Mid m1000 Man
Mid m1000 Man
Mid m1000 Man
ModMAG M1000
INSTRUCTION AND
OPERATION MANUAL
June 2008
MID_M1000_BA_02_0806.doc
Contents
Page
3.2
General....................................................................................................................... 3
3.1.1
3.1.2
3.1.3
Transportation................................................................................................. 4
Mounting..................................................................................................................... 4
3.2.1
Mounting position............................................................................................ 4
3.2.2
3.2.3
Mounting location............................................................................................ 5
3.2.4
3.2.5
Remote version............................................................................................... 7
3.2.6
3.2.7
3.2.8
3.2.9
4. Electrical connection......................................................................................................... 9
4.1
Power ......................................................................................................................... 9
4.2
4.3
6.2
Size............................................................................................................... 16
6.1.2
Detector constant.......................................................................................... 16
6.1.3
6.1.4
6.1.5
6.1.6
Password ...................................................................................................... 17
Measuring................................................................................................................. 18
6.2.1
6.2.2
6.2.3
Full scale....................................................................................................... 19
6.2.4
6.2.5
Flow direction................................................................................................ 19
Contents
6.3
Page
6.2.6
Filter (damping)............................................................................................. 19
6.2.7
Outputs..................................................................................................................... 20
6.3.1
Analog output................................................................................................ 20
6.3.2
6.3.2.2
Pulse output.................................................................................. 21
6.3.2.3
Frequency output.......................................................................... 23
6.3.2.4
Setpoint ........................................................................................ 23
6.3.2.5
Digital input................................................................................... 24
6.3.2.6
Preselection.................................................................................. 24
6.3.2.7
6.3.2.8
6.4
6.5
Info/help.................................................................................................................... 26
6.6
6.5.1
6.5.2
6.5.3
6.5.4
8.2
9. Technical data.................................................................................................................. 30
9.1
9.2
9.3
9.4
9.5
9.6
Page 1/39
MID_M1000_BA_02_0806.doc
Description
Page 2/39
2. Description
The electromagnetic flow meters are ideally suited for flow measurement of all liquids with
a minimum conductivity of 5 S/cm. These meters are very accurate and the flow
measurement is independent of density, temperature and pressure of the medium.
Measuring principle
The operating principle of the electromagnetic flow meter is based on Faraday's law of
magnetic induction: The voltage induced across any conductor, as it moves right angles
through a magnetic field, is proportional to the velocity of that conductor. The voltage
induced within the fluid is measured by two diametrically opposed internally mounted
electrodes. The induced signal voltage is proportional to the product of the magnetic flux
density, the distance between the electrodes and the average flow velocity of the fluid.
MID_M1000_BA_02_0806.doc
Installation
Page 3/39
3. Installation
Warning:
3.1 General
3.1.1
Temperature ranges
Amplifier
Ambient temp.
Detector
Medium temp.
3.1.2
-20 up to + 60 C
PTFE / PFA
-40 up to +150 C
Hard rubber
0 up to +80 C
Soft rubber
0 up to +80 C
Protection class
In order to guarantee the requirements of the protection class, the following points
have to be followed:
Attention: Housing seals have to be undamaged and in a clean condition.
All housing screws have to be tightened.
The outside diameter of the used connection cables have to
correspond with the cable insertions (at PG 13.5 5....15 mm).
At non use of the cable insertion use a filler plug.
Cable insertions have to be tightened.
If possible lead the cable away downwards. Humidity can not reach
the cable insertion.
MID_M1000_BA_02_0806.doc
Installation
3.1.3
Page 4/39
Transportation
Attention: All detectors larger than DN 150 are equipped with lifting eyes. For
transportation or lifting of the meter you have to use them.
Do not lift the meters at the amplifier or detector neck.
Do not lift the detectors at the sheet casing with a fork lift truck,
because the housing will be pushed in.
Do not lead lifting devices (rope, forks of a lifter, etc.) through the
tube, otherwise the lining will be damaged.
