OperatorAs Manual Busbar Differential Protection IED REB 670 1.1
OperatorAs Manual Busbar Differential Protection IED REB 670 1.1
OperatorAs Manual Busbar Differential Protection IED REB 670 1.1
Innovation
from
ABB
COPYRIGHT
WE RESERVE ALL RIGHTS TO THIS DOCUMENT, EVEN IN THE EVENT
THAT A PATENT IS ISSUED AND A DIFFERENT COMMERCIAL
PROPRIETARY RIGHT IS REGISTERED. IMPROPER USE, IN
PARTICULAR REPRODUCTION AND DISSEMINATION TO THIRD
PARTIES, IS NOT PERMITTED.
THIS DOCUMENT HAS BEEN CAREFULLY CHECKED. HOWEVER, IN
CASE ANY ERRORS ARE DETECTED, THE READER IS KINDLY
REQUESTED TO NOTIFY THE MANUFACTURER AT THE ADDRESS
BELOW.
THE DATA CONTAINED IN THIS MANUAL IS INTENDED SOLELY FOR
THE CONCEPT OR PRODUCT DESCRIPTION AND IS NOT TO BE
DEEMED TO BE A STATEMENT OF GUARANTEED PROPERTIES. IN
THE INTEREST OF OUR CUSTOMERS, WE CONSTANTLY SEEK TO
ENSURE THAT OUR PRODUCTS ARE DEVELOPED TO THE LATEST
TECHNOLOGICAL STANDARDS. AS A RESULT, IT IS POSSIBLE THAT
THERE MAY BE SOME DIFFERENCES BETWEEN THE HW/SW
PRODUCT AND THIS INFORMATION PRODUCT.
Manufacturer:
ABB AB
Substation Automation Products
SE-721 59 Vsters
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
www.abb.com/substationautomation
Table of contents
Table of contents
Section 1
Introduction.......................................................................9
Introduction to the operators manual.................................................9
About the complete set of manuals for an IED..............................9
About the operators manual.......................................................10
Intended audience.......................................................................11
Related documents......................................................................11
Revision notes.............................................................................11
Section 2
Safety information..........................................................13
Warnings..........................................................................................13
Section 3
Overview........................................................................15
Operator overview............................................................................15
Identify the IED.................................................................................15
Section 4
Section 5
Section 6
REB 670
Operator's manual
1MRK505179-UEN rev. B
Table of contents
Overview......................................................................................26
View monitoring values.....................................................................26
Current phasors...........................................................................26
Three phase busbar protection (zone A).....................................26
Three phase busbar protection (Zone B).....................................26
Single phase busbar protection (Zone A)....................................27
Single phase busbar protection (Zone B)....................................27
Section 7
Event list.........................................................................29
View events......................................................................................29
Overview......................................................................................29
Section 8
Handle disturbances.......................................................31
Identify a disturbance.......................................................................31
View disturbance record details........................................................31
View general information.............................................................31
View disturbance indications.......................................................31
View event recordings.................................................................31
View trip values...........................................................................32
Trigger a disturbance report manually..............................................32
Section 9
Operator's manual
1MRK505179-UEN rev. B
REB 670
Table of contents
Analog modules...........................................................................38
Overview................................................................................38
Analog modules......................................................................38
I/O modules............................................................................39
HMI..............................................................................................39
Overview................................................................................39
LEDs.......................................................................................39
Screen ...................................................................................40
Functions................................................................................40
Change lock...........................................................................40
Busbar differential protection.......................................................40
Three phase busbar differential protection (ZoneA)...............40
Three phase busbar differential protection (Zone B)..............40
One phase busbar differential protection (Zone A)................40
One phase busbar differential protection (Zone B)................40
Control commands......................................................................41
Single command.....................................................................41
Logic rotating switch (GGIO)..................................................41
Selector mini switch (GGIO)...................................................41
Monitoring....................................................................................41
Overview................................................................................41
Measurements (MMXU).........................................................41
Current phasors......................................................................41
Voltage phasors.....................................................................42
Current sequence components (MSQI)..................................42
Voltage sequence components (MSQI).................................42
Disturbance report (RDRE)....................................................42
Binary signals.........................................................................42
Analog signals........................................................................43
Generic measured value........................................................43
Event function.........................................................................43
Local signal status report.......................................................43
IEC 608705103...................................................................43
Metering.......................................................................................44
Function for energy calculation and demand handling
(MMTR) .................................................................................44
Setting group N.................................................................................44
Overview......................................................................................44
Busbar differential protection.......................................................44
Three phase busbar differential protection (Bay)...................44
Three phase busbar differential protection (Check
zone)......................................................................................44
Three phase busbar differential protection (ZoneA)...............44
Three phase busbar differential protection (Zone B)..............45
REB 670
Operator's manual
1MRK505179-UEN rev. B
Table of contents
Operator's manual
1MRK505179-UEN rev. B
REB 670
Table of contents
REB 670
Operator's manual
1MRK505179-UEN rev. B
Table of contents
Selector switch.......................................................................57
IEC608705103....................................................................57
Automation bits, command function for DNP3.0
(AutomationBits) ....................................................................57
Selector mini switch (GGIO)...................................................57
Logic............................................................................................58
Event counter.........................................................................58
Logic gate...............................................................................58
Logic SR memory...................................................................58
Logic timer set........................................................................58
Boolean 16 to Integer conversion ..........................................58
Integer to Boolean 16 conversion...........................................58
Monitoring....................................................................................59
Disturbance report (RDRE)....................................................59
Generic measured value (GGIO)...........................................59
Measured value expander block............................................59
LEDs.......................................................................................59
Global positioning system......................................................59
Binary signal status report......................................................60
Event counter (GGIO)............................................................60
IEC61850 generic communication I/O functions 16 inputs
(GGIO) ...................................................................................60
IEC61850 generic communication I/O functions (GGIO).......60
Communications..........................................................................60
Remote communication..........................................................60
View station communication values.......................................60
View setting groups.....................................................................61
View test data..............................................................................61
Authorization................................................................................61
Test LEDs.........................................................................................62
Section 13 Reset..............................................................................67
Reset guide......................................................................................67
Reset LEDs.................................................................................67
Start and trip LEDs.................................................................67
All indication LEDs.................................................................67
Reset counters............................................................................67
Reset autorecloser.................................................................67
LDCM clear counters..............................................................67
Reset busbar protection trip........................................................68
Operator's manual
1MRK505179-UEN rev. B
REB 670
Table of contents
Section 14 Authorization..................................................................71
Overview...........................................................................................71
LogOn or logOff...........................................................................71
Authorization handling in the IED................................................72
Section 15 Glossary.........................................................................73
Glossary...........................................................................................73
REB 670
Operator's manual
1MRK505179-UEN rev. B
Section 1
Introduction
Section 1
Introduction
About this chapter
This chapter is an introduction to the operators manual, its purpose and usage.
