Redundancy PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 192

ControlLogix

Redundancy
System
1756-CNB/D/E, 1756-CNBR/D/E,
1756-ENBT, 1756-EWEB, 1756-L55,
1756-L55M12, 1756-L55M13,
1756-L55M14, 1756-L55M16,
1756-L55M22, 1756-L55M23,
1756-L55M24, 1756-L61, 1756-L62,
1756-L63, 1757-SRM

User Manual

Important User Information

Solid state equipment has operational characteristics differing from those of


electromechanical equipment. Safety Guidelines for the Application,
Installation and Maintenance of Solid State Controls (publication SGI-1.1
available from your local Rockwell Automation sales office or online at
http://literature.rockwellautomation.com) describes some important
differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of
uses for solid state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this
equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for
indirect or consequential damages resulting from the use or application of
this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with
any particular installation, Rockwell Automation, Inc. cannot assume
responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to
use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without
written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware
of safety considerations.
WARNING

IMPORTANT
ATTENTION

Identifies information about practices or circumstances that can cause


an explosion in a hazardous environment, which may lead to personal
injury or death, property damage, or economic loss.

Identifies information that is critical for successful application and


understanding of the product.
Identifies information about practices or circumstances that can lead
to personal injury or death, property damage, or economic loss.
Attentions help you identify a hazard, avoid a hazard, and recognize
the consequence

SHOCK HAZARD

Labels may be located on or inside the equipment, for example, a drive


or motor, to alert people that dangerous voltage may be present.

BURN HAZARD

Labels may be located on or inside the equipment, for example, a drive


or motor, to alert people that surfaces may be dangerous
temperatures.

Allen-Bradley, RSLogix, RSLogix 5000, RSNetworx, DH+, PanelView, PanelViewPlus, and VersaView are trademarks of Rockwell
Automation, Inc.
RSView and RSLinx are registered trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Summary of Changes

Introduction

This release of this document contains new and updated information.


To find new and updated information, look for change bars, as shown
next to this paragraph.

Updated Information

The document contains the following changes:

Topic

Page

Series E information for 1756-CNB and -CNBR modules

Throughout manual

Redundant System Firmware Combinations

14

Compatible Software Versions

26

Enhancements in Revision 15.56

26

Corrected Anomalies in Revision 15.56

27

Revised Procedure for Setting the Minimum Value for the Watchdog Time

102

Restrictions and Known Anomalies

Appendix E

Update a System That Is Already at Revision 13

142

Store a Project to Nonvolatile Memory While Process Is Running

139

Change CNB Modules from Series D to Series E

131

Publication 1756-UM523F-EN-P - September 2006

Summary of Changes

Notes:

Publication 1756-UM523F-EN-P - September 2006

Table of Contents
Chapter 1
ControlLogix Redundancy
Overview

Whats in This Chapter? . . . . . . . . . . . . . . . . . . . . . . . . . . . .


What Are The Main Parts of a Redundant System? . . . . . . . .
What Firmware Combinations Make Up a
Redundant System? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
What Are the Important Terms in a Redundant System? . . . .
How Do I Assign the Primary Chassis? . . . . . . . . . . . . . . . . .
What Causes a Switch from One Controller to Another? . . . .
Can I Use a Network Access Port? . . . . . . . . . . . . . . . . . . . .
Do I See a Bump in Outputs During a Switchover?. . . . . . . .
How Does the Second Controller Stay Up to Date? . . . . . . . .
What If I Make Online Edits? . . . . . . . . . . . . . . . . . . . . . . . .
Does My Scan Time Increase? . . . . . . . . . . . . . . . . . . . . . . .
What Happens to Network Addresses During a Switchover? .
If You Have a ControlNet Network. . . . . . . . . . . . . . . . .
If You Have an EtherNet/IP Network . . . . . . . . . . . . . . .
What Cant I Do with a Redundant System? . . . . . . . . . . . . .
Quick Start Checklists . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Redundant Chassis Configuration . . . . . . . . . . . . . . . . . .
RSLogix 5000 Project . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operator Interface Terminals . . . . . . . . . . . . . . . . . . . . .
Compatible Software Versions . . . . . . . . . . . . . . . . . . . . . . .
Enhancements to Redundancy Revision 15.56. . . . . . . . . . . .
Corrected Anomalies in Redundancy Revision 15.56 . . . . . . .

13
13
14
15
15
15
16
16
16
18
18
18
19
20
20
21
21
22
23
25
26
26
27

Chapter 2
Design the System

How to Use This Chapter . . . . . . . . . . . . . . . . . . . . . . .


Lay Out the System . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Place the Pair of Redundant Chassis. . . . . . . . . . . . . . . .
If You Need More Than 100 Meters Between Chassis
Place the I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Place Operator Interface Terminals . . . . . . . . . . . . . . . .
Add Additional Redundant Components. . . . . . . . . . . . .
Redundant ControlNet Media . . . . . . . . . . . . . . . . . .
Redundant Power Supplies. . . . . . . . . . . . . . . . . . . .
Check Connection Requirements . . . . . . . . . . . . . . . . . .
Plan the ControlNet Networks . . . . . . . . . . . . . . . . . . . .
Plan the EtherNet/IP Networks . . . . . . . . . . . . . . . . . . .
Worksheet for IP Swapping . . . . . . . . . . . . . . . . . . .
How an EtherNet/IP Module Handles a Cable Break .
Additional Considerations . . . . . . . . . . . . . . . . . . . . . . .

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

29
30
32
32
33
34
35
35
36
37
37
40
41
42
43

Chapter 3
Install the System
5

When to Use This Chapter. . . . . . . . . . . . . . . . . . . . . . . . . . 45

Publication 1756-UM523F-EN-P - September 2006

Table of Contents

How to Use This Chapter . . . . . . . . . . . . . . . . . .


Preliminary Information. . . . . . . . . . . . . . . . . . . .
Install the Chassis for the Controllers . . . . . . . . . .
Install Modules in the First Redundant Chassis . . .
Install Modules in the Second Redundant Chassis .
Install the Remote Chassis or Rails . . . . . . . . . . . .
Configure the EtherNet/IP Modules . . . . . . . . . . .
Flash the Modules . . . . . . . . . . . . . . . . . . . . . . . .
Check Your Installation . . . . . . . . . . . . . . . . . . . .
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.

45
45
47
48
50
51
52
53
53
53
53
54

Chapter 4
Configure the System Redundancy Purpose of this Chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
When to Use this Chapter . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Module
How to Use this Chapter . . . . . . . . . . . . . . . . . . . . .
Open the SRM Configuration Tool . . . . . . . . . . . . . .
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before You Begin . . . . . . . . . . . . . . . . . . . . . . .
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
What to Do Next . . . . . . . . . . . . . . . . . . . . . . . .
Check the Revision of Your SRM Configuration Tool
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before You Begin . . . . . . . . . . . . . . . . . . . . . . .
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Check the Version of the Configuration Tool . . . . . .
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Set the Clock of the SRM . . . . . . . . . . . . . . . . . . . . .
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before You Begin . . . . . . . . . . . . . . . . . . . . . . .
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Test a Switchover . . . . . . . . . . . . . . . . . . . . . . . . . .
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before You Begin . . . . . . . . . . . . . . . . . . . . . . .
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Change the Auto-Synchronization Option. . . . . . . . .
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Publication 1756-UM523F-EN-P - September 2006

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

55
55
55
55
56
56
57
57
57
58
58
59
59
59
59
60
61
61
61
61
61
63
63
63
63
63
65
65
65
65

Table of Contents

Change the Program Control Option


Purpose. . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . .
Before You Begin . . . . . . . . . . .
Actions . . . . . . . . . . . . . . . . . . .

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

66
66
66
66
67

Chapter 5
Configure and Program the
Controller

When to Use This Chapter. . . . . . . . . . . . . . . . . . . . . . .


How to Use This Chapter . . . . . . . . . . . . . . . . . . . . . . .
Plan for Online Edits . . . . . . . . . . . . . . . . . . . . . . . . . . .
Decide if You Want to Keep Test Edits after
a Switchover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Be Aware That Finalizing Edits Removes
Your Original Logic . . . . . . . . . . . . . . . . . . . . . . . . .
Decide How You Want to Set Aside Unused Memory
Configure a Controller for Redundancy . . . . . . . . . . . . .
Configure Communications . . . . . . . . . . . . . . . . . . . . . .
Configure Produced Tags . . . . . . . . . . . . . . . . . . . .
Configure Message (MSG) Instructions . . . . . . . . . . .
Configure Tags for an HMI . . . . . . . . . . . . . . . . . . . .
Estimate the Crossload Time of a Program . . . . . . . . . . .
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before you begin . . . . . . . . . . . . . . . . . . . . . . . . . . .
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Minimize Scan Time . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintain the Integrity of Your Data During a Switchover
Look for Array Shift Instructions . . . . . . . . . . . . . . . .
Look for Scan-Dependent Logic . . . . . . . . . . . . . . . .
Take Preventative Actions . . . . . . . . . . . . . . . . . . . .
Determine the Status of Your Redundancy System . . . . .
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 1: Ladder Diagram . . . . . . . . . . . . . . . . . . .
Example 2: Structured Text. . . . . . . . . . . . . . . . . . . .
Check Your Work . . . . . . . . . . . . . . . . . . . . . . . . . .
For More Information. . . . . . . . . . . . . . . . . . . . . . . .
Condition Logic to Run After a Switchover . . . . . . . . . . .
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Example 1: Ladder Diagram . . . . . . . . . . . . . . . . . . .
Example 2: Structured Text. . . . . . . . . . . . . . . . . . . .
Send a Message to the SRM . . . . . . . . . . . . . . . . . . . . . .
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . 69
. . . 69
. . . 69
. . . 70
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

71
71
72
74
74
76
76
77
77
77
77
78
79
85
87
87
88
90
90
90
90
90
90
91
91
91
91
92
92
93
94
94
94

Publication 1756-UM523F-EN-P - September 2006

Table of Contents

Before You Begin . . . . . . . . . . . . . . . . . . . .


Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Download the Project to the Primary Controller .
Schedule the ControlNet Networks . . . . . . . . . .
Schedule a New Network . . . . . . . . . . . . . . .
Update the Schedule of an Existing Network.
Check the Keepers. . . . . . . . . . . . . . . . . . . .
Save the Project for Each Controller . . . . . . .
Set the Task Watchdog Times . . . . . . . . . . . . . .

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.

When to Use This Chapter. . . . . . . . . . . . . . . . . . .


How to Use This Chapter . . . . . . . . . . . . . . . . . . .
Find the Cause of a Switchover or Disqualification .
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshoot a Failure to Synchronize . . . . . . . . . .
Update a Keeper Signature . . . . . . . . . . . . . . . . . .
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before You Begin . . . . . . . . . . . . . . . . . . . . . .
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
See if an Edit Session Is in Progress . . . . . . . . . . . .
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Interpret the SRM Event Log . . . . . . . . . . . . . . . . .
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before You Begin . . . . . . . . . . . . . . . . . . . . . .
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Interpret SRM events . . . . . . . . . . . . . . . . . . . .
Export the SRM Event Log . . . . . . . . . . . . . . . . . . .
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
When . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Before You Begin . . . . . . . . . . . . . . . . . . . . . .
....................................
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manually Synchronize the Chassis . . . . . . . . . . . . .
Optimize Communication . . . . . . . . . . . . . . . . . . .
Choose a Greater System Overhead Time Slice .
Enter a System Overhead Time Slice. . . . . . . . .
Make All Your Tasks Periodic. . . . . . . . . . . . . .
Check the Allocation of Unused Memory . . . . . . . .
Adjust CNB Usage. . . . . . . . . . . . . . . . . . . . . . . . .

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.

.
.
.
.
.

95
96
98
98
99
100
100
101
102

Chapter 6
Maintain and Troubleshoot the
System

Publication 1756-UM523F-EN-P - September 2006

105
105
106
106
106
106
108
110
110
110
110
110
111
111
111
112
113
113
113
113
114
117
119
119
119
119
120
120
122
123
124
125
126
127
127

Table of Contents

Use RSLinx Software . . . . . . . . . . . . . . . . . . . .


Look at the Four-Character Display. . . . . . . . . .
Send a Message to the CNB Module . . . . . . . . .
Change CNB modules from Series D to Series E . . .
Before You Begin . . . . . . . . . . . . . . . . . . . . . .
Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Store or Load a Project Using Nonvolatile Memory .
Store a Project to Nonvolatile Memory While a
Process Is Running . . . . . . . . . . . . . . . . . . . . . . . .
Update a Module . . . . . . . . . . . . . . . . . . . . . . . . .
Update a System That Is Already at Revision 13 . . .

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

.
.
.
.
.
.
.

128
128
130
131
131
132
137

. . . . . . 139
. . . . . . 140
. . . . . . 142

Appendix A
Set Up EtherNet/IP
Communication Across Subnets

Purpose of This Chapter . . . . . . . . . . . . . . . . . . . . . . . . . . 149


When to Use This Chapter. . . . . . . . . . . . . . . . . . . . . . . . . 149
How to Use This Chapter . . . . . . . . . . . . . . . . . . . . . . . . . 149
Keep an HMI Communicating with the Primary Chassis . . . 150
Install the ControlLogix Redundancy Alias Topic Switcher
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Configure a Driver to Communicate with the Primary and
Secondary EtherNet/IP Modules . . . . . . . . . . . . . . . . . . 152
Create a DDE/OPC Topic for Each Controller . . . . . . . . 153
Create an Alias Topic . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Set Up the Alias Topic Switcher . . . . . . . . . . . . . . . . . . 155
Address the Alias Topic in the HMI Project . . . . . . . . . . 156
Keep a Message Going to the Primary Chassis . . . . . . . . . . 156
Create a Periodic Trigger for the Messages . . . . . . . . . . 157
Get the Redundancy State of Chassis A . . . . . . . . . . . . 158
Get the Redundancy State of Chassis B . . . . . . . . . . . . . 159
Determine Which Chassis is Primary . . . . . . . . . . . . . . . 161
Send the Message to the Appropriate Controller . . . . . . 162

Appendix B
Convert an Existing System to
Redundancy

Introduction . . . . . . . . . . . . . . . . . . . . . . .
Convert Local Modules to Remote Modules
Reconfigure the Local I/O Modules. . . .
Replace Local I/O Tags . . . . . . . . . . . .
Replace Any Aliases to Local I/O Tags .

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

.
.
.
.
.

165
165
166
166
168

Appendix C
Attributes of the Redundancy
Object

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171

Publication 1756-UM523F-EN-P - September 2006

10

Table of Contents

Appendix D
If You Have Series B ControlNet
Bridge Modules

About This Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175


Communication Loss If You Bridge Through a Series B
ControlNet Bridge Module. . . . . . . . . . . . . . . . . . . . . . . . . 175
Situation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Prevention. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
Communication Could Stop If You Use a Series B ControlNet
Bridge Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Situation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Corrective Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Prevention. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177

Appendix E
Redundant System Restrictions

Publication 1756-UM523F-EN-P - September 2006

Proper Use of an EtherNet/IP Network . . . . . . . . . . . . . . . 181

Preface

Purpose of this Manual

This manual guides the design, development, and implementation of a


redundancy system for a ControlLogix controller.

Who Should Use this


Manual

This manual is intended for those in the following professions who


design and develop applications that use ControlLogix controllers:

When to Use This Manual

Use this manual throughout the lifecycle of a redundancy system. The


lifecycle consists of the following stages:

How to Use this Manual

Software engineers
Control engineers
Application engineers
Instrumentation technicians

Design
Installation
Configuration
Programming
Testing
Maintenance and troubleshooting

This manual is divided into the basic tasks performed during the
design, development, and implementation of a ControlLogix
redundancy system.
Each chapter covers a task.
Tasks are organized in the sequence you will typically perform
them.
In this manual, some text is formatted differently.

Text That Is

Identifies

Italic

The actual name of an item that you Right-click User-Defined


see on your screen or in an example

Right-click on the item that is named


User-Defined.

Courier

Information that you must supply


based on your application (a
variable).

Right-click
name_of_program

You must identify the specific program in


your application. Typically, it is a name or
variable that you have defined.

Press [Enter].

Press the Enter key.

Enclosed in brackets A keyboard key.

11

For Example

Means

Publication 1756-UM523F-EN-P - September 2006

Preface

12

Related Documentation

This table lists ControlLogix products and documentation that may be


valuable as in programming an application.

Catalog Number

Title

Publication Number

1756-CNB/D and
1756-CNBR/D

ControlLogix ControlNet Bridge Module Installation Instructions

1756-IN571B

ControlLogix ControlNet Interface Module Release Notes

1756-RN587H

1756-CNB/E and
1756-CNBR/E

ControlLogix ControlNet Bridge Module, Series E Installation Instructions

1756-IN604A

ControlLogix ControlNet Bridge Module, Series E Release Notes

1756-RN627C

1756-ENBT/A

1756 10/100Mbps EtherNet/IP Bridge, Twisted Pair Media Release Notes

1756-RN602A

1756-ENBT

1756-ENBT ControlLogix EtherNet/IP Product Profile

1756-PP004A

ControlLogix EtherNet/IP Bridge Module Installation Instructions

1756-IN019C

ControlLogix EtherNet/IP Communication Release Notes

1756-RN591N

1756-EWEB EtherNet/IP Web Server Module Release Notes

1756-RN604E

EtherNet/IP Web Server Module Installation Instructions

1756-IN588A

EtherNet/IP Web Server Module User Manual

ENET-UM527D

ControlLogix Controller and Memory Board Installation Instructions

1756-IN101K

ControlLogix Controller and Memory Board Installation Instructions

1756-IN101K

ProcessLogix/ControlLogix System Redundancy Module Installation


Instructions

1757-IN092D

1756-EWEB

1756-L55
1756-L61
1756-L62
1756-L63
1756-M12
1756-M13
1756-M14
1756-M16
1756-M22
1756-M23
1756-M24
1757-SRM/B

Publication 1756-UM523F-EN-P - September 2006

Chapter

ControlLogix Redundancy Overview

Whats in This Chapter?

What Are The Main Parts of


a Redundant System?

This chapter provides an overview of the ControlLogix redundancy


system, including commonly used terms. It also answers some
common questions about a ControlLogix redundancy system.
Topic

Page

What Are The Main Parts of a Redundant System?

13

What firmware combinations make up a redundant system?

14

How Do I Assign the Primary Chassis?

15

What Causes a Switch from One Controller to Another?

15

Can I Use a Network Access Port?

16

Do I See a Bump in Outputs During a Switchover?

16

How Does the Second Controller Stay Up to Date?

16

What If I Make Online Edits?

18

Does My Scan Time Increase?

18

What Happens to Network Addresses During a Switchover?

18

What Cant I Do with a Redundant System?

20

Quick Start Checklists

21

Compatible Software Versions

26

Enhancements to Redundancy Revision 15.56

26

Corrected Anomalies in Redundancy Revision 15.56

27

The ControlLogix redundancy system uses an identical pair of


ControlLogix chassis to keep a machine or process running if a
problem occurs with a controller.
The following diagram shows the layout of a simple redundant setup.

13

Publication 1756-UM523F-EN-P - September 2006

14

ControlLogix Redundancy Overview

Network 1 -

Network 2 - ControlNet network for


I/O communications

EtherNet/IP network or
ControlNet network for HMI

Identical pair of
ControlLogix chassis that
control machine or
process

At least 2 other
ControlNet nodes

Computer that is connected to the


network access port of a remote node
43128

What Firmware
Combinations Make Up a
Redundant System?

The following firmware combinations make up revision 15.56 of the


ControlLogix redundancy system:

Module

Catalog Number

Series

Firmware Revision

ControlLogix5555 controller

1756-L55Mxx

Any

15.56

ControlLogix5561 controller

1756-L61

Any

15.56

ControlLogix5562 controller

1756-L62

Any

15.56

ControlLogix5563 controller

1756-L63

Any

15.56

ControlNet bridge module

1756-CNB
1756-CNBR

7.12

11.1

1756 10/100 Mbps EtherNet/IP Bridge, Twisted Pair Media

1756-ENBT

Any

4.3

1756 10/100 Mbps EtherNet/IP Bridge w/ Enhanced Web Services

1756-EWEB

Any

4.3

Redundancy module

1757-SRM

Any

4.3

Publication 1756-UM523F-EN-P - September 2006

ControlLogix Redundancy Overview

What Are the Important


Terms in a Redundant
System?

15

Redundancy requires no additional programming and is transparent to


any devices connected over an EtherNet/IP or ControlNet network.
Redundancy uses 1757-SRM modules to maintain communication
between the pair of redundant chassis.
In a redundant system, the following terms describe the relationship
between the two redundant chassis:

Term

Description

Primary Controller

The controller that is currently controlling the machine or process.

Primary Chassis

The chassis that contains the primary controller or controllers.

Secondary Controller

The controller that is standing by to take control of the machine or process. A secondary
controller always resides in a different chassis than the primary controller.

Secondary Chassis

The chassis that contains the secondary controller or controllers.

Switchover

Transfer of control from the primary controller to the secondary controller. After a
switchover, the controller that takes control becomes the primary controller. Its partner
controller (the controller that was previously the primary controller) becomes the
secondary controller.

How Do I Assign the


Primary Chassis?

In a pair of redundant chassis, the first chassis turned on becomes the


primary chassis. When to the secondary chassis receives power, it
chassis synchronizes itself with the primary chassis.

What Causes a Switch from


One Controller to Another?

When primary chassis components fail, control switches to the


secondary controller. A switchover occurs for any of the following
reasons:
any of the following situations in the primary chassis:
loss of power
major fault of the controller
removal, insertion, or failure of any module in the primary
chassis
break or disconnection of a ControlNet tap or ethernet cable
command from the primary controller
command from RSLinx software

Publication 1756-UM523F-EN-P - September 2006

16

ControlLogix Redundancy Overview

Can I Use a Network


Access Port?

To connect a device to the network access port (NAP) of a


1756-CNB/D/E or 1756-CNBR/D/E module, use an NAP that is outside
of a redundant chassis.
IMPORTANT

Use of the Network Access Port (NAP)


Do not connect any device to the network access port (NAP) of
a 1756-CNB/D/E or -CNBR/D/E module in a redundant chassis.
If you connect a device to the NAP of a CNB module in a
redundant chassis, a switchover will fail to occur if the
CNB module is disconnected from the network. While
the CNB module is disconnected from the network, the
controller will be unable to control any I/O devices
through that CNB module.
If you connect a workstation to the NAP of a CNB
module in a redundant chassis, the workstation will be
unable to go online after a switchover.
To connect a device to a ControlNet network via a NAP, use a
NAP that is outside of a redundant chassis.

Do I See a Bump in Outputs


During a Switchover?

Depending on how you organize your RSLogix 5000 project, outputs


may or may not experience a change in state (bump) during a
switchover.
During the switchover, outputs controlled by the highest priority
task experience a bump-free switchover. For example, outputs
dont revert to a previous state.
Outputs in lower priority tasks may experience a change of
state.
The switchover time of a redundant system depends on the type of
failure and the network update time (NUT) of the ControlNet network.
For a NUT of 10 ms, the switchover time is approximately 80 ms to
220 ms.

How Does the Second


Controller Stay Up to Date?

Publication 1756-UM523F-EN-P - September 2006

To take over control, the secondary controller requires the same


project as the primary controller. It also requires up-to-date tag values.

ControlLogix Redundancy Overview

17

The following terms describe the process of communication between


the two controllers.
Term

Description

CrossloadC

The transfer of any or all of the contents of the primary


controller to the secondary controller. This could be updated
tag values, force values, online edits, or any other information
about the project. A crossload happens initially when the
chassis synchronize and then repeatedly as the primary
controller executes its logic.

Synchronize

The process that readies a secondary chassis to take over


control if a failure occurs in the primary chassis. During
synchronization, the 1757-SRM modules check that the partner
modules in the redundant chassis pair are compatible with
each other. The SRM modules also provide the path for
crossloading (transferring) the content of the primary controller
to the secondary controller.
Synchronization occurs when power is applied to the secondary
chassis and after a switchover is diagnosed and fixed.
The secondary chassis is ready to assume control if the primary
chassis fails.

Disqualified

The secondary chassis isnt synchronized with the primary


chassis. If a secondary chassis is disqualified, it cant take over
control of the machine or process. A secondary chassis can be
manually disqualified.

Qualify

Same as synchronize

Qualified

Same as synchronized

The 1757-SRM modules keep communication between the primary


and secondary chassis.

Primary chassis

Crossload
1757-SRM modules

43129

Secondary chassis

Synchronized

Dont download the project to the secondary controller. While


the secondary controller is synchronizing with the primary
controller, the 1757-SRM modules automatically let the primary
controller transfer the project to the secondary controller.
Once the secondary controller is synchronized, the 1757-SRM
modules keep the controller synchronized by providing the path
for crossloading any changes that occur in the primary
controller. These changes include:
online edits.
force values.
changes to properties.
changes to data.
results of logic execution.