Mounting
In order to secure the function of the meter in full range, as well as to avoid
damages, following mounting recommendations have to be observed.
Attention: The meter has to be mounted in the pipeline according to the flow
direction sign on the nameplate.
3.2.1
Mounting position
The meter can be mounted in any position. The meter can be mounted in horizontal
as well as vertical pipelines.
At vertical mounting the flow direction is to be provided upwards. Carried solid
particles are sinking downwards.
At horizontal mounting you have to pay attention that the measure electrodes are
lying in a horizontal level. Carried gas bubbles could otherwise lead to a short time
isolation of the measure electrodes.
The meter has to be mounted in the pipeline according to the flow direction sign on
the nameplate.
3.2.2
> 2 x DN
BA74MID
3.2
MID_M1000_BA_02_0806.doc
Installation
3.2.3
Page 5/39
Mounting location
Attention: The detector should not be installed on the suction side of a pump,
otherwise there will be danger of damage to the liner (especially
PTFE liner) by depression.
Please be careful that the pipeline at the measuring point is always
fully filled, otherwise no correct or accurate measuring is possible.
Do not install the detector at the highest point of a system of pipes,
otherwise there will be danger of gas accumulation.
Do not install in a downpipe with following free discharge.
BA75MID
BA76MID
h > 2 x DN
>2
MID_M1000_BA_02_0806.doc
BA78MID
N
xD
BA77MID
-5
>3
xD
Installation
3.2.4
Page 6/39
Size reduction
By using pipe adaption pieces according to DIN 28545 the detectors can be
mounted in pipelines of larger sizes.
The emerging pressure drop can be determined with the depicted nomogram (only
for liquids with a similar viscosity like water).
At very low flow rates the flow rate can be increased by reducing the
size at the measuring point and therefore the measuring accuracy
can be improved.
ma
x .8
Notice:
BA87MID
D = Pipe
d = Detector
MID_M1000_BA_02_0806.doc
Installation
3.2.5
Page 7/39
Remote version
Attention: Do not lay signal cables in the direct surrounding of power cables,
electrical machines, etc.
Fix the signal cables. Cable movements could otherwise lead to
improper measurings by capacity changes.
183
146
60
5.2
BA90MID
65
3.2.6
MID_M1000_BA_02_0806.doc
Installation
Page 8/39
"X" M4:1
BA80MID
"X"
3.2.7
When using non conductive pipelines or pipelines with a non conductive liner, the
equipotential compensation has to happen via an additionally installed grounding
electrode or between the flanges mounted grounding rings. The grounding rings are
mounted like a gasket between the flange and connected by a ground cable with the
detector.
Attention: When using grounding rings the corrosion resistance of the material
has to be paid to. For aggressive media, it is recommended to use
grounding electrodes.
"X" M4:1
Grounding ring
BA81MID
"X"
6 mm Cu
3.2.8
When having a cathodic protection, the meter has to be mounted potential free. The
meter may not have any electrical connection to the system of pipes and the voltage
supply has to happen via a separation transformer.
Attention: It is required to use grounding electrodes in this case (grounding rings
have to be mounted isolated from the system of pipes as well).
National regulations for the potential free mounting have to be
observed.
"X" M4:1
BA82MID
"X"
6 mm Cu
electrical isolation
MID_M1000_BA_02_0806.doc
electrical isolation
Electrical connection
3.2.9
Page 9/39
"X" M4:1
BA83MID
"X"
4. Electrical connection
Only flexible electrical wires can be used for the 2 x M20 cable
insertions.
Use separate line entrances for auxiliary power, signal and in-/output
wires.
BA84MID
Attention:
VDC
Power
VAC
2.
3.
4.
Check the selector switch for the power supply. If the power supply is modified,
please change fuse according to section 8.1.
5.
Close the cover tightly again once the connection has been completed.
MID_M1000_BA_02_0806.doc
FE
1.
