Comfort Control Principles
Comfort Control Principles
Comfort Control Principles
50 '-_
Comfort
Control
Principles
Zone 1
COMMERCIAL HVAC
SYSTEMS
Zone2
Zone 3
Load Estimating
Refrigeration Cycle
Applications
Air-conditioning systems maintain the desired indoor comfort level, starting with space ternperature. Other comfort parameters include maintaining acceptable room humidity, air motion, air
quality, and air purity. The relative importance of each system function depends upon the specific
project and application. Zoning is required to maximize the nurriber of spaces that are successfully conditioned to the design criteria,
..
.!T
There are many different types of HV AC systems, and many more elements that can be used
to achieve the heating and cooling capacity, provide ventilation, maintain humidity, distribute the
air within the spaces, etc. This module will discuss various temperature control strategies and
HV AC systems that can be employed to maximize comfort provided to the building occupants.
The information in thrs publication ISsubject to change Without ncdce. No part of this publication may be reproduced or transmit.
ted In any form or by any means. electronic or mechamcal. for arr{ purpose. without the express written permission of carrier
Corporation
Printed in Syracuse, NY
CARRIER CORPORATION
Carrier Parkway
Syracuse, NY 13221, U.S.A.
Table of Contents
Introduction
Zoning
3
4
4
5
6
6
6
Dampers
7
7
Valves
Fans and Pumps
Space Temperature Control Strategies
Room Sensible Heat (RSH)
Room Latent Heat (RLH)
Room Sensible Heat Factor (RSHF)
Cooling Coil Psychrometries
Simplified Psychrometric Diagrams
Fan Heat Gain
Return Duct Heat Gain/l.oss
Supply Duct Heat GainlLoss
Duct Leakage
7
7
8
8
8
9
10
11
12
12
12
12
13
14
on-off Control
Operating Characteristics
Psychrometric Analysis
Coil Discharge Temperature Control
Operating Characteristics
15
16
Psychrometric Analysis
16
Reheat Control
17
18
18
18
19
20
21
21
Single-Zone Reheat.
Terminal Reheat
Operating Characteristics
Psychrometric Analysis
Variable Air Volume (VA V)
Operating Characteristics
Psychrometric Analysis
,..:
:
Equipment Selection
Face and Bypass Control
23
24
24
Psychrometric Analysis
Equipment Selection
Hot and Cold Air Blending
Operating Characteristics
Psychrometric Analysis
Operational Variations
24
25
25
26
26
27
28
28
29
:;
30
30
3l
32
32
.,
33
34
34
34
35
37
37
38
Introduction
The primary function of an airconditioning system is to maintain the desired
indoor air quality, which starts with space
temperature. Other comfort parameters include maintaining acceptable levels of such
indoor environmental factors as relative humidity, air motion, air quality, and air purity.
Figure 1
Comfortstarts with space temperature.
Fo II Waf!' II'" BCY1y'
ConduclIOn -.---------Convection
Radiation
FOIl' Space
CQIldl1on:.. to Centro:
SUlface
Temperaturo
Air
Temperature
Relative
Humrdrty
Five of these additional parameters relate to the air system conditioning the space. This is because body
heat regulation, key to occupant comfort, relates to space conditions affected by the air system. The relative
importance of each parameter depends upon the specific project and
application.
CfllP
Tulfl'n'hrlI""
All
Water
Hybrid,
Air-Water
Induction,Face
and Bypass
Fan-Powered
Mixing Box
DirectRefrigerant
Duct-Free Spht
Packaged
Terminal Air
COnditioner
(PTAC)
Water Source
Heat Pump
(WSHP)
(FPMB)
Variable Air
Volume(VAV)
Figure 4
System choicesfor each type.
There are six basic space temperature control strategies, each with advantages.and disadvantages.
On-off control
Coil discharge temperature control
Reheat control
Variable air volume (VAV) control
Face and bypass (F&BP) control
Hot and cold air blending control
They define the operation of an air-conditioning system to adjust the cooling capacity that is
supplied to a space so that it equals the actual space cooling load at that moment. Control strategies used to maintain space temperature include such actions as: on-off equipment cycling, airflow (cfm) volume control, and waterflow (gpm) throttling control. Each control strategy performs differently, especially with respect to the resultant relative humidity within the space.
No HVAC system can use all the available control strategies for space temperature control;
some systems can use only one type of control, while others can be used with three or four different types.
fuon'olhrhl'rrh
The comfort performance of each type of HVAC system depends in part upon the type of
control strategy that is used and the system part load operating conditions. The HVAC designer
needs to first consider the required equipment capacity (do not oversize) and the building load
profiles that are likely to occur. Then select a control strategy that will provide reasonable perfonnance during the expected part load conditions. The preferred control strategy may not be
available with the preferred type of HVAC system or equipment. In such cases, the designer
makes a reasonable compromise of HVAC system type or equipment in order to provide acceptable part load comfort performance, paying particular attention to space relative humidity.
Zoning
Air-conditioning systems can be divided into individual control zones for several reasons.
The necessary zoning can be provided by using individual air-conditioning units for each zone, or
by using systems that are capable of providing multiple control zones from a corrunon air source.
The following basic zoning criteria must be carefully observed when selecting and laying out an
HVAC system for a building where multiple zones will be served by a central system.
A control zone
_J
Figure 5
Zoning Possibilities
eftd"
!!!
'11"'1"111(""'1)1""'
3
-----==-
COMFORT
--
CONTROL PRINCIPLES
--
Temperature
Control Zoning
The need for temperature control zoning should be investigated whenever several building
spaces are to be served from a comrnon HVAC system. Temperature conU'olzoning is necessary
whenever building areas do not share the same pattern of variation in cooling and heating loads. The
peak design loads may occur at different times of day
or in different months. This occurs in most buildings
between differing exposures because of the solar load
variability.
Exposure zoning is one form of temperature control zoning. During intermediate seasons, one space
may actually need cooling while another space needs
heating. If the central equipment is controlled by a temperature sensor located in the common
return air mixture from all of the spaces, the temperature in all of the spaces will likely be higher
or lower than the control setting, depending upon the relationship of the space load to the average
load of all of the spaces.
hlllltt.'h,.I,IU.h
_____________
_::C~O::...:._M:..:..:.F_;::O":..!..RT
CONTROL
r --.1:......:-.'<'! '-
".cn.l'L
- Geraa;
-._- J..-"n-t;8f7lFlEl;
-~--_~_
- - - Zone Boundary
--
0<;12pm
10r.._q 10)
seo Jpm
- 2r>.~
- -
PRINCIPLES
am
~ \'-"""'"
....