Publication 1756-UM523F-EN-P - September 2006

18

ControlLogix Redundancy Overview

What If I Make Online


Edits?

Online edits automatically crossload to the secondary controller. They


become inactive if a switchover happens before you assemble them
into the project. This stops a mistake from faulting both the old and
new primary controllers.
Suppose you test an online edit and it causes the controller to fault. In
that case, a switchover happens. The new primary controller
automatically untests the edits and goes back to the original code.
You have the option to keep the edits active after a switchover (at the
risk of faulting both controllers).

Does My Scan Time


Increase?

At the end of each program, the primary controller pauses its


execution to crossload the result of any output instruction that
executed in the program. This results in an increased program scan
time for a synchronized redundancy system.

Program Scan Time


Execute program in
primary controller

Start of program

What Happens to Network


Addresses During a
Switchover?

Publication 1756-UM523F-EN-P - September 2006

Crossload results to
secondary controller

End of program

Each CNB, ENBT, or EWEB module in a redundant chassis shares a


pair of network addresses with its partner in the other chassis.

ControlLogix Redundancy Overview

19

If You Have a ControlNet Network

1 2 3
0
4
7 6 5

1 2 3
0
4
7 6 5

Set each pair of CNB modules to


the same node number.

Primary
chassis

Secondary
chassis

24

25
CNB modules in the primary chassis
use the node number to which they
are set.

1 2 3
0
4
7 6 5

CNB modules swap node numbers.


Switchover

1 2 3
0
4
7 6 5

Secondary
chassis

25

Primary
chassis

24
CNB modules in the secondary chassis use the
node number to which they are set PLUS 1.

CNB modules swap node numbers.

Workstations and HMIs continue to connect


to the same node number.

Workstations and HMIs continue to connect


to the same node number.

Publication 1756-UM523F-EN-P - September 2006

20

ControlLogix Redundancy Overview

If You Have an EtherNet/IP Network


Set both EtherNet/IP modules to
the SAME IP address
Port Configuration

Primary
chassis

Port Configuration

Secondary
chassis

E
N
B
T

E
N
B
T

10.10.10.10

10.10.10.11

An EtherNet/IP module in the primary


chassis uses the IP address to which
it is set.

An EtherNet/IP module in the


secondary chassis uses the IP address
to which it is set + 1 in the last address
segment.
Switchover
EtherNet/IP modules

Secondary
chassis

Primary
chassis

E
N
B
T
10.10.10.11

What Cant I Do with a


Redundant System?

Publication 1756-UM523F-EN-P - September 2006

E
N
B
T
10.10.10.10

Dont use any of these features in a ControlLogix redundancy system:

local chassis I/O, 1756-DHRIO, or 1756-DNB modules


event task
inhibit a task
data storage on a CompactFlash card via the controller. Its OK
to store a project on a CompactFlash card. See page 137.
motion control, such as the following modules:
1756-HYD02

ControlLogix Redundancy Overview

Quick Start Checklists

21

1756-L60M03SE
1756-M02AE
1756-M02AS
1756-M03SE
1756-M08SE
1756-M16SE

The following checklists provide a summary of the criteria for a


successful ControlLogix redundancy system. See the remaining
chapters for more information on each parameter.

System Layout
Parameter
1. ControlNet networks

Criteria

Page

ControlNet networks are the primary networks for the system.

30, 33

OK to bridge to devices on other networks, such as DeviceNet, Universal Remote I/O,


and DH+ networks.
Networks follow the guidelines in Logix5000 Controllers Design Considerations,
publication 1756-RM094.
2. I/O Placement

All I/O modules in remote chassis or DIN rails (no I/O in the local chassis)

30, 33

All I/O in ONLY the following locations:


same ControlNet network as the redundant controllers (no bridging)
DeviceNet network (via a 1756-DNB module in a remote chassis)
universal remote I/O network (via a 1756-DHRIO module in a remote chassis)
3. ControlNet network update
times

NUTs 90 ms

37

NUTs specified relationship to each other

4. Number of ControlNet nodes At least 2 nodes on each network in addition to the CNBs in the redundant chassis - For
example, each ControlNet network has at least 4 nodes.
5. ControlNet node
assignments

Nonredundant nodes use the lowest node numbers

37
18, 37

CNB modules in the redundant chassis set close to the SMAX.


2 consecutive node addresses for each set of partner CNB modules (one in each
chassis)
Switches of each partner CNB module set to the same node address

6. Network Access Ports

No devices connected to the network access ports of CNB modules in the redundant
chassis

30

7. EtherNet/IP networks

EtherNet/IP networks are only for HMIs, workstations, and messaging (no control of I/O). 30, 40
No EtherNet/IP network for:
control of I/O
peer interlocking (produced and consumed tags)

Publication 1756-UM523F-EN-P - September 2006

22

ControlLogix Redundancy Overview

Redundant Chassis Configuration


Parameter

Criteria

Page

1. Chassis size

Same size chassis for each pair of redundant chassis.

31

2. Chassis layout

Only the following modules in each redundant chassis (NO other modules):

31

controllers
ControlNet modules
EtherNet/IP modules
System redundancy module (needs 2 slots)
Each chassis within a redundant pair looks the same:
Identical modules (same catalog number, series, revision, and memory size)
Same slot assignments
3. System redundancy
modules

1757-SRM module:

31, 32

1 in each redundant chassis


Needs 2 slots
Needs 1757-SRCx cable (1, 3, 10, 50, and 100 meter lengths)

4. Controllers

ControlLogix5555, ControlLogix5561, ControlLogix5562, or ControlLogix5563 controllers

31

Which type of controller do you want to use?


If ControlLogix5555, then 1 or 2 controllers in EACH redundant chassis.
If ControlLogix5561, ControlLogix5562, or ControlLogix5563, then ONLY 1 controller in
each redundant chassis.
Same type of controller throughout the chassis.
Enough memory for 2 copies of all data.
7 connections for redundancy
5. ControlNet modules

1756-CNB/D/E or 1756-CNBR/D/E module or modules:


CPU usage 75%
CNB modules have the same keeper information
5 CNB modules. See also parameter 6 below.

Publication 1756-UM523F-EN-P - September 2006

31, 110,
127

ControlLogix Redundancy Overview

23

Redundant Chassis Configuration (Continued)


Parameter

Criteria

Page

6. EtherNet/IP modules

1756-ENBT or 1756-EWEB modules:

31, 40

Which modules do you want to use?


If 1756-ENBT, catalog revision greater than or equal to E01 (E01, E02, , F01). See the
label on the side of the module or its box.
If 1756-EWEB, any catalog revision
Up to 2 EtherNet/IP modules in each redundant chassis, within these limits:
If you have

Use up to

1 ControlNet module

2 EtherNet/IP modules

2 ControlNet modules

2 EtherNet/IP modules

3 ControlNet modules

2 EtherNet/IP modules

4 ControlNet modules

1 EtherNet/IP module

5 ControlNet modules

No EtherNet/IP modules

Dont use more than 5 ControlNet


modules.

RSLogix 5000 Project


Parameter

Criteria

Page

1. Number of projects

Only one RSLogix 5000 project for the pair of redundant controllers. The project automatically
crossloads to the secondary controller when the secondary controller synchronizes with the
primary controller.

69

2. Controller properties

ControlLogix5555, ControlLogix5561, ControlLogix5562, or ControlLogix5563 controller

72

Redundancy enabled
3. Task structure

Only one task at the highest priority

74, 79,
123

If more than one task, all tasks periodic


4. I/O

Outputs that require a bumpless switchover are in the highest priority task

74

Requested packet interval (RPI) less than or equal to 375 milliseconds. (Larger RPIs may
produce a bump at switchover.).
5. Task watchdog time

Watchdog time (2 * maximum_scan_time) + 100 ms

102

where:
Maximum_scan_time is the maximum scan time for the entire task when the secondary
controller is synchronized.

Publication 1756-UM523F-EN-P - September 2006

24

ControlLogix Redundancy Overview

RSLogix 5000 Project (Continued)


Parameter
6. Minimizing scan time

Criteria
A few large programs instead of a lot of small programs

Page
79

No unused tags
Arrays and user-defined data types instead of individual tags
User-defined data types as compact as possible
Code as compact as possible
Code runs only when you need it
Data grouped by how often you need it
DINT tags instead of SINT or INT tags
7. Data integrity

Special treatment for:

85

Bit Shift Left (BSL) and Bit Shift Right (BSR) instructions
FIFO Unload (FFU) instructions
Logic that is scan dependent
8. Produced and
consumed tags

If you want a controller in another chassis to consume a tag from the redundant controller, use
a comm format of None. In the I/O configuration of the consuming controller, select a comm
format of None for the remote CNB module (the CNB that is physically in the redundant
chassis).

74

9. Message (MSG)
instructions

For any MSG instruction from a controller in another chassis to a redundant controller, cache
the connection.

74

Publication 1756-UM523F-EN-P - September 2006

ControlLogix Redundancy Overview

25

Operator Interface Terminals


Parameter

For any of these operator interfaces

Criteria

Page

1. EtherNet/IP network

PanelView Standard terminal

Same as a nonredundant system

30, 34, 40

PanelView Plus terminal


VersaView industrial computer running a
Windows CE operating system

RSView Supervisory Edition software with


RSLinx Enterprise software

Use RSLinx Enterprise software revision


3.0 or later.
Set aside connections for EACH PanelView
Plus or VersaView CE terminal:
In this module

Set aside

controller

5 connections

CNB

5 connections

ENBT

5 connections

EWEB

5 connections

Use RSLinx Enterprise software revision


3.0 or later.
Use IP swapping.
Keep the HMI and both redundant chassis
on the same subnet.

RSView Supervisory Edition software with


RSLinx 2.x software

Limit the number of RSLinx servers that a


controller uses to 1 (ideal) to 3 (maximum).

RSView 32 software
Any other HMI client software that uses
RSLinx 2.x software
2. ControlNet network

PanelView Standard terminal


PanelView 1000e/1400e terminal

Do terminals use unscheduled


communication?

30, 34, 37

Yes Use 4 terminals per controller.


No Use the number of terminals that
you need.
PanelView Plus terminal
VersaView industrial computer running a
Windows CE operating system

RSView Supervisory Edition software


RSView 32 software

Set aside connections for EACH PanelView


Plus or VersaView CE terminal:
In this module

Set aside

controller

5 connections

CNB

5 connections

Limit the number of RSLinx servers that a


controller uses to 1 (ideal) to 3 (maximum).

Any other HMI client software that uses


RSLinx 2.x software

Publication 1756-UM523F-EN-P - September 2006

26

ControlLogix Redundancy Overview

Compatible Software
Versions

With version 15.56 of the ControlLogix redundancy system, use any of


the following software versions:

For This Software

Use This Version

RSLinx

2.50

1757-SRM System Redundancy


Module Configuration tool

3.4

Notes
Important: Dont update the SRM Configuration tool at this time. See
Update a System That Is Already at Revision 13 on page 142.
Get Knowledgebase document G92234770. To access Rockwell
Automations Knowledgebase, go to
http://support.rockwellautomation.com

RSLinx Enterprise

3.0

You need this only for these HMIs:


PanelView Plus terminal
VersaView industrial computer running a Windows CE operating system
RSView Supervisory Edition software
Important: For RSView Supervisory Edition software, install the RSLinx
Enterprise HOTFIX. The HOTFIX improves the EtherNet/IP switchover time.
See Knowledgebase document R154640079. To access Rockwell
Automations Knowledgebase, go to
http://support.rockwellautomation.com

RSLogix 5000

15.01

RSNetWorx

5.11

Enhancements to
Redundancy Revision 15.56

Publication 1756-UM523F-EN-P - September 2006

The following enhancements apply to a redundant system using


revision 15.56:
Enhancement

Description

Update the firmware of


the redundant chassis
while the process is
running

This revision lets you update the firmware in the redundant


chassis without shutting down the process. To do this, the
system must be at revision 13.

Add I/O modules while


online

At runtime, add 1756 I/O modules to a remote chassis via the


unscheduled portion of a ControlNet network.

ControlLogix Redundancy Overview

Corrected Anomalies in
Redundancy Revision 15.56

27

Redundancy revision 15.56 corrects the following anomalies:

Corrected Anomaly

Description

The File Search Compare (FSC)


instruction caused an unrecoverable
fault

The FSC instruction caused a unrecoverable fault if both these conditions occurred:
major fault declared from within the expression of an FSC instruction
fault cleared by user fault routine
Lgx00055522

You couldnt send an SLC typed write


message to a redundant controller

An SLC-typed write message to a redundant controller produced error F007.


Lgx00058402

Memory changes during prescan


werent always crossloaded

Sometimes the primary controller didnt send data changes that it made during prescan to the
secondary controller.
Lgx00060517

Some data table write services


Data table write, big write, and read-modify-write services werent immediately forwarded to the
werent immediately forwarded to the secondary controller if the service used a symbolic address. Instead, they were forwarded after
secondary controller
the next program scan.
Lgx00060643
A secondary SRM faulted with an
E888 error if you unplugged a CNB
module

The secondary 1757-SRM module sometimes faulted while synchronized if you unplugged the tap
to a secondary 1756-CNB module. The error code of the SRM module was E888. This caused the
chassis to become disqualified.
You had to remove and reinsert the secondary SRM module under power to recover.
Lgx00060989

A synchronized chassis pair didnt


The redundant chassis pair didnt automatically synchronize after multiple cycles of
automatically synchronize after being disqualification caused by either unplugging the tap to a secondary 1756-CNB module or
disqualified
power-cycling the secondary chassis.
You had to remove and reinsert the secondary SRM module under power to recover.
Lgx00061808, Lgx00060991
Sometimes a module faulted after a
switchover

Sometimes a module would fault after a broken or disconnected communication cable caused a
switchover. The module showed a fault code of 16#0022.
Lgx00061990

The SRM pair lost the fiber optic


connection under heavy HMI traffic

The synchronized pair of 1757-SRM modules would sometimes lose their connection across the
fiber optic link under heavy HMI traffic conditions. This caused the secondary chassis to become
disqualified either with the SRM modules showing no partner or the secondary module showing
error EA91
You had to remove and reinsert the secondary SRM module under power to recover.
Lgx00062847, Lgx00062839, Lgx00062171

Publication 1756-UM523F-EN-P - September 2006

28

ControlLogix Redundancy Overview

Corrected Anomaly

Description

The primary SRM module rejected a


synchronization command

The primary 1757-SRM module rejected a synchronization command when:


the auto-qualification option was set to Never
and
the synchronization command was given within 30 seconds after disqualification of the
redundant chassis pair.
The SRM module continued to reject any synchronization command. You had to change the
auto-qualification option to Always to synchronize the chassis.
Lgx00062954, Lgx00058896, Lgx00037660

ENBT module wouldnt reply to a ping Sometimes you wouldnt get a reply when you pinged a 1756-ENBT module.
Lgx00062979
Updating a primary SRM module
caused an unrecoverable fault

Updating the firmware of a 1757-SRM module in a primary chassis sometimes caused an


recoverable fault in the controller. This happened if the controller ran out of outgoing unconnected
buffers.
Lgx00063005

CompactFlash image caused a major


fault

A controller had a major fault if you:


stored a CompactFlash image using a controller that was last powered down as a disqualified
secondary controller
and
configured the image to go to run mode after loading.
Lgx00063515

You couldnt download to a


disqualified secondary controller
without enough memory reserved for
logic

You couldnt download to a


disqualified secondary controller
if the slider was too close to Tags.
Lgx00063587

Publication 1756-UM523F-EN-P - September 2006

Chapter

Design the System

Use this chapter to design a redundancy system for a ControlLogix


controller

How to Use This Chapter

29

To design your system, complete the following tasks:


Topic

Page

Lay Out the System

30

Place the Pair of Redundant Chassis

32

Place the I/O

33

Place Operator Interface Terminals

34

Add Additional Redundant Components

35

Check Connection Requirements

37

Plan the ControlNet Networks

37

Plan the EtherNet/IP Networks

40

Additional Considerations

43

Publication 1756-UM523F-EN-P - September 2006

30

Design the System

Lay Out the System

ControlLogix Redundancy Requirements and Recommendations

Use separate networks for unscheduled and scheduled


communication

Unscheduled Communication
EtherNet/IP

or

ControlNet

For unscheduled communication (HMI, workstations,


message instructions), use either an EtherNet/IP or a
ControlNet network.
For scheduled communications (I/O, produced/consumed
tags), use a ControlNet network.

Scheduled Communication
ControlNet

For unscheduled communication,


use 4 PanelView terminals per
controller.
ControlNet network:
Set NUT 90 ms

Multiple redundant chassis


pairs are OK.

Set RPIs 375 ms


If multiple ControlNet
networks, set NUTs
specified values.

Remote location for all:


I/O
DNB, DHRIO, & MVI
communication modules
Assign the lowest node numbers
to nonredundant nodes.

C
N
B

I/O modules

E D D M
N N H V
B B R I
I
O

To connect a computer to the


network via an NAP, use a remote
node.

Other networks
At least 2 nodes in
addition to the CNBs in
the redundant chassis

An additional node can be:


a second CNB module in the same remote chassis or in a different remote chassis
any other ControlNet device (not required to be keeper capable)

Publication 1756-UM523F-EN-P - September 2006

Design the System

31

ControlLogix Redundancy Requirements and Recommendations (Continued)


1756-ENBT or 1756-EWEB modules:
1756-CNB/D/E or 1756-CNBR/D/E module or modules:

1- 2 in each redundant chassis


5 total communication modules (CNBs and ENBTs) in each
redundant chassis

1-5 in each redundant chassis


5 total communication modules (CNBs, ENBTs, and
EWEBs) in each redundant chassis

For 1756-ENBT modules, catalog revision must be greater than


or equal to E01 (E01, E02, , F01). See the side of the module
or its box.

Keep CPU usage 75%,


Allocate 2 consecutive node addresses for each set of
partner CNB modules (one in each chassis).

Requires RSLinx software, version 2.41.00 (Build 10.6) or later.

Assign each partner CNB module to the same node


address.

ControlLogix5555, ControlLogix5561, ControlLogix5562, or


ControlLogix5563 controllers:

Assign the higher node addresses in the system to the


CNB modules in the redundant chassis.

Same type of controller throughout the chassis.


If ControlLogix5555, then 1 or 2 controllers in EACH
redundant chassis.
If ControlLogix5561, ControlLogix5562, or
ControlLogix5563, then only 1 controller in EACH
redundant chassis.

1757-SRM module:

Enough memory for 2 copies of all data.

Only 1 in each redundant chassis

7 connections for redundancy

uses 2 slots
Redundant
Chassis A

E C
N N
B B
T

S
R
M

No other modules

Identical modules:
Same size of chassis

Same slot number


Same catalog number, series, and revision
Same memory size (controller)

Redundant
Chassis B

E C
N N
B B
T

S
R
M

No other modules
1757-SRCx cable
1, 3, 10, 50, and
100 meter lengths

Publication 1756-UM523F-EN-P - September 2006

32

Design the System

Place the Pair of Redundant


Chassis

Redundant
Chassis A

With the standard redundancy module cables, a pair of redundant


chassis (primary and secondary) can function up to 100 meters apart.

E C
N N
B B
T

S
R
M

No other modules

Redundancy Module Cable:


1757-SRC1 cable (1 meter)
1757-SRC3 cable (3 meters)
1757-SRC10 cable (10 meters)
1757-SRC50 cable (50 meters)
1757-SRC100 cable (100 meters)

Redundant
Chassis B

E C
N N
B B
T

S
R
M

No other modules

If You Need More Than 100 Meters Between Chassis


To place the primary and secondary controller chassis more than 100
meters apart, use a custom fiber optic cable. For a custom cable,
follow these rules:
1. Keep total light loss through the cable less than or equal to 7dB.
2. Keep total length less than or equal to 4 km.
3. Use high quality 62.5/125 micron multi-mode fiber-optic cable.
4. Use professionally installed SC-style connectors to connect to
the 1757-SRM modules.

Publication 1756-UM523F-EN-P - September 2006

Design the System

Place the I/O

33

In a ControlLogix redundancy system, place all I/O in ONLY the


following locations:
Same ControlNet network as the redundant controllers (no
bridging to I/O modules on another ControlNet network)
DeviceNet network
Universal remote I/O network

Redundant chassis pair

ControlNet network

C
N I/O modules
B

D D
H N
R B
I

C E
N N
B B

Remote chassis

I/O No
EtherNet/IP network

HMI Yes
I/O No

ControlNet network

HMI Yes
I/O Yes

DeviceNet network

HMI Yes
I/O Yes

Universal remote I/O network

HMI Yes

Publication 1756-UM523F-EN-P - September 2006

34

Design the System

Place Operator Interface


Terminals

For operator interface terminals, stay within these limitations:

For this network

And any of these operator interfaces

Follow these guidelines

EtherNet/IP network

PanelView Standard terminal

Same as a nonredundant system

PanelView Plus terminal


VersaView industrial computer running a
Windows CE operating system

RSView Supervisory Edition software with RSLinx


Enterprise software

Use RSLinx Enterprise software revision 3.0 or


later.
Set aside connections for each PanelView Plus or
VersaView CE terminal:
In this module

Set aside

controller

5 connections

CNB

5 connections

ENBT

5 connections

EWEB

5 connections

Use RSLinx Enterprise software revision 3.0 or


later.
Use IP swapping.
Keep the HMI and both redundant chassis on the
same subnet.

RSView Supervisory Edition software with


RSLinx 2.x software

Limit the number of RSLinx servers that a controller


uses to 1 (ideal) to 3 (maximum).

RSView 32 software
Any other HMI client software that uses
RSLinx 2.x software
ControlNet network

PanelView Standard terminal


PanelView 1000e/1400e terminal

Do your terminals use unscheduled communication?


Yes Use 4 terminals per controller.
No Use the number of terminals that you need.

PanelView Plus terminal


VersaView industrial computer running a
Windows CE operating system

RSView Supervisory Edition software


RSView 32 software
Any other HMI client software that uses
RSLinx 2.x software

Publication 1756-UM523F-EN-P - September 2006

Set aside connections for each PanelView Plus or


VersaView CE terminal:
In this module

Set aside

controller

5 connections

CNB

5 connections

Limit the number of RSLinx servers that a controller


uses to 1 (ideal) to 3 (maximum).

Design the System

Add Additional Redundant


Components

35

In addition to using redundant pairs of controllers, you may also add


the following redundant components to your system:
Redundant ControlNet Media
Redundant Power Supplies

Redundant ControlNet Media


Redundant ControlNet media prevents a loss of communication if a
trunkline or tap is severed or disconnected. It uses the following
components:
1756-CNBR ControlNet modules
Two identical ControlNet links

ControlLogix chassis with


1756-CNBR module

ControlNet node

Redundant media

ControlNet node

Publication 1756-UM523F-EN-P - September 2006

36

Design the System

Redundant Power Supplies


Redundant power supplies let you maintain power to a ControlLogix
chassis if a power supply fails. Redundant power supplies use the
following hardware:
Two redundant power supplies, any combination of 1756-PA75R
and 1756-PB75R
1756-PSCA chassis adapter module, in place of the standard
power supply
Two 1756-CPR cables to connect the power supplies to the
1756-PSCA adapter
User-supplied annunciator wiring to connect the power supplies
to the input modules if needed
1756-PA75R or
1756-PB75R

1756-CPR cable

ControlLogix chassis with


1756-PSCA module

Publication 1756-UM523F-EN-P - September 2006

1756-PA75R or
1756-PB75R

Annunciator wiring
1756 digital
input module

Design the System

Check Connection
Requirements

37

Set aside seven connections in each redundant controller for


redundancy communication:
Two connections for the SRM
Five connections for the partner controller

Plan the ControlNet


Networks

Follow these guidelines to plan a ControlNet networks:

Guideline

Details

1. Make sure the network has at least 2 nodes plus the


redundant chassis pair.

An additional node can be:


a second CNB module in the same remote chassis or in a different remote
chassis
any other ControlNet device
a workstation that is running RSLinx software.
If your ControlNet network contains only one node other than the redundant
chassis pair, that node will drop its connections during a switchover. This may
cause the outputs of that node to change state during the switchover.

2. Give the lowest ControlNet addresses to I/O chassis


and other remote chassis.

Dont give the lowest addresses to the redundant chassis pair.


If you give the lowest address to a CNB module in the redundant chassis pair:
on a switchover, you may temporarily lose communication with I/O
modules, produced tags, and consumed tags.
If you remove the CNB module from the primary chassis while chassis
power is on, you may temporarily lose communication with I/O modules,
produced tags, and consumed tags.
If every ControlNet node powers down at the same time (for example, a
plant-wide power loss), you may have to cycle the power to the primary
chassis to restore communication.