BA85MID
Warning:
BA91MID
FE
4.1
Electrical connection
4.2
Page 10/39
Remote version
Attention:
2.
empty pipe
shield
E2
shield
BA89MID
detector
1.
FE C1 C2
coil
3.
4.
Slide the signal cable on the bottom of the meter (wall mounting) through the cable
insertion.
5.
Insert the board again and fasten it, lead out the signal cable between the housing
wall upwards (on the side of the terminals).
6.
7.
E1
Shield 44
ELECTRODE 46
Shield 44
ELECTRODE 45
From
Detector
Shield 13
COIL 12
COIL 11
40 EMPTY PIPE
44 Shield
46 ELECTRODE
44 Shield
45 ELECTRODE
To Amplifier
13 SHIELD
12 COIL
11 COIL
Badger Meter
JBOX - PRIMO
REMOTE - REV1
Terminal box
11
12
13
45
44*
46
40
44*
Amplifier
C1
C2
FE
E1
shield*
E2
empty pipe
shield*
Description
Coil 1
Coil 2
Shield complete
Electrode 1
Shield electrodes
Electrode 2
Empty pipe detection
Shield empty pipe detection
MID_M1000_BA_02_0806.doc
BA16MID
SHIELD 44
EMPTY PIPE 40
Wire colour
Green
Yellow
Green/Yellow
White
Black
Brown
Pink
Black
Electrical connection
4.2.1
Page 11/39
Notice:
Meter
or
Observe the max. signal cable length between detector and amplifier
(keep the distance as short as possible).
Distance
0 75 m
3 x (2 x 0,25 mm)
> 75 150 m
3 x (2 x 0,50 mm)
=< 80 /km
white (45)
brown (46)
black (44)
white (45)
brown (46)
black
(44)
pink (40)
black (44)
pink (40)
black
(44)
5 to 150 m
yellow/green (13)
yellow/green (13)
yellow (12)
green (11)
BA79MID
yellow (12)
green (11)
150
Cable length [m]
125
100
0,25 mm
75
50
25
0
0
25
50
75
100
Temperature [C]
MID_M1000_BA_02_0806.doc
125
150
175
Electrical connection
4.3
Page 12/39
230 V
RS 232
Fuse
Badger Meter
Boot
3 21
LCD display
analog out
Display
FE
Power
input
pulse out
FGND
Reset
pulse2
shield
E2
shield
detector
empty pipe
BA88-1000AC
FE C1 C2
coil
pulse1
E1
In- / output
Analog
Digital output 1
Terminal
Description
4 - 20 mA
12 - 30 VDC
active*
4 - 20 mA
active*
Digital input
min. 5 V up to max. 36 V
RS232
RS232 plug
active*
Digital output 2
* Either analogue or digital outputs can be used as active output, but not both simultaneously.
MID_M1000_BA_02_0806.doc
Page 13/39
The parameter software is now installed. If you want to start the parameter software, go to
the directory C:\Programme\Mag Meter PC Interface and click on the file
MagMeter.exe.
MID_M1000_BA_02_0806.doc
Parameter setting
Page 14/39
6. Parameter setting
The parameter setting of this meter is done with the RS232 interface. Connect the
measuring unit (RS232 plug) with the PC (COM1 or COM2) via a standard RS232 wire.
BA86MID
RS 232
2.
Measuring mode
The current flow as well as the totalizers and error messages are indicated on the
display on the measuring mode.
MID_M1000_BA_02_0806.doc
Parameter setting
Page 15/39
By pressing the ENTER key in the measuring mode the parameter setting mode can be
reached. If no input is done in the parameter setting mode within 2 minutes, the program
automatically returns to the measuring mode. Even during the parameter setting mode
measurements can be carried out.
The two keys + and enable the item selection in each selection menu as well as any
parameter change. Press ENTER to confirm.
In every selection menu the chosen item or the chosen value is marked with the cursor >
to the left. The ENTER key can then open the menu or confirm the according value.
If you want to show e.g. the menu measurement in the main menu, press the + key until
the cursor > is left to measurement and then press the ENTER key.
