Application Example - RED670 Relay
Application Example - RED670 Relay
Innovation
from
ABB
Content
Chapter
Page
3
RED 670 with built-in GPS clock for unspecified route switching ......................
3.1
Start up of the GPS system (cold start) .........................................................
3.2
Setting for version 1.0 and 1.1 revision 9 and earlier ....................................
3.3
Setting in version 1.1 revision 10 and later with new design of
the time system clock synchronization ..........................................................
3.4
Accuracy of the GPS system .........................................................................
3.5
Enabling of the echo timing according to application (I) ................................
3.6
Blocking of the echo-timing after GPS interruption........................................
3.7
Selectivity planning ........................................................................................
15
15
16
4
Digital signal communication for line differential protection RED 670 ...............
4.1
Configuration of analog signals - Line Data Communication
Module ...........................................................................................................
4.2
Configuration of LDCM output signals ...........................................................
4.3
Configuration of redundant channels.............................................................
21
5
Binary signal transfer for the 670 series ............................................................
5.1
Function block................................................................................................
5.2
Analog and binary input and output signals...................................................
5.3
Setting guidelines ..........................................................................................
30
31
31
32
17
19
19
19
19
22
23
25
7
Communication alternatives .............................................................................. 40
7.1
Fiberoptic communication interfaces with IEEE C37.94
international standard protocol ...................................................................... 41
7.2
Galvanic interface type X.21.......................................................................... 42
8
PDH telecommunication system .......................................................................
8.1
General communication requirements ..........................................................
8.2
Communication structure for IEEE C37.94 fiberoptic interface in 670 series
and 21-216 with G.703 64 kbit/s in a PDH-system .......................................
8.3
Service settings of 21-216.............................................................................
8.4
Start and usage.............................................................................................
8.5
Service settings of 670 series with G.703 co-directional...............................
8.6
Service settings of Transceiver 21-216 G.703 64 kbit ..................................
8.7
Grounding .....................................................................................................
Communication structure for the X.21 built-in
galvanic interface ..............................................................................................
9.1
Connection and Service settings of 670 series with X.21 galvanic interface
9.2
Check of settings on 670 series HMI and communication status..................
9.3
Supervision of the communication on the 670 series HMI ............................
47
47
47
48
51
52
53
53
55
55
55
57
10
This is an Application Example for Communication set-up for RED 670 Differential protection in telecommunication networks and the remaining IED 670 for binary signal
transfer.
Document number: 1MRK 505 197-UEN
Revision: D. Setting in version 1.1 revision 10 and later with new design of the time
system clock synchronization included.
Issue date: September 2008
Data subject to change without notice
We reserve all rights to this document, even in the event that a patent is issued and a
different commercial proprietary right is registered. Improper use, in particular reproduction and dissemination to third parties, is not permitted.
This document has been carefully checked. HOWEVER, IN CASE ANY ERRORS
ARE detected, the reader is kindly requested to notify the manufacturer at the address
below.
The data contained in this manual is intended solely for the CONCEPT OR product
description and is not to be deemed to be a statement of guaranteed properties. In the
interests of our customers, we constantly seek to ensure that our products are developed to the latest technological standards. As a result, it is possible that there may be
some differences between the HW/SW product and this application note.
Manufacturer:
ABB AB
Substation Automation Products
SE-721 59 Vsters
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
www.abb.com/substationautomation
RED 670
670 Differential
Differentialprotection
protection
and
telecommuniand
telecommunication
cation networks
General
General
1
There are two main application areas of telecommunication networks for the multiterminal current differential protection RED 670 for up to 5 line ends.
(I) Telecommunication networks with symmetric or fixed routes, where echo timing can be used, including back-to-back systems.
(II) Telecommunication networks with unspecified route switching, where the
accurate global time in the Global Positioning System (GPS) is required.
Echo-timing according to (I) will be used as fall back system if the GPS reference is
lost in one or more RED 670s in telecom networks type (II).
Note that for Echo-timing, the internal clock in each RED 670 is used as a master and
compared with the internal clocks in the remote RED 670s as slaves. The difference
and drift between the internal clocks are monitored continuously, and compensated for
with echo messages between all ends with 40 ms intervals over the communication
system. At start, it will take around 15 seconds to get full synchronization of the internal clocks. The deviation between the internal clocks are compensated to be within 1
s relative time.
Note also that the internal clock has an additional function as real time clock for other
protection and monitoring functions such as event timing, but this is totally separate
from the current differential function.
For networks with unspecified route switching, the reference for the internal clock is
Global time, for example the global time in the GPS system from a built-in GPS
receiver. The internal clock in each RED 670 will be set according to the global time
from the GPS system. The inaccuracy depends on connection time to the GPS system.
After start-up (cold start) a software calibration procedure is carried out. After less
than one hour, all internal clocks real time deviation from Global time has been
decreased to 1 s.
Note also, there can only be one master clock in the telecommunication system for
synchronization of the multiplexers, transceivers and the differential protection relays
communication modems. (One master, the other slaves) This clock could also be a
GPS clock but the telecommunication network synchronization is totally separate from
the current differential protection internal clock synchronization.
General
The differential protection can be configured as master-slave or master-master. To configure the differential protection to slave, the differential protection is switched off.
The configuration of the communication system is not affected by the protection configuration.
1.1
Other systems
> x Gbit/second
ATM/IP systems
> 622 Mbit/second
SDH systems
> 2 Mbit/second
PDH systems
< 2 Mbit/second
RED
670
RED 670
670 Differential
Differentialprotection
protection
and
telecommuniand
telecommunication
cation networks
1.2
General
A
RED
670
Protection
slave
*Depending on required sensitivity
B
RED
670
Protection
master
RED
670
Protection
slave
en07000221.wmf
1.3
General
1.4
RED 670
670 Differential
Differentialprotection
protection
and
telecommuniand
telecommunication
cation networks
General
e n 0 7 0 0 0 2 2 3 .v sd
General
With an SDH System (>2 Mbit), e.g. G.703 E1, and acceptable small asymmetric
delay, the value 2 x 300 s can be used. With a PDH (nx64 kbit) system and a buffer
memory of for example 100 s, a typical maximum deviation is 2x 400 s. The setting should be calculated accordingly. For example increased minimum operate current for increased deviation.
