water circuit from
corrosion.

Area Requiring Cleaning

Saturation Line

Condenser Water Outlet Temperature (C)

Suction Gas Pressure (MPa)

Discharge Gas Pressure (MPa)

MAINTENANCE 11/41

Saturation Line

Area Requiring Cleaning

Chilled Water Outlet Temperature (C)

11.5. WINTER SHUTDOWN


When shutting down the unit for winter, clean the inside
and outside of the cabinet, and dry the unit. Pump down
the refrigerant to the condenser and close the liquid outlet
stop valves. This unit should be covered during shutdown,
in order to protect it from dust and environmental
conditions. Be sure to tighten the packing glands and the
cap nuts of the valves.

Remove the drain plug and drain all residual water from the
condenser and water cooler piping systems, as such water
may freeze during the cold season. It is very helpful to
supply brine (anti-freezer) to the piping systems.

11.6. SPRING START-UP


After any extended shutdown period, prepare the unit for
operation as follows.
1. Thoroughly inspect and clean the unit.
2. Clean the water piping lines and the strainer.
3. Inspect the pump, the cooling tower and/or regulating
valve.
4. Tighten all wiring connections and access panel.

 CAUTION:

When the main switch for this unit has been at the
OFF position for an extended period of time, it should
be switched ON at least 12 hours before start-up, so
that oil in the compressor discharge casing may be
warmed enough, to prevent oil foaming by the oil
heater during start-up.

11.7. PART REPLACEMENT


Replacement of parts should be undertaken by ordering
from the HITACHI Spare Parts List.

 CAUTION:

Do not replace with spare parts which are not the


equivalent.

11/42 MAINTENANCE
11.8. REFRIGERATION CYCLE
Strainer

Completely evacuate the entire cycle with a vacuum


pump.
Charge refrigerant to the refrigeration cycle by
weighing the charging cylinder. The proper refrigerant
charge is listed on the nameplate.
When charging by weight is stopped due to high
ambient temperature, close the valve and operate the
unit after circulating the chilled water through the water
cooler.
2. When Only Additional Refrigerant is Required.
Connect a gauge manifold to check joint of low pressure
side, and connect a charge cylinder to gauge manifold.
Operate the unit after circulating the chilled water.
Repeat the following procedure until pressure becomes
proper (refer to page 46)
Charge the gas refrigerant a little slowly into
refrigeration cycle from check joint for low pressure.
Check the pressure after refrigeration cycle becomes
stable.

Check for clogging each time when the refrigeration cycle


is opened.
Refrigerant Charge
Inspect the refrigerant charge of the system by checking
the discharge and suction pressures. Perform a leakage
test, if any leakage is suspected, and always perform such
a test after a refrigeration cycle component is replaced.
When refrigerant charge is required, follow the following
instructions given for two cases:
1. When Refrigerant Gas Completely Leaked.
Before charging the entire cycle must be completely
evacuated and dehydrated. A gauge manifold or
equivalent piping preparation shown in the next page is
recommended as a convenient procedure regarding
both charging and evacuation.
Fully open all the stop valves.
Connect the evacuation line to the check joints of the
high and the low pressure sides.

11.9. REFRIGERANT CYCLE DIAGRAM OF HITACHI WATER COOLED CHILLER


MODEL: RCUE 40, 50, 60, 100, 120, 180, 200WG2

Condensing Water Outlet


Design
Pressure

Condensing Water Inlet

Hydrostatic Test
Pressure

Gauge
manifold

Chilled Water
Inlet

Evacuation
Charging

Chilled Water
Outlet
Unit side

Flange Connection
Flare Connection
Solder Connection
Refrigerant Cycle

No.
1
2
3
4
5
6
7
8
9
10
11

Name
Compressor
Check Valve
Pressure Relief Valve
Stop Valve (Option)
Water Condenser
Stop Valve
Stop Valve
Drier
Sight Glass
Electronic Expansion Valve
Water Cooler

NOTE:
R407C shall be charged by LIQUID.

No.
12
13
14
15
16
17
A
B
C
D
E

Name
Stop Valve (Option)
Pressure Sensor (Low)
High Pressure Switch
Pressure Sensor (High)
Compressor Safety Valve (Option)
Compressor Dual Safety Valve (Option)
High Pressure Gauge
Low Pressure Gauge
Stop Valve
Charging Cylinder
Vacuum Pump

MAINTENANCE 11/43

MODEL: RCUE 80, 150, 240WG2

Condensing Water Outlet


Condensing Water Inlet

Design
Pressure
Hydrostatic
Test
Pressure

Gauge
manifold

Chilled
Water Inlet
Chilled
Water Outlet

Evacuation
Unit side

Charging
Flange Connection
Flare Connection
Solder Connection
Refrigerant Cycle

No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14

Name
Compressor
Check Valve
Pressure Relief Valve
Stop Valve (Option)
Water Condenser
Stop Valve
Stop Valve
Drier
Sight Glass
Electronic Expansion Valve
Water Cooler
Stop Valve (Option)
Pressure Sensor (Low)
High Pressure Switch

No.
15
16
17
18
19
20
21
22
A
B
C
D
E

Name
Pressure Sensor (High)
Compressor Safety Valve (Option)
Compressor Dual Safety Valve (Option)
Pressure Switch
Solenoid Valve
Capillary Tube
Economizer
Strainer
High Pressure Gauge
Low Pressure Gauge
Stop Valve
Charging Cylinder
Vacuum Pump

NOTE:
R407C shall be charged by LIQUID.

 CAUTION:

-Do not charge OXYGEN, ACETYLENE or other

flammable and poisonous gases into the refrigeration


cycle when performing a leakage test or an airtight
test. These types of gases are extremely dangerous,
because explosion can occur. It is recommended that
compressed air or nitrogen be charged for these
types of tests.
-Mineral deposits on water cooler plates act as thermal
insulators, and also act as resistance Against water
flow, causing the water flow to decrease running
through them, and resulting in a decreasing of the
cooling capacity. Deposits on the plates should be
inspected at regular, intervals, experience with the
water Chiller will dictate accurate inspection intervals.

-These deposits should be removed by circulating

diluted acid through the water passes after the water


has been drained. As water in different localities
contains different minerals, different acids are
required, depending upon the thickness of the
deposits.
-This unit is equipped with an operation hour meter. In
the case that the total operation time reaches 40,000
hours or 5 years pass after installation, exchange the
bearings of the compressor. For details, refer to the
Service Handbook for HITACHI Screw Compressors.
-For R407C refrigerant system, charge the refrigerant
with liquid condition to avoid its composition change.

11/44 MAINTENANCE
11.10. COMPRESSOR REMOVAL
When Removing the Compressor

Remove the compressor while completing the


following procedures.

5.Operate the water Chiller after circulating water


through the water cooler and condenser.

1.Collect all refrigerant into a condenser before this


work.

6.Stop the water Chiller when the low pressure reaches


at approximately 0.05 MPa. Do not operate at the
pressure lower than 0.05 MPa. If operated, it will
cause a damages to the compressor.

2.Turn off the switch, DSW3 of the PCB in the electrical


box in order not to operate the compressor except for
the cycle.

7.Wait for several minutes. If the low pressure increase


up to 0.15 to 0.2 MPa, repeat the above procedures 5
and 6 four or five times.

3.Circulate the chilled and cooling water sufficiently


through the water cooler and condenser, and operate
the water Chiller for 10 minutes, and check to ensure
that the oil level is maintained at a stable condition.

8.Turn OFF the power supply to the unit.


9. Remove the bolts on the discharge and suction
flanges of the compressor.

4.Stop the water Chiller and completely close the liquid


stop valve.

11.11. SAFETY AND PROTECTION CONTROL


The safety and protective devices are equipped with the
unit to ensure dependable and long life operation.
Their functions should be carefully noted, and field
adjustment is not recommended, if the setting is maintained
at the point listed in the table.

Compressor protection
1. Fuse and thermal relay equipped in the control box cut
out each compressor operation when the current to the
compressor exceeds the setting
2. The internal thermostat embedded in the motor winding
cuts out each operation, when the temperature exceeds
the setting
3. The oil heater in the compressor prevents from oil
foaming during cold starting. This heater warms the oil,
while the compressor is stopped

Refrigeration Cycle
1. The high pressure switch and low pressure control
protect Against excessive discharge pressure and
exceedingly low suction pressure. The switch and
control cut out compressor operation when discharge
pressure or suction pressure is abnormal.
2. The pressure relief valve is equipped on discharge gas
line. When high pressure exceeds the setting, gas
refrigerant will be discharged to prevent abnormal high
pressure

Water Cooler
Pump interlock, freeze protection thermostat, low
pressure control and suction gas thermostat can protect
water cooler Against water cooler freezing

MAINTENANCE 11/45

11.11.1. SAFETY AND CONTROL DEVICE SETTING

RCUE
-WG2

Model
For Compressor
High Pressure Switch
Cut-Out
Low Pressure Switch
(Pressure Sensor)

40

50

60

80

100

120

150

180

200

240

Manual Reset, Non-Adjustable ( One Switch for Each Compressor Motor )


MPa
2,74 2,74 2,74 2,74 2,74 2,74 2,74 2,74 2,74 2,74
Electronic Control
MPa
0,05 0,05 0,05 0,05 0,05 0,05 0,05 0,05 0,05 0,05

Cut-Out
Internal Thermostat for Compressor
Cut-Out
Cut- In
Compressor Motor (380-415V/50Hz)
Fuse

Manual Reset, Non-Adjustable ( One Switch for Each Compressor Motor )


115 115 115 115 115 115 115 115 115 115
C
93
93
93
93
93
93
93
93
93
93
C

A
100 100 125 125 100 125 125 100 125 125
Manual Reset, Adjustable ( One Three-Phase Set for Each Compressor
Motor )
Thermal Relay
A
48
55
70
75
55
70
75
55
70
75
Manual Reset, Adjustable ( One Three-Phase Set for Each Compressor
Motor )
Magnetic circuit Protection (Option)
A
90 107 127 127 107 127 127 107 127 127
One Heater for Each Compressor Motor
Oil Heater
Capacity
W
150 150 150 150 150 150 150 150 150 150
( One for Each Cycle )
Discharge Gas (Electronic Control)
Cut-Out
140 140 140 140 140 140 140 140 140 140
C
Non-Adjustable ( One Timer for Each Compressor )
CCP Timer
Setting Time
S
180 180 180 180 180 180 180 180 180 180
Star-Delta
S
5
5
5
5
5
5
5
5
5
5
Unloading during Starting
S
30
30
30
30
30
30
30
30
30
30
( One for Each Circuit )
For Refrigerant Circuit
Pressure Relief Valve
Setting Pressure
MPa
3,0 3,0 3,0 3,0 3,0 3,0 3,0 3,0 3,0 3,0
( One for Each Water Cooler )
Freeze Protection Thermostat
Cut-Out
2
2
2
2
2
2
2
2
2
2
C

11/46 MAINTENANCE
11.12. NORMAL OPERATING PRESSURE
Check to ensure that Chiller is operating within the working
range as shown below, after at least 15 minutes operation.
Low Pressure: The normal operating low pressure of the
water chiller is indicated in the figure below; lower than 0.3
Mpa indicates an abnormal condition.

Discharge Pressure: Normal operating discharge pressure


is indicated in the figure below; low than 0.9 Mpa or higher
than 2.2 Mpa indicates an abnormal condition

Standard Working Range

Chilled Water Outlet Temperature (C)

 CAUTION:

Periodical Maintenance
Perform periodical maintenance according to the
INSTRUCTIONS to maintain the unit in a good
condition.
Fire
If a fire accidentally occurs, turn OFF the main switch
and use an extinguisher for an oil fire and electric fire.
Flammable Gases
Do not operate the unit near the flammable gases
such as lacquer, paint, oil, etc. to avoid a fire or an
explosion.
Service Panels and Electrical Box Cover
Turn OFF the main switch when service panels or
electrical box covers are removed for setting the
temperature.
Do not operate the unit without fixing panels.
Heated Pipe
Do not touch the parts at discharge gas side by hand,
since the pipes at the discharge side are heated by
refrigerant and temperature becomes higher than 100
C.
Use
Do not utilize this unit for cooling of drinking water or
food. Comply with local codes and regulations.

Discharge Gas
Pressure (MPa)

Suction Gas
Pressure (MPa)

For R407C

Standard Working Range

Condenser Water Outlet Temperature (C)

Failure
Turn OFF all the main switches if refrigerant leakage
or chilled water leakage occurs. Also, if the unit can
not be stopped by the control switch, turn OFF all the
switches for power source.
Activation of Safety Device
In the case that one of safety devices is activated and
unit is stopped, remove the cause of the stoppage
and restart the unit. The protection devices are
utilized to protect the unit from an abnormal
operation.
Therefore, if one of safety devices is activated,
remove the cause by referring the Troubleshooting
in the INSTRUCTION or call the local agency.
Fuse
Utilize a fuse with specified capacity. Do not use a
steel wire or a copper wire instead of a fuse. If an
incorrect wire is utilized, a serious accident such as a
fire will occur.
Safety Devices
Do not make a short-circuit at the protection line. If a
short-circuit is made, a serious accident will occur.
Setting of Safety devices
Do not change the setting of safety devices, if
changed, a serious accident will occur.
Do not touch any electrical parts except for the
operation switches during the operation.
Do not press the button on the magnetic switch. If
pressed, a serious accident will occur.

MAINTENANCE 11/47

11.13. TEST RUNNING AND MAINTENANCE RECORD

MODEL: RCUE

MFG. NO.
COMPRESSOR MFG. NO.

CUSTOMERS NAME AND ADRESS:


DATE:
1. Is there adequate water flow for the condenser and the water cooler?
2. Has all water piping been checked for leakage?
3. Have the cooling water pump, fan and motor been lubricated?
4. Has the unit been operated for at least twenty minutes?

5. Check Chilled Water Temperature:


Inlet

Outlet

Outlet

6. Check Condenser Water Temperature:


Inlet

7. Check Suction Line Temperature and Superheat:


Suction Line Temperature:

Superheat:

MPa

MPa

MPa

MPa

MPa

MPa

8. Check Pressure:
Discharge Pressure:
Suction Pressure:

9. Has the unit been checked for refrigerant leakage?


10. Is the unit clean inside and outside?
11. Are all cabinet panels free from rattling?

11/48 MAINTENANCE

11.14. DAILY OPERATING RECORDS


Model:
Date:
Weather:
Time of Operation Start:

Stop. (
DB

WB

Ambient Temperature

Room Temperature

Compressor

High
Pressure

Mpa

Low
Pressure

Mpa

Voltage

Current

Condenser Water
Temperature

Inlet

Outlet

Chilled Water
Temperature

Inlet

Outlet

Current for Condenser Water Pump

Current for Chilled Water Pump

Current for Cooling Tower

NOTES:

11.15. SERVICING FOR R407C REFRIGERANT SYSTEM


Refrigerant
This R407C refrigerant is HFC type so that it has a feature
of no ozone depletion. If it is mixed with another refrigerant,
the serious changing would occur on its character.
Therefore notice the following point when handling this
refrigerant.
Charge the refrigerant in LIQUID condition and NOT in
GAS. As "R407C" is geotropic mixed refrigerant, if gas
charging is performed, only the easy vaporising
refrigerant would be charged into the system and the
difficult vaporising one would be remained in the
charge cylinder.
The cylinder, gauge equipped manifold and charge hose
are only used for R407C refrigerant.

Adjust the cylinder setting to charge in liquid.


Refrigerant Oil
UX300, which R407C refrigerant is easy to blend into it, is
used for this system. The other oil is prohibited to use, so
that not to be mixed with another kind of oil at the
maintenance and service work. This oil is very hygroscopic.
Therefore minimum humidity handling is necessary.
Servicing Equipment
When servicing R407C system, servicing equipment such
as Charging Cylinder, Charging Hose, Vacuum Pump and
so on, shall not be mixed with R22 equipment to avoid
R407C composition change.

TROUBLESHOOTING 12/49

12. TROUBLESHOOTING
The following table shows efficient checking procedures for trouble.
Fault

Possible Cause
Interlock Circuit for Chilled Water Pump is
Open

Compressor Does Not Operate

Compressor Stops on High


Pressure Switch

Compressor Stops on
Overcurrent Relay

Electrical Protective Devices Are Tripped.