-S-'
l-i'()1
, 2pocok)
(41
\.;'-.[-a.
I_
~
(:{)
_,-
The choice of whether to use a separate unitary system for each zone or to serve many separate zones from a single larger central system is beyond the scope of this text. However, we 'will
discuss several considerations that affect this choice. A more detailed discussion is presented in
TDP-701, System Features and Selection Criteria.
________
lllrtlltllh,.)'I'C"n\.
= 0.69
= 0.75
Redundancy
Redundancy is defined as the ability of a system to continue to serve its loads during a failure. A unitary system with a separate air-conditioning unit to serve each zone is considered to
have good redundancy because the failure of a single unit does not affect the operation of any of
the other zones. For example, 90 percent of the building would not be affected by the failure of
one unit in a building with ten units, A central system can have more or less redundancy than a
unitary system. For example, the entire building is out of service during a failure if the entire
building is served by a single central unit. However, multiple central units can be provided. Two
or three units can be provided with a total capacity equal to the building peak load, and manifolded so that the central units serve all zones equally. Alternatively, three units can be provided
with each unit having a capacity of 50 percent of the building load, so that all of the zones can be
served at full capacity during a failure of anyone of the central units.
Heating Source
Air Handler
Cooling Source
Waterside Conduits
Constant Air
VolumeNariable Air
Temperature
Ventilation Source
Zoning
Filtration Source
Figure 8
System eletrenu: are controlled.
CD
nil" lu'htJ'lon"
Damper's
All-air and air-water (or hybrid) systems use many dampers, both at the air source and at the
zones, to adjust the airflow (cfm) as a means of changing the output capacity to match the need. Large
dampers are found in the mixing box
(return, exhaust/relief and outdoor air),
and coil (fuce and bypass) sections of
~
the air source (rooftop unit, central sta- IS ...'S I SI 'S'"Ad
II"
10
tion, or packaged). Out at the zone
OuldoorAIr Dumper 2-wayValve SolenoIdValve
FOil
level, .dampers are again found in the air
terminals or zone equipment 0f AV and
FPMB terminals, or fan coil and unit
ventilators ).
C7
Pump
Valves
VAV Terminal
lWayValve
EXV
Figure 9
On-off control
Coil discharge temperature control
Reheat control
Variable air volume 0f AV) control
Face and bypass (F&BP) control
Hot and cold air blending control
--.
All of these strategies can be used during either the cooling mode or the heating mode. This
discussion is focused upon the cooling mode.
The International Energy Conservation
throughout the United States has strict requirements relating to using any strategy that in effect
uses simultaneous heating and cooling. The designer needs to consult the enforced version of the
code in the jurisdiction of the project and review the code in detail. Building design for .commercial buildings needs to follow either the referenced ASHRAE 90.1 Energy Standardjor Buildings
Except Low-Rise Residential Buildings, or the related chapter in the IECC.
The space temperature control strategy discussions that follow are based on room sensible
and latent heat loads occurring within a zone on the following design day conditions, and at prot
load conditions that might occur on a cloudy summer morning.
RSH
RLH
RSHF
Design Load
8500
1500
0.85
3400
1500
0.69
Outside air conditions of 800 F dry bulb (loa), 730 F wet bulb (t' oJ, III grains/pound (Woa),
and a space design relative humidity (rh) of 50 percent. The ventilation outdoor airflow rate is 15
percent and the cooling coil bypass factor (bf) is 0.10. The performance of hot and cold air blending control is based on loa of 650 F db, and t' oa of 64.50 F wb, because the heating coil would not
normally be active at an outside temperature of80 F db.
Commercial
Turn ,,)c)I~L'''C'H'
_.;_ __
HVAC Systems
___________
9
-----------------~~
'11'11'"'1&.
I'I'
COMFORT CONTROL_PRIN_9IPLES
------_------_._---
assumed to be at the same conditions as the room air. The mixture (MIX) of ventilation outdoor
ail' (OA) and RA is on a straight line between the two points. The location of the MIX point is the
same proportion of the distance between the RA and OA points as the proportion of outdoor airflow to the total mixture airflow. This MIX state point is the condition of the entering air '(EA) to
the coil.
Many air-conditioning systems are located in moderate climates. The cooling coil selves to
cool the air to remove sensible neat and to dehumidify the air to remove latent heat, The cooling
and dehumidifying process requires that the surface of the coil be maintained at a temperature
below the dew point of the air entering the coil. As the air passes through the coil, it is first cooled
sensibly to the dew point temperature of the entering air. Moisture then condenses onto the coil
:fins as the air is cooled below the entering air dew point.
Some of the air that passes through a cooling coil is not exposed to the coldest coil fins. The
ail' that does not contact the coldest fins is called bypass air, and the percentage of Uris air is identified as the bypass factor (bf) of the coil. The amount of bypass ail' depends upon the configuration of the coil, including the number of rows and fins, and the degree of enhancement of the fin
surface by bending or corrugating the surface to increase the air turbulence.
The precise conditions of the air leaving a coil is usually calculated by complex computer
programs that provide ARI-certified ratings of the coil performance. Several simplified strategies
are used to represent and understand basic coil performance. One strategy is to assume that air
will leave the coil at a constant relative humidity (rh), which depends upon the coil configuration.
Air may leave a coil with relatively few rows and fins/inch at 80 percent I'll, whereas it may leave
a coil with more rows and finslinch at 90 percent or 95 percent rho
The other strategy uses the coil bypass factor and apparatus dew point. The apparatus dew
point (adp) is the temperature of the air leaving the coil that has been in direct contact with the
coldest fins. The bypass air is assumed to have no contact with the fins, so it leaves at the EA
conditions. The actua11eaving air is, therefore, a mixture of the air at the adp and the EA that bypassed the coil fins and tubes. We will use this strategy to show coil performance in this study.
The adp must be known in order to obtain the coil leaving air conditions. It can be calculated
by subtracting the enthalpy (611) that must be removed in the coil from the enthalpy of the entering air, hla, with allowance for the coil bf, as shown in the following formula:
hcoll = GTHcoil + (cfm
h
* 4.5)
- hea - hcoil
adp 1 _bf
The coil adp is at the intersection ofhadp with the saturation curve on the psychrometric chart.