Thus, a route switching, which causes a virtual difference between the internal clocks
in the respective RED 670s due to asymmetry in the communication channel delay, jitter and wander and buffer memory, below the set maximum clock deviation is not
causing any communication failure alarm or blocking of the differential trip function.
It is considered to be within the accuracy requirements and will be compensated for by
the normal synchronization mechanism for the internal clocks.
If the route switching takes longer time than 2 seconds, the master and slave terminal
will start to re-synchronize, after a delay of 4 seconds, with the new channel asymmetry incorporated. The synchronization will adjust the internal clock difference compared to the internal clocks in RED 670 in other line ends within 1 s. The time
synchronization messages are evaluated every 5 ms. With setting of 200 s maximum internal clock deviation between the respective RED 670s, it will take around 10
seconds to reach a new synchronization. The synchronization will reach 1 s accuracy after additional 10-15 seconds.
1.5
10
RED 670
670 Differential
Differentialprotection
protection
and
telecommuniand
telecommunication
cation networks
General
1.6
11
General
1 ms
6000
0.8 ms
4500
0.6 ms
3000
0.4 ms
1500
0.2 ms
0%
0
10
15
20
kA
en07000225.wmf
12
Echo
timingfunction
function
Echo timing
General
See the oscillogram in Figure 5 for explanations of dead band D, measured change dt
and scattering (deviation in calculation), inside the set deadband.
dt
D
en07000226.wmf
Figure 5: Deadband
dt
Scattering
13
General
en07000227.vsd
Figure 6: DeadbandtDiff
DeadbandtDiff equals dead band time difference. This setting is used to compensate
for measuring inaccuracy due to scattering when accumulating changes smaller than
MaxtDiffLevel.
After blocking by MaxtDiffLevel the communication set up must be checked before
restarting.
14
RED 670
670 with
withbuilt-in
built-inGPS
GPSclock
clock
unspecified
forfor
unspecified
route
route switching
General
Td = 40 ms (forward + reverse)
(Protection master-slave)
GPS
clock
RED
670
Unspecified
route
switching
GPS
clock
C
A
B
RED
670
RED
670
GPS
clock
en07000160.vsd
3.1
15
3.2
General
Fast or Slow
Slow
Fast
Fast
In service
Echo timing and no GPS
Slow(< 3h to synchronize with external time source)
GPS and echo timing as back-up Slow (< 3h to shift to GPS from echo)
GPS
Fast (<10 min diffblock at start-up)
If the echo timing has been enabled as back-up for the GPS system, the RED 670 internal clock can not deviate more than +/- 50 s/s, which is the maximum adjustment rate
of the internal clock, depending on the echo timing adjustment capability in a 64 kbit
communication system.
This limitation is not valid for echo timing without GPS.
Note:
Set the course time synchronizing source (CoarseSyncSrc) to OFF when GPS time
synchronization of line differential function is used.
Set the fine time synchronization source (FineSyncSource) to GPS. The GPS will thus
provide the complete time synchronization.
GPS alone shall synchronize the analogue values in such systems.
No other external time synchronizing source is allowed including minute pulse, not
even as back-up in version 1.1 rev 9 and earlier.
This limitation is eliminated in version 1.1 rev 10 and later.
16
RED 670
670 with
withbuilt-in
built-inGPS
GPSclock
clock
unspecified
forfor
unspecified
route
route switching
3.3
General
Setting in version 1.1 revision 10 and later with new design of the
time system clock synchronization
The time system is based on a software clock, which can be adjusted from external
time sources and a hardware clock. The protection and control modules will be timed
from a hardware clock, which runs independently from the software clock. See
figure below.
External
Synchronization
sources
Off
LON
SPA
Min. pulse
GPS
SNTP
DNP
IRIG-B
PPS
TimeRegulator
(Setting,
see TRM)
Events
Protection
and control
functions
SW-time
Connected when GPS-time
is used for differential protection
TimeRegulator
(Fast or
slow)
Synchronization for
differential protection
(ECHO-mode or GPS)
HW-time
A/D
converter
Diff.
commu
-nication
Transducers*
*IEC 61850-9-2
en08000287.vsd
17
General
The synchronization of the hardware clock and the software clock is necessary
only when GPS or IRIG B 00X with optical fibre, IEEE 1344 is used for differentialprotection. The two clock systems are synchronized by a special clock synchronization
unit with two modes, fast and slow. A special feature, an automatic fast clock time regulator is used. The automatic fast mode makes the synchronization time as short as
possible during start-up or at interruptions/disturbances in the GPS timing. The setting
fast or slow is also available on the HMI and can be used for example during commissioning or maintenance.
If a GPS clock is used for other products in the 670-series than current differential
RED 670, the hardware and software clocks are not synchronized.
Fast clock synchronization mode
At start-up and after interruptions in the GPS or IRIG B time signal, the clock deviation between the GPS time and the internal differential time system can be substantial.
A new start-up is also required after for example maintenance of the auxiliary voltage
system.
When the time difference is >16 s, the differential function is blocked and the time
regulator for the hardware clock is automatically using a fast mode to synchronize the
clock systems. The time adjustment is made with an exponential function, i.e. big time
adjustment steps in the beginning, then smaller steps until a time deviation between the
GPS time and the differential time system of <16 s has been reached. Then the differential function is enabled and the synchronization remains in fast mode or switches to
slow mode, depending on the setting.
Slow clock sychronization mode
During normal service, a setting with slow synchronization mode is normally used,
which prevents the hardware clock to make too big time steps, >16 s, emanating from
the differential protection requirement of correct timing.
The time for reaching + 16s deviation, is depending on the adjustment range and
adjustment rate. As the internal clock in the RED670 can be up to 0.5 seconds wrong
after setting the time in seconds (integers) mentioned earlier, the time for reaching +
16s can be up to 10 minutes or up to 3 hours depending on the setting of the adjustment rate.The adjustment of the synchronization of the RED 670 internal clock to the
global time in the GPS system has two modes, Fast or Slow. The mode can be selected
in the HMI or PCM 600, for version 1.0 and 1.1. (In version 1.1 revision 10 or later an
automatic setting is introduced), see HMI window below.
The Fast setting has 1 ms/s second adjustment rate.
The Slow setting has + 50 s/s second adjustment rate.