Publication 1756-UM523F-EN-P - September 2006

38

Design the System

Guideline

Details

3. Set aside 2 consecutive ControlNet addresses for


each pair of redundant chassis (for example, nodes 3
and 4).

If each redundant chassis has multiple CNB modules, set aside a pair of
node numbers for each pair of CNB modules (one in each chassis).
Do not configure any other device on the ControlNet network for either of
these addresses. For example, if you allocated nodes 3 and 4 for the
redundant chassis, then no other device should use those node numbers.

Pair of CNB modules (one in each


redundant chassis)

Slot and node numbers


Slot #

Primary node #

Secondary node #
(primary node # + 1)

1st pair of CNB modules


2nd pair of CNB modules
3rd pair of CNB modules
4th pair of CNB modules
5th pair of CNB modules

4. Know that the switchover time depends on the NUT of Use the network update time (NUT) of the ControlNet network to estimate
the ControlNet network.
how long it takes your system to switchover:
If

And the NUT is

Then the switchover time is

The chassis loses power or


a module fails

6 ms or less

60 ms

7 ms or more

5 (NUT ) + MAX (2 (NUT ), 30)

A CNB module cant


communicate with any
other node

14 (NUT ) + MAX (2 (NUT ), 30) + 50

Example 1
The chassis loses power and the NUT = 4 ms. In that case, the switchover
time is approximately 60 ms.
Example 2
The chassis loses power and the NUT = 10 ms. In that case, the switchover
time is approximately 80 ms.
Example 3
You unplug the CNB from the network and the NUT = 10 ms. In that case, the
switchover time is approximately 220 ms.
5. Use a NUT that is less than or equal to 90 ms.

Publication 1756-UM523F-EN-P - September 2006

If you use a larger network update time (NUT), the controller could lose its
connection with a module during a switchover. This could cause outputs to
change state.

Design the System

Guideline

Details

6. Do the redundant chassis use more than 1 ControlNet


network?
Yes See page 31.

The NUT of each network must be within the values indicated on page 31. If
you use a larger network update time (NUT), the controller could lose its
connection with a module during a switchover. This could cause outputs to
change state.

No Skip this guideline.

Example
If the NUT of this network is 5 ms

39

Then the NUT of this network must be


21 ms or less.

ControlNet
network 1

ControlNet
network 2

If the smallest
NUT on a network
is (ms):

Then the largest NUT on any other


network must be less than or equal
to (ms):

If the smallest
NUT on a network
is (ms):

Then the largest NUT on any other


network must be less than or equal
to (ms):

15

21

55

17

22

57

19

23

59

21

24

62

23

25

64

25

26

66

27

27

68

29

28

71

10

31

29

73

11

33

30

75

12

35

31

78

13

37

32

80

14

39

33

82

15

41

34

84

16

43

35

87

17

46

36

89

18

48

37 - 90

90

19

50

20

52

Publication 1756-UM523F-EN-P - September 2006

40

Design the System

Plan the EtherNet/IP


Networks

Follow these guidelines as you plan your EtherNet/IP networks:

Guideline

Details

1. Use EtherNet/IP ONLY for HMIs, workstations, and


messaging.

In a redundant system, use an EtherNet/IP network only for HMI, workstation,


and message communication. Do not use an EtherNet/IP network for:
control of I/O modules.
peer interlocking (produced and consumed tags).
Important: RSLogix 5000 software lets you set up and download a project
that tries to use an EtherNet/IP network for I/O, produced tags, or consumed
tags. Those communications dont work however.

2. Are communication delays OK during a switchover?


If Yes, then continue with EtherNet/IP.
If No, then use ControlNet.

Communication stops over an EtherNet/IP network with your controllers and


HMIs during a switchover.
You wont be able to communicate with them for up to a minute.
The actual delay depends on your network topology.
If you need bumpless communication, use a ControlNet network.

3. If you need a redundant network, use ControlNet.

2 EtherNet/IP modules in same chassis doesnt give you redundant


EtherNet/IP communication. A switchover still happens if one of the modules
fails or a cable breaks.
See How an EtherNet/IP Module Handles a Cable Break on page 42.

4. Make sure that your ENBT modules are catalog


revision E01 or later.

ControlLog

Ethernet/IP 10/100

CAT. NO./SERIES

CAT. REV.

1756-ENBT

E01

To use a 1756-ENBT module in a redundant controller chassis, make sure the


catalog revision of the module is greater than or equal to E01 (E01, E02, ,
F01).
To find the catalog revision, look at the label on the side of the module or
box.
If you use an older ENBT module, your secondary chassis wont
synchronize.

Catalog revision

Publication 1756-UM523F-EN-P - September 2006

Design the System

Guideline

41

Details

5. Decide how to handle IP addresses.

If BOTH redundant chassis are on Then


Use IP swapping.

Same subnet

During a switchover the primary and


secondary modules swap IP
addresses. This lets you use the same
IP address regardless of which
chassis is primary.

Switch
Primary
chassis

Secondary
chassis

See the next guideline for details.


You MUST change to the new primary
address after a switchover. Use
ControlLogix Redundancy Alias Topic
Switcher software to do this. See
Appendix A.

Different subnets
Router

Switch

Switch

Primary
chassis

6. If youre using IP swapping, give the same IP


address to the primary module and its partner.

Secondary
chassis

A. Give the SAME IP address, subnet mask, and gateway address to BOTH
modules in the redundant pair.
B. Leave the next highest IP address open for the secondary module.

For example
Set the primary and secondary
modules to

10.10.10.10

Leave this open for the secondary

10.10.10.11

The module in the secondary chassis automatically uses the IP address of the
primary + 1.

Worksheet for IP Swapping


Pair of ENBT or EWEB modules
(one in each redundant chassis)

Slot #

Configuration
Primary
IP address

Secondary IP address
(primary address + 1)

Subnet mask

Gateway address

1st pair of ENBT or EWEB modules


2nd pair of ENBT or EWEB modules

Publication 1756-UM523F-EN-P - September 2006

42

Design the System

How an EtherNet/IP Module Handles a Cable Break


An EtherNet/IP module looks for a carrier signal only from the closest
switch. It doesnt know the health of the network beyond that point.
Data doesnt have to be flowing.
If the EtherNet/IP module:
gets the carrier signal, it considers the network as OK.
doesnt get the carrier signal, it shows Link lost.
One switch
One subnet

/LQNORVW

/LQNORVW

Several switches
Several subnets
C
ZRQWVZLWFKRYHU

ZRQWVZLWFKRYHURUGLVTXDOLI\WKH
VHFRQGDU\FKDVVLV

ZLOOV\QFKURQL]H

ZLOOV\QFKURQL]H

+0,FDQWFRPPXQLFDWHZLWK
SULPDU\FKDVVLV

+0,ZRQWEHDEOHWRFRPPXQLFDWH
ZLWKWKLVFKDVVLVLILWEHFRPHVSULPDU\

VZLWFK

6XEQHW%

6XEQHW$

URXWHU
ZLOOVZLWFKRYHU
ZRQWV\QFKURQL]H

ZLOOGLVTXDOLI\

VZLWFK

VZLWFK

(WKHU1HW,3PRGXOH
VKRZV/LQNORVW

(WKHU1HW,3PRGXOH
VKRZV/LQNORVW

SULPDU\FKDVVLV

Publication 1756-UM523F-EN-P - September 2006

ZRQWV\QFKURQL]H

VHFRQGDU\FKDVVLV

Design the System

43

Additional Considerations
Switchover Always Triggers an Event
Task in a Remote, Nonredundant
Controller

A switchover triggers an event task under the following combination of circumstances:


The event task is in a nonredundant controller. An Event task is not permitted in a redundant
controller.
A redundant controller triggers the event task via a produced tag.
This occurs regardless of how you configure the produced tag.

Both configurations always trigger an


event task during a switchover.

Simultaneous Branch Delays the


Execution of a Higher Priority Task
In an SFC, each path of a simultaneous branch delays
the execution of a higher priority task by up to 25 s.

Publication 1756-UM523F-EN-P - September 2006

44

Design the System

Notes:

Publication 1756-UM523F-EN-P - September 2006

Chapter

Install the System

When to Use This Chapter

Use this chapter to install the hardware of a ControlLogix redundancy


system.

How to Use This Chapter

To install the system, complete the following tasks:


Topic

Page

Review the Preliminary Information

45

Install the Chassis for the Controllers

47

Install Modules in the First Redundant Chassis

48

Install Modules in the Second Redundant Chassis

50

Install the Remote Chassis or Rails

51

Configure the EtherNet/IP Modules

52

Flash the Modules

53

Check Your Installation

53

Preliminary Information
IMPORTANT

Use of the Network Access Port (NAP)


Do not connect any device to the network access port (NAP) of
a 1756-CNB/D/E or 1756-CNBR/D/E module in a redundant
chassis.
If you connect a device to the NAP of a CNB module in a
redundant chassis, a switchover will fail to occur if the CNB
module is disconnected from the network. While the CNB
module is disconnected from the network, the controller
will be unable to control any I/O devices through that CNB
module.
If you connect a workstation to the NAP of a CNB module in
a redundant chassis, the workstation will be unable to go
online after a switchover.
To connect a device to a ControlNet network via a NAP, use a
NAP that is outside of a redundant chassis.

45

Publication 1756-UM523F-EN-P - September 2006

46

Install the System

This chapter provides the sequence of tasks and the critical actions for
the successful installation of a ControlLogix redundancy system. It
does not replace the installation instructions for the components of
the system. During installation, refer to the following publications:
Install this component

According to this publication

1756-A4, -A7, -A10, -A13, or -A17 chassis

ControlLogix Chassis Installation Instructions, publication 1756-IN080

1756-PA72 or -PB72 power supply

ControlLogix Power Supplies Installation Instructions, publication 1756-5.67

1756-PA75 or -PB75 power supply

ControlLogix Power Supplies Installation Instructions, publication 1756-5.78

ControlLogix controller

ControlLogix Controller and Memory Board Installation Instructions, publication


1756-IN101

1756-CNB/D/E or -CNBR/D/E module

ControlLogix ControlNet Bridge Installation Instructions, publication 1756-IN571

1756-ENBT module

ControlLogix EtherNet/IP Bridge Module Installation Instructions, publication


1756-IN019

1756-EWEB module

EtherNet/IP Web Server Module Installation Instructions, publication 1756-IN588

1757-SRM module

ProcessLogix/ControlLogix System Redundancy Module Installation Instructions,


publication 1757-IN092

Installation instructions provide important information, such as


detailed installation steps, safety considerations, enclosure
requirements, and hazardous location information.
Before installing the system, review the following guidelines for safe
handling of ControlLogix components:

WARNING

When you insert or remove a module while backplane power is


on, an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed
or the area is nonhazardous before proceeding.

Repeated electrical arcing causes excessive wear to contacts on both a


module and its mating connector. Worn contacts may create electrical
resistance that can affect module operation.

Publication 1756-UM523F-EN-P - September 2006

Install the System

ATTENTION

47

Preventing Electrostatic Discharge


This equipment is sensitive to electrostatic discharge, which
can cause internal damage and affect normal operation. Follow
these guidelines when you handle this equipment:

Touch a grounded object to discharge potential static.


Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
If available, use a static-safe workstation.
When not in use, store the equipment in appropriate
static-safe packaging.

Install the Chassis for the


Controllers
1.

42798

2.

1. Install the two ControlLogix chassis (redundant) that will contain


the controllers.
Place the chassis within the length of a 1757-SRCx cable.
Install each chassis according to the ControlLogix Chassis
Installation Instructions, publication 1756-IN080.
If you are converting an existing system that contains local
I/O modules, you still need two additional chassis. In a
redundant system, you must place all I/O modules outside
the redundant chassis pair.

Publication 1756-UM523F-EN-P - September 2006

48

Install the System

2. For each chassis, install a ControlLogix power supply according


to the corresponding installation instructions:
Install this power supply

According to this publication

1756-PA72

ControlLogix Power Supplies Installation Instructions,


publication 1756-IN078B

1756-PB72
1756-PA75R
1756-PB75R

Install Modules in the First


Redundant Chassis
IMPORTANT

ControlLogix Redundant Power Supply Installation


Instructions, publication 1756-IN573C

Set the rotary switches of the 1756-CNB/D/E or


1756-CNBR/D/E modules for both redundant chassis to the
same node address.

1. Set the rotary switches of each of the 1756-CNB/D/E or


1756-CNBR/D/E modules to the primary node number plus one.
42796

2.

For example, nodes 3 and 4 have a primary node number of 2.


If you allocate nodes 3 and 4 for the redundant chassis, set both
CNB modules to node 3.

This is only an example. You can install the


module in any slot.

C
N
B

3.

42799

2. Install a 1756-CNB/D/E or 1756-CNBR/D/E module. See


ControlLogix ControlNet Bridge Installation Instructions,
publication 1756-IN571.

Publication 1756-UM523F-EN-P - September 2006

Install the System

WARNING

49

If you connect or disconnect the communications cable with


power applied to this module or any device on the network, an
electrical arc can occur. This could cause an explosion in
hazardous location installations.
Be sure that power is removed or the area is nonhazardous
before proceeding.

3. Connect the CNB module to the ControlNet network.


4.

5.

L C E
5 N N
5 B B
T

6.

This is only an example. You can install the


modules in any slot.

S
R
M

42799

4. Install the controller or controllers. See ControlLogix Controller


and Memory Board Installation Instructions, publication
1756-IN101.
5. Install the 1756-ENBT or 1756-EWEB module or modules (2
max.), if required. Connect each module to an ethernet switch.
6. Install the 1757-SRM module. See ProcessLogix/ControlLogix
System Redundancy Module Installation Instructions,
publication 1757-IN092.

Publication 1756-UM523F-EN-P - September 2006

50

Install the System

Install Modules in the


Second Redundant Chassis
1.

L C E
5 N N
5 B B
T

S
R
M

L C E
5 N N
5 B B
T

S
R
M

2.

42800

3.

IMPORTANT

The modules in each redundant chassis must match each other


slot-by-slot.
Set the rotary switches of the 1756-CNB/D/E or 1756-CNBR/D/E
modules for both redundant chassis to the same node address.

1. For each module in the first redundant chassis, install an


identical module into the same slot of the second redundant
chassis.
2. Connect the CNB, ENBT, and EWEB modules to their respective
networks.
3. Connect one of the following fiber optic cables to the 1757-SRM
modules:
1757-SRC1
1757-SRC3
1757-SRC10
1757-SRC50
1757-SRC100

Publication 1756-UM523F-EN-P - September 2006

Install the System

Install the Remote Chassis


or Rails

51

You must install all I/O modules and additional types of


communication modules in remote chassis or on DIN rails. The
following example shows a remote 1756 chassis. You can use any
type of chassis or device that you can connect to the ControlNet
network.
DeviceNet network

L C E
5 N N
5 B B
T

S
R
M

L C E
5 N N
5 B B
T

S
R
M

C
N
B

I/O modules

D
N
B

42197

Other ControlNet node (s)


You must have at least 2 other nodes in addition to the redundant
chassis pair. See Lay Out the System on page 2.

IMPORTANT

If you connect the workstation to the network via a network


access port on a CNB module, use a CNB module in a remote
chassis. This lets a switchover occur after the failure of a
ControlNet tap of a primary chassis.

As you install the chassis, follow these guidelines:


Do not assign any device to the address of the CNB modules in
the redundant chassis plus one.
For example, if you set the rotary switches of the CNB modules
in the redundant chassis to node 11, no other device should use
node 12.
Use a remote chassis for communication modules such as:
1756-ENET
1756-DHRIO
1756-MVI
1756-DNB

Publication 1756-UM523F-EN-P - September 2006

52

Install the System

Configure the EtherNet/IP


Modules

To use an EtherNet/IP module, give it an IP address, subnet mask, and


gateway address:

Action

Details

1. Before you begin.

A. Perform the following steps if you havent already:


Install and connect both 1757-SRM modules
Get the IP address, subnet mask, and gateway address for each EtherNet/IP module.
See Plan the EtherNet/IP Networks on page 12.
B. Do you know how to configure an EtherNet/IP module in a nonredundant system?
If no, then continue with step C.
If yes, then go to step 2.
C. Get the following publication:
EtherNet/IP Modules in Logix5000 Control Systems, publication ENET-UM001
Youll use that publication when you configure each module.

2. Configure the EtherNet/IP modules in


the first chassis.

A. Turn on the power to only one of the redundant chassis.


For example, if both chassis are on, turn off one of them.
B. Configure the EtherNet/IP module in the chassis that is on.
C. Do you see the IP address on the front of the module?
If no, then return to step B.
If yes, then continue with step D.
D. Repeat steps 2B and 2C for each EtherNet/IP module in this chassis.

3. Configure the EtherNet/IP modules in


the second chassis.

A. Turn off the chassis that you just configured.


B. Turn on the other chassis.
C. Configure the EtherNet/IP module in the chassis that is on.
D. Do you see the IP address on the front of the module?
If no, then return to step C.
If yes, then continue with step E.
E. Repeat steps 3C and 3D for each EtherNet/IP module in this chassis.

Publication 1756-UM523F-EN-P - September 2006

Install the System

Flash the Modules


Redundancy Module

PRIM
PRI COM

OK

42801

53

1. Turn on the power to one of the redundant chassis.


2. Wait for the 1757-SRM module to display PRIM.
3. Flash upgrade each module in the chassis with a compatible
revision of firmware.
See the ControlFLASH Firmware Upgrade Kit User Manual,
publication 1756-6.5.6.
To find the chassis in RSLinx software, locate the node
number or IP address on the front of the communication
module.
4. Turn off the power to the chassis.
5. Turn on the power to the second redundant chassis.
6. Wait for the 1757-SRM module to display PRIM.
7. Flash upgrade each module in the chassis with a compatible
revision of firmware. Use the same revisions that you used for
the first redundant chassis.

Check Your Installation

Purpose
To make sure that your redundant chassis are able to synchronize

When
Complete this procedure after you:
install the system.
configure the communication modules.
update firmware.

Publication 1756-UM523F-EN-P - September 2006

54

Install the System

Actions
First chassis
turned on
Redundancy Module

PRIM
PRI COM

Second chassis
turned on
Redundancy Module

SYNC
OK

PRI COM

1. Turn on the chassis power to the partner (secondary) chassis.


2. Wait for the 1757-SRM module to complete its power-up cycle.
The SRM module takes 1 to 3 minutes to power up.
It may also take several minutes to synchronize the secondary
controller.

OK

42801

3. Does 1 of the 1757-SRM modules show PRIM and the other


module show SYNC?
Yes Stop. The system is synchronized.
No There is a problem. The system isnt synchronized. Go
to step 4.
4. Make sure that the Auto-Synchronization option of the SRMs is
set to Always. For help, see Chapter 4.
5. Does 1 of the 1757-SRM modules show PRIM and the other
module show SYNC?
Yes Stop. The system is synchronized.
No Go to Troubleshoot a Failure to Synchronize on page 5.

Publication 1756-UM523F-EN-P - September 2006

Chapter

Configure the System Redundancy Module

Purpose of This Chapter

This chapter shows how to set or change the configuration of a


1757-SRM module. The SRM module controls the synchronization and
switchover of your redundancy system.

When to Use This Chapter

Use this chapter after you have installed your system to:
change how the SRM supports your system.
restart your system after redundant chassis regain power after a
power loss.

How to Use This Chapter

Use this chapter as follows:

If

Do this

On page

You just installed your system

Open the SRM Configuration Tool

55

Check the Revision of Your SRM Configuration Tool

57

Check the Version of Your SRM Configuration Tool

59

Set the Clock of the SRM

61

Test a Switchover

63

You want to change how the SRM


supports your system

Change the Auto-Synchronization Option

65

Change the Program Control Option

66

Both redundancy chassis lost power

Set the Clock of the SRM

61

Open the SRM


Configuration Tool

Purpose
To open the 1757-SRM System Redundancy Module configuration tool

When
Complete this procedure to:
set the SRM clock.
55

Publication 1756-UM523F-EN-P - September 2006

56

Configure the System Redundancy Module

test a switchover.
troubleshoot a system.
store or load a project using nonvolatile memory.
update firmware.

Before You Begin


RSLinx software includes and automatically installs the 1757-SRM
System Redundancy Module configuration tool.

IMPORTANT

Check your revision of the SRM configuration tool when you


open it for the first time.
The revision of tool that you get depends on your version of
RSLinx software.
Some revisions of the SRM configuration tool arent
compatible with some revisions of a ControlLogix
Redundancy system.
The next section shows you how to see if your revision of the
SRM configuration tool is right for your redundancy system.

Actions
1. Start RSLinx software.

Workstation

2. From the Communications menu, choose RSWho.

Linx Gateways, Ethernet

3. Double-click the network to open it.

My_Network

n, 1756 communication module

4. Double-click the communication module in the primary chassis


to show the backplane.

Backplane, 1756-Ax
xx, 1757-SRM

5. Double-click the backplane to see its modules.


6. Right-click the 1757-SRM module and select
Module Configuration.

Publication 1756-UM523F-EN-P - September 2006

Configure the System Redundancy Module

57

What to Do Next
IMPORTANT

Make sure that you check the revision of your SRM


configuration tool before you use it. Later revisions of the SRM
configuration tool arent compatible with earlier revisions of
ControlLogix redundancy systems. See Check the Revision of
Your SRM Configuration Tool on page 57.

Check the Revision of Your Purpose


SRM Configuration Tool
To make sure that you are using the right revision of the SRM
configuration tool for your ControlLogix redundancy system

IMPORTANT

Make sure that you check the revision of your SRM


configuration tool.
Revision 2.6 is compatible only with revision 13.x or later
ControlLogix redundancy systems.
Youll cause the 1757-SRM module to fault if you use
revision 2.6 of the tool with an revision 11.x or earlier
redundancy systems.

Publication 1756-UM523F-EN-P - September 2006

58

Configure the System Redundancy Module

When
Perform this procedure to:
use the SRM configuration tool for the first time.
connect to a different ControlLogix redundancy system for the
first time.
update the firmware of a ControlLogix redundancy system.

Before You Begin


RSLinx software automatically installs the SRM configuration tool. Use
the following table to see which revision of the tool that you get:

Publication 1756-UM523F-EN-P - September 2006

If you install

Then you get

RSLinx software revision 2.42

SRM configuration tool revision 2.5

RSLinx software revision 2.43

SRM configuration tool revision 2.6

Configure the System Redundancy Module

59

Actions
Action

Details

1. Choose which revision to use.

Do you connect your computer to ControlLogix redundancy systems revision 11.x or


earlier?
Yes Use revision 2.5 of the SRM Configuration Tool. DONT use revision 2.6.
No Use revision 2.6 of the SRM Configuration Tool.
Revision 2.6 is compatible only with revision 13.x or later ControlLogix redundancy
systems. Youll cause the 1757-SRM module to fault if you use revision 2.6 of the tool with
an revision 11.x or earlier redundancy systems.
Keep in mind that some features are available only in revision 2.6 or later of the
configuration tool.

2. See which revision you have.

A. Open the SRM configuration tool if you havent already done so.
B. Right-click the title bar of the configuration tool and choose About

3. Change your revision

If you need a different revision of the SRM configuration tool, see:


Knowledgebase document G92234770.
To access Rockwell Automations Knowledgebase, go to
http://support.rockwellautomation.com
Important: The SRM configuration tool lets you install only 1 revision on your computer at
the same time. To change the revision, remove the revision that you installed earlier.

Check the Version of the


Configuration Tool

Purpose
To verify the version of your 1757-SRM System Redundancy Module
Configuration tool

When
Perform this procedure before you configure your 1757-SRM module.

Publication 1756-UM523F-EN-P - September 2006

60

Configure the System Redundancy Module

Actions
Action

Details

1. In RSLinx software, browse to


1757-SRM.

A. Start RSLinx software.


B. Browse to your 1757-SRM.

2. Identify the configuration tool version

A. Right-click the SRM and choose Module Configuration.

B. Right-click the title bar of the configuration tool and choose About

Publication 1756-UM523F-EN-P - September 2006

Configure the System Redundancy Module

Set the Clock of the SRM

61

Purpose
To set clock of the 1757-SRM module

When
Perform this procedure:
after system installation.
after power loss to both chassis.

Before You Begin


The SRM clock records when significant events occur. Please note the
following characteristics of the SRM clock:
Only the primary SRMs clock requires setting. The secondary
SRMs clock synchronizes itself to the primary SRMs clock.
The SRM has no battery to keep its clock running. The clock
stops without SRM power.
With power, the primary SRM synchronizes its clock to the most
recent event in its event log.
The secondary SRM event log records when the secondary SRM
powered up. Look for WCT time change ( > 1 second) event.
An SRM with a firmware revision 3.37 or earlier doesnt log its
power-down time. If only one of the chassis powers down, use
the event log of the other chassis to see when it happened. Look
for The partner RM screamed event. See Interpret the SRM Event
Log on page 10.

