FireFinder XLS Advanced Fire Alarm Control Panel Data Sheet A6V10238846 Us en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Data Sheet

Fire Safety Products

FireFinder XLS

Advanced Fire Alarm Control Panel

ARCHITECT AND ENGINEER SPECIFICATIONS


Standard / 2500-point-capacity
addressable fire-alarm control
panel (FACP)
Ability to network with other
FireFinder XLS systems
Powerful, easy-to-use programming
capabilities
Fully field programmable, via
Windows laptop PC

6", backlit LCD display

Global annunciation and control


capability

12 amps of system power


(expandable to 48 amps)
Numerous Relays: Alarm, Trouble,
Programmable, etc.
SureWireTM addressable-loop technology
Polarity-insensitive detection circuits
(patented)
Useful diagnostic LEDs on all cards
Supports FirePrintTM application-specific
detection

Intelligent / analog detection circuits:

Class A or Class B
Supports single-person Walk Test
Seismic certified

Multiple levels of password protection

Menu-driven operator commands


5000-event, history-logging capability
with on-line and off-line reports
Automatic environmental compensation
for smoke detectors
Alarm verification

Touch screen for maintenance


operations and function keys

Universal AC power input:


120VAC 240VAC @ 50 / 60Hz

Multiple command stations

User-friendly system interface

Multi-language display

Modular assembly
Supervised remote printer
32-character custom messages
Thermal strip printer
Security-device monitoring

( UL 1076 Listed)

Pre-alarm operation

Up to 3.0 amps (24VDC) per NAC

Sprinkler Supervision
Degrade-mode operation
User help screens
Coded outputs
Supported by all Fire Safety

UUKL Listed for smoke control


UL 864 9th Edition Listed & ULC Listed;

Management Stations

FM, CSFM & NYC Fire Dept. Approved

by device or zone

Logic-controlled output functions


Time-based-controlled output functions
Holiday schedule
City tie / leased line
200 notification-appliance-circuits
(NACs) capacity
Built-in strobe synchronization protocol
Supports pre-action, deluge and agent
releasing
Voice evacuation system (optional)
NEC 760 power-limited circuits

( UL 864 Compliant)

Intelligent interface to building / process

management systems
Operates as interactive peer with other
XLS or XLSV units in a XNET network
Distributed processing
Detector Sensitivity Readout / Printout

per NFPA 72

System Overview
FireFinder XLS is a microprocessor-based, advanced
life-safety system that has a 6" display and large, lighted
buttons; making it a highly intuitive fire-alarm user interface.
Through the use of the unique multiprocessor Network
design along with the ability to utilize analog and
conventional detection devices FireFinder XLS
exemplifies a flexible and configurable life-safety system.
FireFinder XLS is ideally suited for commercial, institutional
and industrial fire detection and notification applications.
This FACP complies with the requirements of NFPA Standard
72, and is listed by Underwriters Laboratories under their
UL 864 standard. Underwriters Laboratories of Canada
also lists FireFinder XLS FACPs under ULC-S527.

FireFinder XLS is Factory Mutual (FM #3010) Approved; as


well as California State Fire Marshals (CSFM #71650067:0222) and NYC Fire Department (#6160) Approved.
Additionally, FireFinder XLS is UL Listed under the category
UUKL for smoke control.
FireFinder XLS is also UL Listed and FM Approved for
Sinorix clean-agent systems and pre-action or deluge
sprinkler systems, which include foam or water applications.
FireFinder XLS operates on the releasing requirements
specified in NFPA 13 and 2001.
FireFinder XLS is listed as a Fireman's Smoke Control Station
in high-rise office buildings, malls and other large structures.

FireFinder XLS System Overview


s Industry, Inc.
Building Technologies Division

6300

System Overview (continued)


The FireFinder XLS system has been seismic qualified
in accordance with:
International Building Code, 2006 Edition

California Building Code, 2007 Edition


ASCE Standard 7, 2005 Edition
OSHPD, OSP-0057-10
OSHPD CAN 2-1708A.5, Rev. 3
ICC-ES AC 156, effective 1/1/2007

System Components
A basic FireFinder XLS FACP consists of the following subassemblies: Person Machine Interface (Model PMI-2); Power
Supply (Model PSC-12); Device Loop Card (Model DLC); Zone
Indicating Card (Model ZIC-4A); Card cage (Model CC-5);
Inner Door Blank Single Plate (Model ID-SP); CAB-1, CAB-2 or
CAB-3 enclosures.
Optional modules that can be installed with this FACP
include: Card Cage (Model CC-2); Network Interface Card
(Model NIC-C); 8-Circuit Zone Indicating Card (Models ZIC8B / ZIC-2C); Control Relay Card (Model CRC-6); Output
Control Module (Model OCM-16); Switch Control Module
(Model SCM-8); LED Control Module (Model LCM-8); Fan
Control Module (Model FCM-6); Supervised Input Module
(Model SIM-16); Power Supply Extender (Model PSX-12);
Remote Network Interface (Model RNI); Remote Printer
Module (Model RPM); System Status Display (Model SSD);
Multi-Point Digital Alarm Communicator (Model MDACT);
Two-Module Remote Enclosure (Model REMBOX2); FourModule Remote Enclosure (Model REMBOX4).
FireFinder XLS is compatible with a full line of intelligent
initiating devices, highlighted by the FirePrint applicationspecified detectors: Models HFP-11 and HFPT-11. XLS
functions with the Siemens Fire Safety portfolio of graphics
command centers.