If the echo timing has been enabled as back-up for the GPS system, the RED 670 internal clock can not deviate more than +/- 50 s/s, which is the maximum adjustment rate
of the internal clock, depending on the echo timing adjustment capability in a 64 kbit
communication system.
This limitation is not valid for echo timing without GPS.
18
RED 670
670 with
withbuilt-in
built-inGPS
GPSclock
clock
unspecified
forfor
unspecified
route
route switching
3.4
General
3.5
3.6
3.7
Selectivity planning
A missed protection message due to for example bit errors, prolongs the tripping time.
Maximum interruption time and bit error rate should be part of the selectivity planning.
19
20
General
Introduction
RED
670
64 kbit/s (duplex)
RED
670
en07000169.vsd
RED
670
64 kbit/s (duplex)
RED
670
64 kbit/s (duplex)
en07000170.vsd
21
Introduction
In RED 670, the bias current is considered the greatest phase current in any line end
and it is common for all three phases. When sending full information from both local
CTs to the remote end, as shown in Figure 10, this principle works, but when the two
local currents are added together before sending the single resulting current on the single communication channel, information about the real phase currents from the two
local CTs will not be available in the remote line end.
Whether it will be possible to use one communication channel instead of two (as
shown in Figure 10) must be decided from case to case. It must be realized that correct
information about bias currents will always be available locally, whilst only limited
information will be available at the end, that receives the limited information over only
one channel.
For the configuration of redundant channels see Section 4.2 page 23. For further information see Chapter Remote communication, in Application manual.
4.1
22
Currents
from local CT
Introduction
AD
/
LDCM 1
Currents from
remote end 1
Currents to
remote end 1
LDCM 2
Currents from
remote end 2
Currents to
remote end 2
PR
L3D
( PreProcessing
Block )
( Line
Differential
Function )
en07000230.vsd
Figure 11: Typical configuration of the analog signals for a three ended line
Figure 11 shows how one IED in a three ended line differential protection can be configured. Especially notice that there are two LDCMs, each one supporting a duplex
connection with a remote line end. Thus, the same local current is configured to both
LDCMs, whilst the received currents from the LDCMs are configured separately to the
line differential function.
4.2
23
SI
Introduction
en06000638.vsd
SMBI
Figure 12: Example of LDCM signals as seen in the Signal matrix tool
24
Multiplexer
Introduction
Multiplexer
Telecom.
Network
LDCM
LDCM
CM
LLDDC
M
CM
D
L DC
L M
C
LDDCM
L M
CM
LDDC
L M
en07000228.wmf
4.3
Telecom.
Network
L
DC
L M
DC
M
DC
L M
DC
M
Telecom.
Network
Primary channel
Secondary redundant (reserve) channel
en07000229.wmf
25
Introduction
Note:
Main and redundant channel is placed on the same base card in slot 303-302, 313312 and 323-322. For more details, see Figure 15.
26
Introduction
en07000231.wmf
27
Introduction
en07000232.wmf
28
Introduction
e n 0 7 0 0 0 2 3 3 .v s d
Figure 18: Setting example of RED 670 with redundant channel (two duplex channels)
29
Introduction
RED
670
64 kbit/s (duplex)
RED
670
en07000169.vsd
en07000234.vsd
Figure 20: Setting example of RED 670 with one communication channel for binary
transfer
30
5.1
Introduction
Function block
Note!
The function blocks are not represented in the configuration tool. The signals appear
only in the SMT tool when a LDCM is included in the configuration with the function
selector tool. In the SMT tool they can be mapped to the desired virtual input (SMBI)
in the 670 series and used internally in the configuration.
5.2
Binary signals
Communication slot
CRM- 1
CRB- 1
302
CRM- 2
CRB- 2
303
CRM- 3
CRB- 3
312
CRM- 4
CRB- 4
313
CRM- 5
CRB- 5
322
CRM- 6
CRB- 6
323
Table 2: Output signals for the LDCMRecBinStat (CRM1-) function block in analog mode (see also section 11, fault tracing)
Signal
Description
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
TRDELERR
SYNCERR
REMCOMF
31
Introduction
Table 2: Output signals for the LDCMRecBinStat (CRM1-) function block in analog mode (see also section 11, fault tracing)
Signal
Description
REMGPSER
SUBSTITU
LOWLEVEL
Table 3: Binary output signals for the LDCMRecBinStat (CRB1-) function block
in binary mode (see also section 11, fault tracing)
5.3
Signal
Description
COMFAIL
YBIT
NOCARR
NOMESS
ADDRERR
LNGTHERR
CRCERROR
REMCOMF
LOWLEVEL
Setting guidelines
Channel mode: This parameter can be set ON or OFF. If OFF is set with locally measured currents (analog inputs) trip and transfer trip will be issued. Besides this, it can be
set OutOfService which signifies that the local LDCM is out of service. Thus, with this
setting, the communication channel is active and a message is sent to the remote IED
that the local IED is out of service, but there is no COMFAIL and the analog and
binary values are sent as zero.
Note:
Only applicable for no-load conditions; for example during maintenance of a HVbreaker.
TerminalNo: This setting assigns a number to the local REX 670. Up to 256 REX 670
can be assigned unique numbers. For aline differential protection, maximum 6 IEDs
can be included. The possibility to use the large number of IED designations is
reserved for the case where a high security against incorrect addressing in multiplexed
systems is desired.
RemoteTermNo: this setting assigns a to the remote IED.
DiffSync: Here the method of time synchronization, Echo or GPS, for the line
differential function is selected.
32
Introduction
GPSSyncErr: If GPS synchronization is lost, the synchronization of the line differential function will continue during 16 s. based on the stability in the local 670 units
clocks. Thereafter the setting Block will block the line differential function or the setting Echo will make it continue by using the Echo synchronization method. It shall be
noticed that using Echo in this situation is only safe as long as there is no risk of varying transmission asymmetry.
CommSync: This setting decides the Master/Slave relation in the communication
system and shall not be mistaken for the synchronization of line differential current
samples. When direct fibre is used, one LDCM is set as Master and the other one as
Slave. When a modem and multiplexer is used, the REX 670 is always set as Slave, as
the telecommunication system will provide the clock master.
OptoPower: The setting LowPower is used according to table 7, page 37.