Incorrect Wiring Connection for Compressor
Power Source
Excessively High Discharge Pressure
Malfunction of High Pressure Switch
Excessively High Discharge Pressure and
Suction Pressure
High or Low Voltage, Single-Phase or Phase
Imbalance
Loose connection
Faulty Overcurrent Relay
Excessively Low Chilled water Outlet
Temperature

Compressor Stops on Freeze


Protection Control

Compressor Stops on Internal


Thermostat or Discharge Gas
Thermostat

Insufficient Cooling

Defective Thermistor
Shortage of Chilled Water Flow
Air in water Circuit
High or Low Voltage, Single-Phase or Phase
Imbalance
Excessive Superheat
Defective Element
Excessive High Discharge Pressure and Low
Suction Pressure
High Discharge Pressure or Low Suction
Pressure
Improper Thermostat Setting
Defective Unload Mechanism

Noisy Compressor

Slugging Due to Liquid Flooding Back to


Compressor
Worn parts

Miscellaneous Noise

Loose Fixed Screw


Trouble with the Thermistor

Unloaded Does not Function

Trouble with the Solenoid Valve


Worn Unloader Mechanism

High Discharge Pressure

Warm inlet water or Insufficient Water Flow


Through the Condenser
Gas Outlet Valve on the Condenser Not
Completely Open
Overcharged Refrigerant
Condenser Plates Coated with Scales, Slime,
Corrosion and Others
Suction Pressure is Higher than Standard

Check/Corrective Action
1.Check the pump contactor. Repair or
replace, if necessary.
2.Check for the faulty pump.
1.Remove the causes, and reset the ON
button. See the following causes.
1.Interchange two of three terminals R, S and
T at the main power source terminals.
1.See High Discharge Pressure
1.Readjust the setting or replace, if defective.
1.See High Discharge Pressure and High
Suction Pressure.
1.Check the power supply line and contactors.
Repair, if necessary.
1.Tighten the loose electrical connection or
repair, if necessary.
1.Replace it, if necessary.
1.Check for excessively low setting of the
chilled water setting knob.
1.Check for malfunction of the thermistor.
Replace, if necessary.
1.Check the rotation of the pump.
1.Purge air.
1.Check the power supply line and contactors.
Repair, if necessary.
1.Check for refrigerant leakage
1.Check the contact of the internal thermostat
during the cold condition.
1.See High Discharge Pressure and High
Suction Pressure.
1.See High Discharge Pressure and Low
Suction Pressure.
1.Readjust the setting.
1.Adjust unload mechanism. Repair or
replace unloaded parts, if necessary.
1.Check the superheat of suction gas. Keep
the superheat in proper range.
1.Check for the sound of internal parts.
Replace the compressor, if necessary.
1.Tighten the screws of all parts.
1.Adjust the setting temperature.
2.Replace the thermistor.
1.Check the coil in the solenoid valve.
2.Check oil passage for clogging.
1.Check the unloaded system parts in the
compressor.
1.Open the valve
1.Check the valves, capillary tubes and
strainer. Replace, if necessary.
1.Purge the refrigerant.
1.Clean the Condenser water plates by
chemical cleaner
1.See High Suction Pressure.

12/50 TROUBLESHOOTING

Fault

Possible Cause
Too Much Water Flowing through the
Condenser, or Water is too Cold
Insufficient Refrigerant Charge

1. Add Refrigerant.

Leakage from the Condenser Gas Outlet Valve

1. Check to determine how long it takes to


balance high and low

Liquid Refrigerant Flooding Back from the


Water Cooler, Causing Oil to Foam..

1. Check the operation and the position of


expansion valve coil. Repair or replace if
necessary.
2. Inlet water temperature is considerably
lower than the limited temperature.

Suction Pressure is lower than Standard

1. See Low Suction Pressure

High Discharge Pressure

1. See High Discharge Pressure

Refrigerant Overcharged

1. Purge the refrigerant

Liquid Refrigerant Flooding Back from the


Water Cooler

1. Check the operation and the position of


expansion valve coil. Repair or replace if
necessary.
2. Inlet chilled water temperature to the unit
is considerably higher than the standard
temperature.

Low Discharge Pressure

High Suction Pressure

Check/Corrective Action
1. Adjust the water cock or the regulating
valve.
2. Check the operation of cooling tower.

Leakage from the Condenser Gas Outlet Valve 1. Check the condenser gas outlet valve

Low Suction Pressure

Insufficient Insulation for the Chilled Water


Piping
Condenser Liquid Outlet Valve Not Completely
Open
Expansion Valve not properly controlled, or
faulty valve
Inlet Chilled Water Temperature is
Considerably lower than standard
Temperature.
Insufficient Refrigerant Charge

1. Check the insulation of the piping


1. Open the valve.
1. Check the position of Expansion Valve coil.
Repair or replace if necessary.
1. Check the insulation specifications
1. Add Refrigerant

Excessive Oil Circulatin in the System

1. Check the oil charge

Insufficient Chilled Water Flow through the


water cooler.

1. Check the chilled water piping lines for


pressure loss.

Low Discharge Pressure

1. Adjust the water shutoff valve

Scales on Water Cooler Plates

1. Clean the plates

GENERAL SPECIFICATIONS 13/51

13. GENERAL SPECIFICATIONS


13.1. GENERAL DATA
Model
Cooling Capacity *1
Power Input for Cooling *1
COP
Heating Capacity *2
Power Input for Heating *2
Height
Outer Dimension
Width
Depth
Cabinet Colour
Shipping Weight
Compressor Type
Models
Quantity
Oil Heater
Capacity Control
Cooler Type
Condenser Type
Refrigerant Type
Flow Control
Number of Independent Circuits
Oil Type
Evaporator Connection
Option Common Water Piping
Condenser Connection
Option Common Water Piping
Control System
Chilled Water Outlet Temperature
Cooling Water Outlet Temperature *3
Permissible Water Pressure Max.
Cooler
Condenser

RCUE40WG2

RCUE50WG2

RCUE60WG2

RCUE80WG2

kW
kW
kW
kW
mm
mm
mm
kg
W
%
Inch
Inch
Inch
Inch
C
C

160
194
232
40
49.1
54.5
4.0
4.0
4.3
192.3
233.9
274.7
47.5
58.3
64.7
1520
1520
1520
1105
1105
1105
850
850
850
Natural Gray
750
765
830
950
Semi-Hermetic Screw Type
40ASC-Z
50ASC-Z
60ASC-Z
60ASC-Z
1
1
1
1
150
150
150
150
Continuous Capacity Control
15 100
Brazing Plate Type
Brazing Plate Type
R407C (Factory Charged)
Electronic Expansion Valve
1
1
1
1
JAPAN ENERGY FREOL UX300 (Ester)
3 Victaulic (1Inlet / 1Outlet )
3 Victaulic (1Inlet / 1Outlet )
Micro-Processor
(-10) 5 15
22 45 (55)

MPa
MPa

1.03
1.03

Safety and Protection Devices

Power Supply

134
33.5
4.0
161.1
39.8
1520
1105
850

Reverse Phase Protection,


Fuse and Thermal Relay for Compressor,
Internal Thermostat for Compressor, Compressor Oil Heater,
Control Circuit Fuse, High Pressure Switch, Low Pressure Control,
Discharge Gas Temperature Control,
Suction Gas Temperature Control, Freeze Protection Control
and Compressor Operation Hour Meter
3, N / 380 - 415V / 50Hz

 NOTES:
*1 The nominal cooling capacities are based on the European Standard EN12055.
Chilled Water Inlet / Outlet Temperature : 12 / 7 C
Cooling Water Inlet / Outlet Temperature : 30 / 35 C
*2 The nominal heating capacities are only for Heat Pump Operation Option and based on following conditions.
Chilled Water Inlet / Outlet Temperature : 12 / 7 C
Hot Water (Condenser) Inlet / Outlet Temperature : 40 / 45 C
*3 ( ) is in case of high condensing option and heat pump operation option.

13/52 GENERAL SPECIFICATIONS

Model
Cooling Capacity *1
Power Input for Cooling *1
COP
Heating Capacity *2
Power Input for Heating *2
Height
Outer Dimension
Width
Depth
Cabinet Colour
Shipping Weight
Compressor Type
Models
Quantity
Oil Heater
Capacity Control
Cooler Type
Condenser Type
Refrigerant Type
Flow Control
Number of Independent Circuits
Oil Type
Evaporator Connection
Option Common Water Piping
Condenser Connection
Option Common Water Piping
Control System
Chilled Water Outlet Temperature
Cooling Water Outlet Temperature *3
Permissible Water Pressure Max.
Cooler
Condenser

RCUE100WG2

RCUE120WG2

RCUE150WG2

kW
kW
kW
kW
mm
mm
mm
kg
W
%
Inch
Inch
Inch
Inch
C
C

388
445
98.2
104.5
4.0
4.3
467.9
526.9
116.6
124.1
1700
1700
1105
1105
1465
1465
Natural Gray
1570
1670
1770
Semi-Hermetic Screw Type
50ASC-Z
60ASC-Z
60ASC-Z
2
2
2
150 x 2
150 x 2
150 x 2
Continuous Capacity Control
7.5, 15 100
Brazing Plate Type
Brazing Plate Type
R407C (Factory Charged)
Electronic Expansion Valve
2
2
2
JAPAN ENERGY FREOL UX300 (Ester)
3 Victaulic (1Inlet / 1Outlet )
3 Victaulic (1Inlet / 1Outlet )
Micro-Processor
(-10) 5 15
22 45 (55)

MPa
MPa

1.03
1.03

Safety and Protection Devices

Power Supply

320
80
4.0
384.7
95
1700
1105
1465

Reverse Phase Protection,


Fuse and Thermal Relay for Compressor,
Internal Thermostat for Compressor, Compressor Oil Heater,
Control Circuit Fuse, High Pressure Switch, Low Pressure Control,
Discharge Gas Temperature Control,
Suction Gas Temperature Control, Freeze Protection Control
and Compressor Operation Hour Meter
3, N / 380 - 415V / 50Hz

 NOTES:
*1 The nominal cooling capacities are based on the European Standard EN12055.
Chilled Water Inlet / Outlet Temperature : 12 / 7 C
Cooling Water Inlet / Outlet Temperature : 30 / 35 C
*2 The nominal heating capacities are only for Heat Pump Operation Option and based on following conditions.
Chilled Water Inlet / Outlet Temperature : 12 / 7 C
Hot Water (Condenser) Inlet / Outlet Temperature : 40 / 45 C
*3 ( ) is in case of high condensing option and heat pump operation option.

GENERAL SPECIFICATIONS 13/53

Model
Cooling Capacity *1
Power Input for Cooling *1
COP
Heating Capacity *2
Power Input for Heating *2
Height
Outer Dimension
Width
Depth
Cabinet Colour
Shipping Weight
Compressor Type
Models
Quantity
Oil Heater
Capacity Control
Cooler Type
Condenser Type
Refrigerant Type
Flow Control
Number of Independent Circuits
Oil Type
Evaporator Connection
Option Common Water Piping
Condenser Connection
Option Common Water Piping
Control System
Chilled Water Outlet Temperature
Cooling Water Outlet Temperature *3
Permissible Water Pressure Max.
Cooler
Condenser

RCUE180WG2

RCUE200WG2

RCUE240WG2

kW
kW
kW
kW
mm
mm
mm
kg
W
%
Inch
Inch
Inch
Inch
C
C

600
696
148.5
163.5
4.0
4.3
719.5
824.2
176.4
194.2
1580
1580
1105
1105
2350
2350
Natural Gray
2500
2580
2670
Semi-Hermetic Screw Type
50ASC-Z
60ASC-Z
60ASC-Z
3
3
3
150 x 3
150 x 3
150 x 3
Continuous Capacity Control
5, 15 100
Brazing Plate Type
Brazing Plate Type
R407C (Factory Charged)
Electronic Expansion Valve
3
3
3
JAPAN ENERGY FREOL UX300 (Ester)
3 Victaulic (3Inlet / 3Outlet )
5 Victaulic (1Inlet / 1Outlet )
3 Victaulic (3Inlet / 3Outlet )
5 Victaulic (1Inlet / 1Outlet )
Micro-Processor
(-10) 5 15
22 45 (55)

MPa
MPa

1.03
1.03

Safety and Protection Devices

Power Supply

525
123.5
4.3
621.9
146.7
1580
1105
2350

Reverse Phase Protection,


Fuse and Thermal Relay for Compressor,
Internal Thermostat for Compressor, Compressor Oil Heater,
Control Circuit Fuse, High Pressure Switch, Low Pressure Control,
Discharge Gas Temperature Control,
Suction Gas Temperature Control, Freeze Protection Control
and Compressor Operation Hour Meter
3, N / 380 - 415V / 50Hz

 NOTES:
*1 The nominal cooling capacities are based on the European Standard EN12055.
Chilled Water Inlet / Outlet Temperature : 12 / 7 C
Cooling Water Inlet / Outlet Temperature : 30 / 35 C
*2 The nominal heating capacities are only for Heat Pump Operation Option and based on following conditions.
Chilled Water Inlet / Outlet Temperature : 12 / 7 C
Hot Water (Condenser) Inlet / Outlet Temperature : 40 / 45 C
*3 ( ) is in case of high condensing option and heat pump operation option.

13/54 GENERAL SPECIFICATIONS

13.2. OPTION LINE UP


Following table shows options:
(9 mark shows available)

Specifications
Low Water
Temperature

Standard

Outlet Temperature: -1 -5 (Low2)


Extended Minimum Capacity Control

Local/Remote Changeover Switch


Individual Alarm
Operation Hour Meter
Pressure Sensor (High and Low)
Pump Operation Circuit
Control
System

Non Voltage Contact for Remote indication


DC24V External Control
Short Period Power OFF Protection
Power Failure Recover Control
2 Different Temperature Setting

9
9
9
9
9
9
9
9
9
9
9

BMS Control (HARC-70CE1)/OP


CSC-5S
Number Cable
High Condensing Temperature
Heat Pump Operation
Independent Circuit

Dual safety valve


Compressor Safety Valve
Compressor Dual Safety Valve
Pressure Display (High and Low)

PED Certificate (97/23/EC)

9
9

PN 16 Flange
Water Cooler

Differential Water Pressure Switch


Water Flow Switch (Field Install)
Water Cooler Heater
Common Water Pipe

Others

Witness Test
Foundation Rubber Mats

Pump, Operation, Alarm


Level or pulse

AC 220-240V
LON-WORKS

9
9
9
9
9

Suction Valve

10 bar Water Pressure

Pump ON/OFF Contact

Discharge Valve
Refrigeration
Cycle

For Each Compressor

By Alarm Code

9
9
9
9
9
9

Remote Control Switch

Condenser

DSW 7-3 ON

Compressor Circuit Breaker Protector


Main Isolator Switch

Remarks

9
9
9

Outlet Temperature: 0 4 (Low1)


Outlet Temperature: - 6 -10 (Low3)

Compressor

Option

Standard:
Display on Operation Panel
PED: Pressure
Equipment Directive

9
9
9
9
9
9
9

With Companion Flange

(Only 180, 200 and 240 HP)

DRAWINGS 14/55

14. DRAWINGS
14.1. DIMENSIONAL DRAWINGS
RCUE 40WG2

Electrical Box

Inlet for Power


Supply Wiring

Inlet for Control Wiring


Condenser Water Outlet
Cooler Water inlet
4x Lifting Holes

Cooler Water Outlet

Condenser Water Inlet

(cooler, welding connection)


(cooler, 3 B victaulic connection)
(condenser, welding connection)
(condenser, 3B Victaulic connection)

RCUE 50WG2

Electrical Box

Inlet for Power


Supply Wiring

Inlet for Control Wiring


Condenser Water Outlet
Cooler Water inlet
4x Lifting Holes

Cooler Water Outlet


(cooler, welding connection)
(cooler, 3 B victaulic connection)
(condenser, welding connection)
(condenser, 3B Victaulic connection)

Condenser Water Inlet

14/56 DRAWINGS
RCUE 60WG2

Electrical Box

Inlet for Power


Supply Wiring

Inlet for Control Wiring


Condenser Water Outlet
Cooler Water inlet
4x Lifting Holes

Cooler Water Outlet

Condenser Water Inlet

(cooler, welding connection)


(cooler, 3 B victaulic connection)
(condenser, welding connection)
(condenser, 3B Victaulic connection)

RCUE 80WG2

Electrical Box

Inlet for Power


Supply Wiring

Inlet for Control Wiring


Condenser Water Outlet
Cooler Water inlet
4x Lifting Holes

Cooler Water Outlet


(cooler, welding connection)
(cooler, 3 B victaulic connection)
(condenser, welding connection)
(condenser, 3B Victaulic connection)

Condenser Water Inlet

DRAWINGS 14/57
RCUE 100WG2

Electrical Box

Condenser
Water Outlet
Cooler
Water inlet
4x Lifting Holes

Inlet for Power

Inlet for Control Wiring

Supply Wiring

Condenser Water Inlet


(cooler, welding connection)

Cooler Water Outlet


(cooler, 3 B victaulic connection)

(condenser, welding connection)


(condenser, 3B Victaulic connection)

RCUE 120WG2

Electrical Box

Condenser
Water Outlet
Cooler
Water inlet
4x Lifting Holes

Inlet for Control Wiring

Inlet for Power


Supply Wiring

Condenser Water Inlet


(cooler, welding connection)

Cooler Water Outlet

(cooler, 3 B victaulic connection)


(condenser, welding connection)
(condenser, 3B Victaulic connection)

14/58 DRAWINGS
RCUE 150WG2

Electrical Box

Condenser
Water Outlet
Cooler
Water inlet
4x Lifting Holes

Inlet for Control Wiring

Inlet for Power


Supply Wiring

Condenser Water Inlet


(cooler, welding connection)

Cooler Water Outlet

(cooler, 3 B victaulic connection)


(condenser, welding connection)
(condenser, 3B Victaulic connection)

