I-9105R

Intelligent Reflective Beam Detector


Installation and Operation Manual
(Issue 2.03February 2006)

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual

The Intelligent Solution

CONTENTS
I
II
III
IV
V

General................................................................................................................. 1
Features ............................................................................................................... 1
Technical Specifications..................................................................................... 1
Structure and Operation Principle ..................................................................... 2
Mounting and Wiring........................................................................................... 4
1. Ambient Conditions for Installation .................................................................... 4
2. Mounting Height and Position............................................................................ 5
3. Mounting............................................................................................................ 7
4. Wiring .............................................................................................................. 10

VI Commission....................................................................................................... 10
VII
Cautions ......................................................................................................... 12
VIII Operation........................................................................................................ 12
1. Reading Information ........................................................................................ 12
2. Setting Address Code ...................................................................................... 12
3. Setting Sensitivity Level................................................................................... 12
4. Setting the Device Type................................................................................... 13
5. Other Functions ............................................................................................... 13
IX Troubleshooting ................................................................................................ 13
X Maintenance ...................................................................................................... 15
XI Accessories ....................................................................................................... 15
Appendix 1 Warnings............................................................................................... 16
Appendix 2 Warranty................................................................................................ 17

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual

The Intelligent Solution

General

I-9105R Intelligent Reflective Beam Detector (hereinafter called the detector) is an


addressable reflective infrared beam smoke detector that can be connected with fire
alarm control panel directly, transmitting state information through loop between the
detector and control panel. The detector must be used together with a reflector. The
number of reflector(s) to be used (one or four) depends on the distance from the
detector.
With excellent built-in microprocessor, the detector has strong ability of analysis and
judgment. The detector can carry out system adjustment, compensation of variation of
ambient data, and judgment of fire and fault through fixed algorithm. Integrating
LONworks technology, the detector features high upload speed and abundant
information. With new and reasonable design, esthetical pleasing, flexible judgment and
alignment method its easy to install and adjust. The sensitivity of the detector can be
set through hand held programmer in field, decreasing the demand for cleanliness of
field conditions, and enlarging application areas. The detector is applicable to historical
buildings, warehouses, large storages, shopping malls, leisure centers, exhibition halls,
hotel lobbies, printing houses, clothing factories, museums and prisons, as well as
places where slight smoke particles.

II Features
1.
2.

Wide operating voltage range, big monitoring areas.


Combination of the emitting and receiving part makes mounting easy and optical
pathway accurate.
3. Built-in microprocessor enables intelligent judgment of fire alarm and fault.
4. The detector can calibrate automatically, which ensures a single person complete
adjustment in short time. Its also convenient to operate.
5. Self-diagnosis function can monitor the inner fault.
6. Automatic compensation for factors weakening received signals, such as dust
contamination, positional excursion and ageing transmitter.
7. Simple to control and operate by integrating LONworks protocol.
8. The address can be programmed in field.
9. Two sensitivity levels can be set in field.
10. The detectors optical pathway is designed with strong anti-interference ability.
11. SMT processing technology.
12. Attractive and decent appearance.

III Technical Specifications


1.
2.

Operating Voltage: Power voltage 15VDC28VDC


Loop voltage 15V28V
Operating Current:
Page 1

I-9105R
Intelligent Reflective Beam Detector
The Intelligent Solution
Installation and Operation Manual
Power current: Commission current20mA
Standby current8mA
Alarm current12mA
Loop current2mA
3. Angle of Adjusting: -6+6
4. Dependency Angle of Optical Pathway Orientation: 0.5
5. Sensitivity Level: Level 1: High sensitivity.
Level 2: Low sensitivity.
6. Indication of Detector State:
Commission: Green LED and yellow LED are lit or flash in a certain way. See
details in Section VI Commission.
Normal monitoring state: Red LED flashes periodically.
Fire: Red LED constantly illuminates, and yellow LED turns off. The fire signal has
to be cleared by the control panel, which turns on the detectors red LED in fire
alarm condition.
Fault: Yellow LED constantly illuminates. The detector clears the fault signal
automatically if the condition causing the fault disappears.
Optical pathway obscured totally: the detector first gives fault signal and turns on
yellow LED. 20 second later, it alarms fire again, and the control panel illuminates

7.