TransmCurr: This setting decides which of 2 possible local currents that shall be transmitted, or if and how the sum of 2 local currents shall be transmitted, or finally if the
channel shall be used as a redundant channel.
In a 1 breaker arrangement, there will be 2 local currents, and the grounding on the CTs can
be different for these. CT-SUM will transmit the sum of the 2 CT groups. CT-DIFF1 will transmit CT group 1 minus CT group 2 and CT-Diff2 will transmit CT group 2 minus CT group 1.
CT-GRP1 or CT-GRP2 will transmit the respective CT group, and the setting
RedundantChannel makes it possible to use the channel as a backup channel.
ComFailAlrmDel: Time delay of communication failure alarm. In communication systems, route switching can sometimes cause interruptions with a duration up to 50 ms.
Thus, a too short time delay setting might cause nuisance alarms in these situations.
ComFailResDel: Time delay of communication failure alarm reset.
RedChSwTime: Time delay before switchover to redundant channel in case of primary
channel failure.
RedChRturnTime: Time delay before switchback to the primary channel after channel
failure.
AsymDelay: the asymmetry is defined as transmission delay minus receive delay. If a
fixed asymmetry is known, the Echo synchronization method can be used if the parameter AsymDelay is properly set. From the definition follows that the asymmetry will
always be positive in one end, and negative in the other end.
Note:
A false asymmetric delay can be present when A/D converter revision 1 is used in one
terminal and A/D converter revision 2 is used in the other terminal. This will give a
differential current due to an angle discrepancy of 3-5.
33
Introduction
Setting example:
AsymDelay for RED 670 in end A is set 3 ms - 2 ms = 1 ms
AsymDelay for RED 670 in end B is set 2 ms - 3 ms = -1 ms
C*
2 ms delay
1 ms delay
A
RED
670
Tx
Rx
B
Rx
Tx
2 ms delay
RED
670
*The 3 ms delay in route A-C-B includes the delay in the multiplexer in end C.
The setting can be found under LDCM configuration/CRM-CRB/AsymDelay
en7000235.wmf
Setting parameters
34
Parameter
Range
Step
ChannelMode
Off
ON
OutOfService To be
used in multiterminal lines for example maintenance in
one end to avoid
communication failure and different
protect blocking in
remaining RED
670.
Default
Unit
Description
ON
Introduction
Parameter
Range
Step
Default
Unit
Description
TerminalNo
0 - 255
RemoteTermNo
0 - 255
Terminal number on
remote terminal
DiffSync
ECHO
GPS
ECHO
Diff Synchronization
mode of LDCM, 0=ECHO,
1=GPS
GPSSyncErr
Block
Echo
Block
CommSync
Slave
Master
Slave
Com Synchronization
mode of LDCM, 0=Slave,
1=Master
OptoPower
LowPower
HighPower
LowPower
TransmCurr
CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2
CT-GRP1
ComFailAlrmDel
5 - 500
10
ms
ComFailResDel
5 - 500
10
ms
RedChSwTime
5 - 500
ms
RedChRturnTime
5 - 500
100
ms
AsymDelay
-20.00 - 20.00
0.01
0.00
ms
MaxTransmDelay
0 - 40
20
ms
CompRange
0-10kA
0-25kA
0-50kA
0-150kA
0-25kA
Compression range
MaxtDiffLevel
200 - 2000
600
DeadbandtDiff
200 - 1000
300
InvertPolX.21
Off
ON
Off
35
Introduction
36
Parameter
Range
Step
Default
Unit
Description
ChannelMode
Off
ON
OutOfService
ON
TerminalNo
0 - 255
RemoteTermNo
0 - 255
Terminal number on
remote terminal
DiffSync
ECHO
GPS
ECHO
Diff Synchronization
mode of LDCM, 0=ECHO,
1=GPS
GPSSyncErr
Block
Echo
Block
CommSync
Slave
Master
Slave
Com Synchronization
mode of LDCM, 0=Slave,
1=Master
OptoPower
LowPower
HighPower
LowPower
TransmCurr
CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2
RedundantChannel
CT-GRP1
ComFailAlrmDel
5 - 500
100
ms
ComFailResDel
5 - 500
10
ms
RedChSwTime
5 - 500
ms
RedChRturnTime
5 - 500
100
ms
AsymDelay
(Refers to fixed
routes with known
asymmetric delay)
-20.00 - 20.00
0.01
0.00
ms
MaxTransmDelay
0 - 40
20
ms
CompRange
0-10kA
0-25kA
0-50kA
0-150kA
0-25kA
Compression range
MaxtDiffLevel
200 - 2000
600
DeadbandtDiff
200 - 1000
300
Introduction
Range
Step
Default
Unit
Description
InvertPolX.21
Off
ON
Off
Range
Step
Default
Unit
Description
ChannelMode
Off
On
OutOfService
On
TerminalNo
0 - 255
RemoteTermNo
0 - 255
Terminal number on
remote terminal
CommSync
Slave
Master
Slave
Com Synchronization
mode of LDCM, 0=Slave,
1=Master
OptoPower
LowPower
HighPower
LowPower
ComFailAlrmDel
5 - 500
10/100 depending
on version
ms
ComFailResDel
5 - 500
10
ms
InvertPolX.21
Off
On
Off
Note:
ComfailAlrmDel; COMFAIL Alarm Delay:
ComFailAlrmDel should be set 100 ms, in normal service. Route switching in telecommunication networks normally takes < 50 ms.ComFailResDelay should be set at
10 ms.
(For fault tracing it can be advantageous to set the ComFailAlrmDel at 5 - 10 ms.)
37
Communication channels
Introduction
Communication channels
Each 670 series device can be configured with up to four remote communication interfaces. The communication configuration for each channel is individually set.
Application examples:
Id>
Id >
e n 0 7 0 0 0 1 4 6 .v s d
Id>
Id >
M a in
R edundant
e n 0 7 0 0 0 1 4 7 .v s d
Figure 23: Two ended line with 1 1/2 breaker, redundant channels
38
Communication channels
Introduction
I d>
I d>
I d>
Id>
Id>
en07000148.vsd
39
Communication alternatives
Introduction
Communication alternatives
C 37.94 64 kbit/s communication module up to four
ports
670series
Fibre-optics
CB1
CB2
CB3
en07000236.wmf
No external summation
40
Communication alternatives
7.1
Introduction
Up to 4 modules type LDCM can be included. Three different types are available.