The air will leave the coil on the mixture line between the entering air (EA or MIX) and the adp:
IlIltI ..,lh,I,\I"tMI'
10
_____________
----=C-=-.OMFORT
CONTROL
PRINCIPLES
The air leaving the cooling coil (LA) is assumed the same air that is supplied to the room
(SA). The capacity of the supply air to satisfy the RSH and RLH loads is:
RSH
RLH
If the coil selection does not satisfy the proper proportions of RSH and RLH, it will either
over-dehumidify or under-dehumidify the space. A coil that is selected for too high an adp will
result in the space humidity being too high. Remember, the coil airflow is dependent upon the
selec~ed adp, so a change in adp will result in a corresponding change in airflow.
Several adjustments can be shown on a psychrometric diagram to include additional system
details ofa specific application (Figure 12).
The work of the fan to create the system airflow is dissipated as heat into the airstream, which
warms the airstream from 0.50 F (for a very low pressure drop return air fan) to as much as 30 F
(for a high pressure drop supply fan). The amount of heat varies with the fan pressure and efficiency. Fan heat also includes the heat dissipated from the motor windings and the bell drive loss
if these items are located inside the fan plenum. The fan heat is shown as a temperature lise between the two points representing the fan inlet and outlet. Supply fans can be either a draw-thru
or blow-thru arrangement, described by whether the supply fun is located downstream of the coil
(draw-thru) and draws the air through the cooling coil into the fan. or whether the supply fun is
upstream of the coil (blow-throw) and blows the air through the coil. Draw-thru fan heat is represented by the line from the point leaving the cooling coil, tJa' tOtsa' which is the supply air to the
space. Blow-thru fan heat is represented by the line from the point representing the mixture of
return and outdoor air, lmix, to tea, which is the air entering the cooling coil. Return air fan heat is
usually represented by the line from the point leaving the space, tnt). to tra. which is the return air
condition at the connection to the outdoor and return air mixing plenum.
Kc
Condition
75 80 85 90 95 100130
Air Condition
120
@ Outdoor Air
Entering
@Mixture
ofOA&
RM
Air Condition
Figure 12
Psychrometric Plots, FWI and DuCI Heal Cains
_____________________________
lll1nl"II.-I,I><'"
11
----
-~
----------------,~-
Inward leakage of air into a duct at negative pressure is a mixing process, represented as a
point on a straight.line between the air conditions inside and outside the duct, 'withthe location of
the point determined by the percentage of air leakage. Outward leakage from a positively pressurized duct cannot be represented on the psychrometric diagram because the temperature and moisture condition of the air remaining in the duct is not affected by the leakage.
On-Off Control
This type of control consists of cycling the equipment. Figure 13 shows a typical air-handling
unit that could have either chilled water (shown) or aDX cooling coil. There are two options with
on-off control:
Fan
SupplyAlr
To Zone
Regardless of which option is used, on-off control has the advantage of being simple and inexpensive.
...;_
_
Commercial HVAC Systems
12
Operating Characteristics
The cooling load is usually less than the cooling capacity of the equipment. On-off cont.rol
systems balance the sensible cooling load to the equipment. capacity by cycling the equipment.
DUling normal operation. the space temperature gradually drops toward the off setting of the
space temperature control. When it reaches this point. the control stops the equipment until the
space temperature rises to the on setting of the space temperature control. which restarts the
equipment. The length of the on and off cycles is determined by the space load, the equipment
capacity. and the temperature differential between the on and off settings. The temperature difference of the space control settings must be large enough to prevent short cycling. which can be
damaging to the equipment. An altemative is to provide a timed cycling control to lirnit the frequency of control cycles.
A simplistic view of on-off control is that the cooling coil is always at design cooling temperature during the on cycle. and that no cooling is provided during the off cycle. The percent
operating time is then equal to the RSH (room sensible heat) load divided by the sensible cooling
capacity delivered to the space while the equipment is on.
In reality. the supply air dry bulb temperature is a periodic CUlve.as shown in Figure 14. The
system starts at point A and begins to lower the temperature of the air leaving the coil. No dehumidification occurs until the coil sur- Cooling EqUIpment APullc",B ~1>On~
( ~~1 0
A
face temperature drops below the enCyc'!!S
~p,,:7i:-::H~__;;''':-:''''='=i':':'4)--f-~~'r-~.-I
tering air dew point. The coil leaving
80
\
air temperature continues to drop until
point B. where the equipment capacity
~
is in balance with the load imposed by
~ 70
~~,~~e\
the coil entering and leaving air con"
ditions. A-B is the pulldown portion
:?i
60
E
Cooling Equipmonl
of the operating cycle. The pulldown
~
Coolin!) con
Cycles Olt
cycle can be relatively short if the coil
LeaVing AIr Temp
50 '-------------did not wann up during the previous
T,me'"
off cycle. and quite long if the coil is a
chilled water coil with a much greater Figure 14
mass of coil and water to be cooled.
Titre- Temperature Graph, OttOJ!Coniroi
""'$~
On"
-_
.------h-\_----l-
J -
B-C is the normal operating portion of the cycle. The coil leaving air temperature will gradually drop during this stage because the entering air temperature and moisture content will drop as
the space temperature and humidity gradually drop. Stage B-C continues until the space temperature drops to the off point of the space temperature control. which will take longer when the space
cooling load is a greater percentage of the equipment capacity,
Most systems. especially the residential type. can be arranged to cycle the fan and the cooling coil in unison. with a
fun delay on the off cycle to improve the system efficiency.
In this case. the space temperature control simply waits until
tile space temperature rises to start another cycle. Commercial systems are usually arranged to operate the supply fan
continuously with the outdoor air damper remaining open
while the compressor is off This results in a residual stage CD of the cycle. The cold coil surface is warmed by the flow
of return and outdoor air across the coil. The moisture that
had condensed on the coil surface. but not dropped into the
Commercial HVACSystems
____________
13
6J'It+
h,,,".
ll1t1lloll.r
drain pan, is re-evaporated into the warm airstream and returns to the space where it increases the
space humidity. Once the moisture has re-evaporated, stage D-A is the remainder of the off cycle,
which lasts until the space temperature rises to the on point of the space temperature control.
Operating the fun while the cooling coil is inactive is beneficial in some respects, but harmful
in others. Constant room air motion and sound level are an advantage. In addition, the outdoor air
damper can remain open to provide code-required constant ventilation. The main disadvantage is
the impact on space humidity, which is usually 5 to 10 percent higher if the fun is operated continuously, due to the wet coil condensate re-evaporating into the space.
On-off control is attractive for many reasons. It is simple, inexpensive, and thermally efficient. Other than the poor humidity control discussed above, the disadvantages include the wide
temperature differential that may be necessary to minimize short cycling of equipment, intermittent sound level, and lack of ventilation and room air motion if the fan is also cycled.