8.
9.
10.

11.
12.
13.
14.

its red LED and turns off yellow LED. Note: In this case, it does not necessarily
mean there is a fire. After the obscuration is removed, the detector clears the
fault signal automatically. Fire signal has to be cleared by the control panel.
Operating Environment:
Temperature: -10C+50C
Relative Humidity95%, non condensing
Monitoring Area: Maximum monitoring area: 141001400m2
Maximum width: 14m
Length of Optical Pathway: 8m100m
Ingress Protection Rating:
Under common environment, ingress protection rating is IP20.
Under special environment, ingress protection rating is IP66 through glue-seal
treatment.
Dimension: length: 206mm width: 95mm thickness: 95mm
Material and Color of Enclosure: ABS, gray
Weight: 450g
Mounting Hole Spacing: Spacing for embedding: 158mm
Spacings for surface mounting: 79mm96mm

IV Structure and Operation Principle


1. Appearance of the detector is shown in Fig. 1.

Page 2

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual

The Intelligent Solution

Receiving
Window

Emitting
Window

Wire-in Hole
Commission Zone
LEDs
Fig. 1 Appearance
2. Internal devices of the detector and positions to be glued are shown in Fig. 2.

To Be Glued
Mounting Direction

Adjusting Wheel

Rotary Rack

Flexible Cable
Reed Switch
To Be Glued
Fig. 2 Internal Devices and Positions to Be Glued
3. Operation Principle
The detector and reflector are placed oppositely. The detector includes emitting part

Page 3

I-9105R
Intelligent Reflective Beam Detector
The Intelligent Solution
Installation and Operation Manual
and receiving part. Infrared beam of certain intensity sent out from the emitting part is
reflected by the right-angle prisms of the reflector, and then received by the receiving
part of the detector. The receiving part simultaneously collects and amplifies the
returned infrared beam, analyze and judge the collected signals through its
microprocessor. When the detector is in normal monitoring state, the intensity of
infrared beam received by the receiving part is steady at a certain level. When smoke
particles enter the detecting area, the intensity of infrared light received by the receiving
part falls owing to light scattering. When the smoke particles reach a certain density, and
the intensity of infrared light received by the receiving part is reduced below the preset
threshold value, the detector alarms fire, illuminates red LED, and passes the fire signal
to the control panel. Operation principle is shown in Fig. 3.

Detector Body
Reflector
Smoke

Infrared
Beam
Mounting
Bracket

Fig. 3 Operation Principle

V Mounting and Wiring


1. Ambient Conditions for Installation
The detector works on light obscuration principle. Avoid any fixed or moving obscuration
in its optical pathway when installing.
The wall for mounting either the detector or the reflector should be firm and smooth. The
detector is mounted vertical to the wall. The wall may seem to be smooth, but
corrugated or uneven, or may be changed by the environment (in rainy season or in
winter) and the installer should ensure the detector not affected by these factors. If the
detector is installed on sustaining rack similar to metal tube, make sure the sustaining
rack fixed firmly.
Not Fit For Locations where:
Space height is over 40m.
It is not roofed.
Space height is less than1.5m.
There are a lot of dust, powder or vapor.
It is clean normally, but can be dusty in some special cases.
Page 4

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual

The Intelligent Solution

Temperature is high. Note: Temperature at top part of a workshop with


transparent roof may be over 50 when there is sunshine.
There is no access for maintenance.
The Mounting wall or fitting is greatly affected by mechanical vibration.
There are fixed or moving objects within 1m from the detectors optical pathway.
There is strong magnetic field.
2. Mounting Height and Position
The mounting height of the detector and reflector should be most accessible by smoke
into beam zone. The following recommendations are for reference:
1) When space height is not over 5m, the detector and reflector should be
mounted on the two facing walls 0.5m from the ceiling, see Fig. 4.

Reflector

4.5m

5m

Detector

Fig. 4 Mounting
2) When space height is between 5m and 8m, the detector and reflector should
be mounted on the two facing walls 0.5m to 1m from the ceiling, see Fig. 5.