For Multimode fiberoptic 50/125 m or 62,5/125 m
for 2-3 km to telecommunication equipment (Can also
be used for back-to back applications 2-3 km), (850
nm)
For single mode fiberoptic 9/125 m for back to back
applications < 70 km (1300 nm)
For single mode fiberoptic 9/125 m for back to back
applications < 130 km (1550 nm)
Selection of high or low optical power, see Table 9.
en07000237.wmf
Table 7: Optical budget for 670 series: 64 kbit communication with C37.94
interface
Fiberoptic
communication
Modem type
Contact type
850 nm
850 nm
1310 nm
1550 nm
Multimode fiber
Glass 50/125 m
Multimode fiber
Glass 62,5/125 m
Single mode
Glass 9/125 m
Single mode
Glass 9/125 m
ST
FC/PC
FC/PC
-21 dBm
-17 dBm
-7 dBm
- 3dBm
Minimum receiver
sensitivity
-30 dBm
-30 dBm
-29 dBm
-29 dBm
Optical budget*
9 dB
13 dB
22 dB
26 dB
* The optical budget includes a satisfactory margin for aging in transmitter and
receiver during 20-30 years.
41
Communication alternatives
Introduction
850 nm
850 nm
1310 nm
1550 nm
Multimode fiber
Glass 50/125 m
Multimode fiber
Glass 62,5/125 m
Single mode
Glass 9/125 m
Single mode
Glass 9/125 m
3 db/km
0,32 dB/km
0,21 db/km
1,5 dB
1,5 dB
0,3 dB
0,3 dB
Factory splice
attenuation
0,5 dB/splice
0,3 splices /km
0,5 dB/splice
0,1 splices /km
0,08 dB/splice
0,1 splices /km
0,08 dB/splice
0,3 splices /km
Repair splices
0,25 dB/splice
0,1 splices /km
0,25 dB/splice
0,1 splices /km
0,1 dB/splice
0,05 splices /km
0,1 dB/splice
0,05 splices /km
0,1 db/km
0,1 db/km
0,01 db/km
0,01 db/km
Attenuation
850 nm
1310 nm
1550 nm
Multimode fiber
Glass 62,5/125 m
Single mode
Glass 9/125 m
Single mode
Glass 9/125 m
Maximum distance
2 km
3 km
60 km
110 km
Attenuation in
fiberoptic cables
6 dB
9 dB
19,2 dB
23,1 dB
2 Contacts
2 dB
2 dB
0,6 dB
0,6 dB
0,3 dB
0,45 dB
0,48 dB
0,48 dB
Repair splices
0,1 dB
0,3 dB
0,7 dB
0,7 dB
0,2 db
0,3 dB
0,7 dB
0,7 dB
Attenuation
8,6 dB
12,05 dB
21,68 dB
25,58 dB
9 dB
13 dB
22 dB
26 dB
0,4 dB
0,95 dB
0,036 dB
0,42 dB
6 dB
8 dB
15 dB
15 dB
Optical budget
Extra margin
Extra margin > set low
power
7.2
850 nm
Multimode fiber
Glass 50/125 m
42
Communication alternatives
Introduction
Example of applications:
Line differential protection
Binary signal transfer
7.2.1
Design
The galvanic X.21 line data communication module uses a ABB specific PC*MIP
Type II format.
en07000238.wmf
2 Ground pin
1
15
en07000239.wmf
43
Communication alternatives
Introduction
I/O
100k
100nF
Soft ground
en07000242.vsd
44
Communication alternatives
Introduction
X.21 Connector
7.2.2
Table
Pin number
Signal
Shield (ground)
TXD A
Control A
RXD A
Signal timing A
Ground
TXD B
10
Control B
11
RXD B
13
Signal timing B
5, 7, 12, 14, 15
Not used
Functionality
The data format is HDLC. The speed for the transmission of the messages used is 64
kbit/s.
A maximum of 100 meter of cable is allowed to ensure the quality of the data
(deviation from X.21 standard cable length).
Synchronization
The X.21 LDCM works like a DTE (Data Terminal Equipment) and is normally
expecting synchronization from the DCE (Data Circuit equipment). The transmission
is normally synchronized to the Signal Element Timing signal when a device is a DTE.
When the signal is high it will read the data at the receiver and when the signal is low
it will write data to the transmitter. This behaviour can be inverted in the control
register.
Normally an external multiplexer is used and it should act like the master.
When two X.21 LDCM is directly communicating with each other one must be set as a
master generating the synchronization for the other (the slave). The DTE signal
Element Timing is created from the internal 64 kHz clock.
The Byte Timing signal is not used in ABB devices.
45
Communication alternatives
7.2.3
46
Introduction
Technical data
Quantity
Range of value
Connector, X.21
Standard
CCITT X.21
Communication speed
64 kbit/s
Insulation
1 kV
100 m
Introduction
8.1
8.2
LOCAL
<10m
IED 670
C37.94
Transciever
21-216xx
Multi-mode
Fibre optic
<3km
PCM
PCM
Galvanic
connection
Interface
G.703
External clock
(Slave)
REMOTE
<10m
Internal clock
(Master)
Transciever
21-216xx
Galvanic
connection
Interface
G.703
IED 670
C37.94
Multi-mode
Fibre optic
<3km
External clock
(Slave)
en07000260.vsd
47
8.3
Introduction
en07000247.wmf
en07000248.wmf
48
RJ45 pin
Name
Direction
Tx+ (TIP-out)
Tx- (RING-out)
Rx+ (TIP-in)
Rx- (RING-in
Shield
Metal house
Introduction
Use a cable with twisted pairs and a high quality shield. Only foil shielding is not
enough.
Rx+ and Rx- should form one twisted pair - Tx+ and Tx- another twisted pair.
A Cat5 S/FTP-cable, /Shielded/Foil Twisted Pair) used for example in Ethernet communication is a good cable. The outer shield is a braided mesh around the cable. In
addition every twisted pair has a foil-shielding.
If a S7FTP patchcable for Ethernet is used, be aware that a cross-connected cable has
only the pairs on pin 1-2 and 3-6 cross-connected, the two remaining pairs are not
cross-connected.