Psychrometric Analysis
A typical psychrometric diagram plot of on-off control performance is shown here. The peak
load system design diagram is shown' dotted. The part load diag.ram lines at'e solid. At part load,
the room air conditions (RM) will become more humid. The outdoor air conditions (OA) will
probably be cooler and less humid, The coil entering air conditions (EA), tedlltewb, being a mixture of space return air (assumed to be at RM conditions) and OA entering the coil, will be cooler
but more humid. The cooling coil leaving air conditions (LA), tldlltlwb, will be warmer and more
humid, because the coil load is greater when the air entering the coil is more humid.
Key
75 80 85
90 95 100130
120 ~
110 ~
O'l
100 ?:
90 ~
80 '
70
:r:
l;::
60 '0
(I)
t
wb/dp OF....
50
b.(;)
ldboF-+45
a.
en
50 _55606570758085
Figure 15
Psychrometric Plot, OIl-OffCOIIJrol
Commercial
II,,",",I..-hl...
'''
14
-=-__
HVAC Systems
COMFORT
CONTROL
PRI NCI PLES
-,.-
For the time being, consider the cooling coil LA to be the same as the supply air conditions
(SA) into the room or space. The room sensible and latent loads are absorbed as follows:
RSH
1.1 0 * cfm.;
* percent
OT
Where:
trm
= Room
temperature, of
tsa
percent OT = Operating time percentage (room sensible heat load ..;-room sensible cooling capacity of the equipment while it is operating)
The diagram is in balance when the air leaving the coil will satisfy the room sensible and latent loads at part load conditions, and the equipment will produce the capacity to satisfy these
loads at the same operating conditions. A theoretical balance point at any prut load condition can
be found by using a spreadsheet to equate the loads and the equipment capacity, and iterating the
space condition until the loads and equipment are in balance.
On-off control is preferred for small capacity single zone OX equipment and for small capacity chilled water fan coil units. Large capacity constant volume OX units with multiple cornpressors and multiple refrigerant circuits are more likely to be controlled in multiple steps. When the
coil remains active while the compressor capacity is reduced by unloading or staging compressors, the control system behaves like a coil leaving temperature control with discrete steps. Some
DX units have multiple face-split coil refrigerant circuits that are cycled from space temperature.
This control behaves like a multiple step face and bypass control.
Room-type chilled water fan coil units can easily be provided with a two-position chilled water valve. Modulating chilled water valves should never be used with fan coil systems unless the
system includes a separate dehumidified ventilation air system to control the space humidity.
Outdoor
An Intake
Fan
....
Supply Air
To Zone
Figure 16
Air SOl/TeeComponents,Coil Discharge Tempera/lire Conirol
___________
11.."',.11.
15
-
-------
I"
COMFORTCONTROLP~R~IN~C~IP~L=E~S~ _
The primary advantage of this control method is constant airflow, which provides constant
outdoor air ventilation and air distribution. The room temperature can be very precisely controlled
if a modulating valve is used with a chilled water coil. The most serious disadvantage is the loss
of dehumidification, which results when the coil temperature becomes warmer at part load.
Operating Characteristics
This strategy is easily applied to constant volume air systems using chilled water coils. The
space temperature control positions a modulating chilled water control valve at the chilled water
coil to obtain tile supply air temperature required by the current room sensible heat load. Each
increment of decrease in RSH at part load results in a corresponding increase in the temperature
leaving the cooling coil.
Advantages of this control strategy include the following:
Modulating the coil discharge air temperature provides precise control of the space dry
bulb temperature,
Low energy consumption (c01!lpared to reheat or hot and cold air blending).
No additional space for the air source equipment (compared to face and bypass or hot and
cold air blending).
Psychrometr'ic Analysis
Assuming constant coil airflow, the dry bulb temperature leaving the cooling coil can be calculated as follows:
t1db
= trm
Key
@ Outdoor Air Condition
Figure 17
Psychrometric Plot. Coil Discharge Temperance
The cooling coil adp (apparatus dew point) and bf (bypass factor) determine the moisture
content of the air leaving the coil, as shown by point LA on the psychrometric diagram.
--------------------------~--
16
The space moisture content is calculated by adding the moisture content that is represented by
the room latent heat (RLH) load to the moisture content of the air leaving the coil:
Wrm- W1a + (RLH -;-0.69
* 1.10)
The space humidity of77 percent is determined from the psychrometric chart, using the calculated moisture content at the 75 F space temperature.
The space humidity is high because the moisture content of the air leaving the cooling coil
was increased when the coil valve operated to raise the dry bulb temperature leaving the coil. The
humidity performance of coil temperature control is so poor that it should not be used as the primary means of space temperature control in a humid climate. A high humidity override control
can be provided to add reheat, which will require the coil to operate at a cooler and drier leaving
air temperature. A better solution is to choose a different type of control.
For room fan coil systems, the recommended solutions are to provide a separate dehumidified
ventilation air system (dedicated air system) and to arrange the fan coil unit control valve for twoposition on-off cycling control. Face and bypass control is a preferred solution for constant volume air-handling units and unit ventilators. VAV control is the recommended solution wherever a
constant flow system is not required.
The coils of large systems with multiple coils can be controlled in sequence using modulating
chilled water valves. Each active coil will be a variable temperature control, but the inactive coils
will function as an air bypass control. The result is space humidity between that of coil discharge
air temperature control and coil face and bypass control.
This strategy is not generally applicable to DX coils. The refrigerant pressure (evaporating
temperature) in the coil can be modulated using a pneumatic signal to a refrigerant hot gas bypass
valve or a refrigerant suction line pressure regulator, though this is not done very often in comfort
applications. DX systems with multiple steps of compressor capacity serving a conunon coil provide increments of coil discharge air temperature control. The space humidity will generally be
somewhat better than for a modulating coil control because the coil leaving air temperature will
be colder for a few minutes of each cycle, thus providing a short period of better dehumidification.
Reheat Control
Reheat control starts with the coil discharge temperature control and adds a reheat coil(s) to
the system. The LA set point is established based on the desired space humidity, cooling the air to
a lower dew point than obtainable with space temperature set point. Because the air would be too
cool ~ormost RSH loads, reheat is needed to warm up the supply air to the spaces.
Reheat control provides maximum dehumidification capacity to the space at all times but is
wasteful of both cooling and heating energy. Its use is, therefore, restricted by most energy codes.
Site-recovered waste heat from refrigeration condensers or other sources should be investigated
as a code-compliant source ofreheat energy.