Actions
Action

Details

1. Open the SRM configuration tool for the


primary chassis.

A. Start RSLinx software.


B. From the Communications menu, choose RSWho.
C. Open the network branches until you find the 1757-SRM module in the primary chassis.
D. Right-click the SRM and choose Module Configuration.

Publication 1756-UM523F-EN-P - September 2006

62

Configure the System Redundancy Module

Action

Details

2. Set the clock.

A. Click Configuration.

B. Do you want to set the clock of the SRM to the clock of your computer?
If

Then

Yes

Choose Apply Workstation Time and then Yes.

No

1. Change the date or time.


2. Choose Set and then Yes.

C. Choose OK.

Publication 1756-UM523F-EN-P - September 2006

Configure the System Redundancy Module

Test a Switchover

63

Purpose
To use RSLinx software to manually initiate a switchover

When
Perform this procedure after youve synchronized your system and
want to test a switchover.

Before You Begin


The CNB modules in the new primary chassis show the
synchronization progress after a switchover. Typically, the modules
show the following sequence:

43130

PwNS

PwDS

PwQg

PwQS

primary with no
secondary

primary with
disqualified
secondary

primary with
synchronizing
(qualifying)
secondary

primary with
synchronized (qualified)
secondary

Actions
Action

Details

1. Open the SRM configuration tool for the


primary chassis.

A. Start RSLinx software.


B. From the Communications menu, choose RSWho.
C. Open the network branches until you find the 1757-SRM module in the primary chassis.
D. Right-click the SRM and choose Module Configuration.

Publication 1756-UM523F-EN-P - September 2006

64

Configure the System Redundancy Module

Action

Details

2. Start a switchover.

A. Click Synchronization.

B. Choose Initiate Switchover and then choose Yes to continue.


3. Monitor the synchronization progress.

A. Click Synchronization Status.

If the controller contains a large project, the system may spend some time
synchronizing the secondary controller.
B. If the Secondary Readiness remains Disqualified:
Make sure the Auto-Synchronization option = Always.

See Troubleshoot a Failure to Synchronize on page 5.

Publication 1756-UM523F-EN-P - September 2006

Configure the System Redundancy Module

Change the
Auto-Synchronization
Option

65

Purpose
To change when the 1757-SRM module tries to synchronize the
controllers

When
Perform this procedure to:
help synchronize the system.
prevent the system from crossloading changes.

Actions
Action

Details

1. Decide when you want the system to


synchronize.

Do you plan to manually disqualify a chassis so you can make changes?


No Choose Always
Yes Choose Conditional
If you choose:

Then:

Conditional

The SRM keeps the synchronization command that you give it. If
you:
synchronize the secondary, the SRM always tries to keep the
controllers synchronized.
disqualify the secondary, the SRM keeps the controller
unsynchronized (disqualified). It doesnt crossload changes.

Never
2. Open the SRM configuration tool for the
primary chassis.

The controllers wont try to synchronize, but you can still manually
synchronize the controllers.

A. Start RSLinx software.


B. From the Communications menu, choose RSWho.
C. Open the branches of your network until you find the 1757-SRM module in the primary
chassis.
D. Right-click the SRM and choose Module Configuration.

Publication 1756-UM523F-EN-P - September 2006

66

Configure the System Redundancy Module

Action

Details

3. Set the auto-synchronization option.

A. Click Configuration.

B. Select the Auto-Synchronization option.


C. Choose Apply and then Yes to continue.
D. Choose OK.

Change the Program


Control Option

Purpose
To let the controller send a message to the 1757-SRM module or block
the controller from sending a message to the 1757-SRM module

When
Do this procedure when you:
initially configure the SRM.
decide to send the SRM a message from the controller.

Before You Begin


See page 94 for a list of messages that a controller can send to an SRM
module.

Publication 1756-UM523F-EN-P - September 2006

Configure the System Redundancy Module

67

Actions
Action

Details

1. Open the SRM configuration tool for the


primary chassis.

A. Start RSLinx software.


B. From the Communications menu, choose RSWho.
C. Open all the network branches to find the 1757-SRM module in the primary chassis.
D. Right-click the SRM and choose Module Configuration.

2. Set the program control option.

A. Click Configuration.
B. Do you want to let a controller send a message to the SRM?
Yes Check the Enable User Program Control check box.
No Uncheck the Enable User Program Control check box.

C. Choose Apply and then Yes to continue.


D. Choose OK.

Publication 1756-UM523F-EN-P - September 2006

68

Configure the System Redundancy Module

Notes:

Publication 1756-UM523F-EN-P - September 2006

Chapter

Configure and Program the Controller

When to Use This Chapter

After having installed a system, use this chapter to configure and


program the controller for redundancy.
IMPORTANT

How to Use This Chapter

Plan for Online Edits

Create and maintain only one RSLogix 5000 project for the pair
of redundant controllers. When you download the project to the
primary controller, the project automatically crossloads to the
secondary controller.

To configure and program a controller, complete the following tasks:


Topic

Page

Plan for Online Edits

69

Configure Communications

74

Estimate the Crossload Time of a Program

77

Minimize Scan Time

79

Maintain the Integrity of Your Data During a Switchover

85

Determine the Status of Your Redundancy System

90

Condition Logic to Run After a Switchover

91

Send a Message to the SRM

94

Download the Project to the Primary Controller

98

Schedule the ControlNet Networks

98

Set the Task Watchdog Times

102

Before editing online:


decide if you want to keep test edits after a switchover.
be aware that finalizing edits removes your original logic.
decide how you want to set aside unused memory.

69

Publication 1756-UM523F-EN-P - September 2006

70

Configure and Program the Controller

Decide if You Want to Keep Test Edits after a Switchover


When you edit logic while online with the controller, the edits may
fault the controller and cause a switchover.

Test Edits

If test edits fault the primary controller, they will likely also fault the
secondary controller. To prevent faulting, any test edits are
deactivated (untested) during a switchover. As an option, you can
keep the edits active after a switchover:

Publication 1756-UM523F-EN-P - September 2006

If you want to

Then

Prevent an incorrect online edit from


faulting both the primary and secondary
controller

Do not retain test edits (default setting).

Keep test edits active during a switchover


(at the risk of faulting both controllers)

Retain test edits.

Configure and Program the Controller

71

Be Aware That Finalizing Edits Removes Your Original Logic


Finalize All Edits in Program

The controller removes the original logic when you finalize all edits in
a program. If your changes cause a major fault and a switchover, the
new primary controller also faults. Thats because theres NO original
logic to go back to. For example, the new primary controller cant
untest the edits.
This happens even if you set the
controller to untest edits on a
switchover.

Decide How You Want to Set Aside Unused Memory


IMPORTANT

We recommend that you leave the Memory Usage slider in the


middle (default).

When the secondary controller receives crossload data, it first buffers


tag data in a quarantine section of memory. When it has all of the data
and knows it is valid, it moves the data into the main memory area.
That is why a redundant controller requires twice as much memory
for tags as a nonredundant controller.

Publication 1756-UM523F-EN-P - September 2006

72

Configure and Program the Controller

The controller sets up the quarantine area at the time of download:


The controller divides its memory into two sections:
tags, including a quarantine area
logic
The controller also divides its unused memory. It reserves a
specific amount for tags that you create while online. The rest
for logic.
You configure how to reserve unused memory between tags and
logic. You do this online in program mode.
If you plan to

Then

While online, create roughly the same amount of new


tags and new logic

Leave the default setting.

While online, create a relatively large amount of new


tags but a much smaller amount of new logic

Drag to slider toward Tags.

Notes

Avoid setting the slider all the way to Tags:


You will be unable to perform online edits.
OPC communications may error or fail.

While online, create a relatively large amount of new


logic but a much smaller amount of new tags

Configure a Controller for


Redundancy

Drag to slider toward Logic.

Avoid setting the slider all the way to Logic;


you will be unable to create tags while online.

1. Open or create the RSLogix 5000 project.

2. On the Online toolbar, click the controller button.


3. Does General display the controller type?
If no, go to step 4.
If yes, go to step 7.
4. Click the Change Type button.
5. Select your controller.
6. Choose OK.
7. Click Redundancy.

Publication 1756-UM523F-EN-P - September 2006

Configure and Program the Controller

73

8. Select the Redundancy Enabled check box.

9. Click the Advanced button.

10

11

10. We recommend that you not check this box. Leaving it


unchecked prevents an incorrect online edit from faulting both
the primary and secondary controller.
If you want any test edits to remain active during a switchover,
then check this box. However, by doing so, you run the risk of
faulting both controllers.
11. We recommend that you leave the Memory Usage slider in the
middle, the default position.
12. Choose
13. To close the Controller Properties dialog box,
choose

Publication 1756-UM523F-EN-P - September 2006

74

Configure and Program the Controller

Configure Communications

A redundant system requires some specific configuration choices for


successful communications. Use this section to perform the following
redundancy tasks:

Configure
Configure
Configure
Configure

IMPORTANT

I/O
produced tags
message (MSG) instructions
tags for an HMIConfigure I/O
For each module in your system, make sure that the requested
packet interval (RPI) is less than or equal to 375 milliseconds. If
you use a larger RPI, the controller could lose its connection
with the module during a switchover. This could cause outputs
to change state.

For any outputs that require a bumpless switchover:


put those outputs in the highest priority task.
configure only that task at the highest priority.

Configure Produced Tags


IMPORTANT

During a switchover, the connection for tags that are consumed


FROM a redundant controller may time out.
The data DOES NOT update.
The logic acts on the last data that it received.

After the switchover, the connection reestablishes and the data


begins to update again.

If you want a controller in another chassis to consume a tag from the


redundant controller, use a comm format of None. In the I/O
configuration of the consuming controller, select a comm format of
None for the remote CNB module (the CNB that is physically in the
redundant chassis).

Publication 1756-UM523F-EN-P - September 2006

Configure and Program the Controller

75

Produced tag
To the controller with the consumed tag, this
is the remote CNB module.
Redundant chassis

L C
5 N
5 B
M

S
R
M

Data

Consumed tag
Remote chassis
C L
N 5
B 5
M
x

In the I/O configuration of this controller, select a communication


format of None for the remote CNB module.

Publication 1756-UM523F-EN-P - September 2006

76

Configure and Program the Controller

Configure Message (MSG) Instructions


If the MSG instruction
is

Then

From a redundant
controller

In a redundant controller, any MSG instruction that is in progress during a switchover experiences an error.
(The ER bit of the instruction turns on.) After the switchover, normal communication resumes.

To a redundant controller

For any MSG instruction from a controller in another chassis to a redundant controller, cache the connection:

Properties of the Message to the Redundant Controller

Path to the
redundant controller

42977

Leave this box checked

Configure Tags for an HMI


To monitor tags directly in the secondary controller (not typical),
monitor from no more than 3 devices through a CNB module.
Monitor tags in a secondary controller only via:
RSLogix 5000 software
Any method that does not try to create OPC optimized packets.
Only a primary controller can create an OPC optimized packet.

Publication 1756-UM523F-EN-P - September 2006

Configure and Program the Controller

Estimate the Crossload


Time of a Program

77

Purpose
To estimate the crossload time of a program in a redundant controller

When
Perform this procedure to gauge the time a project spends
crossloading data.

Before you begin


Consideration

Details

The controller crossloads data at the end of


every program.

The primary controller stops at the end of every program to crossload fresh data to the
secondary controller. This keeps the secondary controller up to date and ready to take over.
It also increases the scan time when compared to a nonredundant system.

Scan time of program


Execute program in
primary controller

Start of program

The crossload time depends on how much


data changed.

Crossload results to
secondary controller

End of program

The length of time for the crossload depends on the how much data the primary controller
has to crossload.
The primary controller crossloads any tag to which an instruction wrote a value (even
the same value) since the last crossload.
Crossloading also requires a small amount of overhead time to tell the secondary
controller which program the primary controller is executing.

In a redundant system, a ControlLogix5561,


5562, or 5563 controller is up to 30% faster
than a ControlLogix5555 controller.

The scan time improvement of ControlLogix5561, 5562, and 5563 controllers is less in a
redundant system is than in a nonredundant system.
Even though the ControlLogix5561, 5562, and 5563 controllers execute logic faster,
they must still crossload data.
Given the same project and redundant system, a ControlLogix5561, 5562, or 5563
controller is up to 30% faster than a ControlLogix5555 controller.

Publication 1756-UM523F-EN-P - September 2006

78

Configure and Program the Controller

Actions
Action

Details

1. Get the size of your crossload data.

Use a Get System Value (GSV) instruction to read the REDUNDANCY object.

For this information

Get this attribute

Size of the last crossload LastDataTransfer


Size of the last crossload Size

Data
Type

Description

DINT

This attribute gives the size of data that was or would have
been crossloaded in the last scan.

if you had a secondary


chassis

The size in DINTs (4-byte words).


You must configure the controller for redundancy.
You dont need a secondary chassis.
Is there a synchronized secondary chassis?
Yes This gives number of DINTs that was crossloaded
in the last scan.
No This gives number of DINTs that would have been
crossloaded in the last scan.

Size of the biggest


crossload

MaxDataTransfer
Size

Size of the biggest


crossload if you had a
secondary chassis

DINT

This attribute gives the biggest size of the LastDataTransfer


Size attribute.
The size in DINTs (4-byte words).
You must configure the controller for redundancy.
You dont need a secondary chassis.
To reset this value, use an SSV instruction with a Source
value of 0.
Is there a synchronized secondary chassis?
Yes This gives biggest number of DINTs that was
crossloaded.
No This gives biggest number of DINTs that would
have been crossloaded.

See Logix5000 Controllers General Instructions Reference Manual, publication


1756-RM003, for more information on the GSV and SSV instructions.
2. Estimate the crossload time.

Which controller do you have?


If ControlLogix5555, then crossload time = (0.0015 ms * DINTs) + 1 ms overhead
If ControlLogix5561, then crossload time = (0.0013 ms * DINTs) + 1 ms overhead
If ControlLogix5562, then crossload time = (0.0013 ms * DINTs) + 1 ms overhead
If ControlLogix5563, then crossload time = (0.0013 ms * DINTs) + 1 ms overhead
where DINTs is the size of tag data to be crossloaded, measured in 4-byte words.

Publication 1756-UM523F-EN-P - September 2006

Configure and Program the Controller

Minimize Scan Time

79

To minimize a projects scan time, perform the following procedure:


IMPORTANT

Dont try to get the scan time of a ControlLogix redundancy


project down below about 20 milliseconds. At very low scan
times, crossload data becomes a bigger performance burden.
This burden limits the minimum scan time.

Action

Details

1. Use a few large programs instead of a lot


of small programs.

The controller stops at the end of every program to crossload data. So the more programs
that you have, the more the controller stops to crossload. And it often ends up
crossloading the same data many times.
To cut down the number of crossloads:
A. Use only one or a few programs.
B. Divide each program into whatever number of routines makes the most sense. A
routine doesnt cause a crossload.
C. Use the main routine of each program to call the other routines of the program.
D. If you want to use several tasks for different scan periods, put only one program in
each task. Remember that each program adds a crossload. So use only one or a few
tasks.
This is better

Than this

Publication 1756-UM523F-EN-P - September 2006

80

Configure and Program the Controller

Action

Details

2. Delete unused tags.

This reduces the size of the tag database. A smaller database takes less time to crossload.
To delete unused tags:
A. Open one of the tags folders.

B. Click Edit Tags.


C. From the Show list, select Unused.

D. From the Edit menu, choose Select All.


E. Press the [Delete] key.
3. Use arrays and user-defined data types
instead of individual tags.

When you create a tag, the controller always sets aside at least 4 bytes (32 bits) of
memory. The controller does this even if the tag needs only 1 bit.
When you create an array or a user-defined data type, the controller packs smaller data
types into 4-byte (32-bit) words. This means the controller has less data to crossload.
This array of 32 BOOLs takes only 4-bytes.

The controller crossloads only 4 bytes.


These 3 BOOL tags take 12 bytes total (3 tags x 4 bytes/tag = 12 bytes).

The controller crossloads all 12 bytes.


Arrays and user-defined data types help you the most with BOOL tags. But also use them
for your SINT, INT, DINT, REAL, COUNTER, and TIMER tags.

Publication 1756-UM523F-EN-P - September 2006

Configure and Program the Controller

81

Action

Details

4. If youve already created individual tags,


change them to aliases.

If youve already created individual tags, change them to aliases for elements of an array.
Your logic points to the aliases. The controller crossloads the base array.
A. Create an array.
B. Change each individual tag to an alias for an element in the array.

C. Keep pointing your logic to the


individual tag names.

5. Keep user-defined data types as compact


as possible.

Put like data types together when you lay out a user-defined data type:
Put all the BOOLs together.
Put all the SINTs together.
Put all the INTs together.

This is better
This data type takes 12 bytes. The BOOLs are together.

Than this
This data type takes 20 bytes. The BOOLs are spread out.

Publication 1756-UM523F-EN-P - September 2006

82

Configure and Program the Controller

Action

Details

6. Keep code as compact as possible.

Avoid checking the same conditions many times. Each instruction adds scan time to your
controller.

This is better
This rung checks Bool_B and Bool_C only once each scan.

Than this
This rung checks Bool_B and Bool_C twice each scan. One or two instructions dont add much
scan time. But if you do this often, the extra instructions add up to a much longer scan time.

Publication 1756-UM523F-EN-P - September 2006

Configure and Program the Controller

Action

Details

7. Execute code only when you need it.

The controller crossloads a tag anytime an instruction writes a value to the tag. This
happens even if the value stays the same:

83

Many instructions write a value whenever they run. For example, instructions such as
OTL, OTU, and many instructions with Destination operands write a value each time
the rung-condition-in is true.
Whenever an instruction writes a value, the controller marks the value for the next
crossload. This occurs even if the instruction wrote the same value that was previously
in the tag.
If you execute an instruction only when you need to, you reduce the amount of crossload
data. This reduces scan time. To limit the execution of an instruction:
Make a rung false when you dont need to execute its instructions.
Divide your logic into subroutines and call each subroutine only when needed.
Run noncritical code every few scans instead of every scan.
This is better
The ADD instruction runs only when the controller gets new data (New_Data = on). And
Dest_Tag crossloads only when the ADD instruction produces a new value.

Than this
The ADD instruction writes the sum of Tag_1 + Tag_2 to Dest_Tag each time the rung
executes. The controller crossloads Dest_Tag every scan, even if Tag_1 and Tag_2 stay the
same.

Publication 1756-UM523F-EN-P - September 2006

84

Configure and Program the Controller

Action

Details

8. Group your data by how often you need it. To update the secondary controller, the primary controller divides its memory into blocks of
256 bytes. Anytime an instruction writes a value, the primary controller crossloads the
entire block that contained the value. For example, if your logic writes only 1 BOOL value
to a block, the controller crossloads the entire block (256 bytes).
To minimize crossload time, group your data by how often you need it.
Suppose that you have some DINTs that you use only as constants to initialize your logic.
You have some BOOLs that you update every scan. And you have some REALs that you
update every second.
This is better
One user-defined data type for the
BOOLs. The controller crossloads these
4 bytes every scan.
One user-defined data type for the DINTs.
The controller crossloads these 12 bytes
only once.
One user-defined data type for the REALs.
The controller crossloads these 12 bytes
every second.

Than this
One user-defined data type for all the
data. The controller crossloads these
28 bytes every scan.

9. Use DINT tags instead of SINT or INT


tags

To keep your logic as efficient as possible, use the DINT data type instead of the SINT or
INT data types.
A ControlLogix controller usually works with 32-bit values (DINTs or REALs). If you use a
SINT or INT value:
The controller usually changes a SINT or INT value to a DINT or REAL value before it
uses the value.
If the destination is a SINT or INT tag, the controller usually changes the value back to
a SINT or INT value.
You dont have to program the controller to change values to or from SINTs or INTs. The
controller does it automatically. But it takes extra execution time and memory.

Publication 1756-UM523F-EN-P - September 2006

Configure and Program the Controller

Maintain the Integrity of


Your Data During a
Switchover

85

The redundancy system guarantees a bumpless switchover for any


logic in the highest priority task. In some cases, a switchover may
make lower priority tasks repeat part of their scan. This has to do with
how data crossloads from the primary controller to the secondary
controller.
As the primary controller executes its logic, it updates the secondary
controller at the end of every program.

Interruption by the program


in a higher priority task

End of the program in a


higher priority task

Start of the program in the lower priority


task (for example, the continuous task)

A.

End of the program in the lower


priority task

Primary controller
C.

B.

A. The following data is sent to the secondary controller:


Data from the program in the higher priority task
Data from the first part of the program in the lower priority
task
B. Execution returns to the program in the lower priority task.
C. Data from the second part of the program in the lower priority
task is sent to the secondary controller.
When a switchover interrupts the execution of the primary controller,
the secondary controller reexecutes an interrupted program from the
beginning of the program.

Publication 1756-UM523F-EN-P - September 2006

86

Configure and Program the Controller

Interruption by the program


in a higher priority task

End of the program in a


higher priority task

Start of the program in the lower priority


task (for example, the continuous task)

A.
This portion of the task is not executed
during this scan.

Primary controller

Switchover
occurs

B.

Instructions executing at the time of the


switchover do not complete in this scan.

Secondary controller

C.

A. The following data is sent to the secondary controller:


Data from the program in the higher priority task
Data from the first part of the program in the lower priority
task
B. Execution returns to the program in the lower priority task.
C. The secondary controller:
starts the scan at the beginning of the program that was in
progress in the primary controller during the switchover.
uses the data from the last update.
In this example, the secondary controller starts the scan with an
image of the data as it was during the primary controllers last
scan.
To prevent a scan from repeating after a switchover:
look for array shift instructions.
look for scan-dependent logic.
take preventative actions

Publication 1756-UM523F-EN-P - September 2006

Configure and Program the Controller

87

Look for Array Shift Instructions


The following instructions might corrupt data during a switchover:
BSL
BSR
FFU
Because these instructions shift data within an array, an interruption
by a higher priority task and a subsequent switchover leaves the data
with an incomplete shift.
If a higher priority task interrupts one of these instructions, the
partially shifted array values are sent to the secondary controller.
If a switchover occurs before the instruction completes its
execution, data remains only partially shifted.
The secondary controller starts its execution at the beginning of
the program. When it reaches the instruction, it shifts the data
again.

Look for Scan-Dependent Logic


A rung that must read the output of another rung during the same
scan might miss a scan during a switchover. For example:
A.

C.

D.
B.

43065

A. The CTU instruction counts each scan.


B. The EQU instruction uses the count of each scan
(scan_count.ACC).

Publication 1756-UM523F-EN-P - September 2006

88

Configure and Program the Controller

C. If a higher priority task interrupts the logic, the value of


scan_count.ACC is sent to the secondary controller at the end of
the program in the higher priority task.
D. If a switchover occurs before the EQU instruction, the secondary
controller starts its execution at the beginning of the program.
The EQU instruction misses the last value of scan_count.ACC.

Take Preventative Actions


If logic seems susceptible to an upset during a switchover, take one of
the following preventative actions:
1. Place susceptible logic in the highest priority task.
2. If the logic must remain in a lower priority task, take one of the
following actions:
Use UID and UIE Instruction Pairs.
Buffer critical data.

Place Susceptible Logic in the Highest Priority Task


This prevents the controller from sending any data to the
secondary controller until the program finishes.
If a switchover occurs during the program, the secondary
controller repeats the scan using the same starting data.

Publication 1756-UM523F-EN-P - September 2006

Configure and Program the Controller

89

Use UID and UIE Instruction Pairs


Bound critical rungs with UID and UIE instruction pairs. This prevents
the higher priority task form interrupting the scan-dependent logic, as
shown below:

Buffer Critical Data


The following example shows the use of a buffer together with a BSL
instruction.
1.

2.

3.

43065

1. The COP instruction moves the data into a buffer array.


2. The BSL instruction uses the data in the buffer. If a switchover
occurs, the source data (array tag) remains unaffected.
3. The CPS instruction updates array tag. Since higher priority
tasks cannot interrupt a CPS instruction, the instruction keeps
the integrity of the data.

Publication 1756-UM523F-EN-P - September 2006

90

Configure and Program the Controller

Determine the Status of


Your Redundancy System

Purpose
To write code that determines the status of your redundancy system

When
Perform this procedure to:
show system status on an HMI screen.
condition code to execute based on system status.
get diagnostic information to troubleshoot a system.

