HART Comm Module User's Guide (b0400ff - M)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 162
At a glance
Powered by AI
The document describes HART communication interface modules used with the Foxboro Evo process automation system. It provides an overview, quick start example, installation instructions, and technical specifications for the modules.

HART communication modules are used to connect HART field devices to control systems to enable communication and data exchange between the devices and control software.

The document describes the FBM214/214b, FBM215, FBM216/216b, FBM218, FBM244, FBM245, and FBM247 HART communication modules.

Foxboro Evo

Process Automation System

HART Communication
Interface Modules
Users Guide

*B0400FF*
B0400FF
Rev M
May 6, 2015

*M*

Schneider Electric, Invensys, Foxboro, Foxboro Evo, FoxCAE, I/A Series, and InTouch are trademarks of
Schneider Electric SE, its subsidiaries, and affiliates.
All other brand names may be trademarks of their respective owners.
Copyright 20022015 Invensys Systems, Inc.
All rights reserved.
Invensys is now part of Schneider Electric.

Contents
Preface.................................................................................................................................... xi
1. Introduction ...................................................................................................................... 1
Overview ................................................................................................................................... 1
HART Support in Foxboro Evo Control Software and Foxboro Control Software (FCS) ......... 4
2. Quick-Start Example ......................................................................................................... 5
3. Functional Characteristics ................................................................................................. 9
Functional and Environmental Constraints ............................................................................... 9
Input/Output Cabling ............................................................................................................
Cable Type .........................................................................................................................
Cable Length ......................................................................................................................
Use of Baluns .....................................................................................................................

10
10
11
11

Intrinsic Safety Considerations ................................................................................................ 12


4. Equipment Installation.................................................................................................... 13
HART FBMs, FBM247 and Termination Assembly Installation ............................................ 16
Redundant Adapter and Baseplate-Mounted TA Installation .................................................. 16
HART Device Connections ....................................................................................................
Connections to FBM214/214b/216/216b/244 ..................................................................
FBM214/214b/216/216b Termination Assembly Connections .....................................
FBM214/214b/216/216b Input Signal Flow Diagrams .................................................
FBM214/214b/216/216b, Cable Balun Module, 2-Wire Devices,
Wiring Diagrams ..........................................................................................................
FBM214/214b/216/216b, Cable Balun Module, 4-Wire Devices,
Wiring Diagram ...........................................................................................................
FBM214/214b/216/216b Simplified Schematic ............................................................
Connections to FBM215/218 ............................................................................................
FBM215/218 Termination Assembly Connections .......................................................
Connections to FBM244/245 ............................................................................................
FBM244/245 Termination Assembly Connections .......................................................
Connections to FBM247 ....................................................................................................
Pulse or Digital SOE Contact Sense Input Configuration .............................................
Digital NAMUR Sensor Input (Non-Intrinsically Safe) Configuration .........................
FBM247 Termination Assembly Connections ...............................................................
FBM247, Cable Balun Module, Wiring Diagram Example ...........................................
HART Communication Interface Modules Entity Parameters .......................................

17
18
18
19
23
27
28
29
29
32
32
36
36
37
38
46
47

iii

B0400FF Rev M

Contents

5. Control Block Configuration Information....................................................................... 49


ECBs and DCI Blocks Used with HART FBMs and HART-Capable FBM247 ..................... 49
Block Interconnections ........................................................................................................... 50
Configuration Procedures .......................................................................................................
Configuring IOBAD Options ............................................................................................
Point Addresses for HART and Analog I/O Signals ............................................................
Data Type Conversions ......................................................................................................

50
59
59
61

Equipment Control Blocks (ECBs) ......................................................................................


Creating and Editing FBM ECB (ECB200 or ECB202) ....................................................
Creating and Editing Device ECB (ECB201) .....................................................................
Configuring Blocks for FBM247 ........................................................................................
Configuring FBM ECB (ECB200) for FBM247 ...........................................................
Configuring Device ECB (ECB201) for FBM247 .........................................................
Configuring I/O Blocks (RIN, BIN, ROUT and BOUT) for the FBM247
Hardware Channels .......................................................................................................
Configuring RIN Block for HART Floating Point Digital Variables
for the FBM247 ............................................................................................................
Configuring IIN Block for HART Integer Digital Variables and Device
Status Bits for the FBM247 ...........................................................................................

62
63
64
66
66
69
71
72
73

Configuring DCI Blocks ......................................................................................................... 77


Example for Reading Pressure Measurement ...................................................................... 78
DCI Block Processing ............................................................................................................. 79
Key DCI Block Functions .......................................................................................................
Periodic/Change-Driven Execution ....................................................................................
Auto/Manual Mode Operation ..........................................................................................
Simulation Mode ...............................................................................................................
Signal Conditioning and Linear Scaling .............................................................................
Input Limiting ...................................................................................................................
Confirmed Outputs ............................................................................................................
Output Clamping ..............................................................................................................
Output Initialization ..........................................................................................................
Cascade Initialization .........................................................................................................
Fail-Safe Actions .................................................................................................................
DCI Status Transformations ..............................................................................................

80
80
80
80
80
80
80
81
81
81
82
83

Control Schemes Using DCI Blocks ....................................................................................... 84


6. Process Operator Displays............................................................................................... 87
Block Detail Displays ..............................................................................................................
ECB200 Block Detail Display ............................................................................................
ECB200 Information Pane/Faceplate ............................................................................
ECB200 Primary Data ..................................................................................................
ECB202 Block Detail Display ............................................................................................
ECB202 Information Pane/Faceplate ............................................................................
ECB202 Primary Data ..................................................................................................
ECB201 Block Detail Display ............................................................................................
iv

87
88
88
88
89
89
89
90

Contents

B0400FF Rev M

ECB201 Information Pane/Faceplate ............................................................................ 90


ECB201 Primary Data .................................................................................................. 90
ECB201 Extended Status Support ................................................................................. 91
7. Maintenance.................................................................................................................... 93
Overview ................................................................................................................................. 93
Operating Status ..................................................................................................................... 93
System Manager Displays and System Management Displays ................................................. 94
Display Applications .......................................................................................................... 94
HART FBM214/214b/215 Equipment Status and Information Display ............................ 96
HART FBM216/216b/218 Equipment Status and Information Display ............................ 99
HART-Capable FBM247 Equipment Status and Information Display ............................ 104
FBM214/214b/215/244 and FBM247 Equipment Change Display ................................ 111
Placing the FBM214/214b/215/244 and FBM247 On-Line ....................................... 111
FBM216/216b/218/245 Equipment Change Display ...................................................... 112
Placing the FBM216/216b/218/245 On-Line ............................................................. 113
HART Slave Device Equipment Status and Information Display ..................................... 115
FBM247 Device Equipment Status and Information Display .......................................... 118
HART Device and FBM247 Device/Signal Equipment Change Actions .......................... 121
Enabling Communications with Slave Devices ............................................................ 121
HART-Capable FBM247 Faceplates (Foxboro Evo Control HMI) .................................. 122
ECB200 Faceplate for FBM247 .................................................................................. 122
ECB201 Faceplate for FBM247 Devices ..................................................................... 126
FBM216/216b Redundant Power Supply Test (Internally Powered Transmitter) ................. 128
FBM245 Redundant Power Supply Test ............................................................................... 130
HART FBM and HART Capable FBM247 LED Indicators ................................................. 131
Service and Support .......................................................................................................... 137
Appendix A. HART FBM System Messages (SMON Log)................................................ 139
Index .................................................................................................................................. 143

B0400FF Rev M

vi

Contents

Figures
1-1.
1-2.
2-1.
3-1.
3-2.
3-3.
4-1.
4-2.
4-3.
4-4.
4-5.
4-6.
4-7.
4-8.
4-9.
4-10.
4-11.
4-12.
4-13.
4-14.
4-15.
4-16.
4-17.
4-18.
4-19.
4-20.
4-21.
4-22.
4-23.
4-24.
4-25.
4-26.
4-27.
4-28.
4-29.
4-30.
4-31.
4-32.

Compact 200 Series FBM and Standard 200 Series FBM (Examples) ........................... 2
HART FBMs used in a Typical Network Configuration ............................................... 3
Typical HART/Foxboro Evo Integration Process .......................................................... 5
Cable Balun Module ................................................................................................... 11
Use of a Cable Balun (Externally Powered) ................................................................. 12
Intrinsic Safety Barrier Usage, Module-Powered Device .............................................. 12
Example Standard HART FBM and Termination Assembly Baseplate Installation ..... 13
FBM Mounting Slots in Standard 200 Series Standard Baseplates ............................... 14
Redundant Adapter or Baseplate-Mounted TA Installation (Typical) .......................... 17
FBM214/216 or FBM214b/216b TA Field Device Connections ................................ 18
FBM214/214b Input Signal Flow (1 of 2) .................................................................. 19
FBM216/216b Input Signal Flow (1 of 2) .................................................................. 21
Cable Balun Module, Externally Powered
HART Input Channels, Wiring Diagram .................................................................... 23
Cable Balun Module, Internal and Externally Powered
HART Input Channels, Wiring Diagram .................................................................... 24
Cable Balun Module with Intrinsic Safety or Zener Barriers,
Internal and Externally Powered HART Input Channels, Wiring Diagram ................. 25
Cable Balun Module with Transformer Isolated Barrier,
Internal and Externally Powered HART Input Channels, Wiring Diagram ................. 26
Cable Balun Module with Transformer Isolated Barrier,
Internal and Externally Powered 4-wire Devices, Wiring Diagram .............................. 27
FBM214/214b/216/216b Field Device Input Interface, Simplified Schematic ............ 28
FBM215/218 TA Cable Connections ......................................................................... 29
FBM215 Output Signal Flow ..................................................................................... 30
FBM218 Output Signal Flow ..................................................................................... 30
FBM215/218 Field Device Output Interface, Simplified Schematic ........................... 31
FBM244/245 TA Field Device Connections ............................................................... 32
FBM244 Output Connections .................................................................................... 33
FBM245 Output Connections with Redundant Adapter Connections ....................... 34
FBM244/245 Module, Channel Isolated Output Circuit, Simplified Schematic ......... 35
FBM247 TA Field Device Connections ...................................................................... 38
FBM247 Loop-Powered Current Input Connections .................................................. 39
FBM247 Self-Powered or Externally Powered Current Input Connections ................. 40
FBM247 Analog Voltage Input or Discrete Voltage Monitor Connections ................. 40
FBM247 Loop-Powered Current Output Connections ............................................... 41
FBM247 Self-Powered or Externally Powered Current Output Connections .............. 42
FBM247 Digital Dry Contact Sense Connections ....................................................... 43
FBM247 Solid State Switch Connections ................................................................... 43
FBM247 24 V dc Discrete Output Connections ......................................................... 44
FBM247 Voltage Pulse In - Pulse Count Frequency, etc. Connections ....................... 44
FBM247 Current Pulse In -Pulse Count Frequency, etc. Connections ........................ 45
FBM247 with Cable Balun, Externally Powered HART Input Channels,
Wiring Diagram Example ........................................................................................... 46
vii

B0400FF Rev M

5-1.
5-2.
5-3.
5-4.
5-5.
5-6.
5-7.
5-8.
5-9.
5-10.
5-11.
5-12.
5-13.
7-1.
7-2.
7-3.
7-4.
7-5.
7-6.
7-7.
7-8.
7-9.
7-10.
7-11.
7-12.
7-13.
7-14.
7-15.

viii

Figures

ECB Hierarchy ........................................................................................................... 50


Typical Block Interconnections for FBM214/214b with HART Input Devices .......... 51
Typical Block Interconnections for FBM218 with HART Output Devices ................. 52
Typical Block Interconnections for FBM214/214b with 4-20 mA Input Devices ....... 53
Typical Block Interconnections for FBM247 with Various I/O Devices ..................... 54
System Manager - Connections Tab - For FCP270 Connected to HART FBMs ........ 64
System Manager - General Tab (FBM Equipment Status Display) - For HART FBM 65
SYSCFG Bit Mapping ................................................................................................ 67
Configuring SYSCFG in the Block Configurator From Grid Control ......................... 68
Configuring DVNAME in the Block Configurator From Grid Control ...................... 69
Configuring Channel in Network View ...................................................................... 70
Simple Cascade Configuration .................................................................................... 84
Supervisory Control Configuration ............................................................................. 85
System Manager - General Tab (Equipment Information Display) for HART Device ....................................................................................................... 94
FBM247 System Manager Display - Part 1 ............................................................... 104
FBM247 System Manager Display - Part 2 ............................................................... 105
ECB201 Equipment Information Fields for a FBM247 Channel .............................. 118
ECB200 Faceplates for FBM247 Devices - Main View and Diagnostic View ............ 122
ECB200 Faceplates for FBM247 Devices - Configuration Views .............................. 124
ECB201 Faceplates for FBM247s Devices ............................................................... 126
FBM216 Redundant Adapter Test Point Locations
(Standard FBM216b Redundant Adapter Is Similar) ................................................ 129
Compact FBM216b Redundant Adapter Test Point Locations ................................. 130
FBM245 Redundant Adapter Test Point Locations .................................................. 131
Standard HART FBM214/214b/215/244 LED Status Indicators ............................. 131
Compact HART FBM214b/215 LED Status Indicators ........................................... 132
Standard HART FBM216/216b/218/245 LED Status Indicators ............................. 132
Compact HART FBM216b/218 LED Status Indicators ........................................... 133
HART Capable FBM247 LED Status Indicators ...................................................... 133

Tables
4-1.
4-2.
5-1.
5-2.
5-3.
5-4.
5-5.
5-6.
5-7.
5-8.
5-9.
5-10.
5-11.
5-12.
5-13.
5-14.
7-1.
7-2.
7-3.
7-4.
7-5.
7-6.
7-7.
7-8.
7-9.
7-10.
7-11.
7-12.
7-13.
7-14.
7-15.

Part Numbers for HART FBMs, Redundant Adapters and TAs .................................. 15
Entity Parameters for HART Communication Interface Modules .......................... 47
ECBs and DCI Blocks Used with HART FBMs ......................................................... 49
Key Parameters ............................................................................................................ 55
DCI Block Parameters Requiring a Point Address ....................................................... 60
Point Address Values for DCI Blocks .......................................................................... 60
Data Type Conversions ............................................................................................... 62
ECB200 SYSOPT Parameter - Analog and Pulse Input Integration Period ................. 66
ECB201 DVOPTS Parameter - Device Options ......................................................... 70
RIN, BIN, ROUT, and BOUT PNT_NO Parameter Settings ................................... 71
RIN PNT_NO Parameter Settings for HART Floating-Point Digital Variables ......... 73
IIN PNT_NO Parameter Settings for HART Integer Digital Variables ...................... 73
HART Device Status Bits ............................................................................................ 73
STRIN PNT_NO Parameter Settings for HART String Input Variables .................... 74
PAKIN PKINGP Parameter Settings for HART Packed Boolean Block
Configuration ............................................................................................................. 75
DCI Parameter Status ................................................................................................. 83
FBM214/215 Equipment Status and Information Display Fields ............................... 96
FBM216/216b/218 Equipment Status and Information Display Fields ...................... 99
FBM247 Equipment Status and Information Display Fields ..................................... 105
FBM214/214b/215/244/247 Equipment Change Actions ........................................ 111
FBM216/216b/218/245 Equipment Change Actions ............................................... 112
HART Device Equipment Status and Information Display Fields ............................ 115
FBM247 Channel (ECB201) Equipment Status and Information Display Fields ..... 118
HART Device and FBM247 Device/Signal Equipment Change Actions .................. 121
FBM247 ECB200 ECB Status Indicators ................................................................. 123
FBM247 ECB200 FBM Status Indicators ................................................................. 123
FBM247 Information in a ECB200 Faceplate ........................................................... 125
FBM247s Device ECB201 ECB Status Indicators ................................................... 126
FBM247s Device ECB201 DVC Status Indicators .................................................. 127
FBM247 Information in a ECB200 Faceplate ........................................................... 128
HART FBM Operational Status LEDs ..................................................................... 134

ix

B0400FF Rev M

Tables

Preface
This document describes the HART Communication Interface Modules (FBM214/214b,
FBM215, FBM216/216b, FBM218, FBM244, and FBM245). This document also describes
how to use the HART-capable FBM247, which supports a range of analog, digital and pulse field
I/O signals, with HART analog I/O signals.

Who This Book Is For


This book is intended for the use of process control engineers and operators, instrument and
maintenance engineers, and other qualified and authorized personnel involved in setting up and
configuring, and maintaining Foxboro Evo equipment to provide a HART communication
interface.

What You Should Know


Prior to using this book, you should be generally familiar with the Foxboro Evo Process Automation System, and with DIN Rail Mounted Subsystem Users Guide (B0400FA). Detailed information relating to the various Foxboro Evo software and hardware elements is found in the reference
documents listed below.

Revision Information
For this revision of the document (B0400FF-M), the following changes were made:
Chapter 5 Control Block Configuration Information
Updated information about IOBAD on page 58.
Added Configuring IOBAD Options on page 59.
Added the IOBAD option to Table 5-7 on page 70.

Reference Documents
The following documents provide additional and related information.

Foxboro Documents

PSS 21H-2Z14 B4 FBM214, HART Communication Input Interface Modules


(Legacy)

PSS 31H-2Z14 FBM214b, HART Communication Input Module


PSS 31H-2C214 Compact FBM214b, HART Communication Input Interface
Module
PSS 31H-2Z15 FBM215 HART Communication Output Module
PSS 31H-2C215 Compact FBM215 HART Communication Output Interface
Module
xi

B0400FF Rev M

Preface

PSS 21H-2Z16 B4 FBM216 HART Communication Redundant Input Interface


Modules (Legacy)
PSS 31H-2Z16 FBM216b Redundant HART Communication Input Module
PSS 31H-2C216 Compact FBM216b, HART Communication Redundant Input
Interface Module
PSS 31H-2Z18 FBM218 HART Communication Redundant Output Module
(FBM218)

PSS 31H-2C218 Compact FBM218 HART Communication Redundant Output


Interface Module
PSS 31H-2Z44 FBM244, 0 to 20 mA I/O Module with HART Support
PSS 31H-2Z45 FBM245, 0 to 20 mA I/O Module with HART Support (Redundant)
PSS 31H-2Z47 FBM247, Current/Voltage Analog/Digital/Pulse I/O Configurable
Channel Module
Compact 200 Series I/O Subsystem Overview (PSS 31H-2COV B3)
DIN Rail Mounted Subsystem Users Guide (B0400FA)
100 Series Fieldbus Module Migration User's Guide (B0700BQ)
Field Control Processor 280 (FCP280) User's Guide (B0700FW)
Z-Module Control Processor 270 (ZCP270) User's Guide (B0700AN)
Field Control Processor 270 (FCP270) User's Guide (B0700AR)
Field Control Processor 270 (FCP270) Sizing Guidelines and Excel Workbook
(B0700AV)
Integrated Control Block Descriptions (B0193AX)
Control Processor 270 (CP270) and Field Control Processor 280 (CP280) Integrated
Control Software Concepts (B0700AG)
Block Configurator User's Guide (B0750AH)
System Manager (B0750AP)
Control HMI Application User's Guide (B0750AQ)
Foxboro Evo Process Automation System Deployment Guide (B0750BA)
Field Device Manager for HART Devices Installation Guide (B0750CN)
I/A Series Configuration Component (IACC) User's Guide (B0700FE)
Integrated Control Configurator (B0193AV)
System Definition: A Step-by Step-Procedure (B0193WQ and associated on-line Help)
Process Operations and Displays (B0700BN)
System Management Displays (B0193JC and associated on-line Help)

Control Core Services v9.0 Software Installation Guide (B0700SP)


Computer Aided Engineering for I/A Series Control Station Databases FoxCAE
Version 4.0 (B0193MR)
FoxDraw Software v10.4 (B0700FD)
FoxView Software v10.4 (B0700FC)

xii

Grouped Object Editor for Displays (B0193DV)

Preface

B0400FF Rev M

Intelligent Field Device Configurator IFDC for use with I/A Series Systems (B0700EU)
HT991 Universal Hand terminal for HART Devices [MI EMO0110 A-(en)].
Most of these documents are available on the Foxboro Evo Electronic Documentation media
(K0174MA). The latest revisions of each document are also available through our Invensys
Global Customer Support at https://support.ips.invensys.com.

HART Documents
The following is a partial listing of the documents available at the HART website
(http://www.hartcomm.org):
HART FSK Physical Layer Specification, HCF_SPEC-54
HART Application Guide, HCF LIT 34
End User Info
Complete HART Guide.

Glossary of Terms
The following terminology, used throughout this users guide, relates to the HART FBMs and
their associated equipment.
Baseplate

The baseplate provides mounting for DIN rail mounted FBMs and FCMs
(see Figure 4-1 on page 13). A standard 200 Series baseplates eight
mounting positions can accommodate up to eight FBMs, or a combination of FBMs and FCMs. A Compact 200 Series 16-slot horizontal baseplate can accommodate up to 16 Compact 200 Series FBMs. The
baseplate also provides the necessary connectors for dc power, the Foxboro
Evo module Fieldbus, and termination cables.

Control Station

This is any Foxboro Evo module that effects process control via the Foxboro Evo Ethernet trunk Fieldbus. An example is the Field Control Processor 280 (FCP280). The control station controls process variables using
algorithms contained in functional control blocks configured by on-site
process engineers to implement the desired control strategies.

DIN Rail Mounted Subsystem


The DIN rail mounted subsystem provides a high-speed communication
interface between the host control processor (for example a Foxboro
control station) and field I/O sensors and actuators. DIN rail mounted
devices, which include FBMs, FCMs and supporting cables and connectors, mount on a baseplate which, in turn, mounts on a DIN rail. This
subsystem is described in detail in DIN Rail Mounted Subsystem Users
Guide (B0400FA).
DCI

Distributed Control Interface (DCI) control blocks are Foxboro control


blocks specially designed to handle HART-related digital I/O communications (see block descriptions on Chapter 5 Control Block Configuration Information). They are used in conjunction with the FBM to

xiii

B0400FF Rev M

Preface

interface digital field device I/O communications with the Foxboro control station.
ECB

An equipment control block, created for each FBM and external field
device, provides a holding place for the software data associated with
that FBM or external field device.

FBM

Fieldbus Modules provide the interface between process sensors/actuators


and the Fieldbus in a standard Foxboro Evo system.
FBM214/214b/215/216/216b/218/244/245/247 are examples of the
many types of FBMs offered as part of the Foxboro Evo system.

FCM

The Fieldbus Communications Module is an interface which allows the


HART Communication Interface Modules (and other DIN rail
mounted FBMs) to communicate with the control station via the Foxboro
Evo 10 Mbps Ethernet trunk Fieldbus. It converts the 10 Mbps Ethernet
signals used by the control station to 2 Mbps signals used by the FBM,
and vice versa.

Fieldbus

This term applies in general to two specific buses: the10 Mbps Ethernet
trunk Fieldbus and the 2 Mbps Module Fieldbus. (Figure 1-2 shows how
these buses are used in the Foxboro Evo communication network.)

FoxCAE

Computer-Aided Engineering software, part of the Foxboro Evo Process


Automation System, is used to configure control strategies.

HART

Highway Addressable Remote Transducer - Rosemount product, now


industry standard for digital communications from a DCS to transmitters
and positioners.

IFDC

The Foxboro Evo Intelligent Field Device Configurator is a software package providing remote bidirectional communications with the Foxboro and
Eckardt intelligent field devices.

Letterbug

This is an identifier for Foxboro stations and control devices, particularly


for Fieldbus Modules (FBMs).

Parameter

This is a named element in the data structure of a device function block,


ECB, or Foxboro Evo control block.

Redundant Adapter
The redundant adapter, used with the redundant FBM pairs (FBM216,
FBM216b or FBM218), provides a Y connection between the FBM
pairs and the associated Termination Assembly (TA). This allows either
module in the pair to communicate with the field devices.
TA

xiv

The termination assembly provides the means of attaching the HART


Communication Interface Modules to the field devices.

1. Introduction
This chapter provides an overview of the HART Communication Interface Modules, and the
network configuration in which they are used.

Overview
The HART Communication Input/Output Interface Modules
(FBM214/214b215/216/216b/218/244/245) and the HART-capable FBM247 provide analog
and digital communications to and from HART compliant field devices. They also support standard 4-20mA signals from analog devices. Each of these FBMs contains eight channels that are
group isolated for the FBM214/216 and individually isolated for the
FBM214b/215/216b/218/244/245 and FBM247.
The following HART FBMs are available as either Compact or standard 200 Series FBMs:
FBM214/214b Each channel provides bidirectional digital communications with a
field device, and performs analog to digital conversion on the 4 to 20 mA input control signal from that device.
FBM215 Each channel provides bidirectional digital communications with a field
device, and performs digital to analog conversion to generate the 4 to 20 mA output
control signal to that device.

FBM216/216b These modules, used in pairs, provide a redundant version of the


FBM214/214b.
FBM218 This module, used in pairs, provides a redundant version of the FBM215.
Compact 200 Series FBMs provide the same functionality as standard 200 Series FBMs while utilizing a smaller footprint, as shown in Figure 1-1. While a standard 200 Series FBM baseplate
supports up to eight standard 200 Series FBMs, a Compact 200 Series 16-slot horizontal baseplate supports up to sixteen Compact 200 Series FBMs in a similar amount of space. Compact
200 Series FBMs have the same software as their standard 200 Series FBM counterparts and the
Foxboro Evo Control Core Services does not distinguish between them. The Compact 200 Series
I/O subsystem is described in DIN Rail Mounted Subsystem Users Guide (B0400FA) and Compact
200 Series I/O Subsystem Overview (PSS 31H-2COV B3).

B0400FF Rev M

1. Introduction

Compact 200 Series


FBM (FBM214b Shown)

Standard 200 Series


FBM (FBM214b Shown)

Figure 1-1. Compact 200 Series FBM and Standard 200 Series FBM (Examples)

The following HART FBMs are available only as standard 200 Series FBMs:
FBM244 Each input channel accepts an analog sensor input such as a 4 to 20 mA
transmitter or a self-powered 20 mA source. Each output channel drives an external
load and produces a 0 to 20 mA output. It supports any mix of standard 4 to 20 mA
devices and HART devices.
FBM245 These modules, used in pairs, provide a redundant version of the
FBM244.
FBM247 - This HART-capable FBM supports a wide range of analog, digital or pulse
I/O capabilities, including support for HART I/O signals. Each channel is individually configurable, allowing multiple types of I/O signals to connect to a single
FBM247. Refer to the FBM247 Current/Voltage Analog/Digital/Pulse I/O Configurable Channel Interface Module with HART Support section in DIN Rail
Mounted Subsystem Users Guide (B0400FA) to learn about the full capabilities of this
FBM.
HART FBMs and the HART-capable FBM247 communicate with the fieldbus I/O devices on a
master/slave basis. HART is a communications standard which supports digital communication
between a master (one of the HART FBMs) and a broad range of slave devices which include
transmitters and actuators. Each HART FBM can service up to eight slave devices in a point-topoint network configuration; multidrop network configurations are not supported. During normal operation, each communication is initiated by the HART FBM, which serves as the primary
master. The slave devices can only acknowledge received messages, or send messages to the master
when requested to do so.
The FBM247 can support HART field devices in a similar manner as the HART FBMs, in addition to the I/O signals described in DIN Rail Mounted Subsystem Users Guide (B0400FA).
The HART communication protocol is based on the Bell 202 telephone communication standard
and operates according to the frequency shift keying (FSK) principle. This is in addition to the 4
to 20 mA normal analog input or analog output signal (depending on the FBM model). The digital signal is made up of two frequencies, 1,200 Hz and 2,200 Hz, representing respectively the
bits 1 and 0. The sine waves of these two frequencies are superimposed on the direct current
(analog) signal to provide simultaneous analog and digital communications. The FSK signal
2

1. Introduction

B0400FF Rev M

allows communication at 1200 baud. Burst mode of communication is not used by the HART
FBMs.
The FBMs operate in a point-to-point configuration. In this mode, the traditional 4-20 mA signal is used to communicate one main process variable. The HART communication digital signal
provides access to secondary process variables, configuration parameters, and other device data
that can be used for operations, commissioning, maintenance, and diagnostic purposes.
Figure 1-2 shows the relationship between the various equipment elements in the subsystem. The
HART FBMs and the HART-capable FBM247 provide a communication interface between the
Foxboro control station and the HART I/O field devices. Termination assemblies (TAs) provide
for physical connection of the field devices to the FBMs.
To FCP280, FCP270, or
ZCP270/FCM100E/Et Pair

2 Mbps
Module Fieldbus

FBM214
or
FBM214b

Termination
Assemblies

TA

...

FBM215

TA

...

FBM216
FBM216
or
or
FBM216b FBM216b

FBM218

FBM218

REDUNDANT ADAPTER

REDUNDANT ADAPTER

TA

TA

...

...

Up to 8 Slave Devices per HART FBM


Note: Each HART FBM and HART-capable FBM247 can service up to eight slave devices in a
point-to-point network configuration.
Figure 1-2. HART FBMs used in a Typical Network Configuration

Physically, the FBMs mount on a baseplate that is DIN rail mounted. For detailed information on
the functional aspects of the FCMs and other DIN rail mounted equipment, refer to DIN Rail
Mounted Subsystem Users Guide (B0400FA).
The redundant adapter, used with the redundant FBM pairs (FBM216/216b, FBM218 and
FBM245), provides a Y connection between the FBM pairs and the associated TA. This allows
either module in the pair to communicate with the field devices.
As well, a baseplate-mounted termination assembly (TA) is available for the HART-capable
FBM247 (as well as other non-HART FBMs, as discussed in DIN Rail Mounted Subsystem Users
Guide (B0400FA)). Using a baseplate-mounted TA eliminates the need to have a separate marshalling cabinet for the FBMs I/O, or for the spacing requirements needed to mount a separate,
standard termination assembly. This TA mounts directly onto the field I/O connectors of the 200
Series baseplate, in a similar manner as the redundant adapter. This TA supports two, non-redundant FBMs, provided that these FBMs are installed in adjacent slots as described in Redundant
Adapter and Baseplate-Mounted TA Installation on page 16.

B0400FF Rev M

1. Introduction

The field devices can be configured using any of the following:


The Foxboro Intelligent Field Device Configurator (IFDC) Version 2.2, which is an
optional component of a Foxboro Evo control system
A hand held configurator connected to the active (operational) link between the TA
and the devices.
Software residing in the HART FBMs, control station, and Foxboro Evo control workstations
provide full support of the HART communication protocol. On the Foxboro Evo system side, the
HART FBMs interface with the control station and other hardware and software elements of the
Foxboro Evo system to provide proven control, alarming, trending, and display capabilities. The
major functional components of this software are:
Run-time Software Supports the reading and writing of data to and from the field
device, treating these data as standard field I/O values in Foxboro Evo system. This
includes Distributed Control Interface (DCI) control blocks, which are specifically
designed to interface I/O signals from field devices.
Foxboro Evo System Software Integrates the HART FBMs and connected field
devices into the overall Foxboro Evo system equipment configuration. This integration is consistent with the integration of other Foxboro Evo FBM types, and the field
devices to which they connect.
Diagnostics Startup and maintenance diagnostics are provided for the HART FBMs.

