0% found this document useful (0 votes)
11 views11 pages

Ultra Suoni

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 11

TABLE OF CONTENTS

1. INTRODUCTION ......................................................................................................................................3
2. TRADITIONAL FIXED GAS DETECTION SYSTEMS.................................................................................3
2.1
2.2
2.3
2.4

CAN THE TRADITIONAL GAS DETECTION SYSTEMS DETECT LEAKING GAS?............................................................ 4


HOW IS A TRADITIONAL GAS DETECTION SYSTEM COMMISSIONED AND APPROVED?............................................ 5
WHY IS THE TRADITIONAL COMMISSION PRACTISE QUESTIONABLE?.............................................................................................. 5
CASE STORY ABOUT REAL LIVE GAS RELEASE TESTS ................................................................................................................. 5

3. ULTRASOUND A NEW PHILOSOPHY OF DETECTING LEAKING GAS ................................................6


4. ULTRASONIC GAS LEAK DETECTOR COVERAGE AND GAS DISPERSION..........................................7
4.1

EXAMPLE OF ULTRASONIC DETECTION COVERAGE BASED ON THE LEAK RATE................................................................................. 7

5. THEORY OF ACOUSTIC AND ULTRASOUND .........................................................................................8


5.1
5.2

THE ACOUSTIC FREQUENCY SPECTRUM OF A LEAKING GAS ......................................................................................................... 8


THE ACOUSTICAL SOUND AROUND A LEAK ............................................................................................................................... 8

6. BACKGROUND NOISE IN THE MEASURED AREA .................................................................................8


6.1

FALSE ALARMS AND HOW TO AVOID THEM ................................................................................................................................ 9

7. REDUCE COSTS AND INCREASE SAFETY WITH ULTRASONIC LEAK DETECTION..............................9


8. COMMISSIONING AND TESTING AN ULTRASONIC GAS LEAK DETECTION SYSTEM ..........................9
9. THE INNOVA GASSONIC ULTRASONIC GAS LEAK DETECTORS. ......................................................10
9.1
9.2

THE GASSONIC MM0100 .................................................................................................................................................. 10


THE GASSONIC OBSERVER ................................................................................................................................................ 10

10. CONCLUSION .....................................................................................................................................11

1. INTRODUCTION
Fixed ultrasonic gas leak detection systems have been widely used in the North Sea and at various other locations for
almost a decade now. But only recently it has become a natural part of the decisions that almost any project group
takes regarding the fixed gas detection system. This indicates that the oil and gas industry is increasing its focus on
hydrocarbon gas leak detection all over the world. At the same time it indicates that traditional gas leak detection
systems (open path and point gas detection) have some imminent shortcomings.
Due to the changing weather conditions found on most outdoor installations, the wind may simply blow the gas cloud
away or the gas cloud may dilute before it can build up a concentration and come into physical contact with the
traditional detectors. This leaves the industry with a vital challenge. How do you measure/calculate where to locate
the detectors for optimal detection and how do you verify that they will actually detect the gas leak without being
influenced by the extreme weather conditions?
Besides from discussions on how to optimise the existing technologies, this calls for an alternative to the traditional
detection methods.
This article gives an overall view on the technical aspects of the traditional gas detection technologies. Furthermore, it
gives detailed insights into how and why to use ultrasonic gas leak detection in order to dramatically increase the total
system performance of the plant gas detection system.
The ultrasonic gas leak detection technology is now installed and recognised world-wide by leading oil/gas
companies as a supplement/alternative to traditional gas detection in outdoor gas installations. Innova Gassonic has
delivered more than 1800 Gassonic MM0100 ultrasonic gas leak detectors world-wide and the field installation track
record dates back to 1998.
Due to extensive market knowledge and research, Innova Gassonic has developed the next generation of ultrasonic
gas leak detectors, the GASSONIC OBSERVER.

2. TRADITIONAL FIXED GAS DETECTION SYSTEMS


The traditional gas detection systems available today are based on two main concepts. We call them the sniffing
technologies:

Point Detectors where the gas has to be in physical contact with the detector.
Open Path Detectors, where the gas has to be within a predefined path of infrared light to be detected.

Both detection concepts are based on LEL (Lower Explosive Level) measurements.
The Point detector has been widely used for many years, and the name of the detector refers to the fact that this
type of gas detector detects the gas only in a point around the detector itself. Actually, the gas has to enter INTO the
detector head, before the LEL level will be measured by the Point Detector.