Actions
Use a Get System Value (GSV) instruction to read the attributes of the
REDUNDANCY object. See Appendix C for a list of attributes.

Example 1: Ladder Diagram


Get the ID of the primary chassis. The primary chassis always runs the code.
Store the ID in the Chassis_ID_Now tag. Chassis_ID_Now is a DINT.

Example 2: Structured Text


comment
comment
comment

//Get the ID of the primary chassis.


//Thats always the chassis that runs the code.
//Store the ID in Chassis_ID_Now. Chassis_ID_Now is a DINT.

code

Publication 1756-UM523F-EN-P - September 2006

GSV(REDUNDANCY,,PhysicalChassisID,Chassis_ID_Now);

Configure and Program the Controller

91

Check Your Work


Use the Redundancy tab of the Controller Properties window to check
the code attributes. It doesnt show all the attributes, but it shows the
more common attributes.
1. Download and run your project.
2. Open the Controller Properties window.
3. Click Redundancy.

4. Compare the Redundancy tab with your code.


In this example, the chassis ID A = 1.

For More Information


For more information on

See

Attributes of the REDUNDANCY object

Appendix C

GSV and SSV instructions

Logix5000 Controllers General Instructions


Reference Manual, publication
1756-RM003

Condition Logic to Run After Purpose


a Switchover
To condition a section of your logic to run after a switchover

Publication 1756-UM523F-EN-P - September 2006

92

Configure and Program the Controller

When
Follow these examples to create logic in preparation for a possible
switchover:

Example 1: Ladder Diagram


Get the ID of the primary chassis. Thats always the chassis that runs the code.
Store the ID in the Chassis_ID_Now tag.
Chassis_ID_Now DINT.

If this is the first scan then


Set the last value of the chassis ID = the ID of this chassis.
Chassis_ID_Last DINT.

If the chassis ID changes, a switchover happen


ed. If a switchover happens, then
Turn on the Switchover_Happened bit.
Set the last value of the chassis ID = the ID of this chassis.
Switchover_Happened BOOL.

Continued on next page

Publication 1756-UM523F-EN-P - September 2006

Configure and Program the Controller

93

If Switchover_Happened = on, then


Execute the instructions that you want to execute after a switchover.
Turn off the Switchover_Happened bit.
Put your instructions here.

Example 2: Structured Text


comment
comment
comment
comment

//Get the ID of the primary chassis.


//Thats always the chassis that runs the code.
//Store the ID in Chassis_ID_Now.
//Chassis_ID_Now -- DINT.

code

GSV(REDUNDANCY,,PhysicalChassisID,Chassis_ID_Now);
//If this is the first scan
//Then set the last value of the chassis ID = the ID of this chassis
//Chassis_ID_Last -- DINT.
If S:FS then
Chassis_ID_Last := Chassis_ID_Now;
End_If;
//If the chassis ID changes, a switchover happened.
//If a switchover happens then
//Turn on the Switchover_Happened bit.
//Set the last value of the chassis ID = the ID of this chassis
//Switchover_Happened -- BOOL

Publication 1756-UM523F-EN-P - September 2006

94

Configure and Program the Controller

If Chassis_ID_Now <> Chassis_ID_Last then


Switchover_Happened := 1;
Chassis_ID_Last := Chassis_ID_Now;
End_If;
//If Switchover_Happened = on
//Then
//Execute the instructions that you want to execute after a switchover.
//Turn off the Switchover_Happened bit.
If Switchover_Happened then
Put your statements here.
Switchover_Happened := 0;
End_If;

Send a Message to the


SRM

Purpose
To let your logic initiate actions in the SRM

When
Perform this procedure to:

Publication 1756-UM523F-EN-P - September 2006

initiate a switchover.
Disqualify the secondary controller.
Synchronize the secondary controller.
Set the clock of the SRM module.

Configure and Program the Controller

95

Before You Begin


Before sending a message to an SRM, make sure that:
the SRM is configured for program control.

the message is unconnected.

Leave the Connected check


box clear (unchecked).

Publication 1756-UM523F-EN-P - September 2006

96

Configure and Program the Controller

Actions
Use the following table to configure a message to an SRM module:
Configuring a Message to an SRM
If you want to

On this tab

For this item

Type or select

initiate a switchover

Configuration

Message Type

CIP Generic

Service Code

4e

Class name

bf

Instance name

Attribute name

leave blank

Source

DINT tag with a value of 1

Num. Of Elements

Destination

leave blank

Path

1, slot_number

Communication

where:
slot_number is the left-hand slot number of the
1757-SRM module.

Disqualify the secondary


controller

Configuration

Communication

Connected check box.

Leave the Connected check box clear (unchecked). You can


send only unconnected messages to a 1757-SRM module.

Message Type

CIP Generic

Service Code

4d

Class name

bf

Instance name

Attribute name

Leave blank

Source

DINT tag with a value of 1

Num. Of Elements

Destination

Leave blank

Path

1, slot_number
where:
slot_number is the left-hand slot number of the
1757-SRM module.

Connected check box.

Publication 1756-UM523F-EN-P - September 2006

Leave the Connected check box clear (unchecked). You can


send only unconnected messages to a 1757-SRM module.

Configure and Program the Controller

97

Configuring a Message to an SRM (Continued)


If you want to

On this tab

For this item

Type or select

Synchronize the secondary


controller

Configuration

Message Type

CIP Generic

Service Code

4c

Class name

bf

Instance name

Attribute name

Leave blank

Source

DINT tag with a value of 1

Num. Of Elements

Destination

Leave blank

Path

1, slot_number

Communication

where:
slot_number is the left-hand slot number of the
1757-SRM module.

Set the clock of the SRM


module

Configuration

Connected check box.

Leave the Connected check box clear (unchecked). You can


send only unconnected messages to a 1757-SRM module.

Message Type

CIP Generic

Service Code

10

Class name

8b

Instance name

Attribute name

Source

WallClockTime[0]
where:
WallClockTime is a DINT[2] array that stores the
CurrentValue of the WALLCLOCKTIME object.

Communication

Num. Of Elements

Destination

Leave blank

Path

1, slot_number
where:
slot_number is the left-hand slot number of the
1757-SRM module.

Connected check box

Leave the Connected check box clear (unchecked). You can


send only unconnected messages to a 1757-SRM module.

Publication 1756-UM523F-EN-P - September 2006

98

Configure and Program the Controller

Download the Project to the


Primary Controller

You only have to download the project to the primary controller.


When the secondary controller is synchronized, the system
automatically crossloads the project to the secondary controller.
IMPORTANT

If the secondary chassis becomes disqualified after you


download the project, make sure that you:
configured the project for the right type of controller.
enabled redundancy.
See Plan for Online Edits on page 69.

1. Open or create the RSLogix 5000 project for the controller.


2. From the File menu, choose Save.
3. From the Communications menu, choose Who Active.
4. Browse to the controller in the primary chassis.

A. Open a branch in one of these ways:


Double-click it.
Click its + sign.

Workstation
+

Linx Gateways, Ethernet

My_Network

Select it and press the key.

n, 1756 communication module

Backplane, 1756-Ax

B. Find the primary chassis. Its communication


module uses the address that you gave it.
C. Find the controller.

xx, 1756 controller

5. Select the controller and choose Download.


A confirmation box opens.
6. Choose Download.

Schedule the ControlNet


Networks
IMPORTANT

Publication 1756-UM523F-EN-P - September 2006

Before you schedule a ControlNet network, turn on the power


to both redundant chassis. If you schedule a ControlNet
network while the secondary chassis is off, the keeper
signature of a CNB module may not match its partner, and the
secondary chassis will fail to synchronize.

Configure and Program the Controller

99

To schedule a ControlNet network:

schedule a new network.


update the schedule of an existing network.
check the keepers.
save the project for each controller.

Schedule a New Network


1. Turn on the power to each chassis.
2. Start RSNetworx for ControlNet software.
3. From the File menu, choose New.
4. From the Network menu, choose Online.
5. Select your ControlNet network and choose OK.
6. Select the Edits Enabled check box.
7. From the Network menu, choose Properties.
8. From Network Parameters, type or select the following
parameters:
In this box

Specify

Network Update Time

Repetitive time interval in which data is sent over the ControlNet network

Max Scheduled Address

Greatest node number to use scheduled communications on the network

Max Unscheduled Address

Greatest node number that you will use on the network

Media Redundancy

Channels in use

Network Name

Name for the network

9. Choose OK.
10. From the Network menu, choose Single Pass Browse.
11. From the File menu, choose Save.
12. Type a name for the file that stores the network configuration,
then choose Save.
13. Select the Optimize and rewrite Schedule for all Connections
button (default) and choose OK.

Publication 1756-UM523F-EN-P - September 2006

100

Configure and Program the Controller

Update the Schedule of an Existing Network


1. Turn on the power to each chassis.
2. Start RSNetworx for ControlNet software.
3. From the File menu, choose Open.
4. Select the file for the network and choose Open.
5. From the Network menu, choose Online.
6. Select the Edits Enabled check box.
7. From the Network menu, choose Properties.
8. From Network Parameters, update the following parameters:
In this box

Specify

Max Scheduled Address

Greatest node number to use scheduled communications


on the network

Max Unscheduled Address

Greatest node number to use on the network

9. Choose OK.
10. From the Network menu, choose Single Pass Browse.
11. From the File menu, choose Save.
12. Select the Optimize and rewrite Schedule for all Connections
button and choose OK.

Check the Keepers


On a ControlNet network, each keeper must:
take over the keeper duties if the current keeper drops off the
network.
use the same configuration regardless of which keeper first
comes online after a major network disturbance, such as a cable
short or system power cycle.

Publication 1756-UM523F-EN-P - September 2006

Configure and Program the Controller

101

After you schedule your ControlNet networks:


1.

2.

Keeper Capable Node

Active Keeper Valid Keeper

offline file

N/A

N/A

01

No

Yes

02

Yes

Yes

1. Make sure the network shows all keeper capable nodes.


2. Make sure that each node is a valid keeper.
For more information, see Update a Keeper Signature on page 6.

Save the Project for Each Controller


After your schedule your ControlNet networks, save the online project
of each controller. This lets you download a project in the future
without having to reschedule the networks.
For each controller (redundant and nonredundant) on a ControlNet
network:
1. Go online to the controller.
2. Save the project.

Publication 1756-UM523F-EN-P - September 2006

102

Configure and Program the Controller

Set the Task Watchdog


Times

Give a redundant controller longer watchdog times than a


nonredundant controller.
After a switchover, the secondary controller starts the scan at the
beginning of the program that was running in the primary
controller at the time of the switchover.
The watchdog timer for the task that has the program, however,
is not reset.
A major fault happens (type 6, code 1) if the watchdog timer has
too little time to completely rescan the program.

Action

Details

1. Set the minimum watchdog time for a


task.

Use the following formula to set the minimum watchdog time for a task:
Minimum watchdog time = (2 * maximum_scan_time) + 150 ms
where:
Maximum_scan_time is the maximum scan time for the entire task when the
secondary controller is synchronized.

2. Set the estimated watchdog time for a


task.
+

Controller Primary

Tasks
+

MainTask

A. Right-click the task and choose Properties.


B. Click Configuration.

C. Type a watchdog time that is


more than the watchdog time
from step 1.

D. Choose OK.

Publication 1756-UM523F-EN-P - September 2006

Configure and Program the Controller

Action

Details

3. Determine the real scan time of a task.

Do the following steps while the controller is running.

Controller Primary

Tasks
+

MainTask

103

A. Right-click the task and choose Properties.


B. Click Monitor.

C. Look at the scan times.


Longest time its taken in microseconds
to scan this task
Time it took in microseconds to scan this
task the last time it ran
D. If you want to clear the Max counters and
start over, click Reset.

E. Choose OK.
4. See if the watchdog time is big enough.

A. Calculate the smallest watchdog time for your task using the real scan time of the task:
Smallest watchdog time = (2 * maximum_scan_time) + 100 ms
B. Is your watchdog time more than the smallest watchdog time from step 4A above?
Yes Stop. Your watchdog time is OK.
No Repeat step 2 and enter a new watchdog time.

Publication 1756-UM523F-EN-P - September 2006

104

Configure and Program the Controller

Notes:

Publication 1756-UM523F-EN-P - September 2006

Chapter

Maintain and Troubleshoot the System

When to Use This Chapter


Simultaneous power of redundant
chassis pair may bump another
redundant chassis pair off the
EtherNet/IP network

This chapter provides a variety of procedures to commission, upgrade,


maintain, and troubleshoot your redundancy system.

Under the following combination of conditions (all must apply), duplicate IP addresses on your
EtherNet/IP network will cause you to lose communication with a redundant chassis pair over that
EtherNet/IP network:
You have multiple pairs of redundant chassis on the same EtherNet/IP network. For example,
pair 1 and pair 2.
The IP addresses of one pair of redundant chassis is the same as another pair of redundant
chassis. For example, pair 1 = 10.10.10.10 and pair 2 = 10.10.10.10.
A redundant chassis pair with the conflict (both chassis that make up the pair) simultaneously
powers up. For example, both chassis of pair 2 power up at the same time.
When this occurs the newly powered up chassis use the IP address. The redundant chassis pair
that was previously communicating at that IP address stops communicating on the network. For
example, when pair 2 powers up at 10.10.10.10, pair 1 stops communicating on the network.

How to Use This Chapter


If you want to

Then see this section

Page

Find the Cause of a Switchover or


Disqualification

106

Find why the secondary controller fails to synchronize

Troubleshoot a Failure to Synchronize

108

See if the keeper signature of a CNB module is stopping the


secondary chassis from synchronizing

Update a Keeper Signature

110

See if a computer is stopping the secondary chassis from


synchronizing

See if an Edit Session Is in Progress

111

Look through a log of events to see why system switched


over or failed to synchronize

Interpret the SRM Event Log

113

Find the cause of an unplanned switchover


Find why secondary chassis became disqualified

Export specific events from the SRM event log and view them Export the SRM Event Log
in software such as Microsoft Excel

119

Initiate the synchronization process

Manually Synchronize the Chassis

122

Optimize Communication

123

Check the Allocation of Unused Memory

127

Determine why it takes a very long time to synchronize


the secondary controller
Determine why communication with your HMIs is very
slow
Determine why OPC communication has errored or failed
Determine why you are unable to create tags or edit logic
while online
105

Publication 1756-UM523F-EN-P - September 2006

106

Maintain and Troubleshoot the System

If you want to
Determine the CPU usage of a CNB module

Then see this section

Page

Adjust CNB Usage

127

Reduce the CPU usage of a CNB module


Store a project to the nonvolatile memory of a controller
in a redundant system

Store or Load a Project Using Nonvolatile 137


Memory

Load a project into the controller from the nonvolatile


memory of the controller
Replace 1756-CNB/D or 1756-CNBR/D module(s) with series
E modules

Change CNB modules from Series D to


Series E

131

Change the revision of a module while minimizing the time


your system is off

Update a Module

140

Store an updated project and firmware to the nonvolatile


memory of the controller while the process is running

Store a Project to Nonvolatile Memory


While a Process Is Running

139

Update the firmware of a redundant chassis without shutting


down the process

Update a System That Is Already at


Revision 13

142

Find the Cause of a


Switchover or
Disqualification

Purpose
To find and fix the cause of an unplanned switchover or loss of
synchronization

When
Perform this procedure when:
an unplanned switchover happens.
a chassis that was synchronized becomes disqualified.

Actions
Start here.

1. Do the 1756-CNB/D/E or 1756-CNBR/D/E modules in the


primary chassis show PwQS?
Yes Go to Interpret the SRM Event Log on page 113.
No Go to step 2.
2. Does any module in the primary chassis show PwNS?
Yes Go to step 3.
No Go to step 6.

Publication 1756-UM523F-EN-P - September 2006

Maintain and Troubleshoot the System

107

3. Use the following table to troubleshoot the secondary chassis:


If the secondary chassis

And each communication


module in the primary
chassis

And a secondary
communication module
has a

Then

Has power

Has a matching partner in the


secondary chassis

Red OK light

Replace the module.

Green OK light

Check the 1757-SRC cable for a


proper connection.

Doesnt have a matching partner


in the secondary chassis

Install a matching module.

Doesnt have power

Restore the power.

4. Wait several minutes for the system to try to synchronize.


5. What do the CNB modules in the primary chassis show?
PwQS Stop. Your system is synchronized.
PwDS Go to step 6.
6. Use the following table to troubleshoot the secondary chassis:
If the SRM module
has a

And a secondary CNB


module

And a secondary controller


has a

Then

Green OK LED

Doesnt show NET ERR

Flashing Red OK light

Clear the major fault of the controller.


Its possible that you have to clear the fault on
both the primary and secondary controllers.

Solid Red OK light

A. Cycle the power to the chassis.


B. If the OK light remains solid red, replace the
controller and flash the controller with the
appropriate revision of firmware.

Solid Green OK light


Shows NET ERR
Red OK LED

Go to step 7.
Check all ControlNet taps, connectors, and
terminators for proper connections.
A. Cycle the power to the chassis.
B. If the OK light of the SRM module remains
solid red, contact your local distributor or
Rockwell Automation representative.

7. Wait several minutes for the system to try to synchronize.


8. Do the CNB modules in the primary chassis show PwQS?
Yes Stop. Your system is synchronized.
No Go to Troubleshoot a Failure to Synchronize on
page 108.

Publication 1756-UM523F-EN-P - September 2006

108

Maintain and Troubleshoot the System

Troubleshoot a Failure to
Synchronize
IMPORTANT

If the steps in this section do not correct the situation, check the
usage of the CNB modules. See Adjust CNB Usage on page 127.
If the chassis still doesn't synchronize, try to manually synchronize it.
See Manually Synchronize the Chassis on page 122.

1. Look at the 1756-CNB/D/E or 1756-CNBR/D/E modules in the


primary chassis:
Primary CNB Front panel

Look here.

If

It means

So do this

PwQS

Primary with Synchronized


(Qualified) Secondary

Stop. The redundant chassis are


synchronized.

PwDS

Primary with Disqualified Secondary Go to step 2. A problem exists. The


redundant chassis are not
Primary with No Secondary
synchronized.

PwNS

2. Look at the CNB modules in the secondary chassis.

Publication 1756-UM523F-EN-P - September 2006

Maintain and Troubleshoot the System

Front panel

If the display Then


shows

So check the following

Secondary CNB

!Cpt

1. All CNB modules in each redundant chassis are series D modules.

The CNB modules in the


primary and secondary
chassis dont match in
some way.

109

2. Each CNB module has a partner in the same slot in the other
redundant chassis.
3. Each pair of CNB modules (one in each chassis) is set to the same
node address.
4. Each module has compatible firmware.
5. All CNB modules in each redundant chassis are valid keepers. See
Update a Keeper Signature on page 110.

CMPT

Some module other than


this CNB module doesnt
match between the primary
and secondary chassis.

1. Each module has a partner in the same slot in the other redundant
chassis.
2. Each pair of controllers (one in each chassis) has the same memory
board (for example, 1756-L55M14).
3. Each module has compatible firmware.
4. The RSLogix 5000 project is configured for the right type of controller
and redundancy is enabled. See Configure a Controller for
Redundancy on page 72.
5. The Module Configuration window for the 1757-SRM module does
not list any reasons for the failure to synchronize. See See if an Edit
Session Is in Progresson page 111.

DUPL NODE

More than one device on


your ControlNet network is
using the same node
number.

1. No other device on the ControlNet network is set to the address of


the CNB modules plus one.
For example, if the CNB modules are set to 3, no other device should
be set to 4.
2. The 1757-SRCx cable is connected to both SRM modules.

NET ERR

The ControlNet media is


not completely connected.

All ControlNet taps, connectors, and terminators are connected.

Publication 1756-UM523F-EN-P - September 2006

110

Maintain and Troubleshoot the System

Update a Keeper Signature Purpose


To see if the keeper signature of a CNB module is stopping the
secondary chassis from synchronizing

Secondary

When
Perform this procedure when a secondary chassis wont synchronize
and its CNB modules show !CPT.

!Cpt

Before You Begin


42797

The secondary chassis wont synchronize if the keeper signature of a


CNB module doesnt match its partner. This happens if you schedule
the ControlNet network while the secondary chassis is off or if the
CNB module was previously configured in a different network.

Actions
1. Start RSNetWorx for ControlNet software.
2. Has this network been scheduled before?
If

Then

No

A. From the File menu, select New.


B. From the Network menu, select Online.
C. Select your ControlNet network and choose OK.

Yes

A. From the File menu, select Open.


B. Select the file for the network and choose Open.
C. From the Network menu, select Online.

3. From the Network menu, choose Keeper Status.

Publication 1756-UM523F-EN-P - September 2006

Maintain and Troubleshoot the System

4.

111

5.

Keeper Capable Node

Active Keeper Valid Keeper

offline file

N/A

N/A

01

No

No

02

Yes

Yes

4. Make sure the list contains all your keeper capable nodes. This
includes the CNB modules in the secondary chassis.
5. Make sure that each node has a valid keeper signature.
If the Valid Keeper column shows

Then

Yes

The node has a valid keeper signature.

No

Select the node and choose Update Keeper.

6. Choose Close.

See if an Edit Session Is in


Progress

Purpose
To see if a computer is stopping the secondary chassis from
synchronizing

Secondary

When
CMPT

Perform this procedure when a secondary chassis wont synchronize


and the CNB modules in the secondary chassis show CMPT.

42797

Publication 1756-UM523F-EN-P - September 2006

112

Maintain and Troubleshoot the System

Actions
Actions

Details

1. Open the SRM configuration tool for the


primary chassis.

A. Start RSLinx software.


B. From the Communications menu, choose RSWho.
C. Open the branches of your network until you find the 1757-SRM module in the primary
chassis.
D. Right-click the SRM and choose Module Configuration.

2. Check the recent synchronization


attempts.
A. Click Synchronization.
B. Do you see Edit Session In Progress under Recent
Synchronization Attempts?
Yes Go to step 3.
No An edit session didnt stop
synchronization. Return to Troubleshoot a
Failure to Synchronize on page 108.

3. Look for the reason.

Publication 1756-UM523F-EN-P - September 2006

If

Then

Another computer is editing the project in


the controller.

Stop the edit session.

The project contains test edits.

Untest the edits.

The Nonvolatile Memory Load/Store dialog


box of the controller is open.

Close the Nonvolatile Memory Load/Store


dialog box.

You tried to synchronize the chassis while


downloading a project at the same time.

Wait for the download to finish.

Maintain and Troubleshoot the System

Actions

Details

4. Manually synchronize the chassis.

Choose Synchronize Secondary and then Yes continue with synchronization.

113

Interpret the SRM Event Log Purpose


To look through a log of events to see why the system switched over
or failed to synchronize

When
Perform this procedure when:
a switchover happens but your system synchronizes again.
youve already tried to use the hardware lights to find why your
system wont synchronize.

Before You Begin


The SRM clock is accurate only if you:
initially set it after you installed your system.
reset it after any power loss to both chassis.

Publication 1756-UM523F-EN-P - September 2006

114

Maintain and Troubleshoot the System

Actions
Actions

Details

1. Open the SRM configuration tool for the


primary chassis.

A. Start RSLinx software.


B. From the Communications menu, choose RSWho.
C. Open the network branches until you find the 1757-SRM module in the primary chassis.
D. Right-click the SRM and choose Module Configuration.

2. Go to the event log.

Publication 1756-UM523F-EN-P - September 2006

Click Event Log.

Maintain and Troubleshoot the System

Actions

Details

3. Look through the events of the secondary


chassis for a substantial change in log
times.

A. Start with the secondary chassis.

115

The lower list is the secondary chassis.


The cause of the switchover probably happened to secondary chassis while it was
the primary chassis.
B. Look for a change of months, days, or hours between the log times of events.
Sometimes the difference is only minutes.
The SRM logs only significant events. It doesnt log events while your system is
running normally.
C. Use the slot and module columns to find the module that caused the event.
D. Go to Interpret SRM events on page 117 to interpret the description.
Example

Heres a substantial change


in the log time.
The slot, module, and
description columns show
that the 1756-EWEB module
in slot 2 went lonely. That
usually means it lost its
network connection.

Publication 1756-UM523F-EN-P - September 2006

116

Maintain and Troubleshoot the System

Actions

Details

4. Double-click and event for more


information.

A. Double-click an event to see if it gives more information.


The Extended Information Definition dialog opens.
B. Click OK when youre done to close the Extended Information Definition dialog.
Example

Someone removed the module for slot 2. Or the


module failed.

5. If the secondary log doesnt show the


cause, look at the primary log.

Sometimes you have to use both logs to find out what happened.
Example

A. The secondary log shows that something


happened around 15:40. But its not clear
just what happened.
B. The primary log shows that around that
time the partner SRM screamed. That
means it lost power.