HART Support in Foxboro Evo Control Software and


Foxboro Control Software (FCS)
HART support is provided as part of the software packages included in Foxboro Control Software (FCS) v3.x or earlier. However, in FCS v4.x or Foxboro Evo Control Software v5.0 or later,
additional functionality was added to the HART FBMs. This functionality is supported by a separate software package called Field Device Manager for HART, which is described in the Field
Device Manager for HART Devices Installation Guide. This new Field Device Manager for HART
software must be purchased separately from www.BuyAutomation.com.
If upgrading from FCS v3.x to FCS v4.x or Foxboro Evo Control Software v5.0 or later, or installing a new Foxboro Evo system with FCS v4.x or the Control Software v5.0 or later, be aware that
you must purchase and install this new Field Device Manager for HART to support HART FBMs
on your Foxboro Evo system.

2. Quick-Start Example
This chapter provides an example configuration, which provides most of the information you
need to get your Foxboro Evo system and HART subsystem up and running in the shortest
possible time.
A typical sequence for installing and configuring a HART subsystem in a Foxboro Evo system is
outlined in Figure 2-1. Following this diagram is the procedure, whose steps are keyed to the
diagram.
NOTE

The following assumes that the individual HART field devices have been configured
for the required process control operations.

Start

1
Install HART FBMs
(or FBM247) and
Associated Foxboro Evo
Equipment

Connect Field
Devices to TA(s)

Create and Edit


an ECB110 for
FCM Hosting FBMs

4
Create and Edit
an ECB200 for
Each FBM214/214b/215/
244/247

5
Create and Edit
Create
andfor
Edit
an
ECB202
ECB202
(if required)
Each
FBM216/216b/218

Create and Edit


an ECB201 for
Each Field Device

Configure Field
Devices

Enable
Communication with
Each Field Device

Create and Edit


DCI Blocks for
Control Strategy

10

Verify Slave I/O Data 11


Using Block Detail
Displays

8
Place FBMs On-line

Checkpoint the
Database

12

Stop
NOTE: For the FBM247, all I/O signals may be from various sources, not necessarily field devices.
However, the same basic principles for configuration apply to this FBM.
Figure 2-1. Typical HART/Foxboro Evo Integration Process

B0400FF Rev M

2. Quick-Start Example

NOTE

This following overview of procedures assumes that you are familiar with Foxboro
Evo system concepts and HART concepts. Appropriate documents and sections
herein are referenced in each step.
1. Install the Foxboro Evo system, including the HART FBMs.
a. Plan the major elements of the current Foxboro Evo system, such as the 200 Series
baseplates, HART FBMs, and their power supplies, as described in DIN Rail
Mounted Subsystem Users Guide (B0400FA).
To set up your workstation, refer to the Hardware and Software Specific Instructions
document that was shipped with your workstation.
Plan and install the legacy I/A Series system equipment as described in
System Equipment Installation (B0193AC).
b. Perform the system definition by referring to the Configuration Information
section of DIN Rail Mounted Subsystem Users Guide (B0400FA).
c. Install the current Foxboro Evo Control Core Services software; refer to the appropriate Control Core Services installation document. All these documents are available on the Invensys Global Customer Support website
(https://support.ips.invensys.com).
d. Install the HART FBMs and the associated baseplate, FCM(s), redundant adapters, and TA(s) as described in the DIN Rail Mounted Subsystem Users Guide
(B0400FA) and Chapter 4 Equipment Installation of this user guide.
2. Connect field devices to the TAs.
Connect the field devices directly to the FBM TAs as described in Chapter 4 Equipment Installation.
3. Create and edit ECB110 for FCM or FCM100E/Et that hosts the HART FBMs.
Refer to the appropriate document for your system:
Block Configurator User's Guide (B0750AH)
I/A Series Configuration Component (IACC) User's Guide (B0700FE)
Integrated Control Configurator (B0193AV)

DIN Rail Mounted Subsystem Users Guide (B0400FA).


4. Create and edit ECB200 for each FBM214/214b/215/244/247.
Refer to the appropriate document for your system:
Block Configurator User's Guide (B0750AH)
I/A Series Configuration Component (IACC) User's Guide (B0700FE)
Integrated Control Configurator (B0193AV)
Also see Creating and Editing FBM ECB (ECB200 or ECB202) on page 63.
For the FBM247, refer to Configuring FBM ECB (ECB200) for FBM247 on
page 66.

2. Quick-Start Example

B0400FF Rev M

5. Create and edit ECB202 for each FBM216/216b/218/245.


Refer to the appropriate document for your system:
Block Configurator User's Guide (B0750AH)
I/A Series Configuration Component (IACC) User's Guide (B0700FE)
Integrated Control Configurator (B0193AV)
Also see Creating and Editing FBM ECB (ECB200 or ECB202) on page 63.
6. Create and edit an ECB201 for each field device, or I/O signal for the FBM247.
Refer to the appropriate document for your system:
Block Configurator User's Guide (B0750AH)
I/A Series Configuration Component (IACC) User's Guide (B0700FE)
Integrated Control Configurator (B0193AV)
Also see Creating and Editing Device ECB (ECB201) on page 64.
The FBM247 supports a range of I/O signals, from a variety of sources including
HART field devices. To configure the appropriate I/O signals for the FBM247, refer
to Configuring Device ECB (ECB201) for FBM247 on page 69.
7. Configure HART field devices.
Perform the configuration procedures with the tool of your choice such as the HT991
hand terminal or Foxboro Evo Intelligent Field Device Configurator. (This does not
apply to non-HART field devices or non-field device related signals connecting to the
FBM247.)
8. Place FBM(s) on-line via System Manager or System Management Displays
(SMDH).
See Placing the FBM214/214b/215/244 and FBM247 On-Line on page 111 and
Placing the FBM216/216b/218/245 On-Line on page 113.
9. Enable communication with each field device via System Manager or SMDH.
See Enabling Communications with Slave Devices on page 121. (This does not
apply to non-field device related signals connecting to the FBM247.)
10. Create and edit DCI blocks for all device I/O points to be processed.
See Configuring DCI Blocks on page 77.
11. Verify I/O data using the block detail displays.
a. Access the detail displays with the appropriate application for your system:
For the Foxboro Evo Control Software Block Select application, refer to Control HMI Application User's Guide (B0750AQ).
For the FoxSelect compound/block overview utility, refer to Process Operations
and Displays (B0700BN) for details.
b. Access the block detail display for each DCI block created, and confirm its data.
12. Checkpoint the database. For details, refer to the following documentation:

System Manager (B0750AP)


Block Configurator User's Guide (B0750AH).
System Management Displays (B0193JC)
7

B0400FF Rev M

2. Quick-Start Example

I/A Series Configuration Component (IACC) User's Guide (B0700FE)


Integrated Control Configurator (B0193AV).

3. Functional Characteristics
This chapter addresses various requirements and constraints relating to the connection of the
HART FBMs and the HART-capable FBM247 to the field devices or HART I/O signals, and
their operation in conjunction with the control station.
When planning for installation and operation of the HART FBMs and the associated field
devices, or the HART-capable FBM247 and its associated HART I/O signals (or field devices),
you must consider the following factors:
FBM functional and environmental constraints
Input/Output Cabling.

Functional and Environmental Constraints


The HART FBMs and the HART-capable FBM247 are designed for use with the Foxboro Evo
system hardware and software. The FBMs communicate with the Foxboro Evo system via a
2 Mbps HDLC Module Fieldbus, and coexist on this fieldbus with other Fieldbus Modules
(FBMs).
HART FBM operation requires I/A Series software, version 6.4-v8.8 or Foxboro Evo Control
Core Services v9.0 or later.
NOTE

Foxboro Evo Control Core Services v9.0 or later supports all HART FBMs.
For legacy systems with I/A Series software:
- FBM214b and FBM216b require I/A Series software, version 8.2-v8.8.
- FBM244 and FBM245 require I/A Series software, version 8.6-v8.8.
- The HART-capable FBM247 requires I/A Series software, version 8.7-v8.8.
- The Compact 200 Series FBMs require I/A Series software v8.8 or Foxboro Evo
Control Core Services v9.0 or later.
Refer to the following documents for functional and environmental specifications relating to the
FBM214/214b/215/244, the redundant FBM216/216b/218/245 and FBM247 modules and the
associated TAs:
PSS 21H-2Z14 B4 FBM214, HART Communication Input Interface Modules
(Legacy)
PSS 21H-2Z14 B5 FBM214b, HART Communication Input Interface Module
PSS 31H-2C214 B4 Compact FBM214b, HART Communication Input Interface
Module
PSS 21H-2Z15 B4 FBM215 HART Communication Output Interface Module
PSS 31H-2C215 B4 Compact FBM215 HART Communication Output Interface
Module
PSS 21H-2Z16 B4 FBM216 HART Communication Redundant Input Interface
Modules (Legacy)
9

B0400FF Rev M

3. Functional Characteristics

PSS 21H-2Z16 B5 FBM216b HART Communication Redundant Input Interface


Module
PSS 31H-2C216 B4 Compact FBM216b, HART Communication Redundant Input
Interface Module
PSS 21H-2Z18 B4 HART Communication Redundant Output Interface Module
(FBM218)
PSS 31H-2C218 B4 Compact FBM218 HART Communication Redundant Output
Interface Module
PSS 21H-2Z44 B4 FBM244, 0 to 20 mA I/O Interface Module with HART Support
PSS 21H-2Z45 B4 FBM245, 0 to 20 mA I/O Interface Module with HART Support
(Redundant)
PSS 21H-2Z47 B4 - FBM247, Current/Voltage Analog/Digital/Pulse I/O Configurable
Channel Interface Module
NOTE

The HART-capable FBM247 supports a wide range of analog, digital or pulse I/O
capabilities, including support for HART I/O signals. Refer to the FBM247 Current/Voltage Analog/Digital/Pulse I/O Configurable Channel Interface Module with
HART Support section in DIN Rail Mounted Subsystem Users Guide (B0400FA) to
learn about the full capabilities of FBM247.
HART FBMs and the HART-capable FBM247 are used in the configuration shown in Figure 1-2
on page 3. Factors to be considered when designing a fieldbus network configuration for your
particular application are:
Input/output cabling Type, length, and the use of baluns
Intrinsic safety.
These factors are addressed in the following subsections.
NOTE

These subsections apply only to HART FBMs and the HART-capable FBM247
when connected to HART field devices. To learn about cabling for the FBM247
when connected non-HART field devices, refer to the Field Signal Connections
section in DIN Rail Mounted Subsystem Users Guide (B0400FA).

Input/Output Cabling
The basic cabling scheme is shown in Figure 1-2 on page 3 and the actual connections to the TAs
are addressed in Chapter 4 Equipment Installation. The following paragraphs provide additional information.

Cable Type
Cable Type A, standard shielded twisted pair (STP) cabling, is used to wire the field devices to
termination assemblies (TAs). Unshielded cable may be used only when it has been conclu-

10

3. Functional Characteristics

B0400FF Rev M

sively demonstrated that ambient noise does not affect communication. For details, refer to
HART FSK physical layer specification document HCF_SPEC-54.

Cable Length
The maximum permissible distance from a HART FBM to a compliant field device is a function
of the device type. For details, refer to HART FSK physical layer specification document
HCF_SPEC-54.

Use of Baluns
A cable balun module, shown in Figure 3-1, is used to maintain digital communication line balance for Intelligent Field Devices connected in FBM loops that are powered from a common
external power supply. This powering method effectively connects one line of each loop to a single
point. Without the use of a balun, the multiple common connections at the external power source
would cause cross-talk between the loops.

Figure 3-1. Cable Balun Module

Figure 3-2 shows typical hookup. The Cable Balun module provides protection to the HART signal and eliminates cross-talk between the channels and/or disruption to the HART signal. They
are recommended when the HART protocol on the HART FBMs is being used and the customer
is providing external power to the loop. The use of an external power supply common to two or
more loops requires a Cable Balun Module to maintain communication signal line balance.

11

B0400FF Rev M

3. Functional Characteristics

FBM
Termination
Assembly

_
T
+

Intrinsic
Safety
Barrier
(when used)

iP

Field
Cable
Side

1
2
3
4
5
6
7
8

System
Side

i+
i-

1
2
3
4
5
6
7
8

Cable
Balun
Module
CBM-4
(P0903SV)

To Other
Channels
External
Power
Supply

To NegativeTerminal
of Ext. Power Supply

Note: Each balun module supports four channels. Two balun modules are required for eight
channels of the FBM.
Figure 3-2. Use of a Cable Balun (Externally Powered)

There is no signal isolation circuitry in the Cable Balun that would provide any isolation when
used on the 4-20mA signal. However, if high frequency noise is present on the lines, the baluns
can also tend to cancel out this external interference noise.

Intrinsic Safety Considerations


The HART FBMs and the HART-capable FBM247 do not offer intrinsically safe operation. A
safety barrier can be used as shown in Figure 3-2 (for externally powered field devices) or
Figure 3-3 (for module powered devices). For additional information on intrinsic safety considerations, refer to the HART Application Guide, HCF LIT 34.

Intrinsic
Safety
Barrier
(when used)

FBM
Termination
Assembly
+

iP

i+
i-

Figure 3-3. Intrinsic Safety Barrier Usage, Module-Powered Device

12

4. Equipment Installation
This chapter provides installation information for the HART FBMs, redundant adapters, and
associated termination assemblies (TAs).
Before installing the HART FBMs, you must install the major elements of the Foxboro Evo Process Automation System as follows [refer to DIN Rail Mounted Subsystem Users Guide
(B0400FA)]:
1. Perform the system definition by referring to Configuration Information in the
DIN Rail Mounted Subsystem Users Guide (B0400FA).
2. Install the current Control Core Services - refer to the appropriate Control Core Services installation document. All these documents are available on the Invensys Global
Customer Support website (https://support.ips.invensys.com).
3. Install the HART FBMs associated baseplate, if it is not already installed, as described
in DIN Rail Mounted Subsystem Users Guide (B0400FA).
A typical standard HART FBM installation including an FBM214, FBM215, and a redundant
pair of FBM216s is shown in Figure 4-1.

Module Fieldbus
Baseplate

To Fieldbus
Communications
Modules,
FCP270, or
FCP280

Operational Status

Operational Status

Operational Status
IR Active

01

IR Active

01

IR Active

01

Master

02

Master

02

Tracker

03

Tracker

03

03

04

04

04

05

05

05

06

06

06

07

07

07

08

08

08

FBM216
Baseplate I. D.

8 Communication,
No.
1
Redundant HART
Input
0
ON
P0917TN
1
OFF

2
ON
ON

ON

OFF OFF

To Next
Baseplate (If
Applicable)

02

FBM216

FBM215

8 Communication,
Redundant HART Input
P0917TN

Channel Isolated
8 Communication,
HART Output
P0917TQ

OFF

Termination
Cable
al Status

Operation

01

01

02

03

04

02

03

08

N
P
U
T

05

0607

04
05

i- i+
i-

iP
i+ iP
i- i+ iP
i- i+ iP
i- i+ iP
i- i+ iP
i- i+ iP
i- i+ iP

-2

IR Active

C
C 8
C 70
C 60
C 05 0

C 4
C 30
C 02 0
01

06
07
08

B
B 08

B 07
B 06

B 05
B 04
B 03
B 02
1

A
A 08

A 07

A 06
A 05
04

A
A 03
A 02

FBM21

n,
unicatio
8 Comm ut
Inp
HART Q
P0914X

Fieldbus
Module
(FBM214)

01

Termination
Assembly
Figure 4-1. Example Standard HART FBM and Termination Assembly Baseplate Installation

13

B0400FF Rev M

4. Equipment Installation

NOTE

For diagrams and installation instructions for the Compact 200 Series FBMs, refer
to DIN Rail Mounted Subsystem Users Guide (B0400FA).
As shown in Figure 4-1, the HART FBMs mount on their appropriate baseplate, and the termination assembly (TA) connects to the baseplate by means of a Type 1 termination cable. Figure 4-2
shows the available FBM mounting slots in the horizontal and vertical standard baseplates.
Horizontal-Mount Baseplate
Slots for Non-Redundant HART FBMs
2

OFF

Baseplate I. D.
No.
0
1
2
3

1
ON

2
ON

OFF ON
ON OFF
OFF OFF

Slots for Redundant Pairs

Vertical-Mount Baseplate
1

A
1

OFF

Baseplate I. D.
No.
0
1
2
3

1
ON

2
ON
OFF ON
ON OFF
OFF OFF

B
4
Slots for Redundant Pairs
5

Slots for
Non-Redundant
HART FBMs

C
6
7

D
8

Figure 4-2. FBM Mounting Slots in Standard 200 Series Standard Baseplates

14

4. Equipment Installation

B0400FF Rev M

NOTE

For the available Compact FBM mounting slots in the Compact 200 Series 16-slot
horizontal baseplate, refer to FBM Installation (Placement) in DIN Rail Mounted
Subsystem Users Guide (B0400FA).
The part numbers for HART FBMs and the associated TAs are listed in Table 4-1.
Table 4-1. Part Numbers for HART FBMs, Redundant Adapters and TAs

Equipment
FBM214
FBM214b (Standard)
FBM214b (Compact)
FBM215 (Standard)
FBM215 (Compact)
FBM216
FBM216b (Standard)
FBM216b (Compact)
FBM218 (Standard)
FBM218 (Compact)
FBM244
FBM245
FBM247
Redundant Adapter for FBM216
Redundant Adapter for FBM216b (Standard)
Redundant Adapter for FBM216b (Compact)
Redundant Adapter for FBM218 (Standard)
Redundant Adapter for FBM218 (Compact)
Redundant Adapter for FBM245
Compression-type TA for FBM214/216
Compression-type TA for FBM214b/216b
Compression-type TA for FBM215/218
Compression-type TA for FBM244/245
Compression-type TA for FBM247
Baseplate-mounted TA2 for FBM247
Ring lug-type TA for FBM214/216
Ring lug-type TA for FBM215/218
1.
2.

Part Number
P0914XQ/P0922VT
P0927AH
RH101AB
P0917TQ/P0922VU
RH101AC
P0917TN/P0922VV
P0927AJ
RH101AD
P0917XK/P0922VW
RH101AE
P0927AK
P0927AL
P0927BN
P0917XQ
P0924DT
RH101AX
P0916QD
RH101AY
P0924DU
P0916BX
P0924JH
P0917XV
P0924QU, P0924QZ1
P0924WW
P0924WG
P0926EA
P0926EK

P0924QZ has output bypass jacks.


Baseplate mounted TAs cannot be installed on the Compact 200 Series baseplate.

15

B0400FF Rev M

4. Equipment Installation

For the available termination cables, refer to Polyurethane Termination Cables and Part Numbers, Low Smoke Zero Halogen (LSZH) Termination Cables and Part Number, and Hypalon
TA Cables and Part Numbers in DIN Rail Mounted Subsystem Users Guide (B0400FA).
For general instructions on installing the FBMs and TAs, refer to DIN Rail Mounted Subsystem
Users Guide (B0400FA). The non-redundant FBM214/214b/215/244/247 can be located in any
slot on the baseplate, with the associated TAs connected to the associated cable connectors.
NOTE

FBM247s may use baseplate-mounted TAs, which mount directly onto the field
I/O connectors of the 200 Series baseplate. A baseplate-mounted TA provides field
I/O wiring support for two FBM247s in adjacent positions on the baseplate (positions 1 and 2, 3 and 4, 5 and 6 or 7 and 8).
The redundant FBM216/216b/218/245 require a redundant adapter. They must be located in
adjacent positions on the baseplate:
For the Compact 200 Series 16-slot horizontal baseplate, positions 1 and 2, 3 and 4, 5
and 6, 7 and 8, 9 and 10 (the second 1 and 2), 11 and 12 (the second 3 and 4), 13 and
14 (the second 5 and 6), or 15 and 16 (the second 7 and 8)
For standard 200 Series FBM baseplates, positions 1 and 2, 3 and 4, 5 and 6, or 7 and
8.

HART FBMs, FBM247 and Termination Assembly


Installation
Install the HART FBMs, FBM247, redundant adapters and TAs per the installation instructions
in DIN Rail Mounted Subsystem Users Guide (B0400FA).
The following subsections describe how to install and wire the FBMs TAs and redundant
adapters.

Redundant Adapter and Baseplate-Mounted TA


Installation
The redundant adapter provides a redundant I/O connection to a single termination assembly
(TA). Contained in the adapter are the input sense resistors and output diodes required for operation of a redundant FBM216/216b/218/245 pair with its associated TA.
As well, the baseplate-mounted termination assembly (TA) provides an I/O connection to two
non-redundant FBMs, such as the HART-capable FBM247 (as well as other non-HART FBMs,
such as the FBM202 and FBM203, as discussed in DIN Rail Mounted Subsystem Users Guide
(B0400FA)), provided that these FBMs are installed in adjacent slots as described below.
Using a baseplate-mounted TA eliminates the need to have a separate marshalling cabinet for the
FBMs I/O, or for the spacing requirements needed to mount a separate, standard termination
assembly. A baseplate-mounted TA mounts directly onto the field I/O connectors of the standard
200 Series baseplate, in a similar manner as the redundant adapter. (This TA is not supported on
the Compact 200 Series 16-slot horizontal baseplate.)

16

4. Equipment Installation

B0400FF Rev M

The redundant adapter and the baseplate-mounted TA are position dependent, supporting field
I/O wiring for two FBMs in paired baseplate slots (for example, in positions 1 and 2, 3 and 4, 5
and 6, or 7 and 8), since their connectors must engage the corresponding pairs of connectors on
the baseplate, adjacent to their associated FBM pair.
NOTE

On the horizontal baseplate, paired FBMs (and thus the redundant adapter) are
placed in adjacent odd/even paired positions on the baseplate (see Figure 4-2). On
the vertical baseplate, paired FBMs may be placed in any adjacent odd/even paired
positions.
For a redundant pair of HART FBMs, attach their redundant adapter onto the two I/O connectors which correspond to the FBM pairs slot position on the baseplate. Figure 4-3 shows installation of a redundant adapter for the FBM216. The redundant adapters for the FBM216b,
FBM218 and FBM245 are similar in construction.

Operational Status

Operational Status

IR Active

01

IR Active

01

Master

02

Master

02

Tracker

03

Tracker

OFF

03

04

04

05

05

06

06

07

07

08

08

FBM216

FBM216

8 Communication,
Redundant HART Input
P0917TN

8 Communication,
Redundant HART Input
P0917TN

Baseplate I. D.
2
ON
ON
OFF
OFF

01 02 03 04
Input (P)
Input (P)
08 07 06 05

FBM216
Redundant Adapter

1
ON
OFF
ON
OFF

No.
0
1
2
3

Redundant
Adapter

Input (-)

P0917XQ

01
05

04
08

Figure 4-3. Redundant Adapter or Baseplate-Mounted TA Installation (Typical)

NOTE

For the redundant adapters used on the Compact 200 Series 16-slot horizontal baseplate, refer to Redundant Adapter Installation for Compact 200 Series Baseplates
in DIN Rail Mounted Subsystem Users Guide (B0400FA).

HART Device Connections


HART device connections to the TAs are made in accordance with the labels on the TAs (see
Figure 4-4 and Figure 4-13). Each HART FBM has eight separate communication channels as
17

B0400FF Rev M

4. Equipment Installation

shown on the TA labels. Type A, shielded twisted-pair cables (for making the device connections
to the TAs) are available from Foxboro and have the following part numbers:
P0170GG (flame retardant)
P0170GF (non-flame retardant).

Connections to FBM214/214b/216/216b/244
Make the cable connections to the FBM214/214b/216/216b/244 TA as shown in Figure 4-4. For
reference purposes, schematic representations of the input signal flows for the
FBM214/214b/216/216b are shown in Figure 4-5 and Figure 4-6, respectively. Cable Balun
Module connections for 2-wire devices are shown in Figure 4-7 through Figure 4-10. Cable Balun
Module connections for 4-wire devices are shown in Figure 4-11. Also, a simplified schematic of
the FBM214/214b/216/216b input circuitry is shown in Figure 4-12 on page 28. Entity parameters for the FBM214/214b/216/216b are listed in Table 4-2.

FBM214/214b/216/216b Termination Assembly Connections


FBM214/216, HART Input
01 02 03 04 05 06 07 08

8
C
O
M
M
U
N
I
C
A
T
I
O
N

TA Label

iP iP iP iP iP iP iP iP
i+ i+ i+ i+ i+ i+ i+ i+
i- i- i- i- i- i- i- i-

Signal
Connection
Points:
C = iP
B = i+
A = iTo
HART
Field
Devices

C
B
A

See Note

Note: Cable connections are shown for Channel 1. Other channels are connected in a similar manner.
Figure 4-4. FBM214/216 or FBM214b/216b TA Field Device Connections

18

4. Equipment Installation

B0400FF Rev M

FBM214/214b/216/216b Input Signal Flow Diagrams


Safety (This Side):
Class I, II, III; Div. 2;
Groups A-D,
F and G;
Zone 2, IIC
Hazardous
Locations

Safety (This Side):


Class I; Div. 2; Groups A-D;
Zone 2, IIC; Hazardous Locations

Internally (FBM) Powered Transmitter

iP+ Cx*

Baseplate
(to FBM214
or FBM214b)

i+ Bx*
Transmitter

Ax*
Termination Assembly
(P0916BX, P0926EA, P0924JH)
Field Connections

Termination
Cable Type 1
(25 pin to 37 pin)

Internally (FBM) Powered Transmitter with Intrinsic Safety Barrier

Transmitter

Intrinsic
Safety
Barrier

iP+ Cx*
Baseplate
(to FBM214
or FBM214b)

i+ Bx*
Ax*

Termination Assembly
(P0916BX, P0926EA, P0924JH)
Field Connections

Termination
Cable Type 1
(25 pin to 37 pin)

(Figure continued on next page.)


Figure 4-5. FBM214/214b Input Signal Flow (1 of 2)

19

B0400FF Rev M

Safety (This Side):


Class I, II, III; Div. 2;
Groups A-D,
F and G;
Zone 2, IIC
Hazardous
Locations

4. Equipment Installation

Safety (This Side):


Class I; Div. 2; Groups A-D;
Zone 2, IIC; Hazardous Locations

Externally Powered Transmitter with Intrinsic Safety Barrier and Balun


Termination Assembly
(P0916BX, P0926EA,
Cx*
P0924JH)
Field Connections
i+ Bx*

See Note 8

+
Transmitter

Intrinsic Safety +
Barrier

Field

Cable

System

1
1
2 Balun 2
3 Module 3
4
4
5
5
6 CBM-4 6
7
7
8 P0903SV 8

Baseplate
(to
FBM214 or
FBM214b)

i- Ax*

Refer to Note 2
External Power
Supply

Termination
Cable Type 1

Cable Balun Module


* x indicates FBM channel number.
NOTES:
1. Field circuitry must have entity parameters compatible with those of FBM214 (TA Part No. P0916BX
and P0926EA) and FBM214b (TA Part No. P0924JH) as listed in the table Entity Parameters for
HART Communication Interface Modules for hazardous location applications.
2. Each input requires separate connections to the power supply.
3. For detailed information on balun use and installation, refer to Using the Cable Balun Module with
Intelligent Transmitters in System Equipment Installation (B0193AC).
4. Cable balun used only when multiple loops are connected to a common power supply. The FBM
negative terminals connect directly to the minus (-) terminal of the power supply. The balun system
side negative (-) terminals (2, 4, 6, and 8) connect to the power supply positive terminals when there
are 4 (maximum) power loops.
5. For hazardous environments, install an intrinsic safety barrier such as an MTL 787S+ between the
balun wiring to limit the amount of energy in the wiring.
6. A user-supplied capacitor can be installed across the external power supply(ies) to shunt ac power.
7. The external power supply can be redundant power supplies in parallel.
8. For field cabling, use twisted-pair wiring inside a shielded cable with the shield grounded at the
Foxboro Evo system end.
Figure 4-5. FBM214/214b Input Signal Flow (2 of 2)

20

4. Equipment Installation

Safety (This side)


Class I, II, III;
Div. 2;
Groups A-D,
F and G;
Zone 2, IIC
Hazardous
Locations

B0400FF Rev M

Safety (This Side)


Class I; Div. 2; Groups A-D;
Zone 2, IIC; Hazardous Locations
To
FBM216/216b
(primary
module)

Internally (FBM) Powered Transmitter


Test

iP
iP+ Cx*

i+
280

i+ Bx*
Transmitter

Test

Ax*

iiP
i+

Test

Termination Assembly
(P0916BX, P0926EA,
P0924JH)
Field Connections

Termination
Cable Type 1

i-

To
FBM216/216b
(redundant
FBM216 or
module)
FBM216b
Redundant Adapter

Internally (FBM) Powered Transmitter with Intrinsic Safety Barrier


Test

+
Transmitter

iP+ Cx*
Intrinsic
Safety
Barrier

iP
i+

280

i+ Bx*

Test

Ax*

iiP
i+

Test

Termination Assembly
(P0916BX, P0926EA,
P0924JH)
Field Connections

To
FBM216/216b
(primary
module)

i-

Termination
Cable Type 1
FBM216 or
FBM216b
Redundant Adapter

To
FBM216/216b
(redundant
module)

(Figure continued on next page.)


