ETG1020 CommentFormV1i1i0D 2015-12-01

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

ETG.

1020 EtherCAT Protocol Enhancements


Please return form to [email protected]

ETG
member

Clause/
Paragraph
Subclause Figure/ Table

Type of
comment

Date

Document

18.11.2014
17.11.2015
01.12.2015

ETG1020_v1i1i0_S_D_ProtocolEnhancements.pdf

COMMENTS

Proposed change

OBSERVATIONS OF ETG
on each comment submitted

(General/
Technical/Editorial)

OMRON

Code0x006, what does Slave needs


BOOT-INIT transition means

Table1

I think it can be deleted because Slave


needs BOOT-INIT transition is only
specific action for Semi devices but the
code may also be used by other slaves
which may have different recovering
behavior, e.g. re-download, power cycle

Proposal:
Meaning:
Delete Slave needs BOOT-INIT
transition
Adapt:
SII/EEPROM information does not match
Firmware
Description:
if the slave checks if the SII/EEPROM
content matches the firmware, e.g.
process data description or revision
number, and detects a mismatch
Init -> PreOp, final state ErrInit

OMRON

Table1

ETG

Table 1

OMRON

Table 60

ETG

10

Code0x002E, Cycle time to small

Cycle time too small

Code 0x0070 Description wrong:


Detected Configured Module Ident List
(0xF030) and Configured Detected
Module Ident list (0xF050) does not
match
some Footnote numbers 2 are strange
(too big in size and wrong position)

correct

There are additional objects defined in


ETG.5001 that need this procedure

Add objects
0xF01x, 0xF02x and 0xF03x to the list of
objects

Correct

Accepted by TAB e-mail voting


10.12.2014
Proposal: accepted
Accepted by TAB e-mail voting
10.12.2014
Proposal: accepted
Accepted by TAB e-mail voting
10.12.2014

Proposal: accepted
Accepted by TAB e-mail voting
10.12.2014
Proposal: accepted
Accepted by TAB e-mail voting
10.12.2014

ETG
member

Clause/
Paragraph
Subclause Figure/ Table

Type of
comment

COMMENTS

Proposed change

OBSERVATIONS OF ETG
on each comment submitted

(General/
Technical/Editorial)

OMRON

OMRON

OMRON

11.1

11.2

11.2

What does 0-terminator mean?


Does it apply for ALL single entry with
flexible length? (OCTET_STRING,
UNICODE_STRING, ARRAY_OF_*,
VISIBLE_STRING, Byte stream,
international language string, etc)

Item 6

Item 7

That means some objects are allowed


not to support CompleteAccess. How
does a master/tool know which object
does not support CompleteAccess? By
ESI Object/Flags@SdoAccess?
I believe a tool/master should use
Object/Flags@SdoAccess

what should a master/tool use to identify


whether an object supports
CompleteAccess or not? The specific
DataTypes of entries in an object or ESI
Object/Flags@SdoAccess?

Proposal:
Entries with flexible length, as specified
in table 93, may have a shorter length
than given as the maximum size of the
entry.
For entries with data type
VISIBLE_STRING the following applies:
Write access
- Master can send a VISIBLE_STRING
without 0-terminator:
slave shall add the 0-terminator if the
written VISIBLE_STRING is shorter than
the maximum entry size
- Master can also write
VISIBLE_STRING with 0-terminator
Read access:
- If the master reads a VISIBLE_STRING
the slave should return the
VISIBLE_STRING with its actual length.
- Bytes following the 0-terminator shall
be zero.
Accepted by TAB e-mail voting
10.12.2014
Proposal:
Add new:
Even when the slave supports complete
access there still may be objects that
cannot be accessed via complete
access. For descriptions about complete
access in ESI, see ETG2000.
If
Object/Flags@SdoAccess=CompleteAcc
ess in ESI, the device shall support
complete access to the object.
Accepted by TAB e-mail voting
10.12.2014
Proposal:
See above
Accepted by TAB e-mail voting
10.12.2014

ETG
member

Clause/
Paragraph
Subclause Figure/ Table

Type of
comment

COMMENTS

Proposed change

OBSERVATIONS OF ETG
on each comment submitted

(General/
Technical/Editorial)

OMRON

11.2

OMRON

11.2

OMRON

11.3

OMRON

13.1

Item 10

, also some other objects may not


support CompleteAccess. E.g. very big
objects with thousands bytes, supporting
CompleteAccess will require extra RAM
cost.
I believe ETG should allow other objects
not mentioned explicitly here not support
CompleteAccess. For those objects
without supporting CompleteAccess, it is
required to indicate in ESI by
Object/Flags@SdoAccess=SubIndexAc
cess (default value).
concerns about item 11, 12 of Subclause
11.2.
My assumption is the 2 rules are for
some special objects such as 0x10F3.
My concern is if the 2 rules apply for all
objects, the usability would be very bad
for a tool: it would receive data packages
without knowing how to decode them.
E

Note

typo in 11.3 title: SDI -> SDO

NOTE: A state machine for Diagnosis


Handling is under preparation
When the state machine is supposed to
be available?

OMRON

13.2

Table 27
SI 3

Writing = 0:
(support optional) the slave will clear all
messages

Proposal:
See above
Accepted by TAB e-mail voting
10.12.2014

My proposal: add NOTE:


-- this applies only for 0x1F03, (and other
known ETG-defined objects)
-- this shall not be used for other objects.

