AMF620
AUTO START MODULE
OPERATING MANUAL
Multilizer PDF Translator Free version - translation is limited to ~ 3 pages per translation.
Multilizer PDF Translator Free version - translation is limited to ~ 3 pages per translation.
HGM610/620 AUTO START MODULE
CONTENT
1.
SUMMARY.......................................................................................................................................................... 3
2.
3.
OPERATION.......................................................................................................................................................4
3.1 OPERATION PANEL
............................................................................................................................................. 4
3.2 AUTOMATIC OPERATION
...................................................................................................................................... 5
3.3 MANUAL OPERATION
..........................................................................................................................................6
3.4 RUN ON LOAD
..................................................................................................................................................... 6
4.
5.
6.
SETTING PARAMETER.................................................................................................................................18
1.
2.
3.
4.
5.
HISTORY RECORD
............................................................................................................................................. 18
SET DATE AND TIME
..........................................................................................................................................18
SET PARAMETERS
............................................................................................................................................. 18
INFORMATION
.................................................................................................................................................... 19
SET LANGUAGE
.................................................................................................................................................19
7.
8.
COMMUNICATION..........................................................................................................................................20
9.
SPECIFICATION..............................................................................................................................................20
HGM610/620 MODULE
Page 2 of 24
Multilizer PDF Translator Free version - translation is limited to ~ 3 pages per translation.
Multilizer PDF Translator Free version - translation is limited to ~ 3 pages per translation.
HGM610/620 AUTO START MODULE
1. SUMMARY
HGM610/620 Series generator controller integrating digital, intelligent and network
techniques is used for automatic control system of diesel generator. It can carry out
functions including automatic start/stop, data measure and alarming. The controller uses
LCD display, optional Chinese and English display interface with operation easy and
reliable.
HGM600 Series generator controller uses micro-processing technique which can carry
out precision measure, constant value adjustment, timing and threshold setting and etc.
of multi-parameters. It can be widely used in all types of generator automatic control
system for compact structure, advanced circuits, simple connections and high reliability.
Page 3 of 24
Multilizer PDF Translator Free version - translation is limited to ~ 3 pages per translation.
can be used directly(i.e. VDO, DATCON, CUMMINS, PT100). also may select user
defined sensor via entering 8 point curves;
Functions including RTC(real time clock) and hours count;
Display of generator cumulated electric energy;
Security password-protected programming levels.
Several crank success conditions are optional;
Built-in speed/frequency detecting units can accurately judge the states such as crank
success and over speed;
99 historical records can be stored circularly and inquiring of the records can be made
on site;
Power supply range is wide (DC: 8 to 35V), accommodating to different starting
battery voltage environments;
All parameters use digital modulation, abandoning anolag modulation using
conventional electronic potentiometer, reliability and stability are increased;
Built-in watch dog can never be dead halt, ensuring smooth program execution;
Modular configuration design, inserted type connection terminals, flush type
installation, compact structure, easy installation.
3. OPERATION
LCD display screen can display multi -parameters of generator such as voltage, current,
Battery voltage, various parameters of engine such as engine rotating speed, engine oil
pressure, cooling water temperature, also can display multi-states and alarming amount.
HGM610/620 MODULE
Page 4 of 24
push-button. The
function is used to change a programming value while in the
programming mode. When this push-button is held down, the displayed value will be
decremented to a lower value as desired.
push-button. The
function is used to change a programming value while in the
programming mode or to select a desired programming menu loop. When this
push-button is held down, the displayed value will be incremented to a higher value as
desired.
push-button. The
function is used to entering in setting menu, shifting cursor
in setting and confirming the set information.
push-button. The
engine-generator set.
push-button. The
generator set.
push-button. The
function is used to initiate load test of the engine generator
set when connected to an associated transfer switch.
light viewing window. The
illuminates (flashes) when any pre-programmed
warning or shutdown fault has been activated.