Figure 1: Traditional Point Gas Detection

Inside the detector head the gas concentrations can either be measured by a catalytic pelistor, or by means of
infrared absorption, but still, the concentration measurements are only performed in a point.
The Open Path Detector refers to the fact that this type of gas detector detects the gas in a narrow path of infrared
light. These detectors consist of a separate transmitter and a receiver unit and they make use of the fact that
Hydrocarbon gas absorbs infrared light.

Figure 2: Traditional Open Path Gas Detection

The transmitter emits a concentrated beam of infrared light. This is beamed all the way to the receiver unit that can be
placed in distances up to 60 meters away. The receiver unit consists of an infrared receiver that will detect if
Hydrocarbon absorption has taken place in the infrared path between the transmitter and the receiver and the
absorption is then directly related to the LEL level.

2.1

CAN THE TRADITIONAL GAS DETECTION SYSTEMS DETECT LEAKING GAS?

In outdoor locations the answer is maybe!!!!


A potential gas cloud will ONLY be detected by the traditional detectors IF the gas is in physical contact with the
detector (point detector) or within a predefined beam of infrared light (open path detector).
The main problem is that nobody can predict this due to the following unknown factors:

Leaking gas is extremely fast diluted after escaping the leak.


Changing wind directions are often carrying the gas cloud away.
The leak itself is often directional which may also blow the gas cloud away from the sensors.

The traditional gas detection systems work well IF THE GAS EVER REACHES THE GAS DETECTOR.
This means a gas detector perhaps measures 10% LEL but just a few meters away from the detector the gas
concentration may be 100% LEL. This is due to the dilution that takes place before the leaking gas reaches the gas

detector. If, at the same time, there is just a little wind carrying the gas cloud away from the gas detector, this detector
will NEVER detect the gas leak.
In other words, it can be a false feeling of safety to believe that a low LEL level, measured by traditional sniffing gas
detection technology, means that there is no explosion risk!!
In outdoor installations, the gas cloud from a gas leak often either dilutes or drifts away in the wind before it reaches
the gas detection point.
To support this argument, Helth and Safety Executive (HSE) in UK concludes in a recent report about hydrocarbon
releases in the North Sea that only 65% of all hydrocarbon gas leaks are actually detected by traditional gas detection
systems.

2.2

HOW IS A TRADITIONAL GAS DETECTION SYSTEM COMMISSIONED AND APPROVED?

After a traditional gas detection system has been installed, the normal procedure is that it is calibrated with a
calibration gas that is similar to the gas that the system is supposed to detect, that could be Methane. The calibration
gas is injected directly into the detector, and if all the detectors in the detection system are proven to give correct
readings compared to the concentration of the calibration gas, the total gas detection system is approved.

2.3

WHY IS THE TRADITIONAL COMMISSION PRACTISE QUESTIONABLE?

The injection of gas directly into the detector will only determine if the detector itself is functioning properly, it will not
determine if the gas detection system will pick up a potential gas leak a few meters away from the detector.
None of the traditional gas detection systems available today can ensure a 100% reliable detection of gas within a
predefined area around each gas detector in the gas detection system.
If a predefined coverage area for each gas detector in the complete detection system cannot be predicted, how can
the total gas detection systems ability to detect gas leaks then be ensured?
The only way to find out if a gas detection system is able to detect leaking gas, is to perform so-called live gas
tests where real hydrocarbon gas is released in various places on the platform, and then see if the gas is actually
picked up by the detection system. And of course, for optimal testing this would have to be done under a variety of
environmental conditions.

2.4

CASE STORY ABOUT REAL LIVE GAS RELEASE TESTS

To illustrate a real situation, a test on a North Sea offshore gas platform was performed:
Gas was released through a simulated leak (3 mm hole with a gas pressure of 55 BAR), as illustrated in fig. 3.
On the offshore platform, there were several traditional point detectors and open path detectors installed in order to
detect hydrocarbon gas leaks. The test team carried hand held gas detectors to investigate in what range such a gas
leak could be detected.

Figure 3: The dilution of an outdoor gas leak.

To their astonishment, the gas cloud was diluted into 0% LEL only 4-5 metres from the leak. But the most alarming
was that none of the traditional fixed gas detectors on the platform ever detected the gas from the test leak.
The ultrasonic gas leak detector the Gassonic MM0100 detected the same gas leak instantly up to 19 metres away.