Figure 4-6. FBM216/216b Input Signal Flow (1 of 2)

21

B0400FF Rev M

Safety (This Side)


Class I, II, III; Div.2
Groups A-D,
F and G;
Zone 2, IIC
Hazardous
Locations

4. Equipment Installation

Safety (This Side)


Class I; Div. 2; Groups A-D;
Zone 2, IIC; Hazardous Locations
To
FBM216/
FBM216b
(primary
module)
Externally Powered Transmitter with Intrinsic Safety Barrier
Test

Termination Assembly
(P0916BX, P0926EA,
Cx*
P0924JH)
Field Connections
i+ Bx*

i+
280
Test

+
Transmitter

Intrinsic Safety +
Barrier

Field

System

1 Cable 1
2
2
3 Balun 3
4 Module 4
5
5
6
6
7 CBM-4 7
8
8

P0903SV

Cable Balun Module

iP

i- Ax*

iiP
i+

Test

i-

Refer to Note 2

External Power
Supply

To
FBM216/
FBM216b
(redundant
module)
FBM216 or
FBM216b
Redundant Adapter

Termination
Cable Type 1

NOTES:
1. Field circuitry must have entity parameters compatible with those of FBM216 (TA Part No. P0916BX
and P0926EA) or FBM216b (TA Part No. P0924JH) as listed in the table Entity Parameters for
HART Communication Interface Modules for hazardous location applications.
2. Each input requires separate connections to the power supply.
* x indicates FBM channel number.
Figure 4-6. FBM216/216b Input Signal Flow (2 of 2)

22

4. Equipment Installation

B0400FF Rev M

iiP

i+

i-

i+

iP

TA Terminal Block

FBM214/214b/216/216b, Cable Balun Module, 2-Wire Devices,


Wiring Diagrams

Figure 4-7. Cable Balun Module, Externally Powered


HART Input Channels, Wiring Diagram

23

iiP

i+

i-

i+

iP

i-

i+

4. Equipment Installation

(iP+)

TA Terminal Block

iP

B0400FF Rev M

Figure 4-8. Cable Balun Module, Internal and Externally Powered


HART Input Channels, Wiring Diagram

24

iiP

i+

i-

i+

iP

i-

B0400FF Rev M

(iP+)

i+

TA Terminal Block

4. Equipment Installation

Figure 4-9. Cable Balun Module with Intrinsic Safety or Zener Barriers,
Internal and Externally Powered HART Input Channels, Wiring Diagram

25

4. Equipment Installation

iiP

i+

i-

i+

iP

i-

i+

TA Terminal Block

iP

B0400FF Rev M

Figure 4-10. Cable Balun Module with Transformer Isolated Barrier,


Internal and Externally Powered HART Input Channels, Wiring Diagram

26

4. Equipment Installation

B0400FF Rev M

TA Terminal Block

FBM214/214b/216/216b, Cable Balun Module, 4-Wire Devices,


Wiring Diagram

Figure 4-11. Cable Balun Module with Transformer Isolated Barrier,


Internal and Externally Powered 4-wire Devices, Wiring Diagram

27

B0400FF Rev M

4. Equipment Installation

FBM214/214b/216/216b Simplified Schematic

LP_PWR

+24 V dc

Current Limiter

Transmit Enable

26 V
Transmit Driver
5.5 V
51

4.7 F

+7.5 V

CHPOS

Transmit Signal

Receive Filter
5.1 K
+5 V

680 pF

Receive Signal

220

SIGPOS
7.5 K
61.9

A to D Converter

5.5 V

CHNEG

SIGNEG
7.5 K

2.5 V Ref.

+5 V dc

Figure 4-12. FBM214/214b/216/216b Field Device Input Interface, Simplified Schematic

NOTE

Component values may differ slightly between the various FBMs.

28

4. Equipment Installation

B0400FF Rev M

Connections to FBM215/218
Make the cable connections to the FBM215/218 TA as shown in Figure 4-13. For reference purposes, schematic representations of the output signal flows for the FBM215/218 are shown in
Figure 4-14 and Figure 4-15, respectively. Also, a simplified schematic of the FBM215/218 output circuitry is shown in Figure 4-16. Entity parameters for the FBM215/218 are listed in
Table 4-2.

FBM215/218 Termination Assembly Connections


FBM215/218, HART Output
01 02 03 04 05 06 07 08

8
C
O
M
M
U
N
I
C
A
T
I
O
N

TA Label

Signal
Connection
Points:
B = o+
A = oTo
HART
Field
Device

o+ o+ o+ o+ o+ o+ o+ o+
o- o- o- o- o- o- o- o-

See Note

Note: Cable connections are shown for Channel 1. Other channels are connected in a similar manner.
Figure 4-13. FBM215/218 TA Cable Connections

29

B0400FF Rev M

4. Equipment Installation

Safety (This Side):


Class I, II, III; Div. 2;
Groups A-D, F and G;
Zone 2, IIC
Hazardous Locations

Safety (This Side):


Class I; Div. 2; Groups A-D;
Zone 2, IIC; Hazardous Locations

Actuator
+

o+

Baseplate
(to FBM215)

Bx*

o- Ax*

Termination Assembly
(P0917XV, P0926EK)
Field Connections

Termination
Cable Type 1
(25 pin to 37 pin)
NOTES:
1. Field circuitry must have entity parameters compatible with those of FBM215 (TA Part No. P0917XV,
and P0926EK) as listed in the table Entity Parameters for HART Communication Interface
Modules for hazardous location applications.
* x indicates FBM channel number.
Figure 4-14. FBM215 Output Signal Flow

Safety (This Side):


Class I, II, III; Div. 2;
Groups A-D, F and G;
Zone 2, IIC
Hazardous Locations

Safety (This Side):


Class I; Div. 2; Groups A-D;
Zone 2, IIC; Hazardous Locations

Redundant Adapter (P0916QD)


(mounted on baseplate)
o+

+
-

Actuator

o-

Bx*

o+
o-

Ax*

Termination Assembly
(P0917XV, P0926EK)
Field Connections

FBM218
(primary
module)

Termination
Cable Type 1
(25 pin to 37 pin)
o+
o-

FBM218
(redundant
module)

NOTES:
1. Field circuitry must have entity parameters compatible with those of FBM218 (TA Part No. P0917XV,
and P0926EK) as listed in the table Entity Parameters for HART Communication Interface
Modules for hazardous location applications.
* x indicates FBM channel number.
Figure 4-15. FBM218 Output Signal Flow

30

4. Equipment Installation

B0400FF Rev M

Isolated
Loop
Power
Supply

OUTPOS

24 v p-p 200 KHz


Squarewave

33 V
OUTNEG

Current
Driver
D/A
Converter

Opto-Isolators

TO ASIC
Logic

Transmit Driver
123

1 mF

1.96 K

Transmit Signal

5 K
Receive Filter
Receive Signal
33 V

680 pF

Figure 4-16. FBM215/218 Field Device Output Interface, Simplified Schematic

31

B0400FF Rev M

4. Equipment Installation

Connections to FBM244/245
Make the cable connections to the FBM244/245 TAs as shown in Figure 4-17. For reference purposes, schematic representations of the output signal flows for the FBM244/245 are shown in
Figure 4-18 and Figure 4-19, respectively.
NOTE

The FBM245 has four HART-compatible inputs and four HART-compatible outputs. The test points provide a measurement check of the FBM derived loop supply
voltage for input channels 1-4. These test points do not reflect the loop supply
voltage when loops are externally powered.
TA P0924QZ has four output bypass jacks for use with the Output Bypass Station, and is not
suitable for use in any hazardous locations - ordinary locations only. For more information on the
Output Bypass Station, refer to FBM Replacement using the Output Bypass Station in DIN
Rail Mounted Subsystem Users Guide (B0400FA).
Also, simplified schematics of the FBM244/245 output circuitry are shown in Figure 4-20. Entity
parameters for the FBM244/245 are listed in Table 4-2.

FBM244/245 Termination Assembly Connections


P0924QU

P0924QZ

FBM244/245, HART I/O

FBM244/245, HART I/O Bypass

01 02 03 04 05 06 07 08

Customer
Labeling
Area

Signal
Connection
Points C = iP
B = i+
A = i-

01 02 03 04 05 06 07 08

Customer
Labeling
Area

iP iP iP iP sh sh sh sh
i+ i+ i+ i+ o+ o+ o+ o+
i- i- i- i- o- o- o- o-

Signal
Connection
Points C = iP
B = i+
A = i-

Bypass jacks under cover


iP iP iP iP sh sh sh sh
i+ i+ i+ i+ o+ o+ o+ o+
i- i- i- i- o- o- o- o-

Figure 4-17. FBM244/245 TA Field Device Connections

32

4. Equipment Installation

Safety (This Side):


Class I, II, III; Div. 2;
Groups A-D, F and G;
Zone 2, IIC
Hazardous Locations

B0400FF Rev M

Safety (This Side):


Class I; Div. 2; Groups A-D;
Zone 2, IIC; Hazardous Locations

5 Cx*
Actuator
+

o+

o- Ax*
Termination Assembly
(P0924QU)
Field Connections

Safety (This Side):


Class I, II, III; Div. 2;
Groups A-D, F and G;
Zone 2, IIC
Hazardous Locations

Baseplate
(to FBM244)

Bx*

Termination
Cable Type 1
(25 pin to 37 pin)

Safety (This Side):


Ordinary Locations

5 Cx*
Actuator
+

o+

o- Ax*

Baseplate
(to FBM244)

Bx*

Termination Assembly
(P0924QZ)
Field Connections

Termination
Cable Type 1
(25 pin to 37 pin)

NOTES:
1. Field circuitry must have entity parameters compatible with those of FBM244 (TA Part No. P0924QU)
as listed in the table Entity Parameters for HART Communication Interface Modules for hazardous
location applications.
2. TA P0924QZ has 4 output bypass jacks for 0-20 mA supplied by Output Bypass Station.
3. Each input requires separate connections to Power Supply.
* x indicates FBM channel number.
Figure 4-18. FBM244 Output Connections

33

B0400FF Rev M

Safety (This Side):


Class I, II, III; Div. 2;
Groups A-D, F and G;
Zone 2, IIC
Hazardous Locations

4. Equipment Installation

Safety (This Side):


Class I; Div. 2; Groups A-D;
Zone 2, IIC; Hazardous Locations
Redundant Adapter
(P0924DU) (mounted
on baseplate)

5 Cx*
Actuator
+

o+

o- Ax*

Bx*

o+
o-

Termination Assembly
(P0924QU)
Field Connections

Termination
Cable Type 1
(25 pin to 37 pin)
o+
o-

Safety (This Side):


Class I, II, III; Div. 2;
Groups A-D, F and G;
Zone 2, IIC
Hazardous Locations

FBM245
(primary
module)

FBM245
(redundant
module)

Safety (This Side):


Ordinary Locations

Redundant Adapter
(P0924DU) (mounted
on baseplate)

5 Cx*
Actuator
+

o+

o- Ax*

Bx*

Termination Assembly
(P0924QZ)
Field Connections

o+
o-

FBM245
(primary
module)

Termination
Cable Type 1
(25 pin to 37 pin)
o+
o-

FBM245
(redundant
module)

NOTES:
1. Field circuitry must have entity parameters compatible with those of FBM245 (TA Part No. P0924QU)
as listed in the table Entity Parameters for HART Communication Interface Modules for hazardous
location applications.
2. TA P0924QZ has 4 output bypass jacks for 0-20 mA supplied by Output Bypass Station.
3. Redundant Adapter (P0924DU) must be used with the FBM245.
4. Each input requires separate connections to Power Supply.
* x indicates FBM channel number.
Figure 4-19. FBM245 Output Connections with Redundant Adapter Connections

34

4. Equipment Installation

B0400FF Rev M

Isolated
Loop
Power
Supply

OUTPOS

24 v p-p 200 KHz


Squarewave

33 V
OUTNEG

Current
Driver
D/A
Converter

Opto-Isolators

TO ASIC
Logic

Transmit Driver
123

1 mF

1.96 K

Transmit Signal

5 K
Receive Filter
Receive Signal
33 V

680 pF

Figure 4-20. FBM244/245 Module, Channel Isolated Output Circuit, Simplified Schematic

35

B0400FF Rev M

4. Equipment Installation

Connections to FBM247
The FBM247 contains eight individual channels which can be individually configured for a range
of analog, digital and pulse field I/O signals, including the following:
HART Analog Input (AI)/Analog Output (AO) 4-20 mA
0-20 mA AI/AO, non-HART
0-10 V and 0-5V AI, non-HART

Digital dry contact sense 24 V dc


Discrete voltage monitor, configurable 0 and 1 thresholds 0-10 V
NAMUR sensor discrete input
Signal level according to DIN EN 50227 (NAMUR):
On at 2.1 mA dc with short circuit detection at > 6 mA
Off at 1.2 mA dc with open detection at <0.25 mA
Pulse count, frequency, acceleration and jerk, contact sense or voltage input

Discrete Output 24 V, 20 mA current or solid state switch output


Each I/O channel performs the signal conversion required to interface the electrical input/output
signals from the field sensors and actuators to the redundant Fieldbus, and is galvanically isolated
from other channels and ground.
Two types of passive termination assemblies are available for the FBM247:
DIN rail mounted TA, similar to those used with the other 200 Series FBMs
Baseplate-mounted TA, which mounts directly onto the field I/O connectors of the
200 Series baseplate, in a similar manner as the redundant adapter (see Redundant
Adapter Installation in DIN Rail Mounted Subsystem Users Guide (B0400FA)). This
TA provides field I/O wiring support for two FBM247s in paired baseplate slots (that
is, in positions 1 and 2, 3 and 4, 5 and 6, or 7 and 8).
Make the cable connections to the FBM247 TAs as shown in Figure 4-21. For reference purposes,
schematic representations of the I/O signal flows for the FBM247 are shown in Figure 4-22
through Figure 4-31.
A shield terminal connection (SH) is provided for each I/O point. The shield terminals are connected to the earth at the system power supply.
FBM247 supports cable balun modules as well. A schematic representation of a cable balun used
with FBM247 is provided in Figure 4-32 on page 46.
Entity parameters for the FBM247 are listed in Table 4-2 on page 47.
When configuring the ECB200 and other blocks for the FBM247, refer to Configuring Blocks
for FBM247 on page 66 for details on setting the exact signals used in each channel of the
FBM247.

Pulse or Digital SOE Contact Sense Input Configuration


When a FBM247 channel is configured for pulse I/O or digital Sequence of Events (SOE) signals,
the input circuit detects the digital state of the field device by sensing the current flowing in the
field wiring. The thresholds are fixed at 1.2 mA for a guaranteed logic value of 0 and 2.1 mA for
a guaranteed logic value or 1. When the input is configured to be internally powered, a +27 Volt
loop supply with a source impedance of 220 Ohms is provided. When the configuration is set for
36

4. Equipment Installation

B0400FF Rev M

external loop power, the channel input impedance is approximately 170 Ohms. These configurations allow for the connection of various two-wire sensors such as switches, relay contacts, or
active proximity devices. The input current switching thresholds are chosen to be compatible with
the recommendations of the NAMUR standard. For non-intrinsically safe applications, this
allows the convenience of direct connecting two-wire NAMUR sensors as input devices.
NAMUR fault detection is not implemented for these configurations.
NOTE

For some NAMUR sensors, additional external loop resistance may be required for
proper operation. Follow the details contained within the manufacturer's sensor
device data sheet.

Digital NAMUR Sensor Input (Non-Intrinsically Safe) Configuration


The FBM247 provides a NAMUR configuration which allows the convenience of direct connecting two-wire NAMUR type digital input sensors as input devices when they are used for nonintrinsically safe applications. The switching thresholds and fault levels are chosen to be compatible with the recommendations of the NAMUR standard. When a FBM247 channel is configured
for NAMUR, the input circuit detects the digital state of field device by sensing the current flowing in the field wiring. The thresholds are fixed at 1.2 mA for a guaranteed logic 0 and 2.1 mA
for a guaranteed logic 1. In addition, both NAMUR open (<0.25mA) and short (>6mA) circuit
fault detection is supported. When the input is configured to be internally powered, a +27 Volt
loop supply with a source impedance of 220 Ohms is provided. When the configuration is set for
external loop power, the input impedance is approximately 170 Ohms.
NOTE

For some NAMUR sensors, additional external loop resistance may be required for
proper operation. Follow the details contained within the manufacturer's sensor
device data sheet.
In addition to NAMUR type sensors, the NAMUR configuration supports an array of other types
of contact inputs. To ensure that the open circuit detection functions properly when using nonNAMUR contact type inputs, the addition of a resistor across the contacts is required to provide
the proper non-alarm current level (i.e. 0.5 to 1.0 mA) for the open contact condition.
NOTE

In order to implement an intrinsically safe NAMUR sensor input, an external


barrier must be used.

37

B0400FF Rev M

4. Equipment Installation

FBM247 Termination Assembly Connections


P0924WW

FBM247, Configurable I/O HART

Customer
Labeling
Area

Signal
Connection
Points C = +
B=A = SH
P0924WG
Baseplate-Mounted

(AI/AO)+HART, DI/DO, Pulse

01 02 03 04 05 06 07 08

+ + + + + + + +
- - - - - - - Sh Sh Sh Sh Sh Sh Sh Sh

Signal
Connection
Points C = +
B=A = SH

01 02 03 04 05 06 07 08
FBM POS 1, 3, 5, 7
+ + + + + + + +
- - - - - - - Sh Sh Sh Sh Sh Sh Sh Sh

01 02 03 04 05 06 07 08
FBM POS 2, 4, 6, 8
+ + + + + + + +
- - - - - - - Sh Sh Sh Sh Sh Sh Sh Sh

Field I/O For FBM in


Odd-Numbered Slot

Field I/O For FBM in


Even-Numbered Slot

(AI/AO)+HART, DI/DO, Pulse

FBM247, Configurable I/O, HART

Customer Labeling Area

Figure 4-21. FBM247 TA Field Device Connections

38

4. Equipment Installation

Transmitter
+

B0400FF Rev M

25 V dc
Isolated
Loop Power
Supply

Loop Power

43 V

24 V PP, 200 KHz


Square Wave

Current In
Current
Driver

I Limit
Set to
35 mA

I Limit
from ASIC
Logic

50 Ohms 1 F

HART
Transmit
Driver

+
A/D

120 Ohms

Control
SDI
SCLK

5 KOhms
680
Pf

ISOLATORS

SH

SDO

HART
Receive
Filter

HART
Transmit
Signal
ADC Controls
Serial Data
To ADC
Serial Clock
To ADC
Serial Data
From ADC

HART
Receive
Signal

* Shield connection provided if required.


Figure 4-22. FBM247 Loop-Powered Current Input Connections

39

B0400FF Rev M

4. Equipment Installation

Current In
43 V

Current
Driver

Transmitter
P.S. See Note
- Return

I Limit
Set to
35 mA

SH

I Limit
from ASIC
Logic

50 Ohms 1 F

HART
Transmit
Driver
Control
SDI
SCLK

+
A/D

120 Ohms
-

5 KOhms
680
Pf

ISOLATORS

SDO

HART
Receive
Filter

HART
Transmit
Signal
ADC Controls
Serial Data
To ADC
Serial Clock
To ADC
Serial Data
From ADC

HART
Receive
Signal

NOTE: Power supply may be internal to the transmitter.


* Shield connection provided if required.
Figure 4-23. FBM247 Self-Powered or Externally Powered Current Input Connections

Control

0-5 or
0-10
V dc
Input

43 V

10 MOhms

SDI
A/D

SCLK
SDO

ADC Controls

ISOLATORS

x1

Serial Data
To ADC
Serial Clock
To ADC
Serial Data
From ADC

Offset
SH

* Shield connection provided if required.


Figure 4-24. FBM247 Analog Voltage Input or Discrete Voltage Monitor Connections

40

4. Equipment Installation

Actuator
+

25 V dc
Isolated
Loop Power
Supply

Loop Power

43 V

SH

B0400FF Rev M

24 V PP, 200 KHz


Square Wave

Current In

Current
Driver
D/A
I = 0 to
20.4 mA See Note
HART
Transmit
Driver
Control
SDI
SCLK

+
120 Ohms

A/D
-

5 KOhms

NOTE: 4-20 mA for HART.

680
Pf

ISOLATORS

1550 Ohms** 1 F

I Limit
from ASIC
Logic

SDO

HART
Receive
Filter

HART
Transmit
Signal
ADC Controls
Serial Data
To ADC
Serial Clock
To ADC
Serial Data
From ADC

HART
Receive
Signal

* Shield connection provided if required.


** This resistor must be 1550 Ohms when an actuator is connected.
Figure 4-25. FBM247 Loop-Powered Current Output Connections

41

B0400FF Rev M

4. Equipment Installation

43 V
+

Current In
Current
Driver
D/A
I = 0 to
20.4 mA See Note 2

Return
+
P.S.

1550 Ohms** 1 F

HART
Transmit
Driver

See
Note 1
SH

Control
SDI
SCLK

+
A/D

120 Ohms
-

5 KOhms
680
Pf

SDO

HART
Receive
Filter

I Limit
from ASIC
Logic

ISOLATORS

Actuator
-

HART
Transmit
Signal
ADC Controls
Serial Data
To ADC
Serial Clock
To ADC
Serial Data
From ADC

HART
Receive
Signal

NOTES:
1. Power supply may be internal to the actuator/positioner.
2. 4-20 mA for HART.
* Shield connection provided if required.
** This resistor must be 1550 Ohms when an actuator is connected.
Figure 4-26. FBM247 Self-Powered or Externally Powered Current Output Connections

42

4. Equipment Installation

B0400FF Rev M

25 V dc
Isolated
Loop Power
Supply

Loop Power

+
+

43 V

24 V PP, 200 KHz


Square Wave

Return

External Contact

Current
Driver

I Limit
Set to
10 mA

I Limit
from ASIC
Logic

+
A/D

120 Ohms
* Shield connection provided
if required.

Control
SDI
SCLK

ISOLATORS

SH

SDO

ADC Controls
Serial Data
To ADC
Serial Clock
To ADC
Serial Data
From ADC

Figure 4-27. FBM247 Digital Dry Contact Sense Connections

+
Load

43 V
+

Current
Driver

Output
ON/OFF
from ASIC
Logic

I Limit
20.4 mA

Return
+
P.S.
See
Note
SH

*
+
A/D

120 Ohms
-

Control
SDI
SCLK
SDO

ISOLATORS

ADC Controls
Serial Data
To ADC
Serial Clock
To ADC
Serial Data
From ADC

NOTE: Power supply may be internal to the load.


* Shield connection provided if required.
Figure 4-28. FBM247 Solid State Switch Connections

43

B0400FF Rev M

4. Equipment Installation

25 V dc
Isolated
Loop Power
Supply

Loop Power

+
+
Load

43 V

24 V PP, 200 KHz


Square Wave

Return

Current
Driver
*

Output
ON/OFF
from ASIC
Logic

I Limit
set to
20.4 mA

+
120 Ohms
* Shield connection provided
if required.

A/D

ISOLATORS

SH

Control
SDI
SCLK

SDO

ADC Controls
Serial Data
To ADC
Serial Clock
To ADC
Serial Data
From ADC

Figure 4-29. FBM247 24 V dc Discrete Output Connections

Voltage
Pulse
In
SH

43 V
-

V
Threshold

Data Out

ISOLATORS

Data Out

* Shield connection provided if required.


Figure 4-30. FBM247 Voltage Pulse In - Pulse Count Frequency, etc. Connections

44

4. Equipment Installation

B0400FF Rev M

+
+

43 V

Current
Pulse In
I Limit
10 mA

SH

Source
120 Ohms
* Shield connection provided
if required.

I Threshold
(NAMUR
Units)

Data Out

ISOLATORS

I Set
ON/OFF
from AIS
Logic

Data Out

Figure 4-31. FBM247 Current Pulse In -Pulse Count Frequency, etc. Connections

45

B0400FF Rev M

4. Equipment Installation

* Refer to B0400FA for detailed installation instructions for the P0903SU Cable Balun

i-

i+

SH

i-

i+

SH

TA Terminal Block

FBM247, Cable Balun Module, Wiring Diagram Example

Figure 4-32. FBM247 with Cable Balun, Externally Powered HART Input Channels,
Wiring Diagram Example

46

4. Equipment Installation

B0400FF Rev M

HART Communication Interface Modules Entity Parameters


Table 4-2. Entity Parameters for HART Communication Interface Modules

Entity Parameters3
FBM
Type

TA Type
(P/N)1

FBM214

P0916BX,
P0926EA

FBM214

*, P0926TD

FBM2164

P0916BX,
P0926EA

FBM2164

*, P0926TD

FBM214b/
FBM216b4

P0924JH

FBM215

P0917XV,
P0926EK
*, P0926SP
P0917XV,
P0926EK
*, P0926SP
P0924QU,
P0924QZ

FBM215
FBM2184
FBM2184
FBM244

FBM2454

P0924QU,
P0924QZ

FBM247

P0924WW,
P0924WG

TA Field
Terminal

Field Circuit
Type2

(S) Um
(R) Ui

(S) Io
(R) Ii

(S) Co
(R) Ci

(S) Lo
(R) Li

i+ to iP
i+ to ii+ to iP
i+ to ii+ to iP
i+ to ii+ to iP
i+ to ii+ to iP
i+ to io+ to o-

Input (S)
Input (R)
Input (S)
Input (R)
Input (S)
Input (R)
Input (S)
Input (R)
Input (S)
Input (R)
Output (S)

25
60
25
60
25
60
25
60
25
60
33

33
34
33
34
64
34
33
34
64
34
21

3nF
0
3nF
0
3nF
0
3nF
0
3nF
0
3nF

0
0
0
0
0
0
0
0
0
0
0

o+ to oo+ to o-

Output (S)
Output (S)

33
33

21
21

3nF
3nF

0
0

o+ to oiP to i+
iP to ii+ to io+ to oiP to i+
iP to ii+ to io+ to oi+ to i-

Output (S)
Input (S)
Input (S)
Input (R)
Output (S)
Input (S)
Input (S)
Input (R)
Output (S)
Input/
Output (S)6
Input/
Output (R)

33
25
25
6
32
25
25
6
32
27

21
35
35
215
21
70
70
215
21
30

3nF
0.4
0.4
0
0.18
0.4
0.4
0
0.18
0.309

0
65
65
0
180
16
16
0
180
88.9

30

30

i+ to i1.
2.
3.
4.

The TA part numbers are listed as follows: compression type, ring lug type. * indicates that there
is no compression-type equivalent for this TA.
(S) = the FBM terminals supply energy; (R) = the FBM terminals receive energy. This defines
whether to use Um or Ui, Io or Ii, Co or Ci, and Lo or Li in the entity parameter columns.
Units are expressed as follows: Um and Ui in dc Volts; Io and Ii in dc mA; Co and Ci in F; Lo
and Li in mH.
Requires redundant adapter mounted on baseplate to support redundancy.
47

B0400FF Rev M
5.
6.

48

4. Equipment Installation

Ii for the case of i+ to i- is the current at 6V input.


Each FBM247 channel can be configured to be an input or output. The above parameters reflect
the configuration which has the greatest open circuit voltage and short circuit current. These are to
be used for the nonincendive installation calculations for all FBM247 power sourcing (S) I/O
configurations.

5. Control Block Configuration


Information
This chapter provides information necessary for configuring the control blocks associated with
the HART FBM and HART-capable FBM247 I/O functions. This information is intended for
use in conjunction with the quick-start example presented in Chapter 2 Quick-Start
Example.

ECBs and DCI Blocks Used with HART FBMs and


HART-Capable FBM247
With regard to the HART FBM I/O functions (reading/writing data to/from the HART devices)
and HART-capable FBM247 I/O functions (reading/writing data to/from the full range of I/O
signal supported by the FBM247, including HART devices), control block configuration involves
configuring the associated equipment control blocks (ECBs) and Distributed Control Interface
(DCI) control blocks. Table 5-1 lists the ECBs and DCI blocks used with the HART FBMs. For
detailed descriptions of the ECBs and DCI blocks used with the HART FBMs, refer to Integrated
Control Block Descriptions (B0193AX).
Table 5-1. ECBs and DCI Blocks Used with HART FBMs1

ECB/DCI Block
ECB110
ECB200
ECB202
ECB201
RIN
ROUT
IIN
STRIN
1.

Description
Fieldbus Communications Module (FCM) for DIN rail subsystem
Parent ECB, representing the FBM214, FBM214b, FBM215, FBM244
or FBM247
Parent ECB, representing a pair of redundant FBMs: two FBM216s, two
FBM216bs, two FBM218s or two FBM245s
Child ECB representing a field device, or I/O source for one FBM247
channel
Real Input DCI Block
Real Output DCI block
Integer Input DCI block
String Input DCI block

The FBM247 supports additional blocks not listed in this table (BIN, BOUT and PAKIN).
Refer to Configuring Blocks for FBM247 on page 66 for the full range of blocks supported
by the FBM247 for all the types of I/O signals this FBM supports.

