SAMPLE CALCULATION OF MAKE-UP WATER

WASHER UNIT FOR VENTILATION SYSTEM (V7)

REQUIREMENT

OF

AIR

Capacity of the Air Washer Unit 61,000 CMH


Capacity of the pump selected based on above Air Flow rate 62 CMH
Dry Bulb Temperature (DBT) of air at Inlet of Air Washer Unit 50Deg.C (Maximum
temperature as per Site condition) and Relative Humidity (RH) of air 26% (During
summer)
Density of air at 50 Deg.C 1.109 kg/m
Inlet water temperature at Air washer Unit 20 Deg.C (assumed)
Density of water at 20 Deg.C 998.2 kg/m
As per enclosed Psychometric chart, Corresponding to DBT-50 and RH-26%, The
moisture content at the inlet of Air Washer Unit 20 gm/kg a
Dry Bulb Temperature (DBT) at the outlet of Air Washer Unit- 32 Deg.C (with 90%
Saturation Efficiency) and the Moisture content 27.5 gm/kg a
Hence, water loss due to evaporation may be considered as (27.5-20) =7.5 gm/kg
a i.e,
0.0075x1.109 (m of water/m of air) = 833x10-5 m of water/m of air
998.2
Now, considering the air flow rate of the Air Washer Unit, total quantity of water
loss due to
evaporation 833x10-5x61000 = 0.513m of water which is around 0.82% of the
pump capacity.
With evaporation loss and loss due to carry over of moisture, the makeup water requirement may be considered as 2-3% of the pump capacity.