3. ULTRASOUND A NEW PHILOSOPHY OF DETECTING LEAKING GAS


As explained earlier, the traditional gas detection systems are based on sniffing technology where the gas has to be
in physical contact with the detector in order to be detected.
For the last eight years Innova Gassonic has developed and marketed a new type of gas leak detector for fixed
outdoor installations; a system, which does not rely on the traditional sniffing methods. Instead it is based on
airborne ultrasound, emitted from the gas leak.
An ultrasonic gas leak detector does not provide a concentration level in LEL as traditional gas detectors instead it
gives an instant alarm if a leak is detected.
When the ultrasonic gas leak detector triggers, the alarm indication will be raised at the speed of sound since the
alarm will be active as soon as the detector hears the leak noise. The ultrasonic gas leak detector doesnt have to
wait until the gas concentration accumulates into a potentially dangerous gas cloud. It reacts instantly.

Figure 4: The ultrasonic gas leak detector is not influenced by


dilution or wind

4. ULTRASONIC GAS LEAK DETECTOR COVERAGE AND GAS


DISPERSION
To build up a potentially dangerous gas cloud, a certain amount of gas has to be released through the leak, this
phenomenon is called the leak rate, and is based on mass flow calculations.
The leak rate unit of measurement is Kg/Sec and it tells how many kilograms of gas are released through the leak per
second.
Compared to traditional area limited LEL level measurement, the leak rate can give a picture of potential catastrophic
situations and hazardous gas built-up in the entire detection area.
The question is now how big a leak rate can be tolerated, before the gas detection system should alarm? This is
defined due to the so-called performance standard of the system. The performance standard defines the maximum
release rate of gas, before the gas detection must respond.
The leak rate of the escaping gas can be calculated and will mostly be dependent of the gas pressure and the leak
size. The molecule weight and the heat ratio of the gas will also influence, as well as the temperature of the gas.
Leak rates can be divided into three categories:
Small leak <0,1 Kg/Sec
Medium leak 0,1 Kg/Sec to 2,0 Kg/Sec
Large leak >2,0 Kg/Sec
These categories have been defined based on the potential explosion risk that the leak would cause.
4.1

EXAMPLE OF ULTRASONIC DETECTION COVERAGE BASED ON THE LEAK RATE

In outdoor plant installations, the gas type and the gas pressure are known, and the maximum release rate to be
tolerated would be 0,1 Kg/Sec.
By means of leak rate calculations, it is possible to calculate the mass flow through the leak.
The performance standard of an onshore/offshore platform requires that all methane leaks above 0,1 kg/s are
detected. Gas pressure in the system to be monitored is 90 BAR.

By means of mass flow calculations a methane release rate of 0,1 kg/s at 90 BAR will require a leak size at 3 mm.
The ultrasonic sound emitted from a leak with 3 mm diameter at a pressure of 90 BAR will generate enough
acoustical sound energy to be detected 8 to 12 metres away from the leak by the ultrasonic gas detectors!
In this way it is actually possible to calculate a leak detection coverage, and this coverage will not be influenced by
neither wind nor gas dilution. In addition, due to the fact that this technology does not need the gas to accumulate, the
detection of the gas leak will be instant, at the speed of sound!

5. THEORY OF ACOUSTIC AND ULTRASOUND


When gas moves from a high-pressure area through a hole to a low-pressure area, it expands very rapidly and
produces a turbulent flow, resulting in an audible hissing sound.
The hissing sound is a broadband acoustic sound wave, which ranges from the audible frequency range (20 Hz to
20 kHz) into the ultrasonic frequency range (16 kHz to 10 MHz).
The level of ultrasound produced by a gas leak is determined by three main factors:

The pressure drops across the leak.


The physical size of the leak.
Gas specific properties such as: molecule weight and the specific heat ratio of the gas.

