NW S11 Arc Energy
NW S11 Arc Energy
NW S11 Arc Energy
Arc -Energy
Mitigation Techniques
B y J o h n Cad ick, PE Cadick Corporation
COVER STORY
OK youve done the engineering study and you know the arc-energy levels at all
of your switchgear, panelboards, and other such equipment. Some of the locations
in your facility have unacceptably high incident energy levels. What this means to
any given facility depends somewhat on local philosophy; however, it is a safety
imperative to reduce incident energy levels to the lowest possible value and/or
eliminate the exposure of your workers.
Ideally you would like all incident energy
levels to be zero not a realistic goal. Some
would like to have no incident energies above
8 cal/cm2 or some other low goal. Unfortunately,
your study shows some locations with incident
energy levels of well over 15 cal/cm2, and some
locations are over 40 cal/cm2.
This article describes several techniques
of reducing exposure of your personnel to
high arc-energy levels. The several methods
described all fall into the following three,
broad categories:
Reducing the available arc-energy by
designing/redesigning your power system
Reducing personnel exposure by
designing/redesigning your power system
Reducing personnel exposure by
modifying and enforcing working
procedures.
You will probably find some of these techniques
to be useful in your system, building, or plant.
Others will not be feasible for you because
of work rules, physical plant limitations,
and/or economics. In any event this article
presents several common and not-so-common
techniques that should be considered by you
and/or your engineering consultant.
Where:
EMB = maximum incident energy received
from an arc occurring in a 20 in. cubic
box (cal/cm2)
DB = distance from arc electrodes in inches
(for distances 18 in. and greater)
tA = arc duration in seconds
F = short circuit current in kiloamperes
(for the range of 16 kA to 50 kA)
Equation 1 is one of several formulas that have
been developed by creating arcs in various
controlled environments and measuring the
resulting heat energy. Research in the area is
ongoing and will undoubtedly lead to changes
in the equations that we use; however, the basic
relationships will remain the same available
incident energy decreases as:
time of exposure (tA) decreases
arcing short-circuit current (F) decreases
NETAWORLD
COVER STORY
Figure 1
Refer to Figure 1 Short circuits that occur in zones 2 or 3 must be cleared by either the transformer
secondary breakers (Sec Bkrs) or other protective devices below the Sec Bkrs (not shown). Since
faster tripping times will provide better protection for the transformer, the ideal approach is to set
all protective devices in zones 2 and 3 to trip instantaneously. This solution will also decrease the
available incident energy a seemingly perfect solution.
However, tripping times should also provide selective
tripping. Selective tripping is defined as tripping the closest
protective device upstream of the location of the short
circuit. A fault that occurs below one of the transformer
feeder breakers (Zone 3) should trip the feeder breaker not
the main secondary breaker. This means the following:
Th
e secondary main breaker should
clear faults in Zone 2
Th
e feeder breakers should clear faults
in Zone 3
SPRING 2011
COVER STORY
NETAWORLD
COVER STORY
2
This is why workers
should always be taught to
stand to the side of
a breaker or switch when
it is operated.
3
Many are surprised to
learn that in classic designs
an arc blast is usually not
taken into account for
doors and/or panels.
Arc-Resistant Switchgear
Prior to the advent of arc-resistant switchgear,
virtually all gear was incapable of enclosing the
worst case arcing event. That is to say, if the
worst case arc were to occur, the switchgear
could sustain a rapid, noncoherent disassembly.
It could blow up. The failure point is usually
the front and/or back of the gear.2 Sometimes,
it didnt even take the worst case fault to cause
a failure.
Modern arc-resistant gear incorporates at least
three major features that greatly reduce the
possibility of such an explosive failure.
1. The internal bus structures are better
insulated to reduce the probability of a
sustained arcing event.
2. The construction materials and methods are
much sturdier than older designs. Stronger
metals, thicker walls, interlocking corners,
and heavy duty fasteners and hinges3 are
all employed. Figure 2 shows the door
construction used by one manufacturer for
their arc-resistant gear.
3. The gear has an internal venting system
that directs the by-products of the arc away
from the personnel. Usually it is directed
up and back.
Figure 2
SPRING 2011
COVER STORY
Reducing personnel exposure
by modifying and enforcing
working procedures
Remote Switching and Racking Appliances
Increasing distance from the arc location
will greatly reduce the incident energy.
From equation 1 we see that an increase in
distance will reduce the incident energy by the
1.4738 power.4
Figure 3
Figure 4
Chicken Switch is a
registered trademark of
MarTek, Ltd.
NETAWORLD
COVER STORY
Figure 5
SPRING 2011
Figure 6
Conclusion
I believe that any location with incident
energy over 15 cal/cm2 should be reviewed for
possible mitigation solutions.6
Usually solutions exist to reduce the maximum
incident energy at an exposure location in a
power system. For example, some say that it
is impossible to reduce the incident energy
of a fault occurring between a transformer
secondary and the first secondary protective
device. In fact the normally high, incident
energy in these locations can be mitigated.
Protective schemes such as transformer
differential or zone-interlocking protection
will provide instantaneous tripping for
transformer secondary faults. The cost of
mitigation may be high, but the cost of a
single injury or fatality will be much higher.
Some consultants, as a normal part of an
arc-flash study, will recommend changes in
protective device settings in areas where high
incident energies are present. In fact, system
owners should insist on this as a part of a
contracted study.
However, major redesign efforts are usually
beyond the scope of a contracted study.
Adding current limiting reactors, designing
remote control rooms, and checking the effects
of different protective devices are examples of
such out-of-scope efforts.
COVER STORY
If a study reveals locations where a simple
setting change is not sufficient, the system
owner should commission an engineering
review to determine which of the several design
options will provide the optimal incident
energy mitigation.
Procedural and PPE considerations should
be based on the results of an arc-flash study.
The use of PPE tables in NFPA 70E should be
limited to those locations where a study has not
been performed. However, for a given location,
this should be a temporary fix. The best and
safest approach is the arc-flash study.
NETAWORLD