Page 5

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual

The Intelligent Solution

Reflector

6m

7m

Detector

Fig. 5 Mounting
3) When space height is more than 8m, the roof is normally gabled without ceiling,
the detector and reflector should be mounted on the two facing walls about 8m from
the floor, ensuring that the vertical distance between the detector/reflector and top
of the building is more than 0.5m, see Fig. 6. The distance should be 7m from the
detector to the floor.

Reflector

8m

Detector

7m

Detector

Reflector

Fig. 6 Mounting
4) For gable structure with space height about 8m, the detector and reflector
should be mounted on the two facing walls 1.5m from the gabled girder, see Fig. 7.

Page 6

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual

The Intelligent Solution


Reflector

Reflector

8m

Reflector

Detector

Detector

6.5m

Detecor

Fig. 7 Mounting
5) If the surroundings are glass or transparent plastic, please place the detector
on the south wall in a building. If the detector cannot be mounted northward, then
place the detector on the west wall. For applications where sunlight can reach the
detector after reflected, please consider mounting a sunshade over the detectors
optical pathway or contact our field application engineer for a solution.
3. Mounting
1) Setting Length of Optical Pathway
Before installation, you need to set the length of optical pathway first by setting
device type of the detector. The detector can work at two levels of length. When
mounting distance between the detector and the reflector is not less than 40m (but
not more than100m), the detector type should be set at 52 (factory default). When
the mounting distance between the detector and the reflector is less than 40m (but
more than 8m), the detector type should be set at 51. See Section VIII Operation
for detailed setting methods.
2) Mounting the Detector
Align the detector and the reflector horizontally on the two facing walls in monitoring
area. See Fig. 8.

Page 7

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual

The Intelligent Solution

Fig. 8 Mounting
The detector can be surface-mounted in two ways: with wiring tube embedded or
wiring tube surface-mounted.
(1) Embedding wiring tube
a. Remove the detectors top cover.
b. Align the base of the detector over the embedded box and mark the
positions of mounting holes on the wall.
c. Drill two holes at the marked positions, and push two 6 plastic expansion
bolts in.
d. Thread the wires through wire-in hole, ensuring the length of wires inside
convenient for connection.
e. Fix the detector base on the wall with two plastic expansion bolts and flat
washers
Mounting method is shown in Fig. 9.
Plastic Expansion Bolt

Embedded Box

Fig. 9 Wiring Tube Embedded


(2) Wiring tube surface mounting

Page 8

I-9105R
Intelligent Reflective Beam Detector
The Intelligent Solution
Installation and Operation Manual
a. Put the mounting bracket at position intended to install the detector; mark
the locations of the four holes of mounting bracket on the wall.
b. Drill the holes on marked positions, and push 6 plastic expansion bolts
in.
c. Fix the mounting bracket on the wall with four 6 plastic expansion bolts
and flat washers.
d. Remove the detectors top cover; thread the wires through the wire-in hole,
ensuring the length of wires inside convenient for connection.
e. Fix the detector base onto the bracket with two M410 bolts and flat
washers.
Note: If there is strong magnetic or electric field, please connect the
metal mounting bracket of the detector with ground reliably to ensure
stable operation.
Mounting method is shown in Fig. 10.
Holes for Fixing
Detector

W ire-in Tube
B racket

Bracket
Bracket

P lastic E xpansion B olt

Fig. 10 Wiring Tube Surface Mounted


3) Mounting the Reflector
The reflector is mounted opposite the detector but in line with it. When the distance
between the detector and the reflector is more than 8m (less than or equal to 40m),
one reflector is enough. When the distance is more than 40m (less or equal to
100m), four reflectors are needed. Two 6 plastic expansion bolts are needed to fix
a single reflector. Mounting size is shown in Fig.11a. If four reflectors are needed,
place them seamlessly as shown in Fig. 11b.

Page 9

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual

Fig. 11a Single Reflector

The Intelligent Solution

Fig. 11b Four Reflectorsnot to scale

4. Wiring
Connect 24VDC power wirewithout polarityto terminal D1 and D2 of the detector in
field. Connect the control panel loop (without polarity) to terminal Z1 and Z2. The
reflectors need not to connect with wires. Terminals are shown in Fig. 12.