1.1
1.1.1
Technical
reference
manual
Installation and
commissioning
manual
Operators
manual
Engineering
guide
en06000097.vsd
Operator's manual
1MRK505179-UEN rev. B
Section 1
Introduction
The IED 670 Engineering guide (EG) contains instructions on how to engineer the
IED 670 products. The manual guides to use the different tool components for IED
670 engineering. It also guides how to handle the tool component available to read
disturbance files from the IEDs on the basis of the IEC 61850 definitions. The third
part is an introduction about the diagnostic tool components available for IED 670
products and the PCM 600 tool.
The IEC 61850 Station Engineering guide contains descriptions of IEC 61850
station engineering and process signal routing. The manual presents the PCM 600
and CCT tool used for station engineering. It describes the IEC 61850 attribute editor
and how to set up projects and communication.
1.1.2
The chapter Safety information presents warnings and notices, which the user
should pay attention to.
The chapter Overview describes operations an operator may perform on a daily
basis or when the need arises.
The chapter Understand the local human-machine interface describes how to
use the human-machine interface.
The chapter Understand the HMI tree describes the different menu trees.
The chapter Read measured values describes how to locate and identify
available measurement data.
The chapter Event list describes the location and nature of recorded events.
The chapter Handle disturbances describes how to retrieve disturbance
information and reset alarms.
The chapter Read and change settings describes how to locate, and change
settings and parameters.
The chapter Diagnose IED status describes the location and use of available
diagnostic tools.
The chapter Test the IED describes the tests applicable to the IED.
The chapter Control and supervise the bay describes how to use the Single
Line Diagram to open and close primary apparatuses.
The chapter Reset describes resetting procedures.
The chapter Authorizationdescribes user categories and password procedures.
The chapter Glossary describes words and acronyms used in the literature
describing the IED.
This manual does not contain any instructions for commissioning or testing.
10
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 1
Introduction
1.1.3
Intended audience
General
The operators manual addresses the operator, who operates the IED on a daily basis.
Requirement
The operator must be trained in and have a basic knowledge of how to operate
protection equipment. The manual contains terms and expressions commonly used
to describe this kind of equipment.
1.1.4
Related documents
Documents related to REB 670
Identity number
Operators manual
Application manual
Buyers guide
SPA and LON signal list for IED 670, ver. 1.1
IEC 61850 Data objects list for IED 670, ver. 1.1
1KHA001027-UEN
1MRS755552
1.1.5
Revision notes
Revision
B
REB 670
Description
No functionality added. Minor changes made in content due to problem reports.
Operator's manual
1MRK505179-UEN rev. B
11
12
Section 2
Safety information
Section 2
Safety information
About this chapter
This chapter lists warnings and cautions that must be followed when handling the
IED.
2.1
Warnings
Do not touch circuitry during operation. Potentially lethal voltages
and currents are present.
Always avoid touching the circuitry when the cover is removed. The
product contains electronic circuitries which can be damaged if
exposed to static electricity (ESD). The electronic circuitries also
contain high voltage which is lethal to humans.
REB 670
Operator's manual
1MRK505179-UEN rev. B
13
14
Section 3
Overview
Section 3
Overview
About this chapter
This chapter presents a general overview of the Operator's manual.
3.1
Operator overview
The Human machine interface (HMI) on the IED provides an ideal mechanism for
the day to day operation and even advanced use of the IED. The keypad, LCD and
LEDs on the front of the IED are what constitute the HMI. Troubleshooting,
monitoring, setting and configuring are all possible via this interface. Through the
screens and menu elements available, as well as the keypad, the user is able to navigate
throughout the menu structure and move from screen to screen. This document is, to
a great extent, arranged in the same way as the IED software is structured and
describes all aspects of operation via the HMI.
The operator can document disturbances so that their causes can be analyzed and
evaluated for future reference. For example, the fault currents and voltages at the time
of the fault can be documented. The operator can also retrieve data about protected
objects, providing further information for fault analysis. This implies viewing the
mean value of current, voltage, power and frequency or primary and secondary
measured phasors. The operator can check the IED status at any time.
In some cases the operator may need to change the way the IED operates. This might
include changing the active setting group or a parameter value. This must always be
done strictly according to applicable regulations because un-authorized changes may
lead to severe damage of the protected object especially if a fault is not properly
disconnected.
3.2
REB 670
Operator's manual
1MRK505179-UEN rev. B
15
16
Section 4
Understand the local human-machine interface
Section 4
4.1
Overview
The human machine interface is used to monitor and to some extent control the way
the IED operates. The configuration designer can add functions that alert to events
requiring the attention of the operator.
Figure 1:
REB 670
1/2 x 19 case and 1/1 x 19 case with small and medium LCDs
Operator's manual
1MRK505179-UEN rev. B
17
Section 4
Understand the local human-machine interface
4.2
Keypad
The keypad is used to monitor and operate the IED. The keypad has the same look
and feel in all IEDs in the IED 670 series. LCD screens and other details may differ
but the way the keys function is identical. The keypad is illustrated in figure 2.
Figure 2:
The keys used to operate the IED are described below in table 1.
Table 1:
Key
The help key brings up two submenus. Key operation and IED information.
Opens the main menu, and used to move to the default screen.
The Local/Remote key is used to set the IED in local or remote control mode.
The E key starts editing mode and confirms setting changes when in editing mode.
Table continued on next page
18
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 4
Understand the local human-machine interface
Key
Function
The right arrow key navigates forward between screens and moves right in editing mode.
The left arrow key navigates backwards between screens and moves left in editing mode.