PM I-2 Person Machine I nterface 2

PMI-2 Person Machine Interface 2


The Person Machine Interface 2 (Model PMI-2) is the
primary user interface and central microprocessor for the
FireFinder FACP.
Model PMI-2 uses large, lighted buttons to prompt users as
to the next correct system operation that is available
(Acknowledge, Silence, Unsilence, Audible or Reset). From
each Model PMI-2 interface, the end-user can Acknowledge
events; control the system notification appliance circuits
(NACs), and reset the system. Detailed information about
the nature and location of the events can also be displayed.
The controller in Model PMI-2 provides all system logic and
supervision. Model PMI -2 contains a large (1/4 VGA), 6"
(15.2 cm.), 1200 x 800 pixel full-color liquid-crystal (LCD)
display, touch screen and LEDs for displaying system status.
A sound is made when there is any unacknowledged event
from Model PMI-2. The display is surrounded by keys that are
used to control the displayed information and to navigate
through these screens. Keys are also provided to obtain and
enter "Help" into the menu features of Model PMI-2.
Overlays -- available in Spanish, Portuguese and French -provide name in alternate languages for the text found on
the front of each Model PMI-2. Each overlay is assigned on
the outer assembly, respectively, when affixed to the
display on the user interface.
Each overlay assignment is intended for use in combination
with the run-time, alternate-language files found in the
custom-configuration software tool, Zeus.

Fire Safety Management Stations XLS Compatible

FireFinder XLS Compatibility with Siemens


Fire Safety Management Stations
FireFinder XLS panels are compatible with Siemens Fire
Safety Management Stations, which provide integrated
and reliable FACP monitoring and control of XLS system
events including: Alarm, Trouble, Security and
Supervisory commands.
Each management station includes PC-based, colorgraphics software designed for use with the XNET
network, offering full control and annunciation.
An extensive history log of all XLS-FACP events, as well as
extensive report-generation capabilities, is easily
maintained. Additionally, user-programmable function
buttons allow site-specific control functions.
s Industry, Inc.
Building Technologies Division

ZIC-4A Zone I ndicating Card

ZIC-4A Zone Indicating Card


The Zone Indicating Card (Model ZIC-4A) provides four (4)
fully supervised, programmable output circuits for use
on each FireFinder XLS. Model ZIC-4A supplies four (4)
Class B (Style Y) or Class A (Style Z) type output circuits,
power limited to 3.0 amps maximum per circuit.

FireFinder XLS Components (cont.d)


Each circuit for Model ZIC-4A can be independently
programmed for use with listed audible or visual
notification appliances; listed emergency audio speakers;
municipal tie boxes; leased lines, or as releasing circuits.
Model ZIC-4A plugs into one (1) slot in the Model CC-5 or
Model CC-2 card cage, and has on-board LEDs for system
status and troubleshooting.
Indication of power, communication, internal operation,
and ground-fault conditions are provided, as well as
indication of circuit activation or Trouble conditions.

ZIC-8B / ZIC-2C Zone I ndicating Cards

ZIC-8B / ZIC-2C
The Zone Indicating Card (Model ZIC-8B) provides eight (8)
fully supervised, programmable output circuits for use on
FireFinder XLS. Model ZIC-8B supplies eight (8) Class B
(Style Y) type output circuits, power limited to 2.0 amps
maximum per circuit. Each circuit can be independently
programmed for use with listed audible or visual notification
appliances, or listed emergency audio speakers. Model ZIC8B plugs into one (1) slot in the Model CC-5 or Model CC-2
card cage, and has on-board LEDs for system status.

NIC-C Network I nterface Card

NIC-C Network Interface Card


The Network Interface Card (Model NIC-C) provides HNET or
XNET network communications between enclosures. In
addition to the HNET or XNET communication, Model NIC-C
provides CAN network communication within an enclosure
or external to the enclosure. HNET or XNET communication
can be wired Style 4 or Style 7, but the CAN network can
be wired Style 4 only.
When used for HNET communications, Model NIC-C
provides communication between enclosures on a single
system.
When Model NIC-C is used for XNET communications,
Model NIC-C provides communication between systems.
The maximum of XNET Model NIC-C cards on a single
system (single node) is one (1), for a total of 64 XNET
Model NIC-C cards on a peer-to-peer networked system.
Model NIC -C has diagnostic LEDs that indicate: Card Fail,
CAN Fail, HNET Fail, XNET Fail, Ground Fault, Loop A Fail and
Loop B Fail. Model NIC-C Card also has LEDs to indicate
Power, Style and Active Networks.

Model ZIC-2C mounts directly on Model ZIC-8B, and


allows each of the Model ZIC-8B output circuits to be used
for two-channel voice applications. Indication of power,
communication, internal operation, and ground-fault
conditions are provided, as well as indication of circuit
activation or Trouble conditions.
HCP Control Point Module

DLC Device Loop Card

DLC Device Loop Card


The Device Loop Card (Model DLC) is the interface for
connection with FireFinder XLS detectors and initiating
devices including manual stations, control and input
devices. Model DLC plugs into one (1) slot of the CC-2 or CC5 card cage. Programming Model DLC is accomplished using
the FireFinder XLS system-programming tool, Zeus.
Model DLC takes one (1) address on the network, and
communicates with two (2) device circuits for a total of 252
detectors and devices. Model DLC has 12 LEDs for diagnostic
purposes, and provides ground-fault detection and zoneisolation circuitry.
s Industry, Inc.
Building Technologies Division

HCP Control Point Module


Model HCP provides an intelligent control point for the
FireFinder XLS. Model HCP can be programmed as an
independent, remotely located telephone zone,
speaker zone or notification appliance circuit. Model
HCP is designed to be used with the Siemens Fire
Safety Alarm Signaling Devices product line.
Model HCP communicates through the Model DLC
analog loop, and can be wired either Class A (Style Z)
or Class B (Style Y). The 24 VDC power input comes
from either the control panel or from any UL Listed
power-limited, auxiliary power supply.

FireFinder XLS Components (cont.d)

CRC-6 Controllable Relay Card


MLC MXL Line Card [for FireFinder XLS]

MLC - MXL Line Card [for FireFinder XLS]


The MXL Line Card (Model MLC) is an optional card for
the FireFinder XLS panel that supplies two (2)
intelligent analog circuits, utilizing the Model I series;
Model ID series; Model IL series or Model FP seriestype intelligent devices. Model MLC occupies two (2)
addresses on the HNET network, and devices connected
to the Model MLC circuits are dynamically supervised by
FireFinder XLS through the use of a unique
communications protocol.

