SCADAPack 314
Smart RTU
www.aquatechnologygroup.com
800-513-8993 | +1 513-298-1183
[email protected]
Built on the proven SCADAPack 300 platform, the SCADAPack
314 features high-performance 32-bit processing, high-speed
serial and USB communications, integrated power supply,
advanced power management, and a wide range of digital and
analog I/O in a cost-effective, compact Smart RTU. Featuring
industry-standard Modbus and DNP3 serial protocols, the
SCADAPack 314 can be programmed locally or remotely
through a choice of flexible programming languages.
This Smart RTU has the same I/O offering as the SCADAPack
334 but without an Ethernet or USB Host port. It also offers the
same small footprint, enabling compact mounting enclosures
for applications where space is at a premium.
www.aquatechnologygroup.com
800-513-8993 | +1 513-298-1183
[email protected]
Product Data Sheet SCADAPack 314
Specifications
www.aquatechnologygroup.com
800-513-8993 | +1 513-298-1183
[email protected]
P314: 5212 controller board and integrated 56O7 I/O board
Controller
Processors
CPU: 32-bit ARM7 microcontroller, 32 MHz clock, integrated watchdog timer
Microcontroller co-processor, 20 MHz clock
Memory
16MB FLASH ROM, 4MB CMOS RAM, 4kB EEPROM
Non-Volatile RAM
CMOS SRAM with lithium battery retains contents for 2 years with no power
Datalog Capacity
465k words
I/O
Analog Inputs
8 software configurable: 0-20/4-20mA / 0-5/0-10V (15-bit)
3 internal: measure incoming power supply voltage for solar applications, battery voltage, and controller temperature
Analog Outputs
Standard: None
2 with optional 5305 on 5607 I/O board: 0-20/4-20mA (12-bit)
Digital I/O
16 digital inputs: 12/24V, 48V, 115/125V, 240V
10 relay outputs: dry contact or DC solid state, dry contact rating: 3A, 30VDC or 240VAC (resistive),
DC solid state rating: 3A, 60 VDC
Counter Inputs
1 dry contact: 0-10Hz or 0-5kHz
2 turbine or dry contact: 0-10kHz
Communications
Serial Ports COM1, COM2
RS-232 port, 8-pin modular RJ45 jack, full or half-duplex, or
RS-485 port, 2-wire, half-duplex
Baud Rates
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200
Serial Protocols
Modbus RTU, Modbus ASCII, DNP3, DF1
Serial Protocol Modes
Slave, Master, Master/Slave, Store and Forward
USB Peripheral Port
USB 2.0 compliant B-type receptacle
Wireless1
Spread spectrum radio at 900MHz2 and 2.4GHz2
General
I/O Terminations
5, 6, and 9-pole removable terminal blocks, 12 to 22AWG, 15A contacts
Dimensions
5.65 inch (144mm) wide, 6.50 inch (165mm) high, 2.80 inch (72mm) deep
Packaging
Corrosion resistant, zinc-plated steel with black enamel paint
Environment
5% RH to 95%, non-condensing, 40C (40F) to 70C (158F)
Power
5212 Controller Board
1 - 30VDC, 30mW at 12V during sleep mode.
1
500mW at 12V during normal operation. 32MHz, LEDs off, no expansion, and USB disabled
300mW at 12V during reduced power mode operation. 12MHz, LEDs off, no expansion, USB disabled
Add 190mW when enabling the USB port
Add 30 to 90mW when enabling the LEDs
8.5W at 24V maximum, 5V supply fully-loaded
5607 I/O Module
11 - 30VDC, 10.3mA plus analog outputs
235mA (max.) at 5V required from 5212 controller board
Warranty
3 years on parts and labor
Certifications
Hazardous Locations
North America
Suitable for use in Class I, Division 2, Groups A, B, C and D Hazardous Locations. Temperature Code T4 CSA certified to the
requirements of:
CSA Std. C22.2 No. 213-M1987 - Hazardous Locations
UL Std. No. 1604 - Hazardous (Classified) Locations
Hazardous Locations
Europe
ATEX II 3G, Ex nA IIC T4 per EN 60079-15, protection type n (Zone 2). Does not include Wireless versions.
Hazardous Locations
IECEx, Ex nA IIC T4 per IEC 60079-15, protection type n (Zone 2). Does not include Wireless versions.
1 Available only with optional integrated wireless modules or with stand-alone wireless modules.
2 Not applicable in all countries.
Disclaimer: Schneider Electric reserves the right to change product specifications. For more information visit www.schneider-electric.com.
Product Data Sheet SCADAPack 314
Model Code
www.aquatechnologygroup.com
800-513-8993 | +1 513-298-1183
[email protected]
TBUP314-1A20-AB00 represents a sample code for a SCADAPack 314, 5607 I/O board and Modbus protocol emulation
Model
TBUP314
Code
Select: Controller
SCADAPack 314 , 32 Bit controller, 8 Analog Inputs, 16 Digital Inputs, 10 Digital Outputs, 3 Accumulators
Select: ProductionPlus Option
None
ProductionPlus Controller (Well Pad - no runs)
Code
A
ProductionPlus Controller with 1 run
Select: Gas Flow Run-Time Option
None
Flow Computer Runs
2 Run Gas Flow
4 Run Gas Flow
2 Run Gas Flow - Gas Transmission Version (Requires Realflo 6.72+)
Code
2
Code
0
1
Code
A
4 Run Gas Flow - Gas Transmission Version (Requires Realflo 6.72+)
Select: Protocol Option
Modbus and DNP 3.0 (Level 2) protocol emulation
Select: Programming Environment
Telepace Ladder Logic and C Language firmware loaded - IEC enabled (programming tools sold separately)
IEC 61131-3 and C Language firmware loaded - Telepace enabled (programming tools sold separately)
Select: Analog Inputs
8 selectable as 0-20, 4-20mA, 0-5V or 0-10V
Code
Select: Digital Inputs/Outputs
16 DI (12/24V) and 10 dry contact relays
16 DI (120V) and 10 dry contact relays
16 DI (12/24V) and 10 DC solid-state relays, ATEX and IECEx certification
Code
0
1
Code
0
16 DI (120V) and 10 solid state relays
Select: Analog Outputs
None
2 channel analog output option, 0 - 20mA
Select: Integrated Communication Interfaces
None
FreeWave & MDS Radios (requires one RS232 port)
900Mhz FreeWave Spread Spectrum Radio
900MHz MDS Spread Spectrum Radio
900MHz Trio Spread Spectrum Radio with encryption, 902-928MHz (FCC / IC)
900MHz Trio Spread Spectrum Radio with encryption, 915-928MHz (AUS)
900MHz Trio Spread Spectrum Radio, 915-928MHz (BRAZIL)
900MHz Trio Spread Spectrum Radio, 921-928MHz (NZ)
Trio Radios - 2.4GHz (requires one RS232 port)
2.4GHz Trio Spread Spectrum Radio, ETSI/100mW, ATEX (EUROPE)
2.4GHz Trio Spread Spectrum Radio with Encryption, 500mW (CANADA, USA & AUSTRALIA)
2.4GHz Trio Spread Spectrum Radio, 500mW (OUTSIDE OF EUROPE, CANADA, USA & AUSTRALIA)
Telemetry & Remote SCADA Solutions
| www.schneider-electric.com
Document Number TBULM08002-79
2011 Schneider Electric. All rights reserved - August 2011
Trio Radios - 900MHz (requires one RS232 port)