Page 5 of 24
When the engine fires, the starter motor is disengaged and locked out at a pre-set
frequency from the Alternator output. Alternatively a Magnetic Pickup mounted on the
flywheel housing can be used for speed detection.
After the starter motor has disengaged, the Wait for oil pressure timer is activated.
Once the engine is running, the Warm Up timer is initiated, allowing the engine to
stabilize before accepting the load. After this delay, send out a closing gens signal.
When mains is normal, the mains normal delay timer is initiated, once it has timed out,
the closing gens signal is de-energised, then the closing mains signal is active.
When the mains normal delay has time out, the Stop delay timer is initiated. After this
delay, the Cooling timer is then initiated, allowing the engine a cooling down period off
load before shutting down. Once the Cooling timer expires the Fuel Solenoid is
de-energised, bringing the generator to a stop.
, after
Page 6 of 24
4. BACK BOARD
5. CONNECTING TERMINAL
Page 7 of 24
No.
Function
9
10
11
Diameter
of Wire
1.0mm
1.0mm
1.0mm
12
Sensors Common
1.5mm
13
1.0mm
14
1.0mm
15
Aux. Sensor1
1.0mm
16
Aux. Sensor2
1.0mm
Description
Remarks
17
Generator L1 current
transformer connection.
2.5mm
18
Generator L2 current
transformer connection.
2.5mm
19
Generator L3 current
transformer connection.
2.5mm
20
Current Transformer
Common
2.5mm
21
1.0mm
22
1.0mm
23
1.0mm
24
1.0mm
Remarks
25
DC Supply -ve.
2.5mm
26
DC Supply +ve.
2.5mm
27
2.5mm
Connecting
with
+Ve
Emergency Stop Button
28
2.5mm
HGM610/620 MODULE
through
Page 8 of 24
Diameter
of Wire
No.
Function
29
30
31
32
2.5mm
37
38
2.5mm
1.5mm
1.0mm
35
36
33
34
Remarks
Remarks
Mains position
1.0mm
1.5mm
43
1.0mm
44
1.0mm
45
1.0mm
46
1.0mm
40
41
42
HGM610/620 MODULE
Page 9 of 24
6. PARAMETERS SETTING
Item
Mains normal delay
Setting Range
(0-9999S)
(0-9999S)
(30-360V)
276
(30-360V)
184
55.0
(0-75.0Hz)
45.0
(0-999.9S)
1.0
Start delay
(0-9999S)
Stop delay
(0-9999S)
10
Close time
(0-10.0S)
3.0
11
(30-360V)
264
12
(30-360V)
196
HGM610/620 MODULE
Default
10
description
Mains transient delay, suited
for ATS(automatic transfer
switch)
When mains voltage is over
than the point, mains over
voltage is active. when the
point is 360V, mains over
voltage is disabled.
When mains voltage is under
than the point, mains under
voltage is active. when the
point is zero, mains under
voltage is disabled.
When mains frequency is
over than the point, mains
over frequency is active.
when the point is 75.0Hz,
mains over frequency
is
disabled.
When mains frequency is
low than the point, mains low
frequency is active. when the
point is zero, mains low
frequency is disabled.
its the delay from mains is
opened to generator closing
or from generator is opened
to mains closing.
Its the delay from remote
start signal is active or mains
is failure, to start generator.
Its the delay from remote
start signal is inactive or
mains is normal, to stop
generator.
Mains or Gens switch
closing pulse width, when it
is zero, output is continue.
When generator voltage is
over
than
the
point,
generator over voltage is
active. when the point is
360V, generator over voltage
is disabled.