If a parameter is changed by entering a value, the underline _ shows the relevant number,
which can be increased with the + key or reduced by the key. The entry is
acknowledged with the ENTER key and the next digit to the right is chosen.
MID_M1000_BA_02_0806.doc
Parameter setting
6.1
Page 16/39
Basic configuration
6.1.1
Notice:
Size
This parameter is used for setting the detector diameter (size). The setting of the
different size degrees is possible here.
6.1.2
Notice:
Detector constant
The meter was calibrated in the factory and the detector factor
belonging to the detector has already been programmed. Changes of
the calibration constant are influencing the measuring accuracy of the
meter.
Each meter has been wet calibrated in the factory and the corresponding correction
factor has been determined. Each detector has its individual constant, which is
programmed in the amplifier. This constant is shown on each detector nameplate.
6.1.3
Notice:
Excitation frequency
This value indicates with which frequency the coils of the detector are operated. The
possible settings are according to the power frequency.
Excitation frequency
Power frequency of 50 Hz
3,125 Hz
6,25 Hz
12,5 Hz
Power frequency of 60 Hz
3,75 Hz
7,5 Hz
15 Hz
6.1.4
Notice:
The meter was calibrated in the factory and the detector factor
belonging to the detector has already been programmed. Changes of
the hydraulical zero point are influencing the measuring accuracy of
the meter.
Each meter has been wet calibrated in the factory and the corresponding correction
factor has been determined. Each detector has its individual hydraulical zero point,
which is programmed in the amplifier.
MID_M1000_BA_02_0806.doc
Parameter setting
6.1.5
Notice:
Page 17/39
2.
Go to the menu item Cal. pipe empty and activate the empty pipe calibration
CAL [ON]. The read in voltage in Volt is indicated. Turn off the empty pipe
calibration afterwards CAL [OFF].
3.
4.
5.
Go to the menu item Cal. empty full and activate the empty pipe calibration
CAL [ON]. A voltage is indicated there that has to be lower than the one in the
empty condition. If the value of the indicated voltage should be very high here
(similar to the value in the empty condition), then the conductivity of the medium
is very low. Turn off the empty pipe calibration afterwards CAL [OFF].
6.
The empty pipe detection can now be activated or deactivated with the menu item
On/Off.
The status of the empty pipe detection can be given out on the digital output 1 or 2.
See section digital outputs.
6.1.6
Notice:
Password
Please contact the manufacturer at loss of the password.
The password consists of a number between 0 and 999. The value 0 is for no
password protection active. If a value bigger than zero is entered, the password
protection is activated. When calling the parameter setting mode again, the
password has to be entered.
MID_M1000_BA_02_0806.doc
Parameter setting
6.2
Page 18/39
Measuring
6.2.1
Measuring units
12 flow measuring units can be chosen. The flow values are automatically converted
in the chosen unit.
6.2.2
l/h
Liter/hour
l/min
Liter/minute
l/s
Liter/second
m/h
Cubic meter/hour
m/min
Cubic meter/minute
m/s
Cubic meter/second
GPM
US gallon/minute
MGD
US million gallon/day
LbM
US liquid pounds/minute
OzM
US fluid ounces/minute
IGPM
Imperial gallon/minute
F3M
Cubic feet/minute
BPM
Barrel/minute
Totalizer units
The following totalizer units can be set independently of the flow measuring units.
Liter
Cubic meter
USG
US gallon
MG
US million gallon
Lb
US pounds
Oz
US fluid ounces
UKG
UK gallon
aft
Acre feet
ft
Cubic feet
bbl
Barrel
MID_M1000_BA_02_0806.doc
Parameter setting
6.2.3
Page 19/39
Full scale
The full scale can be chosen in a range of 0,1 up to 12 m/s. A flow is assigned to the
power output as well as the frequency output by the full scale scaling. The scaling is
valid for both flow directions.
Notice:
6.2.4
The full scale and low flow cut off are also referring to the full scale.