Publication 1756-UM523F-EN-P - September 2006

Maintain and Troubleshoot the System

117

Interpret SRM events


Use this table to interpret events recorded in the SRMs event log.
Event description

Meaning

Autoqualification Trigger

Something happened that caused the system to try and synchronize again. Double-click the
event to see what happened.

Blank Memories Rule

A check to choose a primary chassis if both chassis power up at the same time. Suppose
that the controllers in one chassis don't have projects while the controllers in the other
chassis do have projects. In that case, the other chassis becomes primary.

Chassis Modules Rule

A check to choose a primary chassis if both chassis power up at the same time. Suppose
that one chassis has more modules than the other chassis. In that case, the chassis with
the most modules gets the first chance to become primary. It becomes primary as long as
the other chassis isn't more able to control the system.

Chassis Redundancy State changed to

The chassis changed to a different redundancy state.


PwQS Primary with qualified (synchronized) secondary partner
QSwP Qualified (synchronized) secondary with primary partner
DSwP Disqualified secondary with primary partner
DSwNP Disqualified secondary with no partner
PwDS Primary with disqualified secondary partner
PwNS Primary with no secondary partner

Crossloading Error

A module isn't able to get some information to its partner.

Disqualified Secondaries Rule

A check to choose a primary chassis if both chassis power up at the same time. Suppose
that the modules in one of the chassis powered down in a disqualified secondary state. In
that case, the other chassis becomes primary.

Failed Modules Rule

A check to choose a primary chassis if both chassis power up at the same time. Suppose
that a module in one of the chassis is faulted but its partner module in the other chassis
isnt faulted. In that case, the other chassis becomes primary.

Firmware Error

The SRM has a problem.

Module Insertion

The SRM now sees the module on the backplane. This means the module has either just
powered up, just been put into the chassis, or just finished resetting. Double click the event
to see the slot number of the module.

Module Removal

The SRM no longer sees a module on the backplane. This means that the module either
experienced a nonrecoverable fault, was removed from the chassis, or was reset.
Double-click the event to see the slot number of the module.

Modules Chassis State Rule

A check to choose a primary chassis if both chassis power up at the same time. Suppose
that the modules in one chassis are already in a primary state. In that case, that chassis
becomes primary.

NRC Modules Rule

A check to choose a primary chassis if both chassis power up at the same time. NRC stands
for nonredundancy compliant. Suppose that a module in one of the chassis doesn't support
redundancy and all the modules in the other chassis do support redundancy. In that case,
the other chassis becomes primary.

Publication 1756-UM523F-EN-P - September 2006

118

Maintain and Troubleshoot the System

Event description

Meaning

Partner not on same CNet link

A primary CNB isn't able to communicate with the secondary CNB over the ControlNet
network. This means there is either:
a network problem such as noise, a poor connection, or a problem with the termination.
a secondary CNB that isn't connected to the network.

Powerdown Time Rule

A check to choose a primary chassis if both chassis power up at the same time. If the two
chassis powered down more than one second apart, the last chassis to power down gets
the first chance at being primary.

Program Fault

A controller has a major fault.

SRM OS Error

The SRM has a problem.

SRM Serial Number Rule

A check to choose a primary chassis if both chassis power up at the same time. This is the
final tie-breaker. The SRM with the lower serial number gets the first chance to become
primary. It becomes primary as long as the other chassis isn't more able to control the
system.

Standby Secondaries Rule

A check to choose a primary chassis if both chassis power up at the same time. Since
standby isn't available yet, this check always ends in a tie.

SYS_FAIL_L Active

A module has a nonrecoverable fault or lost its connection to the network. When that
happens, the SYS_FAIL signal becomes true.
The backplane of the chassis has a SYS_FAIL signal. Each module in the chassis uses this
signal to indicate a problem.
The signal is normally false (inactive), which means that all modules in the chassis are
OK.
A module turns the SYS_FAIL signal true (active) when the module has a
nonrecoverable fault or it losses its connection to the network.
Look for later events to find out what happened.
If you see a Module Removal event shortly afterward, then a module has a
nonrecoverable fault. Double-click the Module Removal event to see the slot number of
the module. The SYS_FAIL signal may stay true until you cycle power or remove the
faulted module.
If you see a SYS_FAIL_L Inactive event within a few hundred milliseconds, then a cable
is probably disconnected or broken. A communication module pulses the SYS_FAIL
signal when the module loses its connection to the network. Look for a Transition to
Lonely event to see which module lost its connection.

The partner RM has been connected

The partner SRM powered up or become connected by the fiber-optic cable.

The partner RM screamed

The partner SRM lost power, has an unrecoverable fault, or was removed.
An SRM has circuits that hold power long enough for it to send a message to its partner
over the fiber-optic interconnect cable. The SRM sends the message even after you remove
it from the chassis. This message is called a scream. The scream lets the partner SRM tell
the difference between a broken fiber-optic interconnect cable and the power loss or
removal of the primary SRM.
If the fiber optic cable breaks, then there isn't a switchover.
If the SRM loses power or is removed, then there is a switchover.

Publication 1756-UM523F-EN-P - September 2006

Maintain and Troubleshoot the System

119

Event description

Meaning

Transition to Lonely

A communication module doesn't see any other devices on its network. This usually means
that the network cable of the module is disconnected or broken. The event log shows
Transition to Not Lonely when you reconnect the cable.

Unknown Event

The SRM configuration tool doesn't have a description for the event.

WCT time change (> 1 second)

The clock of the SRM changed. This happens when you:


use the SRM configuration tool to set the clock.
connect the SRM to another SRM that is already primary. The SRM synchronizes its
clock to that of the primary SRM.

Export the SRM Event Log

Purpose
To export specific events from the SRM event log to a CSV or TXT file

When
Perform this procedure to:
look at the event log in spreadsheet software such as Microsoft
Excel.
send the event log to someone else.

Before You Begin


The SRM configuration tool lets you export events from both the
primary and the secondary chassis at the same time.

Publication 1756-UM523F-EN-P - September 2006

120

Maintain and Troubleshoot the System

IMPORTANT

When you send event logs to Rockwell Automation:


send events from both the primary and secondary chassis.
include all events from the latest event to the last event
when you knew that the chassis were in a good state.

Actions
Action

Details

1. Open the SRM configuration tool for the


primary chassis.

A. Start RSLinx software.


B. From the Communications menu, choose RSWho.
C. Open the branches of your network until you find the 1757-SRM module in the primary
chassis.
D. Right-click the SRM and choose Module Configuration.

2. Go to the event log.

Publication 1756-UM523F-EN-P - September 2006

Click Event Log.

Maintain and Troubleshoot the System

Action

121

Details

3. Select the events that you want to export. A. Click the first event that you want to export from the primary chassis.
B. Press and hold the [Shift] key and then click the last event that you want to export from
the primary chassis.
C. Repeat steps 3A and 3B for the secondary chassis.

4. Export your selection.

A. Choose Export Selection.

B. Click the Browse button and choose a location and


name for the export file.
C. Choose CSV (Comma-Separated Value).
D. Select the Include Extended Information check box.
E. Choose Export.

Publication 1756-UM523F-EN-P - September 2006

122

Maintain and Troubleshoot the System

Manually Synchronize the


Chassis

After a switchover, you may have to manually synchronize the chassis


because either:
the Auto-Synchronization option is not set to Always or
the chassis failed to synchronize.
To manually synchronize the chassis:
1. Display RSLinx software.
2. From the Communications menu, choose RSWho.
3. Expand the network until you see the 1757-SRM module in the
primary chassis.

Workstation
+

Linx Gateways, Ethernet

AB_KTC-x, ControlNet

n, 1756-CNB/D/E

Backplane, 1756-Ax
xx, 1756 module, 1757-SRM

4. Right-click the 1757-SRM module and select


Module Configuration.
5. Click Synchronization.

6. Choose Synchronize Secondary and then choose Yes to confirm.


7. Choose OK.

Publication 1756-UM523F-EN-P - September 2006

Maintain and Troubleshoot the System

123

8. In the primary chassis, what do the CNB modules display?


Front panel

If you see

Which means

PwQg

Primary with Synchronizing


(Qualifying) Secondary

Synchronization is in progress.

Primary with Synchronized


(Qualified) Secondary

The secondary chassis is synchronized.

Primary with Disqualified


Secondary

The secondary chassis is NOT synchronized.

Look here.
PwQS
PwDS

Then
Continue waiting. It may take several minutes
to synchronize the secondary chassis.
Skip the remaining steps in this section.
Go to step 9.

43130

9. Cycle power to the secondary chassis.


10. If the CNB module in the primary chassis fails to display PwQS,
see Troubleshoot a Failure to Synchronize on page 108.

Optimize Communication

If it takes too long to synchronize the secondary chassis or update


your HMI, there may not be enough controller time for unscheduled
communication. In general, unscheduled communication is any type
of communication that you do not configure through the I/O
configuration folder of the controller:
This type of communication

Is

Update I/O data (not including block-transfers)

Scheduled communication

Produce or consume tags


Communicate with programming devices (for
example, RSLogix 5000 software)

Unscheduled communication

Communicate with HMI devices


Execute Message (MSG) instructions, including
block-transfers
Respond to messages from other controllers
Synchronize the secondary controller of a redundant
system
Reestablish and monitor I/O connections, such as Removal
and Insertion Under Power conditions; this does not
include normal I/O updates that occur during the execution
of logic.
Bridge communications from the serial port of the
controller to other ControlLogix devices via the
ControlLogix backplane

Publication 1756-UM523F-EN-P - September 2006

124

Maintain and Troubleshoot the System

To speed up unscheduled communication:


If an RSLogix 5000 project contains

Then

See Page

Only a continuous task and no other tasks


(This is the default task configuration.)

Choose a Greater System Overhead Time


Slice

124

More than one task (for example, at least 1


periodic task)

Make All Your Tasks Periodic

126

Choose a Greater System Overhead Time Slice


The system overhead time slice specifies the percentage of time
(excluding the time for periodic tasks) that the controller devotes to
unscheduled communication. The controller performs unscheduled
communication for up to 1 ms at a time and then resumes the
continuous task.
The following table shows the ratio between the continuous task and
unscheduled communication at various system overhead time slices:
At this time slice The continuous task
runs for

And unscheduled
communication occurs
for up to

10%

9 ms

1 ms

20%

4 ms

1 ms

33%

2 ms

1 ms

50%

1 ms

1 ms

At a system overhead time slice of 20 % (default), unscheduled


communication occurs every 4 ms of continuous task time for 1 ms.
Legend:
Task executes.
Task is interrupted (suspended).

1 ms

1 ms

1 ms

1 ms

1 ms

Unscheduled
communication
4 ms
Continuous task

Publication 1756-UM523F-EN-P - September 2006

4 ms

4 ms

4 ms

4 ms

Maintain and Troubleshoot the System

125

If you increase the system overhead time slice to 33 %, unscheduled


communication occurs every 2 ms of continuous task time for 1 ms.
1 ms

1 ms

1 ms

1 ms

1 ms

1 ms

1 ms

1 ms

Unscheduled
communication
2 ms

2 ms

2 ms

2 ms

2 ms

2 ms

2 ms

2 ms

2 ms

Continuous task

Enter a System Overhead Time Slice


To change the system overhead time slice:

1.

1. On the Online toolbar, click controller properties button.


2. Click Advanced.
2.

3.

3. Type or select a value for the system overhead time slice.


4. Choose

Publication 1756-UM523F-EN-P - September 2006

126

Maintain and Troubleshoot the System

Make All Your Tasks Periodic


Action

Details

1. If you have more than one task, make


them all periodic tasks.

If the controller contains only a periodic task or tasks, the system overhead time slice value
has no effect. Unscheduled communication happens whenever a periodic task is not
running.
Example
Suppose your task takes 50 ms to execute and you configure its period to 80 ms. In that
case, the controller has 30 ms out of every 80 ms for unscheduled communication.
50 ms

50 ms

50 ms

periodic task
30 ms

30 ms

30 ms

unscheduled communication

2. Follow these guidelines to set the


periods of the tasks.

If you have multiple tasks, make sure that:


1. The execution time of a highest priority task is significantly less than its period.
2. The total execution time of all your tasks is significantly less than the period of the
lowest priority tasks.
This generally leaves enough time for unscheduled communication.
For example, in this configuration of tasks:

Task

Priority

Execution time

Rate

higher

20 ms

80 ms

lower

30 ms

100 ms

total execution time:

50 ms

1. The execution time of the highest priority task (Task 1) is significantly less than its
period (20 ms is less than 80 ms).
2. The total execution time of all tasks is significantly less than the period of the lowest
priority task (50 ms is less than 100 ms).
3. Tune the periods of the tasks.

Adjust the periods of the tasks as needed to get the best trade-off between executing your
logic and servicing unscheduled communication.

4. Look for overlaps.

Look at the Monitor tab of the properties of the task to see if overlaps are happening. An
overlap happens if the period of a task is less than its scan time. If you see overlaps,
increase the period of the task.

Publication 1756-UM523F-EN-P - September 2006

Maintain and Troubleshoot the System

Check the Allocation of


Unused Memory

127

The controller reserves a specific amount of its unused memory for


tags and the rest for logic. Depending on how you configure the
memory usage, you might not have memory for the required
operation.

To display this dialog box:


1. Choose Edit Controller Properties.
2. On the Redundancy tab, choose the Advanced button.

If

Then

Important

OPC communications error or fail

Make sure the slider is not all the way to Tags.

You are unable to create tags while online

Make sure the slider is not all the way to Logic.

You are able to change this setting only


while:

You are unable to perform online edits

offline.
online in program mode.

Adjust CNB Usage

For each CNB module in a redundant chassis, keep CPU usage to less
than 75 percent.
Each redundant CNB module needs enough additional
processing time for redundancy operations.
At peak operations such as synchronization, redundancy uses an
additional 8 percent (approximately) of the CPU of the CNB
module.
A total CPU usage that is higher than 75 percent may prevent a
secondary chassis from synchronizing after a switchover.
To reduce the CPU usage of a module, take any of the following
actions:
Change the network update time (NUT) of the ControlNet
network (Typically, increase the NUT to reduce the CPU usage
of a CNB module.)
Increase the requested packet interval (RPI) of your connections.
Reduce the number of connections to (through) the CNB.
Reduce the number of MSG instructions.
Add another CNB module to each redundant chassis.
Publication 1756-UM523F-EN-P - September 2006

128

Maintain and Troubleshoot the System

To obtain status information about a CNB module:


use RSLinx software.
look at the four-character display.
send a message to the CNB module.

Use RSLinx Software


1. Start RSLinx software.
2. Expand a network until the CNB module appears.
3. Right-click the module and choose Module Statistics.
4. Click Connection Manager.

Number of connections
used

CPU usage

42903

Look at the Four-Character Display


42797

Publication 1756-UM523F-EN-P - September 2006

The four-character display on the front of the 1756-CNB/D/E or


1756-CNBR/D/E module, shows the following information:

Maintain and Troubleshoot the System

129

For this information about a


CNB module

Display

Where

Address of the module

A#xx

xx is the node address of the module.

Percent of CPU usage

%Cxx

xx is the percent of CPU usage. The range for the display is 00 - 99%.

Number of open connections

nCxx

xx is the number of open connections that the module is using.

Number of unconnected client


buffers

Ucxx

xx is the number of unconnected client buffers that the module is using. You see this
number only if the module is using 80% of its buffers or more. The module stops showing
the number if the number drops below 50%.

Number of unconnected server


buffers

Usxx

xx is the number of unconnected server buffers that the module is using. You see this
number only if the module is using 80% of its buffers or more. The module stops showing
the number if the number drops below 50%.

State of the modules keeper


function

Kpxx

xx is the state of the modules keeper function:


If xx is Then the module is
Ai

Active network keeper with either:


invalid keeper information
or
keeper signature that does not match the keeper signature of the network.

Av

Active network keeper with:


valid keeper information.
keeper signature that defines the keeper signature of the network.

Ii

Inactive network keeper with either:


invalid keeper information
or
keeper signature that does not match the keeper signature of the network.

Iv
Oi

Inactive network keeper with valid keeper information that matches the
keeper signature of the network.
Powering up with invalid keeper information
or
offline with invalid keeper information.

Ov

Powering up with valid keeper information that may or may not match the
keeper signature of the network
or
offline with valid keeper information that may or may not match the
keeper signature of the network.

Number of times that the


bandwidth of the module was
exceeded

Bxnn

nn is the number of times that the bandwidth of the module was exceeded (bandwidth
exceeded error) since the module was turned off or reset. You see this number only if the
number is more than zero.

Publication 1756-UM523F-EN-P - September 2006

130

Maintain and Troubleshoot the System

Send a Message to the CNB Module


To use a Message (MSG) instruction to learn the CPU usage of a
CNB module, configure the MSG instruction as follows:
On this tab

For this

Type or select

Configuration

Message Type

CIP Generic

Service Type

Custom

Service Code

4f

Class

a1

Instance

Attribute

Source Element

Tag that uses a user-defined data type:


Members of the data type

Communication

Tag value

Name

Data type

offset

DINT

size_returned

INT

Source Length

Destination

INT tag in which to store the CPU usage of the CNB module
(0 - 99%.)

Path

1, slot_number
where:
slot_number is the slot number of the CNB module.

Publication 1756-UM523F-EN-P - September 2006

Maintain and Troubleshoot the System

Change CNB modules from


Series D to Series E

131

Complete the following procedure to replace 1756-CNB/D or


1756-CNBR/D module(s) with series E modules.
IMPORTANT

Use this procedure only if your redundancy system is already at


revision 15.
Replace CNB modules with CNB modules and CNBR modules with
CNBR modules. Otherwise your chassis wont synchronize.
Finish this procedure once you start it.
Each module must be the same series as its partner in the other
redundant chassis. If you replace a module with a different series,
you must replace the partner module with the same series.

Before You Begin


This procedure is easier to complete if you first update the firmware
of your 1756-CNB/D or 1756-CNBR/D module(s).
If the CNB modules are

And you

Revision 11.1 or later


Not revision 11.1 or later

Then
Go to Actions and start the procedure. You dont need to update the
firmware of the modules.

Have a nonredundant
chassis with an open slot

1. Add the revision 11 EDS files for the CNB modules, if you havent
already done so.
2. Put one of the CNB modules into the open slot of the nonredundant
chassis.
3. Use ControlFlash software and update the firmware of the CNB module.
4. Remove the CNB module.
5. Repeat steps 1 thru 4 for the rest of the CNB modules.
6. Go to Actions and start the procedure.

Dont have a nonredundant


chassis with an open slot

Go to Actions and start the procedure. Youll have to use the secondary
chassis to update the modules.

Publication 1756-UM523F-EN-P - September 2006

132

Maintain and Troubleshoot the System

Actions
Action

Details

1. Add the latest EDS files.

Add the revision 11 EDS files for the 1756-CNB and 1756-CNBR modules, if you havent
already done so,

2. Prepare the RSLogix 5000 project.

A. Start the RSLogix 5000 software and go online with the primary controller.
B. For each CNB/D/E or CNBR/D/E module in the local chassis, set the electronic keying
to compatible keying or disable keying and apply the changes.

C. Save the project.


3. Open the SRM configuration tool for the
primary chassis.

A. Start RSLinx software.


B. From the Communications menu, choose RSWho.
C. Open the branches of your network until you find the 1757-SRM module in the primary
chassis.
D. Right-click the SRM and choose Module Configuration.

Publication 1756-UM523F-EN-P - September 2006

Maintain and Troubleshoot the System

Action

Details

4. Disqualify the secondary chassis,

A. Click Configuration.

133

B. Set Auto-Synchronization to Never.

C. Choose Apply and then Yes.


D. Click Synchronization.

E. Choose Disqualify Secondary and then Yes.

The secondary chassis


is disqualified.
F. Choose OK.
5. Did you already update the firmware of
the series E modules?

Did you already update the firmware of the series E modules?


Yes Go to step 7.
No Continue with step 6.

Publication 1756-UM523F-EN-P - September 2006

134

Maintain and Troubleshoot the System

Action

Details

6. Update the firmware of the series E


modules.

A. Remove the 1757-SRM module from the secondary chassis.


B. Set the address of each series E module to the address of its corresponding series D
module plus one.
C. Replace each series D module with the corresponding series E module.
Important: Make sure you connect the correct ControlNet tap to each module.
D. Use ControlFlash software and update the firmware of each series E module.
E. Remove the series E modules from the secondary chassis and set their addresses to
match the original series D modules.
F. Repeat steps B thru E for the second set of series E modules.
G. Put the secondary SRM back into the secondary chassis.
H. Put one set of series E modules into the secondary chassis.
Important: Make sure that you use the correct address, slot, and ControlNet tap for
each module.
I. Go to step 8.

7. Replace the CNB modules in the


secondary chassis.

Replace the CNB modules in the secondary chassis with series E modules. As you replace
the modules:
make sure that you set each module to the same address as the module that its
replacing.
make sure that you connect the correct ControlNet tap. To avoid connecting the wrong
tap, replace the modules one at a time and reconnect the ControlNet tap.

Publication 1756-UM523F-EN-P - September 2006

Maintain and Troubleshoot the System

Action

Details

8. Update the keeper signatures of the CNB


modules.

A. Start RSNetWorx for ControlNet and open the network configuration file.

135

B. Go online with the network. You dont have to browse the entire network.
C. Select Network > Keeper Status.

D. Select the node number of the secondary CNB and click Update Keeper.

E. Verify that the keeper signature has been updated.

F. Repeat steps D and E for the other CNB modules in the secondary chassis.
G. Click Close.

Publication 1756-UM523F-EN-P - September 2006

136

Maintain and Troubleshoot the System

Action

Details

9. Reset the secondary CNB modules.

A. Cycle power to the secondary chassis.


B. On the Synchronization Status tab of the configuration tool, verify that the modules
show full compatibility.

10. Synchronize the secondary chassis.

A. Click Synchronization.

B. Choose Synchronize Secondary and then Yes.


C. Wait for the chassis to synchronize.

The chassis are synchronized.


11. Initiate a switchover.

Choose Initiate Switchover and Yes.


12. Replace the CNB modules in the new
secondary chassis.

Publication 1756-UM523F-EN-P - September 2006

Repeat steps 7 thru 9 for the CNB modules in the new secondary chassis.

Maintain and Troubleshoot the System

Action

Details

13. Synchronize the chassis.

A. Go to the SRM configuration tool for the primary chassis.

137

B. On the Configuration tab, change the Auto-Synchronization option to Always.

C. Choose Apply and Yes.


14. In the RSLogix 5000 project, change the
revision of the new local CNB modules to
revision 11.

Store or Load a Project


Using Nonvolatile Memory

Nonvolatile memory lets you keep a copy of your project on the


controller.
Term

Description

Nonvolatile memory

Memory of the controller that retains its contents while the


controller is without power or a battery.

Store

To copy a project to the nonvolatile memory of the controller.


This overwrites any project that is currently in the nonvolatile
memory.

Load

To copy a project from nonvolatile memory to the user memory


(RAM) of the controller. This overwrites any project that is
currently in the controller.

Publication 1756-UM523F-EN-P - September 2006

138

Maintain and Troubleshoot the System

In a redundant system, store or load a project only while the


secondary chassis is disqualified.
Action

Details

Store a Project

Important: If your computer is online with the controller over a ControlNet network, check the
CPU usage of the CNB module. The CPU usage module must be less than about 75% for the store
to work.
1. Put the primary controller in program mode (program or remote program).
2. Open the Module Configuration properties for one of the 1757-SRM modules.
3. Set the Auto-Synchronization option to Conditional.
4. Disqualify the secondary chassis.
5. Store the project that is in the primary controller.
For step-by-step procedures on how to store a project, see Logix5000 Controllers Common
Procedures, publication 1756-PM001.
Important: Do not go back online to the primary controller until you complete the rest of the
steps in this procedure.
6. Go online to the secondary controller and store the project.
7. Return to the Module Configuration properties for one of the 1757-SRM modules.
8. Synchronize the controllers.
9. Set the Auto-Synchronization option to the desired option.

Load a ProjectUser Initiated

1. Disqualify the secondary chassis.


2. Go online to the primary controller.
3. In the primary controller, load the project.
For step-by-step procedures on how to store a project, see Logix5000 Controllers Common
Procedures, publication 1756-PM001.
4. Synchronize the controllers.

Load a ProjectOn Power Up

This Load Image option works the same as in a nonredundant system.


The controller loads the project on power up.
The controller loads the project before it activates the redundancy feature.

Load a ProjectOn Corrupt Memory

This Load Image option works the same as in a nonredundant system.


The controller loads the project when the memory is empty or corrupt.
The controller loads the project before it activates the redundancy feature.

