Flame Sensor: Instruction Manual
Flame Sensor: Instruction Manual
Flame Sensor: Instruction Manual
FS-2000E
Instruction Manual
We appreciate your purchase of a TAKEX flame sensor.
Please read this instruction manual carefully for correct and effective use.
This sensor is designed to detect flames and to initiate an alarm, it is not a fire-preventing device.
TAKEX is not responsible for damage, injury or losses caused by accident, theft, Acts of God (including inductive surge by lightning), abuse,
misuse, abnormal usage, faulty installation or improper maintenance.
This sensor detects Ultraviolet rays in the flames and initiates an alarm.
It does not detect smoke, heat.
PRODUCT DESCRIPTION
Flame sensor FS-2000E is designed to detect ultraviolet rays contained in flames, and to initiate an alarm.
In addition to alarm sound, FS-2000E is equipped with form C (N/C, N/O.) output, to meet professional application.
Also, memory LED enables you to find out the initiated sensor out of a series of sensors.
Area adjustment mechanism brings wide selection of protection angle.
Quick separation of sensor and base eases installation and maintenance.
PARTS DESCRIPTION
1-1
Description
Knockout for exposed wiring
Wire lead
(For exposed wiring)
Terminals
Wiring hole
BASE UNIT
Wiring hole
Front mark
Sensor head
Lock window
Detection window
(Sensor built-in)
SENSOR UNIT
Mode selector
Buzzer (Built-in)
Alarm sound : Sounds intermittently during
offdelay 10sec.
1-2
1-3
Accessory
Mode setting
Mode selector
Tapping screw
(425) 2 pcs
Instruction manual
1 copy
1 2 3 4 5
Alarm Sound
Alarm Memory
Detection timer
Detection Sensitivity
ATTENTION
Product classification
Others
Objects to be detected
When
Intense
lamp
discharging lamp such like mercury lamp
Electric sterilizer lamp
Spark of welding
Electric spark (caused by motor, pantograph)
Sunlight
Electric discharge of thunderbolt
High electric field
All the objects which emanates ultraviolet rays
Halogen
Flames
Electric
Lighting
According to the detection area chart and operation check, decide installtion place not to form the death angle.
Do not install in the following places.
Do
Do
Do
This
when
4 WIRING
Terminal arrangement
Alarm output
Power
10 to 30VDC
(non-polarity)
Stand-by : 25mA
Alarm : 75mA Max. (buzzer : ON)
40mA Max. (buzzer : OFF)
Tamper
COM
N.C.
N.O.
Basic connection
Sensor
1
Power
Sensor
2
Signal input
(N.C.)
Control panel
Distance at 12VDC
Note 1) The maximum wire length, when two or more units are
connected, is the above distance divided by the number of units.
2) The protection circuit can be wired to a distance of 3,280 ft
(1,000m) with AWG 22 (0.65mm dia.) wire.
5 INSTALLATION
Locate the installation site.
(Ref : 3, DO'S AND DON'T'S and 7,
DETECTION AREA)
Area locking
screw
Lock window
When
sensor unit is
detached, wrap it in
palm and slide
release lever.
To
[Installation of base]
Installation hole This product is equipped with installation holes (pitch 3.29" or 83.5mm) to make
installation easy and the sensor's direction adjustable.
approx. 5mm
Installation hole
Installation hole
Marking
Buzzer
: Sounds intermittently every 0.2sec.
LED
: Lights on
Alarm output : Continuous
When the flame continues further, the above alarm actions
are also continued for the meantime. 2sec. after the flame
goes out, alarm output stops, and 10sec. after, alarm sound
and LED stop (off delay).
Then sensor goes back to armed mode.
Alarm sound (buzzer)
Mode selector
1 2 3 4 5
Alarm Sound
Alarm Memory
Detection timer
Detection Sensitivity
Detection Sensitivity
SET
SET
SET
ON
1
(Factory set : ON)
OFF
Alarm memory
When 2 or more sensor are connected on 1 loop, which
sensor is initiated can be monitored by Memory LED
(yellow) for 50 min. after alarm output. Memory LED
will be off automatically after 3 min. of blinking and 47
min. of lighting on.