RCUE 180WG2

Electrical Box

3 x Condenser
Water Outlet
3 x Cooler
Water inlet
4x Lifting Holes

3 x Cooler
Water outlet
Inlet for Power Supply Wiring
(cooler, welding connection)
(cooler, 3 B victaulic connection)
(condenser, welding connection)
(condenser, 3B Victaulic connection)

3 x Condenser Water Inlet

DRAWINGS 14/59

RCUE 200WG2

Electrical Box

3 x Condenser
Water Outlet
3 x Cooler
Water inlet
4x Lifting
Holes

3 x Cooler Water Outlet

3 x Condenser Water Inlet

Inlet for PowerSupply Wiring


(cooler, welding connection)
(cooler, 3 B victaulic connection)
(condenser, welding connection)
(condenser, 3B Victaulic connection)

RCUE 240WG2

Electrical Box

3 x Condenser
Water Outlet
3 x Cooler
Water inlet
4x Lifting Holes

3 x Cooler Water Outlet


Inlet for PowerSupply Wiring
(cooler, welding connection)
(cooler, 3 B victaulic connection)
(condenser, welding connection)
(condenser, 3B Victaulic connection)

3 x Condenser Water Inlet

14/60 DRAWINGS

14.2. WIRING DIAGRAMS

Main Switch

POWER CIRCUIT

RCUE 80WG2

RCUE 60WG2

RCUE 50WG2

RCUE 40WG2

Models

POWER CIRCUIT FOR RCUE 40WG2, RCUE 50WG2, RCUE 60WG2 and RCUE 80WG2

DRAWINGS 14/61

Main Switch

POWER CIRCUIT

RCUE 120 WG2


RCUE 150 WG2

RCUE 100 WG2

Models

POWER CIRCUIT FOR RCUE 100WG2, RCUE 120WG2 and RCUE 150WG2

14/62 DRAWINGS

Main Switch

POWER CIRCUIT

RCUE 240 WG2

RCUE 200 WG2

RCUE 180 WG2

Models

POWER CIRCUIT FOR RCUE 180WG2, RCUE 200WG2 and RCUE 240WG2

DRAWINGS 14/63

CONTROL CIRCUIT

RCUE 80WG2

RCUE 60WG2

RCUE 50WG2

RCUE 40WG2

Models

CONTROL CIRCUIT FOR RCUE 40WG2, RCUE 50WG2, RCUE 60WG2 and RCUE 80WG2

14/64 DRAWINGS

CONTROL CIRCUIT

RCUE 150WG2

RCUE 120WG2

RCUE 100WG2

Models

CONTROL CIRCUIT FOR RCUE 100WG2, RCUE 120WG2, RCUE 150WG2

DRAWINGS 14/65

CONTROL CIRCUIT

RCUE 240WG2

RCUE 200WG2

RCUE 180WG2

Models

CONTROL CIRCUIT FOR RCUE 180WG2, RCUE 200WG2 and RCUE 240WG2

For 3 cycles units

MAIN PRINTED CIRCUIT BOARD (MASTER)

Option

For 3 cycles units

Differencial water Pressure


Switch (Condenser side)
(Option)
Differencial water Pressure
Switch (Evaporator side)
(Option)

Field
supply

For >2 cycles


units

For >3 cycles


units

14/66 DRAWINGS

MAIN PRINTED CIRCUIT BOARD

RELAYS PRINTED CIRCUIT BOARD

Free-cooling
Output signal
(only PCBd1)
Only for units with
Economizer

1
2
3

RCUE 40,50,60, 80WG2


RCUE 100,120, 150WG2
RCUE 180, 200, 240WG2

Model

Only PCBd1,3 and


PCBd2 in 3 cycles
units

Option

DRAWINGS 14/67

RELAYS PRINTED CIRCUIT BOARD

14/68 DRAWINGS
CUSTOMER WIRING

NOTE:
1. All the setting shall be performed before Power ON.
2. Remote/Local Change over Switch on Operation Switch shall be set to "Remote".
3. Terminals 1 n57  are for AC220-240V Terminals A D  are for DC24V. Terminals E F 
are H-Link (Low signal)

N
1
2
3
4
5
6
7
8
9
10
11
12

Name
In case of remote control operation this wire shall
be removed.
R Phase
Neutral
Low Voltage / Remote Control
Run/Stop Signal
Alarm Signal
Alarm Lamp
Pump Interlock
Pump operation
Remote Control Switch (RSW-A) (Option)
2,3 cycles
3 cycles

N
13
14
15
16
17
18
19
20
21
22

Name
2 nd. Setting Temperature
External Thermostat Operation
Operation Mode (OPTION)
Only used for:
-Diff. Water Pressure switch (OPTION)
-Flow Switch (OPTION)
Force Compressor Load Operation
Free Cooling
Output signal (Only cycle N 1)
In case of individual indication without Remote
Control Switch
Customer wiring
Force compressor load
Setting of low voltage control

DRAWINGS 14/69

PARTS LIST
(n=1~N)
Mark

Name

MC1-n
MI
CMC1-n

Compressor Motor
Main Isolator
Contactor for Compressor Motor
Contactor for Compressor Motor
(Start Operation)
Contactor for Compressor Motor
(Delta Operation)
Fuse holder for Compressor
Motor

CMCs1-sn
CMCD1-Dn
PFC1-n
EFC11-n3
ORC1-n
ITC1- n

Fuse for Compressor Motor

Remark

or optional
Circuit Breaker
or optional
Circuit Breaker

Overcurrent Relay for


Compressor Motor
Internal Thermostat for
Compressor

Mark

Name

Remark

EF1~5
SV11-n1
SV12-n2

Fuse
Solenoid Valve for Starting
Solenoid Valve for Load-down

6A

SV13-n3

Solenoid Valve for Load-up

TM1-n

Hour Meter

PCBA

Printed Circuit Board for Display

PCBB

Printed Circuit Board for Operation

PCBC1

Printed Circuit Board for CPU

PCBD1-Dn

Printed Circuit Board for Relay

CH1-n

Crankcase Heater

PCB F

AR,h,r,1-n

Auxiliary Relay

WPC

PSH1-n

High Pressure Switch

TF 1,2,3,4,5

Transformer

PBSR2

Pd1-n

High Pressure Sensor

RL(1-n)

Ps1-n

Low Pressure Sensor

OL(1-n, C, H)

EHF1-n

Cooler Heater
Inlet Water Temperature
Thermistor
Outlet Water Temperature
Thermistor
Suction Gas Temperature
Thermistor
Discharge Temperature
Thermistor
Temperature Thermistor Before
Exp. Valve
Outlet Water Temperature
Thermistor (Evap.)
Inlet Water Temperature
Thermistor (heat)
Outlet Water Temperature
Thermistor (heat)
Noise Filter (Ring Cores)

THMi
THMO 1,2,3
THMS1-n
THMd 1-n
THMr2 1-n
THMO 11~31
THMi (h)
THM O n(h)
MFA

OFF: 2.75Mpa
ON: Manual
Reset

PBSR1

Printed Circuit Board for Expansion


valve
Water Pressure Switch,
Water Flow Switch, Evaporator
Circuit
Push Button Switch for Starting
(REMOTE)

CMP1-2

Push Button Switch for Stoppage


(REMOTE)
Pilot Lamp for Remote Indication
(Unit Operation, Cool/Heat)
Pilot Lamp for Remote Indication
(Alarm)
Contactor for Pumps

TRP1-2

Thermal Relay for Pump

WPH

Water Pressure Switch, Water Flow


Switch, Condenser Circuit

CMT

Contactor for Tower

MVn

Electronic Expansion Valve (Exp V.)

PSWn

Pressure switch for Economizer

SVEn

Solenoid Valve for Economizer

OPTION

EHn

Electric Heater for Evaporator

OPTION

SW1~6

Switches field supplied

OPTION

Model
RCUE 40, 50, 60, 80 WG2
RCUE 100, 120, 150 WG2
RCUE 180, 200, 240 WG2

OPTION

N
1
2
3

Field
Supplied

15/70 MODEL SELECTION

15. MODEL SELECTION


15.1. SELECTION EXAMPLE
1. Determine the system requirements
Condenser Water Inlet Temperature:
Condenser Water Outlet Temperature:
Chilled Water Inlet Temperature:
Chilled Water Outlet Temperature:
Cooling Load:
2. Select Model and Read the Performance
From the cooling capacity table,
model RCUE100WG2 can be
selected with the following
performance.
Cooling Capacity:
Chilled Water Flow Rate:
Water Cooler Pressure Drop:
Condenser Water Flow Rate:
Condenser Pressure Drop:
Compressor Input Power:

32 C
37 C
12 C
7 C
300 kw

Fouling Factor
m2h C/kcal
(m2 C/kW)
Water
Cooler

Condenser
316.3 kW
54.4 m/h
36.9 kPa
68.7 m/h
67.5 kPa
83 kW

1.00

1.00

1.00

0.0001(0.086)

0.99

1.01

0
0.0001(0.086)
0.0002(0.172)

1.00
0.98
0.96

1.00
1.03
1.06

PD = x Q
Pressure Drop (kPa)
Water Flow (m/h)
Parameters (table below)

Model:

Parameter

Cooler

RCUE-WG2
40
50
60
80
100
120
150
180
200
240

0.0764
0.0648
0.0437
0.0374
0.0188
0.0188
0.0188
0.0053
0.0053
0.0046

1.912
1.912
1.912
1.912
1.897
1.897
1.897
1.912
1.912
1.912

40
50
60
80
100
120
150
180
200
240

0.0688
0.0480
0.0328
0.0358
0.0225
0.0160
0.0160
0.0041
0.0041
0.0044

1.872
1.881
1.897
1.912
1.893
1.901
1.901
1.897
1.897
1.912

Corrected Capacity = Kfc CAP


CAP:
IPT:
Kfc:
Kfi:

1.00

0.00005(0.043)

PD:
Q:

5(C) Tabulated Flow Rate (CFR)


Given Temp. Difference(C)

The corrected Flow Rate must be confirmed to be within


the working range.
2. Cooling Capacity and Compressor Input.
When the fouling factor is taken into consideration, the
cooling capacity and the compressor input will be
different from the value indicated in the cooling capacity
table.

Condenser

Kfi

4. Water Pressure Drop


Water pressure drop is given by the following formula

3. Correct the Data


1. Flow Rate
When the water Inlet/Outlet temperature difference is
not 5C, correct the flow rate by the following formula:
Corrected
Flow Rate

Kfc

Corrected Input = Kfi IPT


Tabulated Cooling Capacity
Tabulated Compressor Input
Capacity Correction Factor
Compressor Input Correction Factor

MODEL SELECTION 15/71

15.2. PERFORMANCE TABLE


RCUE40WG2
CDOT

22,0

25,0

30,0

35,0

37,0

40,0

45,0

CLOT

5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0

Where,
CDOT:
CLOT:
CCAP:
HCAP:

CCAP

137,9
140,9
143,9
147,0
150,0
153,1
156,1
159,1
162,2
165,2
168,3
135,4
138,5
141,6
144,8
147,9
151,0
154,1
157,2
160,3
163,5
166,6
131,3
134,6
137,8
141,1
144,3
147,5
150,8
154,0
157,3
160,5
163,8
127,3
130,6
134,0
137,4
140,7
144,1
147,5
150,8
154,2
157,6
160,9
125,6
129,1
132,5
135,9
139,3
142,7
146,1
149,6
153,0
156,4
159,8
123,2
126,7
130,2
133,7
137,2
140,7
144,1
147,6
151,1
154,6
158,1
119,1
122,7
126,4
130,0
133,6
137,2
140,8
144,4
148,0
151,7
155,3

CFR

23,7
24,2
24,8
25,3
25,8
26,3
26,8
27,4
27,9
28,4
28,9
23,3
23,8
24,4
24,9
25,4
26,0
26,5
27,0
27,6
28,1
28,7
22,6
23,1
23,7
24,3
24,8
25,4
25,9
26,5
27,1
27,6
28,2
21,9
22,5
23,0
23,6
24,2
24,8
25,4
25,9
26,5
27,1
27,7
21,6
22,2
22,8
23,4
24,0
24,5
25,1
25,7
26,3
26,9
27,5
21,2
21,8
22,4
23,0
23,6
24,2
24,8
25,4
26,0
26,6
27,2
20,5
21,1
21,7
22,4
23,0
23,6
24,2
24,8
25,5
26,1
26,7

CPD

32,5
33,9
35,3
36,8
38,3
39,7
41,3
42,8
44,4
46,0
47,6
31,4
32,8
34,3
35,7
37,2
38,7
40,3
41,8
43,4
45,1
46,7
29,7
31,1
32,5
34,0
35,5
37,1
38,6
40,2
41,9
43,5
45,2
27,9
29,4
30,8
32,3
33,9
35,4
37,0
38,6
40,3
42,0
43,7
27,2
28,7
30,2
31,7
33,2
34,8
36,4
38,0
39,7
41,4
43,2
26,2
27,7
29,2
30,7
32,2
33,8
35,4
37,1
38,8
40,5
42,3
24,6
26,1
27,5
29,1
30,6
32,2
33,9
35,6
37,3
39,1
40,9

HCAP

162,8
166,0
169,3
172,5
175,7
178,9
182,2
185,4
188,6
191,8
195,0
162,3
165,6
168,9
172,1
175,4
178,7
182,0
185,3
188,5
191,8
195,1
161,4
164,8
168,2
171,6
174,9
178,3
181,7
185,1
188,5
191,8
195,2
160,5
164,0
167,5
171,0
174,5
177,9
181,4
184,9
188,4
191,9
195,3
160,2
163,7
167,2
170,7
174,3
177,8
181,3
184,8
188,4
191,9
195,4
159,7
163,2
166,8
170,4
174,0
177,6
181,1
184,7
188,3
191,9
195,5
158,8
162,5
166,1
169,8
173,5
177,2
180,9
184,5
188,2
191,9
195,6

HFR

28,0
28,6
29,1
29,7
30,2
30,8
31,3
31,9
32,4
33,0
33,5
27,9
28,5
29,0
29,6
30,2
30,7
31,3
31,9
32,4
33,0
33,6
27,8
28,3
28,9
29,5
30,1
30,7
31,3
31,8
32,4
33,0
33,6
27,6
28,2
28,8
29,4
30,0
30,6
31,2
31,8
32,4
33,0
33,6
27,6
28,2
28,8
29,4
30,0
30,6
31,2
31,8
32,4
33,0
33,6
27,5
28,1
28,7
29,3
29,9
30,5
31,2
31,8
32,4
33,0
33,6
27,3
27,9
28,6
29,2
29,8
30,5
31,1
31,7
32,4
33,0
33,6

RCUE50WG2
HPD

35,2
36,5
37,8
39,2
40,6
42,0
43,4
44,8
46,3
47,8
49,3
35,0
36,3
37,6
39,0
40,4
41,9
43,3
44,8
46,3
47,8
49,3
34,6
36,0
37,4
38,8
40,2
41,7
43,2
44,7
46,2
47,8
49,4
34,2
35,6
37,1
38,5
40,0
41,5
43,1
44,6
46,2
47,8
49,4
34,1
35,5
37,0
38,4
39,9
41,5
43,0
44,6
46,2
47,8
49,5
33,9
35,3
36,8
38,3
39,8
41,4
42,9
44,5
46,2
47,8
49,5
33,5
35,0
36,5
38,0
39,6
41,2
42,8
44,5
46,1
47,8
49,6

Condenser Water Outlet Temperature (C)


Chilled Water Outlet Temperature (C)
Cooling Capacity (kW)
Condenser Heat Rejection (Kw)

IPT

25,0
25,2
25,3
25,5
25,7
25,9
26,0
26,2
26,4
26,6
26,8
26,9
27,1
27,2
27,4
27,5
27,7
27,9
28,0
28,2
28,4
28,5
30,1
30,2
30,4
30,5
30,6
30,8
30,9
31,1
31,2
31,3
31,5
33,3
33,4
33,5
33,6
33,7
33,8
34,0
34,1
34,2
34,3
34,4
34,5
34,7
34,8
34,9
35,0
35,1
35,2
35,3
35,4
35,5
35,6
36,5
36,6
36,6
36,7
36,8
36,9
37,0
37,1
37,2
37,3
37,4
39,7
39,7
39,8
39,8
39,9
40,0
40,0
40,1
40,2
40,2
40,3

CCAP

164,6
168,2
171,9
175,5
179,1
182,8
186,4
190,0
193,7
197,3
200,9
169,1
174,7
180,4
186,0
191,6
197,3
202,9
208,6
214,2
219,9
225,5
156,8
160,7
164,6
168,4
172,3
176,2
180,0
183,9
187,8
191,7
195,5
149,5
154,7
160,0
165,3
170,5
175,8
181,1
186,3
191,6
196,9
202,1
145,5
150,7
155,9
161,1
166,3
171,5
176,7
181,9
187,1
192,3
197,4
147,1
151,3
155,4
159,6
163,8
167,9
172,1
176,3
180,4
184,6
188,8
129,9
134,8
139,6
144,5
149,4
154,3
159,2
164,1
169,0
173,9
178,7