Clock configuration switch
From 21-216 revision 2 and later, a rotary switch is added to the front panel, to ease
installation and testing.
When two 21-216 are used in a PDH or a PDH/SDH system the two 21-216 shall be
set as slaves, i.e. when external clock is used.
Back-to-back testing
For testing back-to-back with the G703 ports directly connected, one of the 21-216
shall be set as Master (internal clock).
8.3.1
49
Introduction
If both position 8 and 9 are left empty the internal clock in the 21-216 is selected.
For 21-216 R2, (revision 2), or later also a rotary switch on the front panel can be
used for clock synchronization configuration.
The rotary switch has 16 positions, (HEX-switch).
en07000249.wmf
en07000252.wmf
en07000251.wmf
Function
4-7
8-15
When a not used channel is selected or if both codir and fiber clock are selected, the
ERR-LED on the front panel is lit.
50
8.4
Introduction
8.4.1
LED-status
en07000254.wmf
Power
A green LED lit when power is connected to the unit.
RA
Remote Alarm. A red LED indicating that the remote unit has encounter a fault condition and has set A red LED indicating that the remote unit has encounter a fault condition and has set the Yellow Alarm bit in the IEEE C37.94 protocol.
LA
Local Alarm. A red LED indicating that the 21-206 has encounter a fault in the IEEE
C37.94 protocol -LOS Loss Of Signal. The Yellow Alarm bit is set in the outgoing
IEEE C37.94 protocol
ERR
Error. A red LED indicating that the 21-216 has detected an internal error.
The ERR-LED also indicates that not allowed setting of jumpers is made.
LF
Link Fiber. A green LED indicating that the 21-216 receives correct IEEE C37.94
frames, (no LOS).
LT
Link Twisted pair/G.703 codir. A green LED indicating that 21-216 receives G.703
codir 64kbit/s protocol.
51
Introduction
RxF
Receive data on Fiber. A green LED indicating that 21-216 receives data in IEEE
C37.94 format.
RxT
Receive data on twisted pair/G.703 codir. A green LEED indicating that 21-216
receives data in G.703 codir protocol.
Channel
For yellow LEDs representing the channel chosen by jumpers at installation.
The channel is calculated by adding the lit LEDs.
for example if LED 1 and LED 2 are lit 1+2=3 Channel 3 is chosen.
This means that data to/from G.703.codir-port is sent and received on the IEEE C37.94
protocol on the fiber.
Clock synchronization configuration
Clock synchronization configuration can be done on the fly with the rotary switch
on the front panel. Se chapter Service settings of 21-216
8.5
en07000255.vsd
52
8.6
Introduction
en07000256.wmf
Figure 36: 21-216 Fiber optic G.703 Codir - IEEE C37.94 Converter
There is only one setting that is required. The transceiver has to be set to external
clock. The rotating dip switch in position 0. For back-to-back testing one 21-216 has to
be set as master internal clock, rotary switch in position 2, (overrides settings of jumpers 8 and 9).
8.7
Grounding
The recommended grounding is - direct grounding (default setting). At ground loop
problems, the soft ground mode can be advantageous, see Figure 37 and Figure 38.
<10m between ground points
Outer shielding connected to
ground at both ends
Internal
electronics
PCM
21-216
Direct
ground
(Default)
For Soft ground
Remove jumper P4
See figure37
R= 100 k ohm
C= 100 nF
Internal
electronics
directly
grounded
Protective earth
screw (or any
screw, which
has good
ground
connection)
en08000073.vsd
53
Introduction
en07000253.vsd
There is a supervision on the 21-216 which can be used for fault tracing.
RA
Remote Alarm. A red LED indicating that the remote unit has encountered a fault condition and has set A red LED indicating that the remote unit has encountered a fault
condition and has set the Yellow Alarm bit in the IEEE C37.94 protocol.
LA
Local Alarm. A red LED indicating that the 21-206 has encountered a fault in the
IEEE C37.94 protocol -LOS Loss Of Signal. The Yellow Alarm bit is set in the outgoing IEEE C37.94 protocol
If IED 670 has a communication fail alarm and there is no indication for RA or LA on
the 21-216 then the communication interruption is in the telecommunication system.
54
Introduction
LOCAL
< 100 m
REMOTE
< 100 m
PCM
IED 670
IED 670
PCM
Built-in X.21
Galvanic
Interface
Built-in X.21
Galvanic
Interface
en07000259.wmf
9.1
9.2
Table 10: Basic general settings for the LDCMRecBinStat (CRM1-) function
Parameter
Range
Step
Default
Unit
Description
ChannelMode
Off
ON
OutOfService
ON
TerminalNo
0 - 255
RemoteTermNo
0 - 255
Terminal number on
remote terminal
55
Introduction
Table 10: Basic general settings for the LDCMRecBinStat (CRM1-) function
Parameter
Range
Step
Default
Unit
Description
DiffSync
ECHO
GPS
ECHO
Diff Synchronization
mode of LDCM, 0=ECHO,
1=GPS
GPSSyncErr
Block
Echo
Block
CommSync
Slave
Master
Slave
Com Synchronization
mode of LDCM, 0=Slave,
1=Master
OptoPower
LowPower
HighPower
LowPower
TransmCurr
CT-GRP1
CT-GRP2
CT-SUM
CT-DIFF1
CT-DIFF2
CT-GRP1
ComFailResDel
5 - 500
10
ms
RedChSwTime
5 - 500
ms
RedChRturnTime
5 - 500
100
ms
AsymDelay
-20.00 - 20.00
0.01
0.00
ms
MaxTransmDelay
0 - 40
20
ms
CompRange
0-10kA
0-25kA
0-50kA
0-150kA
0-25kA
Compression range
MaxtDiffLevel
200 - 2000
600
DeadbandtDiff
200 - 1000
300
InvertPolX.21
Off
ON
Off
After making these settings check the result on the HMI of the IED 670.
Look under Test/Function Status/Communication/Remote communication/
LDCM312/CRM3/ on both end terminals and verify that the result is OK. Received
100%, transmit 100%.
56
Introduction
9.3
9.3.1
During laboratory testing one of the 21-216 has to provide the timing. This is done by
removing the jumper on S14 EXT CLK in one of them. Remember to restore after testing.