In case that the sensor initiates alarm again while its
memory LED is lighting, LED continues to light on for
further 47 min. after that. (re-trigger action)
Detection timer
An alarm output occurs when the flame continues for set time of
detection timer or longer.
SET
AUTO
(ON)
OFF
Timer
0.2 sec
4 5
(Factory set : 0.2 sec)
1sec
6 sec
STD (100%)
SET
L (50%)
30 sec
When
For
At
7 DETECTION AREA
1. DETECTION AREA
2. AREA ADJUSTMENT
When
Detection
Approx. 120
Adjustment range
Horizontal 25By base unit
Vertical 30(4 steps) By sensor head
The
sensor head
30variable
Condition
of detection area
Detection timer : 0.2sec.
Origin of flame : Gas lighter
Size of flame : Approx. 2.75" (7cm)
Detection area
23' 20'
(7m)(6m)
10'
(3m)
10'
(3m)
20' 23'
(6m)(7m)
23' 20'
(7m)(6m)
10'
(3m)
10' (3m)
20' (6m)
20' (6m)
30' (9m)
30' (9m)
33' (10m)
30
varia
b
le
4 ste
ps
Lock window
Lock window
20' 23'
(6m)(7m)
10' (3m)
33' (10m)
10'
(3m)
FIXED
To be fixed
Lock window
To be loosened
OPERATION CHECK
2. Ignite a lighter etc. within detection area for more than the set time.
3. After the set time, an alarm output is issued, buzzer sounds intermittently and
LED blinks. (Alarm action)
4. 2 sec. after the flame goes off, alarm output ends. 10sec. after the flame
goes off, other alarm actions ends. (Check the alarm output by connecting
a device such like bell / siren.)
TROUBLESHOOTING
Trouble
No
Low
Completely inactive
Sensor
Dry
Detection
area setting
window is soiled with dust
Unexpected
Sensor
Poor
The
Relocate
Remove
Correct
voltage
Large
wire
Remove
Low
Activated without
flame
Correct
Interrupting
Improper
Sometimes inactive
Corrective action
Check
power supply
Relocate
the sensor
Remove
Dry
Check
Check
Maintenance
Detection area
Distance
Angle
Adjustment
range
LED
Alarm sound
(buzzer)
Tamper output
Wiring
Terminals
Weight
Buzzer
(built in)
Accessories
Option
35
Memory LED
(Yellow)
5-0.17"
(5-4.2mm)
Wiring hole
Detection window
R0.59"
(R15mm)
2.63"
(66.7mm)
3.29"
(83.5mm)
0.35"
(9mm)
OPTION
Ceiling/wall mount attachment
(variable attachment)
35
0
(4.2 .17"
mm
)
Sensor head
30
ble
Varia
35
Alarm memory
Release lever
Alarm LED
(Red)
Sensor unit
Locking
screw hole
10 to 30VDC (non-polarity)
Alarm output
Base unit
3.88" (98.5mm)
4.72" (120mm)
0.41"
(10.5mm)
Detection system
1.34"
(34mm)
FS-2000E
35
FLAME SENSOR
Model No.
0.31" (8mm)
Product name
1.58" (40mm)
10
11 EXTERNAL DIMENSIONS
SPECIFICATIONS
BCW-401
Limited Warranty :
TAKEX products are warranted to be free from defects in material and workmanship for 12 months from original date of shipment. Our warranty does not cover
damage or failure caused by natural disasters, abuse, misuse, abnormal usage, faulty installation, improper maintenance or any repairs other than those provided
by TAKEX. All implied warranties with respect to TAKEX, including implied warranties for merchantability and implied warranties for fitness, are limited in
duration to 12 months from original date of shipment. During the Warranty Period, TAKEX will repair or replace, at its sole option,free of charge, any defective
parts returned prepaid. Please provide the model number of the products, original date of shipment and nature of difficulty being experienced. There will be
charges rendered for product repairs made after our Warranty Period has expired.