CFR

28,3
28,9
29,6
30,2
30,8
31,4
32,1
32,7
33,3
33,9
34,6
29,1
30,1
31,0
32,0
33,0
33,9
34,9
35,9
36,8
37,8
38,8
27,0
27,6
28,3
29,0
29,6
30,3
31,0
31,6
32,3
33,0
33,6
25,7
26,6
27,5
28,4
29,3
30,2
31,1
32,0
33,0
33,9
34,8
25,0
25,9
26,8
27,7
28,6
29,5
30,4
31,3
32,2
33,1
34,0
25,3
26,0
26,7
27,5
28,2
28,9
29,6
30,3
31,0
31,8
32,5
22,3
23,2
24,0
24,9
25,7
26,5
27,4
28,2
29,1
29,9
30,7

CPD

38,7
40,4
42,1
43,8
45,5
47,3
49,1
51,0
52,9
54,8
56,7
40,8
43,4
46,1
48,9
51,8
54,8
57,8
60,9
64,1
67,4
70,7
35,3
37,0
38,7
40,5
42,3
44,1
46,0
47,9
49,8
51,8
53,8
32,2
34,4
36,7
39,0
41,5
43,9
46,5
49,1
51,8
54,5
57,4
30,6
32,7
34,9
37,2
39,5
41,9
44,4
46,9
49,5
52,1
54,9
31,2
33,0
34,7
36,5
38,4
40,3
42,2
44,2
46,2
48,2
50,3
24,6
26,4
28,3
30,2
32,2
34,2
36,3
38,5
40,7
43,0
45,4

HCAP

194,4
198,3
202,1
206,0
209,8
213,6
217,5
221,3
225,2
229,0
232,9
201,2
207,0
212,9
218,7
224,5
230,4
236,2
242,1
247,9
253,7
259,6
192,7
196,8
200,8
204,8
208,9
212,9
217,0
221,0
225,0
229,1
233,1
189,2
194,6
200,0
205,4
210,8
216,2
221,6
227,0
232,4
237,8
243,2
186,8
192,1
197,4
202,7
208,1
213,4
218,7
224,0
229,3
234,6
239,9
190,6
194,9
199,2
203,5
207,7
212,0
216,3
220,6
224,8
229,1
233,4
177,2
182,2
187,1
192,1
197,1
202,0
207,0
212,0
216,9
221,9
226,9

HFR

33,4
34,1
34,8
35,4
36,1
36,7
37,4
38,1
38,7
39,4
40,1
34,6
35,6
36,6
37,6
38,6
39,6
40,6
41,6
42,6
43,6
44,6
33,2
33,8
34,5
35,2
35,9
36,6
37,3
38,0
38,7
39,4
40,1
32,5
33,5
34,4
35,3
36,3
37,2
38,1
39,0
40,0
40,9
41,8
32,1
33,0
34,0
34,9
35,8
36,7
37,6
38,5
39,4
40,4
41,3
32,8
33,5
34,3
35,0
35,7
36,5
37,2
37,9
38,7
39,4
40,1
30,5
31,3
32,2
33,0
33,9
34,8
35,6
36,5
37,3
38,2
39,0

RCUE60WG2
HPD

35,4
36,7
38,1
39,5
40,9
42,3
43,7
45,2
46,7
48,2
49,7
37,8
39,8
42,0
44,2
46,4
48,7
51,1
53,5
55,9
58,4
61,0
34,8
36,2
37,6
39,1
40,5
42,0
43,5
45,0
46,6
48,2
49,8
33,6
35,5
37,3
39,3
41,2
43,2
45,3
47,4
49,5
51,7
53,9
32,8
34,6
36,4
38,3
40,2
42,2
44,2
46,2
48,3
50,4
52,6
34,1
35,6
37,1
38,6
40,1
41,7
43,3
44,9
46,5
48,2
49,9
29,7
31,3
32,9
34,6
36,3
38,1
39,8
41,7
43,5
45,4
47,3

HFR: Condenser Water Flow Rate at 5C (m3/h)


HPD:Condenser Water Pressure Drop (kPa)
CFR:Chilled Water Flow Rate at 5C (m3/h)
CPD:
Water Cooler Pressure Drop (kPa)
IPT:
Compressor Input Power (kW)

IPT

29,8
30,0
30,2
30,5
30,7
30,9
31,1
31,3
31,5
31,7
32,0
32,1
32,3
32,5
32,7
32,9
33,1
33,3
33,5
33,7
33,9
34,1
35,9
36,1
36,2
36,4
36,6
36,7
36,9
37,1
37,2
37,4
37,6
39,7
39,9
40,0
40,1
40,3
40,4
40,5
40,7
40,8
41,0
41,1
41,2
41,4
41,5
41,6
41,8
41,9
42,0
42,1
42,3
42,4
42,5
43,5
43,6
43,8
43,9
44,0
44,1
44,2
44,3
44,4
44,5
44,6
47,3
47,4
47,5
47,6
47,7
47,7
47,8
47,9
48,0
48,1
48,1

CCAP

199,6
204,0
208,4
212,8
217,2
221,6
226,0
230,4
234,8
239,2
243,6
205,0
211,8
218,7
225,5
232,4
239,2
246,1
252,9
259,7
266,6
273,4
190,1
194,8
199,5
204,2
208,9
213,6
218,3
223,0
227,7
232,4
237,1
181,2
187,6
194,0
200,4
206,8
213,2
219,5
225,9
232,3
238,7
245,1
176,5
182,8
189,1
195,4
201,6
207,9
214,2
220,5
226,8
233,1
239,4
178,4
183,4
188,5
193,5
198,6
203,6
208,7
213,7
218,8
223,8
228,9
157,5
163,4
169,3
175,2
181,2
187,1
193,0
198,9
204,9
210,8
216,7

CFR

34,3
35,1
35,8
36,6
37,4
38,1
38,9
39,6
40,4
41,1
41,9
35,3
36,4
37,6
38,8
40,0
41,1
42,3
43,5
44,7
45,9
47,0
32,7
33,5
34,3
35,1
35,9
36,7
37,5
38,4
39,2
40,0
40,8
31,2
32,3
33,4
34,5
35,6
36,7
37,8
38,9
40,0
41,1
42,2
30,4
31,4
32,5
33,6
34,7
35,8
36,8
37,9
39,0
40,1
41,2
30,7
31,5
32,4
33,3
34,2
35,0
35,9
36,8
37,6
38,5
39,4
27,1
28,1
29,1
30,1
31,2
32,2
33,2
34,2
35,2
36,3
37,3

CPD

37,8
39,4
41,0
42,7
44,4
46,1
47,9
49,7
51,5
53,4
55,3
39,8
42,3
45,0
47,7
50,5
53,4
56,4
59,4
62,5
65,7
68,9
34,4
36,1
37,7
39,5
41,2
43,0
44,8
46,7
48,6
50,5
52,5
31,4
33,6
35,8
38,1
40,4
42,8
45,3
47,9
50,5
53,2
55,9
29,8
31,9
34,1
36,3
38,5
40,8
43,2
45,7
48,2
50,8
53,5
30,5
32,1
33,8
35,6
37,4
39,2
41,1
43,1
45,0
47,0
49,1
24,0
25,8
27,6
29,4
31,4
33,4
35,4
37,5
39,7
41,9
44,2

HCAP

HFR

236,2
240,8
245,5
250,2
254,8
259,5
264,2
268,8
273,5
278,2
282,8
244,4
251,5
258,6
265,7
272,7
279,8
286,9
294,0
301,1
308,2
315,2
234,2
239,1
244,0
248,9
253,8
258,7
263,6
268,5
273,4
278,3
283,2
230,0
236,5
243,1
249,7
256,2
262,8
269,3
275,9
282,4
289,0
295,5
227,1
233,6
240,0
246,5
252,9
259,3
265,8
272,2
278,7
285,1
291,6
231,8
237,0
242,2
247,4
252,5
257,7
262,9
268,1
273,3
278,5
283,7
215,6
221,6
227,6
233,6
239,7
245,7
251,7
257,7
263,8
269,8
275,8

Conversion Multiplier:
1 kW = 860 kcal/h
= 3412 Btu/h
1 kPa = 0.102 mAq

40,6
41,4
42,2
43,0
43,8
44,6
45,4
46,2
47,0
47,8
48,6
42,0
43,3
44,5
45,7
46,9
48,1
49,3
50,6
51,8
53,0
54,2
40,3
41,1
42,0
42,8
43,7
44,5
45,3
46,2
47,0
47,9
48,7
39,6
40,7
41,8
42,9
44,1
45,2
46,3
47,4
48,6
49,7
50,8
39,1
40,2
41,3
42,4
43,5
44,6
45,7
46,8
47,9
49,0
50,2
39,9
40,8
41,7
42,5
43,4
44,3
45,2
46,1
47,0
47,9
48,8
37,1
38,1
39,2
40,2
41,2
42,3
43,3
44,3
45,4
46,4
47,4

HPD

37,0
38,4
39,8
41,2
42,7
44,2
45,7
47,3
48,8
50,4
52,0
39,5
41,7
43,9
46,2
48,6
51,0
53,5
56,0
58,6
61,2
63,9
36,4
37,9
39,3
40,8
42,4
44,0
45,5
47,2
48,8
50,5
52,2
35,2
37,1
39,1
41,1
43,1
45,3
47,4
49,6
51,9
54,2
56,6
34,3
36,2
38,1
40,1
42,1
44,2
46,3
48,4
50,6
52,9
55,1
35,7
37,2
38,8
40,4
42,0
43,6
45,3
47,0
48,8
50,5
52,3
31,1
32,8
34,5
36,2
38,0
39,8
41,7
43,6
45,6
47,6
49,6

IPT

36,6
36,9
37,1
37,4
37,7
37,9
38,2
38,4
38,7
39,0
39,2
39,4
39,7
39,9
40,1
40,4
40,6
40,9
41,1
41,3
41,6
41,8
44,1
44,3
44,5
44,7
44,9
45,1
45,3
45,5
45,7
45,9
46,1
48,8
48,9
49,1
49,3
49,4
49,6
49,8
49,9
50,1
50,3
50,4
50,6
50,8
50,9
51,1
51,3
51,4
51,6
51,7
51,9
52,0
52,2
53,4
53,6
53,7
53,8
54,0
54,1
54,2
54,4
54,5
54,6
54,8
58,1
58,2
58,3
58,4
58,5
58,6
58,7
58,8
58,9
59,0
59,1

15/72 MODEL SELECTION


Performance Table (cont.)
RCUE80WG2
CDOT

22,0

25,0

30,0

35,0

37,0

40,0

45,0

CLOT

5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0

Where,
CDOT:
CLOT:
CCAP:
HCAP:

CCAP

238,7
243,9
249,2
254,5
259,7
265,0
270,3
275,5
280,8
286,1
291,3
234,4
239,8
245,2
250,6
256,0
261,4
266,8
272,2
277,6
283,0
288,4
227,4
233,0
238,6
244,2
249,8
255,5
261,1
266,7
272,3
277,9
283,5
220,3
226,2
232,0
237,8
243,7
249,5
255,3
261,1
267,0
272,8
278,6
217,5
223,4
229,4
235,3
241,2
247,1
253,0
258,9
264,8
270,8
276,7
213,3
219,3
225,4
231,4
237,5
243,5
249,6
255,6
261,6
267,7
273,7
206,2
212,5
218,8
225,0
231,3
237,5
243,8
250,1
256,3
262,6
268,8

CFR

41,1
42,0
42,9
43,8
44,7
45,6
46,5
47,4
48,3
49,2
50,1
40,3
41,3
42,2
43,1
44,0
45,0
45,9
46,8
47,7
48,7
49,6
39,1
40,1
41,0
42,0
43,0
43,9
44,9
45,9
46,8
47,8
48,8
37,9
38,9
39,9
40,9
41,9
42,9
43,9
44,9
45,9
46,9
47,9
37,4
38,4
39,4
40,5
41,5
42,5
43,5
44,5
45,6
46,6
47,6
36,7
37,7
38,8
39,8
40,8
41,9
42,9
44,0
45,0
46,0
47,1
35,5
36,6
37,6
38,7
39,8
40,9
41,9
43,0
44,1
45,2
46,2

CPD

45,5
47,4
49,4
51,4
53,5
55,6
57,7
59,9
62,1
64,3
66,6
44,0
45,9
47,9
50,0
52,0
54,2
56,3
58,5
60,8
63,0
65,3
41,5
43,5
45,5
47,6
49,7
51,8
54,0
56,3
58,5
60,9
63,2
39,1
41,1
43,1
45,2
47,3
49,5
51,8
54,0
56,4
58,8
61,2
38,1
40,1
42,2
44,3
46,4
48,6
50,9
53,2
55,5
57,9
60,4
36,7
38,7
40,8
42,9
45,1
47,3
49,6
51,9
54,2
56,7
59,1
34,4
36,4
38,5
40,7
42,8
45,1
47,4
49,7
52,2
54,6
57,1

HCAP

279,3
284,9
290,4
296,0
301,5
307,1
312,6
318,2
323,8
329,3
334,9
278,2
283,8
289,5
295,2
300,8
306,5
312,2
317,8
323,5
329,2
334,8
276,3
282,2
288,0
293,8
299,7
305,5
311,4
317,2
323,0
328,9
334,7
274,5
280,5
286,5
292,5
298,5
304,5
310,6
316,6
322,6
328,6
334,6
273,7
279,8
285,9
292,0
298,1
304,2
310,2
316,3
322,4
328,5
334,6
272,6
278,8
285,0
291,2
297,4
303,6
309,8
315,9
322,1
328,3
334,5
270,8
277,1
283,5
289,9
296,2
302,6
309,0
315,3
321,7
328,1
334,4

HFR

48,0
49,0
50,0
50,9
51,9
52,8
53,8
54,7
55,7
56,6
57,6
47,8
48,8
49,8
50,8
51,7
52,7
53,7
54,7
55,6
56,6
57,6
47,5
48,5
49,5
50,5
51,5
52,5
53,6
54,6
55,6
56,6
57,6
47,2
48,2
49,3
50,3
51,3
52,4
53,4
54,5
55,5
56,5
57,6
47,1
48,1
49,2
50,2
51,3
52,3
53,4
54,4
55,5
56,5
57,5
46,9
48,0
49,0
50,1
51,1
52,2
53,3
54,3
55,4
56,5
57,5
46,6
47,7
48,8
49,9
51,0
52,0
53,1
54,2
55,3
56,4
57,5

RCUE100WG2
HPD

58,8
61,1
63,4
65,7
68,1
70,5
73,0
75,5
78,0
80,6
83,2
58,4
60,7
63,0
65,4
67,8
70,3
72,8
75,3
77,9
80,5
83,2
57,6
60,0
62,4
64,8
67,3
69,8
72,4
75,0
77,7
80,4
83,2
56,9
59,3
61,8
64,3
66,8
69,4
72,1
74,8
77,5
80,3
83,1
56,6
59,0
61,5
64,0
66,6
69,2
71,9
74,6
77,4
80,2
83,1
56,2
58,6
61,1
63,7
66,3
69,0
71,7
74,5
77,3
80,2
83,1
55,4
58,0
60,5
63,2
65,8
68,6
71,4
74,2
77,1
80,0
83,0

Condenser Water Outlet Temperature (C)


Chilled Water Outlet Temperature (C)
Cooling Capacity (kW)
Condenser Heat Rejection (Kw)

IPT

40,6
40,9
41,2
41,5
41,8
42,1
42,4
42,7
43,0
43,2
43,5
43,7
44,0
44,3
44,5
44,8
45,1
45,3
45,6
45,9
46,1
46,4
48,9
49,2
49,4
49,6
49,8
50,1
50,3
50,5
50,8
51,0
51,2
54,1
54,3
54,5
54,7
54,9
55,1
55,2
55,4
55,6
55,8
56,0
56,2
56,4
56,5
56,7
56,9
57,1
57,2
57,4
57,6
57,7
57,9
59,3
59,5
59,6
59,8
59,9
60,1
60,2
60,3
60,5
60,6
60,8
64,5
64,6
64,7
64,8
64,9
65,0
65,2
65,3
65,4
65,5
65,6

CCAP

329,2
336,5
343,7
351,0
358,3
365,5
372,8
380,0
387,3
394,6
401,8
323,4
330,8
338,3
345,7
353,1
360,6
368,0
375,5
382,9
390,3
397,8
313,6
321,4
329,1
336,9
344,6
352,3
360,1
367,8
375,6
383,3
391,0
303,9
312,0
320,0
328,0
336,1
344,1
352,2
360,2
368,2
376,3
384,3
300,0
308,2
316,3
324,5
332,7
340,8
349,0
357,1
365,3
373,4
381,6
294,2
302,5
310,9
319,2
327,5
335,9
344,2
352,6
360,9
369,2
377,6
284,5
293,1
301,7
310,4
319,0
327,6
336,3
344,9
353,5
362,2
370,8