CRC-6 Controllable Relay Card


The Controllable Relay Card (Model CRC-6) is used with
the FireFinder XLS FACP. Model CRC-6 is designed to
provide auxiliary control of building functions, such as:
door-holder release, elevator capture, smoke control, lock
release, etc. Model CRC-6 plugs into one (1) slot in the
Model CC-5 or Model CC-2 card cage. Model CRC-6
provides six (6), fully programmable relays. Each relay
contains one (1) set of SPDT contacts rated at 4 Amps 30 VDC
/ 120VAC resistive and 3.5 amps 120VAC inductive (0.6 P.F.)

SI M-16 Supervised Input Module


NRC Network Ring Card

NRC Network Ring Card Second Generation


Model NRC, which is the 2nd generation of Model NRC, is a
networking ring card that transmits single-mode or multimode network communication via fiber-optic or copper
lines. Each card uses a Class A (Style 7) ring configuration
for connection with each FireFinder XLS FACP.
One (1) Model NRC (per system node) provides XNET, peerto-peer communication between FireFinder XLS FACPs,
allowing a max, 64, XLS FACPs to be networked together.

SIM-16 Supervised Input Module


The Supervised input Module (Model SIM-16) is a
remotely located, general-purpose input module. Model
SIM-16 provides 16 input circuits for remote system
monitoring. Each input can be individually programmed
as supervised (dry-contact only) or unsupervised (generalpurpose input.) Model SIM-16 has two (2) Form C
relays. The relays and inputs are programmed using the
Zeus system software-programming tool.

FCM-6 Fan, Motor, Dampers Control Module


CDC-4 Conventional Detector Card

CDC-4 Conventional Detector Card


The Conventional Detector Card (Model CDC-4) is used
to monitor Siemens Fire Safety conventional detectors
on the FireFinder XLS system. Model CDC-4 can be
used in applications where conventional detectors are
more suited than addressable detectors, such as
hallways or large meeting rooms. Also, Model CDC-4
can be used to upgrade Siemens conventional fire-alarm
panels to the FireFinder XLS system without requiring
detector replacement.
s Industry, Inc.
Building Technologies Division

FCM-6 Fan, Motor, Dampers Control Module


The Fan, Motor, Dampers Control Module (Model FCM-6) is a
FireFinder XLS command-console option module that
provides manual control of building HVAC system fans,
motors, and dampers. Each Model FCM-6 module provides
six (6) sets of three (3) push-button switches for manualsystem control. Each switch has three (3), associated
LEDs to indicate Fan / Damper / Motor status: OFF (RED LED),
ON (GREEN LED), Trouble (YELLOW LED).

FireFinder XLS Components (cont.d)

CC-2 Card Cage-2 Slots

CC-5 Card Cage-5 Slots

CC-5 / CC-2 Card Cages


The Models CC-5 / CC-2 card cages provide the physical
mounting location and all wiring connection points for all
fire-and-voice system options cards for the FireFinder XLS
system. Model CC-5 has five (5) slots, while Model CC-2
has two (2) slots.
All cards plugged into the CC-5 / CC-2 card cage
communicate with other FireFinder XLS modules via a
common data bus. Connectors are provided on the left and
right side of the CC-5 to connect a 60-pin cable for
communications with the FireFinder XLS operator interface,
power supplies and amplifiers modules.
Field wiring to devices and circuits terminates on the
Models CC-5 / CC-2 card cages. All cards designed for use
with the Models CC-5 / CC-2 route their field wiring
terminations to the top of the Model CC-5 / CC-2 card
cages. These connections are all power limited. Internal
wiring connections distribute 24VDC to cards or high-level
audio signals (depending on application used) connect to
the bottom of the Model CC-5 / CC-2 card cages. These
connections are all non-power limited.
All wiring connections to the Model CC-5 / CC-2 card cages
are to removable terminal blocks. Terminal blocks are
rated for use with wire sized 12 American Wire Gauge
(AWG) to 24AWG. Each connector is numbered to make
wiring terminations to the correct position on the
terminal block simple in order to reduce potential wiring
errors.

Each Model SCM-8 switch is fully programmable, and may


be used to control speaker circuits and a wide range of
general-system functions such as: All Call, All Evac,
Warden's Page, Speaker, etc. Any number of circuits may
be grouped and controlled by a single switch.
Switch usages and zone groupings are assigned using the
Zeus system software-programming software. Model
SCM-8 modules are mounted on a hinged panel, as a part
of the FireFinder XLS Command Console enclosure.

LCM-8 LED Control Module

LCM-8 LED Control Module


The LED Control Module (Model LCM-8) is a FireFinder
XLS-option module that provides LED annunciation for
FireFinder XLS system activity. Each Model LCM-8
contains eight (8) groups of two (2) LEDs each of which
can be assigned to desired outputs using the Zeus
system software-programming tool.
Eight (8) LEDs are dual-color capable (Red or Green /
flashing or steady). The remaining LEDs are Amber
flashing or steady. A space is provided for labeling of LED
functions. The label slides behind a clear, protective
membrane. Model LCM-8 dimensions are identical to
Model SCM-8, and Model LCM-8 is mounted on the same
hinged panel, as a part of the FireFinder XLS Command
Console enclosure.