Low flow cut off
6.2.5
Flow direction
Filter (damping)
This option is used for damping all output signals. The damping factor (time
constant) can be set from inactive up to max. 30 s. The damping corresponds to a
low pass filter.
Notice:
6.2.7
The totalizers can be individually resetted via the menu Clear Totals.
Notice:
MID_M1000_BA_02_0806.doc
Parameter setting
6.3
Page 20/39
Outputs
6.3.1
Analog output
If you are using the passive analog output, the following max. loads RL have to be
observed:
External power
supply
max. RL
36 VDC
1100 ohms
24 VDC
750 ohms
20 VDC
680 ohms
18 VDC
560 ohms
12 VDC
220 ohms
Power supply 20 mA
Flow direction
Flow direction
forward
backward
21 mA
20 mA
RL
12 36 VDC
12 - 36 VDC
4 0/4
20- mA
20 mA
1
Current output (active)
4...20 mA
0...20 mA
+ 18 V
4 mA
3
2
Qr
Full scale
Full scale
MID_M1000_BA_02_0806.doc
4
-20
0/4
20mA
mA
RL max.
max. 560
560 Ohms
RL
Ohm
Qv
0 mA
Parameter setting
6.3.2
Page 21/39
The following functions can be assigned to the two digital outputs or the
digital input:
Digital outputs
Function
Output 1
Pulse forward
Output 2
Digital
input
Pulse backward
Frequency
Preselection
Setpoint
Meter error
Flow direction
AMR (US)
6.3.2.2
X
Pulse output
The pulse value defines how many pulses per volume unit are dispensed.
These can be totalized and displayed as total flow volume via an external
counter.
A setting of 0,001 up to 10.000 pulse/volume unit is possible. A max. output
frequency of 10 kHz (10.000 pulses/sec) may not be exceeded. The program
is checking if the entered pulse rate at the given full scale exceeds the max.
output frequency.
Notice:
The volume unit can be set independently of the flow unit (see
units).
max. 24 V DC
50 mA
max. 10 kHz
MID_M1000_BA_02_0806.doc
FGND
P2
max. 24 V DC
50 mA
max. 10 kHz
Parameter setting
Page 22/39
Pulse output 2 (active)
R about 10 KOhms
+ 18 V
Digit. Out. 1
Total 12345
Digit. In.
P2
Digit. Out. 2
Total 12345
FGND
IP
P1
R about 10 KOhms
FGND
Digit. Out. 2
Digit. In.
Digit. Out. 1
IP
P2
P1
100 ms
1 second
1 second
The pulse/break relation is approx. 1:1. At a setting of pulse width 0 ms, the
pulse width is automatically adjusted to each pulse frequency. The pulse
width can however be programmed up to max. 9999 ms.
The program is checking, which maximum pulse length is possible at
maximum pulse output frequency (full scale) and allows no higher values.
Normal closed
MID_M1000_BA_02_0806.doc
Parameter setting
Page 23/39
6.3.2.3
Frequency output
The frequency for the scaled terminal value can be set from 0,01 up to 15
kHz and is indicated via the digital output 2.
6.3.2.4
Setpoint
The set point (min, max) is used for control of the momentary flow rate and is
set in percent from the full scale. The values can be chosen in 1% steps
between 0 to 199%. The exceeding/underflowing of the set setpoint is
indicated via the digital output 1 or 2.
Flow
100 %
Full
scale
Max. %
Min. %
T
Output
Closed
Open
Max. alarm
Digital output 1
Min. alarm
Digital output 2
FGND
P1
max. 24 V DC
50 mA
MID_M1000_BA_02_0806.doc
FGND
P2
max. 24 V DC
50 mA
Parameter setting
Page 24/39
6.3.2.5
Digital input
Switch (normally
closed)
5 - 36 V DC
IP
Switch (normally
closed)
FGND
0.000
Digit. In.
2.
IP
6.3.2.6
Preselection
The menu point preselection is used for realisation of simple batches. The
value for the preselection quantity can be set from 0,01 to 9999,99 volume
units in steps of 0,01 volume units.