Publication 1756-UM523F-EN-P - September 2006

Maintain and Troubleshoot the System

Store a Project to
Nonvolatile Memory While
a Process Is Running

139

Complete the following procedure to store an updated project and


firmware to the nonvolatile memory of the controller. This procedure
lets you store a project while the process is running.
IMPORTANT

Use this procedure only with a 1756-L6x controller. Do not use


the nonvolatile memory of a 1756-L55M2x controller if youve
updated it to revision 15. Otherwise the controller will have an
unrecoverable fault (solid red OK light) and clear the project
from its memory.

Action

Details

1. Make sure the chassis are synchronized.

Synchronize the chassis if they arent already synchronized.

2. Disqualify the secondary chassis.

A. Open the SRM configuration tool for the primary chassis.


B. Set the Auto-Synchronization option to Never.
C. Disqualify the secondary chassis.

3. Store the secondary controllers project.

A. Go online to the secondary controller


B. Store the project to the nonvolatile memory of the secondary controller.
For step-by-step procedures on how to store a project, see Logix5000 Controllers
Common Procedures, publication 1756-PM001.
Important: Do not go back online to the secondary controller until you complete the
rest of the steps in this procedure.

4. Initiate a switchover.

A. Go to the SRM configuration tool.


B. Synchronize the chassis.
C. Initiate a switchover.

5. Store the new secondary controllers


project.

A. Go online to the new secondary controller


B. Store the project to the nonvolatile memory of the secondary controller.
For step-by-step procedures on how to store a project, see Logix5000 Controllers
Common Procedures, publication 1756-PM001.
Important: Do not go back online to the secondary controller until you complete this
procedure.

6. Synchronize the chassis.

A. Go to the SRM configuration tool.


B. Set the Auto-Synchronization option to the desired option.
C. Synchronize the chassis.

Publication 1756-UM523F-EN-P - September 2006

140

Maintain and Troubleshoot the System

Update a Module

Complete the following procedure to upgrade the revision of your


redundant modules. This procedure minimizes the time your process
is down during an upgrade.
IMPORTANT

Dont connect your computer to the network access port on a


CNB module in the primary chassis. Youll lose access to the
network when you turn off power to the chassis.

Action

Details

1. Upload and save the project.

A. Do you have an up-to-date copy of the project for the controller stored offline?
Yes Go to step 2.
No Continue with step B.
B. Upload the project in the primary controller.
C. Save the project.

2. Open the SRM configuration tool for the


secondary chassis.

A. Start RSLinx software.


B. From the Communications menu, choose RSWho.
C. Open the branches of your network until you find the 1757-SRM module in the primary
chassis.
D. Right-click the SRM and choose Module Configuration.

Publication 1756-UM523F-EN-P - September 2006

Maintain and Troubleshoot the System

Action

Details

3. Disqualify the secondary chassis,

A. Click Configuration.

141

B. Set Auto-Synchronization to Never.

C. Choose Apply and then Yes to confirm.


D. Click Synchronization.

E. Choose Disqualify Secondary and then Yes to confirm.


4. Upgrade the required firmware of the
secondary chassis.

See the ControlLogix Controller and Memory Board Installation Instructions, publication
1756-IN101.

5. Make the secondary controller the new


primary controller.

A. Start RSLogix 5000 software.


B. Download the project to the secondary controller.
C. When it is safe to stop the system, change the primary controller to Program Mode.
D. Turn off power to the primary chassis.
E. Go to the 1757-SRM properties of the secondary chassis.

F. Choose Become Primary.

Publication 1756-UM523F-EN-P - September 2006

142

Maintain and Troubleshoot the System

Action

Details

6. Clear the fault of the new primary


controller.

A. In RSLogix 5000 software, go online to the new primary controller.


B. The controller is faulted. When a disqualified secondary controller becomes a primary
controller, the controller experiences a major fault.
C. From the Communications menu, choose Clear Faults.
D. To start control of the process, from the Communications menu, choose Run Mode.

7. Upgrade the other redundant chassis.

A. Turn on power to the other redundant chassis.


B. Upgrade the required firmware of the chassis.

8. Change the Auto-Synchronization Option


to ALWAYS.

A. Open the SRM configuration tool for the primary chassis.


B. On the Configuration tab, change the Auto-Synchronization option to Always.
C. Choose OK.

Update a System That Is


Already at Revision 13

Complete the following procedure to update the firmware of a


redundant chassis without shutting down the process:
IMPORTANT

Use this procedure only if your system is already at revision 13.


Do not use this procedure if:
your system is at revision 11 or earlier.
your system isnt operating yet.
During this procedure, you wont be able to use RSLogix 5000
software to change the mode of the controller. Use the keyswitch on
the front of the controller to change its mode.
Leave RSNetWorx for ControlNet software closed or offline
throughout this procedure. Otherwise, youll see errors in the
RSNetWorx software during the update process.
During this procedure:
Do not make any changes to the RSLogix 5000 project other than
the ones called out in this procedure.
Make sure no one else makes changes to the project.

Publication 1756-UM523F-EN-P - September 2006

Maintain and Troubleshoot the System

Action

Details

1. Update the software

A. Go to the tool tray of your computer and shutdown RSLinx software.

143

B. Update the following software:


1. 1757-SRM System Redundancy Module Configuration tool
2. RSLogix 5000 software
3. RSLinx software
4. RSNetWorx software
5. ControlFLASH firmware update kit.
If youre planning to uninstall version 13 of your RSLogix 5000 software, wait until youve
completed and validated your update.
2. Add the latest EDS files.

Start Programs Rockwell Software RSLinx Tools EDS Hardware Installation


Tool

3. Put the keyswitches in the REM position.

Put the keyswitch of each redundant controller to the REM position. Otherwise you wont
be able to update the system.

4. Open the SRM configuration tool for the


primary chassis.

A. Start RSLinx software.


B. From the Communications menu, choose RSWho.
C. Open the branches of your network until you find the 1757-SRM module in the primary
chassis.
D. Right-click the SRM and choose Module Configuration.

Publication 1756-UM523F-EN-P - September 2006

144

Maintain and Troubleshoot the System

Action

Details

5. Disqualify the secondary chassis,

A. Click Configuration.
B. Set Auto-Synchronization to Never.

C. Choose Apply and then Yes.


D. Click Synchronization.

E. Choose Disqualify Secondary and then Yes.

The secondary chassis is


disqualified.
F. Choose OK.
6. Update the SRM module in the secondary
chassis.

A. Start the ControlFLASH firmware update tool.


B. Update the 1757-SRM module in the secondary chassis.

7. Synchronize the chassis.

A. Go to the SRM configuration tool.

B. Choose Synchronize Secondary and then Yes.

The chassis are synchronized.

Publication 1756-UM523F-EN-P - September 2006

Maintain and Troubleshoot the System

Action

145

Details

8. Initiate a switchover.

A. Choose Initiate Switchover and Yes.


B. Wait for the system to switchover.

The other chassis is now the


primary chassis.
9. Update the modules in the new
secondary chassis.

Use the ControlFLASH firmware update tool to update the modules in the new secondary
chassis.

10. Prepare the RSLogix 5000 project for the


update.

A. Start RSLogix 5000 software and go online to the primary controller.


B. Set the watchdog time for each task to this value or more:
Minimum watchdog time = (2 * maximum_scan_time) + 150 ms
where:
Maximum_scan_time is the maximum scan time for the entire task when the
secondary controller is synchronized.
C. Cancel or assemble any test edits.
D. Remove all SFC forces from the project.
E. Make sure that you dont need to make any changes to:
I/O Forces Once you start this procedure, you wont be able to disable or
enable I/O forces until you update both chassis.
I/O configuration
You can make those changes again when the update is done and both chassis
synchronize.
F. Save the project.

Publication 1756-UM523F-EN-P - September 2006

146

Maintain and Troubleshoot the System

Action

Details

11. Change the project revisions.

A. Go offline.

B. Click the Controller Properties button.


C. Change the controller to the newer revision.

Example: Change the controller from revision 13 to revision 15.


D. Change the Revision of each local communication module to match what its revision
will be after you update its firmware.
Example: Suppose you plan to update the firmware of each CNB/D module in the
redundant chassis to revision 7.12. In that case, open the properties for each CNB/D
module in the chassis and set the revision to 7.12.

If you cant select the new revision, then change the electronic keying to either
compatible keying or disable keying.

Publication 1756-UM523F-EN-P - September 2006

Maintain and Troubleshoot the System

147

Action

Details

12. Download the project to the secondary


controller.

Important: If I/O forces are enabled in the offline project, the software asks if you want to
enable the forces in the controller. Even if you choose No, I/O forces stay enabled in the
primary controller and become enabled in this controller after you switchover.
A. Use RSLogix 5000 software to download the project to the controller in the secondary
chassis. The secondary chassis has the higher network address of the redundant pair.
B. Go offline.
Important: Stay offline until you finish this procedure.

13. Lock the system for update.

Important: Do not abort a system lock. Otherwise, youll clear the project from the
secondary controller.
A. Open the SRM configuration tool for the primary chassis.
B. Click System Update.

C. Choose Lock For Update and Yes.


D. Wait for the system to lock. It takes longer than a normal synchronization.

The system is locked.

Publication 1756-UM523F-EN-P - September 2006

148

Maintain and Troubleshoot the System

Action

Details

14. Initiate a Locked Switchover.

A. Choose Initiate Locked Switchover and Yes.


B. Wait for the system to switchover. A locked switchover takes about as long as a
normal switchover.

The other chassis is now the


primary chassis.
15. Update the other redundant chassis.

Use the ControlFLASH firmware update tool to update the rest of the modules in the new
secondary chassis. Youve already updated the SRM module in this chassis.

16. Synchronize the chassis.

A. Go to the SRM configuration tool for the primary chassis.


B. On the Configuration tab, change the Auto-Synchronization Option to ALWAYS.

C. Choose Apply and Yes.

The chassis synchronize.

D. Change the Date and Time in the SRM module.


E. Choose OK.

Publication 1756-UM523F-EN-P - September 2006

Appendix

Set Up EtherNet/IP Communication Across


Subnets

Purpose of This Chapter

To keep HMIs and messages pointing to the primary chassis when IP


swapping is not in use

When to Use This Chapter

Use this chapter when:


you want to use alias topics instead of IP swapping.
your primary and secondary chassis are on different EtherNet/IP
subnets.
If both redundant chassis are on

Then

Different subnets

You must point your HMIs and messages to


the new primary chassis after a switchover.
Use this appendix to show you how.

Router

Switch

Switch
Primary
chassis

Secondary
chassis

Same subnet
Switch
Primary
chassis

Secondary
chassis

Stop. Use IP swapping instead. This lets you


use the same IP address regardless of
which chassis is primary.
See Chapter 2.

When primary and secondary chassis are on different EtherNet/IP


subnets, they keep their IP addresses during a switchover. This means
that your and other controllers must be able to switch between the IP
address of each redundant chassis.

How to Use This Chapter

149

This chapter provides the following information:


Topic

Page

Keep an HMI Communicating with the Primary Chassis

150

Keep a Message Going to the Primary Chassis

156

Publication 1756-UM523F-EN-P - September 2006

150

Set Up EtherNet/IP Communication Across Subnets

Keep an HMI
Communicating with the
Primary Chassis

If youre not using IP swapping, your HMIs must direct their


communication to the new primary chassis after a switchover.
ControlLogix Redundancy Alias Topic Switcher software can most
easily do this. Look for this software on the CD along with your
firmware.
IMPORTANT

To use the ControlLogix Redundancy Alias Topic Switcher


software, your computer needs an activation file for RSLinx
software. The activation file lets you perform DDE/OPC
communication.

The ControlLogix Redundancy Alias Topic Switcher software works


with RSLinx alias topics. Together they keep your HMI communicating
with the primary controller after a switchover.
HMI tags In your HMI project, each tag references an
alias topic in RSLinx software. This lets RSLinx software
redirect communications to the appropriate chassis.
Xxxx Xx
012345

Alias topic In RSLinx software, an alias topic


represents a flexible communication path to one of
several controllers (topics).
In a ControlLogix redundancy system, the alias topic
points to the topic for the primary controller.

RSLinx
software

When a switchover occurs, the alias topic points to


the topic for the new primary controller.

Alias Topic

Topic for Chassis A

L E
5 N
5 B

Chassis A

Publication 1756-UM523F-EN-P - September 2006

Topic for Chassis B

L E
5 N
5 B

Chassis B

ControlLogix Redundancy Alias Topic Switcher software


Automatically reads a value in RSLinx software to
determine which controller is primary. It then commands
the alias topic to switch to the topic for that controller.

Topic In RSLinx software, a topic represents a


specific path to a controller. Since each ENBT
and EWEB module uses a unique IP address,
create a topic for the controller in each
redundant chassis.

Set Up EtherNet/IP Communication Across Subnets

151

To keep an HMI communicating with the primary chassis:


install the ControlLogix Redundancy Alias Topic Switcher
Software.
configure a Driver to Communicate with the Primary and
Secondary EtherNet/IP Modules.
create a DDE/OPC topic for each controller.
create an alias topic.
set up the alias topic switcher.
address the alias topic in the HMI project.

Install the ControlLogix Redundancy Alias Topic Switcher


Software
The ControlLogix Redundancy Alias Topic Switcher software
maintains communication between your HMI project and the primary
controller after a switchover.
To install the Alias Topic Switcher software, use the ControlLogix
Redundancy Alias Topic Switcher.Exe file. The file is located on the
same CD as the firmware for your redundancy system.
The Alias Topic Switcher software runs as a service. It starts
automatically when you start your computer and shows up in the tool
tray of your desktop.

ControlLogix Redundancy Alias


Topic Switcher

Publication 1756-UM523F-EN-P - September 2006

152

Set Up EtherNet/IP Communication Across Subnets

Configure a Driver to Communicate with the Primary and


Secondary EtherNet/IP Modules
1. Start RSLinx software.

2. Click

3. Select Ethernet devices and choose

4. Accept the default name.


5. Type the IP address of each ENBT or EWEB module.
To add another IP address, choose
6. Choose
7. Click

and then
.
Driver that you just added
Modules in the redundant chassis

Publication 1756-UM523F-EN-P - September 2006

Set Up EtherNet/IP Communication Across Subnets

153

Create a DDE/OPC Topic for Each Controller

1. Browse to the controller in Chassis A.


2. Right-click the controller and choose Configure New
DDE/OPC Topic.

3. Rename the topic to indicate that this is Chassis A.


4. Choose
update topic.)

and then

(Yes

5. Create a topic for the controller in Chassis B.

Publication 1756-UM523F-EN-P - September 2006

154

Set Up EtherNet/IP Communication Across Subnets

Create an Alias Topic


1. In RSLinx software, choose DDE/OPC
Alias Topic Configuration.

2. Type a name for the alias topic that will communicate with this pair of redundant controllers

3. Add the topic for each redundant controller to


the Aliased Topics list.
To add a topic, select the topic and choose

4. Select (check) the Switch on command check


box. Clear (uncheck) the remaining check boxes.
This lets the ControlLogix Redundancy Alias
Topic Switcher software control which topic the
alias topic uses for communication.
5. Choose

and then

Publication 1756-UM523F-EN-P - September 2006

Set Up EtherNet/IP Communication Across Subnets

155

Set Up the Alias Topic Switcher


IMPORTANT

If you start the Alias Topic Switcher software without access to


an RSLinx activation file (for example, without a version of
RSLinx which supports OPC), the following error occurs:
0x80040112
(The text for the message depends on your operating system.)

1. In the system tray, right-click the Redundancy Switch icon and choose Open Alias Topic Switching Tool.

2. In the Redundancy Alias Topic Switching Tool window, choose

3. Type the topic names:


a. Alias topic
b. Topic for the controller in Chassis A

Topic that the alias topic is currently using

Publication 1756-UM523F-EN-P - September 2006

156

Set Up EtherNet/IP Communication Across Subnets

Address the Alias Topic in the HMI Project

When you create tags for your HMI project, use the alias topic in the address of the tag.

Keep a Message Going to


the Primary Chassis

If youre not using IP swapping, any controller that sends a message


to a redundant chassis has to point to the new primary chassis after a
switchover.
L E
x N
B
T

IP Address A
L
5
5
M

IP Address B
L E
5 N
5 B

E
N
B
T

Chassis A
Primary

Chassis B
Switchover

Primary

In this procedure, use CIP Generic messages to determine which


chassis is primary. Then send a Message (MSG) instruction to the
primary controller.

Publication 1756-UM523F-EN-P - September 2006

Set Up EtherNet/IP Communication Across Subnets

L E
x N
B

MSG
Type - CIP Generic

L
5
5
M

157

E
N
B
T

Chassis A
MSG
Type - CIP Generic

L E
5 N
5 B

Chassis B

To keep a Message (MSG) instruction going to the new primary


chassis after a switchover:

create a periodic trigger for the messages.


obtain the redundancy state of chassis A.
obtain the redundancy state of chassis B.
determine which chassis is primary.
send the message to the appropriate controller.

Create a Periodic Trigger for the Messages


Free-running timer that triggers the execution of MSG instructions. The timer runs for 2 seconds (2000 ms) and then resets
and starts timing again. Every 2 seconds, Timer_RedundancyMSGs.DN = 1 for a single scan. The MSG instructions use this
bit as one of their conditions for execution.

Tag Name

Description

Alias For

Timer_RedundancyMSGs

Periodic trigger for the


execution of MSG
instructions. Triggers MSGs
every 2s.

Data Type
TIMER

Publication 1756-UM523F-EN-P - September 2006

158

Set Up EtherNet/IP Communication Across Subnets

Get the Redundancy State of Chassis A


If Timer_RedundancyMSGs.DN = 1 (2 seconds are up so execute the MSG instruction again)
And ChasA_GetRedundState_FromENBT.EN = 0 (The MSG instruction is not currently enabled.)
Then
Execute a MSG instruction that gets the redundancy state of Chassis A from the ENBT module in Chassis A. Store the
value in ChasA_RedundancyState (data type = DINT).

Tag Name

Description

Alias For

Timer_RedundancyMSGs

Periodic trigger for the execution of MSG


instructions. Triggers MSGs every 2s.

TIMER

ChasA_GetRedundState_FromENBT

Message instruction that gets the redundancy state


of Chassis A

MESSAGE

ChasA_RedundancyState

Redundancy state of the Chassis A:

DINT

2 = PwQS
3 = PwDS
4 = PwNS
MSG parameter

Value

Message Type

CIP Generic

Service Type

Get Attribute Single

Service Code

Class

c0

Instance

Attribute

Source Element

Publication 1756-UM523F-EN-P - September 2006

Data Type

Set Up EtherNet/IP Communication Across Subnets

MSG parameter

159

Value

Source Length
Destination

ChasA_RedundancyState

Path
(Communication tab)

Specify the 1756-ENBT module in Chassis A. Use either of the


following methods:
Add the module to the I/O configuration of the controller. Then
use the Browse button on the Communication tab to identify
the module.
Type the path using port numbers and addresses.

Get the Redundancy State of Chassis B


If Timer_RedundancyMSGs.DN = 1 (2 seconds are up so execute the MSG instruction again)
And ChasB_GetRedundState_FromENBT.EN = 0 (The MSG instruction is not currently enabled.)
Then
Execute a MSG instruction that gets the redundancy state of Chassis B from the ENBT module in Chassis B. Store the
value in ChasB_RedundancyState (data type = DINT).

Tag Name

Description

Alias For

Data Type

Timer_RedundancyMSGs

Periodic trigger for the execution of MSG


instructions. Triggers MSGs every 2s.

TIMER

ChasB_GetRedundState_FromENBT

Message instruction that gets the redundancy state


of Chassis B

MESSAGE

ChasB_RedundancyState

Redundancy state of the Chassis B:

DINT

2 = PwQS
3 = PwDS
4 = PwNS

Publication 1756-UM523F-EN-P - September 2006

160

Set Up EtherNet/IP Communication Across Subnets

MSG parameter

Value

Message Type

CIP Generic

Service Type

Get Attribute Single

Service Code

Class

c0

Instance

Attribute

Source Element
Source Length
Destination

ChasB_RedundancyState

Path
(Communication tab)

Specify the 1756-ENBT module in Chassis B. Use either of the


following methods:
Add the module to the I/O configuration of the controller. Then
use the Browse button on the Communication tab to identify
the module.
Type the path using port numbers and addresses.

Publication 1756-UM523F-EN-P - September 2006

Set Up EtherNet/IP Communication Across Subnets

161

Determine Which Chassis is Primary


If ChasA_RedundancyState = 2, 3, or 4 then
ChasA_IsPrimary = 1. (Chassis A is the primary chassis.)

If ChasB_RedundancyState = 2, 3, or 4 then
ChasB_IsPrimary = 1. (Chassis B is the primary chassis.)

Tag Name

Description

ChasA_RedundancyState

Redundancy state of the Chassis A:

Alias For

Data Type
DINT

2 = PwQS
3 = PwDS
4 = PwNS
ChasB_RedundancyState

Redundancy state of the Chassis B

DINT

2 = PwQS
3 = PwDS
4 = PwNS

Publication 1756-UM523F-EN-P - September 2006

162

Set Up EtherNet/IP Communication Across Subnets

Tag Name

Description

Alias For

Data Type

ChasA_IsPrimary

If set (1), then Chassis A is the primary chassis.

IsPrimary.0

BOOL

ChasB_IsPrimary

If set (1), then Chassis B is the primary chassis.

IsPrimary.1

BOOL

IsPrimary

Each bit represents the primary status for an


individual chassis within a redundant chassis pair.
1 = primary.
0 = not primary.
A single DINT tag for all the chassis uses less
memory than a unique tag for each chassis.

Send the Message to the Appropriate Controller


If Timer_RedundancyMSGs.DN = 1 (2 seconds are up.)
And ChasA_IsPrimary = 1. (Chassis A is the primary chassis.)
And ChasA_MSG.EN = 0 (The message is not currently enabled.)
Then
Execute the MSG instruction for the controller in Chassis A.

Publication 1756-UM523F-EN-P - September 2006

DINT

Set Up EtherNet/IP Communication Across Subnets

163

If Timer_RedundancyMSGs.DN = 1 (2 seconds are up.)


And ChasB_IsPrimary = 1. (Chassis B is the primary chassis.)
And ChasB_MSG.EN = 0 (The message is not currently enabled.)
Then
Execute the MSG instruction for the controller in Chassis B.

Tag Name

Description

Alias For

Data Type

ChasA_IsPrimary

If set (1), then Chassis A is the primary chassis.

IsPrimary.0

BOOL

ChasA_MSG

Message instruction that transfers data between this


controller and the controller in redundant Chassis A

ChasB_IsPrimary

If set (1), then Chassis B is the primary chassis.

ChasB_MSG

Message instruction that transfers data between this


controller and the controller in redundant Chassis B

MESSAGE
IsPrimary.1

BOOL
MESSAGE

Publication 1756-UM523F-EN-P - September 2006

164

Set Up EtherNet/IP Communication Across Subnets

Notes:

Publication 1756-UM523F-EN-P - September 2006

Appendix

Convert an Existing System to Redundancy

Introduction

If you are adding redundancy to an existing system, follow these


guidelines:
Changing the node number of a CNB module may affect
messages, tags, or listen-only connections in other devices.
Choose node numbers that have the least impact on existing
communications.
An existing system that contains local I/O modules still requires
two additional chassis.
A redundant system can use only I/O that is in a remote
chassis (for example, not in the same chassis as the
controller).
We recommend that you move the existing 1756-L55Mxx
controller from the original chassis and place it in a redundant
chassis.
Change any event tasks to periodic tasks. You cant use event
tasks in a ControlLogix redundancy system.

Convert Local Modules to


Remote Modules

If you are converting an existing system to a redundant system:


And the system

Then

Contained only I/O modules that


were not in the same chassis as
the controller

Do not change the I/O configuration of the controller.

Contained local I/O modules

Use the procedures in this section to convert the


configuration of local modules to remote modules.

To convert a local module to a remote module:


reconfigure the local I/O modules.
replace local I/O tags.
replace any aliases to local I/O tags.

165

Publication 1756-UM523F-EN-P - September 2006

166

Convert an Existing System to Redundancy

Reconfigure the Local I/O Modules


1. If you have not already done so, add the CNB module of the
remote chassis to the I/O configuration of the controller. See the
ControlLogix System User Manual, publication 1756-UM001.

I/O Configuration
[x] 1756-xxx name_of_local_module

Cut local I/O modules from here.

[x] 1756-CNB/x name_of_local_CNB


z [x] 1756-CNB/x name_of_remote_CNB

Paste the I/O modules


here.

2. In the controller organizer, cut the modules from the local I/O
configuration and paste them into the remote CNB module. Cut
and paste the following modules:
I/O
1756-DHRIO
1756-DNB
1756-ENET or -ENB
1756-MVI

Replace Local I/O Tags


1. Open a routine. If a routine is already open, click within the
routine to activate the window.
2. Press the Ctrl + H keys.