RN I Remote Network Interface

SCM-8 Switch Control Module

SCM-8 Switch Control Module


The Switch Control Module (Model SCM-8) is a FireFinder
XLS-option module that provides manual control to the
Emergency Voice Evacuation System (EVAC) or manual
fire-system control. Each Model SCM-8 module provides
eight (8) momentary push-button switches and 16
light-emitting diodes (LEDs) to indicate their status.
Each switch is assigned two (2) LEDs, as well as a label
to indicate the switch's programmed usage. The label
slides behind a clear protective membrane. One set of
LEDs assigned to each switch is a dual-colored LED,
which is used to indicate what type of signal is active.

s Industry, Inc.
Building Technologies Division

RNI Remote Network Interface


The Remote Network Interface (Model RNI) provides a
connection point for use with equipment mounted in a
remote-lobby enclosure on the FireFinder XLS FACP. Model
RNI is used to provide additional input, output and control
features to the system remotely, via the main FACP.
These additional features may include control switches
and indicators: (Models SCM-8, LCM-8 and FCM-6),
remote-emergency paging microphones or telephones:
(Models LVM, FMT), or controls used in graphic annunciators
(Models SIM16, OCM-16) or system-status display with the
ability to acknowledge alarms, silence audibles and
reset the system (Model SSD-C-REM).
Model RNI allows The Person Machine Interface to be
mounted in the Model REMBOX2 or Model REMBOX4
remote lobby enclosure.

FireFinder XLS Components (cont.d)

PSC-12 Power Supply Charger Module

PSC-12 Power Supply Charger Module


The Power Supply Charger Module (Model PSC-12) is a
high-current power supply that provides the FireFinder
XLS primary-regulated 24VDC power to operate. Model
PSC-12 is rated at 12Amps (Alarm) / 5Amps (Standby), and
has a built-in battery charger, capable of charging up to 100
AH batteries. Model PSC-12 is an addressable-intelligent,
microprocessor-controlled module that communicates its
status to the system-operator interface.
Each Person Machine Interface is then able to query the
status of the power supply to obtain data regarding
system-charging current, terminal-loading information,
ground-fault conditions and more.

PTB Power Termination Board

PTB Power Termination Board


Model PSC-12 comes packaged with a module called the
Power Termination Board (Model PTB). Model PTB is
required for operation with Model PSC-12. Model PTB filters
the power from the incoming AC mains, and distributes
it to the Model PSC-12 power supply and the optional Model
PSX-12 power-supply extender.
Model PTB has an optional connector that can be used during
system installation, commissioning and service to provide
the technician with a place to plug in their laptop PC, if
required. Model AC-ADPT is an optional accessory cable
that allows connection on one side to Model PTB, via a
keyed connector and on the other end directly into to the
laptop's transformer.
Most laptop-computer external power transformers have
removable AC power cords, which can be replaced by the
optional Model AC-ADPT to temporarily provide an AC
power source for laptop-PC usage during system
installation, service and maintenance calls when needed.

PSX-12 Power Supply Extender

PSX-12 Power Supply Extender


The Power Supply Extender (Model PSX-12) is a high-current,
auxiliary power supply that expands the main Model PSC-12
power supply and battery charger of the FireFinder XLS
system with an additional 24VDC power. Model PSX-12
is rated at 12 Amps.

TSP-40A Thermal Strip Printer

TSP-40A Thermal Strip Printer


The Thermal Strip Printer (Model TSP-40A) is designed for
use with the FireFinder XLS system. Model TSP-40A acts
as an event-logging device, providing a permanent
history report of all system activity.

RPM Remote Printer Module

RPM Remote Printer Module


The Remote Printer Module (Model RPM) provides a
means of connecting the FireFinder XLS system to a
printer, such as Model PAL-1, for creating a hard copy of
system status and configuration reports. Concurrently,
Model RPM provides an output port that can be
configured to communicate with external systems.

s Industry, Inc.
Building Technologies Division

Model TSP-40A mounts in the FireFinder XLS Model CAB


1, Model CAB2 or Model CAB3 enclosure, and its printout is
visible through a window in the locked-door enclosure.
Printouts are automatically spooled onto a take-up reel for
tidy, uniformed records storage.

FireFinder XLS Components (cont.d)


RNI Remote Network Interface

System-Status Display

SSD-Series System-Status Display


The System Status Display (SSD-series model displays)
is a remote LED / LCD display that shows the local status of
a FireFinder XLS system. An LED illuminates when
Alarm, Supervisory, Trouble, and Security events occur
on the system. A (4) four-line liquid-crystal display
(LCD) will give details of the event in alphanumeric
form.
The display can be toggled to display additional events.
Optional remote system control capabilities are
available.
Models SSD-C, SSD-C-INT, and Model SSD-C-REM have
three (3) additional control buttons to acknowledge
events, silence audible circuits, and reset the system.

MDACT Multi-Point Digital Alarm


Communicator Transmitter

MDACT - Multi-Point Digital Alarm


Communicator Transmitter
The Multi-Point Digital Alarm Communicator Transmitter
(Model MDACT) is used in FireFinder XLS systems where
point identification of Alarm, Supervisory, Security and
Trouble events is required at Central or Remote Receiving
Stations. An intelligent RS485 communications protocol
transmits all system information to Model MDACT.
The installer selects the specific event or groups of
events that are set to transmit from Model MDACT over
phone lines to listed receiving station equipment. In
turn, Model MDACT can transmit point information, via
the Ademco Contact ID and the SIA protocol. A mounting
plate (Model MOM2-XMP), MOM-2 card cage, and an XMI
Interface Card are required for installation.

IIC I nterface I solation Card

IIC Interface Isolation Card


The Interface Isolation Card (Model IIC) is designed to
isolate network signals when used with a Model NCC
ring configuration, via Model NRC. Model IIC executes
the aforementioned isolation by removing the
backplane network signals from each Model CC-2 card
cage. Model IIC also provides one (1) end of CAN
termination on each side of Model CC-2.
Models SSD-C and SSD-C-INT have an integral keyswitch
that enables these control buttons to operate. Model
SSD-C-REM is located within a locked cabinet.
Therefore, no additional keyswitch is required for
manual activation of the control buttons.

s Industry, Inc.
Building Technologies Division

CAB1 Single Row Enclosure

CAB1 Single Row Enclosure


Model CAB 1, the smallest of the FireFinder XLS
enclosures, can house a single Model CAB-MP cabinet
mounting plate for mounting card cages, power supplies
and bulk amplifiers. Model CAB1 also has four (4)
mounting slots on the inner door for mounting The Person
Machine Interface and Model ID-MP switch module
brackets.
Model CAB1 comes complete with a black back box; black
inner and outer doors; a single lock and key set on the outer
door; a single, installed cabinet mounting plate (Model
CAB-MP), and a single, installed outer door lens plate
(Model OD-LP). A red version (Model CAB1-R) is also
available.
Approximate size: 27" (68.6cm.) high, 26" (66cm.) wide,
and 8" (20.3cm.) deep.

