Carolprene 105 CWelding Cable Spec Sheet
Carolprene 105 CWelding Cable Spec Sheet
Carolprene 105 CWelding Cable Spec Sheet
Industrial Cord
Product Construction:
Conductors:
6 AWG through 4/0 AWG fully annealed
stranded bare copper per ASTM B-172
Jacket:
Carolprene 105C, black
Temperature Range: -50C to +105C
Jacket Marking:
CAROLPRENE 105C WELDING CABLE 600 VOLT 30 AWG STRANDING
mm
APPROX.
NET WT.
LBS/M'(S)
STD.
CTN.
0.430
10.92
152
1000'
418/30
0.475
12.07
215
1000'
646/30
0.540
13.72
296
1000'
NOMINAL O.D.
CATALOG
NUMBER
AWG
SIZE
NOMINAL
STRAND
INCHES
01758*
259/30
01757*
01756*
01755*
836/30
0.580
14.73
360
1000'
01754*
1/0
1032/30
0.615
15.62
424
1000'
01753*
2/0
1290/30
0.655
16.64
513
1000'
01752*
3/0
1672/30
0.720
18.29
644
1000'
01751*
4/0
2066/30
0.780
19.81
824
1000'
(S)
length in feet for total circuit for secondary voltages only do not use this table for 600 Volt in-line applications
100'
150'
200'
250'
300'
350'
400'
4
4
2
2
1
1/0
1/0
4
2
1
1/0
2/0
3/0
3/0
2
1
1/0
2/0
3/0
4/0
4/0
1
1/0
2/0
3/0
4/0
1/0
2/0
3/0
4/0
1/0
3/0
4/0
2/0
3/0
2/0
4/0
3/0
4/0
3/0
4/0
4/0
REQUIRED CABLE SIZES SHOWN IN AWG NUMBERS
The total circuit length includes both welding and ground leads (based on 4-volt drop) 60% duty cycle.
These values for current-carrying capacity are based on a copper temperature of 60C (140F), an ambient temperature
of 40C (104F) and yield load factors from approximately 32% for the No. 2 AWG cable to approximately 23% for
the No. 3/0 AWG cable, and higher for the smaller sizes. The sizes of cables generally used range from No. 2 AWG to
No. 3/0 AWG. In actual service, the load factor may be much higher than indicated without overheating the cable, as the
ambient temperature will generally be substantially lower than 40C.
Applications:
Secondary voltage resistance welding leads
in heavy duty or mining applications
Power supply applications not exceeding
600 volts AC
Sizes 1/0 and larger for permanent wiring
in conduit or tray of 600 V power supplies,
hoists, cranes or other applications where
flexible power leads must be installed in
conduit, raceways or trays
Features:
Water-resistant
Sunlight-resistant
Designed to withstand severe environmental
conditions
Withstands exposure to oil, acids, alkalies,
heat, flame, moisture and chemicals
Meets or exceeds flame test requirements
of MSHA
TRU-Mark marking system and indent
printed MSHA number
Industry Approvals:
MSHA Approved
RoHS Compliant
Packaging:
250' (76.2 m), 1000' (304.8 m) reels
Other put-ups available on special order
Suggested Ampacities
For 600 Volt In-Line Applications
AWG
AMPERES
AWG
AMPERES
4/0
405
220
3/0
350
190
2/0
300
140
1/0
260
105