When generator voltage is
under
than the point,
Page 10 of 24
No
Item
13
(0-75.0Hz)
57.0
14
(0-75.0Hz)
40.0
15
CT rate
(5-6000)/5
500
16
(5-6000)A
500
17
(50-130)%
120
18
(0-9999)S
1296
19
20
21
22
23
24
25
26
Number of start
Cranking time
Crank rest time
Oil bypass delay
Start idle time
Warming up time
Cooling time
Stop idle time
(1-9)
(3-60S)
(3-60S)
(1-60S)
(0-9999S)
(3-9999S)
(3-9999S)
(0-9999S)
3
5
10
10
0
10
10
0
27
(0-120S)
30
28
29
30
(0-120S)
(0-300S)
(0-300S)
0
0
0
31
Crank disconnect
(1-7)
32
Flywheel
numbers
(10-300)
33
Over speed
HGM610/620 MODULE
Setting Range
teeth
(0-6000RPM)
Default
description
generator under voltage is
active. when the point is 30V,
generator under voltage is
disabled.
When generator frequency is
over than the point and hold
great than 3 seconds,
generator over frequency is
active. when the point is
75.0Hz,
generator
over
frequency is disabled.
When generator frequency is
low than the point, generator
low frequency is
active.
when the point is 0Hz,
generator low frequency is
disabled.
Current transformer rate
Mains or generator set
maximum rated current.
When the load current is
over than the point, the over
current delay is initiated.
When load current is over
than the point and hold great
than the timer, send out over
current signal. when the
delay is zero, over current is
disabled.
numbers of crank cycles.
in
118
1710
No
Item
Setting Range
Default
34
Under speed
(0-6000RPM)
1200
35
(2-16p)
36
Freq disconnect
(14-30Hz)
14
37
WL volts disconnect
(0-30V)
8.0
38
Speed disconnect
(0-3000RPM)
360
39
(1-2)
40
(0-400)kPa
103
41
(0-20.0)S
2.0
42
High temperature
(80-140)
celsius degree
95
43
High
delay
(0-20.0)S
2.0
temperature
HGM610/620 MODULE
description
active.
When the engine speed is
under than the point and
hold great than 10 seconds,
generator under speed is
active.
Generator pole numbers
When generator frequency is
large than this point, starter
will disconnect.
When charge alternator
WL/D+ voltage is large than
this
point,
starter
will
disconnect.
When engine speed is large
than this point, starter will
disconnect.
When disabled, this feature
will inhibit the run output and
allow the ETS solenoid
energize until the controller
receives a speed sensing
signal,
thus
preventing
possible
damage
from
starting the engine with no
speed sensing for
crank
disconnect and overspeed.
When engine oil pressure
sensor value is less than this
point, the low oil pressure
delay start. when the value is
zero, low oil pressure signal
is disabled. (its suited for oil
pressure sensor only)
When the value is zero, its a
warning
alarm,
not
a
shutdown alarm. (its suited
for oil pressure sensor only)
When engine temprature
sensor value is large than
this
point,
the
high
temperature delay start.
when the value is 140, high
temperature
signal
is
disabled. (its suited for
engine temperature sensor
only).
When the value is zero, its a
warning
alarm,
not
a
shutdown alarm. (its suited
Page 12 of 24
No
Item
44
(0-100)%
45
(12.0-40.0V)
33.0
46
(4.0-30.0V)
8.0
47
(0.0-30.0V)
6.0
48
Gens transient
(1-25S)
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
Digit input1
Digit input2
Digit input3
Digit input4
Digit input5
Digit input6
Digit input1 delay
Digit input2 delay
Digit input3 delay
Digit input4 delay
Digit input5 delay
Digit input6 delay
Digit output1
Digit output2
Digit output3
Digit output4
Communication addr
66
Temperature sensor
67
68
Select analog1
HGM610/620 MODULE
Setting Range
Default
10
(1-254)
13
14
15
02
05
10
2.0
2.0
0.0
1.0
2.0
0.0
08
10
11
2
1
(1-11)
(1-23)
(0.0-20.0S)
(1-60)
(1-11)
(1-5)
6
1
description
for
engine
temperature
sensor only).
When fuel level sensor value
is less than this point and
remain for 10 seconds, send
out warning alarm.