CD
Commercial HVACSystems
1ul'll .n.11e1"llI'"'
______________________________
17
----------_._
---'--__
Single-Zone Reheat
This type of control is arranged as shown. A heating
coil (reheat coil) is installed
downstream of the cooling
coil. The space temperature
control adjusts the temperature
of the air leaving the reheat
coil. The temperature leaving _
the cooling coil is either uncontrolled or controlled by a
sensor in the air leaving the
cooling coil. The system has a
single reheat coil to provide Figure 18
one large temperature control Air Source Components. Single-Zone Reheat Control
zone.
Fan
Supply Ail
~ToZol1e
Terminal Reheat
Another reheat strategy
uses a multitude of small zone
reheat coils to provide multiple control zones from a single
large cooling unit, as shown.
Terminal
Reheat,
Unit
Zone 1
Ii
Zone 2
.'
Zone 3
Zone 4
II
Figure 19
HVAC System Components, Terminal Reheat Control
Operating Characteristics
Reheat control can be provided on almost any air-conditioning system by installing a heating
coil downstream of the cooling coil, either inside the air-handling unit or in the supply duct leaving the air handler. It cannot be applied with ductless systems unless the unit is designed to accept
a heating coil in the reheat position:
The space temperature control modulates the output of the reheat coil located downstream of
the cooling coil to prevent the space temperature from dropping when the actual RSH is less than
the design RSH. Reheat control provides excellent control of space humidity throughout the entire load range from 100percent RSH to near zero percent RSH.
IHfIl,uftu
,p, ..,
18
Psychrometric Analysis
Figure 20 shows the typical system performance at part load. If the dry bulb temperature of
the air leaving the cooling coil (state point LA) is the same as at design load, the space relative
humidity remains at 50 percent at 40 percent RSH and 100percent RLH load.
The amount of reheat is:
The moisture content of the air leaving the cooling coil is found from the psychrometric
chart, with allowance for coil bypass factor. The actual room moisture content is calculated, from
which the room relative humidity can be obtained by use of the psychrometric chart:
Wnn = W1a + (RLH -;-0.69 * 1.10)
Key
@ Outdoor
Air Condition
Entering
Air Condition
75
80
@ Apparatus
Supply
-
90 95 100130
120 ~
110 ~
en
100 ;i.
90 :0
85
Dew Point
Air Conditions
'E
80 ::l
:c
70 a;:
o
60 '~
0.
50 (/)
/dp "F~tJ.?
Vlb/'
tdb F_ 45
50
55
60
Figure 20
Psychrometric Plot, Reheat Control
The cooling coil entering air conditions are found by mixing the proportions of outdoor and
retum air at their actual part load conditions. As mentioned earlier, the solution is an iterative
process, because the assumed space humidity affects the mixed air moisture content entering the
cooling coil, which affects the moisture content of the air leaving the cooling coil, which in tum
affects the humidity inthe space.
Contrary to some expectations, the cooling coil can experience a large reduction in load at
part load. Any reduction in room latent load causes a drop in space humidity, and a corresponding
drop in the moisture content of the mixed air entering the coil. Any drop in outdoor air temperature or moisture content is also reflected in a reduction in heat content of the air entering the coi I.
___________
19
Parallel
Fan-Powered
Mixing Box
,,
II-,
20
o perating
Characteristics
VAV control modulates the supply airflow at each zone to balance the room sensible cooling
loads. The reduced airflow requires less fan power than constant volume systems. There is no
reheat penalty as in reheat or hot and cold air blending systems. VAV systems are sized for the
system block load, not the sum of the zone peak loads; so whatever load diversity exists can be
used to downsize the ductwork sections feeding multiple zones. Any capacity (airflow) that is not
required in one zone is available for any other nearby zone. This can be viewed as a built-in
safety factor or allowance for future loads in sizing the system. When fed from a self-balancing
ductwork design. damper modulation is quiet and unobtrusive within the spaces. FPMB systems
coupled with DCV eliminate the IAQ issues of traditional VAV, and use of high efficiency ECM
motors reduces the energy penalty of the zone-level fans.
Psychrometric Analysis
Typical VAV system performance is shown at part load. In this case, the coil LA is assumed
constant and controlled at the design load set point. At 40 percent RSH and 100 percent RLH
loads, the supply airflow was reduced to 40 percent of the design flow. The space relative humidity increased to 58 percent.
The space airflow, cfinsa, was calculated as follows:
cfm.,
* (trm - tsa)
The moisture content at the space (state point RM) can then be calculated as follows:
Wrm = W1a + (RLH -:-0.69 * 1.10)
Key
75 80 85
90 95 100130
120 ~
.0
110 'is
CJ)
~QIo/
50 55 60 65
70 75 80 85
~
90 95 100
70
60
50
40
:r:
I.)
r.;:
'g
0..
C/)
Figure 22
Psychrometric Plot, YAY Control
___________
21
.,.
Tum".'lwl,I"n'
;-__
'.
Point EA, the condition entering the cooling coil, is found by mixing the proportions of outdoor air and return air at their actual part load conditions. If the ventilation air quantity is held
constant, the percentage of outdoor air will increase as the supply airflow is reduced.
In a VA V system. the outdoor airflow rate will be variable unless a positive flow control is
provided. In this case, we asswned that the outdoor airflow was constant at the design flow rate.
Without control, the outdoor airflow would be somewhat proportional to the supply flow, but
would be also influenced by the building exhaust systems and infiltration.
V AV control is limited by the ventilation air requirements in each zone. It is also limited by
the performance of the air distribution devices. Most ceiling diffusers provide reasonable comfort
with up to a 40 percent volum-e reduction. A few linear diffusers of superior design provide reasonable space coverage without drafts at up to a 75 percent volume reduction.
In dry climates, the useful volume reduction range
of a V AV system can be extended by resetting the supply air temperature upwards as the system airflow is reduced.
1111111111""1 '1"'"
22
Equipment
Selection
VAV control cannot be used unless the HVAC equipment fans and cooling system are designed to operate satisfactorily throughout the necessary range of supply airflows and cooling
loads.
Small DX packaged units can be
used successfully with special VAV
systems such as the Carrier VVT
(variable volume and temperature)
system, which limits the range of volume reduction that can occur.
VAV Rooftop
Figure 23
VAV Equipment Options
For all VAV equipment, the funs must be capable of operating satisfactorily throughout the
expected range of airflows and operating pressures. Small capacity forward-curved fans with discharge dampers are used on many lower pressure class systems 2 in. wg static pressure). Variable inlet vanes provide better operation with higher pressure class systems and those using
backward-curved or airfoil wheel funs. Electronic variable speed control provides the best control
and efficiency for all types of funs.