This chapter provides key information regarding control block configuration. For specific information on the ECB/DCI control block parameter settings, refer to Integrated Control Block
Descriptions (B0193AX) and Integrated Control Block Descriptions for FOUNDATION fieldbus
Specific Control Blocks (B0700EC).
49

B0400FF Rev M

5. Control Block Configuration Information

Block Interconnections
In order for process control operations to be performed, you must create and configure ECBs,
DCI blocks, and other Foxboro Evo control blocks for control scheme implementation.
Figure 5-1 shows the ECB hierarchy.
Foxboro
Control Station

ECB110
(FCM)
ECB200
(FBM214/215)
or
ECB202*
(FBM216/218)

ECB201

ECB201

HART Devices
* Each ECB202 block represents a pair of redundant FBMs: FBM216s, FBM216bs,
FBM218s or FBM245s.
Figure 5-1. ECB Hierarchy

Configuration Procedures
As indicated in Figure 5-1, an ECB200 must be configured for each FBM214, FBM214b,
FBM215, FBM244, or FBM247 and an ECB202 must be configured for each FBM216,
FBM216b, FBM218 or FBM245 redundant pair. For each device associated with the FBMs (or
for the FBM247, each I/O signal associated with the FBM247), a child ECB201 must be configured and connected to the (parent) ECB200 or ECB202. In addition, a DCI block must be configured for each HART FBM or FBM247 parameter that is connectable. (Table 5-1 above lists the
DCI block types used in HART data transfer operations for the HART FBMs, and for other data
transfer operations supported by the FBM247.) The DCI blocks can be configured anywhere in
the Continuous List hierarchy (List 1 or 2), in any compound in a control station.
NOTE

In the following examples, the source of the I/O signal does not need to be a HART
device for the HART-capable FBM247.
Figure 5-2 shows the user-configured connections between the various elements of a typical control scheme using an FBM214/214b with HART input devices. In this figure, a RIN block is used
to process a real input from HART devices. (This real input could be derived from an alternative
source for the FBM247.)
Figure 5-3 on page 52 shows the user-configured connections between the various elements of a
typical control scheme using an FBM218 with HART output devices. In this figure, a ROUT

50

5. Control Block Configuration Information

B0400FF Rev M

block is used to process a real output value directed to HART devices. (This real output could be
derived from an alternative source for the FBM247.)
Figure 5-4 on page 53 shows the user-configured connections between the various elements of a
typical control scheme using an FBM214/214b with 4-20 mA input devices. In this figure, a RIN
block is used to process a real input from 4-20 mA devices. (This real input could be derived from
an alternative source for the FBM247.)
Configuration for other types of device I/O parameters and corresponding DCI blocks is similar,
with similar interconnections between the ECBs and DCI blocks. Table 5-2 on page 55 lists key
parameters, which either specify the linkages between ECBs and DCI blocks or contain information relating to the transfer of I/O values.
The ECB200, ECB201, ECB202, and DCI block parameters are defined in Integrated Control
Block Descriptions (B0193AX).
ECB200
NAME
DEV_ID

HART
Device
Channel#1

HART
Device
Channel#8

SLOT03
SLOT03

ECB201
NAME
PARENT
DVOPTS
DVNAME

PT_101
:SLOT03
HART
CH1
(See Note 3)

ECB201
NAME
PARENT
DVOPTS
DVNAME

PT_108
:SLOT03
HART
CH8
(See Note 3)

RIN Block
NAME
PT_101
IOMID
CP6SG5_ECB:PT_101
PNT_NO (See Note 2)

RIN Block
NAME
PT_108
IOMID
CP6SG5_ECB:PT_108
PNT_NO (See Note 2)

NOTES:
1. A DCI block (such as RIN) must be configured and connected to the devices ECB201 for
each HART signal/value that is to be interfaced to the Foxboro Evo system.
2. Certain DCI block parameters (PNT_NO, in this case) must be configured to contain a point
address which indicates, to the HART device, the I/O operation to be performed. Refer to Point
Addresses for HART and Analog I/O Signals on page 59 for details.
3. DVNAME contains the channel number CH1-CH8 of the associated device.
Figure 5-2. Typical Block Interconnections for FBM214/214b with HART Input Devices

51

B0400FF Rev M

5. Control Block Configuration Information

ECB202
NAME
DEV_ID

HART
Device
Channel#1

HART
Device
Channel#8

SLOT0C
SLOT0C

ECB201
NAME
PARENT
DVOPTS
DVNAME

VP_101
:SLOT0C
HART
CH1
(See Note 3)

ECB201
NAME
PARENT
DVOPTS
DVNAME

VP_108
:SLOT0C
HART
CH8
(See Note 3)

ROUT Block
NAME
VP_101
IOMID
CP6SG5_ECB:VP_101
PNT_NO (See Note 2)

ROUT Block
NAME
VP_108
IOMID
CP6SG5_ECB:VP_108
PNT_NO (See Note 2)

NOTES:
1. A DCI block (such as ROUT) must be configured and connected to the devices ECB201 for
each HART signal/value that is to be interfaced to the Foxboro Evo system.
2. Certain DCI block parameters (PNT_NO, in this case) must be configured to contain a point
address which indicates, to the HART device, the I/O operation to be performed. Refer to Point
Addresses for HART and Analog I/O Signals on page 59 for details.
3. DVNAME contains the channel number CH1-CH8 of the associated device.
Figure 5-3. Typical Block Interconnections for FBM218 with HART Output Devices

52

5. Control Block Configuration Information

B0400FF Rev M

ECB200
NAME
DEV_ID

Input
Device
Channel#1

Input
Device
Channel#8

SLOT04
SLOT04

ECB201
NAME
PARENT
DVOPTS
DVNAME

FT_101
:SLOT04
4-20
CH1
(See Note 2)

ECB201
NAME
PARENT
DVOPTS
DVNAME

FT_108
:SLOT04
4-20
CH8
(See Note 2)

RIN Block
NAME
FT_101
IOMID
CP6SG5_ECB:FT_101
PNT_NO CURRENT

RIN Block
NAME
FT_108
IOMID
CP6SG5_ECB:FT_108
PNT_NO CURRENT

NOTES:
1. A DCI block (such as RIN) must be configured and connected to the devices ECB201 for
each signal that is to be interfaced to the Foxboro Evo system.
2. DVNAME contains the channel number CH1-CH8 of the associated device.
Figure 5-4. Typical Block Interconnections for FBM214/214b with 4-20 mA Input Devices

53

B0400FF Rev M

5. Control Block Configuration Information

ECB200
NAME
DEV_ID
HART Input Device
Channel #1

Analog Input Device


Channel #2

Digital 24V Input


Channel #3

HART Output Device


Channel #8

FBM247_01
FBM001

ECB201
NAME
PT_0101
DEV_ID
DV0102
PARENT
:FBM247_01
DVOPTS
HART (4)
DVNAME
CH1 I LPWR (3)

NAME
DEV_ID
PARENT
DVOPTS
DVNAME

ECB201
FT_0102
DV0102
:FBM247_01
4-20 (4)
CH2 I EPWR (3)

ECB201
NAME
DI_0103
DEV_ID
DV0103
PARENT
:FBM247_01
DVOPTS
VOLT (4)
DVNAME
CH3 I (3)

ECB201
NAME
VP_0108
DEV_ID
DV0108
PARENT
:FBM247_01
DVOPTS
NOFAIL (4)
DVNAME
CH8 O LPWR (3)

RIN Block
NAME
IOM_ID
PNT_NO
SCI

PRESS_01
PT_0101
CURRENT (2)
3 or 0 (2)

RIN Block
NAME
IOM_ID
PNT_NO
SCI

FLOW_02
FT_0102
CURRENT (2)
1 or 3

BIN Block
NAME
IOM_ID
PNT_NO

DIN_03
DI_0103
DI 20 80 (2)

ROUT Block
NAME
IOM_ID
PNT_NO
SCO

VALVE_08
VP_0108
CURRENT (2)
3

NOTES:
1. A DCI block (such as RIN, BIN or ROUT) must be configured to the devices ECB201 for
each HART, current or voltage signal or value that is to be interfaced to the Foxboro Evo system.
2. DCI block parameters defined in PNT_NO must be configured to contain a point address
which indicates the I/O operation to be performed. Refer to Table 5-8 through Table 5-13 beginning on page 71 for details.
3. DVNAME contains the channel number (CH1-CH8), Input or Output (I or O) and External or
Loop Power (EPWR or LPWR) options. Refer to page 69 for details.
4. DVOPTS may be HART, NOFAIL or NOALARM for HART devices or 4-20 for ordinary current I/O or VOLT for voltage inputs. Refer to Table 5-7 on page 70 for details.
Figure 5-5. Typical Block Interconnections for FBM247 with Various I/O Devices

54

5. Control Block Configuration Information

B0400FF Rev M

Table 5-2 lists key parameters, which either specify the linkages between ECBs and DCI blocks or
contain information relating to the transfer of I/O values.
Table 5-2. Key Parameters
ECB or DCI Block

Parameter

Usage

Typical Syntax

ECB110

NAME

A user-configured name used for communications between the control station and DIN rail
baseplate(s).

:SLOT00

55

B0400FF Rev M

5. Control Block Configuration Information

Table 5-2. Key Parameters (Continued)


ECB or DCI Block

Parameter

Usage

Typical Syntax

ECB200/ECB202

NAME

A user-configured name used by the control


station to access this ECB. If a ZCP/FCM pair
control this FBM, the first 4 characters must
match first 4 characters of FCM name.
For the FBM247, if an FCP controls this FBM,
the first 4 characters must match first
4 characters of FCP name.

:SLOT03 for ECB200


:SLOT0C for ECB202
(See Note below)

DEV_ID

User-configured letterbug of the FBM. It is copied into the DEV_ID parameter of each DCI I/O
block connected to this ECB200/ECB202.

:SLOT03 for ECB200


:SLOT0C for ECB202
(See Note below)

FSDLAY

Must be greater than the BPC of the CP to give


the CP adequate time to respond to FBM. If
FSDLAY is shorter than the CPs BPC, the FBM
times out the CP and takes the configured failsafe actions.

1000 ms

DESCRP

User-defined string of up to 32 characters that


are used to describe the ECBs function (for
example, PLT 3 FURNACE 2 HEATER CONTROL).

1 to 32 chars

PERIOD

Indexed configuration parameter that dictates


the block's scanning frequency and allowable
PHASE values. Refer to Integrated Control
Block Descriptions (B0193AX) for allowable
values.
Be aware that the fastest allowed ECB period
for the HART FBMs and FBM247 is 100 milliseconds (PERIOD = 0). However, it is recommended that you refer to the Sizing Guidelines
and Excel Workbook appropriate for your Control Processor to determine the optimal BPC for
this ECB in order to prevent overloading.

PHASE

Configured integer input that causes the ECB


to be scanned at a specific BPC within the time
determined by the PERIOD. For instance, an
ECB with PERIOD of 3 (2.0 sec.) can be
scanned within the first, second, third, or fourth
BPC of the 2-second time period, assuming the
BPC of the control station is 0.5 sec.

HWTYPE

Hardware Type is configured based on the type


of connected FBM. See ECB200 Information
Pane/Faceplate on page 88 for the list of available values.

214

SWTYPE

Software Type is always identical to the hardware type (HWTYPE) in the


DCI family of ECBs.

214

SYSOPT

(ECB200 Only) For the FBM247, this must be


set as described in Configuring FBM ECB
(ECB200) for FBM247 on page 66.
For all other FBMs, refer to Integrated Control
Block Descriptions (B0193AX).

SYSCFG

(ECB200 Only) For the FBM247, this must be


set as described in Configuring FBM ECB
(ECB200) for FBM247 on page 66.
For all other FBMs, refer to Integrated Control
Block Descriptions (B0193AX).

1000ms

56

5. Control Block Configuration Information

B0400FF Rev M

Table 5-2. Key Parameters (Continued)


ECB or DCI Block

Parameter

Usage

Typical Syntax

ECB201

NAME

A user-configured name used by the control


station to access this ECB.

PT_100

PARENT

Contains the user-configured


pathname of the parent ECB
(ECB200/ECB202) hosting the
associated HART field device, or, for the
FBM247, the associated I/O signal source.

:SLOT03 for ECB200


:SLOT0C for ECB202
(See Note below)

DVOPTS1

Specifies the behavior of the FBM for the I/O


channel specified in DVNAME. See footnote
below for recommended settings.

HART

DVNAME

Specifies the channel number (CH1 to CH8) of


HART field device or, for the FBM247, the associated I/O signal source, associated with this
ECB201.
For the FBM247, this must be set as described
in Configuring Device ECB (ECB201) for
FBM247 on page 69.

CH1

DESCRP

User-defined string of up to 32 characters that


are used to describe the ECBs function (for
example, PLT 3 FURNACE 2 HEATER CONTROL).

1 to 32 chars

PERIOD

Indexed configuration parameter that dictates


the block's scanning frequency and allowable
PHASE values. Refer to Integrated Control
Block Descriptions (B0193AX) for allowable
values.
Be aware that the fastest allowed ECB period
for the HART FBMs and FBM247 is 100 milliseconds (PERIOD = 0). However, it is recommended that you refer to the Sizing Guidelines
and Excel Workbook appropriate for your Control Processor to determine the optimal BPC for
this ECB in order to prevent overloading.

PHASE

Configured integer input that causes the ECB


to be scanned at a specific BPC within the time
determined by the PERIOD. For instance, an
ECB with PERIOD of 3 (2.0 sec.) can be
scanned within the first, second, third, or fourth
BPC of the 2-second time period, assuming the
BPC of the control station is 0.5 sec.

HWTYPE

Hardware Type is configured based on the type


of connected FBM. See ECB201 Information
Pane/Faceplate on page 90 for the list of available values.

214

SWTYPE

Software Type is always identical to the hardware type (HWTYPE) in the


DCI family of ECBs.

214

IOMID

Contains the user-configured


pathname of the ECB201 (device ECB) associated with the HART device (or, for the FBM247,
the associated I/O signal source) to be
accessed by this block.

CP6SG5_ECB:PT_1
00

All DCI Blocks:


RIN, ROUT, IIN,
STRIN

57

B0400FF Rev M

5. Control Block Configuration Information

Table 5-2. Key Parameters (Continued)


ECB or DCI Block

Parameter

Usage

RIN, ROUT, IIN,


STRIN

PNT_NO

These parameters (PNT_NO, RI1_PT, RI2_PT, and RI3_PT) must contain a specific point address specifying the required data I/O operation.
(See Table 5-4 on page 60.)
For the FBM247, configure IIN as described in Configuring IIN Block for
HART Integer Digital Variables and Device Status Bits for the FBM247
on page 73, configure RIN and ROUT as described in Configuring I/O
Blocks (RIN, BIN, ROUT and BOUT) for the FBM247 Hardware Channels on page 71, and configure STRIN as described in Configuring
STRIN Block for HART String Input Variables for the FBM247 on
page 74.

BIN, BOUT, PAKIN

[Varies]

(For the FBM247 only) Configure these blocks as described in Configuring I/O Blocks (RIN, BIN, ROUT and BOUT) for the FBM247 Hardware
Channels on page 71 and Configuring PAKIN Block for HART Packed
Boolean Variables for the FBM247 on page 75.

1.

Typical Syntax

At the present time, for the HART FBMs (not FBM247), there are five legitimate values for
DVOPTS in the ECB201.
If the device is a HART device, one of the following four settings should be used, depending on the
desired OOS and system alarm handling. With any of these settings the ECB201 block will collect
HART status and diagnostic information which may be used for asset management purposes. With
all four settings, the 4-20 mA analog current signal is available for fast control by setting the
PNT_NO parameter of the DCI block such as an RIN or ROUT to the point address of
CURRENT. See Table 5-4 for valid DCI block point address settings.
HART Enables HART communication to the device and if the communication is interrupted for
more than a few seconds, all points are marked OOS (Out of Service).
NOFAIL Enables HART communication; however, the current input or output will always be
OK regardless of the HART communication failure.
NOALARM The same as NOFAIL with the exception that system alarms will also be suppressed
for HART communication failures.
OCD (Open Circuit Detection) Enables HART communication similar to NOFAIL but will
mark the current input or output as OOS after 10 seconds of continuous HART communication
failure.
IOBAD - Enables HART communication to the device and reads additional status information of
the device from HART Command 48. For information about configuring the IOBAD option, refer
to Configuring IOBAD Options on page 59.
If the device or I/O signal source is not a HART device, the following setting should be used:
4-20 - Disables all HART communication on that channel. When configuring the DCI block such
as RIN, the only valid point address is the CURRENT parameter. This setting is not recommended
for HART devices as the ECB201 block will not collect the HART device status and diagnostic
information useful in asset management of the device.
If the DVOPTS parameter is left BLANK, the behavior will default to be the same as the HART setting.
For FBM247, configure DVOPTS as described in Configuring Device ECB (ECB201) for
FBM247 on page 69.

58

5. Control Block Configuration Information

B0400FF Rev M

NOTE

For configurations in which a ZCP270 is connecting to the FBMs via an FCM, the
first four characters of the FBM letterbug (SLOT) are created per user preference,
but they must match the first 4 characters of FCM name. For a non-redundant
FBM, the last two characters (03) reflect the physical position (slot 3) of the FBM
and its associated baseplate (0). For a redundant FBM pair, the last two characters
(0C) reflect the physical position (slot C) of the module pair and its associated baseplate (0). For additional information, refer to Figure 4-2 on page 14 and DIN Rail
Mounted Subsystem Users Guide (B0400FA).

Configuring IOBAD Options


The following is the syntax for the IOBAD options:
IOBAD N.MM N.MM N.MM N.MM N.MM
N represents the decimal number indicating the byte location in the command 48
response. Command 48 provides additional status up to 25 bytes.
Valid range of N is 1<= N <= 25.

MM represents the hexadecimal bit mask to identify the valid IOBAD condition.
Valid range of MM is 1<= MM <= FF.
The IOBAD options have a minimum of one field and a maximum of five fields in the form of
N.MM where N is the byte number and MM is a hex bit mask. If more than one N is greater
than 9, the option can have only four fields due to the 32 character limit in the DVOPTS string.
The bit mask specifies bits that are to be used from command 48 to generate IOBAD in the control blocks, independent of the setting of the Device Malfunction bit. This allows flexibility to
consider other status bits that are unrelated to the Device Malfunction bit, thereby decoupling the
two functions entirely.
Example:
IOBAD 3.FF 4.FD 1.01 25.18
3. FF field monitors all bits in the 3rd byte and generates IOBAD if any one bit of the
3rd byte is active.
4.FD field monitors all bits except the 2nd bit in the 4th byte and generates IOBAD
if any one of that bit is active.
1.01 field monitors only the first bit in the 1st byte and generates IOBAD if that bit is
active.

25.18 field monitors only the 4th and 5th bits in the 25th byte and generates IOBAD
if any one of those bits is active.
You can configure the 3rd byte and then the 1st byte as shown in the example. The HART
check box is selected in FBM247 SYSCFG when the IOBAD options are configured. For
details, refer to Configuring Blocks for FBM247 on page 66.

Point Addresses for HART and Analog I/O Signals


Each DCI block used in conjunction with HART devices and other analog I/O supported by the
HART FBMs and the FBM247 contains at least one parameter which specifies a point address in
the field device (see Table 5-3). This point address indicates, to the HART device or other analog
59

B0400FF Rev M

5. Control Block Configuration Information

I/O source, the specific data I/O operation (command) to be performed (see Table 5-4). The
HART FBMs and the FBM247 support the HART universal commands. For specific commands
supported by HART devices or the analog I/O source, refer to literature from the device
manufacturer.
! CAUTION
Make sure to know what dynamic variables your HART devices or other analog I/O
source support. Only with this knowledge can you know when a seemingly good
value is invalid because it is associated with an unused variable.
The values returned by HART devices or other analog I/O sources depend on the dynamic variables they support. For example, in response to a Read Dynamic Variables and P.V. Current
command (PVCURR), some devices or other sources return data only for the variables they support. Other devices or other sources return data for all four possible dynamic variables supported
by the HART protocol, with the data for unused variables being zero.
The FBM knows that a variable is unused only if the device does not return a value for it. For such
(unused) variables, the data is marked out of service (OOS).
When the device or other source returns a value (such as 0) for unused variables, the FBM treats
this value as good (not OOS) because it has no way of knowing that the variable is unused. In this
case, you are responsible for knowing that data for unused variables is invalid.
Table 5-3. DCI Block Parameters Requiring a Point Address

DCI Block
RIN
ROUT
IIN
STRIN

Connection Parameter(s)
to be Configured
PNT_NO
PNT_NO
PNT_NO
PNT_NO

Table 5-4. Point Address Values for DCI Blocks

Point Address*
UID
CURRENT
CURRENT
PV
PVUNITS
PVCURR
PVPCTRNG
SV

60

Description
Unique Identifier
Current (analog input current value)
Current (analog output current value)
Primary Variable
Primary Variable Units
Primary Variable Current
Primary Variable Percent of Range
Secondary Variable

DCI Block

Signal
Condition
Index

Device
Type

STRIN
RIN
ROUT
RIN
STRIN
RIN
RIN
RIN

---SCI = 1-10
SCO = 1-5
SCI = 0
---SCI = 0
SCI = 0
SCI = 0

Input
Input
Output
Input
Input
Input
Input
Input

5. Control Block Configuration Information

B0400FF Rev M

Table 5-4. Point Address Values for DCI Blocks (Continued)

Point Address*
SVUNITS
TV
TVUNITS
FV
FVUNITS
MSG
TAG
DESC
DATE
PVSENSER
PVSENSUP
PVSENSLOW
PVSENSPAN
PVSENUNITS
PVALMSEL
PVXFRFUN
PVUPRNG
PVLOWRNG
PVDAMP
PVRNGUNITS
WP
PLDC
FINASSYNUM

Description
Secondary Variable Units
Tertiary Variable
Tertiary Variable Units
Fourth Variable
Fourth Variable Units
Message
Tag
Descriptor
Date
Primary Variable Sensor Serial Number
Primary Variable Sensor Upper Limit
Value
Primary Variable Sensor Lower Limit
Value
Primary Variable Sensor Minimum
Span Value
Primary Variable Sensor Limits and
Minimum Span Units
Primary Variable Alarm Select Code
Primary Variable Transfer Function
Code
Primary Variable Upper Range Value
Primary Variable Lower Range Value
Primary Variable Damping Value
Primary Variable Upper and Lower
Range Values Units
Write Protect Code
Private Label Distributor Code
Final Assembly Number

DCI Block

Signal
Condition
Index

Device
Type

STRIN
RIN
STRIN
RIN
STRIN
STRIN
STRIN
STRIN
STRIN
IIN
RIN

---SCI = 0
---SCI = 0
------------------SCI = 0

Input
Input
Input
Input
Input
Input
Input
Input
Input
Input
Input

RIN

SCI = 0

Input

RIN

SCI = 0

Input

STRIN

----

Input

IIN
IIN

-------

Input
Input

RIN
RIN
RIN
STRIN

SCI = 0
SCI = 0
SCI = 0
----

Input
Input
Input
Input

IIN
IIN
IIN

----------

Input
Input
Input

* For standard 4 to 20 mA analog I/O devices (not HART devices), use point address CURRENT.

Data Type Conversions


The control station logic automatically converts HART I/O data from the data type specified in
the DCI input scan record (transferred from the HART FBM to the control station) to the data
type of the DCI block parameter when the DCI block is processed.
In the RIN blocks, the input value is converted to Foxboro Evo format before applying signal
conditioning and/or linear scaling to the data. The output value to be written to the FBM is

61

B0400FF Rev M

5. Control Block Configuration Information

converted to HART format after the inverse scaling and/or inverse signal conditioning has been
applied.
In ROUT blocks, the readback value is converted to Foxboro Evo format before applying signal
conditioning and/or linear scaling to the data. The output value to be written to the FBM is converted to HART format after the inverse scaling and/or inverse signal conditioning has been
applied.
Table 5-5. Data Type Conversions

DCI Block

Parameters

Foxboro Evo
Data Type

HART Data Type

RIN

RIN

single-precision
float

Signed or unsigned 8-bit, 16-bit, or 32-bit


integer, or single precision float

ROUT

OUT

single-precision
float

Signed or unsigned 8-bit, 16-bit, or 32-bit


integer, or single precision float

IIN

IIN

32-bit long
integer

Signed or unsigned 8-bit, 16-bit, or 32-bit


integer, or single precision float (truncated)

NOTE

All other HART data types not specified in this table are converted by the HART
FBM to/from the appropriate Foxboro Evo data type.

Equipment Control Blocks (ECBs)


! CAUTION
When modifying an ECB201configuration with changes that are related to DCI
connections (for example, when changing a device address), you are advised not to
wait for the system to report any possible error(s) associated with that change.
Rather, you should monitor the ECB201 block detailed display while modifying the
ECB201 configuration (see Chapter 6 Process Operator Displays). This ensures
that all possible errors are detected (and resolved) before commencement of process
control operations.

NOTE

Be aware that the fastest allowed ECB period for the HART FBMs and FBM247 is
100 milliseconds (PERIOD = 0). However, it is recommended that you refer to the
Sizing Guidelines and Excel Workbook appropriate for your Control Processor to
determine the optimal BPC for this ECB in order to prevent overloading.

62

5. Control Block Configuration Information

B0400FF Rev M

Creating and Editing FBM ECB (ECB200 or ECB202)


To support FBM214, FBM214b, FBM215, FBM244 or FBM247 operation, one ECB200 must
be created and edited for each FBM. To support FBM216, FBM216b, FBM218 or FBM245
operation, one ECB202 must be created and edited for each redundant pair.
NOTE

The only supported control configurators for the HART-capable FBM247 are the
Foxboro Control Software editors and the ICC.
To create and edit an ECB using the Foxboro Evo Control Editors Block Configurator, refer to
the section Configuring Blocks in Block Configurator User's Guide (B0750AH).
To create and edit an ECB using the ICC, refer to the section View Blocks/ECBs in this Compound and Insert New Block in Integrated Control Configurator (B0193AV).
To create and edit an ECB using the I/A Series Configuration Component (IACC) (for any
FBMs other than the FBM247), refer to the section Control Blocks in I/A Series Configuration
Component (IACC) Users Guide (B0700FE).
To create and edit an ECB using FoxCAE software (for any FBMs other than the FBM247), refer
to Computer Aided Engineering for I/A Series Control Station Databases, FoxCAE Version 4.0
(B0193MR).
For the ECB200 and ECB202 parameter definitions, refer to Integrated Control Block Descriptions
(B0193AX).
For the FBM247, also refer to Configuring Blocks for FBM247 on page 66.

63

B0400FF Rev M

5. Control Block Configuration Information

Figure 5-6. System Manager - Connections Tab - For FCP270 Connected to HART FBMs

Creating and Editing Device ECB (ECB201)


For each HART device associated with the FBMs, a child ECB201 must be configured and connected to the (parent) ECB200 or ECB202. The ECB201 can reside in the same compound as
the ECB200, or it can reside in any other user-configured compound.
NOTE

The only supported control configurators for the HART-capable FBM247 are the
Foxboro Control Software editors and the ICC.
To create and edit the slave device ECBs (ECB201s) using the Control editors Block Configurator, refer to the section Configuring Blocks in Block Configurator User's Guide (B0750AH).
To create and edit the slave device ECBs (ECB201s) using the ICC, refer to the sections View
Blocks/ECBs in this Compound and Insert New Block in Integrated Control Configurator
(B0193AV).
To create and edit an ECB using the I/A Series Configuration Component (IACC) (for any
FBMs other than the FBM247), refer to the section Control Blocks in I/A Series Configuration
Component (IACC) Users Guide (B0700FE).
64

5. Control Block Configuration Information

B0400FF Rev M

To create and edit an ECB using FoxCAE software (for any FBMs other than the FBM247), refer
to Computer Aided Engineering for I/A Series Control Station Databases, FoxCAE Version 4.0
(B0193MR).
For the ECB201 parameter definitions, refer to Integrated Control Block Descriptions (B0193AX).
For the FBM247, also refer to Configuring Blocks for FBM247 on page 66.
NOTE

You can use the block name for the PARENT parameter whenever the child ECB and
the parent ECB reside in the same compound. For example, you might enter
ECB200BK15 for the PARENT parameter because the child ECB201 and the parent
ECB (ECB200 or ECB202) reside in the PRIMARY_ECB compound
(F41CP6_ECB).
If the child ECB and the parent ECB are not in the same compound, you must enter
the full compound:block pathname for the PARENT parameter.

Figure 5-7. System Manager - General Tab (FBM Equipment Status Display) - For HART FBM

65

B0400FF Rev M

5. Control Block Configuration Information

Configuring Blocks for FBM247


The HART-capable FBM247 supports a wide range of analog, digital or pulse I/O signals, as
detailed in DIN Rail Mounted Subsystem Users Guide (B0400FA). When powered on and before
any configuration data is downloaded to the FBM247, the default state of each channel is the
externally-powered current input mode.
Using your preferred block configuration tool, configure the FBM247s block parameters as
described in the following subsections. The following Foxboro Evo blocks are used in conjunction
with the FBM247:
ECB200 - the ECB for the FBM247
ECB201 - the ECB for each of the eight FBM247 I/O channels
RIN, BIN, ROUT, BOUT and IIN - the blocks for configuring the signal types for
FBM247 I/O channels
IIN, STRIN, PAKIN - the blocks used to retrieve and interpret the HART device
statuses.
The FBM247 also supports the BINR, IINR and RINR blocks but there are no special configuration instructions for these blocks. Refer to Integrated Control Block Descriptions (B0193AX) for
more information on configuring these blocks parameters.
NOTE

The only supported control configurators for the FBM247 are the Foxboro Evo
Control Editors and the ICC.

Configuring FBM ECB (ECB200) for FBM247


The following ECB200 parameters must be configured as described below for the FBM247, in
addition to the ECB200 parameters described in Table 5-2 Key Parameters on page 55:
HWTYPE = 247
SWTYPE = 247
FSENAB = toggles fail-safe logic to fieldbus devices connected to the FBM:
0 = Disables failsafe logic (default)
1 = Enables failsafe logic; activates the FSDLAY timer to detect loss of communications with the control station, and starts fail-safe action to field devices hosted by the
FBM.
action to those field devices
FSDLAY = As described in Table 5-2 Key Parameters on page 55.
SYSOPT = the analog and pulse input integration period for all channels; see
Table 5-6 below

SYSCFG = the configuration parameter for HART communications (see below)

Table 5-6. ECB200 SYSOPT Parameter - Analog and Pulse Input Integration Period

SYSOPT Value
1

66

Analog/Pulse Integration Period


100 milliseconds

Frequency Measurement Settling Time


250 milliseconds, 8 Hz minimum

5. Control Block Configuration Information

B0400FF Rev M

Table 5-6. ECB200 SYSOPT Parameter - Analog and Pulse Input Integration Period (Continued)

SYSOPT Value

Analog/Pulse Integration Period

2
3
4
Any other value

Frequency Measurement Settling Time

250 milliseconds
500 milliseconds
1 second
500 milliseconds

500 milliseconds, 4 Hz minimum


1 second, 2 Hz minimum
1 second, 2 Hz minimum
1 second, 2 Hz minimum

The SYSCFG parameter data is used as a bit mapped parameter to indicate that a channel is preconfigured as a HART device, as an input or an output, and if loop power is required. This
enables the FBM247 to obtain a live list for the selected channels. SYSCFG is an unsigned long
(32-bit) which should be entered as a hex value. Each of the four bytes has a function in defining
the I/O channel type, with channel 1 as the least significant bit (LSB) and channel 8 as the most
significant bit (MSB), as shown in Figure 5-8 below:

HART Channel (Byte 3)

0
B32

B31

31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9

B30

B29

B28

B27

B26

B25

B24

B23

B22

B21

B20

B19

B18

B17

B16

B15

B14

B13

B12

B11

B10

B9

B8

B7

B6

B5

B4

B3

Loop Power (Byte 0)


1

B2

HART Channel (Byte 1)


2

B1

Output Channel (Byte 2)

Figure 5-8. SYSCFG Bit Mapping

NOTE

In Figure 5-8, the output (Byte 2) and loop power (Byte 0) configuration bits are
only valid when HART communications have been enabled.
The purpose of each of the bytes is as follows:
1. Byte 3 (most significant) and byte 1 must be identical as they indicate which channels
are to be preconfigured by the SYSCFG parameter. As a security feature, the entire
configuration will be ignored if these two bytes do not match exactly. When a bit is set
in these two bytes, the corresponding channel is enabled for the HART live list
according to the information in other two bytes. If the bit is clear, the channel remains
in an unpowered state.
2. Byte 2 indicates that the channel is an output device when the bit is set. The channel
is an input device when the bit is clear.
3. Byte 0 (least significant) indicates that the channel uses loop (FBM) power when the
bit is set, or uses an external power source when the bit is clear. Note that most output
devices require loop power to provide the current output, whereas input devices usually do use loop power but some devices either provide their own power or are powered from a separate field power supply.
For example, the value 0x83018303 indicates a loop powered HART output device on channel 1,
a loop powered HART input device on channel 2 and an externally powered HART input device
on channel 8 with channels 3 through 7 not configured.

67

B0400FF Rev M

5. Control Block Configuration Information

NOTE

1. The default value for SYSCFG is 1000 (0x000003E8) which does not configure
any of the channels since that value does not meet the security requirements outlined in the first item above. Therefore, if the user takes no explicit action to configure this parameter, the channels will not be configured until the ECB201 and I/O
block configurations are downloaded to the FBM.
2. Channels that have been preconfigured in SYSCFG require that the ECB201 and
I/O block configurations are appropriate for that channel. If the ECB201 or I/O
block configuration is incompatible with the preconfigured value, the configuration
is rejected by the FBM. Preconfigured channels must be analog current input or
output and powered as defined in SYSCFG.
3. Channels that have not been preconfigured remain in a safe powered-off state
until the ECB201 and I/O block configurations have been downloaded and validated by the FBM.
To configure the SYSCFG parameter in the Control Softwares Block Configurator, you will need
to invoke a grid control from the V button, beside the System Configuration (HART
Options) field in the ECBs -> FBM tab for the ECB200, as shown in Figure 5-9.