The up arrow key is used to move up in the single line diagram and in menu tree.
The down arrow key is used to move down in the single line diagram and in menu tree.
4.3
4.3.1
General operation
The General Operation submenu provides information about the IED keypad.
The I and O keys are used to open (OFF) and close (ON) breakers and disconnectors
when using the Single Line Diagram (SLD) in direct control situations.
4.3.2
Reset LEDs
Reset counters
Reset BBP trip
Reset BBP open CT
The Reset LEDs submenu consists of two lower level menus which are the Start and
trip LEDs and All indication LEDs submenus. To reset a counter, the actual
counter must first be selected. The submenus and the their structures are discussed in
the Reset chapter of this document.
REB 670
Operator's manual
1MRK505179-UEN rev. B
19
Section 4
Understand the local human-machine interface
4.4
LCD
4.4.1
Small
The small sized HMI is available for 1/2, 3/4 and 1/1 x 19 case. The LCD on the
small HMI measures 32 x 90 mm and displays 7 lines with up to 40 characters per
line. The first line displays the product name and the last line displays date and time.
The remaining 5 lines are dynamic. This LCD has no graphic display potential.
4.4.2
Medium
The 1/2, 3/4 and 1/1 x 19 cases can be equipped with the medium size LCD. This is
a fully graphical monochrome LCD which measures 120 x 90 mm. It has 28 lines
with up to 40 characters per line. To display the station matrix, this LCD is required.
4.5
LED
The LED module is a unidirectional means of communicating. This means that events
may occur that activate a LED in order to draw the operators attention to something
that has occurred and needs some sort of action.
4.5.1
Information
Green:
Steady
In service
Flashing
Internal failure
Dark
No power supply
Yellow:
Steady
Flashing
Red:
Steady
4.5.2
Indication LEDs
20
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 4
Understand the local human-machine interface
The LED indication module comprising 15 LEDs is standard in IED 670s. Its main
purpose is to present an immediate visual information for protection indications or
alarm signals.
There are alarm indication LEDs and hardware associated LEDs on the right hand
side of the front panel. The alarm LEDs are found to the right of the LCD screen.
They can show steady or flashing light. Flashing would normally indicate an alarm.
The alarm LEDs are configurable using the PCM 600 tool. This is because they are
dependent on the binary input logic and can therefore not be configured locally on
the HMI. Some typical alarm examples follow:
The RJ45 port has a yellow LED indicating that communication has been established
between the IED and a computer.
The Local/Remote key on the front panel has two LEDs indicating whether local or
remote control of the IED is active.
4.6
REB 670
Operator's manual
1MRK505179-UEN rev. B
21
Section 4
Understand the local human-machine interface
Press the I key to save and exit the screen and wait for the IED to start. Observe that
only the basic contrast setting will be saved.
4.7
How to navigate
4.7.1
Read
To read values and access information about the objects being monitored the operator
must navigate the menu tree using the arrow keys. The active submenu or value is
highlighted.
Navigation is as follows:
4.7.2
Change
To change a parameter setting the following steps should be followed:
1.
2.
3.
4.
5.
6.
7.
8.
22
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 5
Understand the HMI tree
Section 5
5.1
Overview
The local HMI has the following main menu:
Control
Measurements
Events
Disturbance records
Settings
Diagnostics
Test
Reset
Authorization
Language
5.1.1
Sub menu
Control
Measurements
Sub-sub menu
Events
Disturbance records
Manual trig
Settings
Time
REB 670
Operator's manual
1MRK505179-UEN rev. B
23
Section 5
Understand the HMI tree
Main menu
Sub menu
Sub-sub menu
General settings
Power system
Communication
Analog modules
I/O modules
HMI
Differential protection
Current protection
Control
Monitoring
Metering
Setting group N
Differential protection
Current protection
Control
Monitoring
Logic
Internal events
IED status
Test
Reset
Reset counters
Reset internal eventlist
Reset LEDs
Authorization
Language
24
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 6
Read measured values
Section 6
6.1
Overview
The measurement menu contains primarily analog measurement data. External
signals can also be viewed as they are or as they appear in the Signal Matrix Tool
(SMT). These signals are a virtual representation of the hard wired signals on the
various inputs and outputs. The SMT is only accessible via the PCM and is intended
to simplify the configuration of the IED. It allows hardware changes to be made
without having to reconfigure the internal logic. Signals that can be used in the SMT
are indicated with the Suffix SMT.
The functions available under measurements are outlined below.
1.
2.
3.
Analog primary values are the quantities measured on the primary side of the
current and voltage transformers (CTs and VTs).
Analog secondary values are the quantities measured on the secondary side of
the current and voltage transformers. These are the quantities measured on the
Transformer module (TRM) inputs.
Under Monitoring a number of submenus are available. These include Current
phasors and busbar protection.
6.2
6.2.1
Overview
REB 670
Operator's manual
1MRK505179-UEN rev. B
25
Section 6
Read measured values
The analog primary values are analog quantities measured on the primary side of the
TRM and reflect the actual current or voltage on the primary side of the VTs and CTs.
The ratio is adjusted under settings and also depends on the rating of the TRM. 24
primary values and phase angles are displayed in this view.
Measurements/Analog Primary Values
Displays the quantities measured by the transformer module (TRM). For each channel
used the amplitude of the voltage or current and its phase angle is shown. The status
of the module is always shown and channels not in use are indicated with the
abbreviation NC. Data from up to two TRMs and LDCMs can be viewed. All
currents and voltages are given in RMS values.
6.3
6.3.1
Overview
Analog secondary values shows secondary CT currents and VT voltages. These are
the actual current and voltage values at the TRM inputs.
Measurements/Analog Secondary Values
Displays up to 24 channels with secondary CT and VT data. RMS values are shown.
6.4
6.4.1
Current phasors
Measurement/Monitoring/Current Phasors/CP
All three phase currents and their phase angles are displayed here. As many as 10 sets
of current data can be shown.
6.4.2
6.4.3
26
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 6
Read measured values
Displays the magnitude of the currents and the differential currents in the three phase
system.
6.4.4
6.4.5
REB 670
Operator's manual
1MRK505179-UEN rev. B
27
28
Section 7
Event list
Section 7
Event list
About this chapter
This chapter describes how to find and read the event list.