The preselection quantity is counted down to 0 from the programmed value
and the reaching of the preselected quantity is indicated via the digital output
2. The preselection meter can be resetted via an external switch.
Notice:
Digital output 2
FGND
P2
max. 24 V DC
50 mA
MID_M1000_BA_02_0806.doc
Parameter setting
Page 25/39
6.3.2.7
6.3.2.8
Output type
The output type function controls the behaviour of the two digital outputs 1
and 2. Is the output type set to Normal open, the output is closed if it is
activated. At Normal closed it is reversed.
This behaviour is valid for all functions of these two outputs.
Normal open
6.4
Normal closed
RS 232
TxD
9 pol. plug
2
1
RxD
3
6
= 9600
=8
=1
= none
= none
RS 232
BA86MID
GND
Baud
Data bits
Stop bits
Parity
Protocol
MID_M1000_BA_02_0806.doc
Parameter setting
6.5
Page 26/39
Info/help
6.5.1
Error list
The following error list and the frequency of the occurred error are displayed.
Error
Sensor
Empty pipe
Full scale
Totalizer
ADC24 int.
WDT reset
only service
Sys error
only service
Temp. range
only service
Mem alloc
only service
ADC range
The error messages in this list can be resetted individually. Choose the error
message from the list and press the ENTER key. Move the cursor to Resetting the
meter and press again ENTER. Choose Store with the key + and the error counter
is resetted to 0 with ENTER.
6.5.2
Power Up counter
This function shows the sum of all switch-on actions; it can also be used for an easy
check of possible voltage losses.
6.5.3
Version number
All in- and outputs are set to factory default values. Other factors like size and
detector constant remain unchanged.
6.6
Language selection
Another language can be selected via this menu.
MID_M1000_BA_02_0806.doc
Measuring mode
Page 27/39
7. Measuring mode
The backlighted LCD display consists of 4 lines each 16 digits and is used for displaying
the following information:
Notice:
Uni-directional
Line
Information
Value*
16 digits
Actual flow Q
8 digits
10 digits
10 digits
Preselection meter VW
7 digits
Bi-direction
Line
Information
Value*
16 digits
Current flow Q
8 digits
10 digits
Totalizer backward T-
10 digits
10 digits
Preselection meter VW
16 digits
You can scroll the display with the + or keys to display the preselection meter and the
net totalizer.
The parameter mode is shown by pressing the ENTER key in the measuring mode.
If a password is used, following display appears:
MID_M1000_BA_02_0806.doc
Page 28/39
Possible cause
Measures
Err: sensor
No detector connected.
increase
the
Contact service.
Possible cause
Measures
No operation of
the meter
No power.
Provide power.
Fuse defective.
Despite of flow
ZERO is
displayed
Inaccurate
measuring
the
coils
Parameter wrong.
MID_M1000_BA_02_0806.doc
Warning:
230 VAC
100mA (slow-blow)
115 VAC
200mA (slow-blow)
24 VDC
630mA (slow-blow)
FE
Fuse
8.2
BA85MID
8.1
Page 29/39
Warning:
Switch off the auxiliary power before opening the casing cover.
Selector switch for power supply
S4
S3
230 V
RS 232
FE
Badger Meter
Display
Boot
3
2
1
analog out
3 21
input
Reset
pulse out
FGND
pulse2
E2
shield
E1
S1
BA88-1000AC
shield
detector
empty pipe
FE C1 C2
coil
pulse1
S2
1.
Loosen the electrode and coil cables. Loosen the screws S1 to S4 and take out the
circuit board.
2.
Put in new circuit board and fasten with the screws S1 to S4. Connect the signal
cable again.
3.
The new circuit board possibly has to be programmed to the existing detector
(transmitter factor, size, in-/outputs, etc.).
