Chillers Formulae

This document discusses how to calculate system flow requirements for selecting a pump. It explains that the flow rate in gallons per minute (GPM) depends on the building's heat load and the designed temperature change (delta T) of the fluid as it travels through the system. A formula is provided to calculate GPM based on the BTU load and delta T, with factors provided for water and common glycol mixtures. The document also discusses determining the heat load and typical delta T values for different system types, and includes tables of freeze/burst points for ethylene and propylene glycol solutions.

Uploaded by

burhan kathiria
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
281 views5 pages

Chillers Formulae

This document discusses how to calculate system flow requirements for selecting a pump. It explains that the flow rate in gallons per minute (GPM) depends on the building's heat load and the designed temperature change (delta T) of the fluid as it travels through the system. A formula is provided to calculate GPM based on the BTU load and delta T, with factors provided for water and common glycol mixtures. The document also discusses determining the heat load and typical delta T values for different system types, and includes tables of freeze/burst points for ethylene and propylene glycol solutions.

Uploaded by

burhan kathiria
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Calculating System Flow Requirements

To select a pump, we need to know the flow rate (the amount of fluid to be
pumped) and the system resistance or head. In the U.S., flow rates are given in gallons
per minute, or GPM. The GPM is a function of the heat loss (or gain) of the building
space served by the pump or the process load that is to be met by the pumped
systems. It is ALSO a function of the design temperature change of the fluid as it
travels through the hydronic system. The temperature change is commonly called the
Delta T, or T, where the triangle is the Greek symbol for the word Delta.
Heat Load
Determining the heat load of a building, a zone, or a process is beyond the scope
of this paper. Once a time-consuming manual procedure, computer software now
simplifies building load calculations considerably. You can download trial versions of
some software from the Internet.
Loads are expressed in British Thermal Units Per Hour, or BTUH. Other units of
measure are:
1. MBH = 1,000 BTUH
2. Tons = 12,000 BTUH (used for cooling applications)
3. Cooling tower tons = 15,000 BTUH*
*This term is used only when the tower serves an electric chiller or other
refrigeration system. In this application, the cooling tower must handle a building load of
12,000 BTUH per ton plus the compressor heat of about 3,000 BTUH/ton. 1 This is
conservative in light of todays chiller efficiencies, which often consume less than 3,000
BTUH/ton.
Design T (Design Temperature Drop)
The system designer determines what T he/she will use in the design. Normal
Ts for comfort systems are:

Heating Systems

Cooling Systems

Cooling Towers

20, 30, or 40 F

8, 10 or 12 F

10 Degrees

Note that these figures are only typical and are common in the HVAC industry.
For specific HVAC applications and many process applications, the chosen delta T might
be outside these ranges.
Assuming that the chosen fluid will be water, once the T is chosen, the GPM of
the pump can be determined by the following formula:
Formula 1: GPM = BTUH / 500 X T
Note that as the chosen T goes up, the GPM goes down. This results in smaller
pumps and smaller piping. However, larger Ts tend to result in larger terminal
equipment in the form of more rows of coil, more fan horse power, longer lengths of fin
tube, etc.
Note that the 500 factor in Formula 1 applies only to water. This is derived
from the formula BTUH = #/HR X BTU/# X T X S.H. where T is given deg-F and
S.H. is Specific Heat in BTU/#-Deg F. Note that #/HR of water = GPM X 8.33
#/GAL X 60 MIN/HR = GPM X 500; The S.H. for water = 1.0 at normal HVAC
temperatures. Combining these equations and doing the appropriate algebraic
substitutions yields Formula 1.
For hydronic systems, we often use glycol mixtures to guard against freezing
piping and coils that may be exposed to outside air. 2 These mixtures have different
densities (#/GAL) and different specific heats (S.H) than water. So for various glycol
mixtures, use the factors from Table 1 instead of 500.
For other fluids, the more general formula applies:
Formula 2: GPM = BTUH /(500 X S.G. X S.H. X T) where S.G. is the fluids
specific gravity.
1

Single stage steam absorption chillers require about 3.6 GPM/Ton and have a heat rejection of around
30,000 BTUH/ton. Two stage absorption chillers require about 3.6-4.0 GPM/ton and have a heat rejection
of around 22,000 BTUH/ton.
2
Freeze and burst temperatures for various concentrations of ethylene and propylene glycol are listed in
Appendix I at the end of this chapter.

TABLE 1
Load Factors for Propylene Glycol
Volume %
Temp. deg. F
20
40
60
80
100
120
140
160
180
200

10%
N/A
491.0
491.5
491.6
492.0
491.6
490.8
489.7
487.7
486.0

20%
481.7
482.8
484.0
485.1
485.6
486.0
485.5
485.1
484.4
483.3

30%
469.1
471.0
473.1
474.4
475.4
476.5
476.8
476.7
476.8
476.0

40%
453.3
455.6
458.1
460.3
462.2
463.7
464.4
465.2
465.7
465.7

50%
433.5
436.7
439.7
442.4
445.2
447.1
448.8
450.0
451.4
451.8

40%
428.7
432.2
435.4
438.2
440.8
443.1
445.2
447.3
448.7
449.7

50%
407.4
411.4
415.7
419.2
422.9
425.8
428.7
431.1
433.6
435.2

Load Factors for Ethylene Glycol


Volume %
Temp. deg. -F
20
40
60
80
100
120
140
160
180
200

10%
N/A
479.5
480.7
481.5
482.1
481.8
481.7
481.3
480.1
479.0

20%
464.4
466.3
468.4
469.7
470.8
466.4
471.8
472.5
472.2
471.6

30%
447.4
450.4
453.0
454.8
456.8
458.6
460.1
460.6
461.4
461.9

Once the flow rate in GPM is determined, the next step in selecting the pump is to
determine the head requirement. A discussion on this topic can be found as a separate
topic within the Technical Data section of this website.

Appendix 1---Freeze and Burst Temperatures for


Glycol Solutions

Note: Dowfrost products are propylene glycol based.

Note: Dowtherm products are ethylene glycol based.

Note: Dowfrost and Dowtherm are registered trademarks of the Dow Chemical
Company. The information above is from Dows 1996 Engineering and Operating guides
for their Downtherm and Dowfrost products and is included here for illustration.