Z2

Z1

D2

D1

Fig. 12 Terminals
Wiring: BV cable with cross section not less than 1.5mm2 for power cable connecting
with D1 and D2. Twisted pair with cross section not less than 1.0mm2 for signal wires
connecting with Z1 and Z2.
Note: If the detector is mounted in special environment where there are slight
dust or where its damp, seal the three positions shown in Fig. 2 (two mounting
holes and one wire-in hole) with glass glue or 703 silica gel after the detector is
fixed and wiring is finished to ensure the detector work stably.

VI Commission
1.

Steps:
1) Take off the protective membrane carefully on the surface of the reflector and.
Do not scratch or contaminate their surfaces.
2) Remove the detectors top cover, and connect to 24VDC power and the control
panel power. Two minutes later, put the magnet of commission tool close to the
reed switch (around the red LED) of detectors interface board. There may be two
Page 10

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual
cases with the LEDs:
(1) Green LED flashes.
(2) Green LED illuminates continuously.
Take away the commission tool.

The Intelligent Solution

3) If green LED flashes, it means the received light is quite weak (the slower the
flashing frequency, the weaker the received light signal is). Tune the adjusting
wheel and rotary rack on the detector to align the light beam until green LED is lit
continuously, showing that the light received by the detector is strong. Then stop
regulating and enter step 4). If green LED illuminates continuously, it means the
received light is quite strong, you can go straight to step 4).
Note: Observe the detectors optical pathway carefully to ensure that the
received light signal is reflected by the reflector rather than by obscurations
like wall, ceiling, or pillar. If uncertain, verify by covering the reflector with
opaque objects.
4) Put on the top cover gently, and screw the two bolts on the cover.
5) The green LED illuminates continuously. Put the magnet of commission tool
close to the zone where marked M until yellow LED illuminates constantly, then
remove the filter quickly and make sure there is no obscuration on the optical
pathway. About 5 seconds later, the detector begins to adjust automatically. Yellow
LED flashing means weak light, green LED flashing means strong light. If red LED,
yellow LED and green LED flash alternately, this means the detector failed to adjust
automatically and cannot enter normal monitoring state. Please open the detectors
top cover and do adjustment from step 2). If yellow LED and green LED illuminate
no more, and red LED flashes periodically, this means the detector is at the best
position and has entered normal monitoring state. The commission is finished.
2.

3.

Registration
Register the detector, please see the details in the relevant control panels
installation and operation manual.
Fire alarm test
After the detector has been in normal monitoring state for 20 seconds, cover the
receiving window and emitting window with the IR Light Filter (please use the part
for fire alarm test), the fire alarm control panel should alarm fire in 30 seconds and
red LED should turn on. Remove the filter and clear the fire alarm from the control
panel, red LED should turn off and the detector should be in normal polling.

4.

Fault test
Cover the receiving or emitting window of the detector quickly with the IR Light
Filter (please use the part for commission) to obscure the optical pathway. Yellow
LED of the detector should be turned on. Taking off the filter immediately, yellow
LED of the detector should be turned off.

5.

Failed Detector
During testing, repair failing detectors according to directions in Section IX
Troubleshooting and X Maintenance, and test again, if they fail again, return them
to factory for repair.

Page 11

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual

The Intelligent Solution

VII Cautions
1.
2.
3.
4.

Power up only after all devices are well connected.


Adjust the detector after installation and maintenance.
During adjustment, the detector may give fault signal (fault passive output contact
is closed), but this will not affect the commission.
The detector base should be fixed directly on solid wall or frame that will not be
deformed by vibration. Any deformable material such as paperboard, plastic board,
foam board or thin wood board should not be placed between the base and the wall
or the bracket.

VIII Operation
The detector can be simply programmed by a programmer. Address, device type and
sensitivity level of the detector can be set with P-9910B Hand Held Programmer. Open
the detectors top cover, connect I2C cable of hand held programmer (PS/2 cable) with
XT3 of the detector. Turn on the power of hand held programmer, input 2, 5, 9 and
Function to enter I2C programming mode, the screen shows a 0. After carrying out
operation needed, input 2, 5, 9 and Function again to exit I2C programming mode and
return to power-on state.
1.