As described earlier, it is the turbulent flow in the hole that produces the ultrasound. This turbulent flow can only occur
if the pressure on one side of the leak is at least twice the pressure on the other side of the leak.
The level of ultrasound in the turbulent flow is related to the pressure behind the leak and the size of the hole. For
example, if the hole is too large, the pressure drop across the hole will be too little, and no ultrasound will be
produced.
5.1

THE ACOUSTIC FREQUENCY SPECTRUM OF A LEAKING GAS

The sound waves produced by a leaking gas are very close to so-called white noise. White noise is acoustic sound
waves with a continuous and uniform spectrum, but capable of containing many frequencies. These range from very
low frequencies up to several hundred kHz. Practical tests have shown that most of the ultrasonic sound energy from
a gas leak will be in the frequency range between 5 kHz to 50 kHz. Tests were carried out to see if different gases
emit different kinds of white noise. The results showed that the ultrasonic noise spectra for Methane and Nitrogen are
almost similar.
5.2

THE ACOUSTICAL SOUND AROUND A LEAK

A basic rule of thumb of the theory of acoustics is that the sound pressure level (SPL) will drop 6 dB when doubling
the distance. This means that if an ultrasonic sound level of 100 dB is measured 1 metre from a leak, the sound level
will drop to 100-6 = 94 dB two metres from the leak, and so on. In this way it is possible to calculate the coverage of
the ultrasonic gas detector, if the ultrasonic sound level from a given leak is known.

6. BACKGROUND NOISE IN THE MEASURED AREA


Because an Ultrasonic Gas Leak Detector detects the gas by listening for sound waves, ultrasonic background
noise from compressors, turbines, or large fans, could cause false alarms. However, tests have shown that the typical
outdoor background noises do not exceed frequencies above 6-8 kHz, and as the filter of the ultrasonic gas leak
detector does not cover these frequencies, they are not able to activate the alarm.

It is, however, still very important to perform an analysis of the ultrasonic background noise in the measured area in
order to determine the exact number of detectors needed and to make sure that no sound waves will affect the
detector. For this purpose, Innova Gassonic has developed a customised ultrasonic mapping meter, which is battery
powered and has a read-out of the airborne ultrasound.
The sensitivity of the ultrasonic mapping meter can be adjusted in exactly the same way as the ultrasonic gas leak
detector. A graduated scale on the readout shows if the ultrasonic level is above or below the alarm trigger level of
the detector.
This makes it possible to map the area and determine the ultrasonic background noise level at the locations to be
monitored.
6.1

FALSE ALARMS AND HOW TO AVOID THEM

It is essential that a gas leak detection system will detect the gas leak quickly before it causes any damage. At the
same time, it is equally important that the detector does not cause false alarms. In an industrial environment,
spontaneous air-releases may generate ultrasound and trigger the alarm.
However, spontaneous air releases only last for a few seconds whereas the ultrasound emitted from a gas leak lasts
for a longer time. Therefore, there is a built-in delay function in the ultrasonic gas leak detectors. Alternatively, the
trigger level and the alarm delay can be integrated into the plant DCS system through the 4-20 mA signal of the new
detector the Gassonic Observer.

7. REDUCE COSTS AND INCREASE SAFETY WITH ULTRASONIC LEAK


DETECTION
Cost savings are always a very relevant topic within all fields of plant instrumentation, including the plant fire/gas
detection system. In some parts of the industry, it seems there is a trend towards more and more unmanned
installations. This means that the instrumentation on these unmanned installations must require as little maintenance
as possible, and at the same time it needs to operate continuously in all weather conditions, without breakdown or the
need for re-calibration.
Using traditional gas detection methods a potential leak spot would need at least 3-4 traditional point gas detectors to
ensure proper gas detection with different wind directions. Using ultrasonic gas leak detectors, the same spot may be
monitored by only 1 or 2 gas leak detectors. This will not only reduce the overall system price, but also reduce the
regular maintenance costs, since the ultrasonic gas leak detectors do not need calibration.

8. COMMISSIONING AND TESTING AN ULTRASONIC GAS LEAK


DETECTION SYSTEM
When commissioning a traditional gas detection system, calibration gas is injected into the sensor head, and if all the
sensors indicate the correct concentration level, it is said to be commissioned and operational. There is only one
problem. This commisioning of the detectors ONLY shows that the sensors are working correctly, but it does not say
anything about whether the sensor will pick up a gas leak just a few meters away.
With an ultrasonic gas leak detection system it is possible to verify that the ultrasonic gas leak detectors will also pick
up gas leaks AT A DISTANCE from the gas leaks. Innova Gassonic provides the service of performing on-site
commissioning of the ultrasonic gas leak detection system. A high-pressure hose connected to a bottle of nitrogen
enables the Innova Gassonic service engineer to simulate real gas leaks at a leak rate of e.a. 0,1 kg/sec in all the
potential leak locations (flanges, fittings, wellheads, etc.). This makes it possible to verify that the ultrasonic gas
detection system does in fact comply with the pre-defined safety standards.