7.1
View events
7.1.1
Overview
Events displays recorded events such as trips and breaker opened or closed.
Events
Displays a list of events in chronological order and where each event has a time stamp.
The latest event is at the top of the list.
REB 670
Operator's manual
1MRK505179-UEN rev. B
29
30
Section 8
Handle disturbances
Section 8
Handle disturbances
About this chapter
This chapter describes disturbance detection and handling. This includes resetting
LED alarms, triggering disturbance reports and the viewing of several fault indicators.
8.1
Identify a disturbance
A disturbance record can be generated manually by using the Manual Trig
functionality in the HMI menu. Other disturbance records are generated automatically
in the system dependant on the settings made. Disturbance reports generate a
disturbance sequence number and are time tagged. The fault location and fault loop
are among the data generated in a fault record. Under each fault report there are five
categories of information available. These are described in the sections that follow.
8.2
8.2.1
8.2.2
8.2.3
REB 670
Operator's manual
1MRK505179-UEN rev. B
31
Section 8
Handle disturbances
8.2.4
8.3
32
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 9
Read and change settings
Section 9
9.1
9.1.1
System time
Settings/Time/System time
Under System time, the system clock date and time are set.
9.1.2
Time synchronization
9.1.2.1
Overview
The synchronization settings are divided into categories Time synch, Time synch
BIN, Time synch SNTP, Time synch DST Begin, Time synch DST End, Time synch
time zone and Time synch IRIG-B. The settable parameters are found under each
category.
9.1.2.2
TimeSynch
Settings/Time/Synchronization/TimeSynch
Here the parameters FineSyncSource, CourseSyncSrc and SyncMaster are switched
on or off.
REB 670
Operator's manual
1MRK505179-UEN rev. B
33
Section 9
Read and change settings
9.1.2.3
TimeSynchBIN
Settings/Time/Synchronization/TimeSynchBIN
Binary input synchronization settings available here are the position of the of the
module, the number of the binary input and the detection mode.
9.1.2.4
TimeSynchSNTP
Settings/Time/Synchronization/TimeSynchSNTP
Here the IP addresses for the Simple Network Time Protocol servers are set.
9.1.2.5
TimeSynchDSTBegin
Settings/Time/Synchonization/TimeSynchDSTBegin
The starting point for Daylight Savings Time is set here.
9.1.2.6
TimeSynchDSTEnd
Setttings/Time/Synchronization/TimeSynchDSTEnd
The end point of Daylight Savings Time is set here.
9.1.2.7
TimeZone
Settings/Time/Synchronization/TimeSynchTimeZone
The time zone according to Coordinated Universal Time (UTC) is set here.
9.1.2.8
TimeSynch IRIG-B
Settings/Time/Synchronization/TimeSynchIRIG-B
The type of input, time domain, type of encoding and time zone for IRIG-B are set
here.
9.2
General settings
Parameters under General settings that are changed will cause the IED to restart. This
occurs automatically and requires no manual intervention.
34
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 9
Read and change settings
9.2.1
Power system
9.2.1.1
Overview
Under Power system in General settings there are four parameter categories. These
are Identifiers, Primary values, three phase analog group and three phase analog sum
group.
9.2.1.2
Identifiers
Settings/General Settings/Power System/Identifiers
Displays list with Station Name, Station Number, Object Name, Object Number, Unit
Name and Unit Number.
9.2.1.3
Primary values
Settings/General Settings/Power System/Primary Values
Displays the system frequency.
9.2.2
Communication
9.2.2.1
Overview
The parameter settings for communications are found under General Settings
\Communications. Communication settings cover network interfaces, protocol,
remote communication and reception of interlocking information.
9.2.2.2
TCP-IP
Settings/General settings/Communication/Front port
The IP Address and IP mask for the ethernet port on the front panel of the IED are
set here. These are generally used when connecting a PC directly to the IED.
Remember that this is a static IP address and that the appropriate network settings
must also be made in the PC.
Settings/General settings/Communication/TCP-IP/Rear OEM-Port AB
The IP address, IP mask and Link for the Optical Ethernet card at the rear of the IED
are set here.
Settings/General settings/Communication/TCP-IP/Rear OEM-Port CD
The same as the above but with different IP address if a second port is used.
Settings/General settings/Communication/TCP-IP/Gateway
REB 670
Operator's manual
1MRK505179-UEN rev. B
35
Section 9
Read and change settings
If a gateway is used to access the system the address to that gateway is entered here.
9.2.2.3
The menu for the rear optical LON port has five submenus for various settings
affecting LON parameters. The HMI paths to these submenus and their contents are
described below.
Settings/General settings/Communication/SLM configuration/Rear optical
LON port/General
In the General submenu there are three settings. These are for the Subnet address, the
Node address and the NeuronID.
Settings/General settings/Communication/SLM configuration/Rear optical
LON port/ServicePinMessage
In this submenu a Service pin message can be generated. This is similar to a ping
in traditional networks. This sends a signal to another node in the system which is
then made aware of the Neuron ID of LON port and can respond to that port.
Settings/General settings/Communication/SLM configuration/Rear optical
LON port/ADE
The Application Data Event (ADE) menu is where operation of LON is set on or off
and where the data exchange speed can be set. If LON is used primarily to send event
data then the appropriate setting is slow. Should LON be used, for example, as a
channel for TRIP signals then the setting fast would be appropriate.
Settings/General settings/Communication/SLM configuration/Rear optical
LON port/SPA
Settings for SPA over LON are made here. The operation setting is used to switch
the function on or off and the slave address setting is where the slave address is
entered.
Settings/General settings/Communication/SLM configuration/Rear optical
LON port/Horizontal communication
This setting is used to activate or deactivate horizontal communication.
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 9
Read and change settings
SPA and IEC cannot run at the same time and in this submenu one of the options is
chosen.
Settings/General settings/Communication/SLM configuration/Rear optical
SPA-IEC port/SPA
When SPA is chosen the baud rate and slave address are set here.
Settings/General settings/Communication/SLM configuration/Rear optical
SPA-IEC port/IEC608705103
When IEC 608705103 is used the settings Slave address, Baud rate, RevPolarity
and CycMeasRepTime are done here.