When generator battery
voltage is over than the point
and and remain
for 20
seconds, battery over vlltage
signal is active. its a warning
alarm.
When generator battery
voltage is less than the point
and and remain
for 20
seconds,
battery
under
vlltage signal is active. its a
warning alarm.
During generator is running,
when
charge
alternator
WL/D+ voltage is low than
this point and remain for 5
seconds,
generator
will
shutdown and alarm.
Generator voltage transient
delay
from
normal
to
abnormal
Auxiliary digital input
See below table 3
Transient delay
No
Item
Setting Range
69
Select analog2
(1-5)
70
Select analog3
(1-3)
71
Temperature unit
(1-2)
72
Pressure unit
(1-3)
73
Sensor curve
74
Select line
(1-2)
Default
description
1#. see behind table 4
Configurable analog sensor
1
2#. see behind table 4
Configurable analog sensor
2
3#. see behind table 4
Select display temperature
1
unit on LCD.
Select display oil pressure
1
unit on LCD.
Refer to the setting information behind.
Select mains or generator
1
sensing line.
Definition
not used
Common alarm
Open shutter
Excitate Gens
Fuel relay on
Crank relay on
Energised to stop
(ETS)
Idle control
10
Raise speed
11
Drop speed
HGM610/620 MODULE
description
Page 14 of 24
No.
Definition
12
Preheat output
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
Stop mode
Gens running
AUTO mode
Manual mode
Auto running
Manual running
Not used
Running on load
Not used
Close mains
Close gens
Open mains & gens
Low oil pressure
High temperture
Over speed
Under speed
30
Failed to start
31
Failed to stop
32
Emergency stop
33
PC emergency stop
34
Loss of speed
35
Failed to Charge
36
37
38
39
40
41
42
Over current
HGM610/620 MODULE
description
The designated programmable output relay will energize
during the preheat delay timer period until the engine start
to crank. The preheat output is typically used for an
engine starting aid such as glow plugs.
The designated programmable output relay will energize
when the engine has started and has reached crank
disconnect speed.
Its active when generator enter standby state.
Its active from entering warming to cooling down.
Its active in automation mode.
Its active in manual mode.
Generator is running in automation mode.
Generator is running in manual mode.
Generator is running on load.
Switch mains breaker on.
Switch generator breaker on.
Switch breaker off. the output delay is 5 seconds.
Low oil pressure shutdown alarm.
High engine temperture shutdown alarm.
Over speed shutdown alarm.
Under speed shutdown alarm.
If the engine does not fire after the pre-set number of
attempts has been made a shutdown will be initiated.
If the module detects the engine is still running when the
Fail to stop timer expires, its active.
Removal of the +VE DC Supply from the Emergency Stop
input initiates the following sequence, firstly it will initiate a
controlled shutdown of the Generator and prevent any
attempt to restart the Generator until the Emergency Stop
push-button has been reset. Secondly it removes the +VE
DC supply from both the Fuel Solenoid and Starter
Solenoid.
The emergency stop is come from PC (personal
Computer) or the monitor room.
Loss of speed shutdown alarm
If the module does not detect a voltage from the warning
light terminal on the auxiliary charge alternator, its active.
If the module detects that the plant DC supply has risen
above the high volts setting level, its active.
If the module detects that the plant DC supply has fallen
below the low volts setting level, its active.
When mains voltage is normal, thr output is active.
When generator voltage is normal, thr output is active.
When mains voltage is abnormal, thr output is active.
When generator voltage is abnormal, thr output is active.
If the module detects a generator output current in excess
of the pre-set trip the warning is initiated.
ISSUE 2009-02-18 Version 2.1
Page 15 of 24
No.
43
44
45
46
47
48
49
50
51
52
Definition
Digit input1 state
Digit input2 state
Digit input3 state
Digit input4 state
Digit input5 state
Digit input6 state
Alarm(delay 60s)
Mains closed port
Remote start port
Not used
53
54
55
description
When the input terminals is connected to VE DC, these
are active.