CFR

56,6
57,9
59,1
60,4
61,6
62,9
64,1
65,4
66,6
67,9
69,1
55,6
56,9
58,2
59,5
60,7
62,0
63,3
64,6
65,9
67,1
68,4
53,9
55,3
56,6
57,9
59,3
60,6
61,9
63,3
64,6
65,9
67,3
52,3
53,7
55,0
56,4
57,8
59,2
60,6
62,0
63,3
64,7
66,1
51,6
53,0
54,4
55,8
57,2
58,6
60,0
61,4
62,8
64,2
65,6
50,6
52,0
53,5
54,9
56,3
57,8
59,2
60,6
62,1
63,5
64,9
48,9
50,4
51,9
53,4
54,9
56,4
57,8
59,3
60,8
62,3
63,8

CPD

39,8
41,5
43,2
44,9
46,7
48,5
50,4
52,3
54,2
56,1
58,1
38,5
40,2
41,9
43,7
45,5
47,3
49,2
51,1
53,0
55,0
57,0
36,3
38,0
39,8
41,6
43,4
45,3
47,2
49,1
51,1
53,1
55,2
34,2
35,9
37,7
39,5
41,4
43,3
45,2
47,2
49,2
51,3
53,4
33,4
35,1
36,9
38,7
40,6
42,5
44,4
46,4
48,5
50,5
52,7
32,1
33,9
35,7
37,5
39,4
41,3
43,3
45,3
47,4
49,5
51,6
30,2
31,9
33,7
35,6
37,5
39,4
41,4
43,5
45,6
47,7
49,9

HCAP

388,8
396,5
404,2
411,9
419,6
427,3
435,0
442,7
450,4
458,1
465,8
387,6
395,4
403,2
411,1
418,9
426,8
434,6
442,4
450,3
458,1
465,9
385,5
393,5
401,6
409,7
417,8
425,8
433,9
442,0
450,1
458,1
466,2
383,4
391,7
400,0
408,3
416,6
424,9
433,3
441,6
449,9
458,2
466,5
382,5
390,9
399,4
407,8
416,2
424,6
433,0
441,4
449,8
458,2
466,6
381,3
389,8
398,4
406,9
415,5
424,0
432,6
441,1
449,7
458,2
466,8
379,2
388,0
396,8
405,5
414,3
423,1
431,9
440,7
449,5
458,3
467,1

HFR

66,9
68,2
69,5
70,8
72,2
73,5
74,8
76,1
77,5
78,8
80,1
66,7
68,0
69,4
70,7
72,1
73,4
74,7
76,1
77,4
78,8
80,1
66,3
67,7
69,1
70,5
71,9
73,2
74,6
76,0
77,4
78,8
80,2
65,9
67,4
68,8
70,2
71,7
73,1
74,5
75,9
77,4
78,8
80,2
65,8
67,2
68,7
70,1
71,6
73,0
74,5
75,9
77,4
78,8
80,3
65,6
67,0
68,5
70,0
71,5
72,9
74,4
75,9
77,3
78,8
80,3
65,2
66,7
68,2
69,8
71,3
72,8
74,3
75,8
77,3
78,8
80,3

RCUE120WG2
HPD

64,2
66,6
69,1
71,6
74,2
76,8
79,4
82,1
84,8
87,6
90,4
63,8
66,3
68,8
71,3
73,9
76,6
79,3
82,0
84,8
87,6
90,4
63,2
65,7
68,3
70,9
73,6
76,3
79,0
81,8
84,7
87,6
90,5
62,5
65,1
67,8
70,4
73,2
76,0
78,8
81,7
84,6
87,6
90,6
62,3
64,9
67,5
70,3
73,0
75,8
78,7
81,6
84,6
87,6
90,7
61,9
64,5
67,2
70,0
72,8
75,7
78,6
81,5
84,6
87,6
90,8
61,2
63,9
66,7
69,5
72,4
75,4
78,3
81,4
84,5
87,7
90,9

HFR: Condenser Water Flow Rate at 5C (m3/h)


HPD:Condenser Water Pressure Drop (kPa)
CFR:Chilled Water Flow Rate at 5C (m3/h)
CPD:
Water Cooler Pressure Drop (kPa)
IPT:
Compressor Input Power (kW)

IPT

59,6
60,1
60,5
60,9
61,3
61,8
62,2
62,6
63,1
63,5
63,9
64,2
64,6
65,0
65,4
65,8
66,2
66,6
67,0
67,3
67,7
68,1
71,8
72,2
72,5
72,8
73,2
73,5
73,8
74,2
74,5
74,8
75,2
79,5
79,7
80,0
80,3
80,5
80,8
81,1
81,4
81,6
81,9
82,2
82,5
82,7
83,0
83,3
83,5
83,8
84,0
84,3
84,5
84,8
85,0
87,1
87,3
87,5
87,7
87,9
88,2
88,4
88,6
88,8
89,0
89,2
94,7
94,8
95,0
95,2
95,3
95,5
95,6
95,8
95,9
96,1
96,3

CCAP

399,2
408,0
416,8
425,6
434,4
443,2
452,0
460,8
469,6
478,4
487,2
392,1
401,1
410,1
419,2
428,2
437,2
446,2
455,3
464,3
473,3
482,3
380,3
389,7
399,1
408,4
417,8
427,2
436,6
446,0
455,4
464,8
474,1
368,5
378,3
388,0
397,7
407,5
417,2
427,0
436,7
446,5
456,2
466,0
363,8
373,7
383,6
393,5
403,4
413,2
423,1
433,0
442,9
452,8
462,7
356,7
366,8
376,9
387,0
397,1
407,3
417,4
427,5
437,6
447,7
457,8
344,9
355,4
365,9
376,3
386,8
397,3
407,7
418,2
428,7
439,1
449,6

CFR

68,7
70,2
71,7
73,2
74,7
76,2
77,7
79,3
80,8
82,3
83,8
67,4
69,0
70,5
72,1
73,6
75,2
76,8
78,3
79,9
81,4
83,0
65,4
67,0
68,6
70,3
71,9
73,5
75,1
76,7
78,3
79,9
81,6
63,4
65,1
66,7
68,4
70,1
71,8
73,4
75,1
76,8
78,5
80,1
62,6
64,3
66,0
67,7
69,4
71,1
72,8
74,5
76,2
77,9
79,6
61,4
63,1
64,8
66,6
68,3
70,0
71,8
73,5
75,3
77,0
78,7
59,3
61,1
62,9
64,7
66,5
68,3
70,1
71,9
73,7
75,5
77,3

CPD

57,3
59,8
62,2
64,8
67,3
69,9
72,6
75,3
78,1
80,9
83,7
55,4
57,9
60,4
62,9
65,5
68,2
70,9
73,6
76,4
79,2
82,1
52,3
54,8
57,3
59,9
62,5
65,2
68,0
70,8
73,6
76,5
79,5
49,3
51,8
54,3
57,0
59,6
62,4
65,2
68,0
70,9
73,9
76,9
48,1
50,6
53,2
55,8
58,5
61,2
64,1
66,9
69,9
72,8
75,9
46,3
48,9
51,4
54,1
56,8
59,6
62,4
65,3
68,3
71,3
74,4
43,5
46,0
48,6
51,3
54,0
56,8
59,7
62,7
65,7
68,7
71,9

HCAP

HFR

472,4
481,7
491,0
500,4
509,7
519,0
528,4
537,7
547,0
556,4
565,7
470,9
480,4
489,9
499,4
508,9
518,4
527,9
537,4
546,9
556,5
566,0
468,5
478,3
488,1
497,9
507,6
517,4
527,2
537,0
546,8
556,6
566,4
466,0
476,1
486,2
496,3
506,4
516,4
526,5
536,6
546,7
556,8
566,9
465,1
475,3
485,5
495,7
505,9
516,1
526,3
536,5
546,7
556,8
567,0
463,6
474,0
484,3
494,7
505,1
515,5
525,8
536,2
546,6
556,9
567,3
461,2
471,8
482,5
493,1
503,8
514,5
525,1
535,8
546,5
557,1
567,8

Conversion Multiplier:
1 kW = 860 kcal/h
= 3412 Btu/h
1 kPa = 0.102 mAq

81,2
82,9
84,5
86,1
87,7
89,3
90,9
92,5
94,1
95,7
97,3
81,0
82,6
84,3
85,9
87,5
89,2
90,8
92,4
94,1
95,7
97,3
80,6
82,3
83,9
85,6
87,3
89,0
90,7
92,4
94,1
95,7
97,4
80,2
81,9
83,6
85,4
87,1
88,8
90,6
92,3
94,0
95,8
97,5
80,0
81,7
83,5
85,3
87,0
88,8
90,5
92,3
94,0
95,8
97,5
79,7
81,5
83,3
85,1
86,9
88,7
90,4
92,2
94,0
95,8
97,6
79,3
81,2
83,0
84,8
86,7
88,5
90,3
92,2
94,0
95,8
97,7

HPD

68,3
70,9
73,6
76,2
79,0
81,7
84,6
87,4
90,3
93,3
96,3
67,9
70,6
73,2
76,0
78,7
81,6
84,4
87,3
90,3
93,3
96,4
67,3
70,0
72,7
75,5
78,4
81,3
84,2
87,2
90,3
93,4
96,5
66,6
69,4
72,2
75,1
78,0
81,0
84,0
87,1
90,2
93,4
96,7
66,3
69,1
72,0
74,9
77,8
80,9
83,9
87,0
90,2
93,4
96,7
65,9
68,8
71,7
74,6
77,6
80,7
83,8
87,0
90,2
93,5
96,8
65,3
68,2
71,1
74,2
77,2
80,4
83,6
86,8
90,1
93,5
97,0

IPT

73,2
73,7
74,3
74,8
75,3
75,8
76,4
76,9
77,4
77,9
78,5
78,8
79,3
79,8
80,3
80,7
81,2
81,7
82,2
82,7
83,2
83,6
88,2
88,6
89,0
89,4
89,8
90,2
90,6
91,0
91,4
91,9
92,3
97,5
97,9
98,2
98,5
98,9
99,2
99,5
99,9
100,2
100,6
100,9
101,3
101,6
101,9
102,2
102,5
102,8
103,1
103,4
103,7
104,0
104,4
106,9
107,1
107,4
107,7
107,9
108,2
108,5
108,7
109,0
109,3
109,5
116,2
116,4
116,6
116,8
117,0
117,2
117,4
117,6
117,8
118,0
118,2

MODEL SELECTION 15/73


Performance Table (R407C) (cont.)
RCUE 150 WG2
CDOT

22,0

25,0

30,0

35,0

37,0

40,0

45,0

Where,
CDOT:
CLOT:
CCAP:
HCAP:

CLOT

5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0

CCAP

457,8
467,9
478,0
488,1
498,2
508,3
518,4
528,5
538,6
548,7
558,8
449,7
460,0
470,4
480,7
491,1
501,4
511,8
522,1
532,5
542,8
553,2
436,2
446,9
457,7
468,5
479,2
490,0
500,7
511,5
522,3
533,0
543,8
422,6
433,8
445,0
456,2
467,4
478,5
489,7
500,9
512,1
523,2
534,4
417,2
428,6
439,9
451,3
462,6
474,0
485,3
496,6
508,0
519,3
530,7
409,1
420,7
432,3
443,9
455,5
467,1
478,7
490,3
501,9
513,5
525,0
395,6
407,6
419,6
431,6
443,6
455,6
467,6
479,6
491,7
503,7
515,7

CFR

78,7
80,5
82,2
84,0
85,7
87,4
89,2
90,9
92,6
94,4
96,1
77,3
79,1
80,9
82,7
84,5
86,2
88,0
89,8
91,6
93,4
95,1
75,0
76,9
78,7
80,6
82,4
84,3
86,1
88,0
89,8
91,7
93,5
72,7
74,6
76,5
78,5
80,4
82,3
84,2
86,2
88,1
90,0
91,9
71,8
73,7
75,7
77,6
79,6
81,5
83,5
85,4
87,4
89,3
91,3
70,4
72,4
74,4
76,4
78,3
80,3
82,3
84,3
86,3
88,3
90,3
68,0
70,1
72,2
74,2
76,3
78,4
80,4
82,5
84,6
86,6
88,7

RCUE 180 WG2

CPD

HCAP

HFR

HPD

IPT

CCAP

CFR

74,4
77,5
80,7
84,0
87,3
90,7
94,2
97,7
101,2
104,9
108,6
71,9
75,1
78,3
81,6
85,0
88,4
91,9
95,5
99,1
102,8
106,5
67,9
71,1
74,3
77,7
81,1
84,6
88,2
91,8
95,5
99,3
103,1
63,9
67,2
70,5
73,9
77,4
80,9
84,5
88,2
92,0
95,8
99,8
62,4
65,6
69,0
72,4
75,9
79,4
83,1
86,8
90,6
94,5
98,4
60,1
63,4
66,7
70,2
73,7
77,3
80,9
84,7
88,5
92,5
96,5
56,4
59,7
63,1
66,5
70,1
73,7
77,4
81,3
85,2
89,1
93,2

535,7
546,4
557,0
567,7
578,3
589,0
599,7
610,3
621,0
631,6
642,3
533,6
544,4
555,3
566,1
577,0
587,9
598,7
609,6
620,5
631,3
642,2
530,0
541,2
552,4
563,6
574,8
586,0
597,2
608,4
619,6
630,8
642,0
526,4
538,0
549,5
561,0
572,6
584,1
595,6
607,2
618,7
630,3
641,8
525,0
536,7
548,3
560,0
571,7
583,4
595,0
606,7
618,4
630,0
641,7
522,9
534,7
546,6
558,5
570,4
582,2
594,1
606,0
617,9
629,7
641,6
519,3
531,5
543,7
555,9
568,1
580,4
592,6
604,8
617,0
629,2
641,4

92,1
94,0
95,8
97,6
99,5
101,3
103,1
105,0
106,8
108,6
110,5
91,8
93,6
95,5
97,4
99,2
101,1
103,0
104,8
106,7
108,6
110,5
91,2
93,1
95,0
96,9
98,9
100,8
102,7
104,6
106,6
108,5
110,4
90,5
92,5
94,5
96,5
98,5
100,5
102,5
104,4
106,4
108,4
110,4
90,3
92,3
94,3
96,3
98,3
100,3
102,3
104,4
106,4
108,4
110,4
89,9
92,0
94,0
96,1
98,1
100,1
102,2
104,2
106,3
108,3
110,4
89,3
91,4
93,5
95,6
97,7
99,8
101,9
104,0
106,1
108,2
110,3

86,8
90,1
93,5
96,9
100,4
104,0
107,6
111,2
114,9
118,7
122,6
86,1
89,5
92,9
96,4
100,0
103,6
107,2
111,0
114,8
118,6
122,5
85,1
88,5
92,0
95,6
99,2
102,9
106,7
110,6
114,5
118,4
122,5
84,0
87,5
91,1
94,8
98,5
102,3
106,2
110,1
114,2
118,2
122,4
83,5
87,1
90,7
94,4
98,2
102,1
106,0
110,0
114,0
118,2
122,4
82,9
86,5
90,2
94,0
97,8
101,7
105,7
109,7
113,8
118,0
122,3
81,8
85,5
89,3
93,1
97,1
101,1
105,2
109,3
113,5
117,9
122,2

77,9
78,5
79,0
79,6
80,1
80,7
81,3
81,8
82,4
82,9
83,5
83,9
84,4
84,9
85,4
85,9
86,4
86,9
87,5
88,0
88,5
89,0
93,8
94,3
94,7
95,1
95,6
96,0
96,4
96,9
97,3
97,7
98,2
103,8
104,1
104,5
104,9
105,2
105,6
105,9
106,3
106,7
107,0
107,4
107,8
108,1
108,4
108,7
109,1
109,4
109,7
110,1
110,4
110,7
111,0
113,7
114,0
114,3
114,6
114,9
115,1
115,4
115,7
116,0
116,3
116,6
123,7
123,9
124,1
124,3
124,5
124,7
124,9
125,1
125,3
125,5
125,7

540,1
552,0
563,9
575,8
587,8
599,7
611,6
623,5
635,4
647,3
659,3
530,5
542,7
554,9
567,2
579,4
591,6
603,8
616,0
628,2
640,4
652,6
514,6
527,3
540,0
552,7
565,4
578,1
590,8
603,5
616,2
628,9
641,6
498,6
511,8
525,0
538,2
551,4
564,6
577,7
590,9
604,1
617,3
630,5
492,2
505,6
519,0
532,4
545,8
559,2
572,5
585,9
599,3
612,7
626,1
458,3
474,9
491,6
508,2
524,9
541,6
558,2
574,9
591,5
608,2
624,8
466,7
480,9
495,1
509,2
523,4
537,5
551,7
565,9
580,0
594,2
608,4

92,9
94,9
97,0
99,0
101,1
103,1
105,2
107,2
109,3
111,3
113,4
91,2
93,3
95,5
97,6
99,7
101,8
103,9
106,0
108,1
110,2
112,3
88,5
90,7
92,9
95,1
97,2
99,4
101,6
103,8
106,0
108,2
110,3
85,8
88,0
90,3
92,6
94,8
97,1
99,4
101,6
103,9
106,2
108,4
84,7
87,0
89,3
91,6
93,9
96,2
98,5
100,8
103,1
105,4
107,7
78,8
81,7
84,6
87,4
90,3
93,1
96,0
98,9
101,7
104,6
107,5
80,3
82,7
85,1
87,6
90,0
92,5
94,9
97,3
99,8
102,2
104,6