As mentioned before, it is not necessary to calibrate the ultrasonic gas leak detector but some times local plant
regulations require regular documented test of the sensors. Both the Gassonic MM0100 and the Gassonic Observer
can be tested with the Portable Test and Calibration Unit the Gassonic 1701 that is a hand held unit especially
designed for field tests of the Gassonic ultrasonic gas leak detectors. Furthermore, the Gassonic 1701 can also be
used for calibration of the Gassonic Observer.

9. THE INNOVA GASSONIC ULTRASONIC GAS LEAK DETECTORS


Today Innova Gassonic produces and manufactures two types of ultrasonic gas leak detectors, the Gassonic
MM0100 and the Gassonic Observer.
9.1

THE GASSONIC MM0100

In the Gassonic MM0100 a special high quality stainless steel microphone picks up broad noise from the
surroundings and feeds the signals to a specially designed ultrasonic high-pass filter. A level detection circuit detects
if the ultrasonic level exceeds the alarm level. The level detection is user definable. If the alarm level has been
exceeded, the detection circuit will trigger an alarm delay timer, which will prevent false alarms. The timer runs for a
predefined period (the user-definable alarm delay). If the ultrasonic level is still above the alarm level after the alarm
delay time-out, the alarm relay of the detector is activated.
The Gassonic MM0100 can be connected to the plant DCS system or to the existing fire and gas detection system by
means of EX approved safety barriers. The Gassonic MM0100 is an intrinsically safe unit that needs tobe electrically
connected through approved safety barriers.
9.2

THE GASSONIC OBSERVER

The latest invention within ultrasonic gas leak detection is called the
Gassonic Observer (see picture to the right). The Gassonic
Observer has a high quality stainless steel microphone installed,
which is acoustically comparable with the Gassonic MM0100.
The Gassonic Observer was developed on the basis of field
experiences as well as continuos inputs from the industry. It holds
the following features:

4 20 mA standard analogue interface.


RS485 digital communication interface for adressable
communication
Integrated acoustic selftest function to ensure that no
unrevealed failures will occur
Integrated connection cable termination so that no additional
junction box is necessary.
Full stainless 316 steel design for installation in corrosive
offshore environment
Approved for installation in explosive environment (ATEX and
UL/ULC CLASS1 DIV1)

Figure 5: Gassonic Observer

Since the Gassonic Observer has the same acoustical charteristics as the exsisting Gassonic MM0100 this
means that it can be installed according to the same performance criteria with regards to leak detection
performance (detection of methane leaks at 0,1 Kg/sec) as the wellknown Gassonic MM0100.

10. CONCLUSION
Relying on traditional gas detection technologies can be highly problematic. Although these technologies may work
fairly well, changing wind directions and fast dillution of the gas cloud make it extremely difficult to ensure that these
technologies will in fact detect gas leaks. The LEL level does give an indication of the concentration of the leaking gas
but only in the sensor head or within the beam of IR light. Just a few metres away the concentration could be 100%
LEL.
The acoustic alternative makes it possible to pre-define the safety standards and use them when verifying the
performance of the entire detection system. Besides, the ultrasonic gas leak detection technology minimises the
influence of ever changing weather conditions found on most outdoor gas installations. An issue that is becoming
increasingly relevant because the tendency seems to be that the industry strives to have more ventilated and open
modules so that potential leaks will dillute as quickly as possible!
Along with discussions on improvements of the traditional technologies, that ought to be taken into account also on
future project group sessions regarding the fire and gas detection system.
As a British oil and gas supplier in the North Sea concludes in a report.
It is my opinion that in the future, gas production platforms will be protected from gas releases by a few strategically
positioned IR open path detectors and the main source of leak detection will be by ultrasound detection.
For additional information please contact:
Martin T. Olesen
General Manager
Innova Gassonic
Ultrasonic Gas Leak Detection
Energivej 30
2750 Ballerup
DK - Denmark
Phone:
+45 44200100
Fax: +45 44200101
Email: [email protected]
Web: www.gassonic.com

You might also like