FireFinder XLS Components (cont.d)

CAB-MP Cabinet Mounting Plate


The Model CAB-MP cabinet mounting plate provides
mounting for a single row of modules in a FireFinder
XLS cabinet. Four (4) module spaces are available on
Model CAB-MP, which is used to mount the Model CC-5
card cage; the Model CC-2 card cage; the Model PSC-12
power supply; the Model PSX-12 power-supply extender,
and the Model ZAM-80 / 180-zone amplifiers.

CAB2 Two-Row Enclosure

CAB2 Two-Row Enclosure


The Two-Row Enclosure (Model CAB2) is the mid-sized
FireFinder XLS enclosure capable of housing up to two
(2) Model CAB-MP cabinet mounting plates. The inner
door has two (2) rows of four (4) mounting slots.
The outer door has space for mounting two (2) outer door
plates (Models OD-LP, OD-BP or OD-GP), and can be
configured to open from either side. Model CAB2 consists
of the black Model CAB2-BB back box, the Model CAB2-BD
black inner and outer door package, and one (1) Model ODLP lens plate. The outer door has a single lock and key set
installed. A red version (Model CAB2R) is also available, and
a CAB2- RB back box is used with Model CAB2R.
Approximate size is 45 (114.3cm.) high, 26 (66cm.)
wide, and 8 (20.3cm.) deep.

Enclosure Trim Kits


Trim kits are available for all system enclosures for semiflush mounting applications. Model CAB1-TK (for black
enclosures) and the Model CAB1R-TK (for red enclosures)
fit inside the Models CAB1 and CAB1-R enclosures.
Similarly, Models CAB2-TK and CAB-2R-TK fit inside the
Model CAB-2 enclosure, while Models CAB3-TK and CAB3RTK fit the Model CAB-3 enclosure.
Remote Transponders
The FireFinder XLS system can use remote transponders
for mounting additional modules such as amplifiers
without requiring a Person Machine Interface or any
control switches. Special doors are available for systems
using Model CAB-2 or Model CAB-3 remote transponders.
These doors (Models CAB2-XBD and CAB3-XBD) omit the
unused inner door, and come complete with ventilation
louvers built into the door.
Model CAB2-XBD fits into Model CAB2-BB, and Model CAB3XBD fits into Model CAB3-BB. Model CAB2-XBD and CAB3XBD are supplied in black. Red versions (Models CAB2-XRD
and CAB3-XRD) are also available. Complete box and door
kits are available, Models CAB2-X and CAB3-X.

CAB3 Three-Row Enclosure

CAB3 Three-Row Enclosure


Model CAB3, the single largest FireFinder XLS
enclosure available, can house a maximum three (3)
Model CAB-MP cabinet mounting plates in the enclosure,
and three (3) rows of inner-door mounting slots.
The outer door can be configured to open from either
side. Model CAB3 consists of the Model CAB3-BB back
box, the Model CAB3-BD black inner and outer door
package, and one (1) Model OD-LP lens plate. The outer
door has two (2) locks and key sets installed. A red
version (Model CAB3R) is also available.
Approximate size is 63" (160cm.) high, 26" (66.4cm.)
wide, and 8" (20.3cm.) deep.

CAB-MP Cabinet Mounting Plate

s Industry, Inc.
Building Technologies Division

ID-MP I nner Door Mounting Plate

ID-MP Inner Door Mounting Plate


The inner door mounting plate (Model ID-MP) is mounted
on the inner door of any given model CAB enclosure.
Model ID-MP plates are used to mount switch-control
modules (Model SCM-8); LED control modules (Model
LCM-8), or fan-control modules (Model FCM-6).
Four (4) mounting plates are included with each order of
Model ID-MP. Each mounting plate has four (4) spaces for
control modules, and can hold either four (4) Model
SCM-8 modules (one [1] control module space for each
module); four (4) LCM-8 (one [1]control module space
for each module), or two (2) Model FCM-6 modules (two
[2] module spaces for each module).

FireFinder XLS Components (cont.d)


ID-MP Inner Door Mounting Plate
Combinations are also allowed. Blank spaces in Model IDMP can be covered using the blank-control-module
plate (Model BCM). Up to four (4) Model ID-MP
modules can be mounted in a single row on the inner
door.

OD-BP Outer Door Blank Plate

OD-BP Outer Door Blank Plate


The Outer Door Blank Plate (Model OD-BP) entirely
covers an unused row of a XLS system cabinet, and is
mounted on the outer door. One (1) blank plate is
included with each order of Model OD-BP.

I D-SP I nner Door Blank Single Plate

ID-SP Inner Door, Blank Single Plate


The inner door, blank single plate (Model ID-SP) is used
to cover any single-module blank spaces within the inner
door where no Person Machine Interface or Model IDMP is being used. Up to four (4) Model ID-SP modules
can be mounted in a single row on the inner door. Two
(2) blank plates are included with each order of Model IDSP.

BCM Blank Control Module Plate

BCM Blank Control-Module Plate


Model BCM plates can be mounted on a single ID-MP.
Four (4) blank module plates are included with each
order of Model BCM.

