Wye-Wye Transformers & Tertiary Windings
Wye-Wye Transformers & Tertiary Windings
Wye-Wye Transformers & Tertiary Windings
The primary and secondary circuits are in phase (no phase angle displacements). This is an
important advantage where transformers are used to interconnect systems of different
voltages in a cascading manner.
As an example, suppose there are four systems operating at 500, 230, 138, and 69 kV that
need to be interconnected. Substations can be constructed using wye-wye transformer
connections to interconnect any two of these voltages. The 500 kV system can be tied with
the 69 kV system through a single 500 to 69 kV transformation or through a series of
cascading transformations at 230, 138, and 69 kV.
If the neutral end of a Y-connected winding is grounded, reduced levels of insulation are
required at the neutral end of the winding. A winding that is connected across the phases
(delta) requires full insulation throughout the winding.
The first advantage is the major reason that wye-wye connected transformers are frequently
found in substation installations. They may be appropriate when one is confident that the
secondary load is sinusoidal and not comprised of non-linear loads such as variable speed drives
and rectifier feeds. When providing power to non-sinusoidal loads however, serious
consideration must be made to address and manage the following:
Triplen harmonics can pass through the transformer. Triplen harmonics are comprised of the
odd multiples of the 3rd harmonic (ex. 3rd, 9th, 15th, 21st etc.).
A harmonic is a component of a wave at a frequency that is a multiple of the fundamental
(usually 60 Hz) power line frequency. Harmonics are attributed to loading from large
amounts of electronic devices, using solid state power switching supplies for converting
incoming AC to DC and/or industrial loads for rectifier feeds and induction heating. These
non linear loads create harmonics by drawing current in abrupt short pulses, rather than in a
smooth sinusoidal manner.
Ground faults on the transformer secondary are seen as ground faults on the primary since
the zero sequence (neutral) current passes directly through the transformer, making relay
protection difficult. With a delta-wye transformer, the secondary ground faults do not cause
zero sequence current to flow in the primary circuit.
On three-phase power systems, neutral current is the sum of the three line-to neutral currents.
With balanced three-phase linear currents consisting of sine waves spaced 120 electrical degrees
apart, the sum at any instant in time is zero, and so there is no neutral current. In most threephase power systems supplying single-phase loads however, there will be some phase current
imbalance and some neutral current. Small neutral current resulting from slightly unbalanced
loads does cause problems for typical power distribution systems. Nonlinear loads however,
such as rectifiers and power supplies, have phase currents which are not sinusoidal. The sum of
balanced, non-sinusoidal, three-phase currents can be substantially above zero. These nonsinusoidal components are referred to as harmonics.
Harmonics loading can result in waveform distortion. The triplen harmonics are of primary
concern since their effect on the fundamental waveform are additive.
Figure 1
Figure1 depicts three-phase fundamental waveforms space 120 degrees. It also shows the third
harmonic waveform. Note that the harmonic waveform is in phase with all three fundamental
waveforms and has the same phase relationship to the 2nd and 3rd fundamental waveforms as it
does with the 1st. With each positive half-cycle of the fundamental waveforms, there are two
positive half-cycles and one negative half-cycle of the harmonic waveform. The 3rd-harmonic
waveforms of three 120 degree phase-shifted fundamental frequency waveforms are therefore
in phase with one other. Further, since the angular displacement is at 120 degrees and the
triplen harmonics are comprised of the odd multiples of 3 (3, 9, 15, 21, etc.) all triplens would
precisely overlap and appear as a single, unified waveform.
Figure 2
Although the triplen harmonics waveform is uniform, the values of each are additive. Heavy
harmonic loading therefore can result in significant fundamental waveform distortion. Figure 2
depicts a single phase fundamental waveform with compound triplen harmonic loading. The
resultant distortion of the fundamental is significant.
Depending on the method of operation, load side equipment can be affected in a variety of ways
by the distortion of the fundamental waveform. Significant harmonic content can lead to
overheating in motors which may result in the degradation of insulation and loss of life. Other
equipment may be dependent on accurate waveshapes and may malfunction when harmonics
are present. Harmonics due to multiple single phase distorting loads can result in neutral
currents that exceed rated line current which in turn may result in a reduction in electrical
distribution system wiring life and the possibility of fire. For the transformer itself, unmanaged
harmonics may result in increased winding and core losses which may lead to overheating and
loss of service life due to gassing and degradation of the insulation system.
Transformers that are connected delta-delta, delta-wye, and wye-delta have balanced voltages
due to the absence of a floating neutral. A floating neutral is however the case with a wye-wye
connected transformer. The primary and secondary windings are connected in a wye
configuration with the neutral and phase winding terminated at the bushings. To accommodate
and mitigate the propagation of harmonics, a third winding connected in a delta configuration
can be buried as a tertiary (stabilizing) winding. The tertiary winding provides a circulating
path for the harmonics that are produced with the power frequency.
The addition of a delta connected tertiary winding within a wye-wye transformer provides a
path for the balancing current to flow when the secondary must supply an unbalanced load and
the neutral point on the primary winding cannot be connected to the system neutral. Without the
tertiary winding, an unbalanced load would result in a voltage shift on the secondary neutral and
nonsymmetrical voltages.
Figure 3
Figure 3 represents a wye-wye connected transformer with a buried tertiary winding. The
primary and secondary windings terminate at the transformers HV and LV bushings. It is not
necessary to terminate the delta connected tertiary external to the tank when it is used solely to
accommodate harmonic loading. The tertiary windings can however, be used to provide
supplemental power in which case they can be terminated on their own tank bushings.
The rating of the tertiary winding until recently has been managed casually by specifiers and
manufacturers. Recently however, the IEEE Transformers Committee met and approved the
following:
The group has been working for three years to resolve the subject of default kVA rating for
stabilizing windings. A new clause was prepared by the group for inclusion in C57.12.00, and the
following text was surveyed among the Performance Characteristics and Insulation Life
Subcommittees prior to this meeting.
5. 11.1.2 Thermal Rating for Stabilizing Windings (buried tertiary) In addition to the short circuit
duty stabilizing windings shall be designed to withstand the transient and continuous thermal
duty as specified by the user and in accordance with the allowable temperature limits of 5.11.1. In
the event no continuous thermal duty for the stabilizing winding can be established from the
users specification, the manufacturer shall design the stabilizing winding considering the
4
circulating current in that winding, resulting from a full single phase load in the largest main
secondary winding. The manufacturer shall determine kVA rating for the stabilizing winding based
on the transformers equivalent circuit for single phase loading condition.
In the event of a line to ground fault on primary or secondary, the fault current in the tertiary
winding will be 1/3 of that in the main winding. Therefore, to insure sufficient mechanical
withstand strength in the total winding, the tertiary winding capacity must be designed to equal
or exceed 1/3 of the transformer kVA.
Above is an image of a nameplate drawing for a transformer recently supplied by PCT. Note the
buried tertiary. The transformer was designed for generator step-up duty.
.