9.2.2.4
LDCM
Settings/General settings/Communication/LDCM configuration/LDCM
identical sets of settings for Remote Binary Communication (CRB) and four for
Remote Multi Communication (CRM). The multi communication block can send
both binary and analog data whereas the binary can only send binary data.
Each instance of CRB has seven settable parameters where the channel mode can be
set on or off, terminal numbers can be entered, synchronization can be set to master
or slave and opto power can be set high or low.
Each instance of CRM has 17 settable parameters. These include those above and
others such as transmission delay and transmission current.
9.2.2.5
Station communication
Multicommand send
Settings/General settings/Communication/Station communication/
MulticommandSend/MT
The up to ten instances of MulticommandSend settings allow the user to adjust the
maximum and minimum cycle time.
Multicommand receive
Settings/General settings/Communication/Station communication/
Multicommand receive/CM
The up to 60 instances of MulticommandReceive settings available here allow the
user to adjust the maximum and minimum cycle time, the pulse duration and mode
of operation. The mode of operation is either steady or pulsed.
Settings/General Settings/Communication/Station communication/IEC61850
81
REB 670
Operator's manual
1MRK505179-UEN rev. B
37
Section 9
Read and change settings
Includes settings for the IED name, operation (on/off) and GOOSE.
9.2.3
Analog modules
9.2.3.1
Overview
Under Analog modules in the General settings menu there are settings for Analog
inputs and I/O modules. Within each instance of analog input there are settings for
all 12 channels that include the name of the channel, star point of the CT circuit, the
primary and secondary values from the measuring transformers (CTs and VTs). The
channel type and ratings are shown but cannot be changed.
A mix of up to 14 instances of BIM, BOM and IOM is possible depending on the
physical configuration of the IED. Operation ON or OFF can be set for all of these
and for the BIMs oscillation release and oscillation block settings are available. These
settings are on board level and apply to all binary inputs or outputs on a board.
9.2.3.2
Analog modules
Settings/General Settings/Analog modules/AnalogInputs
Displays all variations of analog input modules with parameters. The analog input
modules have different combinations of current and voltage inputs. Each channel has
parameters where the type of channel is set, the primary and secondary values from
VTs and CTs and for Current Transformers the star point location (line side or busbar
side) is set.
Settings/General Settings/Analog modules/3PhAnalogGroup/PR
38
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 9
Read and change settings
Here, settings for the Fourier filters, the minimum system voltage required to measure
frequency, the item designation of CTs or VTs, and the system voltage are set. These
settings are required by the preprocessing blocks and are usually only adjusted during
the initial engineering phase.
Setting/General Settings/Analog modules/3PhAnalogSummationGroup/SU
Here is where the settings for the summation block are done. The summation type,
Fourier filter reference frequency, minimum voltage for frequency measurement and
the system voltage are some of the parameters that can be set here.
Settings/General Settings/Analog modules/Reference channel service values
The phase angle reference is set here.
9.2.3.3
I/O modules
Settings/General Settings/I/O Modules
Settings for binary inputs and outputs (BIM, BOM, IOM), and under each binary
module there are one or more adjustable parameters. In the I/O modules folder there
is also a reconfigure setting that starts a dialog box prompting the user to confirm
or cancel the command. Since only I/O modules installed in the IED are shown, the
parameters available for setting depend on the physical configuration of the IED. All
I/O modules include the operation parameter which enables the operator to switch
the module on or off.
9.2.4
HMI
9.2.4.1
Overview
Under HMI in General settings there are submenus for LEDs, Screen, Functions,
Reference channel service values and the Change lock function. In the LED submenu
there are settings for operation, illumination times, and sequence types for the LEDs
on the IED front panel. In the Screen submenu Contrast level, Default screen, Auto
repeat and Timeout display can be set. In the Functions submenu the Event list sorting
order and Distance presentation can be set.
9.2.4.2
LEDs
Settings/General settings/HMI/LEDs
Parameters such as Operation, tRstart, tMax and 15 instances of SeqTypeLED can
be set here. The SeqTypeLED offers several options for the type of illumination
sequence the LEDs should follow.
REB 670
Operator's manual
1MRK505179-UEN rev. B
39
Section 9
Read and change settings
9.2.4.3
Screen
Settings/General Settings/HMI/Screen
Local HMI setting parameters such as Language, Contrast level and Default menu
can be set here.
9.2.4.4
Functions
Settings/General Settings/HMI/Functions
The settings here are used to determine the way information is presented in the HMI.
9.2.4.5
Change lock
Settings/General settings/HMI/Change lock
The operation of the Change lock function can be activated or deactivated here.
9.2.5
9.2.5.1
9.2.5.2
9.2.5.3
9.2.5.4
40
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 9
Read and change settings
Parameters for this function are found here. Limits, reporting types, substituted
values, hysteresis values, deadband values and related parameters can be set here.
9.2.6
Control commands
9.2.6.1
Single command
Settings/General settings/Control/Commands/Single command/CD
The mode for single command is set here.
9.2.6.2
9.2.6.3
9.2.7
Monitoring
9.2.7.1
Overview
Under monitoring there are parameters for setting current phasors, Disturbance
reports and the Measured value expander block.
9.2.7.2
Measurements (MMXU)
Settings/General Settings/Monitoring/ServiceValues/SVR
Displays three instances of SVR.
9.2.7.3
Current phasors
Settings/General Settings/Monitoring/Current phasors/CP
Displays available instances of the current phasor function (CP) with output regarding
current amplitude, current range, phase angle, zero sequence current magnitude and
negative sequence current magnitude.
REB 670
Operator's manual
1MRK505179-UEN rev. B
41
Section 9
Read and change settings
9.2.7.4
Voltage phasors
Settings/General Settings/Monitoring/Voltage phasors/Phase-Phase
Displays available instances of the voltage phasor function (VP) with output data for
phase to phase voltage, (amplitude, phase angle). The setting parameters for
supervision levels, deadband etc. are set here
Settings/General Settings/Monitoring/Voltage phasors/Phase-Earth
Displays available instances of the voltage phasor function (VN) with output data for
phase to earth voltage, (amplitude, phase angle). The setting parameters for
supervision levels, deadband etc. are set here.