OD-LP Outer Door Lens Plate

OD-LP Outer Door Lens Plate


The Outer Door Lens Plate (Model OD-LP) is a clear plastic
lens plate mounted on the outer door of a system
cabinet. Model OD-LP is used to allow operators to see
the system interface and controls mounted on the inner
door, but restricts access to unauthorized users. The plate
covers an entire row on the outer door. A single lens
plate is included with each order of Model OD-LP.

s Industry, Inc.
Building Technologies Division

OD-GP Outer Door Grill Plate

OD-GP Outer Door Grill Plate


The Outer Door Grill Plate (Model OD-GP) also covers an
entire row on the outer door of a system cabinet, but has
four (4) rows of ventilation louvers on it. Model OD-GP is
mounted in front of system bulk amplifiers, card
amplifiers, or other modules that generate heat. Using
Model OD-GP will permit airflow across these modules to
aid in heat dissipation. One (1) grill plate is included
with each order of Model OG-GP.
Remote System Enclosures
Models REMBOX2 and REMBOX4 are FireFinder XLS
system enclosures that are used for remotely mounting
inner-door modules, such as: Person Machine Interfaces;
switch modules (Model SCM series); Live Voice Modules
(Model LVM), and Firefighters Master Telephone (Model
FMT) modules.
Models REMBOX2 and REMBOX4 are thinner than regular
Model CAB-series of enclosures just 5" (12.7cm.) deep
overall, and are perfect for mounting in limited-space areas
(e.g. office-complex lobbies or behind a receptionist's
desk).
No card cages, power supplies or bulk amplifiers can be
mounted in a given Model REMBOX-series enclosure due
to their smaller depth. However, Person Machine
Interfaces and some modules (e.g. the remote network
interface module [Model RNI]; the output control module
[Model OCM-16], and the supervised input module
[Model SIM-16]) can be mounted in a given Model
REMBOX-series enclosure.
Due to the depth of Models LVM and FMT, no Model OCM16 or Model SIM-16 modules can be used simultaneously
with Model LVM or Model FMT. Model REMBOX2 and
Model REMBOX4 are designed for flush mounting with no
trim kit required. Both enclosures also come with a clear
lens plate on the cover.

FireFinder XLS Components (cont.d)

REMBOX2 Two-Module Remote Enclosures

REMBOX2 Two Module Remote Enclosures


Model REMBOX2 has two (2) inner-door module spaces,
and can hold a single Person Machine Interface, up to two
(2) switch module brackets and one (1) Model LVM.
Combinations are also allowed.
Model REMBOX2 can also mount a single RNI remote
network interface on a bracket included in the backbox. A
bracket, known as Model REMBOX2-MP, can be used to
mount up to four (4) Model OCM-16 output control
modules or SIM-16 supervised input modules.

XLS-MSE2-ADPT Enclosure Adapter

XLS-MSE2/R-ADPT XLS MSE-2/R Enclosure Adapter


Model XLS-MSE2-ADPT, which must be used in conjunction
with Model CAB-MP, is an adapter that allows FireFinder
XLS cards to be mounted in older-generation MXL Model
MSE-2 small black enclosures.
Model XLS-MSE2R-ADPT, which must be used in
conjunction with Model CAB-MP, is an adapter that allows
FireFinder XLS cards to be mounted in older-generation
MXL Model MSE-2R small red enclosures.

Model REMBOX2-MP must be purchased separately.


Approximate size of Model REMBOX2 is 14-1/2" (36.8cm.)
wide, 18-1/2" (47cm.) high and 5" (12.7cm.) deep.

XLS-MME3-ADPT Enclosure Adapters

XLS-MME3/R-ADPT XLS MME-3/R or MBR-2


Enclosure Adapters

REMBOX4 Four-Module Remote Enclosures

REMBOX4 Four-Module Remote Enclosures


Model REMBOX4 has space for mounting four (4) inner-door
modules. Any combination of A Person Machine Interface
(two-module spaces); switch module brackets; Model
LVM, or Model FMT (one-module space each) can be
used. Unused module spaces can be covered with Model
ID-SP blank plates. Model REMBOX4 can also mount a
single, remote network interface (Model RNI) on a
bracket included in the backbox.
A bracket known as Model REMBOX4-MP can be used to
mount up to eight (8) output control modules (Model OCM16) or supervised input modules (SIM-16).
Approximate size of Model REMBOX4 is 24" (61cm.)
wide, 18-1/2" (47cm.) high and 5" (12.7cm.) deep.
Model REMBOX4-MP must be purchased separately.

Model XLS-MME3-ADPT, which must be used in


conjunction with Model CAB-MP, is an adapter that allows
FireFinder XLS cards to be mounted in older- generation
MXL Model MME-3 or Model MBR-2 medium black
enclosures.
Model XLS-MME3R-ADPT, which must be used in
conjunction with Model CAB-MP, is an adapter that allows
FireFinder XLS cards to be mounted in older-generation
MXL Model MME-3R medium red enclosures.

XLS-MLE6-ADPT Enclosure Adapter

XLS-MLE6/R-ADPT XLS MLE-6/R Enclosure Adapter


Model XLS-MLE6-ADPT, which must be used in
conjunction with Model CAB-MP, is an adapter that
allows FireFinder XLS cards to be mounted in oldergeneration MXL Model MLE-6 large black enclosures.
Model XLS-MLE6R-ADPT, which must be used in
conjunction with Model CAB-MP, is an adapter that
allows FireFinder XLS cards to be mounted in oldergeneration MXL MLE-6R large red enclosures.

s Industry, Inc.
Building Technologies Division

FireFinder XLS Components (cont.d)

XLS-MSE3-ADPT Enclosure Adapters

XLS-MSE3/R-ADPT XLS MSE-3L/R or MSE-3M/R


Enclosure Adapters

Model XLS-MSE3-ADPT is an adapter that allows


FireFinder XLS cards to be mounted in oldergeneration MXL-IQ Model MSE-3L or Model MSE-3M
black enclosure.
Model XLS-MSE3R-ADPT is an adapter that allows
FireFinder XLS cards to be mounted in oldergeneration MXL-IQ Model MSE-3LR or Model MSE3MR red enclosure.