Condenser Water Outlet Temperature (C)


Chilled Water Outlet Temperature (C)
Cooling Capacity (kW)
Condenser Heat Rejection (Kw)

CPD

31,0
32,3
33,7
35,1
36,5
37,9
39,3
40,8
42,3
43,8
45,4
30,0
31,3
32,7
34,0
35,5
36,9
38,4
39,9
41,4
43,0
44,5
28,3
29,6
31,0
32,4
33,8
35,3
36,8
38,3
39,9
41,5
43,1
26,6
28,0
29,4
30,8
32,3
33,8
35,3
36,8
38,4
40,0
41,7
26,0
27,3
28,7
30,2
31,6
33,1
34,7
36,2
37,8
39,5
41,1
22,6
24,3
25,9
27,6
29,4
31,2
33,0
34,9
36,9
38,9
41,0
23,5
24,8
26,3
27,7
29,2
30,7
32,3
33,9
35,5
37,2
38,9

HFR: Condenser Water Flow Rate at 5C (m3/h)


HPD:Condenser Water Pressure Drop (kPa)
CFR:Chilled Water Flow Rate at 5C (m3/h)
CPD:
Water Cooler Pressure Drop (kPa)
IPT:
Compressor Input Power (kW)

HCAP

HFR

632,2
644,7
657,3
669,9
682,5
695,0
707,6
720,2
732,8
745,4
757,9
629,6
642,5
655,3
668,1
680,9
693,7
706,5
719,4
732,2
745,0
757,8
625,5
638,7
651,9
665,1
678,3
691,5
704,7
718,0
731,2
744,4
757,6
621,3
634,9
648,5
662,1
675,7
689,3
702,9
716,6
730,2
743,8
757,4
619,6
633,4
647,1
660,9
674,7
688,5
702,2
716,0
729,8
743,5
757,3
592,7
609,7
626,7
643,7
660,7
677,6
694,6
711,6
728,6
745,6
762,6
612,9
627,3
641,7
656,1
670,5
684,9
699,3
713,8
728,2
742,6
757,0

108,7
110,9
113,1
115,2
117,4
119,5
121,7
123,9
126,0
128,2
130,4
108,3
110,5
112,7
114,9
117,1
119,3
121,5
123,7
125,9
128,1
130,3
107,6
109,9
112,1
114,4
116,7
118,9
121,2
123,5
125,8
128,0
130,3
106,9
109,2
111,5
113,9
116,2
118,6
120,9
123,2
125,6
127,9
130,3
106,6
108,9
111,3
113,7
116,0
118,4
120,8
123,2
125,5
127,9
130,3
101,9
104,9
107,8
110,7
113,6
116,6
119,5
122,4
125,3
128,2
131,2
105,4
107,9
110,4
112,9
115,3
117,8
120,3
122,8
125,2
127,7
130,2

HPD

29,8
30,9
32,1
33,2
34,4
35,6
36,9
38,1
39,4
40,7
42,0
29,6
30,7
31,9
33,1
34,3
35,5
36,8
38,1
39,3
40,7
42,0
29,2
30,4
31,6
32,8
34,0
35,3
36,6
37,9
39,2
40,6
42,0
28,8
30,0
31,3
32,5
33,8
35,1
36,4
37,8
39,1
40,5
42,0
28,7
29,9
31,1
32,4
33,7
35,0
36,3
37,7
39,1
40,5
41,9
26,4
27,8
29,3
30,8
32,4
34,0
35,6
37,3
39,0
40,7
42,5
28,1
29,3
30,6
32,0
33,3
34,7
36,1
37,5
38,9
40,4
41,9

IPT

92,1
92,7
93,4
94,0
94,7
95,4
96,0
96,7
97,3
98,0
98,7
99,1
99,7
100,3
100,9
101,5
102,2
102,8
103,4
104,0
104,6
105,2
110,9
111,4
111,9
112,4
112,9
113,5
114,0
114,5
115,0
115,5
116,0
122,7
123,1
123,5
123,9
124,3
124,8
125,2
125,6
126,0
126,5
126,9
127,4
127,7
128,1
128,5
128,9
129,3
129,7
130,1
130,5
130,8
131,2
134,4
134,7
135,1
135,4
135,7
136,1
136,4
136,7
137,1
137,4
137,7
146,2
146,4
146,7
146,9
147,1
147,4
147,6
147,9
148,1
148,4
148,6

Conversion Multiplier:
1 kW = 860 kcal/h
= 3412 Btu/h
1 kPa = 0.102 mAq

15/74 MODEL SELECTION


Performance Table (cont.)
RCUE 200 WG2
CDOT

22,0

25,0

30,0

35,0

37,0

40,0

45,0

Where,
CDOT:
CLOT:
CCAP:
HCAP:

CLOT

CCAP

CFR

5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0
5,0
6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0
14,0
15,0

617,2
630,9
644,5
658,1
671,7
685,3
699,0
712,6
726,2
739,8
753,4
606,3
620,3
634,2
648,2
662,1
676,1
690,0
704,0
718,0
731,9
745,9
588,1
602,6
617,1
631,6
646,1
660,6
675,2
689,7
704,2
718,7
733,2
569,9
584,9
600,0
615,1
630,1
645,2
660,3
675,4
690,4
705,5
720,6
562,6
577,9
593,2
608,5
623,7
639,0
654,3
669,6
684,9
700,2
715,5
551,6
567,3
582,9
598,5
614,1
629,8
645,4
661,0
676,7
692,3
707,9
533,4
549,6
565,8
582,0
598,2
614,3
630,5
646,7
662,9
679,1
695,3

106,2
108,5
110,9
113,2
115,5
117,9
120,2
122,6
124,9
127,3
129,6
104,3
106,7
109,1
111,5
113,9
116,3
118,7
121,1
123,5
125,9
128,3
101,2
103,6
106,1
108,6
111,1
113,6
116,1
118,6
121,1
123,6
126,1
98,0
100,6
103,2
105,8
108,4
111,0
113,6
116,2
118,8
121,3
123,9
96,8
99,4
102,0
104,7
107,3
109,9
112,5
115,2
117,8
120,4
123,1
94,9
97,6
100,3
102,9
105,6
108,3
111,0
113,7
116,4
119,1
121,8
91,7
94,5
97,3
100,1
102,9
105,7
108,5
111,2
114,0
116,8
119,6

CPD

40,0
41,7
43,5
45,2
47,1
48,9
50,8
52,7
54,6
56,6
58,6
38,7
40,4
42,2
44,0
45,8
47,6
49,5
51,5
53,4
55,4
57,5
36,5
38,2
40,0
41,8
43,7
45,6
47,5
49,5
51,5
53,6
55,6
34,4
36,1
37,9
39,8
41,6
43,6
45,5
47,5
49,6
51,7
53,8
33,5
35,3
37,1
38,9
40,8
42,8
44,8
46,8
48,8
50,9
53,1
32,3
34,1
35,9
37,7
39,6
41,6
43,6
45,6
47,7
49,9
52,0
30,3
32,1
33,9
35,8
37,7
39,7
41,7
43,8
45,9
48,0
50,3

Condenser Water Outlet Temperature (C)


Chilled Water Outlet Temperature (C)
Cooling Capacity (kW)
Condenser Heat Rejection (Kw)

HCAP

HFR

728,0
742,4
756,8
771,2
785,6
800,0
814,4
828,8
843,3
857,7
872,1
725,5
740,2
754,9
769,6
784,2
798,9
813,6
828,3
843,0
857,6
872,3
721,4
736,6
751,7
766,8
781,9
797,1
812,2
827,3
842,5
857,6
872,7
717,3
732,9
748,5
764,1
779,7
795,2
810,8
826,4
842,0
857,6
873,1
715,7
731,5
747,2
763,0
778,7
794,5
810,3
826,0
841,8
857,6
873,3
713,3
729,3
745,3
761,3
777,4
793,4
809,4
825,5
841,5
857,5
873,6
709,2
725,7
742,1
758,6
775,1
791,6
808,0
824,5
841,0
857,5
874,0

125,2
127,7
130,2
132,6
135,1
137,6
140,1
142,6
145,0
147,5
150,0
124,8
127,3
129,8
132,4
134,9
137,4
139,9
142,5
145,0
147,5
150,0
124,1
126,7
129,3
131,9
134,5
137,1
139,7
142,3
144,9
147,5
150,1
123,4
126,1
128,7
131,4
134,1
136,8
139,5
142,1
144,8
147,5
150,2
123,1
125,8
128,5
131,2
133,9
136,7
139,4
142,1
144,8
147,5
150,2
122,7
125,4
128,2
131,0
133,7
136,5
139,2
142,0
144,7
147,5
150,3
122,0
124,8
127,6
130,5
133,3
136,1
139,0
141,8
144,7
147,5
150,3

RCUE 240 WG2


HPD

38,9
40,4
41,9
43,4
45,0
46,6
48,2
49,8
51,4
53,1
54,8
38,7
40,2
41,7
43,2
44,8
46,4
48,1
49,7
51,4
53,1
54,9
38,3
39,8
41,4
43,0
44,6
46,2
47,9
49,6
51,3
53,1
54,9
37,8
39,4
41,0
42,7
44,3
46,0
47,7
49,5
51,3
53,1
55,0
37,7
39,3
40,9
42,5
44,2
45,9
47,7
49,5
51,3
53,1
55,0
37,4
39,1
40,7
42,4
44,1
45,8
47,6
49,4
51,2
53,1
55,0
37,0
38,7
40,4
42,1
43,8
45,6
47,4
49,3
51,2
53,1
55,0

IPT

110,7
111,5
112,3
113,1
113,9
114,7
115,5
116,3
117,1
117,8
118,6
119,2
119,9
120,6
121,4
122,1
122,8
123,6
124,3
125,0
125,7
126,5
133,3
134,0
134,6
135,2
135,8
136,4
137,0
137,7
138,3
138,9
139,5
147,5
148,0
148,5
149,0
149,5
150,0
150,5
151,0
151,6
152,1
152,6
153,1
153,6
154,1
154,5
155,0
155,5
155,9
156,4
156,9
157,3
157,8
161,6
162,0
162,4
162,8
163,2
163,6
164,0
164,4
164,8
165,2
165,6
175,8
176,1
176,4
176,6
176,9
177,2
177,5
177,8
178,1
178,4
178,7

CCAP

716,0
731,8
747,6
763,4
779,2
795,0
810,8
826,6
842,4
858,2
874,0
703,3
719,5
735,7
751,9
768,1
784,3
800,4
816,6
832,8
849,0
865,2
682,2
699,0
715,8
732,7
749,5
766,4
783,2
800,0
816,9
833,7
850,5
661,0
678,5
696,0
713,5
731,0
748,4
765,9
783,4
800,9
818,4
835,9
652,6
670,3
688,1
705,8
723,5
741,3
759,0
776,8
794,5
812,3
830,0
639,9
658,0
676,2
694,3
712,4
730,5
748,7
766,8
784,9
803,1
821,2
618,7
637,5
656,3
675,1
693,9
712,6
731,4
750,2
769,0
787,7
806,5

CFR

123,2
125,9
128,6
131,3
134,0
136,7
139,5
142,2
144,9
147,6
150,3
121,0
123,8
126,5
129,3
132,1
134,9
137,7
140,5
143,2
146,0
148,8
117,3
120,2
123,1
126,0
128,9
131,8
134,7
137,6
140,5
143,4
146,3
113,7
116,7
119,7
122,7
125,7
128,7
131,7
134,7
137,8
140,8
143,8
112,2
115,3
118,3
121,4
124,4
127,5
130,6
133,6
136,7
139,7
142,8
110,1
113,2
116,3
119,4
122,5
125,7
128,8
131,9
135,0
138,1
141,2
106,4
109,7
112,9
116,1
119,3
122,6
125,8
129,0
132,3
135,5
138,7

CPD

45,5
47,4
49,4
51,4
53,5
55,6
57,7
59,9
62,1
64,3
66,6
44,0
45,9
47,9
50,0
52,0
54,2
56,3
58,5
60,8
63,0
65,3
41,5
43,5
45,5
47,6
49,7
51,8
54,0
56,3
58,5
60,9
63,2
39,1
41,1
43,1
45,2
47,3
49,5
51,8
54,0
56,4
58,8
61,2
38,1
40,1
42,2
44,3
46,4
48,6
50,9
53,2
55,5
57,9
60,4
36,7
38,7
40,8
42,9
45,1
47,3
49,6
51,9
54,2
56,7
59,1
34,4
36,4
38,5
40,7
42,8
45,1
47,4
49,7
52,2
54,6
57,1

HFR: Condenser Water Flow Rate at 5C (m3/h)


HPD:Condenser Water Pressure Drop (kPa)
CFR:Chilled Water Flow Rate at 5C (m3/h)
CPD:
Water Cooler Pressure Drop (kPa)
IPT:
Compressor Input Power (kW)

HCAP

837,9
854,6
871,2
887,9
904,6
921,3
937,9
954,6
971,3
987,9
1004,6
834,6
851,5
868,5
885,5
902,5
919,5
936,5
953,5
970,5
987,5
1004,4
829,0
846,5
864,0
881,5
899,0
916,6
934,1
951,6
969,1
986,6
1004,1
823,4
841,5
859,5
877,5
895,6
913,6
931,7
949,7
967,8
985,8
1003,9
821,2
839,4
857,7
875,9
894,2
912,5
930,7
949,0
967,2
985,5
1003,7
817,8
836,4
855,0
873,6
892,1
910,7
929,3
947,8
966,4
985,0
1003,6
812,3
831,4
850,5
869,6
888,7
907,8
926,9
946,0
965,1
984,2
1003,3

HFR

144,1
147,0
149,9
152,7
155,6
158,5
161,3
164,2
167,1
169,9
172,8
143,5
146,5
149,4
152,3
155,2
158,2
161,1
164,0
166,9
169,8
172,8
142,6
145,6
148,6
151,6
154,6
157,6
160,7
163,7
166,7
169,7
172,7
141,6
144,7
147,8
150,9
154,0
157,1
160,2
163,4
166,5
169,6
172,7
141,2
144,4
147,5
150,7
153,8
156,9
160,1
163,2
166,4
169,5
172,6
140,7
143,9
147,1
150,3
153,4
156,6
159,8
163,0
166,2
169,4
172,6
139,7
143,0
146,3
149,6
152,9
156,1
159,4
162,7
166,0
169,3
172,6

HPD

58,8
61,1
63,4
65,7
68,1
70,5
73,0
75,5
78,0
80,6
83,2
58,4
60,7
63,0
65,4
67,8
70,3
72,8
75,3
77,9
80,5
83,2
57,6
60,0
62,4
64,8
67,3
69,8
72,4
75,0
77,7
80,4
83,2
56,9
59,3
61,8
64,3
66,8
69,4
72,1
74,8
77,5
80,3
83,1
56,6
59,0
61,5
64,0
66,6
69,2
71,9
74,6
77,4
80,2
83,1
56,2
58,6
61,1
63,7
66,3
69,0
71,7
74,5
77,3
80,2
83,1
55,4
58,0
60,5
63,2
65,8
68,6
71,4
74,2
77,1
80,0
83,0

IPT

121,9
122,8
123,6
124,5
125,4
126,3
127,1
128,0
128,9
129,7
130,6
131,2
132,0
132,8
133,6
134,4
135,2
136,0
136,8
137,6
138,4
139,2
146,8
147,5
148,2
148,8
149,5
150,2
150,9
151,6
152,3
152,9
153,6
162,4
162,9
163,5
164,1
164,6
165,2
165,7
166,3
166,9
167,4
168,0
168,6
169,1
169,6
170,1
170,7
171,2
171,7
172,2
172,7
173,2
173,7
177,9
178,4
178,8
179,3
179,7
180,2
180,6
181,0
181,5
181,9
182,4
193,5
193,8
194,2
194,5
194,8
195,1
195,5
195,8
196,1
196,4
196,7

Conversion Multiplier:
1 kW = 860 kcal/h
= 3412 Btu/h
1 kPa = 0.102 mAq

MODEL SELECTION 15/75


Performance Table (Heating Operation, Only for Heat Pump Operation Option)
RCUE40WG2