MID_M1000_BA_02_0806.doc
Technical data
Page 30/39
9. Technical data
9.1
Detector type II
Technical data
Size
Process connections
Nominal pressure
Protection class
Min. conductivity
Liner materials
Electrodes materials
Housing
Lay length
DN 6 200 (1/4...8)
Flange: DIN, ANSI, JIS, AWWA etc.
Up to PN 100
IP 65, optional IP 68
5 S/cm
Hard-/soft rubber
from DN 25
PTFE
DN 6 - 600
Hastelloy C (standard)
Tantalum
Platinum/Gold plated
Platinum/Rhodium
Steel/optional stainless steel
DN 6 20
170 mm
DN 25 50
225 mm
DN 65 100
280 mm
DN 125 200
400 mm
BA67MID
BA66MID
0 up to +80C
-40 up to +150C
MID_M1000_BA_02_0806.doc
Technical data
Page 31/39
Dimensions (mm)
DN
Size A Std A ISO B1
B2
6
1/2 170
228
191
8
3/10 170
228
191
10
3/8 170
228
191
15
1/2 170
200
238
201
20
3/4 170
200
238
201
25
1
225
200
238
201
32
1 1/4 225
200
253
216
40
1 1/2 225
200
253
216
50
2
225
200
253
216
65
2 1/2 280
200
271
234
80
3
280
200
271
234
100
4
280
250
278
241
125
5
400
250
298
261
150
6
400
300
310
273
200
8
400
350
338
301
Standard
With ANSI flanges from DN 6 1400
With DIN flanges
from DN 6 200
d2 x n
15,9 x 4
15,9 x 4
15,9 x 4
15,9 x 4
15,9 x 4
15,9 x 4
15,9 x 4
15,9 x 4
19 x 4
19 x 4
19 x 4
19 x 8
22,2 x 8
22,2 x 8
22,2 x 8
MID_M1000_BA_02_0806.doc
Technical data
9.2
Page 32/39
Technical data
Size
Process connections
Nominal pressure
Protection class
Min. conductivity
Liner materials
Electrodes materials
Housing
Lay length
DN 10 100 (3/8...4)
Tri-Clamp, DIN 11851, ISO 2852, etc.
PN 10
IP 65, optional IP 68
5 S/cm
PTFE
-40 up to +150C
Hastelloy C (standard)
Tantalum
Platinum/Gold plated
Platinum/Rhodium
Stainless steel
Tri-Clamp connection DN 10 50
145 mm
DN 65 100
200 mm
DIN 11851 connection DN 10 20
170 mm
DN 25 50
225 mm
DN 65 100
280 mm
BA71MID
MID_M1000_BA_02_0806.doc
Technical data
Page 33/39
BA72MID
BA70MID
B2
10
15
20
25
40
50
65
80
100
191
191
191
191
201
206
219
224
232
74
74
74
74
94
104
129
140
156
D
74
74
74
74
84
94
104
129
140
156
3/8
1/2
3/4
1
1 1/2
2
2 1/2
3
4
145
145
145
145
145
145
200
200
200
228
228
228
228
238
243
256
261
269
MID_M1000_BA_02_0806.doc
Technical data
9.3
Page 34/39
Technical data
Size
Process connections
Nominal pressure
Protection class
Min. conductivity
Liner materials
Electrodes materials
Housing
Lay length
DN 25 100 (1...4)
Wafer connection,
(in-between flange mounting)
PN 40
IP 65, optional IP 68
5 S/cm
PTFE
-40 up to +150C
Hastelloy C (standard)
Tantalum
Platinum/Gold plated
Platinum/Rhodium
Steel/optional stainless steel
DN 25 50
100 mm
DN 65 100
150 mm
Wafer connection
Meter mounted
BA69MID
BA68MID
Wafer connection
Wall mounted
Dimensions (mm)
DN
Size
25
1
32
1 1/4
40
1 1/2
50
2
65
2 1/2
80
3
100
4
A
100
100
100
100
150
150
150
B1
238
243
248
253
266
271
279
B2
201
206
211
216
229
234
242
MID_M1000_BA_02_0806.doc
D
74
84
94
104
129
140
156
Technical data
9.4
Page 35/39
Technical data
Type
Power
Analog output
Pulse output
Status output
Empty pipe detection
Parameter setting
Interface
Measuring range
Measuring accuracy
Repeatability
Flow direction
Pulse length
Outputs
Low flow cut off
Display
Housing
Protection class
Cable insertion
Signal cable
Ambient temperature
M1000
24 VDC, optional 115 / 230 VAC
4 20 mA passive, optional active
Flow direction is displayed upon a separate status
display.