Reading Information
The hand held programmer can conveniently get original information like address
code, sensitivity level and device type. See details below:
z Enter I 2 C programming mode, the screen shows a 0.
z Press Test, the screen shows the address code of the detector.
z Press Up, the screen shows sensitivity level and device type in sequence.
z Press Down, the screen shows above contents in opposite way.

2.

Setting Address Code


The detector offers address code programming for field application. See operation
below:
z Enter I2C programming code, and the screen is a 0.
z Input address code for programming1242.
z Press Program to start programming. P will be shown when successful,
otherwise an E will be shown.
z If programming is successful, press Clear, the screen will show a 0, and you
can go on with further operations.
z If programming fails, press Clear, the screen will show a 0, input address
code once more.

3.

Setting Sensitivity Level

The hand held programmer can set two sensitivity levels to the detector. 2 is sensitivity
one. 3 is sensitivity two. See the details below:

Page 12

I-9105R
Intelligent Reflective Beam Detector
The Intelligent Solution
Installation and Operation Manual
z Enter I2C programming mode of hand held programmer, the screen shows a
0.
z Input unlock password and press Clear, the lock is opened.
z Press Function then the figure 3, the screen shows a .
z

z
4.

Input sensitivity level to be set, and press Program to begin programming. The
screen will show a P when if programming is successful, otherwise it will show
an E.
Press Clear, the screen shows a 0, and you can go on with further operations.

Setting the Device Type


You can also set the device type of the detector by hand held programmer. See
detailed operations below:
z Enter I2C mode of the programmer, the screen shows a 0.
z Input unlock password and press Clear, the lock is opened.
z Press Function and then figure 4, the screen shows a .
z Input the device type, press Program, to begin programming, P will be shown
when successful, otherwise an E will be shown.
z Press Clear, the screen shows a 0, and you can go on with further operations.
Note: The hand held programmer has lock password to prevent non-special
personnel from modifying some important data. Unlocking password is
456locking password is 789.

5.

Other Functions
1) Automatic Compensation of Light
When dust exists in the working environment of the detector, the emitting window,
receiving window and reflector will be covered with dust, which will affect normal
operation. In order to solve the problem, we designed the function of automatic
compensation of light. When there is dust on windows, the detector can judge the
amount of dust, and compensate the received signal through internal program and
circuit to ensure the detector can continue to work normally. The detector gives
fault signal when dust on the lens and reflector surface reaches a certain level and
light compensation reaches the limit for the detector to work normally.
2) Self-diagnosis on Optical Signal
The detector has functions of checking emitting, receiving and amplifying circuit.
When there is fault with these three parts of circuit during operation, the detector
will generate fault information.

IX Troubleshooting
Common problems and repair methods are as follows:

Page 13

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual

The Intelligent Solution

Table 1
Problems
Working
indicators not
lit after power
on.

Fault indicator
constantly
illuminates
after power on
Alarms loop
fault after
power register

Gives fault
signal after
power register
Not register
after power

Green LED
constantly
flashes after
power on
Gives fault
signal after a
period of
normal
operation
Alarms fire
after operation
for some time,
and gives fault
signal after
restart

Reasons
a) 24V power off
b) Working indicators damaged.
c) Transient suppressor VD12
damaged.
d) DiodeVD1, VD2, VD10, VD11
breakdown resulting in short
circuit with ground.
e) N1, N2 damaged.
f) The flexible cable inside was
not connected, or not
connected correctly.
Wrong device type.

a) Diode VZ1, VZ2, VD3, VD4


breakdown resulting in short
circuit with ground.
b) Momentary restraint VD13
damaged.
a) The detector is not in normal
working state.
b) The detector top cover is not
on.
a) The detector connects with
loop loosely.
b) 24V power does not offer
electricity.
c) N3, N4 damaged.
d) The soft cable inside the
detector does not insert or
incorrectly insert.
e) N1 and N2 damaged
a) Emitting diode or circuit
damaged.
b) Receiving diode or amplifying
circuit damaged.
The detector cant work normally.

Repair Methods
If the problems are mentioned in
a) ~ e) , replace the component
with problem.
If in f) connect again in right way.