9.2.7.5
9.2.7.6
9.2.7.7
9.2.7.8
Binary signals
Settings/General settings/Monitoring/Disturbance report/Binary signals/
Channel xx-yy
42
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 9
Read and change settings
There are some groups of several channels with several binary outputs per channel.
Each channel has some settable parameters. These are operation, trig level, indication
MA and set LED.
9.2.7.9
Analog signals
Settings/General settings/Monitoring/Disturbance report/Analog signals/
Channel xx-yy
There are some groups of a number of channels with a number of analog signals per
channel. Each signal has some settable parameters such as operation, Nominal value
and trig values.
9.2.7.10
9.2.7.11
Event function
Settings/General settings/Monitoring/Event function/EV
The Event function menu consists of several sets of settable parameters (EV01
EV20) where the SPA channel mask, LON channel mask, Event mask and minimum
repetition interval can be set.
9.2.7.12
9.2.7.13
IEC 608705103
Settings/General settings/Monitoring/IEC 608705103
The IEC 608705103 part of the settings menu is divided into two separate
submenus. These are Measurements and Disturbance report. In the Measurements
menu there are four sets of measurement settings, one with standard settings and three
with user defined settings. The standard settings include some standard service value
thresholds.
In the Disturbance report menu Binary signal parameters on up to 96 channels are
configured.
REB 670
Operator's manual
1MRK505179-UEN rev. B
43
Section 9
Read and change settings
9.2.8
Metering
9.2.8.1
9.3
Setting group N
9.3.1
Overview
There are some default setting groups. Under general settings, parameters in these
groups can be changed to suit the needs of an application. The default settings have
been chosen according to established practice in the industry but will usually require
a certain amount of adjustment to suit the requirements of individual applications.
9.3.2
9.3.2.1
9.3.2.2
9.3.2.3
44
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 9
Read and change settings
9.3.2.4
9.3.2.5
9.3.2.6
9.3.2.7
9.3.2.8
9.3.2.9
9.3.2.10
REB 670
Operator's manual
1MRK505179-UEN rev. B
45
Section 9
Read and change settings
This function has two settings in this view. Operation for turning the function on or
off and the threshold time for the alarm.
9.3.2.11
9.3.3
Impedance protection
9.3.4
Current protection
9.3.4.1
Overview
Under Current protection there are settings for Phase overcurrent four step and
Breaker failure. There are several instances of each function with parameter settings
for rated data, operation and many others.
9.3.4.2
9.3.4.3
9.3.4.4
46
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 9
Read and change settings
9.3.4.5
9.3.5
Voltage protection
9.3.6
Control
9.3.6.1
Overview
Under Control in the Setting group N menu settings for Autorecloser are available.
Some instances of settings are available meaning that the settings for all available
apparatuses can be made here. The autorecloser settings include the number of shots,
first shot combinations and many other useful settings.
9.3.6.2
9.3.6.3
9.3.7
Logic
9.3.7.1
Overview
Under Logic there are settings for Trip logic, Trip matrix, Event counter, Logic gate,
Logic SR memory and Logic timer set. Under each of these function categories there
are a number of instances, each with a parameter set.
REB 670
Operator's manual
1MRK505179-UEN rev. B
47
Section 9
Read and change settings
9.3.7.2
LogicGate
Settings/Setting Group N/Logic/LogicGate/GT
Displays parameter settings for operation (On or Off).
9.3.7.3
LogicSRMemory
Settings SettingGroup N/Logic/LogicSRMemory/SM
Displays setting parameters for operating mode of memory function.
9.3.7.4
LogicTimerSet
Settings/Setting Group N/Logic/LogicTimerSet
Displays settable parameters for operation (On or Off) and delay for settable timer.
9.3.8
Monitoring
9.3.8.1
Overview
Fault locator settings are found under Monitoring in the Setting Group N menu.
9.3.8.2
9.4
9.5
Language
Under the language part of the main menu the language options available in the HMI
are located. These vary depending on the configuration ordered.
48
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 10
Diagnose IED status
10.1
10.1.1
10.1.2
REB 670
Operator's manual
1MRK505179-UEN rev. B
49
50
Section 11
Test the IED
11.1
Overview
The test part of the tree view in the HMI has a number of submenus for test and
viewing activities. When IED test mode is set to ON functions are inactivated so that
no signals are transmitted during testing. Under Function test modes individual
functions can be activated. The LED test are also activated here.
The submenus for binary inputs and outputs as well as the submenu titled Function
status are used to view data generated by the system. These categories of data are
outlined below.
1.
2.
3.
4.
5.
6.
7.
8.
REB 670
Binary output values has two submenus. These are Binary output modules
(BOM) and SMT binary outputs. Under these the status of binary outputs and
SMT outputs is displayed.
Binary input values has two submenus. These are Binary input modules (BIM)
and SMT binary inputs. These screens show the state of all the inputs on the
Binary input modules (BIM). These are represented as digits but may also be a
number if the input is being used to receive pulses for power measurement.
Differential Protection displays a choice of differential functions available to the
operator. Function related measurements can be viewed by navigating to the
screen for each individual function.
Current protection displays a choice of functions. To view data related to these
functions it is necessary to choose one from the list and navigate to the screen
for the function in question.
Control displays the , Autorecloser functions. and the Autorecloser functions
include a number of function related measurements such as calculated
differences of measurements and number and kind of reclosing attempts.
Logic displays a choice of functions available to the operator. These are Event
counter, Logic gate, Logic memory and Logic timer set each with their own set
of measurements.
Monitoring displays a choice of functions available to the operator. Function
related measurements can be viewed by navigating to the screen for each
individual function. One of the submenus shows the status of the LEDs on the
HMI.
Communication displays submenus for Remote communication.
Operator's manual
1MRK505179-UEN rev. B
51
Section 11
Test the IED
11.2
11.3
11.3.1
Overview
Binary input values display the state of each individual input in the Binary input
modules (BIM). These are indicated with a 1 or 0 depending on whether a signal is
present or not. Binary input modules with enhanced pulse counting capabilities can
receive pulses used for power measurement. The number of pulses received is used
to measure power.
11.3.1.1
11.3.1.2
11.4
11.4.1
Overview
52
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 11
Test the IED
Binary output values show the status of each individual output in the Binary output
module (BOM). If the signal matrix tool is used binary outputs are depicted as virtual
outputs. Note, that only modules installed in the IED are shown in the HMI.