RCUE50WG2

RCUE60WG2

CLOT

HOT

HCAP

HFR

HPD

CCAP

CFR

CPD

IPT

HCAP

HFR

HPD

CCAP

CFR

CPD

IPT

HCAP

HFR

HPD

CCAP

CFR

CPD

IPT

5,0

25,0

162,3

27,9

35,0

135,4

23,3

31,4

26,9

193,8

33,3

35,2

161,7

27,8

37,4

32,1

235,5

40,5

36,8

196,0

33,7

36,5

39,4

30,0

161,4

27,8

34,6

131,3

22,6

29,7

30,1

192,7

33,2

34,8

156,8

27,0

35,3

35,9

234,2

40,3

36,4

190,1

32,7

34,4

44,1

35,0

160,5

27,6

34,2

127,3

21,9

27,9

33,3

191,7

33,0

34,5

152,0

26,1

33,3

39,7

233,0

40,1

36,0

184,3

31,7

32,4

48,8

40,0

157,2

27,0

32,9

120,7

20,8

25,3

36,5

187,7

32,3

33,1

144,2

24,8

30,1

43,5

228,2

39,3

34,6

174,8

30,1

29,3

53,4

45,0

154,0

26,5

31,7

114,4

19,7

22,8

39,7

183,9

31,6

31,9

136,6

23,5

27,1

47,3

223,7

38,5

33,3

165,6

28,5

26,4

58,1

50,0

151,0

26,0

30,5

108,2

18,6

20,5

42,8

180,3

31,0

30,7

129,1

22,2

24,4

51,2

219,4

37,7

32,1

156,6

26,9

23,7

62,8

55,0

148,1

25,5

29,5

102,1

17,6

18,3

46,0

176,9

30,4

29,6

121,9

21,0

21,8

55,0

215,3

37,0

31,0

147,8

25,4

21,3

67,5

25,0

168,9

29,0

37,6

141,6

24,4

34,3

27,2

201,6

34,7

37,9

169,1

29,1

40,8

32,5

245,0

42,1

39,6

205,1

35,3

39,8

39,9

30,0

168,2

28,9

37,4

137,8

23,7

32,5

30,4

200,8

34,5

37,6

164,6

28,3

38,7

36,2

244,0

42,0

39,3

199,5

34,3

37,7

44,5

35,0

167,5

28,8

37,1

134,0

23,0

30,8

33,5

200,0

34,4

37,3

160,0

27,5

36,7

40,0

243,1

41,8

39,1

194,0

33,4

35,8

49,1

40,0

164,2

28,2

35,7

127,6

21,9

28,1

36,6

196,1

33,7

36,0

152,3

26,2

33,4

43,8

238,4

41,0

37,6

184,7

31,8

32,6

53,7

45,0

161,1

27,7

34,5

121,3

20,9

25,5

39,8

192,3

33,1

34,7

144,8

24,9

30,3

47,5

233,9

40,2

36,3

175,6

30,2

29,6

58,3

50,0

158,1

27,2

33,3

115,2

19,8

23,1

42,9

188,8

32,5

33,5

137,5

23,7

27,5

51,3

229,7

39,5

35,1

166,8

28,7

26,8

62,9

7,0

55,0

155,3

26,7

32,2

109,2

18,8

20,8

46,1

185,4

31,9

32,4

130,4

22,4

24,8

55,0

225,6

38,8

33,9

158,1

27,2

24,2

67,5

25,0

178,7

30,7

41,9

151,0

26,0

38,7

27,7

213,4

36,7

42,2

180,3

31,0

46,1

33,1

259,2

44,6

44,1

218,6

37,6

44,9

40,6

30,0

178,3

30,7

41,7

147,5

25,4

37,1

30,8

212,9

36,6

42,0

176,2

30,3

44,1

36,7

258,7

44,5

44,0

213,6

36,7

43,0

45,1

35,0

177,9

30,6

41,5

144,1

24,8

35,4

33,8

212,5

36,5

41,8

172,1

29,6

42,2

40,4

258,2

44,4

43,8

208,6

35,9

41,1

49,6

40,0

174,8

30,1

40,1

137,8

23,7

32,5

36,9

208,7

35,9

40,4

164,6

28,3

38,7

44,1

253,7

43,6

42,3

199,6

34,3

37,8

54,1

45,0

171,7

29,5

38,8

131,7

22,7

29,8

40,0

205,0

35,3

39,1

157,3

27,1

35,5

47,7

249,3

42,9

41,0

190,7

32,8

34,6

58,6

50,0

168,8

29,0

37,6

125,7

21,6

27,3

43,0

201,5

34,7

37,9

150,1

25,8

32,5

51,4

245,1

42,2

39,7

182,0

31,3

31,7

63,1

55,0

166,0

28,6

36,5

119,9

20,6

24,9

46,1

198,2

34,1

36,7

143,1

24,6

29,7

55,1

241,2

41,5

38,5

173,6

29,9

28,9

67,6

25,0

195,1

33,6

49,3

166,6

28,7

46,7

28,5

233,0

40,1

49,7

198,9

34,2

55,6

34,1

283,0

48,7

52,1

241,2

41,5

54,2

41,8

30,0

195,2

33,6

49,4

163,8

28,2

45,2

31,5

233,1

40,1

49,8

195,5

33,6

53,8

37,6

283,2

48,7

52,2

237,1

40,8

52,5

46,1

35,0

195,3

33,6

49,4

160,9

27,7

43,7

34,4

233,3

40,1

49,9

192,2

33,1

52,1

41,1

283,4

48,8

52,3

233,0

40,1

50,8

50,4

40,0

192,3

33,1

48,0

154,9

26,6

40,7

37,4

229,6

39,5

48,4

185,0

31,8

48,4

44,6

279,1

48,0

50,7

224,3

38,6

47,2

54,8

45,0

189,4

32,6

46,7

149,1

25,6

37,8

40,3

226,1

38,9

47,0

178,0

30,6

45,0

48,1

274,9

47,3

49,3

215,8

37,1

43,9

59,1

50,0

186,6

32,1

45,4

143,3

24,6

35,0

43,3

222,8

38,3

45,7

171,1

29,4

41,7

51,6

270,9

46,6

48,0

207,5

35,7

40,7

63,4

55,0

183,9

31,6

44,1

137,7

23,7

32,5

46,2

219,5

37,8

44,5

164,4

28,3

38,6

55,2

267,0

45,9

46,7

199,3

34,3

37,7

67,7

CLOT

HOT

HCAP

HFR

HPD

CCAP

CFR

CPD

IPT

HCAP

HFR

HPD

CCAP

CFR

CPD

IPT

HCAP

HFR

HPD

CCAP

CFR

CPD

IPT

5,0

25,0

278,2

47,8

58,4

234,4

40,3

44,0

43,7

387,6

66,7

63,8

323,4

55,6

38,5

64,2

470,9

81,0

67,9

392,1

67,4

55,4

78,8

30,0

276,3

47,5

57,6

227,4

39,1

41,5

48,9

385,5

66,3

63,2

313,6

53,9

36,3

71,8

468,5

80,6

67,3

380,3

65,4

52,3

88,2

35,0

274,5

47,2

56,9

220,3

37,9

39,1

54,1

383,4

65,9

62,5

303,9

52,3

34,2

79,5

466,0

80,2

66,6

368,5

63,4

49,3

97,5

40,0

268,3

46,2

54,5

209,0

36,0

35,3

59,3

375,4

64,6

60,1

288,3

49,6

30,9

87,1

456,5

78,5

64,0

349,6

60,1

44,6

106,9

10,0

15,0

RCUE80WG2

7,0

10,0

15,0

RCUE100WG2

RCUE120WG2

45,0

262,5

45,2

52,3

198,0

34,1

31,8

64,5

367,8

63,3

57,8

273,1

47,0

27,9

94,7

447,4

76,9

61,6

331,1

57,0

40,2

116,2

50,0

256,9

44,2

50,2

187,3

32,2

28,6

69,7

360,6

62,0

55,7

258,3

44,4

25,1

102,3 438,7

75,5

59,4

313,2

53,9

36,2

125,6

55,0

251,7

43,3

48,2

176,8

30,4

25,6

74,9

353,8

60,8

53,7

243,8

41,9

22,5

109,9 430,6

74,1

57,3

295,7

50,9

32,4

134,9

25,0

289,5

49,8

63,0

245,2

42,2

47,9

44,3

403,2

69,4

68,8

338,3

58,2

41,9

65,0

489,9

84,3

73,2

410,1

70,5

60,4

79,8

30,0

288,0

49,5

62,4

238,6

41,0

45,5

49,4

401,6

69,1

68,3

329,1

56,6

39,8

72,5

488,1

83,9

72,7

399,1

68,6

57,3

89,0

35,0

286,5

49,3

61,8

232,0

39,9

43,1

54,5

400,0

68,8

67,8

320,0

55,0

37,7

80,0

486,2

83,6

72,2

388,0

66,7

54,3

98,2

40,0

280,5

48,2

59,3

220,9

38,0

39,2

59,6

392,2

67,5

65,3

304,7

52,4

34,3

87,5

476,8

82,0

69,6

369,4

63,5

49,5

107,4

45,0

274,7

47,3

57,0

210,0

36,1

35,6

64,7

384,7

66,2

62,9

289,7

49,8

31,2

95,0

467,9

80,5

67,1

351,2

60,4

45,0

116,6

50,0

269,3

46,3

54,9

199,4

34,3

32,3

69,8

377,6

64,9

60,7

275,1

47,3

28,3

102,5 459,3

79,0

64,8

333,5

57,4

40,8

125,8

55,0

264,0

45,4

52,8

189,1

32,5

29,2

74,9

370,8

63,8

58,7

260,8

44,9

25,6

110,0 451,3

77,6

62,7

316,2

54,4

36,9

135,0

25,0

306,5

52,7

70,3

261,4

45,0

54,2

45,1

426,8

73,4

76,6

360,6

62,0

47,3

66,2

518,4

89,2

81,6

437,2

75,2

68,2

81,2

30,0

305,5

52,5

69,8

255,5

43,9

51,8

50,1

425,8

73,2

76,3

352,3

60,6

45,3

73,5

517,4

89,0

81,3

427,2

73,5

65,2

90,2

35,0

304,5

52,4

69,4

249,5

42,9

49,5

55,1

424,9

73,1

76,0

344,1

59,2

43,3

80,8

516,4

88,8

81,0

417,2

71,8

62,4

99,2

40,0

298,7

51,4

66,9

238,6

41,0

45,5

60,1

417,3

71,8

73,4

329,2

56,6

39,8

88,2

507,3

87,3

78,3

399,1

68,6

57,3

108,2

45,0

293,1

50,4

64,5

228,0

39,2

41,7

65,0

410,0

70,5

71,0

314,5

54,1

36,5

95,5

498,6

85,8

75,7

381,4

65,6

52,6

117,2

50,0

287,7

49,5

62,3

217,7

37,4

38,2

70,0

403,1

69,3

68,7

300,3

51,6

33,4

102,8 490,2

84,3

73,3

364,1

62,6

48,2

126,2

55,0

282,6

48,6

60,2

207,6

35,7

34,8

75,0

396,4

68,2

66,6

286,3

49,2

30,5

110,1 482,3

83,0

71,1

347,1

59,7

44,0

135,2

25,0

334,8

57,6

83,2

288,4

49,6

65,3

46,4

465,9

80,1

90,4

397,8

68,4

57,0

68,1

566,0

97,3

96,4

482,3

83,0

82,1

83,6

30,0

334,7

57,6

83,2

283,5

48,8

63,2

51,2

466,2

80,2

90,5

391,0

67,3

55,2

75,2

566,4

97,4

96,5

474,1

81,6

79,5

92,3

35,0

334,6

57,6

83,1

278,6

47,9

61,2

56,0

466,5

80,2

90,6

384,3

66,1

53,4

82,2

566,9

97,5

96,7

466,0

80,1

76,9

100,9

40,0

329,0

56,6

80,5

268,3

46,1

56,9

60,8

459,2

79,0

88,0

370,0

63,6

49,7

89,2

558,2

96,0

93,9

448,6

77,2

71,6

109,5

45,0

323,7

55,7

78,0

258,1

44,4

52,8

65,6

452,2

77,8

85,5

356,0

61,2

46,2

96,3

549,8

94,6

91,2

431,6

74,2

66,5

118,2

50,0

318,5

54,8

75,6

248,1

42,7

49,0

70,4

445,5

76,6

83,1

342,2

58,9

42,8

103,3 541,7

93,2

88,7

414,9

71,4

61,7

126,8

55,0

313,5

53,9

73,4

238,3

41,0

45,4

75,2

439,1

75,5

80,8

328,7

56,5

39,7

110,3 534,0

91,9

86,3

398,6

68,6

57,2

135,4

Where,
CLOT: Chilled Water Outlet Temperature (C)
HOT: Hot Water Outlet Temperature (C)
HCAP: Heating Capacity (kW)
CCAP: Cooling Capacity (kW)

HFR: Condenser Water Flow Rate at 5C (m3/h)


HPD:Condenser Water Pressure Drop (kPa)
CFR:Chilled Water Flow Rate at 5C (m3/h)
CPD:Water Cooler Pressure Drop (kPa)
IPT:Compressor Input Power (kW)

Conversion Multiplier:
1 kW = 860 kcal/h
= 3412 Btu/h
1 kPa = 0.102 mAq

15/76 MODEL SELECTION


Performance Table (Heating Operation, Only for Heat Pump Operation Option)
RCUE150WG2