Figure 5-9. Configuring SYSCFG in the Block Configurator From Grid Control

The grid control shown above allows you to configure channels for up to eight HART devices.
SYSCFG will not be changed if you do not make any changes via this grid control.
In order to configure a channel, the checkbox in the HART column of that channel must be
checked (see Figure 5-9 above). If the checkbox in the HART column for a channel is checked,
the Input/Output and Power columns are enabled. If the checkbox in the HART column for a
channel is unchecked, the Input/Output and Power columns are disabled.
When the SYSCFG parameter has a value of 1000 (or any invalid values), the grid control will not
have any selections to configure.
Refer to the Block Configurator Users Guide (B0750AH) for additional details on using this editor.
68

5. Control Block Configuration Information

B0400FF Rev M

During normal system operation, you can view the current configuration of the SYSCFG parameter for an FBM247 via the FBM247s ECB200 faceplate (detail view) in the Foxboro Evo Control HMI. See Figure 7-6 ECB200 Faceplates for FBM247 Devices - Configuration Views on
page 124.
The following ECB200 parameters are not used with FBM247:
PORTEX
WDTMR
FILEID
SFILID.

Configuring Device ECB (ECB201) for FBM247


Each of the FBM247s eight I/O channels may have a device ECB201 configured for it. The following ECB201 parameters must be configured specifically for the FBM247 type and channel
type, in addition to the ECB201 parameters described in Table 5-2 Key Parameters on page 55:

HWTYPE = 247
SWTYPE = 247
DVNAME = CHn t [LPWR]:
Where
n is 1 to 8
t is I or O representing input or output.
[LPWR] selects the loop power option for current I/O.
If configured as EPWR (or omitted), the external power option is selected for current
I/O signal. This identifies the I/O channel and power option used by the current I/O
device connected to the channel.
To configure the DVNAME parameter in the Control Softwares Block Configurator,
you will need to invoke a grid control from the V button, beside the Device Name
(Channel Configuration) field in the ECBs -> FBM tab for the ECB201 derived
from $DEV_ECB201 template, as shown in Figure 5-10.

Figure 5-10. Configuring DVNAME in the Block Configurator From Grid Control

The grid control allows you to configure Input/Output and Power values for the
DVNAME parameter. You cannot configure the Channel value in the grid control.
To set the Channel value for ECB201 device, drag and drop the device on FBM247
channel in Network View as shown in Figure 5-11.

69

B0400FF Rev M

5. Control Block Configuration Information

Figure 5-11. Configuring Channel in Network View

Refer to the Block Configurator Users Guide (B0750AH) for additional details on
using this editor.
DVOPTS = Device Options; see Table 5-7 below.
DVOPTS sets up the hardware interface for the appropriate signal types to be connected to the I/O channel. The actual signal type is defined by the I/O block type and
connection string.
The mode VOLT sets the I/O channel into voltage input mode with no HART
communication. All the other modes set the channel into the current I/O mode and
specify if HART communication is enabled or not.
Table 5-7. ECB201 DVOPTS Parameter - Device Options

DVOPTS Mode
VOLT
4-20
NOFAIL
NOALARM
POWER OFF

HART

IOBAD

Device Option
Analog voltage input mode; no HART communication
Analog current only mode, input or output; no HART communication
Enables HART communication; however, the current input or output will
always be OK regardless of the HART communication failure
The same as NOFAIL with the exception that system alarms also will be
suppressed for any HART communication failures
Disconnects the I/O channel from the device for troubleshooting or driving
the device with an external source. It is a software equivalent to a quick
disconnect.
Enables HART communication to the device and if the communication is
interrupted for more than about five seconds; all points are marked out-ofservice (OOS)
Enables HART communication to the device and reads additional status
information of the device from HART Command 48. For information about
configuring the IOBAD option, refer to Configuring IOBAD Options on
page 59.

Note that certain combinations of DVOPTS and PNT_NO configurations of the I/O blocks are
invalid. For example, when DVOPTS = VOLT, the RIN blocks parameter PNT_NO can only be
10V, 5V, PULSE, FREQ, ACCEL or JERK to be valid.

70

5. Control Block Configuration Information

B0400FF Rev M

The Mode column in Table 5-8 in the next subsection shows if the variable is valid for current (I),
voltage (V) or either (I/V) mode. Output block variables are only available in current mode. Conflicts must be resolved before the I/O block can come on-line.
Also, the DDIAG1 parameter of the ECB201 allows you to read the current HART device status
- a single byte returned with each HART message response to the FBM247. The general details of
this parameter are discussed in ECB201 Extended Status Support on page 91; however, the specific use of this parameter with FBM247 and HART devices is discussed in Configuring IIN
Block for HART Integer Digital Variables and Device Status Bits for the FBM247 on page 73.
During normal system operation, you can view the current configuration of the DDIAG1 parameter for an FBM247 via the FBM247 devices ECB201 faceplate (detail view) in the Foxboro Evo
Control HMI. See Figure 7-7 ECB201 Faceplates for FBM247s Devices on page 126.
Finally, the following ECB201 parameters are not used with FBM247:
PORTNO
FILEID
DVADDR
DVTYPE
SFILID
MANFTR
VERNUM
ERROPT.

Configuring I/O Blocks (RIN, BIN, ROUT and BOUT) for the FBM247
Hardware Channels
The PNT_NO parameter in the RIN, BIN, ROUT and BOUT blocks configures an FBM247
hardware I/O channel along with the signal type. One (and only one) of the blocks listed in
Table 5-8 below may be configured for each FBM247 I/O channel with one exception; if any one
of the pulse channel inputs marked with (*) in the Block column are configured, the other three
inputs may also be configured since they are all obtained from the pulse counter channel data.
HART communication is only available when the PNT_NO is set to CURRENT or
CURRENT+LFD.
Table 5-8. RIN, BIN, ROUT, and BOUT PNT_NO Parameter Settings

PNT_NO
CURRENT
CURRENT+LFD
10V
5V
PULSE
FREQ

Block
RIN

Description

Analog input current value, HART or


non-HART
RIN
Analog input current value, HART or
non-HART with Line Fault Detection1
RIN
Analog input voltage value, 0-10 volt range
RIN
Analog input voltage value, 0-5 volt range
RIN (*) Pulse count input, range 0 to 65535
RIN (*) Frequency counter input, range 0 to
25000 Hz.

Mode

SCI/SCO

1 to 10

1 to 10

V
V
I/V
I/V

1 to 10
1 to 10
0
8

71

B0400FF Rev M

5. Control Block Configuration Information

Table 5-8. RIN, BIN, ROUT, and BOUT PNT_NO Parameter Settings (Continued)

PNT_NO
ACCEL

RIN (*)

JERK
DI 0t 1t

SOE
NAMUR

CURRENT
CURRENT+LFD
CURRENT
CURRENT+LFD
DO
PO nnn

1.

Block

Description

Acceleration input, Frequency/Second


(dF/dt)
RIN (*) Jerk input, Acceleration/Second (dA/dt)
BIN
Digital input, 0t = off threshold, 1t = on
threshold in percent of 10V or 20 mA
input range
BIN
Digital input, 1 ms fast scan for SOE, fixed
5 volt (V) or NAMUR (I) input thresholds
BIN
Digital input, NAMUR input current
thresholds with open/short circuit
detection
ROUT Analog output current value, HART
positioners
ROUT Analog output current value with Line
Fault Detection, HART positioners
ROUT Analog output current value, non-HART
positioners
ROUT Analog output current value with Line
Fault Detection, non-HART positioners
BOUT Sustained digital output
BOUT Momentary digital output,
nnn = 3 to 255 in 10 ms increments
(30 ms min, 2.55 sec max)

Mode

SCI/SCO

I/V

I/V
I/V

8
n/a

I/V

n/a

n/a

3 or 5

3 or 5

1 to 5

1 to 5

I
I

n/a
n/a

Life Fault Detection is a feature in which the FBM monitors for specific conditions which might
indicate issues with the I/O signal, such as the analog current input is below or above specific levels,
or the analog output current loop is open.

For the block parameter definitions, refer to Integrated Control Block Descriptions (B0193AX).
NOTE

The variables listed in the following two subsections are not available if the ECB201
DVOPTS parameter is in either the VOLT or 4-20 modes.

Configuring RIN Block for HART Floating Point Digital Variables


for the FBM247
The HART floating point digital variables are accessed by using RIN blocks with the PNT_NO
connection strings in Table 5-9 below.

72

5. Control Block Configuration Information

B0400FF Rev M

Table 5-9. RIN PNT_NO Parameter Settings for HART Floating-Point Digital Variables

PNT_NO
PV
PVCURR
PVPCTRNG
SV
TV
FV
PVSENSUP
PVSENSLOW
PVSENSPAN
PVUPRNG
PVLOWRNG
PVDAMP

Description

SCI

Primary HART variable in engineering units


Primary HART variable value in milliamps
Primary HART variable in percent of range
Secondary HART variable
Tertiary HART variable
Fourth HART variable
Primary HART variable sensor upper limit
Primary HART variable sensor lower limit
Primary HART variable sensor minimum span value
Primary HART variable upper range limit
Primary HART variable lower range limit
Primary HART variable damping value

0
0
0
0
0
0
0
0
0
0
0
0

Configuring IIN Block for HART Integer Digital Variables and Device
Status Bits for the FBM247
The HART integer digital variables are accessed by using IIN blocks with the PNT_NO connection strings in Table 5-10 below.
Table 5-10. IIN PNT_NO Parameter Settings for HART Integer Digital Variables

PNT_NO
PVSENSER
PVALMSEL
PVXFRFUN
WP
PLDC
FINASSYNUM
DEVSTS

Description
Primary Variable Sensor Serial Number
Primary Variable Alarm Select Code
Primary Variable Transfer Function Code
Write Protect Code
Private Label Distributor Code
Final Assembly Number
HART device status (see below)

The HART device status (DEVSTS) is a single byte returned with each HART message response
to the FBM247. (This value is also obtainable through the DDIAG1 parameter of the ECB201.)
These bits are shown in the System Management Equipment Information display for each HART
device and are universally defined for all HART devices. The I/O block state is also changed based
upon the value of certain bits as shown in Table 5-11:
Table 5-11. HART Device Status Bits

Bit
0 (LSB)

Description
PV Out-of-Limits

I/O Block State


Error

73

B0400FF Rev M

5. Control Block Configuration Information

Table 5-11. HART Device Status Bits (Continued)

Bit
1
2
3
4
5
6
7 (MSB)

Description

I/O Block State

Non-PV Out-of-Limits
PV Analog Output Saturated
PV Analog Output Fixed
More Status Available
Cold Start
Configuration Changed
Field Device Malfunction

Normal
Error
Track
Normal
Normal
Normal
BAD

If the HART device reports a Field Device Malfunction in the HART device status (bit 7), this
causes the following alarms to occur regardless of the setting of the DVOPTS parameter in
ECB201:
All I/O blocks connected to that HART device show BAD I/O.
The device shows a Warning Condition or Device Failure in the applicable system
management application.
None of the other bits cause a system alarm.
Bit 4 is set (More Status Available) when the HART device has additional device-specific
statuses to report. When this bit is set, the FBM247 retrieves up to 25 additional status bytes
from the HART device; these bytes contain the additional status information. Refer to the
documentation provided by the original manufacturer of the HART device for a description of
the statuses indicated by these bits. These status bytes can be displayed in a STRIN block and in
multiple PAKIN blocks, as discussed in next two subsections.
Configuring STRIN Block for HART String Input Variables for the FBM247

As discussed above, the device-specific status bytes returned by the HART device can be displayed
via the STRIN block.
HART string input variables, as well as the input signal type, can be configured via a STRIN
block with the PNT_NO connection strings in Table 5-12 below.
Table 5-12. STRIN PNT_NO Parameter Settings for HART String Input Variables

PNT_NO
UID
PVUNITS
SVUNITS
TVUNITS
FVUNITS
MSG
TAG
DESC
DATE
PVSENUNITS
74

Description
Unique Identifier
Primary Variable Units
Secondary Variable Units
Tertiary Variable Units
Fourth Variable Units
Message
Tag
Descriptor
Date
Primary Variable Sensor Limits and Minimum Span Units

5. Control Block Configuration Information

B0400FF Rev M

Table 5-12. STRIN PNT_NO Parameter Settings for HART String Input Variables (Continued)

PNT_NO

Description

PVRNGUNITS
STATUS

Primary Variable Upper and Lower Range Values Units


Additional status bytes returned by HART command 48 in hex format

You can use the STRIN block to view HART device-specific status information as described in
the previous subsection. This status information can be retrieved in conjunction with the PAKIN
block, as discussed below.
Configuring PAKIN Block for HART Packed Boolean Variables for the FBM247

As discussed above, the device-specific status bytes returned by the HART device can be displayed
via multiple PAKIN blocks.
PAKIN blocks are used to retrieve up to four individual HART device status bytes which can be
displayed via a STRIN block configured with the STATUS parameter. This configuration allows
an operator to connect to and monitor the states of specific bits and bytes in the additional status
information provided by the response to HART command 48, discussed above. While 25 bytes
are made available by these block connections, not all devices return that many bytes. Bytes that
are not returned by the device are always set to zero (0), whereas the STATUS parameter setting in
Table 5-12 above only displays the number of bytes that were actually returned from the HART
device.
The STRIN block displays the bytes in ascending order like 01020304 whereas the PAKIN block
displays the bytes in descending order like 04030201. This means that the most significant bit
(MSB) of byte 04 is displayed as bit 1 and the least significant bit (LSB) of byte 01 is displayed as
bit 32. If the STRIN value is 01020304 this would show bits 6, 15, 16, 23 and 32 as ON and all
of the other bits OFF in the PAKIN block.
The PKIOPT parameter in the PAKIN block must be changed from the default value (1) to 3
to display the bits and bytes in the order described above. (Leaving this parameter set to 1 causes
the PAKIN block to swap the order of the bits and bytes which would make bit 1 display the least
significant bit of byte 01 and bit 32 would display the most significant bit of byte 04.)
A Boolean connection can be made to any individual bit by using
COMPOUND:BLOCK.PAKCIN.Bn where n is the bit number from 1 to 32.
For example, the connection can be made to a CIN block to provide a state alarm message when
the state of the corresponding bit changes.
Set the PKINGP parameter as shown in Table 5-13 to extract the appropriate bytes from the
HART devices response to the request for status bytes from the FBM247.
Table 5-13. PAKIN PKINGP Parameter Settings for HART Packed Boolean Block
Configuration

PKINGP
STATUS1
STATUS2
STATUS3
STATUS4
STATUS5

Description
Bytes 4 to 1 (4=MSB) of HART device response
Bytes 8 to 5 (8=MSB) of HART device response
Bytes 12 to 9 (12=MSB) of HART device response
Bytes 16 to 13 (16=MSB) of HART device response
Bytes 20 to 17 (20=MSB) of HART device response
75

B0400FF Rev M

5. Control Block Configuration Information

Table 5-13. PAKIN PKINGP Parameter Settings for HART Packed Boolean Block
Configuration (Continued)

PKINGP
STATUS6
STATUS7

76

Description
Bytes 24 to 21 (24=MSB) of HART device response
Byte 25 (LSB) of HART HART device response

5. Control Block Configuration Information

B0400FF Rev M

Configuring DCI Blocks


NOTE

This section applies to all HART FBMs and the HART-capable FBM247.
In a control strategy, the DCI control blocks interface the Foxboro Evo system to the HART slave
devices. The DCI blocks used with HART devices are listed in Table 5-1.
The DCI blocks are created in the same general manner as the ECBs. For detailed information,
refer to Integrated Control Configurator (B0193AV). For parameter definitions, refer to Integrated
Control Block Descriptions (B0193AX).
As part of the editing operations performed on the newly created DCI blocks, certain parameters
(PNT_NO, R11_PT and others) must contain a point address to specify the particular HART
universal command to be performed regarding the input or output data handled by the DCI
block. Refer to Point Addresses for HART and Analog I/O Signals on page 59 for detailed
information.
In conjunction with creating and editing DCI blocks, you will need to configure the various
blocks and compounds required for the desired control scheme. Refer to the following documents
to perform these operations:
DIN Rail Mounted Subsystem Users Guide (B0400FA)
Control Processor 270 (CP270) and Field Control Processor 280 (CP280) Integrated
Control Software Concepts (B0700AG)
Integrated Control Block Descriptions (B0193AX).
NOTE

The only supported control configurators for the HART-capable FBM247 are the
Foxboro Control Software editors and the ICC.
To create and edit a DCI block in an existing compound using the Control Softwares Block Configurator, refer to the section Configuring Blocks in Block Configurator User's Guide
(B0750AH).
To create and edit a DCI block in an existing compound using the ICC, refer to the sections
View Blocks/ECBs in this Compound and Insert New Block in Integrated Control Configurator (B0193AV).
To create and edit a DCI block using the I/A Series Configuration Component (IACC) (for any
FBMs other than the FBM247), refer to the section Control Blocks in I/A Series Configuration
Component (IACC) Users Guide (B0700FE).
To create and edit a DCI block using FoxCAE software (for any FBMs other than the FBM247),
refer to Computer Aided Engineering for I/A Series Control Station Databases, FoxCAE Version 4.0
(B0193MR).
NOTE

The engineering units configured for the block detail display must match the units
configured in the device.

77

B0400FF Rev M

5. Control Block Configuration Information

To verify operation of the DCI blocks and the HART device data using the block detail
displays:
1. Access the appropriate application:
For the Foxboro Console Software Block Select application, refer to the Control
HMI Application User's Guide (B0750AQ) for details.
For the FoxSelect compound/block overview utility, refer to Process Operations and
Displays (B0700BN) for details.
2. Access the block detail display for each DCI block created, and confirm its data.

Example for Reading Pressure Measurement


A RIN block may be configured to read pressure from a pressure transmitter.
NOTE

The only supported control configurators for the HART-capable FBM247 are the
Foxboro Control Software editors and the ICC.
To create and configure a RIN block to read pressure measurement using the Control Softwares
Block Configurator, refer to the section Configuring Blocks in Block Configurator User's Guide
(B0750AH).
To create and configure a RIN block to read pressure measurement using the ICC, refer to the
sections View Blocks/ECBs in this Compound and Insert New Block in Integrated Control
Configurator (B0193AV).
To create and edit a RIN block using the I/A Series Configuration Component (IACC) (for any
FBMs other than the FBM247), refer to the section Control Blocks in I/A Series Configuration
Component (IACC) Users Guide (B0700FE).
To create and edit a RIN block using FoxCAE (for any FBMs other than the FBM247), refer to
Computer Aided Engineering for I/A Series Control Station Databases, FoxCAE Version 4.0
(B0193MR).
For parameter definitions for the RIN block, refer to Integrated Control Block Descriptions
(B0193AX).
If the RIN block PNT_NO parameter is set to CURRENT, the RIN block output will be the Primary Variable (Pressure in this example), based only on the 0 to 20 mA dc current signal coming
into the HART FBM from the HART device, and this output will be the raw counts of the 0 to
20 mA dc signal converted to the equivalent Engineering Units in the exact same manner as an
AIN block does the conversion with a 0-to-20-mA-only FBM. If the PNT_NO parameter is set
to the HART variable PV, the RIN block reads the Primary variable from the transmitter (Pressure
in this example) in a digital response format which has the value already converted to engineering
units by the transmitter, and, therefore, the RIN block output is just this digitally-read value without any additional conversions or manipulations applied to it.

78

5. Control Block Configuration Information

B0400FF Rev M

DCI Block Processing


The following is an overview of DCI block processing (and data read/write) operations.
NOTE

Scheduling of block processing depends on the period/phase of the ECB or control


block. For proper operation, you must synchronize the associated ECB and control
block processing, if required, by configuring these parameters appropriately. It is
recommended that you use the default ECB values and modify only the DCI block
periods and phase.
The control station processes the ECBs and DCI blocks as an integral part of its compound processing, each basic processing cycle (BPC). The order of processing is the same as the order of the
compounds, ECBs, and blocks configured in the control database.
Processing of the ECBs and control blocks is performed in the following sequence.
1. ECBs scheduled to be processed are executed to read fresh inputs.
When a parent or child ECB is processed, its DCI linked list is examined. For each
DCI input or output block ready to be run in that BPC, its DCI connection requests
are added to a read list for that ECB.
When the read list is complete, a Read_Data message is sent to the HART FBMs to
retrieve the current data contained in the DCI connection records in the FBM. (If
necessary, multiple messages are used to retrieve, from each FBM, all data required by
the DCI blocks for that BPC.) All read list data is moved into the DCI connection
records in the DCI blocks as it is retrieved.
2. Control blocks scheduled to be processed are executed.
When all ECBs have been processed, the control blocks are processed. When the DCI
blocks are processed, all DCI connection data is processed. (Refer to Key DCI Block
Functions on page 80 for a description of the common functions performed in the
DCI blocks.) During this processing, the DCI blocks set write request flags in the
DCI connection records for any outputs that need to be written to the field devices.
3. ECBs scheduled to be processed, and containing fresh outputs to be written, are
executed.
When all control blocks have been processed, the ECBs are processed once again to
drive the field outputs (in the control output blocks) that have been changed in that
BPC. When a DCI parent or child ECB is processed, its linked list is examined once
again. For each DCI connection record with a pending write request flag, a write list is
generated.
When the write list is complete, a Write_Data message is sent to the HART FBMs to
write the current output data contained in the DCI output connection records in the
control station. (If necessary, multiple messages are used to write all data requested by
the DCI blocks for that BPC.)

79

B0400FF Rev M

5. Control Block Configuration Information

Key DCI Block Functions


Some key DCI block functions that can be selected by parameter settings are described in the
following paragraphs. [For more specific information on these functions, refer to the DCI block
descriptions (RIN, ROUT, IIN, and STRIN) in Integrated Control Block Descriptions
(B0193AX)].

Periodic/Change-Driven Execution
All DCI blocks are executed periodically according to their Period/Phase parameter configuration.
The ROUT block normally sets write requests to the HART FBM only when the output value
changes. If the secondary loop timer (SECTIM) is configured non-zero, write requests are also set
if the timer expires between output changes.

Auto/Manual Mode Operation


All DCI blocks except STRIN support the Auto/Manual mode of operation. This allows the
operator to manually substitute the inputs in the RIN, and IIN blocks, and to manually drive the
ROUT output directly.

Simulation Mode
Simulation mode is supported in all DCI blocks. When SIMOPT is set, the DCI connections are
not used. In the STRIN block, the string value may be written into the block by an object manager (OM) write access command. In the RIN, and IIN blocks, the input is provided by a separate, configurable input parameter. In the ROUT block, confirmation of the output value change
is simulated automatically. The simulation mode may be used in conjunction with the
Auto/Manual mode. The two features may co-exist in any DCI block.

Signal Conditioning and Linear Scaling


Signal conditioning and linear scaling of analog inputs/outputs can be configured in the RIN and
ROUT blocks. The SCI and SCO parameters can be used to specify any of the standard signal
conditioning algorithms supported by the Foxboro control station, except for thermocouple and
RTD conversions. For a description of the SCI conditioning algorithms, refer to the appendix
associated with the RIN block, in Integrated Control Block Descriptions (B0193AX). For a description of the SCO conditioning algorithms, refer to the ROUT block [also in Integrated Control
Block Descriptions (B0193AX)].

Input Limiting
The input values of the RIN block are constrained by the engineering range (HSCI1/LSCI1) configured in the block. If the input value is out-of-range, it is clamped to the high/low range value,
and the corresponding LHI/LLO status bit is set in the value record.

Confirmed Outputs
The output of the ROUT block is confirmed by a readback of the actual value written to the
HART FBM. When an output is changed in one of these blocks by the Foxboro Evo system, it is
stored in a request location that is part of the output value record in the block. (In Foxboro Evo
terminology, this type of output is referred to as a shadow output and is reflected in the shadow
status bit (Bit 12) in the value record.) The actual output value of the block is not updated until

80

5. Control Block Configuration Information

B0400FF Rev M

confirmation of the requested change at the field device is received during the next processing
cycle of the DCI block.
The request value is written to any output-capable HART FBM (such as FBM215/218/244/245
or FBM247), which writes the value to the HART field device. If the write operation is successful,
the output-capable HART FBM stores the value as the readback value in its DCI connection
record.
On the next ROUT block cycle, the block output value is updated in the Foxboro control station
with the readback value from the HART FBM, thus completing confirmation of the change.

Output Clamping
The output value of the ROUT block is constrained by the limit values (HOLIM/LOLIM) configured in the block. The limit values are constrained by the engineering range (HSCO1/LSCO1)
configured in the block. If the output value exceeds its limiting constraints, it is clamped to the
high/low value, and the corresponding LHI and LLO status bit is set in the value record. This feature can be enabled in Auto mode only or in both Auto and Manual modes.

Output Initialization
The output value of a ROUT block initializes to the readback value in each of the following cases:
When the compound containing the block is turned on
When the block is installed and runs its first cycle
When control station-to-FBM communication recovers from a failure condition
When the Initialization Input (INI_PT), if used, is set.
The readback value contains the most recent value written to the HART FBM by the control
station.
Whenever a ROUT block is initialized (such as when its compound is turned on), it sends an initial value to the FBM and this value is sent by the FBM to the slave device. The initial value used
for the ROUT block is the value that you have configured into the blocks fail-safe value parameter FSOUT.
The ROUT block output initialization is done whether or not fail-safe is configured for the block;
the default value for the fail-safe value for the ROUT block is zero. If you care about what value is
written to the ROUT block when it is initialized, you must configure the fail-safe value for the
block, even if the fail-safe option is not used.

Cascade Initialization
Upstream logic in a cascade is initialized by a ROUT block in each of the following cases:
When the DCI block initializes
When the DCI block mode changes from Manual to Auto mode

When control station-to-FBM communication recovers from a failure condition


When the readback value transitions from Bad and/or Out-of-Service status to Good
status
When the Initialization Input (INI_PT), if used, is cleared.

81

B0400FF Rev M

5. Control Block Configuration Information

Fail-Safe Actions
Fail-safe actions are performed in accordance with specific parameters set in ECB200 or ECB202,
and in the ROUT DCI block. In ECB200 or ECB202, the following parameters control fail-safe
actions:
FSENAB Fail-Safe Enable, when true, activates the FSDLAY timer to detect a communication failure from the control station, and start fail-safe action in the FBM. The
FSENAB setting is downloaded to the HART FBMs when the FBM is rebooted. It is
used by the HART FBMs to enable/disable the logic to assert fail-safe action when a
loss of control station communication is detected, or when a control station fail-safe
request is received.
FSDLAY Fail-Safe Delay is a communications fail timer. When enabled by
FSENAB, it specifies the length of time (in units of 0.01 seconds) that the FBM can
be without communication from the control station before taking fail-safe action. If
the Fail-Safe On Commfail bit is set in the FSOPTN parameter of the output control
block (ROUT), the FBM sets the Initialize Fail-safe bit in the status of the OUT
parameter of the associated AO function block. When this value is next received by
the connected device, the device asserts fail-safe and drives its output to the fail-safe
value. For example, the default value of 1000 in FSDLAY causes the FBM to wait 10
seconds between read/write messages before going to the Fail-safe state (provided
FSENAB is configured true).
In the ROUT DCI block, the following parameters control fail-safe actions:

FSOPTN Fail-safe Option is a configurable option that specifies the fail-safe conditions and action to be taken in the FBM for an output point in a ROUT block:
Assert fail-safe if input/measurement error.
Set/clear fail-safe when SETFS input is set/cleared.
Assert fail-safe if control station-to-FBM communication failure was detected by
the FBM.
Combinations of these conditions for fail-safe can be specified.
SETFS Set Fail-safe Request is a settable Boolean parameter that requests fail-safe
action to be set/reset by the FBM and/or field device for the specific output value of
the ROUT block.

FSOUT Fail-safe Real Output (ROUT block) specifies the real fail-safe value that is
to be used by the external device when any condition specified in FSOPTN exists.
A Failsafe Enable (FSENAB) option may be configured by the user in an ECB200 or ECB202.
This option is downloaded to the HART FBM when it is rebooted or when configuration of the
ECB200 or ECB202 is changed. FSENAB is used by the HART FBM to enable/disable logic to
assert fail-safe action on the HART channels automatically when a loss of control station communications is detected. It is also used by the HART FBMs to override all explicit fail-safe request
actions from the control station for each DCI output connection.
If the FSENAB option is set, the Fail-safe Delay (FSDLAY) value configured in the ECB200 or
ECB202 is used to set the fail-safe timer in the HART FBM. The fail-safe timer counts down and
is reset to the FSDLAY value whenever a DCI message is received. If the fail-safe timer expires, the
HART FBM stops communication on the channels, and sets the Fail-safe Active (FSA) status in
the associated DCI output connection records.

82

5. Control Block Configuration Information

B0400FF Rev M

When communication with the control station is restored, the fail-safe timer is automatically reset
to full value by the first DCI message received, and the HART FBM clears the FSA status in the
associated DCI output connection records.
Fail-safe options (FSOPTN) can also be configured in each DCI output block. These options are
downloaded into the HART FBM when the DCI output connection is established. If any of the
fail-safe options are set, the HART FBM writes the associated fail-safe value into the DCI connection record.
Fail-safe action can also be triggered by either of two events in a DCI output block:
The Fail-safe Request parameter (SETFS) is toggled or, if the error option (EROPT) is
configured
The status of the primary input in the block goes bad (or becomes good).
When either of these events occurs, a Write_Data message is sent to HART FBMs with the Failsafe Request bit set (or cleared) in the message. If FSENAB is set, and if the Fail-safe Upon CP
Request option is set in the DCI output connection, the HART FBM sets (or clears) the FSA
status in the DCI connection record. If the Fail-safe Request is set, the HART FBM writes the
fail-safe value stored in the DCI connection record to the HART field device.
Refer to the DCI block descriptions in Integrated Control Block Descriptions (B0193AX) for additional details.

DCI Status Transformations


Table 5-14 shows the DCI parameter status (for example, the value record status for MEAS in a
RIN block), as implemented by the Foxboro control station. The bit numbers in Table 5-14 represent the bit numbers in the parameter status word, not the Block Status bit of the DCI or other
control blocks. User-written software applications can access any of the 16 bits of the value record
status word. Refer to Control Processor 270 (CP270) and Field Control Processor 280 (CP280) Integrated Control Software Concepts (B0700AG).
Table 5-14. DCI Parameter Status

DCI Parameter Status1


Out-of-Service (OOS)
(Bit 11)
Bad Value (BAD)
(Bit 8)
Error (ERR)
(Bit 15)
Limited High (LHI)
(Bit 13)
Limited Low (LLO)
(Bit 14)
Fail-safe (FS)
(Bit 4)
1.