Publication 1756-UM523F-EN-P - September 2006

Convert an Existing System to Redundancy

167

4
5

6
42804

3. Type Local.
4. Type the name of the CNB module that is in the remote chassis.
5. Select All Routines.
6. Choose Find Within >>.

42805

7. Select Ladder Diagram.


8. Check Instruction Operands.
9. Choose Replace All.
The Search Results tab displays the changes to the logic.

Publication 1756-UM523F-EN-P - September 2006

168

Convert an Existing System to Redundancy

10. Choose Close.


The following example shows the results of replacing Local with
chassis_c.
Replacing "Local" with "chassis_c"...

EXAMPLE

Searching through MainProgram - MainRoutine...


Replaced: Rung 0, XIC, Operand 0: XIC(Local:16:I.Data.0)
Replaced: Rung 0, OTE, Operand 0: OTE(Local:2:O.Data.0)
Replaced: Rung 1, XIC, Operand 0: XIC(Local:16:I.Data.1)
Replaced: Rung 1, OTE, Operand 0: OTE(Local:2:O.Data.1)
Replaced: Rung 2, XIC, Operand 0: XIC(Local:16:I.Data.2)
Replaced: Rung 2, OTE, Operand 0: OTE(Local:2:O.Data.2)
Replaced: Rung 8, OTE, Operand 0: OTE(Local:15:O.CommandRegister.Run)

Complete - 7 occurrence(s) found, 7 occurrence(s) replaced.

Replace Any Aliases to Local I/O Tags


Are any tags aliases for I/O devices that were previously in a local
chassis?
If

Then

Yes

Go to step 1.

No

Skip this procedure.

1. From the Logic menu, choose Edit Tags.


2. Press the Ctrl + H keys (replace).

Publication 1756-UM523F-EN-P - September 2006

Convert an Existing System to Redundancy

169

4
5

6
42815

3. Type Local.
4. Type the name of the CNB module that is in the remote chassis.
5. Select All Tags.
6. Choose Find Within >>.

42815

7. Check Alias.
8. Choose Replace All.
9. Choose Close.

Publication 1756-UM523F-EN-P - September 2006

170

Convert an Existing System to Redundancy

Notes:

Publication 1756-UM523F-EN-P - September 2006

Appendix

Attributes of the Redundancy Object

Use the redundancy object to learn about the status of your


redundancy system.
For this information

Get this attribute

Data
type

GSV/SSV

Description

Redundancy status of the


entire chassis

ChassisRedundancy
State

INT

GSV

If

Then

16#1

Power up or undetermined

16#2

Primary with synchronized secondary

16#3

Primary with disqualified secondary

16#4

Primary with no secondary

If

Then

16#8

Synchronized secondary

16#9

Disqualified secondary with primary

16#E

No partner

If

Then

16#1

Power up or undetermined

16#2

Primary with synchronized secondary

16#3

Primary with disqualified secondary

16#4

Primary with no secondary

16#6

Primary with synchronizing secondary

If

Then

16#7

Synchronizing secondary

16#8

Synchronized secondary

16#9

Disqualified secondary with primary

16#E

No partner

If

Then

Undetermined

No compatible partner

Fully compatible partner

Redundancy state of the


partner chassis

Redundancy status of the


controller

Redundancy state of the


partner

Results of the compatibility


checks with the partner
controller

171

PartnerChassis
RedundancyState

ModuleRedundancy
State

PartnerModule
RedundancyState

INT

INT

INT

CompatibilityResults INT

GSV

GSV

GSV

GSV

Publication 1756-UM523F-EN-P - September 2006

172

Attributes of the Redundancy Object

For this information

Get this attribute

Data GSV/SSV
type

Description

Status of the
synchronization
(qualification) process

Qualification
InProgress

INT

If

Then

-1

Synchronization (qualification) is not in progress.

Unsupported

1 - 99

For modules that can measure their completion


percentage, the percent of synchronization
(qualification) that is complete.

50

For modules that cannot measure their completion


percentage, synchronization (qualification) is in
progress.

100

Synchronization (qualification) is complete.

If

Then

One of the following:

Keyswitch settings of the


controller and its partner
match or do not match

KeyswitchAlarm

DINT

GSV

GSV

The keyswitches match.


No partner is present.
Position of the keyswitch of
the partner

Status of the minor faults of


the partner (if the
ModuleRedundancyState
indicates that a partner is
present)

PartnerKeyswitch

PartnerMinorFaults

Publication 1756-UM523F-EN-P - September 2006

DINT

DINT

GSV

GSV

Keyswitches do not match

If

Then the keyswitch is in

Unknown

RUN

PROG

REM

This
bit

Means this minor fault

Problem with an instruction (program)

Periodic task overlap (watchdog)

Problem with the serial port

10

Low battery

Attributes of the Redundancy Object

For this information

Get this attribute

Data
type

GSV/SSV

Description

Mode of the partner

PartnerMode

DINT

GSV

If

Then

16#0

Power up

16#1

Program

16#2

Run

16#3

Test

16#4

Faulted

16#5

Run-to-program

16#6

Test-to-program

16#7

Program-to-run

16#8

Test-to-run

16#9

Run-to-test

16#A

Program-to-test

16#B

Into faulted

16#C

Faulted-to-program

If

Then

Unknown

Chassis A

Chassis B

In a pair of redundant
chassis, identification of a
specific chassis without
regard to the state of the
chassis.

PhysicalChassisID

INT

GSV

173

Publication 1756-UM523F-EN-P - September 2006

174

Attributes of the Redundancy Object

For this information

Get this attribute

Data GSV/SSV
type

Slot number of the


1757-SRM module in this
chassis

SRMSlotNumber

INT

GSV

DINT

GSV

Size of the last crossload LastDataTransfer


Size of the last crossload Size
if you had a secondary
chassis

Description

This attribute gives the size of data that was or would have
been crossloaded in the last scan.
The size in DINTs (4-byte words).
You must configure the controller for redundancy.
You dont need a secondary chassis.
Is there a synchronized secondary chassis?
Yes This gives number of DINTs that was crossloaded in
the last scan.
No This gives number of DINTs that would have been
crossloaded in the last scan.

Size of the biggest


crossload

MaxDataTransfer
Size

Size of the biggest


crossload if you had a
secondary chassis

DINT

GSV
SSV

This attribute gives the biggest size of the LastDataTransfer


Size attribute.
The size in DINTs (4-byte words).
You must configure the controller for redundancy.
You dont need a secondary chassis.
To reset this value, use an SSV instruction with a Source
value of 0.
Is there a synchronized secondary chassis?
Yes This gives biggest number of DINTs that was
crossloaded.
No This gives biggest number of DINTs that would have
been crossloaded.

Publication 1756-UM523F-EN-P - September 2006

Appendix

If You Have Series B ControlNet Bridge


Modules

About This Appendix

This appendix describes several situations that could happen if you


use series B of a ControlNet Bridge module:
Topic

Page

Communication Loss If You Bridge Through a Series B ControlNet Bridge Module 175
Communication Could Stop If You Use a Series B ControlNet Bridge Module

177

Communication Loss if You Situation


Bridge Through a Series B
could temporarily lose communication with a remote chassis if
ControlNet Bridge Module You
you use both these modules in the remote chassis:
1756-CNB/B or 1756-CNBR/B module
1756-DHRIO module that is connected to a remote I/O network.

175

Publication 1756-UM523F-EN-P - September 2006

176

If You Have Series B ControlNet Bridge Modules

Redundant chassis pair

L C
5 N
5 B
M
x

S
R
M

1756-CNB/B or 1756-CNBR/B module


Remote chassis
C
N
B/
B

Other modules

D
H
R
I
O

Remote I/O

IMPORTANT

On the first switchover after you download a project to the controller, you may
temporarily lose communications with these devices

The loss of communication happens on the first switchover after you


download the project to the redundant controller.
You lose communication with the remote chassis and any
devices to which you were bridging via the chassis, such as the
remote I/O modules.
During the communication loss, the I/O modules go to their
configured state for a communication fault.
The communication loss is temporary. Communications restore
themselves.

Prevention
To prevent this situation, use series D ControlNet Bridge modules.

Publication 1756-UM523F-EN-P - September 2006

If You Have Series B ControlNet Bridge Modules

177

Communication Could Stop Situation


If You Use a Series B
communication on a ControlNet network could stop if the lowest
ControlNet Bridge Module All
node is a 1756-CNB/B or 1756-CNBR/B module. This happens if you
unplug or break the tap of the module while it is turned on.

Corrective Action
If

Then

Tap of a series B ControlNet Bridge module


becomes unplugged or broken.

1. Turn off the power to the module.


2. Replace the tap.
3. Turn on the power to the module.

Communication on the network stops


because of an unplugged or broken tap.

Cycle power to each primary controller on


the network.

Prevention
To prevent this situation, use series D ControlNet Bridge modules.

Publication 1756-UM523F-EN-P - September 2006

178

If You Have Series B ControlNet Bridge Modules

Restriction

Description

Communication Loss When Bridging


Through a Series B ControlNet Bridge
Module

You could temporarily lose communication with a remote chassis if you use both these modules in
the chassis:
1756-CNB/B or 1756-CNBR/B module
1756-DHRIO module that is connected to a remote I/O network.
Redundant chassis pair

L C
5 N
5 B
M
x

S
R
M

1756-CNB/B or 1756-CNBR/B module


Remote chassis
C
N
B
/
B

D
H
R
I
O

Other modules

Remote I/O

IMPORTANT

On the first switchover after you download a project to the controller, you may
temporarily lose communications with these devices

The loss of communication occurs on the first switchover after you download the project to the
redundant controller.
You lose communication with the remote chassis and any devices to which you were bridging
via the chassis, such as the remote I/O modules.
During the communication loss, the I/O modules go to their configured state for a
communication fault.
The communication loss is temporary. Communications restore themselves.
To prevent this situation, use 1756-CNB/D/E or 1756-CNBR/D/E modules.

Publication 1756-UM523F-EN-P - September 2006

If You Have Series B ControlNet Bridge Modules

Restriction

Description

If the Lowest Node Is a 1756-CNB/B


or -CNBR/B Module, Removing a Tap
or Breaking a Cable Could Stop All
Communications over the Network

If the lowest node on a ControlNet network is a 1756-CNB/B or 1756-CNBR/B module, all


communications over the network could stop if:

179

a tap to the 1756-CNB/B or -CNBR/B module is disconnected or breaks and then is replaced
while power is still applied to the 1756-CNB/B or -CNBR/B module
If a tap to a 1756-CNB/B or -CNBR/B module becomes disconnected or broken, take these actions:
1. Turn off the power to the 1756-CNB/B or -CNBR/B module.
2. Replace the tap.
If a communication failure occurs because of a disconnected or broken tap, cycle power to each
primary controller on the network.
To prevent this situation, use a 1756-CNB/D/E or -CNBR/D/E module as your lowest node on the
network.

Publication 1756-UM523F-EN-P - September 2006

180

If You Have Series B ControlNet Bridge Modules

Notes:

Publication 1756-UM523F-EN-P - September 2006

Appendix

Redundant System Restrictions

Proper Use of an
EtherNet/IP Network

For EtherNet/IP communication and messaging, keep the following


restrictions in mind:
IMPORTANT

In a redundant system, use an EtherNet/IP network only for


HMI/workstation communication and messaging.
Do not use an EtherNet/IP network for:
communication with I/O modules.
communication between devices via produced/consumed
tags.

Restriction

Details

Dont use ControlLogix5564 controllers.

You cant use this revision with 1756-L64 controllers.

Dont use 1756-CN2 modules in a redundant


chassis.

You cant use this revision with 1756-CN2 ControlNet bridge modules in a redundant
chassis.

Dont use equipment phases.

This revision wont let you download a project that has equipment phases or create
equipment phases online.

Dont use this revision to update a


revision 11 or earlier system.

Use this revision only if your redundant chassis are already updated to revision 13 or arent
in operation yet

Dont use the nonvolatile memory of a


ControlLogix5555 controller.

Dont use the nonvolatile memory of a 1756-L55M2x controller. This includes storing a
project to nonvolatile memory and loading it from nonvolatile memory. Otherwise the
controller will have an unrecoverable fault (solid red OK light) and clear the project from its
memory.
Lgx00068091

181

Publication 1756-UM523F-EN-P - September 2006

182

Redundant System Restrictions

Restriction

Details

Always keep the controller unlocked.

Make sure the controller stays unlocked.

Dont lock the controller.

A redundancy system automatically unlocks a locked controller during a switchover. But


the workstation that locked the controller doesnt show the change. The workstation
continues to show that the controller is locked even though it isnt. Once the controller is
unlocked, multiple workstations can edit the project in the controller.
Lgx00067869
Revision 2.6 or later of the SRM
configuration tool doesnt work with revision
11 or earlier systems.

Revision 2.6 or later of the 1757-SRM System Redundancy Module Configuration tool
doesnt work with revision 11 or earlier redundancy systems. You can cause the 1757-SRM
module to fault.
Use revision 2.6 or later of the configuration tool only with revision 13 or later
ControlLogix redundancy systems.
RSLinx software version 2.43 or later automatically installs version 2.6 or later of
the configuration tool.
To connect to a revision 11 or earlier redundancy system, uninstall the
configuration tool and install a compatible version. Use version 2.5 of the
configuration tool for revision 11 redundancy systems.

Make sure your ENBT modules are catalog

revision E01 or later.

To use a 1756-ENBT module in a redundant controller chassis, make sure its catalog
revision is E01 or later. Otherwise, the secondary chassis wont synchronize with the
primary chassis.
ControlLogix

Ethernet/IP 10/100

CAT. NO./SERIES

CAT. REV.

1756-ENBT

E01

To find the catalog revision of a module,


look at the label on the side of the
module or box.

Catalog revision
Example: Use a catalog revision, such as E01, E02, or F01.

Publication 1756-UM523F-EN-P - September 2006

Redundant System Restrictions

Restriction

Details

For a series B controller with 1.7 firmware,


use a nonredundant chassis to update it the
first time.

Example

183

You just took the controller out of its box. Its label shows that it is a series B controller
with 1.7 firmware, as in the following example:.

1.7

F/W REV.

LOGIX 5563
PROCESSOR UNIT
CATALOG / SERIES

CATALOG REV.

1.7
PART NO.

1756-L63 B

In this case:
1. Put the controller in a nonredundant chassis.
2. Update the controller.
3. Put the controller in the redundant chassis.
Otherwise, the controller will have a an unrecoverable fault.
After you update it the first time, you can update it in the redundant chassis from then on.
Nonexample
The controller is already running in your system. You want to update it to a later revision.
In this case, leave it where it is and update it there.
Give an SRM module several minutes or
more to update.

It takes several minutes to update a 1757-SRM module and the module resets itself at
least 4 times. An SRM module with 3.37 or earlier firmware may become inoperative if
you interrupt the update process.

Wait until you see this box


turn green and say Update
complete.

If the update fails, leave the power on and try again. The update failed if you see:
Update Status window turn red and say the update failed.
OK LED on the SRM module is red flashing and the 4-character display is blank.
Wait at least 45 seconds after the redundant
chassis are disqualified before you try to
synchronize them

If your secondary chassis becomes disqualified or you manually disqualify it, do these
actions before you try to synchronize the chassis:
Make sure the synchronization status of the primary modules is full compatibility.
Wait at least 45 seconds before you give the command to synchronize the
secondary chassis.

Publication 1756-UM523F-EN-P - September 2006

184

Redundant System Restrictions

Restriction

Details

If you unplug the fiber optic cable between


the SRM modules, wait until they stabilize
before you reconnect it

If you unplug the fiber optic cable between the 1757-SRM modules, check the
synchronization status of the secondary SRM module before you reconnect the cable. Wait
until its status is secondary with no partner. You can reconnect the cable once the module
is in that state. Otherwise, the secondary SRM could fault with EA91 error.

Publication 1756-UM523F-EN-P - September 2006

Index
Numerics
1756-ENBT module
See ENBT module
1756-EWEB module
EWEB module
1756-HYD02 20
1756-L60M03SE 21
1756-M02AE 21
1756-M02AS 21
1756-M03SE 21
1756-M08SE 21
1756-M16SE 21
1757-SRC cable
lengths 32
1757-SRM module
See SRM module

A
auto-synchronization 65

B
BSL instruction 85
BSR instruction 85

C
change
CNB modules from series D to series E
131
chassis
assign a chassis as primary 15
install 47
clock
SRM module 61, 94
CNB module
4 character display 128
addresses during a switchover 19
connection 37
install 48
requirements 22, 31
statistics 127
usage 127
CNB modules
changing from series D to series E 131
communication
optimize 123
compatible software versions
redundant system 26
configure
controller 72

EtherNet/IP module 52
I/O 74
SRM module 55
connection 37
consumed tag
configure 74
controller
configure 72
connection 37
download project 98
install 48
nonvolatile memory 137
periodic task 126
program scan time 77, 79
project 69
requirements 22, 31
synchronize 53, 122
system overhead time slice 124
watchdog time 102
ControlLogix5555 controller 22
ControlLogix5561 controller 22
ControlLogix5562 controller 22
ControlLogix5563 controller 22
ControlNet network
assign addresses 37
general lay-out 30
guidelines 37
keeper signature 100, 110
redundant media 35
schedule 98
conversion
to redundant system 165
corrected anomalies
redundancy revision 15.56 27
crossload 16, 18
estimate time for 77

D
data
crossload 18
integrity 85
DeviceNet network
design 21, 33
disqualified
overview 16
troubleshoot 106
download 98

E
edit
edit online 18, 69
Publication 1756-UM523F-EN-P - September 2006

186

Index

edit session in progress


troubleshoot 111
ENBT module
addresses during a switchover 20
configure 52
requirements 23
enhancements
redundancy revision 15.56 26
estimate program scan time 77
EtherNet/IP network
alias topics 149
configure modules 52
design 21, 33, 40
guidelines 40
IP swapping 20
module requirements 23
proper use 181
without IP swapping 149
event log
export 119
interpret 113
event task 20
EWEB module
addresses during a switchover 20
configure 52
requirements 23
export
event log 119

F
FFU instruction 85
finalize
online edits 71
firmware
update 53, 140
firmware combinations
redundant system 14

G
Get System Value instruction 90, 171
GSV instruction 90, 171

H
HMI
configure tags 76
design guidelines 30, 34
optimize communication 123
switch between topics 149

Publication 1756-UM523F-EN-P - September 2006

I
I/O
configure 74
convert local to remote 165
placement 21, 33, 51
redundant power supplies 36
import
event log 119
inhibit a task 20
install
system components 45
IP address
assign 52
IP swapping 40
manage without IP swapping 149
what happens during a switchover 20
IP swapping
overview 20

K
keeper signature
check 100
update 110

L
load
project from nonvolatile memory 137

M
message
configure 76
instruction 76
send to SRM module 94
Microsoft Excel
import event log 119
motion 20
MSG instruction 76

N
NAP 16
network access port
restrictions 16
network update time
guidelines 37
nonvolatile memory
load a project 137
store a project 137

Index

O
online edits
during a switchover 18
finalize 71
plan for 69
operator interface
design guidelines 34

P
PanelView terminal
design guidelines 30, 34
periodic task 126
power supplies
redundant 36
primary chassis
assign a chassis as primary 15
produced tag
configure 74
program
finalize online edits 71
number of 79
program scan time
estimate crossload time 77
minimize 79
overview 18
project
create and maintain 69
download 98
edit online 18
load 137
store 137
project storage
storing while process is running 139
proper use
EtherNet/IP network 181

Q
qualify. See synchronize

R
REDUNDANCY object 171
redundancy revision 15.56
corrected anomalies 27
enhancements 26
redundant system
compatible software versions 26
firmware combinations 14
restrictions 181
remote I/O network

187

design 21, 33
requested packet interval 74
restrictions
redundant system 181
revision 13
updating system 142
RIO network
design 21, 33

S
scan time
See program scan time, task scan time
schedule a ControlNet network 98
secondary chassis
troubleshoot 106
SRM configuration tool
find the revision 57
open 55
SRM module
auto-synchronization 65
configure 55
enable program control 66
export event log 119
install 48
interpret event log 113
program control 66
send message to 94
set the clock 61, 94
synchronization status 63
synchronize controllers 122
status
of my redundancy system 90
store
project to nonvolatile memory 137
project to nonvolatile memory while
process is running 139
switchover
causes 15
data integrity 85
diagnose cause 106
run code after 91
test 63
trigger with MSG instruction 94
troubleshoot 106
what happens to network addresses 19,
20
what happens to online edits 18
synchronize
controllers 122
diagnose failure 106
overview 16
status 63
Publication 1756-UM523F-EN-P - September 2006

188

Index

synchronize controllers 53
system information
get 90, 171
system overhead time slice 124

T
task
event 20
inhibit 20
number of 126
watchdog time 102
test
switchover 63
test edits

Publication 1756-UM523F-EN-P - September 2006

finalize 71
what happens during a switchover 18, 69
troubleshoot
switchover 106

U
update
system that is already at revision 13 142
update firmware 53, 140

W
watchdong time 102
workstation
connect to a NAP 16

How Are We Doing?


Your comments on our technical publications will help us serve you better in the future.
Thank you for taking the time to provide us feedback.
You can complete this form and mail it back to us, visit us online at www.ab.com/manuals, or
email us at [email protected]
Pub. Title/ ControlLogix Redundancy System
Type
Cat. No.

1756-CNB/D, 1756-CNBR/D, 1756-ENBT, 1756-EWEB, Pub. No. 1756-UM523F-EN-P Pub. Date September 2006 Part No. 953030-15
1756-L55, 1756-L55M12, 1756-L55M13, 1756-L55M14,
1756-L55M16, 1756-L55M22, 1756-L55M23,
1756-L55M24, 1756-L61, 1756-L62, 1756-L63,
1757-SRM

Please complete the sections below. Where applicable, rank the feature (1=needs improvement, 2=satisfactory, and 3=outstanding).
Overall Usefulness

Completeness
(all necessary information
is provided)

Technical Accuracy
(all provided information
is correct)

How can we make this publication more useful for you?

Clarity
1
(all provided information is
easy to understand)

Other Comments

Can we add more information to help you?


procedure/step

illustration

feature

example

guideline

other

explanation

definition

Can we be more accurate?


text

illustration

How can we make things clearer?

You can add additional comments on the back of this form.

Location/Phone

Your Name
Your Title/Function

Would you like us to contact you regarding your comments?


___No, there is no need to contact me
___Yes, please call me
___Yes, please email me at __________________________
___Yes, please contact me via ________________________

Return this form to:

Allen-Bradley Marketing Communications, 1 Allen-Bradley Dr., Mayfield Hts., OH 44124-9705


Phone: 440-646-3176 Fax: 440-646-3525 Email: [email protected]

Publication ICCG-5.21- January 2001

PN 955107-82

PLEASE FASTEN HERE (DO NOT STAPLE)

PLEASE FOLD HERE

NO POSTAGE
NECESSARY
IF MAILED
IN THE
UNITED STATES

BUSINESS REPLY MAIL


FIRST-CLASS MAIL PERMIT NO. 18235 CLEVELAND OH
POSTAGE WILL BE PAID BY THE ADDRESSEE

1 ALLEN-BRADLEY DR
MAYFIELD HEIGHTS OH 44124-9705

PLEASE REMOVE

Other Comments

Rockwell Automation
Support

Rockwell Automation provides technical information on the web to assist you


in using our products. At http://support.rockwellautomation.com, you can
find technical manuals, a knowledge base of FAQs, technical and application
notes, sample code and links to software service packs, and a MySupport
feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation,
configuration and troubleshooting, we offer TechConnect Support programs.
For more information, contact your local distributor or Rockwell Automation
representative, or visit http://support.rockwellautomation.com.

Installation Assistance
If you experience a problem with a hardware module within the first 24
hours of installation, please review the information that's contained in this
manual. You can also contact a special Customer Support number for initial
help in getting your module up and running:
United States

1.440.646.3223
Monday Friday, 8am 5pm EST

Outside United
States

Please contact your local Rockwell Automation representative for any


technical support issues.

New Product Satisfaction Return


Rockwell tests all of our products to ensure that they are fully operational
when shipped from the manufacturing facility. However, if your product is
not functioning and needs to be returned:
United States

Contact your distributor. You must provide a Customer Support case


number (see phone number above to obtain one) to your distributor in
order to complete the return process.

Outside United
States

Please contact your local Rockwell Automation representative for


return procedure.

Back Cover

Publication 1756-UM523F-EN-P - September 2006 2


Supersedes Publication 1756-UM523E-EN-P - May 2005

PN 953030-15
Copyright 2006 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like