XLS-RCC1-ADPT Enclosure Adapter

XLS-RCC-1-ADPT XLS RCC-1 Enclosure Adapter


Model XLS-RCC1-ADPT is an adapter that allows the
FireFinder XLS Model SSD/-C series remote annunciator
to be mounted in older-generation Model RCC-1 surfacemount enclosure.

VPM-MP VESDA Mounting Plate

VPM, VESDA-HLI-KIT and VMP-MP

VESDA Interface Equipment

The Very Early Smoke Detection Aspiration (VESDA)


Peripheral Module (Model VPM) and the VESDA HighLevel Interface Kit (Model VESDAHLI-KIT) are optional
FireFinder XLS modules that work in conjunction to
provide bi-directional communication between the
FireFinder XLS FACP and multiple VESDA detection
networks for the following types of VESDA detectors:
LaserCOMPACT
LaserFOCUS
LaserPLUS
LaserSCANNER
Model VPM allows each FireFinder XLS FACP to
annunciate Alert, Action, Fire 1, and Fire 2 levels,
as well as provide faults from any zone on a
connected VESDA network.
The VPM Mounting plate (Model VPM-MP) allows
mounting one (1) Model VPM and two (2) of Model
VESDAHLI-KIT inside a standard FireFinder XLS Model
CAB1, Model CAB2 or Model CAB3 enclosure. Model
VPM-MP utilizes two (2) module spaces on a single
row of each enclosure.

XLS-RCC13F-ADPT Enclosure Adapters

XLS-RCC13F/R-ADPT XLS RCC-1F/R or RCC-3F/R


Enclosure Adapters

Model XLS-RCC13F-ADPT is an adapter that allows the


FireFinder XLS Model SSD/-C series remote annunciator
to be mounted in older-generation Model RCC-1F or
Model RCC-3F black, flush-mount enclosure.
Model XLS-RCC13FR-ADPT is an adapter that allows the
Model SSD/-C series to be mounted in older-generation
RCC-1FR and RCC-3FR, red flush-mount enclosure.

C900V2 Dialer-Capture Ethernet Module

C900V2 Dialer-Capture Ethernet Module


The Dialer-Capture Ethernet Module (Model C900V2)
links the data output of Model MDACT from the
FireFinder XLS FACP to an Ethernet connection on a
local-area network (LAN) or wide-area network (WAN)
for communication to a central station over the Internet.
Model C900V2 also allows Model MDACT to be
optionally linked to the public switched telephone
network (PSTN) for communication to a central station
over telephone lines.

Temperature and Humidity Range


VPM VESDA
Interface Equipment

VESDA-HLI-KIT VESDA HighLevel Interface Kit

s Industry, Inc.
Building Technologies Division

FireFinder XLS components are UL 864 9th Edition


Listed for indoor dry locations within a temperature
range of 120+/-3F (49+/-2C) to 32+/-3F (0+/2C) and a relative-humidity range of 93+/-2% at a
temperature of 90+/-3F (32+/-2C).

Details for Ordering


Model

Part
Number

Details for Ordering (continued)

Description

AC-ADPT

500-633992

BCM

500-033320

C900V2
CAB-1
CAB-1R
CAB1-TK
CAB1R-TK
CAB2-BB
CAB2-RB
CAB2-BD
CAB2-RD
CAB2-TK
CAB2R-TK
CAB2-XBD

S54430-C13-A2
500-633007
500-633728
500-633013
500-633729
500-633009
500-634941
500-633008
500-633755
500-633014
500-633753
500-633768

CAB2-X

599-034252

CAB2-XRD

500-633792

CAB3-BB
CAB3-RB
CAB3-BD
CAB3-RD
CAB3-TK
CAB3R-TK
CAB3-XBD

500-633011 (3) Three-Row Back Box, black


500-634942 (3) Three-Row Back Box, red
500-633010 (3) Three-Row Inner & Outer Door set, black
500-633757 (3) Three-row Inner & Outer Door set, red
500-633015 (3) Three-Row Trim-kit Cabinet, black
500-633754 (3) Three-Row Trim-kit Cabinet, red
500-633769 CAB3 Transponder Door
Complete CAB3 w/ Transponder Door
599-034253 [no inner door]

CAB3-X
CAB3-XRD

500-633793

CAB-MP

500-633012

CCL

599-634214

Technician Laptop-Power connector


Blank control module plate,
[four (4) per package]

Dialer-Capture Ethernet Module


Complete Single-Row Cabinet, black
Complete Single-Row Cabinet, red
Single-Row Trim-kit Cabinet, black
Single-Row Trim-kit Cabinet, red
(2) Two-Row Back Box, black
(2) Two-Row Back Box, red
(2) Two-Row Inner & Outer Door set, black
(2) Two-Row Inner & Outer Door set, red
(2) Two-Row Trim-kit Cabinet, black
(2) Two-Row Trim-kit Cabinet, red
CAB2 Transponder Door
Complete CAB2 w/ Transponder Door
[no inner door]
Medium-Enclosure Transponder Door, red
[mounts to Model CAB2-RB]

Large-Enclosure Transponder Door, red


[mounts to Model CAB3-RB]

Back Box Module Mounting Plate


CAN Cable
3 ft. (91.4 cm.) Length required for:

CC-2
CC-5
CDC-4
COM-BRK
CRC-4
CSB
DCT-P
DLC

500-633440
500-633037
500-034200
S54430-B7-A1
500-033250
500-033130
500-699291
500-033090

FCM-6

500-033140

GPMI-UK

500-650066

SCM / LCM / FCM modules from Models CC-5 / CC-2

Inner Doors and from Row-to-Row on Model CAB-series


Inner Doors

Two (2) Slot Card Cage


Five (5) slot Card Cage
Conventional Detector Card
Communications Bracket
Controllable Relay Card
CAN Sounder Board
MDACT Programmer
Device Loop Card
Fan-Control-Module Switches
{ON, OFF, AUTO}