Program the device type 51 or 52


again according to Section VIII
Operation.
Replace the component with
problem.

Commission once more.

Replace the component with


problem and commission again.

Replace the component with


problem.

Commission once more

Commission once more


The detector has deviated due to
external vibration.

Page 14

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual
a) There are obscuration on the
Fire signal
optical pathway between the
cannot be
detector and the reflector.
cleared
b) The angle of optical pathway
has changed and need to be
aligned again.
c) The emitting diode or circuit
damaged.
d) The photodiode or amplifying
circuit damaged.
The control
panel cant
Wrong connection with
receive
inadaptable wire.
fire and fault
signals.

X
1.

2.

3.
4.
5.

The Intelligent Solution

If the problems are mentioned in


a), b), commission once again.
If in c), d), e) replace the
component with problem.

Connect correctly.

Maintenance
If the detector gives fault signal after working for a long time, first check whether
the detector is damaged or not, and make sure that it is fixed to the wall or other
fittings. Then check whether it is the accumulating dust and positional excursion,
causing compensation fault, then consider other types of fault.
If emitting window, receiving window and reflector surface are found contaminated,
clean them with soft cloth and alcoholavoid scraping. Never use water or other
chemicals. Commission the detector again after cleaning.
The detector is fire protection product, whose operation must be well recorded by
the personnel on duty and shift.
Personnel on duty should be familiar with the functions and operation process of
the device to avoid mis-operation.
Test alarm function once half a year.

XI Accessories
Accessories provided with the detector are as follows:
Four 6 plastic expansion bolts.
One bracket.
One IR Light Filter.
Two M410 cross recessed pan head screws.
Six 4 flat washers.
One commission tool.

Page 15

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual

The Intelligent Solution

Appendix 1 Warnings
Limitations of Smoke Detector
The smoke detector is designed for triggering and initiating emergency fire equipments,
but it only functions when matching with other equipments. Installation of this smoke
detector must conform to electrical codes and standards in your country.
The smoke detector cannot work without power. It cannot work if power is cut off for any
reason.
The smoke detector may not sense fire that where smoke cannot reach it, such as in
chimneys, in walls, on roofs, or on the other side of closed doors.
The detector also may not sense a fire on another level of a building. Therefore,
detectors should be placed on every level of a building.
All types of smoke detector have limitations. Because fires develop in different ways
and are often unpredictable in their growth, it is impossible to predict which type of
detector will provide the earliest warning. No types of smoke detector can sense every
kind of fire every time. Generally speaking, detectors may not warn you about fires
caused by insufficient safety measures, violent explosions, leaking gas, improper
storage of flammable materials like diluents and other safety hazards, arson or children
playing with fire. The alarm of a smoke detector used in high velocity environment will
be delayed due to dilution of smoke by frequent and fast airflow. Whats more, the
smoke detector has to be maintained frequently because there will be more dust
contamination.
The smoke detector cannot last forever. In order to keep the detector working in good
condition, please maintain the equipment continuously according to recommendations
from manufacturers and relative nation codes and laws. Take specific maintenance
measures on the basis of different environments. The smoke detector contains
electronic parts. Even though its made to last for a long period of time, any of these
parts could fail at any time. Therefore, test your smoke detector at least every half-year
according to national codes or laws. Any smoke detectors, fire alarm devices or any
other components of the system must be repaired or replaced as long as they fail.

Page 16

I-9105R
Intelligent Reflective Beam Detector
Installation and Operation Manual

The Intelligent Solution

Appendix 2 Warranty
Our company warrants that the detector will be free from defects in design, materials
and workmanship. The warranty is valid for a period of 2 years from time of dispatch.
This warranty shall not apply to any product that is found to have been damaged,
improperly installed or used in any way not in accordance with the instructions supplied
with the product. Anybody, including the agents, distributors or employees, is not in the
position to amend the contents of this warranty. Products not covered by this warranty
shall also be returned for repair. Please return the products together with a description
of fault and possible reason to the company.

Page 17

GST China
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei,
P. R. China 066004
Tel: +86 (0) 335 8502528
Fax: +86 (0) 335 8508942
Email: [email protected]
www.gst.com.cn

GST UK
Global System Technology PLC