RCUE180WG2

CLOT

HOT

HCAP

HFR

HPD

CCAP

CFR

CPD

IPT

HCAP

5,0

25,0

533,6

91,8

86,1

449,7

77,3

71,9

83,9

629,6 108,3

30,0

530,0

91,2

85,1

436,2

75,0

67,9

93,8

625,5 107,6

29,2

514,6

88,5

28,3

110,9

35,0

526,4

90,5

84,0

422,6

72,7

63,9

103,8 621,3 106,9

28,8

498,6

85,8

26,6

122,7

40,0

514,7

88,5

80,4

400,9

69,0

57,8

113,7 607,4 104,5

27,6

473,0

81,4

24,1

134,4

45,0

503,5

86,6

77,1

379,8

65,3

52,2

123,7 594,2 102,2

26,5

448,1

77,1

21,7

146,2

50,0

492,8

84,8

74,1

359,2

61,8

46,9

133,6 581,7 100,0

25,4

423,7

72,9

19,5

157,9

55,0

482,7

83,0

71,2

339,1

58,3

42,1

143,6 569,7

98,0

24,4

400,0

68,8

17,5

169,7

25,0

555,3

95,5

92,9

470,4

80,9

78,3

84,9

655,3 112,7

31,9

554,9

95,5

32,7

100,3

30,0

552,4

95,0

92,0

457,7

78,7

74,3

94,7

651,9 112,1

31,6

540,0

92,9

31,0

111,9

35,0

549,5

94,5

91,1

445,0

76,5

70,5

104,5 648,5 111,5

31,3

525,0

90,3

29,4

123,5

40,0

538,0

92,5

87,5

423,7

72,9

64,2

114,3 634,9 109,2

30,0

499,8

86,0

26,7

135,1

45,0

526,9

90,6

84,1

402,8

69,3

58,4

124,1 621,9 107,0

28,9

475,3

81,7

24,3

146,7

50,0

516,4

88,8

81,0

382,5

65,8

52,9

133,9 609,5 104,8

27,8

451,3

77,6

22,0

158,2

87,1

7,0

HFR

HPD

CCAP

CFR

CPD

IPT

29,6

530,5

91,2

30,0

99,1

55,0

506,4

78,0

362,7

62,4

47,8

143,7 597,7 102,8

26,8

427,9

73,6

19,9

169,8

25,0

587,9 101,1 103,6

501,4

86,2

88,4

86,4

693,7 119,3

35,5

591,6 101,8

36,9

102,2

30,0

586,0 100,8 102,9

490,0

84,3

84,6

96,0

691,5 118,9

35,3

578,1

99,4

35,3

113,5

35,0

584,1 100,5 102,3

478,5

82,3

80,9

105,6 689,3 118,6

35,1

564,6

97,1

33,8

124,8

40,0

572,9

98,5

98,6

457,7

78,7

74,4

115,1 676,1 116,3

33,8

540,0

92,9

31,0

136,1

45,0

562,1

96,7

95,1

437,4

75,2

68,2

124,7 663,4 114,1

32,6

516,0

88,8

28,4

147,4

50,0

551,8

94,9

91,8

417,5

71,8

62,5

134,3 651,3 112,0

31,5

492,6

84,7

26,0

158,7

55,0

542,0

93,2

88,7

398,1

68,5

57,1

143,9 639,7 110,0

30,5

469,7

80,8

23,7

170,0

25,0

642,2 110,5 122,5

553,2

95,1

106,5

89,0

757,8 130,3

42,0

652,6 112,3

44,5

105,2

30,0

642,0 110,4 122,5

543,8

93,5

103,1

98,2

757,6 130,3

42,0

641,6 110,3

43,1

116,0

35,0

641,8 110,4 122,4

534,4

91,9

99,8

107,4 757,4 130,3

42,0

630,5 108,4

41,7

126,9

40,0

631,1 108,5 118,5

514,5

88,5

92,8

116,6 744,8 128,1

40,6

607,0 104,4

38,8

137,7

45,0

620,8 106,8 114,9

495,0

85,1

86,3

125,7 732,6 126,0

39,4

584,0 100,5

36,0

148,6

50,0

610,8 105,1 111,4

475,9

81,9

80,1

134,9 720,9 124,0

38,2

561,5

96,6

33,4

159,5

55,0

601,3 103,4 108,1

457,2

78,6

74,2

144,1 709,7 122,1

37,1

539,3

92,8

30,9

170,3

CLOT

HOT

HCAP

5,0

25,0

10,0

15,0

RCUE200WG2

7,0

10,0

15,0

HFR

HPD

CCAP

725,5 124,8

38,7

30,0

721,4 124,1

35,0

717,3 123,4

40,0

CFR

RCUE240WG2
CPD

IPT

HCAP

HFR

HPD

CPD

IPT

606,3 104,3

38,7

119,2

834,6

143,5 58,4

CCAP

703,3 121,0

CFR

44,0

131,2

38,3

588,1 101,2

36,5

133,3

829,0

142,6 57,6

682,2 117,3

41,5

146,8

37,8

569,9

98,0

34,4

147,5

823,4

141,6 56,9

661,0 113,7

39,1

162,4

702,2 120,8

36,3

540,6

93,0

31,1

161,6

805,0

138,5 54,5

627,1 107,9

35,3

177,9

45,0

687,8 118,3

34,9

512,1

88,1

28,0

175,8

787,5

135,5 52,3

594,0 102,2

31,8

193,5

50,0

674,2 116,0

33,6

484,3

83,3

25,2

189,9

770,8

132,6 50,2

561,8

96,6

28,6

209,1

55,0

661,3 113,7

32,4

457,2

78,6

22,5

204,1

755,0

129,9 48,2

530,3

91,2

25,6

224,7

25,0

754,9 129,8

41,7

634,2 109,1

42,2

120,6

868,5

149,4 63,0

735,7 126,5

47,9

132,8

30,0

751,7 129,3

41,4

617,1 106,1

40,0

134,6

864,0

148,6 62,4

715,8 123,1

45,5

148,2

35,0

748,5 128,7

41,0

600,0 103,2

37,9

148,5

859,5

147,8 61,8

696,0 119,7

43,1

163,5

40,0

733,7 126,2

39,5

571,2

98,3

34,5

162,4

841,5

144,7 59,3

662,6 114,0

39,2

178,8

45,0

719,5

123,8

38,1

543,1

93,4

31,3

176,4

824,2

141,8 57,0

630,1 108,4

35,6

194,2

50,0

706,0 121,4

36,7

515,7

88,7

28,4

190,3

807,8

138,9 54,9

598,3 102,9

32,3

209,5

55,0

693,2 119,2

35,5

489,0

84,1

25,6

204,2

792,1

136,2 52,8

567,3

97,6

29,2

224,8

25,0

798,9 137,4

46,4

676,1 116,3

47,6

122,8

919,5

158,2 70,3

784,3 134,9

54,2

135,2

30,0

797,1 137,1

46,2

660,6 113,6

45,6

136,4

916,6

157,6 69,8

766,4 131,8

51,8

150,2

35,0

795,2 136,8

46,0

645,2 111,0

43,6

150,0

913,6

157,1 69,4

748,4 128,7

49,5

165,2

40,0

780,8 134,3

44,5

617,2 106,2

40,0

163,6

896,1

154,1 66,9

715,9 123,1

45,5

180,2

45,0

767,0 131,9

43,0

589,8 101,4

36,7

177,2

879,3

151,2 64,5

684,1 117,7

41,7

195,1

50,0

753,8 129,7

41,6

563,0

96,8

33,6

190,8

863,1

148,5 62,3

653,0 112,3

38,2

210,1

55,0

741,2 127,5

40,3

536,8

92,3

30,6

204,4

847,8

145,8 60,2

622,7 107,1

34,8

225,1

25,0

872,3 150,0

54,9

745,9 128,3

57,5

126,5

1004,4 172,8 83,2

865,2 148,8

65,3

139,2

30,0

872,7 150,1

54,9

733,2 126,1

55,6

139,5

1004,1 172,7 83,2

850,5 146,3

63,2

153,6

35,0

873,1 150,2

55,0

720,6 123,9

53,8

152,6

1003,9 172,7 83,1

835,9 143,8

61,2

168,0

40,0

859,4 147,8

53,3

693,8 119,3

50,1

165,6

987,1

169,8 80,5

804,8 138,4

56,9

182,4

45,0

846,2 145,5

51,8

667,5 114,8

46,5

178,7

971,0

167,0 78,0

774,3 133,2

52,8

196,7

50,0

833,4 143,3

50,3

641,7 110,4

43,1

191,7

955,5

164,3 75,6

744,3 128,0

49,0

211,1

55,0

682,5 117,4

34,4

477,7

24,5

204,8

779,7

134,1 51,3

554,2

27,9

225,5

Where,
CLOT: Chilled Water Outlet Temperature (C)
HOT: Hot Water Outlet Temperature (C
HCAP: Heating Capacity (kW)
CCAP: Cooling Capacity (kW)

82,2

HFR: Condenser Water Flow Rate at 5C (m3/h)


HPD:Condenser Water Pressure Drop (kPa)
CFR:Chilled Water Flow Rate at 5C (m3/h)
CPD:Water Cooler Pressure Drop (kPa)
IPT:Compressor Input Power (kW)

95,3

Conversion Multiplier:
1 kW = 860 kcal/h
= 3412 Btu/h
1 kPa = 0.102 mAq

MODEL SELECTION 15/77

15.3. ELECTRICAL DATA

Model
RCUE 40WG2
RCUE 50WG2
RCUE 60WG2
RCUE 80WG2
RCUE100WG2
RCUE120WG2
RCUE150WG2
RCUE180WG2
RCUE200WG2
RCUE240WG2

Unit Main Power


(V)
400
400
400
400
400
400
400
400
400
400

(Hz)
50
50
50
50
50
50
50
50
50
50

Applicable
Instantaneous
Voltage (V)
Maximum
440
440
440
440
440
440
440
440
440
440

Minimum
360
360
360
360
360
360
360
360
360
360

Commpressor
Motor
STC*1
RNC
(A)
(A)
121
155
188
188
155
188
188
155
188
188

54,9
65,6
80,5
89,4
131,2
161,1
171,4
202,6
243,6
268,2

IPT
(kW)

Maximum
Unit
Current
(A)

STC*2
Unit
Maximum
(A)

33,5
40,0
49,1
54,5
80,0
98,2
104,5
123,5
148,5
163,5

69
82
101
112
164
201
214
253
304
335

121
155
188
188
172
209
209
190
230
230

NOTES:
1. This data is based on the following conditions
Chilled Water Inlet/Outlet Temperature: 12/7C,
AmbientTemperature: 35C.
2. The "Maximum Unit Current" shown in the above table is the maximum
total unit running current at the following conditions.
Supply Voltage: 90% of the rated voltage, Unit Capacity: 100% at max.
operating conditions
3. The power supply cables must be sized to cover this maximum current
value.
4. Starting Current (*1, *2) means as follows.
*1:First Compressor Starting Current
2
* :Unit Maximum Starting Current, when Last Compressor starts.
5. Compressor motor is star-delta starting

VOL: Rated Unit Supply Voltage(V)


STC: Starting Current(A)
Hz: Frequency(Hz)
RNC: Running Current(A)
IPT: Input(kW)

15/78 MODEL SELECTION

15.4. SOUND DATA


Standard Models
Sound Pressure Level (dB)
Frequency Band (Hz)

Model

Overall

63

125

250

500

1000

2000

4000

8000

RCUE40WG2

77

69

71

63

62

61

53

37

68

RCUE50WG2

74

76

71

64

65

64

51

35

69

RCUE60WG2

77

69

67

62

68

66

53

35

71

RCUE80WG2

77

70

70

71

62

64

50

39

71

RCUE100WG2

79

71

70

67

68

67

54

38

72

RCUE120WG2

80

72

70

65

71

69

56

38

74

RCUE150WG2

81

73

72

69

70

69

56

40

74

RCUE180WG2

82

74

73

71

70

69

56

41

75

RCUE200WG2

83

75

74

71

72

71

58

42

76

RCUE240WG2

84

76

75

71

73

72

59

42

77

Sound Power Level (dB)


Frequency Band (Hz)

Model

Overall
(dBA)

63

125

250

500

1000

2000

4000

8000

RCUE40WG2

92

84

86

78

77

76

68

52

83

RCUE50WG2

89

91

86

79

80

79

66

50

84

RCUE60WG2

92

84

82

77

83

81

68

50

86

RCUE80WG2

92

85

85

86

77

79

65

54

86

RCUE100WG2

95

87

86

83

84

83

70

54

88

RCUE120WG2

96

88

86

81

87

85

72

54

90

RCUE150WG2

97

89

88

85

86

85

72

56

90

RCUE180WG2

98

90

89

87

86

85

72

57

91

RCUE200WG2

99

91

90

87

88

87

74

58

92

RCUE240WG2

100

92

91

87

89

88

75

58

93

NOTE:
1. The sound pressure is based on the following conditions.
-1 meter from the control panel surface and 1.5 meter from the floor level.
-Voltage of the power source is 380V.
-The above data was measured in an anechoic chamber, so that reflected sound should be taken into consideration in
the field.
2. Operating conditions are as follows.
Standard Models: Cooler Water Inlet/Outlet Temperature 12/7 C, Condenser Water Inlet / outlet 30C/35C.

APPLICATION DATA 16/79

16. APPLICATION DATA


16.1. WORKING RANGE
Working Range
Item
Working Voltage
Voltage Imbalance

Power Supply

Condenser Water
Outlet Temperature

Starting Voltage
Standard
High Condensing
Temperature and Heat Pump
operation option
Standard

Cooler Water
Outlet Temperature

Description
90% 110% of Rated Voltage
Within 3% Deviation from Each Voltage
at Compressor Terminals
Higher than 85% of Rated Voltage
22 45

Remark

22 55
5 15
4 0 (Low 1)
-1 -5 (Low2)
-6 -10 (Low3)
1.0 MPa

Low Temperature
Option

Maximum Permissible Water Pressure

Water
Ethylene glycol

16.2. PART LOAD PERFORMANCE


The European Seasonal Energy Efficiency Ratio is a weighted formula enabling to take into account the variation of EER with
the load rate and the variation of water inlet condenser temperature.

ESEER = A . EER100 + B . EER75 + C . EER50 + D . EER25


The following part-load ratings shall be considered:

With the following weighting coefficients:

A = 0.03
B = 0.33
C = 0.41
D = 0.23

Load Ratio
(%)
100
75
50
25

Water temperature
at condenser inlet
(C)
30
26
22
18

Model RCUE-WG2

40

50

60

80

100

120

150

180

200

240

ESEER

4,52

4,52

4,52

4,86

4,52

4,52

4,86

4,86

4,52

4,86

16/80 APPLICATION DATA

16.3. ETHYLENE GLYCOL APPLICATION


Low Water Temperature Application (Option)
When utilizing water less than 5 C, antifreezing mixture of
ethylene glycol shall be input to the water system.
Low water temperature Option is categorised 3 level
depending on water outlet temperature.
Therefore, please specify the level when ordering .
Freeze Protection Thermostat has been set in the factory.
Table shows Required Ethylene Glycol percentage for each
category.

1. Category

Category

Outlet Water
Temp. (C)

Required
Ethylene
Glycol (wt%)

Low 1
Low 2
Low 3

4~0
-1 ~ -5
-6 ~ -10

20
30
40

Ethylene
Glycol
Freezing
Temp. (C)
-7
-13
-22

 NOTE:
Freeze Protection Thermostat is the electronic control,
but non-adjustable.

For the performance, each value can be given by using following table. (See below example)
2. Performance

Ethylene
Glycol
(wt%)

20

30

40

Outlet
Water
Temp.

Flow Rate
Correction
Factor

Pressure
Drop
Correction
Factor

(C)
4
3
2
1
0
-1
-2
-3
-4
-5
-6
-7
-8
-9
-10

(Kf)
1.011
1.012
1.013
1.013
1.014
1.034
1.035
1.037
1.037
1.038
1.073
1.075
1.076
1.076
1.077

(Kp)
1.15
1.16
1.17
1.18
1.19
1.30
1.32
1.34
1.36
1.38
1.50
1.52
1.54
1.56
1.58

Condenser Water Outlet Temperature


(C)
25
CAP IPT
(%)
(%)
97
79
94
78
92
78
90
78
88
77
84
77
82
76
80
76
78
75
75
75
72
73
70
73
68
72
66
72
64
71

 NOTE:
1.CAP: Cooling Capacity, IPT: Compressor Input
2.Capacity and Compressor Input show the percentage
of the standard condition: Condenser Water Inlet /
Outlet 30/35c, Cooler.
3.Water Flow Rate and Pressure Drop can be calculated
by the Correction Factor Kf and Kp.
4.Example:
a)Model: RCUE120 WG2
b)Standard Condition: Capacity 388kW, Compressor
Input 98.2kW
c)Outlet/Inlet Water Temperature -3/2C, Condenser
Water Outlet Temp. 30C

30
CAP IPT
(%)
(%)
94
88
91
88
89
88
87
87
84
87
81
86
79
86
76
86
74
85
72
85
69
84
66
83
64
83
62
82
59
82

35
CAP CAP
(%)
(%)
91
98
88
98
86
97
83
97
81
97
78
96
75
96
73
96
70
95
68
95
65
94
62
93
60
93
57
93
55
93

40
IPT
(%)
88
85
82
80
77
74
71
69
66
64
61
58
56
53
51

IPT
(%)
107
107
107
107
106
106
106
106
105
105
104
103
103
103
103

45
CAP IPT
(%)
(%)
84
117
82
117
79
117
77
116
74
116
71
116
68
116
65
116
63
115
60
115
57
114
54
114
52
113
49
113
46
113

- Ethylene glycol: 30%


- Capacity = 388*0.76=295 kW, Compressor Input =
98.2*0.86=84.5 kW
- Water Flow(m/h) = Kf*Capacity(kW)*0.86T
(T=Inlet Temp.-Outlet Temp.)
= 1.037*295*0.86/(2-(-3))
= 52.6 m/h
- Pressure Drop = Kp*Pressure Drop (water)
1.897
= 1.34*0.0188*52.6
= 46 kPa
where, Pressure Drop(water)= x Q: see "Water
Pressure Drop"

COMPONENTS DATA 17/81

17. COMPONENTS DATA


17.1. COMPRESSOR
Model

40ASC-Z

Type
Revolution
Displacement
Capacity Control
Pneumatic Pressure
High Side
Low Side
Motor Type
Starting Method
Nominal Output
Poles
Insulation
Oil
Name
Charge
Net Weight

rpm
m3/h
%

137.4

MPa
MPa

50ASC-Z

60ASC-Z

Semi-Hermetic
2880
169.5
100 15, 0

208.7

3.0
2.0
Special Squirrel Cage, Three-Phase Motor
Star-Delta Starting
30
37
45
2
E
JAPAN ENERGY, FREOL UX300
6
400
440
460

kW

Litre
kg

17.2. CONDENSER AND WATER COOLER


CONDENSER

Model RCUE-WG2
Condenser
Type (Quantity)

40

50

A (1)

B (1)

TYPE
REFRIGERANT CYCLE
Dimensions
Height (H)
Width (W)
Depth (D)
Maximum Permissible Pressure
Refrigerant Side
Water Side
Internal Volume
Water Side
Material
Approval

60
80
100
120, 150
Brazed Type Plate Heat Exchanger
C (1)
D (1)
E (1)
F (1)

180, 200

240

C (3)

D (3)

A
40HP

B
50HP

C
60HP

D
80HP

E
100HP

F
120, 150HP

mm
mm
mm

525
243
272

525
243
338

525
243
431

525
243
497

694
304
441

694
304
538

MPa
MPa

1.8
1.0

1.8
1.0

1.8
1.0

1.8
1.0

1.8
1.0

1.8
1.0

Liter

14.8

18.6

23.9
27.6
Stainless Steel
PED ( 1 )

40.2

49.4

17/82 COMPONENTS DATA


WATER COOLER

Model RCUE-WG2

40

50

60

Water Cooler
Type (Quantity)

80

100, 120, 150

180, 200

240

C (3)

D (3)

Brazed Type Plate Heat Exchanger


A (1)

TYPE
REFRIGERANT CYCLE
Dimensions
Height (H)
Width (W)
Depth (D)
Maximum Permissible Pressure
Refrigerant Side
Water Side
Internal Volume
Water Side
Material
Approval

B (1)

C (1)

D (1)

E (1)

A
40HP

B
50HP

C
60HP

D
80HP

E
100, 120, 150HP

mm
mm
mm

525
243
227

525
243
305

525
243
389

525
243
431

694
304
489

MPa
MPa

1.8
1.0

1.8
1.0

1.8
1.0

1.8
1.0

1.8
1.0

Liter

15.1

16.7

21.5
23.9
Stainless Steel
PED ( 1 )

44.8

NOTE:
Pressure equipment Directive (97/23/EC)

SINGLE TYPE CONDENSER AND WATER COOLER

DUAL TYPE CONDENSER AND WATER COOLER


WATER OUT

WATER OUT

No.1 REFRIGERANT IN

REFRIGERANT IN

No.2 REFRIGERANT IN

WATER IN
WATER IN

REFRIGERANT OUT
No.1 REFRIGERANT OUT
No.2 REFRIGERANT OUT
REFRIGERANT

No.1 REFRIGERANT
No.2 REFRIGERANT

PLATES

WATER

PLATES

WATER

TCGB0045 - 12/06 - Printed in Spain

You might also like