Required Inputs For Relay Setting Calculation

This document provides required inputs for relay setting calculations for transmission lines and equipment at the Kelaniya Grid Substation in Sri Lanka. It includes technical details like line configurations, lengths, conductor types and impedance values for several 145kV and 33kV transmission lines connected to the substation. It also lists transformer ratings and generator parameters. If the line-specific information is unavailable, the document recommends contacting the distribution planning engineer for typical 145kV and 36kV system data including short circuit levels and X/R ratios.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
245 views

Required Inputs For Relay Setting Calculation

This document provides required inputs for relay setting calculations for transmission lines and equipment at the Kelaniya Grid Substation in Sri Lanka. It includes technical details like line configurations, lengths, conductor types and impedance values for several 145kV and 33kV transmission lines connected to the substation. It also lists transformer ratings and generator parameters. If the line-specific information is unavailable, the document recommends contacting the distribution planning engineer for typical 145kV and 36kV system data including short circuit levels and X/R ratios.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Required Inputs for

Relay Setting Calculation

LTL Projects (Pvt) Ltd.

30-03-16

Annexure - 1
Project : CEAIP Part - 3, Kelaniya-Grid SubStation Augmentation Project
Client : Ceylon Electricity Board, Sri Lanka
Subject : Required Inputs for Relay Setting Calculation
Description
A

Main Equipment / Line Details

145kV Kotugoda
Line Configuration
Mutual Impedance (if parallel)
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Longest Line: (Aniyakanda)
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Shortest Line: (Katunayaka)
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance

Required Data

0.26577+0.66769j Ohms/km
19.3
Zebra
0.0760+0.3870j
0.33601+1.18857j
10

km

10
Zebra
0.0760+0.3870j
0.33601+1.18857j
10

km

7
Zebra
0.0760+0.3870j
0.33601+1.18857j
10

km

Ohms/km
Ohms/km
Ohms

Ohms/km
Ohms/km
Ohms

Ohms/km
Ohms/km
Ohms

145kV Aniyakanda
Line Configuration
Mutual Impedance (if parallel)
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Longest Line: (Kotugoda)
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Shortest Line:
Length

0.26577+0.66769j Ohms/km
11
Zebra
0.0760+0.3870j
0.33601+1.18857j
10

km

10
Zebra
0.0760+0.3870j
0.33601+1.18857j
10

km

km

Ohms/km
Ohms/km
Ohms

Ohms/km
Ohms/km
Ohms

Page 1 of 6

LTL Projects (Pvt) Ltd.

Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
3

30-03-16

Ohms/km
Ohms/km
Ohms

145kV Sapugaskanda - 1
Line Configuration
Mutual Impedance (if parallel)
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Longest Line: (Biyagama)
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Shortest Line:
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance

Required Inputs for


Relay Setting Calculation

0.26577+0.66769j Ohms/km
4.6
Zebra
0.0760+0.3870j
0.33601+1.18857j
10

km

4.2
Zebra
0.0760+0.3870j
0.33601+1.18857j
10

km

km

Ohms/km
Ohms/km
Ohms

Ohms/km
Ohms/km
Ohms

Ohms/km
Ohms/km
Ohms

145kV Sapugaskanda - 2
Line Configuration
Mutual Impedance (if parallel)
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Longest Line:
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Shortest Line:
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance

0.26577+0.66769j Ohms/km
4.6
Zebra
0.0760+0.3870j
0.33601+1.18857j
10

km

4.2
Zebra
0.0760+0.3870j
0.33601+1.18857j
10

km

km

Ohms/km
Ohms/km
Ohms

Ohms/km
Ohms/km
Ohms

Ohms/km
Ohms/km
Ohms

Page 2 of 6

LTL Projects (Pvt) Ltd.

Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Longest Line:
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Shortest Line:
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance

0.26577+0.66769j Ohms/km
3.6
Zebra
0.0760+0.3870j
0.33601+1.18857j
10

km

km

km

Ohms/km
Ohms/km
Ohms

Ohms/km
Ohms/km
Ohms

Ohms/km
Ohms/km
Ohms

145kV KHD - 2
Line Configuration
Mutual Impedance (if parallel)
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Longest Line:
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Shortest Line:
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance

30-03-16

145kV KHD - 1
Line Configuration
Mutual Impedance (if parallel)

Required Inputs for


Relay Setting Calculation

0.26577+0.66769j Ohms/km
3.6
Zebra
0.0760+0.3870j
0.33601+1.18857j
10

km

km

km

Ohms/km
Ohms/km
Ohms

Ohms/km
Ohms/km
Ohms

Ohms/km
Ohms/km
Ohms

145kV Kolonnawa - 1
Line Configuration

Page 3 of 6

LTL Projects (Pvt) Ltd.

Required Inputs for


Relay Setting Calculation

Mutual Impedance (if parallel)

0.26577+0.66769j Ohms/km

Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Longest Line: (Seethawaka)
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Shortest Line: (Kelanitissa)
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance

6.6
Zebra
0.0760+0.3870j
0.33601+1.18857j
10

km

43
Lynx
0.178+0.401j
0.39735+1.31149j
10

km

2.2
Invar
0.038+0.0306j
0.30196+1.07744j
10

km

Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Longest Line:
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance
Adjacent Shortest Line:
Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Tower Foot Resistance

10

Ohms/km
Ohms/km
Ohms

Ohms/km
Ohms/km
Ohms

Ohms/km
Ohms/km
Ohms

145kV Kolonnawa - 2
Line Configuration
Mutual Impedance (if parallel)

30-03-16

31.5MVA, 132/33kV Transformer (Existing)


Transformer Name Plate Details
% Impedance
OLTC Details
33kV Line Feeders (New)
OHL/Cable Length

0.26577+0.66769j Ohms/km
6.6
Zebra
0.0760+0.3870j
0.33601+1.18857j
10

km

43
Lynx
0.178+0.401j
0.39735+1.31149j
10

km

2.2
Invar
0.038+0.0306j
0.30196+1.07744j
10

km

Ohms/km
Ohms/km
Ohms

Ohms/km
Ohms/km
Ohms

Ohms/km
Ohms/km
Ohms

10.38
-

km

Page 4 of 6

LTL Projects (Pvt) Ltd.

Required Inputs for


Relay Setting Calculation

Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
11

33kV Generator Feeders (New)


OHL/Cable Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Generator Rating
Rated Power Factor
X''d (Sub Transient Reactance)
X'd (Transient Reactance)
Xd (Direct Axis Reactance)
Maximum Overexcitation (U/f) max
Permissable Overexcitation Duration t (U/f) max
Thermal Continuous Permissable Primary Current
Negative Sequence Capability I2S
I22t

30-03-16

Ohms/km
Ohms/km

km
Ohms/km
Ohms/km

pu
pu
pu
%

%
sec.

Transformer Name Plate Details (if applicable)


% Impedance (if applicable)
OLTC Details (if applicable)
12

13

33kV Line Feeders (Existing)


OHL/Cable Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
33kV Generator Feeders (Existing)
OHL/Cable Length
Conductor Type
Positive Sequence Impedance
Zero Sequence Impedance
Generator Rating
Rated Power Factor
X''d (Sub Transient Reactance)
X'd (Transient Reactance)
Xd (Direct Axis Reactance)
Maximum Overexcitation (U/f) max
Permissable Overexcitation Duration t (U/f) max
Thermal Continuous Permissable Primary Current
Negative Sequence Capability I2S
I22t

km
Ohms/km
Ohms/km

km
Ohms/km
Ohms/km

pu
pu
pu
%

%
sec.

Transformer Name Plate Details (if applicable)


% Impedance (if applicable)
OLTC Details (if applicable)

Page 5 of 6

LTL Projects (Pvt) Ltd.

Required Inputs for


Relay Setting Calculation

30-03-16

If Items A.1 to A.11 are not available

145kV Basic Data


3-Phase Symmetrical Short Circuit Level
X/R Ratio

26.3 -86.0
-

kA

36kV Basic Data


3-Phase Symmetrical Short Circuit Level
X/R Ratio

10 -89.6
-

kA

- Please contact Distribution Planning Engineer - WPN

Page 6 of 6