Meaning
FBM to HART device communication failure, HART device disabled, device/point connection is unresolved, compound is off, or
control station to FBM communication failure
Transmitter/sensor failure, valve/actuator failure, I/O diagnostic
failure, device failure, or control station to FBM communication
failure
Set when the PV is out of limits or the analog output is saturated
Set when the PV is past its high limit.
Set when the PV is past its low limit.
Fail-safe has been asserted by the HART FBM.

Standard Foxboro Evo status bits (used with all blocks).

83

B0400FF Rev M

5. Control Block Configuration Information

Control Schemes Using DCI Blocks


The DCI blocks can be integrated into many different Foxboro Evo control schemes. Examples of
simple cascade and supervisory control configurations using DCI blocks are illustrated in
Figure 5-12 and Figure 5-13.

Parent
ECB200/ECB202
(HART FBM)
Child ECB201
(HART device)

Child ECB201
(HART device)

PARENT

RIN Block
IOM_ID
(1) PNT_NO
MEAS
RIN

PARENT

PIDA Block

MEALM
Block (2)

MEAS
SPT

OUT
BCALCI

MEAS

RIN Block
IOM_ID
(1) PNT_NO
MEAS
RIN

PIDA Block

MEALM
Block (2)
MEAS

MEAS
RSP
BCALCO
OUT
BCALCI
SUP_IN
SUPBCP

Notes:
(1) PNT_NO = Point address of HART device
(2) MEALM blocks are used to perform BAD alarming.
Figure 5-12. Simple Cascade Configuration

84

ROUT Block
IOM_ID
PNT_NO (1)

MEAS OUT
BCALCO

MEALM
Block (2)
MEAS

5. Control Block Configuration Information

B0400FF Rev M

Parent
ECB200/ECB202
(HART FBM)
Child ECB201
(HART device)

Child ECB201
(HART device)

PARENT
RIN Block
IOM_ID
(1) PNT_NO
MEAS
RIN

PIDA Block

MEALM
Block (2)
MEAS

RIN Block
IOM_ID
(1) PNT_NO
MEAS
RIN

PARENT

MEAS
SPT

OUT
BCALCI

PIDA Block

MEALM
Block (2)
MEAS

MEAS
RSP
BCALCO
OUT
BCALCI
SUP_IN
SUPBCO

ROUT Block
IOM_ID
PNT_NO (1)

MEAS OUT
BCALCO
MEALM
Block (2)
MEAS

Supervisory Control
Application
(for example,
Connoisseur MPC)

Solaris/Windows NT
Workstation

Notes:
(1)
(2)

PNT_NO = Point address of HART device


MEALM blocks are used to perform BAD alarming.
Figure 5-13. Supervisory Control Configuration

85

B0400FF Rev M

86

5. Control Block Configuration Information

6. Process Operator Displays


This chapter provides references for information on the process operator displays used with the
Foxboro Evo system (and thus with the HART FBMs and the HART-capable FBM247).
The Foxboro Evo system provides the following types of displays for performance of process control operations:
Group Displays
User-Generated Displays
Block Detail Displays
Compound Detail Displays
Station Displays.
For information on how these displays are used, refer to documentation for the appropriate application:
System Manager (B0750AP)
NOTE

The only system management package that supports the HART-capable FBM247 is
the System Manager.

Control HMI Application User's Guide (B0750AQ).


Process Operations and Displays (B0700BN).

Block Detail Displays


Three ECBs (ECB200, ECB201 and ECB202) relate to HART FBMs, the HART-capable
FBM247s and their associated field devices. The block detail displays for these ECBs are
described in the following subsections.
To access the block detail displays, use the appropriate application select the appropriate compound and then select the ECB200, ECB201 or ECB202:
View the Information Pane in the System Manager as discussed in System Manager
(B0750AP).
Use FoxSelect as discussed in Process Operations and Displays (B0700BN).

87

B0400FF Rev M

6. Process Operator Displays

ECB200 Block Detail Display


ECB200 Information Pane/Faceplate
ECB Description
Compound Name
ECB Name
DEV_ID
FBM Status (line 1)
FBM Status (line 2)
FBM Status (line 3)
FBM Status (line 4)
HWTYPE

SWTYPE

ECB200s description as configured in the DESCRP parameter.


Name of the compound that holds the ECB200.
ECB200s name as configured in the NAME parameter.
Device Identification (the text configured for the ECB200s
DEV_ID parameter).
DCI READY or DCI NOT READY The FBM is ready or not
ready for operation.
FBM FAILED The FBM is inoperable.
FBM OFF-LINE The FBM has been switched off-line using
the SMDH display, or has never been placed on-line.
UNRESOLVED A failure occurred whose source is unknown.
Potential exists for recovery from failure.
Hardware Type is configured based on the type of the associated
FBM.
For FBM214, HWTYPE is 214.
For FBM214b, HWTYPE is 214.
For FBM215, HWTYPE is 215.
For FBM244, HWTYPE is 244.
For FBM247, HWTYPE is 247.
Software Type is configured based on the type of the associated
FBM.
For FBM214, SWTYPE is 214.
For FBM214b, SWTYPE is 214.
For FBM215, SWTYPE is 215.
For FBM244, SWTYPE is 244.
For FBM247, HWTYPE is 247.

ECB200 Primary Data


The ECB200 primary data consists of ECB200 parameters, which are described in Integrated
Control Block Descriptions (B0193AX).
For the FBM247, also refer to Configuring FBM ECB (ECB200) for FBM247 on page 66.

88

6. Process Operator Displays

B0400FF Rev M

ECB202 Block Detail Display


ECB202 Information Pane/Faceplate
ECB Description
Compound Name
ECB Name
DEV_ID
FBM Status (line 1)
FBM Status (line 2)
FBM Status (line 3)
FBM Status (line 4)
HWTYPE

SWTYPE

ECB202s description as configured in the DESCRP parameter.


Name of the compound that holds the ECB202.
ECB202s name as configured in the NAME parameter.
Device Identification (the text configured for the ECB202s
DEV_ID parameter).
DCI READY or DCI NOT READY The FBM is ready or not
ready for operation.
FBM FAILED The FBM is inoperable.
FBM OFF-LINE The FBM has been switched off-line using
the SMDH display, or has never been placed on-line.
UNRESOLVED A failure occurred whose source is unknown.
Potential exists for recovery from failure.
Hardware Type is configured based on the type of the associated
FBM.
For FBM216, HWTYPE is 216.
For FBM216b, HWTYPE is 216.
For FBM218, HWTYPE is 218.
For FBM245, HWTYPE is 245.
Software Type is configured based on the type of the associated
FBM.
For FBM216, SWTYPE is 216.
For FBM216b, SWTYPE is 216.
For FBM218, SWTYPE is 218.
For FBM245, SWTYPE is 245.

ECB202 Primary Data


The ECB202 primary data consists of ECB202 parameters, which are described in Integrated
Control Block Descriptions (B0193AX).

89

B0400FF Rev M

6. Process Operator Displays

ECB201 Block Detail Display


ECB201 Information Pane/Faceplate
ECB Description
Compound Name
ECB Name
DEV_ID
Device Status (line 1)
Device Status (line 2)
Device Status (line 3)
Device Status (line 4)
HWTYPE

SWTYPE

ECB201s description as configured in the DESCRP parameter.


Name of the compound that holds ECB201.
ECB201s name as configured in the NAME parameter.
Device Identification (the text configured for the ECB201s
DEV_ID parameter).
DCI READY or DCI NOT READY The device is ready or not
ready for operation.
DEVICE FAILED The device is inoperable.
DISABLED Communication to the device has been disabled.
UNRESOLVED A failure occurred whose source is unknown.
Potential exists for recovery from failure.
Hardware type (same as for parent ECB200);
For FBM214, HWTYPE is 214.
For FBM214b, HWTYPE is 214.
For FBM215, HWTYPE is 215.
For FBM216, HWTYPE is 216.
For FBM216b, HWTYPE is 216.
For FBM218, HWTYPE is 218.
For FBM244, HWTYPE is 244.
For FBM245, HWTYPE is 245.
For FBM247, HWTYPE is 247.
Software type (same as for parent ECB200);
For FBM214, SWTYPE is 214.
For FBM214b, SWTYPE is 214.
For FBM215, SWTYPE is 215.
For FBM216, SWTYPE is 216.
For FBM216b, SWTYPE is 216.
For FBM218, SWTYPE is 218.
For FBM244, SWTYPE is 244.
For FBM245, SWTYPE is 245.
For FBM247, SWTYPE is 247.

ECB201 Primary Data


The ECB201 primary data consists of ECB201 parameters, which are described in Integrated
Control Block Descriptions (B0193AX).
For the FBM247, also refer to Configuring Device ECB (ECB201) for FBM247 on page 69.

90

6. Process Operator Displays

B0400FF Rev M

ECB201 Extended Status Support


NOTE

The following section describes an enhancement that was added in EEPROM


Version 2.28B and later FBM software, and is not present in earlier versions.
Additional Device Status

The DDIAG1 (Device Diagnostics #1) parameter of ECB201 is a 32-bit packed Boolean output
which reports additional issues using Byte 0, Bit 4 (More status available for HART devices
only).
FBM214/214b/215/216/216b/218/247 monitors the state of this status bit from the device, and
when this bit changes from 0 to 1, the FBM issues the HART Common Practice Command 48 to
the device to read the additional status. The FBM stores the returned data as a 25-byte additional
status value where it can be read by the control processor. While this status bit remains at 1, the
FBM will read this additional status data from the device approximately every ten seconds.
When the status bit changes state from 1 to 0, as observed by the FBM, the additional status is
read once more. After this final reading, the FBM discontinues the read until the status bit transitions to 1 again.
The 25-byte additional status value is accessible with standard DCI input blocks. All twentyfive bytes can be read as a string of hex digits using a STRIN block and specifying STATUS for
the PNT_NO parameter. The bytes are presented by this block least significant to most significant order; for example, 01 02 03 ... 24 25.
Additionally, the individual status bits can be read in groups of 32 bits using the PAKIN block
with PKIOPT set to 3, displayed in most significant to least significant order, as shown below
Bytes
4-1
8-5
12 - 9
16 - 13
20 - 17
24 - 21
25

Configure PKINGP
STATUS1
STATUS2
STATUS3
STATUS4
STATUS5
STATUS6
STATUS7

Example
04 03 02 01
08 07 06 05
12 11 10 09
16 15 14 13
20 19 18 17
24 23 22 21
00 00 00 25

Be aware of the following with regards to the 25-byte additional status value:
Not all devices provide additional status. It is assumed that a device that does not support the Common Practice Command 48 will never set the More status available bit
in ECB201.

A device that does provide additional status may not provide a full 25 bytes of additional status. For this reason, before the FBM issues the first Command 48 following
transition of the More status available bit from 0 to 1, the FBM clears (sets to 0) the
entire 25-byte storage area so that any unused bytes will not contain misleading ones
(1s). The STRIN block will only display the number of bytes actually received from
the device.

91

B0400FF Rev M

6. Process Operator Displays

The PKIOPT parameter of the PAKIN blocks must be set to 3 to avoid swapping of
the bits and bytes. The default setting of this parameter is 1.
The PAKIN block detail display shows the PAKCIN parameter as in the examples
above, but the individual bits are displayed as most significant bit=1 (upper left) and
least significant bit=32 (lower right). This means that the top line displays the bits in
byte 4 and the bottom line displays the bits in byte 1.
Refer to Integrated Control Block Descriptions (B0193AX) for definitions of the additional bits in
the DDIAG1 parameter of ECB201.
Also, for the FBM247, refer to Configuring IIN Block for HART Integer Digital Variables and
Device Status Bits for the FBM247 on page 73 for additional details on reading HART device
status using the IIN, STRIN and PAKIN blocks with the FBM247.
System Alarming

Whenever DDIAG1 Byte 0, Bit 7 (Device Malfunction) is 1, the FBM sets the System Alarm
bit for the device. On the transition from 0 to 1 of the System Alarm bit for a device, a system
warning message is sent to the SMON log and the System key on FoxView software flashes red. In
addition, all I/O blocks connected to a device with this bit set will indicate BAD I/O (Red) and
the data will not be used for control.
While the System Alarm bit for a device is set, the device icon in SMDH will be yellow as a
warning indicator.

92

7. Maintenance
This chapter provides maintenance information for the HART FBMs and the HART-capable
FBM247.
NOTE

In general, maintenance includes periodic inspection and cleaning, checking the


status of LED indicators, and checking for loose cable connections.

! WARNING
To prevent explosion, install and remove cables, wiring, modules and other replaceable components only when the area is known to be nonhazardous.

Overview
The general Foxboro Evo system management philosophy applies to the HART FBMs incorporated into the Foxboro Evo system. Through the System Management Displays, you can receive
status information on the HART FBMs, as well as send change requests to the FBMs.
System management for the HART FBMs is supported on the following system and display management packages:
System Manager - discussed in System Manager (B0750AP)
NOTE

The only system management package that supports the HART-capable FBM247 is
the System Manager.

SMDH - discussed in System Management Displays (B0193JC)


FoxView software - discussed in Process Operations and Displays (B0700BN)
Foxboro Evo Control HMI - discussed in Control HMI Application User's Guide
(B0750AQ).

Operating Status
The operating status of the HART FBMs and the HART-capable FBM247 is reported by the
Foxboro Evo system using on-screen and printed messages. Refer to the following documents for
information on the reporting of equipment operating status and errors:

System Manager (B0750AP)


System Management Displays (B0193JC)
Control Core Service V9.x System Error Messages (B0700AF)
Process Operations and Displays (B0700BN).
93

B0400FF Rev M

7. Maintenance

System Manager Displays and System Management


Displays
Display Applications
Operators will view data regarding their control equipment using display applications such as the
System Manager or the System Management Display Handler (SMDH).
The System Manager allows you to access equipment information and status for a Foxboro Evo
system, including the HART FBMs, HART slave devices, FBM247 devices/signals and their associated Control Processor. This display reflects the systems current operating status and provide a
valuable maintenance aid by allowing you to observe the current operating status of the various
system elements and intervene in system operations. For information on navigating through the
System Manager screens, see System Manager (B0750AP).
For information on viewing the HART FBM and device runtime information in the Foxboro Evo
Control HMI, refer to Control HMI Application User's Guide (B0750AQ).
Figure 7-1 shows an example System Manager display page for a HART device which contains
operational status, hardware and software information.

Figure 7-1. System Manager - General Tab (Equipment Information Display) for HART Device

94

7. Maintenance

B0400FF Rev M

In the Foxboro Evo system, the System Management Display Handler (SMDH) obtains current
and historical information about the system, and displays this information in System Management displays. With regard to HART FBMs and the associated HART slave devices, the SMDH
provides the following displays:
A Fieldbus1 level display (PIO Network), which shows the control station, FCM(s),
and any other Fieldbus devices
A module Fieldbus1 level display (PIO Sub-Network), which shows the selected FCM
and associated FBMs
A device level display (I/O Display), which shows the associated HART devices for
the selected FBM
Detailed equipment information (EQUIP INFO) and equipment change (EQUIP
CHG) displays for each HART FBM and the associated HART devices.
For detailed information on the first three items above (Fieldbus level display, module Fieldbus
level display, and I/O device display), refer to System Management Displays (B0193JC).

1. The

term Fieldbus used here refers to the Foxboro Evo 10 Mbps Ethernet trunk Fieldbus and/or
the 2 Mbps module Fieldbus.
95

B0400FF Rev M

7. Maintenance

HART FBM214/214b/215 Equipment Status and Information


Display
Table 7-1 describes the available Equipment Information fields provided for FBM214/214b/215
in the order that they appear on the System Manager and SMDH display pages.
Table 7-1. FBM214/215 Equipment Status and Information Display Fields

Field
NAME
RUN MODE

FAIL ACK STATE

DB DOWNLOAD
STATE
LAST CABLE ACCESS

COMPOUND NAME
BLOCK NAME
HARDWARE TYPE
SOFTWARE TYPE
HARDWARE PART
HARDWARE REV
SOFTWARE REV
EEPROM REV
SERIAL NUMBER
MANUF DATE
LOGICAL ADDR
TYPE
DEVICE STATE

96

Description
User-supplied ECB name.
On-line or Off-line (default) is displayed. Set the RUN MODE using the
GO ON-LINE and GO OFF-LINE options in the Equipment Change
Display. If the FBM automatically goes off-line:
Check hardware
Check related fields, such as FBM STATUS
Download (restart) the FBM.
Acknowledged (default) or Not Acknowledged is displayed. If the
DEVICE STATE value changes from Not Failed to Failed, the FAIL ACK
STATE value changes to Not Acknowledged to indicate this transition,
and remains until the FBM failure is acknowledged by the user.
Not applicable to HART FBMs.
Both Cables OK, Cable A Not OK, Cable B Not OK, or Both Cables
Not OK is displayed. This field indicates whether transmissions were
successfully sent the last time either Bus A or B was used. A Not OK
status indicates a PIO bus send failure. To resolve this:
Check the PIO bus.
Switch to the other cable if the bus is bad.
Compound name containing the FBM ECB200.
Block name for the FBM ECB200.
Configured value for HWTYPE parameter in ECB200.
Configured value for SWTYPE parameter in ECB200.
Hardware part number related to this FBM.
Hardware release level of this FBM hardware type.
Release level of this FBM software.
Firmware release for this FBM.
Serial number assigned to this FBM hardware module.
Date of manufacture for this FBM. For MANUF DATE 180133, the
factory number is 18, the year is 01, and the week is 33.
Logical Address is the number of the FBM, 1 through 120. FBMs are
typically numbered as they appear in the display (left to right).
Predefined FBM type from ECB200.
Failed or Not Failed (default) is displayed. This field changes to Failed if
a fatal hardware fault (including a possible communications cable
break) causes the FBM to fail.

7. Maintenance

B0400FF Rev M

Table 7-1. FBM214/215 Equipment Status and Information Display Fields (Continued)

Field
ALARMING STATE

WARNING CONDITION
DEVICE ATT
FAIL DEV ATT
FAIL DEV ACK

POWER 1
POWER 2
DIAG STATUS 1

DIAG STATUS 2

Description
Alarming State indicates whether alarming is Enabled or Inhibited for
the device. When alarming is inhibited, the System Monitor continues
to indicate overall system and network health (a green SYS BAR) while
equipment is Failed or Off-line.
Yes is displayed if the device has a non-fatal error condition; otherwise,
No is displayed.
Yes is displayed if the FBM has devices attached; otherwise, No is displayed.
Yes is displayed if one or more HART devices connected to the FBM
have failed; otherwise, No is displayed.
Acknowledged (default) or Not Acknowledged is displayed. If any of
the devices attached to the FBM fail and become unacknowledged, Not
Acknowledged is displayed.
OK or Failed indicates the state of primary power to FBM.
OK or Failed indicates the state of backup power to FBM.
Diagnostic Status 1 is a hexadecimal value related to the FBM status.
Typically this value is 4, indicating a non-fail-safe condition typical
status for an FBM with a green status LED on.
If the FBM is operating normally, this field can be safely ignored. For
resolution of the FBM hardware and software errors indicated by this
diagnostic status field, call Global Product Support (GPS).
Diagnostic Status 2 is a hexadecimal value indicating the FBM startup
condition. If the value is 0, there is no history of the last start condition
due to lack of communications. Hexadecimal values and the related
conditions are as follows:
Value Condition
1 - Cold start (power up)
2 - Power fail recovery
4 - Watchdog timer failure
8 - Warm reset (equipment change download)

DIAG STATUS 3

If the FBM is operating normally, this field can be safely ignored. For
resolution of the FBM hardware and software errors indicated by this
diagnostic status field, call the Global Product Support.
Diagnostic Status 3 is a hexadecimal value relating to the previous software or hardware error for the selected FBM.
If the FBM is operating normally, this field can be safely ignored. For
resolution of the FBM hardware and software errors indicated by this
diagnostic status field, call the Global Product Support.

97

B0400FF Rev M

7. Maintenance

Table 7-1. FBM214/215 Equipment Status and Information Display Fields (Continued)

Field
DIAG STATUS 4

Description
Diagnostic Status 4 is a hexadecimal value relating to the current software or hardware error for the selected FBM. Normally, this value is 0
(no error). Other values are fatal errors; the FBM is not operational.
Typical values and their meaning are as follows:
Value Condition
0 - No error
15 - Hardware type mismatch (FBM installed in the wrong slot)
16 - Software type mismatch (ECB configuration error)

PRIM CMD STATE

IOM CMD STATUS

Corrective actions include:


Installing the FBM in the correct slot
Correcting ECB200 and ECB201 configuration errors
Restarting the FBM using the DOWNLOAD function on the
Equipment Change display
Reloading the FBM software using the EEPROM UPDATE
function.
If the above actions do not correct the problem, call the Global Product
Support.
Primary Command Status is a value related to the status of communication between the primary FBM and the HART FBM. Typically, this
value is 0 or 1, where 1 indicates that a successful retry took place and
communication has been restored to normal. Primary Command Status
can have the following values:
Value Condition
0 - Normal, no error
1 - Success with retry (this condition is very rare)
2 - FCM timed out FBM
3 - CP timed out FCM
> 3 - Link level protocol error (this is very rare and transient)
IOM Command Status is a hexadecimal value associated with the
return status included in the header of every response from the HART
FBM to the primary FBM. Typically, the hexadecimal value is 0, indicating the command was understood and action was taken.
Value Condition
1 - Command not understood.
2 - Command understood, but unable to take action.
4 - Invalid argument.

98

7. Maintenance

B0400FF Rev M

Table 7-1. FBM214/215 Equipment Status and Information Display Fields (Continued)

Field
IOM STATUS

EXTENSION TYPE
FILE REVISION
FBM TYPE
VERSION NUMBER
FILE ID
PORT1 FAIL STATE
PORT2 FAIL STATE
FBM STATUS

BUS ID
PORT1 STATUS
PORT2 STATUS

Description
IOM Status is a hexadecimal value related to the current FBM status.
Typically this value is 4, indicating the instructions are valid.
Value Condition
1 - FBM status has changed requests CP to poll for extended status.
2 - Diagnostic Register is nonzero. This indicates a fatal error. The
FBM does not start if this value is set.
4 - Non-fail-safe condition. This is the typical status for a HART
FBM (green status LED on). This value is reset only if the output mode
of operation is fail-safe.
40 - FBM is off-line. In off-line mode, the software control is ROMbased. In on-line mode, the software is RAM-based.
80 - Initialization is taking place all channel and I/O data is initializing. Also, indicates that the FBM has a delayed response message ready.
Not applicable to HART FBMs.
Not applicable to HART FBMs.
Type of FBM supported by ECB200.
Version number of the FBM.
Not applicable to HART FBMs.
Not applicable to HART FBMs.
Not applicable to HART FBMs.
The following may be displayed to define the FBM status:
HART FBM FBM On-Line
DCI Not Ready FBM Off-Line
DCI Ready Unresolved Connection
FBM Failed System Alarm
Not applicable to HART FBMs.
Not applicable to HART FBMs.
Not applicable to HART FBMs.

HART FBM216/216b/218 Equipment Status and Information


Display
Table 7-2 describes the available text fields in the Equipment Status and Information display
pages for FBM216/216b/218 in the order that they appear on the System Manager and SMDH
display pages.
Table 7-2. FBM216/216b/218 Equipment Status and Information Display Fields

Field
NAME
MAIN SLOT NO

Description
User-supplied ECB name.
Baseplate slot number where the main FBM is installed.

99

B0400FF Rev M

7. Maintenance

Table 7-2. FBM216/216b/218 Equipment Status and Information Display Fields (Continued)

Field
MAIN STATE

TYPE
FAIL ACK STATE

FAIL DEV ACK


ALARMING STATE

FAIL DEV ATT


PRIM CMD STATE

IOM CMD STATUS

MAIN LOGICAL
ADDR

100

Description
Main State indicates the main FBM operational state:
Main Downloading Main Off-Line
Main EE Updating Master
Main Failed Tracker
Predefined FBM type from ECB202.
Acknowledged (default) or Not Acknowledged is displayed. If the
DEVICE STATE value changes from Not Failed to Failed, the FAIL ACK
STATE value changes to Not Acknowledged to indicate this transition,
and remains until the FBM failure is acknowledged by the user.
Yes (default) or No is displayed. If any of the devices attached to the
FBM fail and become unacknowledged, No is displayed.
Alarming State indicates whether alarming is Enabled or Inhibited for
the device. When alarming is inhibited, the System Monitor continues
to indicate overall system and network health (a green SYS BAR) while
equipment is Failed or Off-line.
Yes is displayed if one or more HART devices connected to the FBM
has failed; otherwise, No is displayed.
Primary Command Status is a value related to the status of communication between the primary FBM and the HART FBM. Typically, this
value is 0 or 1, where 1 indicates that a successful retry took place and
communication has been restored to normal. Primary Command Status
can have the following values:
Value Condition
0 - Normal, no error
1 - Success with retry (this condition is very rare)
2 - FCM timed out FBM
3 - CP timed out FCM
> 3 - Link level protocol error (this is very rare and transient)
IOM Command Status is a hexadecimal value associated with the
return status included in the header of every response from the HART
FBM to the primary FBM. Typically, the hexadecimal value is 0, indicating the command was understood and action was taken.
Value Condition
1 - Command not understood.
2 - Command understood, but unable to take action.
4 - Invalid argument.
Logical Address is the number of the main FBM, 1 through 120. FBMs
are typically numbered as they appear in the display (left to right).

7. Maintenance

B0400FF Rev M

Table 7-2. FBM216/216b/218 Equipment Status and Information Display Fields (Continued)

Field
FBM DIAG STAT 1

FBM DIAG STAT 3

MAIN HDWR PART


NO
MAIN HARDWARE
REV
MAIN EEPROM REV
MAIN SERIAL NUMBER
BKUP SLOT NO
BACKUP STATE

ACT CABLE ACCESS

WARNING CONDITION
COMPOUND NAME
BLOCK NAME
HARDWARE TYPE
SOFTWARE TYPE
POWER 1
POWER 2

Description
Diagnostic Status 1 is a hexadecimal value related to the FBM status.
Typically this value is 4, indicating a non-fail-safe condition typical
status for an FBM with a green status LED on.
If the FBM is operating normally, this field can be safely ignored. For
resolution of the FBM hardware and software errors indicated by this
diagnostic status field, call the Global Product Support.
Diagnostic Status 3 is a hexadecimal value relating to the previous software or hardware error for the selected FBM.
If the FBM is operating normally, this field can be safely ignored. For
resolution of the FBM hardware and software errors indicated by this
diagnostic status field, call the Global Product Support.
Hardware part number related to the main FBM.
Hardware release level of the main FBM.
Firmware release for the main FBM.
Serial number assigned to the main FBM.
Baseplate slot number where the backup FBM is installed.
Backup State indicates the main FBM operational state:
Bkup Downloading Bkup Off-Line
Bkup EE Updating Master
Bkup Failed Tracker
Both Cables OK, Cable A Not OK, Cable B Not OK, or Both Cables
Not OK is displayed. This field indicates whether transmissions were
successfully sent the last time either Bus A or B was used. A Not OK
status indicates a PIO bus send failure. To resolve this:
Check the PIO bus.
Switch to the other cable if the bus is bad.
Yes is displayed if the device has a non-fatal error condition; otherwise,
No is displayed.
Compound name containing the FBM ECB202.
Block name for the FBM ECB202.
Configured value for HWTYPE parameter in ECB202.
Configured value for SWTYPE parameter in ECB202.
OK or Failed indicates the state of primary power to FBM.
OK or Failed indicates the state of backup power to FBM.

101

B0400FF Rev M

7. Maintenance

Table 7-2. FBM216/216b/218 Equipment Status and Information Display Fields (Continued)

Field
FBM DIAG STAT 2

Description
Diagnostic Status 2 is a hexadecimal value indicating the FBM startup
condition. If the value is 0, there is no history of the last start condition
due to lack of communications. Hexadecimal values and the related
conditions are as follows:
Value Condition
1 - Cold start (power up)
2 - Power fail recovery
4 - Watchdog timer failure
8 - Warm reset (equipment change download)

FBM DIAG STAT 4

If the FBM is operating normally, this field can be safely ignored. For
resolution of the FBM hardware and software errors indicated by this
diagnostic status field, call the Global Product Support.
Diagnostic Status 4 is a hexadecimal value relating to the current software or hardware error for the selected FBM. Normally, this value is 0
(no error). Other values are fatal errors; the FBM is not operational.
Typical values and their meaning are as follows:
Value Condition
0 - No error
15 - Hardware type mismatch (FBM installed in the wrong slot)
16 - Software type mismatch (ECB configuration error)

BKUP HDWR PART


NO
BKUP HARDWARE
REV
BKUP EEPROM REV
BKUP SERIAL NUMBER
MAIN MANUF DATE
MAIN SOFTWARE
REV
102

Corrective actions include:


Installing the FBM in the correct slot
Correcting ECB200 and ECB201 configuration errors
Restarting the FBM using the DOWNLOAD function on the
Equipment Change display
Reloading the FBM software using the EEPROM UPDATE
function.
If the above actions do not correct the problem, call the Global Product
Support.
Hardware part number related to the backup FBM.
Hardware release level of the backup FBM.
Firmware release for the backup FBM.
Serial number assigned to the backup FBM.
Date of manufacture for this FBM. For MAIN MANUF DATE 180151,
the factory number is 18, the year is 01, and the week is 51.
Release level of the main FBM software.

7. Maintenance

B0400FF Rev M

Table 7-2. FBM216/216b/218 Equipment Status and Information Display Fields (Continued)

Field
MAIN FBM TYPE
MAIN VER NO
FILE ID
FILE REVISION
FBM STATUS

BKUP MANUF DATE


BKUP SOFTWARE
REV
MAIN STATUS

BKUP STATUS

1.

Description
Type of main FBM supported by ECB202.
Version number of the main FBM.
Not applicable to HART FBMs.
Not applicable to HART FBMs.
The following may be displayed to define the FBM status:
HART FBM FBM On-Line
DCI Not Ready FBM Off-Line
DCI Ready Unresolved Connection
FBM Failed System Alarm
Date of manufacture for this FBM. For BKUP MANUF DATE 180133,
the factory number is 18, the year is 01, and the week is 33.
Release level of the backup FBM software.
Main Status indicates the operational status of the main FBM:
Not Operational HART Comm Fault1
Off-line Slot Conflict
Master Power 1 Fault
Tracker Power 2 Fault
HDLC Fault Fatal Error Flash
Interlink Fault Non Spec Fatal
A/D Converter Fault Non Spec NonFatal
D/A Converter Fault
Backup Status indicates the operational status of the backup FBM:
Not Operational HART Comm Fault1
Off-line Slot Conflict
Master Power 1 Fault
Tracker Power 2 Fault
HDLC Fault Fatal Error Flash
Interlink Fault Non Spec Fatal
A/D Converter Fault Non Spec NonFatal
D/A Converter Fault

The HART COMM Fault text field is displayed if the FBM is unable to communicate with a
HART device on any of the eight channels, even if this is due to the lack of an electrical connection
to the device.