11.4.1.1
11.4.1.2
11.5
11.5.1
Overview
With the IED, in test mode the different protections (except line differential
protection) can be individually released for test here. Events can be disabled or
enabled.
11.5.2
Current protection
Test/Function test modes/Current protection
Test of breaker failure protection and phase overcurrent protection.
11.5.3
Control
Test/Function test modes/Control/Autorecloser(RREC, 79)/AR
Shows available instances of autorecloser for test of state.
Test/Function test modes/Control/Commands/Selector switch(GGIO)/SL
Shows available instances of selector switch for test of state.
11.5.4
Monitoring
Test/Function test modes/Monitoring
REB 670
Operator's manual
1MRK505179-UEN rev. B
53
Section 11
Test the IED
11.5.5
Logic
Test/Function test modes/Logic
Test of event counter functions.
11.6
Function status
11.6.1
11.6.2
11.6.2.1
11.6.2.2
11.6.2.3
11.6.2.4
11.6.2.5
54
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 11
Test the IED
11.6.2.6
11.6.2.7
11.6.2.8
11.6.2.9
11.6.2.10
11.6.2.11
Switchgear status
Test/Function status/Differential protection/SwitchgearStatus/SSxx-yy/SSxx
In the this view data output indicating the status of the switchgear is displayed.
11.6.3
Impedance protection
11.6.4
Current protection
11.6.4.1
REB 670
Operator's manual
1MRK505179-UEN rev. B
55
Section 11
Test the IED
11.6.4.2
11.6.4.3
11.6.4.4
11.6.5
Voltage protection
11.6.6
11.6.7
Control
There are large amounts of output data from the control functions. The main
categories of data are found under Autorecloser.
11.6.7.1
11.6.7.2
56
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 11
Test the IED
11.6.8
Commands
In the commands menu it is possible to view three sets of values. These are found
under the submenus Single command, Selector switch and IEC608705103.
11.6.8.1
Single command
Test/Function status/Control/Commands/Single command
There are OUT signals under the Single command menu.
11.6.8.2
Selector switch
The HMI path to the Selector switch data is:
Test/Function status/Control/Commands/Selector Switch
An application dependent number of switches can be displayed here. The position of
each switch is indicated here. There are up to a number of possible switch positions.
The number of switches and switch positions is determined by the configuration in
the PCM configuration tool.
11.6.8.3
IEC608705103
The path to the IEC608705103 menu is:
Test/Function Status/Control/Commands/IEC608705103
Under this part of the HMI tree there are the following three submenus:
IED Commands
Function Commands
User Defined Commands
Various IED, function and user defined command data can be viewed here.
11.6.8.4
11.6.8.5
REB 670
Operator's manual
1MRK505179-UEN rev. B
57
Section 11
Test the IED
11.6.9
Logic
Under the Logic function folder there is viewable data for event counter values, Logic
gate outputs, Logic SR memory output states and Logic timer set output states are
also shown here.
11.6.9.1
Event counter
Test/Function status/Logic/Event counter/CNTx
Available instances of CNTx presenting some output values each.
11.6.9.2
Logic gate
Test/Function status/Logic/LogicGate/GT
Displays available instances of the gate output. The output data type is an integer with
a possible value from 0 to 255.
11.6.9.3
Logic SR memory
Test/Function status/Logic/LogicSRMemory/SN
Displays available instances of the function (SM). There are two measurement
parameters per instance, SMnn OUT (Output) and SMnn N_OUT (Output inverted).
The output data presented in the HMI is boolean and indicates whether or not a signal
is present. For example, an output of one from SM01 OUT indicates that a signal
exists on that output.
11.6.9.4
11.6.9.5
11.6.9.6
58
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 11
Test the IED
11.6.10
Monitoring
Monitoring includes large amounts of viewable data including Disturbance report
data, Current phasors, Binary signal status report, Events, MVGGIO, MVExpander
and LEDs.
11.6.10.1
11.6.10.2
11.6.10.3
11.6.10.4
LEDs
Test/Function status/Monitoring/LEDs/Start and trip LEDs
Displays the status of start and trip LEDs.
Test/Function status/Monitoring/LEDs/All indication LEDs
Shows new and accumulated indications and the status of the HMI indication LEDs.
11.6.10.5
REB 670
Operator's manual
1MRK505179-UEN rev. B
59
Section 11
Test the IED
Displays the number of satellites supplying positioning and timing data to the GPS
module.
11.6.10.6
11.6.10.7
11.6.10.8
11.6.10.9
11.6.11
Communications
The communication output data available under Test includes remote communication
and station communication.
11.6.11.1
Remote communication
Test/Function status/Communication/Remote communication
Displays an application dependent number of instances of CRB (Remote Binary
Communication) and up to four instances of CRM (Remote Multi Communication)
with measurement data.
11.6.11.2
60
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 11
Test the IED
valid. Several apparatuses can be displayed. There are also indications of reservation
requests, reservation granted and the validity of data and communication.
MultiCommand send
Test/Function status/Communication/Station communication/
MultiCommandSend/MT
The MultiCommand Send indication is used to display data from the Local Optical
network (LON).
MultiCommand receive
Test/Function status/Communication/Station communication/
MultiCommandReceive/CM
The MultiCommand Receive indications displayed here show available sets of output
data. Each set of output data has a number of signals. Other information displayed
here shows whether there has been a change in data and whether data is valid.
11.6.12
11.6.13
11.6.14
Authorization
Test/Function status/Authorization
Shows if any user is logged on and if any user is blocked by invalid password.
REB 670
Operator's manual
1MRK505179-UEN rev. B
61
Section 11
Test the IED
11.7
Test LEDs
Test/LED test
The Test LEDs menu enables the operator to activate LEDs manually. LEDs that do
not light up are defective. Defective LEDs are also logged in Disturbance records
under Monitoring.
62
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 12
Control and supervise the bay
12.1
Overview
The control menu in the HMI includes the Single command and Selector switch
functions as well as the station matrix.
The Single command function is used to view LON interlocking data and is only
visible if LON is configured and used in the system.