Return air and/or relief air funs are more difficult to apply with VAV systems, because they
must be arranged and controlled to operate in conjunction with the supply fan without overpressurization or under-pressurization of the building. A building pressurization analysis is necesS31Y to determine whether such fans are needed. RetlUTIand relief air fans are usually not necesS31Y, unless the system has extensive return air ductwork, and is provided with an outdoor air
economizer that is sized for 100 percent of the system peak load airflow. Then the large amounts
of outdoor air that are brought into the building to cool the building during mild weather, plus the
return ductwork static pressure, usually require removal by fans to avoid over-pressurization of
the building.
___________
hIlUI,I.t't "1
23
-------------------------
Duct to Zone A
Typical
Zone
Damper
and
Motor
Figure 25
Air Source Components, Millmone Face and Bypass Control
Commercial HVACSystems
..;;...,,-_
24
Dual-Duct
Dual-duct systems overcome these limitations by installing higher pressure/velocity class
ducts throughout the building from the cold air and bypass air plenum connections of the multizone unit, as shown here. A dual-duct mixing box is installed at each control zone. It mixes the
cold air and bypassed neutral
air. Dual-duct systems are
limited by the space and cost
of the supply ducts. Portions
of the cold ductwork can be
N
sized based on the diversified
peak block cooling airflows of
all the downstream zones. The
bypass duct can provide warm
air to heat the building during
Cooling
cold weather, as described
Coil
later under.blending control. It
is usually sized for 60 to 75
Figure 26
percent of the cold airflow.
HVAC System Components, Dual-Duct Face and Bypass Control
Operating Characteristics
Face and bypass control maintains humidity like VAV control, with the air distribution and
ventilation characteristics of all constant volume control strategies. Blow-thru multizone and
dual-duct air blending systems provide face and bypass control when their heating coils are inactive.
The space temperature control modulates the amount of fan discharge air that passes through
and around the cooling coil. The coil airflow is roughly proportional to the percentage of RSH
load. The bypass airflow percentage is the inverse of the coil airflow, so the fan airflow is roughly
constant. Most bypass dampers have a leakage rate of 5 to 10 percent, so the fan design airflow
must be that much greater than the design coil airflow.
....
25
COMFORTCONTROLPRI~N=C~IP~L=E=S
_
"
Psychrometric Analysis
The part load psychrometric performance is shown here. The mixture of room air and outdoor
air entering the cooling coil at point EA is the same as for other systems. The portion of air passing through the cooling coil leaves at point LA, which is assumed to be at the same adp as the
design load. The air leaving the bypass damper is at point EA. The temperature of the supply air
mixture of cool coil air and neutral bypass air at point SA is calculated as follows:
= W1a + (RLH
+- 0.69
* 1.10)
Key
75 80 85
90 95 100130
120 ~
.0
110 =;::
(
100 ;:;.'
90 "'0
80
70 o
10::
~Qt.. /
tdb F~ 45
'
.)'9'
50 55 60 65
70 75 80 85
60
'u
Cl)
50
C/)
a.
40
90 95 100
Rgure27
Psychrometric Plot, Face and Bypass Control
The space humidity is approximately 64 percent rh at the pan load condition. This is considerably better than the 77 percent I'll, which would result if coil discharge temperature control were
used, but not as good as the 58 percent rh, which would result with VA V control.
In most climates, resetting the cooling coil t1a (and the adp) upwards at part load will result in
unacceptable space humidity, In humid climates, the part load performance is improved by letting
the adp drop several degrees as the bypass damper is opened.
Equipment Selection
Most face and bypass systems' are arranged to take bypass air from the outdoor and return air
mixing plenum. This bypasses some of the outdoor air around the coil, resulting in higher space
humidity than would otherwise occur. The air handler can sometimes be arranged to bypass 100
percent return air, but this requires a separate bypass air filter bank with the associated cost and
space.
Cli+
...;;___
Commercial HVAC Systems
26
COMFORT
CONTROL PRINCIPLES
e-
To prevent ice buildup, the cooling coils ofDX equipment with face and bypass control must
be provided with multiple steps of capacity control and proper refrigerant circuiting, similar to
that required for DX-VAV cooling coils due to the variable airflow through the cooling coil. As
mentioned previously, air-handling units with multiple cooling coils can be controlled so that one
cooling coil is completely inactive before the capacity of the next cooling coil stage is reduced.
The result is similar to that of single-coil face and bypass control with discrete steps of refrigeration capacity.
Most SITk'1l1 DX packaged equipment is not designed for use with face and bypass control.
Central station air-handling units are usually available with an optional face and bypass zoning
damper assembly to provide a multizone system. The same unit without the zoning damper can
serve a dual-duct system, or two separate single-zone air-handling units can be provided to supply
the cold and neutral air ductwork.
___________
27
""",,"11.1
I,
o perating
Characteristics
This control strategy is similar to face and bypass control, except that a heating coil is installed in the bypass around the cooling coil, so that the cold air is cold with respect to the space
and the hot air is hot with respect to the space. Face and bypass OCClU"S when one of the two airstreams is neutral with respect to the space.
Psychrometric Analysis
The heating coil is usually-inactive during the peak cooling load, so the design load performance is the same as that for face and bypass systems. The typical part load performance shown
here is for an outside weather condition in which the heating coil is being operated to provide
humidity control for a critical application. The mixture of outdoor and return air at EA is the same
as with other systems. The airflow splits at this point, with one portion being cooled and dehumidified to a condition leaving the cooling coil at point CSA (cold supply air), and the other portion being heated sensibly to a condition at point HSA (hot supply air). The proper proportions of
these two airstreams are mixed to obtain point SA, which is the supply air condition that will absorb the RSH and RLH to maintain the required space condition at point RM.
Key
75 80 85
90 95 100130
120 ~
.0
110 1::
0>
100 &:90 U
80
70 ~
.c>:
\w/dp F.......b.~
t db F_ 45
50 55 60 65
70 75 80 85
60 Ti
Q)
50
0.
(J)
.)'}/'
40
90 95 100
Figure 29
Psychrometric Plot, Air Blending Control
Using the same example as-the previous strategies with a hot air temperature of 950 F results
in space humidity of approximately 54 percent r11.This is lower than any other control strategy
except reheat control.