Software-Upgrade Kit for PMI (vers. 1)


{to allow global functionality}

S54430-C3-A1 Model PMI -2 [with GPMI-HW-KEY ]


500-034860 Intelligent Control Point Module
500-033170 Line-Isolator Module
Inner-Door Enclosure Mounting Plate,
500-633027

GPMI-2
HCP
HLIM
ID-MP

[four (4) per package]

ID-SP

Single-Module Inner-Door Enclosure


Mounting Plate, [two (2) per package]
500- 850328 Interface Isolation Card
LED Annunciator Module
500-033100 [eight (8) LED sets]
500-633028

IIC
LCM-8

Multi-Point Digital-Alarm
Communication Transmitter
MLC
S54431-B4-A1 MXL Addressable-Device Line Card
MOM2-XMP 500-634822 Mounting Plate for Model MOM-2
MXL Module Card Cage
MOM-2
500-892766 [one (1) full slot]
MDACT

500-699254

Part
Number

Model

500-033240 Network Interface Card

NIC-C
NRC
OD-BP
OD-BP-R
OD-GP-R
OD-GP
OD-LP
PAL-1

PMI-2

Description

S54430-A2-A1
500-633017
500-634919
500-634920
500-633018
500-633016
500-692407
599-050092
S54430-C1-A1

Network Ring Card: 2nd Generation


Outer Door Blank Plate
Outer Door Blank Plate, red
Outer Door Grill Plate, red
Outer Door Grill Plate
Outer Door Lens Plate
UL Listed Parallel Printer
PMI and GPMI
Person Machine Interface 2
PMI-2-SPAN-LAB S54430-C10-A1 Spanish Overlay for Model PM I -2
PMI-2-PORT-LAB S54430-C11-A1 Portuguese Overlay for Model PMI -2
PMI-2-FRENCH-L S54430-C12-A1 Canadian [French] Overlay for Model PM I-2

PSC-12

500-033340

PSX-12

500-034120

PTB
REMBOX2
REMBOX2R
REMBOX2-MP
REMBOX4
REMBOX4-MP
REMBOX4R
RNI
RPM
SCM-8
SIM-16
SSD
SSD-C
SSD-INT

Power supply with battery charger


[12A @ 24VDC]

Power supply extender


[12A @ 24VDC]

500-033390 Power termination board


500-633772 (2) Two-module remote lobby enclosure, black
500-650612 (2) Two-module remote
lobby enclosure, red
Mounting plate for Models
500-634211
OCM-16 / SIM-16 in Model REMBOX2
500-633914 (4) Four-module remote lobby enclosure, black
Mounting plate for Models OCM-16 /
500-634212
SIM-16 in Model REMBOX4
500-650613 (4) Four-module remote lobby enclosure, red
500-033420 Remote network interface module
500-033270 Remote printer module
500-033040 Switch module, eight (8) switches
500-034060 Supervised input module
500-034740 System-status display
500-648733 System-status display with control
500-034740 System-status display with
multi-lingual overlays

500-034750 System-status display with control


and multi-lingual overlays
SSD-C-REM
500-634773 System-status display with control for
remote lobby enclosure
TSP-40A
500-634933 Thermal-strip printer
TSP-XB
500-849949 Brackets for thermal-strip printer
TSP-XC
500-849950 Cables for thermal-strip printer
S54430-F93-A2 VESDA Peripheral Module
VPM
VPM-MP
S54430-F95-A2 Mounting Plate for VESDA
Peripheral Module
VESDA-HLI-KIT S54430-F99-A2 VESDA High-Level Interface Kit
XLS-MLE6-ADPT S54430-C9-A1 MLE-6 enclosure adapter for XLS, black
SSD-C-INT

XLS-MLE6R-ADPT
XLS-MME3-ADPT
XLS-MME3R-ADPT

XLS-MSE2-ADPT
XLS-MSE2R-ADPT

XLS-MSE3-ADPT

S54430-C9-A2 MLE-6R enclosure adapter for XLS, red


MME-3 and MBR-2 enclosure adapters for
S54430-C8-A1
FireFinder XLS, black
S54430-C8-A2 MME-3R enclosure adapter for XLS, red
S54430-C7-A1 MSE-2 enclosure adapter for XLS, black
S54430-C7-A2 MSE-2R enclosure adapter for XLS, red
S54430-C14-A1

MXL-IQ MSE-3L and MSE-3M enclosure adapters


for XLS, black

MXL-IQ MSE-3LR & MSE-3MR enclosure


adapters for XLS, red
XLS-RCC1-ADPT S54430-Z14-A1 RCC-1enclosure adapter for XLS-SSD, black
XLS-RCC13F-ADPT S54430-Z13-A1 RCC-1F & RCC-3F enclosure adapters, black
XLS-RCC13FR- ADPT S54430-Z13-A2 RCC-1FR & RCC-3FR enclosure adapters, red
XLS-MSE3R-ADPT

ZIC-2C
ZIC-4A
ZIC-8B

S54430-C14-A2

500-648671 (2) Two-channel adapter card,


via (Model ZIC-8B)
500-033050 (4) Four-circuit zone indicating card
500-648670 (8) Eight-circuit zone indicating card

Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each products installation instructions.

s Industry, Inc.
Building Technologies Division

Fire Safety
8 Fernwood Road
Florham Park, NJ 07932
Tel: (973) 593-2600
FAX: (908) 547-6877
URL: www.usa.Siemens.com/Fire

(SII-FS)
Printed in U.S.A.

Fire Safety
1577 North Service Road
East Oakville, Ontario
L6H 0H6 / Canada
Tel: [905] 465-8000
URL: www.Siemens.C A

April 2015
Supersedes sheet dated 1/2015
(Rev. 15)

You might also like