103

B0400FF Rev M

7. Maintenance

HART-Capable FBM247 Equipment Status and Information


Display
Table 7-3 describes the available Equipment Information fields provided for FBM247 in the
order that they appear on the System Manager display pages.

Figure 7-2. FBM247 System Manager Display - Part 1

104

7. Maintenance

B0400FF Rev M

Figure 7-3. FBM247 System Manager Display - Part 2

Table 7-3. FBM247 Equipment Status and Information Display Fields

Field
Name
Type
Run Mode

Device State

Devices Attached
Failed Devices Attached
Failed Acknowledged
State

Description
User-supplied ECB name.
Set to FBM247.
On-line or Off-line (default) is displayed. Set the RUN MODE using the
GO ON-LINE and GO OFF-LINE options in the Equipment Change
Display actions (right-click the FBM). If the FBM automatically goes
off-line:
Check hardware
Check related fields, such as FBM STATUS
Download (restart) the FBM.
Failed or Not Failed (default) is displayed. This field changes to Failed if
a fatal hardware fault (including a possible communications cable
break) causes the FBM to fail.
Yes is displayed if the FBM has devices attached; otherwise, No is displayed.
Yes is displayed if one or more HART devices connected to the FBM
have failed; otherwise, No is displayed.
Acknowledged (default) or Not Acknowledged is displayed. If the
DEVICE STATE value changes from Not Failed to Failed, the FAIL ACK
STATE value changes to Not Acknowledged to indicate this transition,
and remains until the FBM failure is acknowledged by the user.

105

B0400FF Rev M

7. Maintenance

Table 7-3. FBM247 Equipment Status and Information Display Fields (Continued)

Field
EEPROM Update State

Description

Yes is displayed if the module is currently executing an EEPROM


update; otherwise, No is displayed.
If this operation does not complete, take the FBM OFF-LINE and then
return it back ON-LINE followed by a DOWNLOAD operation. This
cancels the EEPROM UPDATE operation.
Failed Devices Acknowl- Acknowledged (default) or Not Acknowledged is displayed. If any of
edged
the devices attached to the FBM fail and become unacknowledged, Not
Acknowledged is displayed.
Last Cable Access
Both Cables OK, Cable A Not OK, Cable B Not OK, or Both Cables
Not OK is displayed. This field indicates whether transmissions were
successfully sent the last time either Bus A or B was used. A Not OK
status indicates a PIO bus send failure. To resolve this:
Check the PIO bus.
Switch to the other cable if the bus is bad.
Alarm Enabled State
Alarming State indicates whether alarming is Enabled or Inhibited for
the device.
Warning Conditions
Yes is displayed if the device has a non-fatal error condition; otherwise,
Exist
No is displayed.
Compound:Block
Compound and block name containing the FBM ECB200.
EEPROM Revision
Firmware release for this FBM.
FBM Type
Predefined FBM type from ECB200.
Hardware Part
Hardware part number related to this FBM.
Hardware Revision
Hardware release level of this FBM hardware type.
Hardware Type
Configured value for HWTYPE parameter in ECB200 - FBM247.
Manufacture Date
Date of manufacture for this FBM. For MANUF DATE 180133, the
factory number is 18, the year is 01, and the week is 33.
Serial Number
Serial number assigned to this FBM hardware module.
Software Revision
Release level of this FBM software.
Software Type
Configured value for SWTYPE parameter in ECB200 - FBM247.
Power 1
OK or Failed indicates the state of primary power to FBM.
Power 2
OK or Failed indicates the state of backup power to FBM.
Version Number
Version number of the FBM.
FBM Status
The following may be displayed to define the FBM status:
DCI Ready/DCI Not Ready
FBM Failed
FBM On-line/FBM Off-line
DB Download Failed
DB Download Active
Unresolved Connection
System Alarm
System Message

106

7. Maintenance

B0400FF Rev M

Table 7-3. FBM247 Equipment Status and Information Display Fields (Continued)

Field

Description

FBM Diagnostic Status

The following may be displayed to define the FBM status:


HDLC Fault
Not used
A/D Converter Fault
D/A Converter Fault
HART Comm Fault
Analog/Pulse integration period
(Information is per channel) Indicates the status of the SYSCFG bit
map - see Configuring FBM ECB (ECB200) for FBM247 on
page 66.
HART Enabled: Indicates which channel(s) that have been enabled for
HART communication or Not Configured if no channel is configured.
Input Channel: Indicates which of the HART Enabled channels that
are configured as an input channels.
Output Channel: Indicates which of the HART Enabled channels that
are configured as an output channels.
Loop powered: Indicates which of the HART Enabled channels that are
configured to supply loop power.
(Information is per channel) Indicates the status of the SYSCFG bit
map - see Configuring FBM ECB (ECB200) for FBM247 on
page 66.
HART Enabled: Indicates which channel(s) that have been enabled for
HART communication or Not Configured if no channel is configured.
Input Channel: Indicates which of the HART Enabled channels that
are configured as an input channels.
Output Channel: Indicates which of the HART Enabled channels that
are configured as an output channels.
Loop powered: Indicates which of the HART Enabled channels that are
configured to supply loop power.
(Information is per channel) Indicates the status of the SYSCFG bit
map - see Configuring FBM ECB (ECB200) for FBM247 on
page 66.
HART Enabled: Indicates which channel(s) that have been enabled for
HART communication or Not Configured if no channel is configured.
Input Channel: Indicates which of the HART Enabled channels that
are configured as an input channels.
Output Channel: Indicates which of the HART Enabled channels that
are configured as an output channels.
Loop powered: Indicates which of the HART Enabled channels that are
configured to supply loop power.

Integration Period
HART Enabled

Input Channel

Output Channel

107

B0400FF Rev M

7. Maintenance

Table 7-3. FBM247 Equipment Status and Information Display Fields (Continued)

Field
Loop Powered

Bus ID
Log Count
(Diag Status 3)

PIO Bus Logical


Address
Slot Number
Primary Cmd State

IOM Cmd Status

108

Description
(Information is per channel) Indicates the status of the SYSCFG bit
map - see Configuring FBM ECB (ECB200) for FBM247 on
page 66.
HART Enabled: Indicates which channel(s) that have been enabled for
HART communication or Not Configured if no channel is configured.
Input Channel: Indicates which of the HART Enabled channels that
are configured as an input channels.
Output Channel: Indicates which of the HART Enabled channels that
are configured as an output channels.
Loop powered: Indicates which of the HART Enabled channels that are
configured to supply loop power.
Module ID of the FCM that connects the FBM247 to a ZCP270.
Not used if the FBM is attached to an FCP270 or FCP280.
Diagnostic Status 3 is a hexadecimal value relating to the previous software or hardware error for the selected FBM.
If the FBM is operating normally, this field can be safely ignored. For
resolution of the FBM hardware and software errors indicated by this
diagnostic status field, call the Global Product Support.
Logical Address is the number of the FBM, 1 through 120. FBMs are
typically numbered as they appear in the display (left to right).
Physical address of the FBM on the baseplate chain.
Primary Command Status is a value related to the status of communication between the primary FBM and the HART FBM. Typically, this
value is 0 or 1, where 1 indicates that a successful retry took place and
communication has been restored to normal. Primary Command Status
can have the following values:
Value Condition
0 - Normal, no error
1 - Success with retry (this condition is very rare)
2 - FCM timed out FBM
3 - CP timed out FCM
> 3 - Link level protocol error (this is very rare and transient)
IOM Command Status is a hexadecimal value associated with the
return status included in the header of every response from the HART
FBM to the primary FBM. Typically, the hexadecimal value is 0, indicating the command was understood and action was taken.

7. Maintenance

B0400FF Rev M

Table 7-3. FBM247 Equipment Status and Information Display Fields (Continued)

Field
IOM Status

Power Status
(Diag Status 1)

Description
IOM Status is a hexadecimal value related to the current FBM status.
Typically this value is 4, indicating the instructions are valid.
Value Condition
Status Change - FBM status has changed requests CP to poll for
extended status.
Error - Diagnostic Register is nonzero. This indicates a fatal error.
The FBM does not start if this value is set.
Not failsafe (default) - Non-fail-safe condition. This is the typical status for a HART FBM (green status LED on). This value is reset only if
the output mode of operation is fail-safe.
Power fail restart - Power fail restart.
SOE Data Available - SOE Data is available.
Out of Service - FBM is out of service.
Off Line - FBM is off-line. In off-line mode, the software control is
ROM-based. In on-line mode, the software is RAM-based.
Poll request - Poll request is occurring.
Diagnostic Status 1 is a hexadecimal value related to the FBM status.
Value Condition
0x00 - Non-fail-safe condition typical status for an FBM with a
green status LED on
0x01 - Primary power supply (1) is missing.
0x01 - Secondary power supply (2) is missing.

Startup Status
(Diag Status 2)

If the FBM is operating normally, this field can be safely ignored. For
resolution of the FBM hardware and software errors indicated by this
diagnostic status field, call IOM Global Product Support (GPS).
Diagnostic Status 2 is a hexadecimal value indicating the FBM startup
condition. If the value is 0, there is no history of the last start condition
due to lack of communications. Hexadecimal values and the related
conditions are as follows:
Value Condition
Cold Start - Power up
Cold Reset - Power fail recovery
Watchdog Failure - Watchdog timer failure
Warm Start - Warm reset (equipment change download)
Fatal Error Flashed - Fatal error has occurred.
If the FBM is operating normally, this field can be safely ignored. For
resolution of the FBM hardware and software errors indicated by this
diagnostic status field, call the Global Product Support.

109

B0400FF Rev M

7. Maintenance

Table 7-3. FBM247 Equipment Status and Information Display Fields (Continued)

Field
FBM Runtime Status
(Diag Status 4)

Description
Diagnostic Status 4 is a hexadecimal value relating to the current software or hardware error for the selected FBM. Normally, this value is 0
(no error). Other values are fatal errors; the FBM is not operational.
Typical values and their meaning are as follows:
Value Conditions
OK
Config Table Invalid
Fatal Babble
Secure Write Failed
Clock Overrun
AI Overrun
HW Type Mismatch
SW Type Mismatch
RAM Checksum Fail
Illegal Interrupt
Pulse Input Overrun
FPGA Failure
EEPROM UPDATE Fail
Bad RAM Stack Pointer
Bad ROM Stack Pointer
Flashed Error
Main IO Status Error
Max IO Errors Exceeded
EEPROM Checksum Fail
Mfg Data Checksum Fail
Mfg Ext Checksum Fail
EEPROM Update In Progress
Corrective actions include:
Installing the FBM in the correct slot
Correcting ECB200 and ECB201 configuration errors
Restarting the FBM using the DOWNLOAD function on the
Equipment Change display
Reloading the FBM software using the EEPROM UPDATE
function.
If the above actions do not correct the problem, call the Global Product
Support.

110

7. Maintenance

B0400FF Rev M

FBM214/214b/215/244 and FBM247 Equipment Change Display


The actions that are active for the Equipment Change display for the FBM214/214b/215/244 in
the System Manager and SMDH are described in Table 7-4. These are also available for the
FBM247 in the System Manager.
Table 7-4. FBM214/214b/215/244/247 Equipment Change Actions

Action
GO ON-LINE
GO OFF-LINE
DOWNLOAD
EEPROM
UPDATE

Description
Connects the FBM to the Foxboro control station, thus enabling
communication.
Disconnects the FBM from the Foxboro control station, thus disabling
communication.
Restarts the FBM logic. This action does not download the FBM image.
Use this action to update the firmware in an FBM with updated
EEPROM Foxboro software. You should use this action only with an
authorized and distributed official Foxboro release.
! CAUTION
Do not attempt to use or power down the FBM while the
EEPROM is being updated.

ENABLE
DEVICE
ALARMING
INHIBIT
DEVICE
ALARMING

To update firmware in an FBM with updated EEPROM software, click


EEPROM UPDATE on the Equipment Change display. The FBM becomes
inoperable. The update takes less than one minute. When the update is
complete, the FBM is placed on-line. The system displays a message in the
message line indicating whether the update was a success or failure.
Allows device alarms to propagate upward in the Foxboro system.

Inhibits device alarms from propagating upward in the Foxboro Evo system.

Placing the FBM214/214b/215/244 and FBM247 On-Line


After you have installed the equipment, configured the HART devices and ECBs, you place the
FBM214/214b/215/244 or FBM247 on-line (see Chapter 2 Quick-Start Example).
To place the FBM on-line:
1. If you are using the System Manager, open the System Manager, and select the FBM
in the left-hand pane.
2. Either:

Right-click the FBM to open its context menu. -OR From the Actions menu, open the Equipment Change submenu.
3. Click Go On-line.
More information is available in System Manager (B0750AP).
111

B0400FF Rev M

7. Maintenance

-OR1. Access the System Management displays. For detailed information, refer to System
Management Displays (B0193JC).
2. On the PIO SUB NETWORK display, click the FBM and then click EQUIP CHG.
3. On the EQUIPMENT CHANGE display, click GO ON-LINE.
The FBM is now on-line.

FBM216/216b/218/245 Equipment Change Display


The actions that are active for the Equipment Change display for the FBM216/216b/218/245 in
the System Manager and SMDH are described in Table 7-5.
Table 7-5. FBM216/216b/218/245 Equipment Change Actions

Action
GO ON-LINE
GO OFF-LINE
DOWNLOAD

112

Description
Connects the FBM to the Foxboro control station, thus enabling
communication.
Disconnects the FBM from the Foxboro control station, thus disabling
communication.
Restarts the FBM logic. This action does not download the FBM image.

7. Maintenance

B0400FF Rev M

Table 7-5. FBM216/216b/218/245 Equipment Change Actions (Continued)

Action
EEPROM UPDATE

Description
Use this action to update the firmware in an FBM with updated
EEPROM Foxboro software. You should use this action only with an
authorized and distributed official Foxboro software release.
! CAUTION
Do not attempt to use or power down the FBM while the
EEPROM is being updated.
Following an EEPROM update of one or both FBM216/218 modules,
the updated modules are placed in the state (on-line or off-line) that they
were in prior to the EEPROM update. Other 200 Series FBMs are placed
on-line following an EEPROM update.
To update firmware in a redundant pair of FBMs with updated EEPROM
software, click EEPROM UPDATE on the Equipment Change display, and
then click MAIN, BACKUP, or BOTH.
Updating FBMs Off-Line
When you update the main or backup module, that module becomes
inoperable, is updated, and returns to the off-line state. When you update
both modules, the main module becomes inoperable, is updated, and
returns to the off-line state. Then, the backup module becomes inoperable, is updated, and returns to the off-line state. The update takes less than
one minute for each module. The system displays a message in the message line indicating whether the module update was a success or failure.

ENABLE DEVICE
ALARMING
INHIBIT DEVICE
ALARMING
SWITCH ROLES

Updating FBMs On-Line


When you update the main or backup module, that module becomes
inoperable, is updated, and becomes the Tracker. When you update both
modules, the main module becomes inoperable, is updated and becomes
the Tracker with the backup module as Master. Then, the backup module
becomes inoperable, is updated, and becomes the Tracker with the main
module as Master. The update takes less than one minute for each module.
The system displays a message in the message line indicating whether the
module update was a success or failure.
Allows device alarms to propagate upward in the Foxboro Evo system.
Inhibits device alarms from propagating upward in the Foxboro Evo system.
Switches the Master/Tracker roles of the main and backup modules.

Placing the FBM216/216b/218/245 On-Line


After you have installed the equipment, configured the HART devices and ECBs, you place the
FBM216/216b/218 on-line (see Chapter 2 Quick-Start Example).
113

B0400FF Rev M

7. Maintenance

To place the FBMs on-line:


1. If you are using the System Manager, open the System Manager.
2. In the left-hand pane, select whichever FBM in the redundant pair is off-line.
3. Either:
Right-click this FBM to open its context menu. -OR From the Actions menu, open the Equipment Change submenu.
4. Click Go On-line.
5. Repeat steps 2-4 for the other FBM in the redundant pair, if it is also off-line.
More information is available in System Manager (B0750AP).
-OR1. Access the System Management displays. For detailed information, refer to System
Management Displays (B0193JC).
2. On the PIO SUB NETWORK display, click the FBM and then click EQUIP CHG.
3. On the EQUIPMENT CHANGE display, click GO ON-LINE and then click MAIN.
4. On the EQUIPMENT CHANGE display, click GO ON-LINE and then click BACKUP.
The FBM main and backup modules are now on-line.

114

7. Maintenance

B0400FF Rev M

HART Slave Device Equipment Status and Information Display


Table 7-6 describes the available text fields in the Equipment Status and Information display
pages for HART devices in the order that they appear on the System Manager and SMDH display
pages.
Table 7-6. HART Device Equipment Status and Information Display Fields

Field

Description

NAME
COMMUNICATIONS

User-supplied ECB name.


Indicates the state (Enabled or Disabled) of communications to/from
the HART device.
Acknowledged (default) or Not Acknowledged is displayed. If the
DEVICE STATE value changes from Not Failed to Failed, the FAIL ACK
STATE value changes to Not Acknowledged to indicate this transition,
and remains until the device failure is acknowledged by the user.
Downloading is displayed when the FBM is downloading its application image; otherwise, Not Downloading is displayed.
Yes is displayed if one or more HART devices connected to the FBM
have failed; otherwise, No is displayed.
Compound name containing the FBM ECB201.
Updating is displayed if the EEPROM in the FBM is being updated;
otherwise, Not Updating is displayed.
Configured value for HWTYPE parameter in ECB201.
Primary Status is a value related to the status of communication
between the primary FBM and the HART FBM. Typically, this value is
0 or 1, where 1 indicates that a successful retry took place and communication has been restored to normal. For HART FBM, Primary Status
can have the following values:

FAIL ACK STATE

DB DOWNLOAD
STATE
FAIL DEV ATT
COMPOUND NAME
EE UPDATE STATE
HARDWARE TYPE
PRIMARY STATUS

FBM CMD STATUS

Value Condition
0 - Normal, no error
1 - Success with retry (this condition is very rare)
2 - FCM timed out FBM
3 - CP timed out FCM
> 3 - Link level protocol error (this is very rare and transient)
FBM Command Status is a hexadecimal value associated with the
return status included in the header of every response from the HART
FBM to the primary FBM. Typically, the hexadecimal value is 0, indicating the command was understood and action was taken.
Value Condition
0 - Command understood.
1 - Command not understood.
2 - Command understood, but unable to take action.
4 - Invalid argument.

115

B0400FF Rev M

7. Maintenance

Table 7-6. HART Device Equipment Status and Information Display Fields (Continued)

Field
FBM IOM STATUS

FILE REVISION
DEVICE TYPE
VERSION NUMBER

FILE ID
MANUFACTURER
TYPE
DEVICE STATE

ALARMING STATE

WARNING CONDITION
FAIL DEV ACK

BLOCK NAME
116

Description
FBM IOM Status is a hexadecimal value related to current HART
FBM status. Typically this value is 4, indicating the instructions are
valid.
Value Condition
1 - FBM status has changed requests CP to poll for extended status.
2 - Diagnostic Register is nonzero. This indicates a fatal error. The
FBM does not start if this value is set.
4 - Non-fail-safe condition. This is the typical status for a HART
FBM (green status LED on). This value is reset only if the output mode
of operation is fail-safe.
40 - FBM is off-line. In off-line mode, the software control is ROMbased. In on-line mode, the software is RAM-based.
80 - Initialization is taking place all channel and I/O data is initializing. Also, indicates that the FBM has a delayed response message ready.
Not applicable.
Type of field device represented by the ECB201.
Version information returned by the field device in response to the
HART command Read Unique Identifier. Version Number has four
parts that are separated by semicolons (for example,
005; 001; 013; 016):
Universal Command Major Revision Number implemented by
this device
Device Revision Level
Software Revision Level of this device
Hardware Revision Level of the electronics in this device.
Not applicable.
Manufacturer Identification Code for the field device. Refer to HART
Common Tables Specifications (HFC_SPEC-183).
Field device (DEV 214, 215, 216 or 218) represented by the ECB201.
Failed or Not Failed (default) is displayed. This field changes to Failed if
a device fatal hardware fault (including a possible communications
cable break) causes the device to fail.
Indicates whether alarming is enabled or inhibited for the device. When
alarming is inhibited, the System Monitor continues to indicate overall
system and network health (a green SYS BAR) while equipment is
Failed or Off-line.
Yes is displayed if the device has a non-fatal error condition; otherwise,
No is displayed.
Acknowledged (default) or Not Acknowledged is displayed. If any of
the devices attached to the FBM fail and become unacknowledged, Not
Acknowledged is displayed.
Block name for the FBM ECB201.

7. Maintenance

B0400FF Rev M

Table 7-6. HART Device Equipment Status and Information Display Fields (Continued)

Field

Description

MANUF DATE
SOFTWARE TYPE
FBM DIAG STATUS 2
FBM DIAG STATUS 3
FBM DIAG STATUS 4
BUS ID
PORT NUMBER
MODEL
DEVICE NAME
DEVICE ADDRESS

Field Device date of manufacture.


Configured value for SWTYPE parameter in ECB201.
Not applicable.
Not applicable.
Not applicable.
Bus ID is not applicable for HART FBMs.
Not applicable.
Not applicable.
Name of the field device associated with the ECB201.
Reflects the DVADDR parameter in the associated ECB201. This
parameter is not used by HART FBMs.
Device Options reflects the DVOPTS parameter in the associated
ECB201, which controls the use of HART protocol or standard
4-20 mA communication.
Refer to the footnote on page 58 for a description of the allowed values
of DVOPTS in ECB201.
Not applicable.
Not applicable.

DEVICE OPTIONS

MASTER ADDRESS
IDENTIFICATION
NO
DEVICE STATUS

DEV DIAG STATUS

The following are displayed to define the slave device status:


HART Device Device Disabled
DCI NOT Ready Unresolved Connection
DCI Ready System Alarm
Device Failed
The following are displayed to define the slave device diagnostic status:
Field Device Malfunction Non-Primary Out-of Limits
Configuration Changed Primary Out-of Limits
Cold Start A/D Converter Fault
More Status Available D/A Converter Fault
Primary Output Fixed HART Comm Fault
Primary Output Saturated

117

B0400FF Rev M

7. Maintenance

FBM247 Device Equipment Status and Information Display


The System Manager can display Equipment Information fields for each FBM247 channel (via its
ECB201), as shown in Figure 7-4.

Figure 7-4. ECB201 Equipment Information Fields for a FBM247 Channel

Table 7-7 describes the available Equipment Information fields provided for the FBM247s channels in the order that they appear on the System Manager display pages.
Table 7-7. FBM247 Channel (ECB201) Equipment Status and Information Display Fields

Field
Name
Type
Communications
Device State

Failed Acknowledged
State

Alarm Enabled State

118

Description
User-supplied ECB name.
Set to FBM247.
Run mode status of channel/device; either Enabled or Disabled.
Failed or Not Failed (default) is displayed. This field changes to Failed if
a fatal hardware fault (including a possible communications cable
break) causes the associated channel/device to fail.
Acknowledged (default) or Not Acknowledged is displayed. If the
DEVICE STATE value changes from Not Failed to Failed, the FAIL ACK
STATE value changes to Not Acknowledged to indicate this transition,
and remains until the channel/device failure is acknowledged by the
user.
Alarming State indicates whether alarming is Enabled or Inhibited for
the channel.

7. Maintenance

B0400FF Rev M

Table 7-7. FBM247 Channel (ECB201) Equipment Status and Information Display Fields (Continued)

Field
Warning Conditions
Exist
Compound:Block
Device Name
Device Options
Circuit Type

HART Device

Point Type
HART System Alarm
Option
HART OOS Option

Block Config
Hardware Type
Software Type
Manufacturer
Device Type
Version Number

Fieldbus Type

Description
Yes is displayed if the channel has reported a non-fatal error condition;
otherwise, No is displayed.
Compound and block name containing the FBM ECB200.
The device name for the channel - the value of DVNAME; see Configuring Device ECB (ECB201) for FBM247 on page 69.
The device options for the channel - the value of DVOPTS; see Configuring Device ECB (ECB201) for FBM247 on page 69.
Voltage, Current, or Disabled.
This is determined by the DVOPTS parameter; see Configuring
Device ECB (ECB201) for FBM247 on page 69.
Yes is displayed if the channel is supporting a HART device; otherwise,
No is displayed.
This is determined by the DVOPTS parameter; see Configuring
Device ECB (ECB201) for FBM247 on page 69.
Indicates the type of point: AI, AO, DI, DO, Pulse In, Pulse Out,
SOE Input, or NAMUR Input.
Enabled or Disabled.
This is determined by the DVOPTS parameter; see Configuring
Device ECB (ECB201) for FBM247 on page 69.
Enabled or Disabled.
This is determined by the DVOPTS parameter; see Configuring
Device ECB (ECB201) for FBM247 on page 69.
Primary connection string for the block connection to the channel.
Configured value for HWTYPE parameter in ECB201 - FBM247.
Configured value for SWTYPE parameter in ECB201 - FBM247.
Manufacturer Identification Code for the field device. Refer to HART
Common Tables Specifications (HFC_SPEC-183).
Device type identification for this channel.
Version information returned by the field device in response to the
HART command Read Unique Identifier. Version Number has four
parts that are separated by semicolons (for example,
005; 001; 013; 016):
Universal Command Major Revision Number implemented by
this device
Device Revision Level
Software Revision Level of this device
Hardware Revision Level of the electronics in this device.
Indicates type of communication protocol used, such as HART.

119

B0400FF Rev M

7. Maintenance

Table 7-7. FBM247 Channel (ECB201) Equipment Status and Information Display Fields (Continued)

Field
Device Status

Device Diagnostic
Status

120

Description
The following are displayed to define the device/signal status:
DCI Ready/DCI Not Ready
Device Failed
Device Disable
DB Download Failed
DB Download Active
Unresolved Connection
System Alarm
System Message
The following are displayed to define the device/signal diagnostic status:
Primary Out of Limits
Non-Primary Out of Limits
Primary Output Saturated
Primary Output Fixed
More Status Available
Cold Start
Configuration Changed
Field Device Malfunction
A/D Converter Fault
D/A Converter Fault
HART Comm Fault

7. Maintenance

B0400FF Rev M

HART Device and FBM247 Device/Signal Equipment Change


Actions
The actions that are active for the Equipment Change display for the HART slave device in the
System Manager and SMDH are described in Table 7-8. These also pertain to the FBM247
devices/signals in the System Manager.
Table 7-8. HART Device and FBM247 Device/Signal Equipment Change Actions

Action
ENABLE
COMMUNICATIONS1
DISABLE
COMMUNICATIONS1
ENABLE DEVICE
ALARMING
INHIBIT DEVICE
ALARMING
1.

Description
Enables HART communication between the device and FBM.
Disables HART communication between the device and FBM.
Enables device alarms to propagate upward to the Foxboro Evo system.
Inhibits device alarms from propagating upward to the Foxboro Evo
system.

If the device parent FBM214/215 is off-line, these key actions are not available. If the device parent
FBM216/218 main and backup modules are off-line, these key actions are not available.

Enabling Communications with Slave Devices


After you have placed the FBM on-line, you enable communications with each HART slave
device connected to the FBM.
To enable communications with each slave device:
1. If you are using the System Manager, open the System Manager, and select the HART
FBM or FBM247 in the left-hand pane.
2. Do one of the following:
Click the Connections tab in the Information pane.
Click Enable Communications to enable communications to the HART slave
device.
-OR Right-click the FBM to open its context menu and click Enable Communications for Multiple Devices.
-OR From the Actions menu, open the Equipment Change submenu and click Enable
Communications for Multiple Devices.
More information is available in System Manager (B0750AP).
-OR1. Access the System Management displays. For detailed information, refer to System
Management Displays (B0193JC).
2. On the PIO SUB NETWORK display, click the FBM and then click NEXT LEVEL to
open the I/O DISPLAY.
121

B0400FF Rev M

7. Maintenance

3. On the I/O DISPLAY, click the device and then click EQUIP CHG.
4. On the EQUIPMENT CHANGE display, click ENABLE COMMUNICATIONS.
5. Repeat Steps 3 and 4 for each additional slave device.
Communications with the slave devices is now enabled.

HART-Capable FBM247 Faceplates (Foxboro Evo Control HMI)


The ECB200 for FBM247 and ECB201 for the FBM247s devices are represented in the Foxboro
Evo Control HMI with a faceplate (or detail display, or detail view) which provides run-time
information about the FBM247 or devices status.
More information about the Control HMI is provided in the Control HMI Application User's
Guide (B0750AQ).

ECB200 Faceplate for FBM247


The ECB200s faceplates for FBM247 are shown in Figure 7-5 and Figure 7-6 below.
Main View

Diagnostic View

Figure 7-5. ECB200 Faceplates for FBM247 Devices - Main View and Diagnostic View

The ECB200 faceplates main view consists of:


Title bar showing the ECB compound (CPSV31_ECB) and ECB name (F00001),
the block description if any, the block type (ECB200) and the
button to close the
overlay.
ECB parameters identifying the FBM247. The DEV_ID contains the moduless sixcharacter device identifier, and 247 in SWTYPE and HWTYPE parameters indicate
that the module is an FBM247.
ECB STATUS and FBM STATUS tables display information from the ECBSTS and
FBMSTS parameters, respectively.
The current value of the OPSTAT parameter (module is indicated to be OK in
Figure 7-5) at the bottom of the overlay.

122

7. Maintenance

B0400FF Rev M

The
button adds buttons to the right side of the faceplate for selecting configuration and diagnostic displays (see Figure 7-6 below).
The trends button (
) is not used as there are no trend displays associated with
equipment control blocks.
The ECB Status display in the ECB200 faceplates main view indicates operational states of the
ECB200 (above the bold line in Table 7-9) and error conditions when they apply (below the bold
line in Table 7-9). The information is sourced from the ECB200 BLKSTA parameter. Refer to
Integrated Control Block Descriptions (B0193AX) for a detailed description of the parameter.
Table 7-9. FBM247 ECB200 ECB Status Indicators

Status
ECB ON or
ECB OFF
DEV READY or
DEV NOT READY
ON SCAN or
OFF SCAN
DEV FAIL
UNDEF
DEV SHUT DWN
COMM FAIL

Description
The ECB200s compound is either ON or OFF.
The FBM is either ready or not ready to exchange data with the
attached devices.
The ECB200 is either in on-scan or off-scan mode.
There was a hardware failure in the FBM.
The ECB has an unresolved configuration problem.
The FBM is not operating.
There is a problem with communications between the FBM and
the CP.