The Selector Switch function is configured in the PCM 600 tool and the switch
position can be changed in the HMI. The selector switch has the same function as a
rotating switch with up to 32 positions. Each position is configured in the PCM 600
to match a certain application. Each position number corresponds to the equivalent
position of a rotating switch. It is only visible if it has been configured in the PCM
600.
12.1.1
Station matrix
The station matrix provides the operator with information about the bay and
connections there. It provides information on switchgear object status. The
illustrations below are an example of how the station matrix data is presented on the
HMI.
REB 670
Operator's manual
1MRK505179-UEN rev. B
63
Section 12
Control and supervise the bay
1.
2.
3.
64
User defined bay name. This can only be set in the PCM software tool.
Internally used bay FB.
Connections to internal zones
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 12
Control and supervise the bay
1.
2.
REB 670
Operator's manual
1MRK505179-UEN rev. B
65
66
Section 13
Reset
Section 13 Reset
About this chapter
This chapter describes how to reset the IED and when this is necessary.
13.1
Reset guide
13.1.1
Reset LEDs
13.1.1.1
13.1.1.2
13.1.2
Reset counters
13.1.2.1
Reset autorecloser
The recorded number of reclosings are reset under Reset counters in the HMI tree.
Reset/Reset counters/Autorecloser(RREC.79)
In the dialog box that appears, choose YES to reset.
13.1.2.2
REB 670
Operator's manual
1MRK505179-UEN rev. B
67
Section 13
Reset
Activating Reset of LDCM counters sets the counter concerned to zero. A reset can
be performed by affirmation in the dialog box. This is done by pressing the E key
when YES is highlighted.
13.1.3
13.1.3.1
13.1.3.2
13.1.3.3
13.1.3.4
13.1.4
13.1.4.1
13.1.4.2
13.1.4.3
68
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 13
Reset
13.1.4.4
REB 670
Operator's manual
1MRK505179-UEN rev. B
69
70
Section 14
Authorization
Section 14 Authorization
About this chapter
This chapter describes password procedures and levels of access in the system.
14.1
Overview
To safeguard the interests of our customers, both the IED 670 and the tools that are
accessing the IED 670 are protected, subject of authorization handling. The concept
of authorization, as it is implemented in the IED 670 and the associated tools is based
on the following facts:
There are different levels (or types) of users that can access or operate different
areas of the IED and tools functionality; the pre-defined user types are defined
as follows:
User type
Access rights
Guest
Read only
SuperUser
Full access
SPAGuest
SystemOperator
ProtectionEngineer
All settings
DesignEngineer
UserAdministrator
The IED users can be created, deleted and edited only with the User Management
Tool (UMT) within PCM 600. The user can only LogOn or LogOff on the LHMI of
the IED, there are no users, groups or functions that can be defined on the IED LHMI.
14.1.1
LogOn or logOff
The Authorization menu allows the user to logOn and, logOff. The HMI path is as
follows:
Authorization
REB 670
Operator's manual
1MRK505179-UEN rev. B
71
Section 14
Authorization
14.1.2
72
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 15
Glossary
Section 15 Glossary
About this chapter
This chapter contains a glossary with terms, acronyms and abbreviations used in ABB
technical documentation.
15.1
REB 670
Glossary
AC
Alternating current
A/D converter
ADBS
ADM
ANSI
AR
Autoreclosing
ArgNegRes
Setting parameter/ZD/
ArgDir
Setting parameter/ZD/
ASCT
ASD
AWG
BBP
Busbar protection
BFP
BIM
BOM
BR
BS
British standard
BSR
BST
C37.94
CAN
CAP 531
Operator's manual
1MRK505179-UEN rev. B
73
Section 15
Glossary
74
CB
Circuit breaker
CBM
CCITT
CCM
CCVT
Class C
CMPPS
CO cycle
Close-open cycle
Co-directional
COMTRADE
Contra-directional
CPU
CR
Carrier receive
CRC
CS
Carrier send
CT
Current transformer
CVT
DAR
Delayed auto-reclosing
DARPA
DBDL
DBLL
DC
Direct current
DFT
DIP-switch
DLLB
DNP
DR
Disturbance recorder
DRAM
DRH
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 15
Glossary
REB 670
DSP
DTT
EHV network
EIA
EMC
EMF
EMI
EnFP
ESD
Electrostatic discharge
FOX 20
FOX 512/515
Access multiplexer
FOX 6Plus
G.703
GCM
GI
GIS
GOOSE
GPS
GSM
HDLC protocol
HFBR connector
type
HMI
HSAR
HV
High voltage
HVDC
IDBS
IEC
IEC 60044-6
Operator's manual
1MRK505179-UEN rev. B
75
Section 15
Glossary
76
IEC 60870-5-103
IEC 61850
IEEE
IEEE 802.12
IEEE P1386.1
IED
I-GIS
IOM
Instance
IP
IP 20
IP 40
IP 54
IRF
IRIG-B:
ITU
LAN
LIB 520
LCD
LDCM
LDD
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 15
Glossary
REB 670
LED
LNT
LON
MCB
MCM
MIM
Milli-ampere module
MPM
MVB
NCC
NUM
Numerical module
OCO cycle
Open-close-open cycle
OCP
Overcurrent protection
OEM
OLTC
OV
Over voltage
Overreach
PCI
PCM
PCM 600
PC-MIP
PISA
PMC
POTT
Process bus
Bus or LAN used at the process level, that is, in near proximity
to the measured and/or controlled components
PSM
PST
PT ratio
PUTT
RASC
Operator's manual
1MRK505179-UEN rev. B
77
Section 15
Glossary
78
RCA
REVAL
Evaluation software
RFPP
RFPE
RISC
RMS value
RS422
RS485
RTC
RTU
SA
Substation Automation
SC
SCS
SCT
SLM
SMA connector
SMS
SNTP
SPA
SRY
ST
Starpoint
SVC
TC
Trip coil
TCS
TCP
TCP/IP
Operator's manual
1MRK505179-UEN rev. B
REB 670
Section 15
Glossary
REB 670
TEF
TNC connector
Underreach
U/I-PISA
UTC
UV
Undervoltage
WEI
VT
Voltage transformer
X.21
3IO
3UO
Operator's manual
1MRK505179-UEN rev. B
79
80