21-16xx
(Local)
RED 670
(Local)
TX
RX
RX
TX
RJ
G.703
cable
<10 m
RED 670
(Remote)
21-16xx
(Remote)
RJ
RX
TX
TX
RX
Multi mode
Optical fiber
Multi mode
Optical fiber
E
en07000155.vsd
57
10
Introduction
10.1
10.1.1
Service settings with the port for 21-219 synchronized to the SDH system master clock
Setting up of a SDH system requires that the port for 21-219 is synchronized from the
actual SDH network master clock. Thus the SDH telecommunication multiplexer
(MUX) must be set to fulfil this. These settings are vendor dependent, but normally the
SDH MUX has to be set for retiming and the format according G.704 framed, structured, unstructured etc.
The format transparent cannot be used in SDH systems because no synchronization on
the 21-219 SDH port is available.
Communication structure:
670 series
Transceiver 21-219 Optical/electrical interface converter
SDH MUX = Multiplexer in the SDH system
58
LOCAL
Introduction
<10m
RED 670
Transciever
21-219
Multi-mode
Fibre optic
<3.5 km
Slaves
REMOTE
<10m
SDH
MUX
SDH
MUX
Galvanic
connection
Interface
G.703 E1
(2MB)
SDH
Master
Transciever
21-219
Galvanic
connection
Interface
G.703 E1
(2MB)
G704 (framed etc.)
RED 670
Multi-mode
Fibre optic
<3.5 km
In normal operation the 21-219 at both end of a line shall be configured for External
clock, thus the configuration switch at the front shall be in position 0, the led 1, 2, 4, 8
shall all be off.
10.1.2
Service settings with the SDH/PDH port synchronized from one of the 21-219
transceivers (PDH system)
The communication quality in PDH systems are normally not as good as in SDH systems due to less stable clocks as Master. The bit error rate is normally BER 10-6.
Set-up as PDH system requires that the synchronization is provided from an external
source, for example one of the 21-219 transceivers. Thus the SDH MUX must be set
not to interfere with the synchronization. This setting is normally fulfilled by setting
the SDH MUX in transparent mode.
Communication structure:
59
LOCAL
Introduction
<10m
RED 670
Transciever
21-219
SDH
MUX
SDH
MUX
Multi-mode
Fibre optic
<3.5 km Galvanic
connection
Interface
G.703 E1
(2MB)
Slave
REMOTE
<10m
21-219
Master
Multi-mode
Fibre optic
<3.5 km
Galvanic
connection
Interface
G.703 E1
(2MB)
Transparent
Slaves
(External clock)
en07000157.vsd
Local end Master 21-219; In normal operation the 21-219 master should be set for
Internal clock. Thus the configuration switch at the front shall be in position 1 and
LED 1 shall be lit. The LED 2, 4, 8 shall all be off.
Remote end Slave 21-219; In normal operation the 21-219 slave shall be configured
for External clock. Thus the configuration switch at the front shall be in position 0.
The LED 1, 2, 4, 8 shall all be off.
Both 670 series devices shall be set as slaves.
Note that the differential protection clock is a separate issue not involved in communication and always is set as Master for the differential protection, even if the differential
protection is configured Master - Slave.
60
10.1.3
Introduction
There is only one setting that is required. The 21-219 has to be set for external or internal clock, depending on configuration of the telecomsystem.
en07000245.vsd
10
6
en07000244.vsd
61
Introduction
Transceiver 21-219 has two channels which can be used for redundant communication,
see Figure 44 below.
en07000241.vsd
Configuration
Normal use
Normally no configuration is needed!
When two 21-219 are connected back-to-back, (E1 ports connected to each other), one
of the 21-219 should be set to Master mode.
62
Introduction
en07000249.wmf
en07000252.wmf
en07000252.wmf
LED
2
LED
3
LED
4
FUNCTION
63
10.1.5
Introduction
Signals on front
1
en07000246.vsd
64
10.1.6
Introduction
There is supervision on the 21-219 which can be used for fault tracing.
There are two red light emitting diodes on the front of the 21-219, LA (Local Alarm) if
there is some problem in 21-219, and RA (Remote Alarm) which is supervising the
fiber optic link from the 21-219 to the 670 series, see section 10.1.5 page 67.
If 670 series has a communication fail alarm and there is no indication for LA or Ra on
the 21-219, then the communication interruption is in the telecommunication system.
Grounding of 21-219
The interface protection circuitry in the 21-219 is based on the requirement that the telecommunication multiplexer (MUX) interface is directly or low resistive grounded to
the same ground as the grounding screw on the front of the 21-219. There is no overturned protection in 21-219. If there is a potential difference between the 21-219
ground and the MUX ground it will result in a current flowing in the outer shield of the
connecting cable that may damage the cable and degrade the system functionality with
bite errors as a consequence.
Thus a correct grounding is essential, with the coaxial cables outer shield grounded to
the chassi via the BNC contacts at both ends, see Figure 48.
< 10 m
B N C co n tac ts w ith th e s cre e n
co n n ec te d d ire c tly to c ha s si (g rou n d )
T ra n s c e iv e r
2 1 -2 1 9
TX
RX
RX
TX
SDH
MUX
C oa x ia l ca b les
G ro u n d ing
s cre w o n fro nt
Im po rta n t: P o w e r su p ply
fro m the sa m e b atte ry .
e n 07 0 0 0 15 8 .v sd
Figure 48: Coaxial cables outer shield grounded to the chassi at both ends
65
Introduction
The same setting as for 21-216 are used, see Section 10.1.3 page 61.
Communication structure for laboratory testing
During laboratory testing back-to-back one of the 21-219 must be set as Master. This is
done by turning the configuration switch to pos 1 "EXT CLK" on one of them, LED 1
shall be lit and LED 2, 4, 8 shall be off.
66
Introduction
11
11.1
SMT/ CRM and CRB: Signal Matrix Tool connection number to connect information
to for example the event recorder.