The FBM Status display in the ECB200 faceplates main view is derived from the FBMSTS
parameter. The display indicates operational states of the FBM247 (above the bold line in
Table 7-10) and error conditions (below the line in Table 7-10) when they apply.
Table 7-10. FBM247 ECB200 FBM Status Indicators

Status
DCI READY or
NOT READY
ON LINE or
OFF LINE
FBM OK or
FBM FAIL
DWNLD FAIL

UNRESOLVED

Description
The DCI configuration in the FBM is ready.
The FBM is on-line or off-line.
The FBM is OK (that is, operating and communicating with the
CP), or failed.
A reset of the FBM247 failed because the FBM could not receive its
configuration correctly. Also shown when a DB Download fails for
an FBM configured with ICC.
The control processor reports that there is an unresolved connection to the FBM.

123

B0400FF Rev M

7. Maintenance

To view additional information about the FBM247s configuration:


1. Click the
button in the lower left corner of the faceplate to add the CONFIG and
DIAG buttons to the upper right side of the overlay (see Figure 7-6).
Click
to refresh the display.
Click
to return to the initial display.
Configuration View - Block

Configuration View - FS

Configuration View - SYSCFG

Mapping (HEX) of the


SYSCFG Parameter

Gray Indicates Channels


are Not Configured
for the FBM247

Indicates which channels


Indicates channel
are configured for HART
power source
Indicates channel I/O mode
(Input or Output)
Figure 7-6. ECB200 Faceplates for FBM247 Devices - Configuration Views

2. Click CONFIG to display the ECB parameters in the BLOCK overlay (Figure 7-6,
Configuration View - Block).

124

7. Maintenance

B0400FF Rev M

3. Click FS at the bottom of the view to display failsafe settings (Figure 7-6,
Configuration View - FS).
4. Click SYSCFG to display the mapping for the SYSCFG parameter (described in
Configuring FBM ECB (ECB200) for FBM247 on page 66).
Table 7-11 describes the ECB parameters displayed on the Configuration Views in the ECB200
faceplate.
Table 7-11. FBM247 Information in a ECB200 Faceplate

Parameter
TYPE
PERIOD
PHASE
ERCODE
SYSCFG

SYSOPT

FSENAB
FSDLAY

Description
The ECB type is ECB200 for an FBM247
Scanning frequency set for the ECB
BPC phase in which the ECB is scanned
Error Code is not used by the FBM247
The length of time at which the System Configuration parameter is polled. The
SYSCFG parameter is described in Configuring FBM ECB (ECB200) for
FBM247 on page 66.
System Option parameter specifies whether system alarming and/or messaging
are to be disabled. This is described in Configuring FBM ECB (ECB200) for
FBM247 on page 66.
When Failsafe is enabled (FSENAB=1), the FBM starts a timer when it loses
communications with the control station. If communications are not restored at
the end of the specified time, the FBM takes failsafe action. The time is specified
in units of 10 ms. In Figure 7-6 for example, the parameter is set to 1000 (the
default) for a delay of 10 seconds. These are described in Configuring FBM
ECB (ECB200) for FBM247 on page 66.

The Diagnostic View (not shown) provides a general list of diagnostic messages applicable to the
FBM247s operation.

125

B0400FF Rev M

7. Maintenance

ECB201 Faceplate for FBM247 Devices


The ECB201s faceplates for FBM247s devices are shown in Figure 7-7.
Main View

Configuration View

Figure 7-7. ECB201 Faceplates for FBM247s Devices

The ECB201 faceplates main view consists of:


Title bar showing the ECB compound (FCP012_ECB) and ECB name (ECB201),
the block description if any, the block type (ECB200) and the
button to close the
overlay.
ECB parameters identifying the FBM247s device. The DEV_ID contains the moduless device identifier, and 247 in SWTYPE and HWTYPE parameters indicate that
the module is an FBM247.
ECB STATUS and FBM STATUS tables display information from the ECBSTS and
FBMSTS parameters, respectively.
The current value of the OPSTAT parameter (module is indicated to be OK in
Figure 7-7) at the bottom of the overlay.

The
button adds buttons to the right side of the faceplate for selecting configuration and diagnostic displays.
The trends button (
) is not used as there are no trend displays associated with
equipment control blocks.
The ECB Status display in the ECB201 faceplates main view indicates operational states of the
ECB201 (above the bold line in Table 7-12) and error conditions when they apply (below the
bold line in Table 7-12). The information is sourced from the ECB200 BLKSTA parameter. Refer
to Integrated Control Block Descriptions (B0193AX) for a detailed description of the parameter.
Table 7-12. FBM247s Device ECB201 ECB Status Indicators

Status
ECB ON or
ECB OFF
126

Description
The ECB201s compound is either ON or OFF.

7. Maintenance

B0400FF Rev M

Table 7-12. FBM247s Device ECB201 ECB Status Indicators (Continued)

Status

Description

DEV READY or
DEV NOT READY
ON SCAN or
OFF SCAN
DEV FAIL
UNDEF
DEV SHUT DWN
COMM FAIL

The FBM is either ready or not ready to exchange data with the
attached devices.
The ECB201 is either in on-scan or off-scan mode.
There was a hardware failure in the FBM.
The ECB has an unresolved configuration problem.
The FBM is not operating.
There is a problem with communications between the FBM and
the CP.

The DVC Status display in the ECB201 faceplates main view is derived from the DEVSTS
parameter. The display indicates operational states of the FBM247s device (above the bold line in
Table 7-13) and error conditions (below the line in Table 7-13) when they apply.
Table 7-13. FBM247s Device ECB201 DVC Status Indicators

Status
DCI READY or
NOT READY
DEV ENABLD or
DEV DISBLD
DVC OK or
DVC FAIL
PORT DISABLD
DWNLD FAIL

UNRESLVD

Description
The DCI configuration in the FBM is ready.
Whether the device is on-line or off-line.
The FBMs device is OK (that is, operating and communicating
with the CP), or failed.
Shown if the port is disabled.
A reset of the FBM247 failed because the FBM could not receive its
configuration correctly. Also shown when a DB Download fails for
the host FBM configured with ICC.
Shown when there is an unresolved connection to the device.

To view additional information about the FBM247 devices configuration:


1. Click the
button in the lower left corner of the faceplate to add the CONFIG,
BLKERR and DIAG buttons to the upper right side of the overlay (see Figure 7-7).
Click
to refresh the display.
Click
to return to the initial display.
2. Click CONFIG to display the ECB parameters in the BLOCK overlay (Figure 7-7,
Configuration View - Block).

127

B0400FF Rev M

7. Maintenance

Table 7-14 describes the ECB parameters displayed on the Configuration View in the ECB201s
faceplate.
Table 7-14. FBM247 Information in a ECB200 Faceplate

Parameter
TYPE
PERIOD
PHASE
ERROPT
ERCODE
PORTNO
DVNAME

MODLID
DVADDR
DVOPTS
DVTYPE
MANFTR
PARENT

Description
Equipment control block type, always ECB201
ECBs execution time base
Configured execution phase for the ECB
Error Alarm Option is not used for DeviceNet devices
Error Code is not used by the FBM247
Port 1 identifies the FBM247s port for this device
Device Name is the name of the field device associated with the ECB201. It is
used by the FBM to validate the identity of the field device when the device connection is made.
Model name (ProdName) and model ID (ProdCode) extracted from the EDS
file
Device address read back from the device itself
Device address as configured in ICC or Foxboro Evo Control Editors
Device type (ProdTypeStr) and type ID (ProdCode) extracted from the EDS file
Device manufacturer (VendName) and ODVA number (VendCode) extracted
from the EDS file
Compound and name of the parent ECB200, that is, the ECB of the FBM247
to which the device is connected

Selecting the DIAG1 button in these ECB201 views (see Figure 7-7 on page 126) displays the
contents of the DDIAG1 parameter of the ECB201, which allows you to read the current HART
device status. The general details of this parameter are discussed in ECB201 Extended Status
Support on page 91; however, the specific use of this parameter with FBM247 and HART
devices is discussed in Configuring IIN Block for HART Integer Digital Variables and Device
Status Bits for the FBM247 on page 73.

FBM216/216b Redundant Power Supply Test


(Internally Powered Transmitter)
NOTE

This status check pertains to redundant FBM216/216b inputs that are powered
from the FBM. It does not pertain to externally powered inputs.
The purpose of the following test is to validate operation of the per channel power supply for each
module in the FBM216 or FBM216b module pair. The test should be performed periodically.
The more often the test is performed, the higher the reliability.

128

7. Maintenance

B0400FF Rev M

The power supplies of each input channel of a redundant pair are diode ORd on the redundant
adapter associated with the input pair. Test points are provided on the redundant adapter to measure loop power for each channel.
The FBM216 redundant adapter for the standard FBM is shown in Figure 7-8, and the adapter
for the Compact FBM216b is shown in Figure 7-9. Along the bottom of the redundant adapter
are test point commons [Input (-)] for each channel. Along the top and right side are positive test
points [Input (P)] for each channel. Two test points are provided for each channel, one for the left
FBM216 module (1), and one for the right FBM216 module (2)].
To perform the status check, refer to Figure 7-8 and proceed as follows:
1. Place the negative probe of a voltmeter at test point common 01 [Input (-)], and test
the loop power (voltage) for channel 01, modules 1 and 2 (at Input (P) 01). Both
readings should be 24 V dc 5%. A reading significantly below specification indicates
a defective module (defective loop power).
2. Repeat Step 1 for the remaining seven channels (02 through 08), using the respective
common points and loop power test points.
Test Points

P0917XQ

01
05

2
1
01 02 03 04
Input (P)

Input (P)
08 07 06 05
1

FBM216
Redundant Adapter

Input (-)
04
08

Test Point Commons


Figure 7-8. FBM216 Redundant Adapter Test Point Locations
(Standard FBM216b Redundant Adapter Is Similar)

129

B0400FF Rev M

7. Maintenance

Test Points

Test Point Commons


Figure 7-9. Compact FBM216b Redundant Adapter Test Point Locations

FBM245 Redundant Power Supply Test


NOTE

The FBM245 has four HART-compatible inputs and four HART-compatible outputs. The test points provide a measurement check of the FBM derived loop supply
voltage for input channels 1-4. These test points do not reflect the loop supply
voltage when loops are externally powered.
The purpose of the following test is to validate operation of the per channel power supply for each
module in the FBM245 module pair. The test should be performed periodically. The more often
the test is performed, the higher the reliability.
The power supplies of each input channel of a redundant pair are diode ORd on the redundant
adapter associated with the input pair. Test points are provided on the redundant adapter to measure loop power for each channel.
The FBM245 redundant adapter is shown in Figure 7-10. Along the bottom of the redundant
adapter are test point commons [Input (-)] for each channel. Along the top and right side are positive test points [Input (P)] for each channel. Two test points are provided for each channel, one
for the left FBM245 module (1), and one for the right FBM245 module (2)].
To perform the status check, refer to Figure 7-10 and proceed as follows:
1. Place the negative probe of a voltmeter at test point common 01 [Input (-)], and test
the loop power (voltage) for channel 01, modules 1 and 2 (at Input (P) 01). Both
readings should be 24 V dc 5%. A reading significantly below specification indicates
a defective module (defective loop power).
2. Repeat Step 1 for the remaining three channels (02 through 04), using the respective
common points and loop power test points.

130

7. Maintenance

B0400FF Rev M

Test Points
Input (P)

2
FBM245
Redundant Adapter

01 02 03 04

01 02 03 04

Input (-)

P0924DU

Test Point Commons


Figure 7-10. FBM245 Redundant Adapter Test Point Locations

HART FBM and HART Capable FBM247 LED


Indicators
Light-emitting diodes (LEDs) incorporated into the front of the HART FBMs and FBM247
provide visual indication of each modules operational status, and communication activity of its
eight channels (see Figure 7-11 through Figure 7-15).

Operational Status
01

All LEDs are shown in the


On state for illustration of
color and position.

02
03
04
05

All LEDs are clear in the


Off state.

06
07
08

FBM214
8 Communication,
HART Input
P0914XQ

Figure 7-11. Standard HART FBM214/214b/215/244 LED Status Indicators

131

B0400FF Rev M

7. Maintenance

All LEDs are shown in the


On state for illustration of
color and position.
LEDs indicate their channel is
clear when in the Off state.

Figure 7-12. Compact HART FBM214b/215 LED Status Indicators

Operational Status
01
Master

02

Tracker

03

All LEDs are shown in the


On state for illustration of
color and position.

04
05

All LEDs are clear in the


Off state.

06
07
08

FBM216
8 Communication,
Redundant HART Input
P0917TN

Figure 7-13. Standard HART FBM216/216b/218/245 LED Status Indicators

132

7. Maintenance

B0400FF Rev M

All LEDs are shown in the


On state for illustration of
color and position.
LEDs indicate their channel is
clear when in the Off state.

Figure 7-14. Compact HART FBM216b/218 LED Status Indicators

Operational Status
01
02

All LEDs are shown in the


On state for illustration of
color and position.

03
DI/DO, Pulse

04
05

HART

All LEDs are clear in the


Off state.

06
07
08

FBM247

Channel Isolated
8 Configurable Channels
(AI/AO)+HART, DI/DO, Pulse
P0927BN

Figure 7-15. HART Capable FBM247 LED Status Indicators

133

B0400FF Rev M

7. Maintenance

On the front of all HART FBMs and the FBM247, two Operational Status LEDs (red and green)
indicate the operational status of the module. During normal on-line operation of the FBM with
communications enabled with the connected HART devices, the green LED is on, and the red
LED is off.
LEDs 01 through 08 provide different information on the HART FBMs than on the FBM247:
For the HART FBMs, LEDs 01 through 08 indicate the operational status of the
eight HART communication channels. Each LED is on when the FBM is expecting
and receiving valid messages from the HART device on the channel. If the ECB201 is
configured as 4-20 (4 to 20 mA analog channel), the LED is always off.
For the FBM247, LEDs 01 through 08, indicate the operational status of the eight
communication channels, depending on what the source of each channel has been
configured for. When a channel is configured for HART or analog communications,
its associated LED is on when the FBM is expecting and receiving valid messages on
the channel. If the ECB201 is configured as 4-20 (4 to 20 mA analog channel), the
LED is always off.
When a channel is configured for digital I/O signals, the yellow LED indicates the on
or off state of the digital input or output channel.
On the redundant HART FBMs (not currently supported on the FBM247), the Master and
Tracker LEDs indicate the master/tracker status of the redundant module pair. The Master LED
is on when the module is controlling HART communications. The Tracker LED is on when the
module is ready to control HART communications.
Table 7-15 lists the state of the FBM LEDs under various operating conditions. This table
assumes that you have properly configured the ECB201s for communication with HART devices
(or with the FBM247, the FBMs associated I/O source). It also assumes that you have placed the
FBMs on-line and enabled device communications using the appropriate displays (System Manager or SMDH).
Table 7-15. HART FBM Operational Status LEDs

Operational Status
Red LED

Green LED

01 to 08

Master

Tracker

Status

Normal Operation
Off

On

On for
channels
with normal
HART
communications

On or
Off

On or
Off

FBM is on-line and functional with


device communications enabled.
LEDs 01 to 08 are on only for channels with normal HART communications. State of Tracker or Master is
determined by the appropriate display (System Manager or SMDH).

Power Off
Off

134

Off

Off

Off

Off

Power to FBM is failed or switched


off.

7. Maintenance

B0400FF Rev M

Table 7-15. HART FBM Operational Status LEDs (Continued)

Operational Status
Red LED

Green LED

01 to 08

Master

Tracker

Status

Diagnostic Failure1
On

Flashing
0.5 s on,
0.5 s off

Off

Off

Off

On

Flashing
three 0.5 s
flashes
every 5 s
Flashing
four 0.5 s
flashes
every 5 s

Off

Off

Off

Off

Off

Off

On

Off

Off

Off

On

On

RAM test Green LED flashing


once every 5 s indicates a failure in
the low byte RAM chip. Green LED
flashing twice every 5 s indicates a
failure in the high byte RAM chip.
HDLC, DMA, Timer, and Interrupt Controller tests Green LED
flashing 3 times every 5 s indicates a
failure (an ASIC problem).
ROM test Green LED flashing
4 times every 5 s indicates ROM
checksum error was detected in the
primary or secondary ROM, or in
the ROM copy of the Product Data
Block. (Error message is printed on
the system alarm printer.)
Startup diagnostics passed and FBM
is ready to be brought on-line by the
CP.

Off-Line
On

On

Off

On or
Off

On or
Off

FBM is off-line but functional.


LEDs 01 to 08 are always off. Master LED flashes if both modules of a
redundant pair are off-line.

Download (Reboots the FBM)


Flashing

Flashing

Off

On or
Off

On or
Off

Red and green LEDs flash together


or independently. Master and
Tracker LEDs flash (depending on
which module is being downloaded)
to show role switching between the
modules. Download action completes in less than one minute.

EEPROM Update
Flashing

Flashing

Off

Flashing

Flashing

Red and green LEDs flash together


or independently. Master and
Tracker LEDs flash (depending on
which module is being updated) to
show role switching between the
modules. EEPROM Update action
completes in less than one minute.
135

B0400FF Rev M

7. Maintenance

Table 7-15. HART FBM Operational Status LEDs (Continued)

Operational Status
Red LED

Green LED

01 to 08

Master

Tracker

Status

Channel Communication Problem


Off

On

Any one
LED off

On or
Off

On or
Off

If any one LED 01 through 08 is


off, this indicates a fault in the associated field device, cabling or FBM
channel.

Channel Communication Problem Tracker Module


Off

On

Occasional
flickering of a
Trackers
LED

On or
Off

On or
Off

If the Trackers LEDs 01 through 08


mostly follow the Masters LEDs 01
through 08, but one occasionally
flickers, this indicates a problem in
the Trackers HART communication hardware for the channel. The
FBM eventually declares a fault
(after enough communication
errors).

Redundant FBM Software Problem


Off

On

Trackers
LEDs are
consistently
different
than
Masters
LEDs

On or
Off

On or
Off

If the Trackers LEDs 01 through 08


are consistently different than the
Masters LEDs 01 through 08, this
indicates an FBM software problem.

Fail Safe
Off

Flashing

On for
channels
with normal
HART
communications

On or
Off

On or
Off

During normal on-line operation,


the FBM experienced a break in
communications with the Foxboro
control station and reverted to its
fail-safe mode. (Refer to Fail-Safe
Actions on page 82 for details.)

Module Failure
On
1.

136

Off

Off

On or
Off

On or
Off

Module failure.

Failure detected during startup diagnostics. Reboot the module to clear the diagnostic error. If the
problem still exists, remove the module from the baseplate and reinstall it in the same slot (refer to
the WARNING at the beginning of this chapter on page 93). If problem continues, replace the
module. Refer to DIN Rail Mounted Subsystem Users Guide (B0400FA) for details.

7. Maintenance

B0400FF Rev M

Service and Support


Technical support is available from the Invensys Global Customer Support, 1-866-746-6477 or
visit at https://support.ips.invensys.com.

137

B0400FF Rev M

138

7. Maintenance

Appendix A. HART FBM System


Messages (SMON Log)
This appendix defines the complete list of system messages which can be generated by the HART
FBMs. For redundant HART FBMs, only the Master FBM posts these messages to the System
Monitor log (smon_log).
The format for HART FBM system messages in the smon_log is as follows:

Figure A-1. HART FBM System Message Format

These system messages may contain an [M|B] device type for messages reported from a Main or
Backup Master FBM:
M indicates the Main Master FBM sent the message.
B indicates the Backup Master FBM sent the message.
However, a Tracker FBM can record messages that need to be posted, but will hold them until it
takes the Master role. Such messages are marked with [m|b] instead:
m indicates the Main Tracker FBM sent the message.
b indicates the Backup Tracker FBM sent the message.
The internal time of each message (the actual time of the event) is recorded in the smon_log. This
time represents the number of milliseconds since the last reboot of the particular FBM. The
recording of the message in the smon_log can be delayed. For example, when an FBM is not in
the Master role, and it is holding messages until it takes this role, such a delay occurs.
! WARNING
This field rolls over every 1.8 hours. It is intended to provide relative timing to
other messages posted by the same FBM only.
Some of these messages may be turned off by setting gating bits in the SYSOPT register. Those
gating bits are shown in Table A-1 below.

139

B0400FF Rev M

Appendix A. HART FBM System Messages (SMON Log)

Table A-1. Gating Bits in the SYSOPT Register for HART FBM System Messages
Gated
by Bit

Error
Code

Error Text

Corrective Action

08

21

A/D Reinitialized - Lockup

08

22

A/D Reinitialized - GI lockup

These are notifications of recoveries of operation


by the FBM; no action is required.

08

22

A/D Reinitialized - Offset Error

08

22

A/D Reinitialized - Gain Error

08

23

Calibration O register changed to


0xNNNNNN

08

24

Calibration G register changed to


0xNNNNNN

08

25

GIRUN stuck, recovering

08

26

Group sample time overrun/recover

08

44

AI Init Fail chN code 0xNNNN

HARD FAILURE: A/D converter hardware


Replace FBM

*= These were listed as n/a before v2.47.


08*

60

comms failure to valid config

HART device communication failed on initial


startup with DVOPTS set to NOFAIL and not
NOALARM. No action required.

08*

61

comms timeout

These indicate that the HART device has communication timeouts with DVOPTS set to OCD. HART
Device fault

08*

62

comms error cleared

No action required. (code 60 cleared) for DVOPTS


set to NOFAIL or OCD

08*

63

device is powered off

FBM247 Configuration has powered off the device

08*

64

08*

65

malfunction retry count exceeded

FBM has set device malfunction alarm

08*

66

malfunction cleared

FBM has cleared device malfunction alarm (code


65 cleared)

08*

67

sys alarm cleared

FBM has cleared system alarm for new configuration


(set for codes 60, 61, 63, 64, 65)

n/a

Ch1-8

DVNAME Bad Channel Number

ERROR: FBM247 DVNAME CHn number(n) is not


1 through 8

n/a

Ch1-8

DVNAME Bad I/O Option

ERROR: FBM247 DVNAME I/O channel type not


I or O

n/a

Ch1-8

DVNAME/SYSCFG LPWR Mismatch

ERROR: FBM247 DVNAME and SYSCFG LPWR


option mismatch

n/a

Ch1-8

DVNAME/SYSCFG I/O Mismatch

ERROR: FBM247 DVNAME and SYSCFG I/O


mismatch

n/a

Ch1-8

DVOPTS Is Invalid

ERROR: FBM247 DVOPTS string not permitted

n/a

Ch1-8

Input Block Not Voltage

ERROR: FBM247 RIN block not voltage and DVOPTS is VOLT

n/a

Ch1-8

Input Block Not Current

ERROR: FBM247 RIN block is voltage, DVOPTS


is current

n/a

Ch1-8

DVOPTS/Out Block Mismatch

ERROR: FBM247 ROUT block conflict with DVOPTS value

n/a

Ch1-8

DI Thresholds Backwards

ERROR: FBM247 DI thresholds are in the wrong


order

n/a

Ch1-8

I/O Block Type Mismatch

ERROR: FBM247 I/O block type mismatch to


DVOPTS I/O type

140

Appendix A. HART FBM System Messages (SMON Log)

B0400FF Rev M

Table A-1. Gating Bits in the SYSOPT Register for HART FBM System Messages
Gated
by Bit

Error
Code

Error Text

Corrective Action

10

48

Power 2 fault cleared

The FBM is no longer seeing power issues (code


58) on the 2nd power bus.

10

49

Slot conflict cleared

The FBM pair is on the same page regarding the


interlink, (code 59) no longer exists

10

53

HART fault detected

ERROR: One FBM of pair has had HART issues


for 4 health checks in a row and is declaring a
problem. Check connections, possibly replaced
FBMs.

10

54

Power 1 fault cleared

The FBM is no longer seeing power issues (code


57) on the 1st power bus.

10

55

A2D fault detected

ERROR: The FBM is reporting broken hardware.


The FBM should be replaced.

10

56

Fatal Error Flashed

ERROR: The FBM has logged an error that is


tagged with the FATAL attribute. FBM will have to
be rebooted before it can be used again.

10

57

Power 1 Fault

WARNING: The FBM is seeing power issues on


the 1st power bus. Check connections.

10

58

Power 2 Fault

WARNING: The FBM is seeing power issues on


the 2nd power bus. Check connections.

10

59

Slot conflict

ERROR: Either
- The Master FBM and its partner are not agreeing
on the interlink use
- The Master FBMs expectation of the partners
sending state does not match the reported state.
Best to reseat the pair one at a time, starting with
Tracker.

The following bits are for ECB202 Only


10

40

tracker; serious error

ERROR: The Master FBM is becoming Tracker


because of a serious error (The ErrorStopIO flag is
set).
Bad timer
Bad HDLC
Bad memory location
Bad OpCode
Bad FLASH
Bad Configuration
Overrun of INT depth
If flashing error code, replace module. Otherwise
reboot module. If problem recurs, replace.

10

41

master; partner faulted

ERROR: The Tracker FBM is declaring a Master


FBM fault and asserting a takeover. The type of
fault may generate additional messages.

10

42

master; partner offline

Partner FBM has gone offline; Tracker is asserting


Mastership.

10

43

partner not answering

ERROR: Tracker is noticing that Master is not


responding to CP messages/requests for the last
10 requests. It will try to assert Mastership.

10

44

Partner report err code 0xNNNN

Tracker FBM sent over a problem code. The


NNNN is usually the channel number.

10

45

master: no partner

ERROR: Master FBM has lost communications


with Tracker across the interlink.

141

B0400FF Rev M

Appendix A. HART FBM System Messages (SMON Log)

Table A-1. Gating Bits in the SYSOPT Register for HART FBM System Messages
Gated
by Bit

Error
Code

Error Text

Corrective Action

10

46

tracker: attempt master

ERROR: Tracker is noticing that Master has a


fault. It will try to assert Mastership.

10

47

warm reset of partner

Master requested a partner reset because of


some issue, can be at operator request. No action
required unless this is frequent replace Tracker.

10

50

Interlink fault detected

ERROR: Interlink is having a problem. Push/pull


Tracker or force a warm reset.

10

51

Interlink fault cleared

Interlink fault (code 50) has cleared

10

52

3+ consec LRC errs ilink

The interlink between the pair of modules is experiencing problems. As the interlink is very short,
this is usually a seating issue.

142

Index
A
Auto/Manual mode, DCI blocks 80
B
Baseplate xiii, 3
Baseplate, FBM mounting slots 14
Baseplate-mounted TA
FBM247 36
Block detail display 7, 87
ECB200 88
ECB201 90
ECB202 89
C
Cable balun module 11
Cable length 11
Cable Type A 10
Cascade initialization
ROUT block 81
Compound detail displays 87
Configuration information
DCI blocks 49
Configuration procedures 50
Configuring DCI blocks 77
Control schemes
DCI blocks 84
Control station xiii
Creating and editing ECB
ECB200 63
ECB201 64
ECB202 63
D
Data type conversions
DCI blocks 61, 62
DCI xiii
DCI blocks 50
Auto/Manual mode of operation 80
block interconnection example 51, 52, 53, 54
cascade initialization 81
configuration information 49
configuration procedures 50
configuring 77
143

B0400FF Rev M

control schemes 84
data type conversions 61, 62
fail-safe actions 82
functions 80
HART point addresses 59, 60
input limiting 80
key parameters 55
list of 49
output clamping 81
output confirmation 80
output initialization 81
periodic/change-driven execution 80
signal conditioning and linear scaling 80
simulation mode 80
status transformations 83
Device connections to TAs 17
Device data verification 7
Diagnostics 4, 135
Distributed Control Interface xiii
E
ECB xiv
ECBs
creating and editing 63, 64
hierarchy 50
list of 49
Entity parameters 47
Environmental constraints 9
Equipment Change display
FBM214/214b/215 111
FBM216/216b/218 112
HART device 121
Equipment Control Block xiv
Equipment Information display
FBM214/214b/215 96
FBM216/216b/218 99
FBM247 104
FBM247 device/signal 118
HART device 115
Equipment installation 13
Example
DCI block interconnections 51, 52, 53, 54
F
Faceplate
FBM247 122
Fail-safe actions
DCI blocks 82
144

Index

Index

B0400FF Rev M

FBM xiv
FBM214/214b 1
FBM215 1
FBM216/216b 1
FBM216/216b redundant power supply test 128, 130
FBM218 1
FBM244 2
FBM245 2
FBM247 2
FCM xiv
Fieldbus xiv
Fieldbus Communications Module xiv
Fieldbus Module xiv
FoxCAE software xiv
G
Glossary xiii
Group displays 87
H
Hand held configurator 4
HART communications standard 2
HART point addresses
DCI blocks 59, 60
I
IFDC xiv
Input limiting
RIN 80
Input signal flow
FBM214/214b 19
FBM216/216b 21
Install the Foxboro Evo system 6
Installation
equipment 13
FBMs and TAs 16
redundant adapter 16, 17
Intrinsic safety considerations 12
Invensys Global Customer Support xiii
K
Key parameters 55
L
LED status indicators
Compact FBM214b/215 132
Compact FBM216b/218 133
145

B0400FF Rev M

FBM operational status 134


FBM214/214b/215/244 131
FBM216/216b/218/245 132
FBM247 133
Letterbug xiv, 59
N
Network configuration 3
O
Output clamping
ROUT block 81
Output confirmation
ROUT block 80
Output initialization
ROUT block 81
Output signal flow
FBM215 30
FBM218 30
P
Parameter xiv
Part numbers
FBMs 15
redundant adapters 15
TAs 15
Periodic/change-driven execution
DCI blocks 80
Process operator displays 87
Product application 9
Q
Quick-start example 5
R
Redundant Adapter xiv
installation 16, 17
Reference documents xi
Revision information xi
Run-time software 4
S
Signal conditioning and linear scaling
RIN and ROUT blocks 80
Simulation mode

146

Index

Index

B0400FF Rev M

DCI blocks 80
SMDH 95
Station displays 87
Status transformations
DCI blocks 83
SYSCFG parameter for FBM247 67, 124
System Management displays 94, 121
System Manager displays 94
T
TA xiv, 3, 13
TA cable connections
FBM214/214b/215 18
FBM215/218 29
FBM244/245 32
FBM247 38
TAs
device connections 17
Termination assemblies xiv, 3, 13
U
User-generated displays 87

147

Invensys Systems, Inc.


10900 Equity Drive
Houston, TX 77041
United States of America
http://www.invensys.com

Global Customer Support


Inside U.S.: 1-866-746-6477
Outside U.S.: 1-508-549-2424
Website: https://support.ips.invensys.com

You might also like