Proposal:
The concerns are reasonable. But it is up
to the slave vendor if a complete access
makes sense for an object or not. An
EtherCAT master need to rely on the
structure information provided by the ESI
(or slave application).
Accepted by TAB e-mail voting
10.12.2014
Proposal: accepted
Accepted by TAB e-mail voting
10.12.2014
Proposal: the diagnosis state machine
handling is implicitly described by the
existing diagnosis chapters.
Delete Note
Accepted by TAB e-mail voting
10.12.2014
Proposal:
Add
, i.e. resetting SI2, SI3, SI4 and Si5 Bit 5
Accepted by TAB e-mail voting
10.12.2014

ETG
member

Clause/
Paragraph
Subclause Figure/ Table

Type of
comment

COMMENTS

Proposed change

OBSERVATIONS OF ETG
on each comment submitted

(General/
Technical/Editorial)

OMRON

Beckhoff

13.2

13.3.

ETG

14.3

OMRON

14.4.

OMRON

19.2.1.1.6

SEW

23

Table 27
SI 5

If any bit is changeable by write, SI_5 is


writable. For bits not changeable by write
of Bit0, Bit3 and Bit4, the slave shall
check with its respective default bit
values. If all are matched, the
slave responds positively

Table 28

Table 32

Proposal:

There can be additional data types for


DiagMessage parameter

Bit 0-11 = Data type Index of the data


type of parameter 1

Bit 0-11 = Data type Index of the data


type of parameter 1
0x0001: BOOLEAN; ESI specifier: %c
0x0002: INTEGER8; ESI specifier: %d
0x0003: INTEGER16; ESI specifier: %d
0x0004: INTEGER32; ESI specifier: %d
0x0005: UNSIGNED8; ESI specifier: %u
0x0006: UNSIGNED16;
ESI specifier: %u
0x0007: UNSIGNED32;
ESI specifier: %u

Data type IDs:


0x0001: BOOLEAN
0x0002: INTEGER8
0x0003: INTEGER16
0x0004: INTEGER32
0x0005: UNSIGNED8
0x0006: UNSIGNED16
0x0007: UNSIGNED32
0x0008 : REAL32
0x0011 : REAL64Ae
0x0015 : INTEGER64
0x001B : UNSIGNED64

Add:
When writing SI5, the readonly bits
should match the current values. Bit5
shall be "dont care".
The slave should send an abort with
0x6090030 Value exceeded in case the
readonly bits differ from current values.
Accepted by TAB e-mail voting
10.12.2014
Proposal: accept
Accepted by TAB e-mail voting
10.12.2014

The corresponding text parameters and


formatting are specified in the ETG.2000.
Typo
Change to TxPDO Parameter
Proposal: accept
Name: RxPDO Parameter
Accepted by TAB e-mail voting
10.12.2014
the last extension is allowed to have size Please delete "end of entry" from the last Proposal: accept
of 240 according to Rule3.
2 examples
There is no need for "end of entry" in the
Accepted by TAB e-mail voting
last 2 examples.
30.11.2015
renumber items starting from 1, not
Proposal: accepted
current 5
Accepted by TAB e-mail voting
10.12.2014
Data types are already defined in
Add note that this chapter enhances the
Proposal: accepted
ETG.1000.6
data type definition of ETG.1000.6
Accepted by TAB e-mail voting
10.12.2014

ETG
member

Clause/
Paragraph
Subclause Figure/ Table

Type of
comment

COMMENTS

Proposed change

OBSERVATIONS OF ETG
on each comment submitted

(General/
Technical/Editorial)

OMRON

23

Table 93

I have a concern about explanation in


Table93 for VISUAL_STRING. It may
conflict with the definition in ETG2000
and our discussions.

OMRON

23

Table 92, 93
94

OMRON

23

Table 93

Why do you put GUID for some


add a GUID for the other data types as
DataTypes, not for others in Table92, 93, well
94?
What are the GUID is supposed to be
used?
Table 93 contains strange texts, e.g
{18071995-????????????-xxxx}, in
explanations about Index 0x0009,
0x000A and 0x000B

OMRON

23

Table 93

2. Can GUID be used in ESI? If yes, it


will cause a compatible problem:
almost all tool can not support it.
To avoid the trouble, I would like to
propose adding a NOTE: using GUID in
ESI is reserved.

Please clarify

I propose to delete ByteSize = xxx+1 in


table 93 and adapt description for xxxx
as follows:
VISIBLE_STRING
with xxxx equals n (in HEX)
OCTET_STRING
with xxxx equals n+1 (in HEX)
UNICODE_STRING
with xxxx equals n+1 (in HEX)
Accepted by TAB e-mail voting
10.12.2014
Proposal: accepted
Accepted by TAB e-mail voting
10.12.2014

Proposal:
GUID is missing in the last cell of the
table heading.
xxxx is described in the corresponding
cell, i.e. "with xxxx (in HEX) is length of
data."
Accepted by TAB e-mail voting
10.12.2014
Proposal: reject
There might be objects/entries, that are
of type GUID. E.g. we already defined
some in the EAP specification.
Therefore a definition of a GUID data
type is useful and should be allowed as
any other BaseDataType.
For the configuration tools: this is a
feature enhancement, which needs an
enhancement in the configuration tools.
However, in the moment there are no
standardizes objects in the EtherCAT
specs, hence it might not be necessary
to be supported any time soon in the
tools.
Agreed by TAB e-mail voting 30.11.2015

You might also like