Window
Remote communication/LDCM(slot)/CRM for RED 670 and /CRB for the 670 series
HMI Info
Signal Name
Normal
Faulty
Specification
(Example) (Example)
TransmDelay in 2 ms
Echo mode 1)
Transmission
delay in GPS
mode 1)
2 ms
NoOfShInterr
50
Time
Time
Counter
67
11.1.1
Introduction
IED A
IED B
ECHO mode
Settings in IED A
Settings in IED B
asymDelay
-3.10 ms
asymDelay
3.10
transmDelay
0.400 ms
transmDelay
3.50
asymDelay
asymDelay
transmDelay
0.4 ms
transmDelay
3.500 ms
asymDelay
-3.1 ms
asymDelay
3.100 ms
HMI Info
68
Signal Name
NoOfMEDInterr 10
Counter
No of medium interruptions,
50-150 ms
NoOfLongInterr 5
Counter
CommStatus
OK
NoRXD
Status
Communication status/no of
received messages
COMFAIL
Status
NoOfTXD
100.000
<100
Status %
No of sent messages
NoOfRXD
100.000
<75*
Status %
No of received messages
Ybit
Status
AsymDelay 1)
0,5 ms
Setting/GPS
ms
19
19
13
13
HMI Info
NOCARR
Introduction
Signal Name
0
25
Status
24
24
ADRERR
Status
14
14
LNGTHERR
Status
23
CRCERROR
Status
15
TRDELERR**
Status
N.A**
SYNCERR**
Status
N.A**
REMCOMFAIL
Status
18
18
REMGPSER**
Status
20
N.A**
SUBSTITU**
Status
N.A**
LOWLEVEL
Status
26
15
* Around 75 % RXD is typical if for example two Master clocks are present in the
communication system
** Only in RED 670
11.2
69
Introduction
If IED 670 has a communication fail alarm and there is no indication for LA or Ra on
the 21-216, then the communication interruption is in the telecommunication system.
11.3
11.4
70
Introduction
Note:
For loop-back tests with X21 galvanic interface special procedures and equipment is
needed. Contact your local ABB representative.
71
72
Introduction
Appendix 1
Sample specification of communication requirements for differential protection RED 670 and
the 670 series protection and control terminals in digital telecommunication networks
73
Appendix 1
Sample specification of communication requirements for differential protection RED 670 and the
670 series protection and control terminals in digital telecommunication networks
Both channels must have the same route with maximum asymmetry of 0,2-0,5
ms, depending on set sensitivity of the differential protection.
A fixed asymmetry can be compensated (setting of asymmetric delay in built in
HMI or the parameter setting tool PST).
IED 670 with GPS clock
Independent of asymmetry.
74
Appendix 2
Related documents
Related documents
Documents related to RED 670
Identity number
Operators manual
Application manual
Buyers guide
Connection diagram, Single breaker arr. Three phase tripping 1MRK 002 801-BA
arr.
Connection diagram, Single breaker arr. Single phase tripping 1MRK 002 801-CA
Connection diagram, Multi breaker arr. Three phase tripping
arr.
Configuration diagram A, Single breaker with single or double 1MRK 004 500-82
busbars
Configuration diagram B, Single breaker with single or double 1MRK 004 500-83
busbars
Configuration diagram C, Multi breakers such as 1 1/2 or ring 1MRK 004 500-84
busbar arr.
Configuration diagram D, Multi breakers such as 1 1/2 or ring 1MRK 004 500-85
busbar arr.
Setting example 1, 230 kV Short cable line with 1 1/2 CB arr
Identity number
Operators manual
Application manual
Buyers guide
Connection diagram, Single breaker arr. Three phase tripping 1MRK 002 801-BA
arr.
75
Appendix 2
Related documents
Connection diagram, Single breaker arr. Single phase tripping 1MRK 002 801-CA
arr.
Connection diagram, Multi breaker arr. Three phase tripping
arr.
Configuration diagram A, Single breaker with single or double 1MRK 004 500-86
busbar, 3 pole tripping (A31)
Configuration diagram B, Single breaker with single or double 1MRK 004 500-87
busbar, 1/3 pole tripping (A32)
Configuration diagram C, Multi breaker such as 1 1/2 or ring
busbar arr. 3 pole tripping (B31)
Setting example 1, 400 kV Long overhead power line with 1 1/ 1MRK 506 267-WEN
2 CB arr. Quadrilateral characteristic.
Setting example 2, Setting example 1, 400 kV Long overhead 1MRK 506 291-WEN
power line with 1 1/2 CB arr. Mho characteristic.
Setting example 3, 230 kV Extremely long overhead power
line, double bus, single CB arr. Quadrilateral characteristic.
Setting example 5, 132 kV Short overhead power line, double 1MRK 506 269-WEN
bus, single CB arr. Quadrilateral characteristic.
Setting example 6, 132 kV Short overhead power line, double 1MRK 506 290-WEN
bus, single CB arr. Mho characteristic.
Setting example 7, 70 kV power line on a resonance earth
system. Double bus, single breaker arrangement.
Setting example 8, 400 kV long series compensated line. 1 1/ 1MRK 506 294-WEN
2 breaker arrangement.
76
Identity number
Operators manual
Application manual
Buyers guide
Appendix 2
Related documents
Identity number
Operator's manual
Application manual
Buyer s guide
Configuration diagram B, Two winding transf. in multi breaker 1MRK 004 500-94
arr. on one or both sides (A40)
Configuration diagram C, Three winding transf. with single or 1MRK 004 500-95
double busbar but with a single breaker arr. on both sides
(B30)
Configuration diagram D, Three winding transf. in multi
breaker arr. on one or both sides (B40)
Configuration diagram E, Two or three winding transf., backup protection package (A10)
Configuration diagram F. Tap changer control package for two 1MRK 004 500-140
parallel transformers. (A25)
77
Appendix 2
Related documents
Configuration diagram F. Tap changer control package for four 1MRK 004 500-140
parallel transformers. (A25)
78
Identity number
Operators manual
Application manual
Buyers guide
Identity number
Operators manual
Application manual
Buyers guide
Setting example
Identity number
SPA and LON signal list for IED 670, ver. 1.1
IEC 61850 Data objects list for IED 670, ver. 1.1
1KHA001027-UEN
Appendix 2
Related documents
1MRS755552
1MRB520004-BEN
Note:
Latest versions of the described documentation can be found at
www.abb.com/substationautomation.
Fibersystem 21-216 manual at www.fibersystem.se
Fibersystem 21-219 manual at www.fibersystem.se
79
Appendix 2
Related documents
80
ABB AB
Substation Automation Products
SE-721 59 Vsters
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
Internet: www.abb.com/substationautomation