max. 24 VDC, 50 mA, max. 10 kHz passive, optional
active
Free configurable
Separate electrode
RS 232
RS 232
0,03 12 m/s
0,5 m/s better 0,5% of actual flow
< 0,5 m/s 2,5 mm/s of actual flow
0,1%
Bidirectional
Programmable up to 10 s
Short-circuit proof
0 10%
None
Varnish aluminium die cast
IP 65
Supply and signal cable (outputs) 2 x M20
From detector M20
-20 up to + 60C
BA110MID
Dimensions
MID_M1000_BA_02_0806.doc
Technical data
9.5
Page 36/39
Error limits
Measuring range
Pulse output
0,5 m/s
< 0,5 m/s
Analog output
Repeatability
Measuring error in % of
actual flow
5,0%
4,0%
3,0%
2,0%
1,0%
0,5 %
0,0%
0
Reference conditions:
Ambient and
medium temperature :
20C
Electr. conductivity
Warm up time
60 min
Mounting conditions :
MID_M1000_BA_02_0806.doc
10
Technical data
9.6
Page 37/39
Size selection
DN 6 - DN 100
100
m/s
10
0,1
0,01
0,01
0,1
10
100
1.000
10.000
L/min
DN 125 - DN 200
100
10
0,1
0,01
10
100
1000
m/h
MID_M1000_BA_02_0806.doc
10.000
100.000
Program structure
Page 38/39
0.0000 m3h
0.0000 m3
0.0000 m3
E - key
Meter Setup
Pipe Diameter
Detector Factor
Excitation Frequency
Calibration
Hydr. Zero-Manual
Hydr. Zero-Auto
Empty Pipe
Change Password
Measurements
Flow Unit
Totalizer Unit
Full ScaleFlow
Low Flow Cut Off
Flow Direction
Damping Factor
Inputs/Outputs
Analog Output
Zero Calibrate
FS Calibrate
Digital Input 1
Digital Output #1
Pulses / unit
Pulse width
Set point min.
Set point max.
Output Type
Select Function
Digital Output #2
Pulses / unit
Pulse width
Clear Totals
Communications
Info/Help
Language Select
Versions Number
Restore Defaults
MID_M1000_BA_02_0806.doc
Return of goods
Page 39/39
Harmlessness declaration
To
__________________________________________________________________
Attn.
__________________________________________________________________
From
__________________________________________________________________
Dept.
__________________________________________________________________
Please note that no repair will be performed prior to receiving of this declaration duly
signed by you!
Please send all parts clean from medium and inform us about possible medium wastes
remaining in the part. For this purpose, please use this form. A security specification sheet of
the medium must accompany this declaration in the following cases: Toxical, dangerous or
objectionable media, or media belonging to any dangerous materials class. We inform you
that uncleaned parts lead to additional costs. Extra clean costs will be charged to you.
Furthermore, we reserve us the right to send the parts back to you for cleaning!
Declaration
We herewith confirm that the part(s) sent for repair has/have been cleaned and is/are free of
any liquid and/or solid wastes of the medium and/or cleaning medium: Any eventually
remaining wastes are:
harmless
dangerous, toxic, etc. Security specifications are attached
Signature of person in charge:
______________________________________
______________________________________
Company stamp:
______________________________________
MID_M1000_BA_02_0806.doc
Hotline
Tel.
+49-7025-9208-0 or -30
Fax
+49-7025-9208-15