QFSN-660-2-22A 40 AHL
RBSISAT PLB
OPERATION OF GENERATOR
4% ~—Q907
He 34 a Thc rf
we 2 4
KEK & fe +3 0095.18
git] R| £ A
GEO
AR TG HALA BR ZS i]
DONGFANG ELECTRIC MACHINERY Co.,LTD.
= 00 Au4F A
April, 2009* REV.Z
| OPERATION OF GENERATOR Q907
|
OPERATION OF GENERATOR
TABLE OF CONTENTS.
Section 1
Section 2
Section 3
Section 4
Section 5
Sections 6
(CHECK BEFORE TRIAL RUN. ccs
GENERATOR START-UP AND SHUTDOWN..,......
OPERATION AT UNBALANCED LOAD AND OVER LOAD...
OPERATION OF HYDROGEN COOLER... Seer
EFFECT OF LEADING AND LAGGING POWER FACTOR AND LOSS
OF EXCITATION
ON ABNORMAL OPERATIO!
eC awn
wo 10
DONGFANDG ELECTRIC MACHINERY CO., LTD. Sheet No. 1 Of 13OPERATION OF GENERATOR Q907
Section 1 CHECK BEFORE TRIAL RUN.
(1) Check that the temperature by embedded temperature detector is reasonable.
{lt should be at a temperature near the ambient temperature or the temperature of the
stator casing.).
(2) Check that the bearing oil pressure and the amount of bearing feed oil are
reasonable(including the jack oil ).
3) Check there is no rubbing around oil deflector labyrinths etc. when turning gear
operates.
(4) On the hydrogen cooler, first fully open the water supply valves and extract the air
from the air vent.
Adjust the cold gas temperature of hydrogen coolers by means of valves at the outlet
water side, if necessary. Do not create negative pressure in any way is the hydrogen cooler
and verify that water supply pressure is below design value.
DONGFANDG ELECTRIC MACHINERY CO., LTD. Sheet No. 2