ELECTRICAL REPORT

W.O. No.

64410

BILL TO:

McKeever Water Well & Pump Service Inc.


49024 Croquet Ct
Indio

REFER TO THIS NUMBER WHEN CALLING

SHIP TO:

CA 92201

P.O. No.

3/23/05

McKeever Water Well & Pump Service


82550 Avenue 60
Thermal
CA 92274

MARKS: Venos

Reqn/Rel.

Nameplate Data
Brand
Rating
Speed
Frame

CD=31-1/8" BX: 1-1/4"

Encl ODP
Auxiliary P-End Bearing: 7220
Type RU
Equipment 0-End Bearing: 6211
NRR complete
Nameplates
Model 6233
Ser. No. T04S277RO57R-4 (mfd April 1990)

US VHS Motor
60 HP
1775 (1800) RPM
364TP WP1

Data As found
AC Volts 460 PWS 6-lead
AC Amps 74.3
Rotor Data

As returned
460
74.3

Photo as rec'd
Cause of Failure or Reason for Service
The windings tested as shorted, but not shorted to ground. Winding insulation
resistance to ground was 50+M. The lower (i.e., O-end) bearing housing was
worn oversized and the keyways in the quill bore and shaft were worn
oversized.

What was Done


Assess core per EASA Tech Note #17; rewind stator with QuadCoat wire; VPI; epoxy-dip and bake to cure; measure brg hsgs
and shaft jrnls and compare to ABMA Std 7 k5 and H6 fits; install bushing into worn O-end brg housing and remachine;
machine oversized keyways into shaft and quill bore; fit special keystock; dynamically balance rotor; replace bearings, oil
sight glass and fill plug; reassemble and test.
AC Stator Winding Tests (as connected at high voltage; if multi-speed 1-winding, then test at high-speed)
Resistance
, A
As rec'd : Wdg 1
As left : Wdg 1 0.1723
As rec'd : Wdg 2
As left: Wdg 2

, B

, C

0.1726

0.1720

As rec'd
After bake
After rwd
Final

Surge results /Init


No Good at 2kV

Hipot VDC; A

Stator Polar-Index

OK to 4kV
OK to 4kV

2200vdc .1A BK
3280vdc .1A JS

Winding Insulation Resistance to Ground in Megohms

As rec'd
After bake
Final
Device

Stator
50+M
2000M
2000M

Initials
JH Sr
JS
JS

Megger

DC High-pot

AC High-pot

1000 vdc

Squirrel cage rotor test, incoming


No-Load Run Test After Repair

A- B
B-C
C -A
Armature
Shunt

Volts
460
460
460

A
B
C

500 vdc

9000 vdc

2000 vac

If Vertical,Axial endplay final 0.007


Connected for

Amps
23.0
23.0
23.0

460

Lubricant O- endMobil Polyrex EM


Vibration Amp, mils
P - end
O - end
.26
.10

Horizontal
Vertical
Axial
.12
Meas. RPM
1800
Squirrel cage rotor test, final

2500 vac

Initials

JS

P-end Shipped dry

Vibration Vel., in./sec.


P - end
O - end
.030
.018

Brg Temp
hrs.
F P-end
F O-end

.014
LV
115 VAC OK per LV

Initials