Resetting the temperature of the cold airstream at point CSA affects the space humidity, with
a lower temperature producing lower space humidity. The temperature setting of the hot airstream
at point HSA also affects the space humidity by changing the proportion of cooled and dehumidified airflow. A warmer setting results in greater dehumidification, but more heating energy waste.
fU'"'IJ,lrvl
\1.r1"-
28
_____________
---=C'-=o:..:..:M.:.:.F~O:...:.....:...RT
CONTROL
PRINCI
PLES
Like face and bypass control, there is a tendency for the total system airflow to increase when
the airflowis divided through both cooling and heating coil paths, The fan motor must be selected
for the maximum flow condition unless automatic air volume control is provided. In addition, like
face and bypass control, most systems are arranged for both cooling and heating coils to be supplied from a common outdoor air and return air mixing plenum. This results in some of the high
humidity outdoor air passing through the heating coil into the space, thus increasing the space
humidity compared to what would occur if all of the outdoor air was directed through the cooling
coil, Custom air-handling units me usually arranged for 100 percent return airflow to the heating
coil, with all of the ventilation outdoor air directed through the cooling coiL
DX cooling coil limitations me similar to those for face and bypass control.
o peratioual Variations
Most hot and cold blending systems, both multizone and dual-duct type, are arranged with a
constant volume supply fan discharging into a plenum from which the air can enter either the
cooling coil or the heating coil. With hot and cold air blending control, it is generally not desirable to provide an outdoor ail' economizer cycle because most hot and cold mixing systems use a
common blow-thru fan to serve both ducts. The increase in heating load is usually greater than
the decrease in cooling load.
A waterside economizer, in which the cold outdoor air is used to provide chilled water for the cooling coil, is a much more effective type of economizer. A waterside economizer will provide chilled
water to cool the cold duct air without increasing the
heating load for the hot air duct. An even better alternative is to operate the refrigeration plant to satisfy the cooling coil load, with a heat recovery system to divert as much of the heat rejection as necessary to satisfy the heating coil load,
Hot and cold air blending is more energy efficient than constant volume reheat, but less efficient than any of the other control strategies. Therefore, its use is restricted by energy codes to
critical applications. Systems with heat recovery as described above me usually considered acceptable for almost any application,
Commercial HVACSystems
29
.,
Combinations
Each of the control strategies described above has unique advantages, but none of them. when
used alone, are perfect for all applications. A combination of several strategies can usually provide a system that will serve the needs of a proj ect better than anyone method.
F or example, the VA V control strategy is the most energy efficient option because it is the
only one that provides fan horsepower savings. VA V can be combined with face and bypass
when using a multizone or dual-duct system. or with reheat when using a single-duct multiplezone system. The result is a system that is more energy efficient and self-balancing than either
constant volume face and bypass or reheat, but without the air distribution and ventilation problems that can occur with full-range YAY.
Reheat control can be combined with either face and bypass or coil discharge air temperature
control to create a system that will provide constant airflow and positive humidity control without
as much energy waste as a constant volume reheat system.
The blow-thru multizone system shown in Figure 25 uses face and bypass of the cooling coil,
which provides good performance when all of the zones require cooling. However, many old
multizone systems have a single heating coil located in the bypass plenum that is activated whenever any of the zones require heating. The system operates with hot and cold mixing control during Uris mode, which is very wasteful of cooling and heating energy. Modem multizone systems
include a separate heating coil installed in the supply duct to each zone, sequenced with the zone
damper so that all of the air that is to be heated will bypass the cooling coil. Operation of the
heating coil for one zone has no effect upon the air supplied to the other zones.
lurulutl,.
"1"'1\------------------------------
30
The availability of a particular control strategy depends upon the design of the HVAC
equipment. in particular whether space is available at. the proper location within the equipment for
the necessary control dampers and heating coils. These components mayor may not be available
as accessory items for a particular item of equipment. It also depends upon code requirements
regarding energy usage and ventilation.
In comparison with the others, each control strategy has advantages and disadvantages with
respect to the responsiveness of temperature control, the space humidity that is likely to occur
during part load conditions, the amount of energy used by the operation of the control stJategies,
and the cost of the necessary control components and equipment arrangements.
these general reconunendations are appropriate for cl:ima1eswhere dehumidification of outdoor ventilation air is necessary:
On-off control is best for small packaged DX units and for chilled water fan coil units.
Coil discharge air temperature control is best for room-type chilled water fan coil units
that are provided with a separate preconditioned ventilation air system to maintain the
space humidity independently of the fan coil unit operation,
Reheat control is best for code-acceptable applications where the part load humidity cannot be adequately controlled by other strategies. Examples include process, healthcare,
and laboratories with specific relative humidity requirement, or large outdoor air quantities for ventilation or exhaust hood makeup,
VAV control is best for most office applications, especially with demand controlled ventilation. and reheat where code-acceptable .
Face and bypass control is best where constant airflow and ventilation are important, such
as meeting rooms and training rooms.
Hot and cold air blending control is an excellent alternative to reheat control for applications that cannot be served adequately by the other control strategies.
Finally, the availability ofDDC (Direct Digital Control) microprocessor-based control systems makes it relatively easy to combine several of the basic control strategies to fonn a hybrid
control sequence that will better serve the needs of a specific project.
__
Imu,u,',r
J,!lIfI1\.
32
-IL.
(No TranSil'llssion)
The same office on a top floor
will be different because of the addiW,nler
tion of the roof load, which may be
Indoor
DeSign
Design
either a cooling or heating load, depending upon the outside conditions.
Outside Temperature'"
Top floor interior zones may require
some heating throughout the day, de- Figure 32
pending upon the presence of a ceiling Interior Office Design Load
return plenum, a well-insulated roof,
and a large, constant lighting load.
Commercial HVACSystems
Summer
Design
Summer
Design
'1IIn .. l,h,
33
"I"
--'",
Latent Loads
The RLH load is due to occupants and to activities within the space such as cooking. These
latent loads are equally possible regardless of outside weather. The result is that the RSHF can
become very low at part load conditions in exterior zones, even though it is quite high at peak
load. This table shows the room sensible heat ratio for a typical perimeter office, at design load,
and at a part load condition that might occur on a cloudy summer morning.
.
Design Load
RSH
8500
RLH
1500
RSHF
0.85
3400
1500
0.69
A low RSHF load condition indicates the need for a cold dew point temperature, tadp. at the
cooling coil.
Control Strategy
Part load rh
On-Off
Coil Discharge Temperature
Reheat
Variable Ail' Volume
Face and Bypass
Hot and Cold Air Blending
64%
77%
50%
58%
64%
54%
These evaluations of part load humidity performance were based on the same conditions used
in the space temperature control strategy discussions.
Summary
Comfort is the primary design parameter for air-conditioning systems. Since space temperature is the foundation for determining occupant comfort satisfaction, control strategies for HV AC
systems should first focus on proper control of space temperature. Space relative humidity, especially under part load conditions, must be carefully reviewed when selecting control strategies for
the HV AC system design. Energy codes will limit the use of strategies that employ simultaneous
heating and cooling. Always utilize psychrometric plots of system part load performance to
evaluate the use of various central equipment and zone control strategy options.
hUHI... h,J'flof11\
34
GQMFQRTGQNTROL
Work Session
1. What is the most common comfort parameter used to control HVAC systems?
2. Zoning is used to group spaces with similar load characteristics. This maximizes comfort
Withoutproviding a thermostat for every space. What are tlu:eeconunon zoning methods?
a)
b)
c)
3. HVAC equipment capacity is modulated, or controlled, to affect a change in room temperature by controlling one of the three fluids listed below. After each, write in at least two controlled devices that would be used in an HVAC system to implement the control strategy.
a)
Air:
b)
Water:
c)
Refrigerant:
W.bichone of the eight psychrometric processes represents the actions of the space temperature control strategies presented in this TOP?
S.
6. Simple on-off control has many disadvantages created by the cycling of the fan; list the one
major benefit.
_-_._._._ .._----------
._.-..
._------------35
7.
Each space temperature control strategy has distinct advantages and disadvantages.
primary advantage (think feature) of the following strategies:
a)
b)
Reheat control:
c)
d)
List the
01AV) control:
8. Simultaneous heating and cooling strategies, best represented by reheat are not permitted by
Energy Conservation Codes in most applications. Name two or three applications that are
given exceptions, and for what reasons.
9. True or False? Cooling coil selection parameters, like leaving air temperature and/or airflow,
can be adjusted to meet both the room sensible heat and room latent heat loads.
10. Part load operation occms on many projects due to variation in load components. Name five
conditions that would affect load variations in the conditioned spaces.
a)
b)
c)
d)
e)
hl,,,Ul,h.
',t"'t"------36
, GQME.QET.G.9t-1TR.9L
PRINCIPLES
Appendix
References
Carrier Corp.
Variable Air Volume Sy&tems. 2005.
TDP-703 Book. Cat. No. 796-068
TDP-70) Instructor Presentation, Cat. No. 797-068
Rooftops, Levell: Constant Volume. 2005.
TDP-631 Book. Cat. No. 796-056.
TDP-63l Inst.ructorPresentation, Cat. No. 797-056
Demand Controlled Ventilation System Design. 2001
Cat. No. 811-10088.
ASHRAE
ASHRAE Standard 62.1 - 2004, "Ventilation for Acceptable Indoor Air Quality"
ASHRAE Standard 90.1 - 2004, "Energy Efficient Design of New Buildings Except Low-Rise
Residential Buildings"
'.
37
---------------
..-.
--
an
3. Controlled devices used in HVAC system to implement the control strategy are:
a) Air:
fan, outdoor air damper or VAV terminal.
b) Water:
pump, 2-way valve or 3-way valve.
c) Refrigerant:
solenoid valve or electronic expansion valve (EXV).
4. Six basic space temperature control strategies are:
a) On-off control
b) Coil discharge temperature control
c) Reheat control
d) Variable air volume (V AV) control
e) Face and bypass control
f) Hot and cold air blending control
5. Cooling and dehumidification
6. When the fan turns off after satisfying the cooling load, the wetted coil surface does not reevaporate the condensate into the supply air, raising space relative humidity.
7. Primary advantages:
a) Coil discharge temperature control: precise control of the space dry bulb temperature
using a modulating chilled water coil control valve.
b) Reheat control: maximum dehumidification capacity to the space at all times.
c) Variable air volume (VAV) control: variable airflow to multiple zones from a single
piece of central cooling equipment.
d) Face and bypass control: improved dehumidification performance from the central
cooling equipment during part load conditions.
8. Laboratories, healthcare, or process, for special pressurization relationships, crosscontamination requirements, or relative humidity needs.
9. True. A colder temperature leaving the cooling coil will provide more dehunudificauon
usually with greater energy consumption to produce the colder coil.
10. Conditions affecting load variations in conditioned spaces are:
a) Time of day and solar orientation of the space.
b) Outside weather conditions and solar cloud cover.
c) Occupancy of the spaces.
d) Usage of lights and internal equipment.
e) Scheduling of control set points.
Commercial HVACSystems
.....;;_
__
hUflltl.hrJ"" ..'
38
.. "., ..,g.QMEQRT
CQNTROL
PR.INqp~E;$
!.'; (,,'i'n'n!.~((:}
nt ~'f\!/\ (; ~:;V:.:..t:<~~~
1;':'
.........
"._
__
__
._
hUtcIlU",,.,'hltt
39
Prerequisites:
An understanding of human comfort parameters, air-conditioning equipment and systems, along
with fundamentals of load estimating and psychrometric properties of air-water mixtures. This
knowledge can be gained from TOP-102 ABCs of Comfort, TDP-103 Concepts of Air Conditioning, TDP-301 Load Estimating Level 2: Fundamentals, TOP-302 Load Estimating Level 3: Block
and Zone Loads, and TDP-201 Psychrometries Level 1: Introduction.
Learning Objec1lves:
In this module, participants will learn the skills and knowledge necessary to:
Identify the different space temperature and relative humidity control strategies.
Compare typical peak design operation and part load operation of the strategies.
Select the appropriate control' strategy, considering the building, application, and tradeofts.
Supplemental Materl aJ :
,:
Those who wish to build their knowledge in control of HVAC systems should consider the following related publications for their library:
TOPNo.
Book
Cat No.
Instructor CD
Cal No.
TOP-701
TDP-801
TDP-631
TDP-632
TOP-703
TDP-704
796-066
796-074
796-056
796-057
796-068
796-069
797-066
797-074
797-056
797-057
797-068
797-069
~
System Features and Selection Criteria
Controls, Level 1 Fundamentals
Rooftop Units, Level 1: Constant Volume Units
Rooftop Units, Level 2: Variable Volume Units
Variable Air Volume Systems
Variable Volume and Temperature Systems
Instructor Information
Each TOP topic is supported with a number of different items to meet the specific needs of the
user. Instructor materials consist of a CO-ROM disk that includes a PowerPoint'" presentation
with convenient links to all required support materials required for the topic. This always includes:
slides, presenter notes, text file including work sessions and work session solutions, quiz and
quiz answers. Depending upon the topic, the instructor CD may also include sound, video,
spreadsheets, forms, or other material required to present a complete class. Self-study or student
material consists of a text including work sessions and work session answers, and may also
include forms, worksheets, calculators, etc.
'.
Carrier Corporation
Technical Training
800 644-5544
www.training.carrier.com