Shutdown alarm output. after 60 seconds it is inactive.
The inport state of mains closed.
The inport state of remote start.
The designated programmable output relay will energize
when any shutdown fault circuit has been activated.
The designated programmable output relay will energize
when any warning fault circuit has been activated.
If the fuel level detected by the fuel level sender falls
below the low fuel level setting, this warning will occur.
56
Not used
57
Not used
58
Not used
59
Not used
60
Not used
Note: The 38, 40, 50 item of HGM610 is Not used.
description
Definition
Not used
Over speed input
Low fuel level
Shutter status
5
6
7
Auxiliary warn
Auxiliary shutdown
Not used
9
10
11
12
13
14
15
16
17
18
19
20
Inhibit start
Gen closed input
Aux. charger fail
Low water level
high Temp input
Low OP input
Remote start input
Inhibit Load input
Low engine temp
Breaker tripped
Remote emerg.stop
High oil level
HGM610/620 MODULE
Page 16 of 24
No.
21
22
23
Definition
Low fuel pressure
Gen breaker open
Failed to sync
description
Auxiliary Low fuel pressure input.
Auxiliary Generator breaker open input.
Auxiliary Failed to sync input.
defined
1 not used
2 defined voltage type
3 defined resistive type
4 VDO 120 degree
5 DATCON 120 degree
Temperature
6 SG 120 degree
Sensor
7 DATCON high
8 DATCON high
9 MURPHY
10 CUMMINS
11 PT100
1 not used
2 defined volt_type
3 defined res_type
4 VDO 10 bar
5 DATCON 10 bar
Oil pressure
6 SG 10 bar
Sensor
7 VDO 5 bar
8 DATCON 7 bar
9 DATCON 5 bar
10 MURPHY 7 bar
11 CMB812
1 Not used
2 defined voltage type(Temperature)
Auxiliary
3 defined voltage type (Fuel level)
Sensor1
4 defined resistive type(emperature)
5 defined resistive type(Fuel level)
1 Not used
2 defined voltage type(Pressure)
3 defined voltage type(Temperature)
Auxiliary
Sensor2
4 defined resistive type(Pressure)
5
defined
resistive
type
(Temperature)
1 Not used
Auxiliary
2 Charger W/L
Sensor3
3 defined voltage type(oil Pressure)
description
1 Configurable
voltage
type input voltage range
is 0-30Vdc
2 Configurable
resistive
type input resistance
range is 0-9999 ohm
1 Configurable voltage
type
input
voltage
range is 0-30Vdc
2 Configurable resistive
type input resistance
range is 0-9999 ohm
1 Configurable
voltage
type input voltage range
is 0-5.0Vdc
2 Configurable
resistive
type input resistance
range is 0-9999 ohm
Note: please specify on ordering when Auxiliary Sensor3 is selected for defined voltage
type(Pressure).
HGM610/620 MODULE
Page 17 of 24
Setting Content
Magnetic Pickup
Charge Alternator D+(or WL)
Magnetic Pickup and Charge Alternator D+(or WL)
Generating Frequency
Magnetic Pickup and Generating Frequency
Generating Frequency and Charge Alternator D+(or WL)
Magnetic Pickup, Charge Alternator and Generating Frequency
7. SETTING PARAMETER
After the controller is powered up, press the key
1 History record
2 Set Date and time
3 Set Parameters
4 Information
5 Set Language/
1. History record
When looking for history record, press
button to lookup nest
record,press UP or DOWN to lookup previous or next item of current record.
The controller may store 99 records circularly. The record will be stored
when these below events has happen:
Emergency stop shutdown
High temperature shutdown
Low oil pressure shutdown
Over speed shutdown
Auxiliary shutdown alarm
Failed to start
Failed to stop
Loss of speed shutdown
Failed to charge shutdown
Generator under frequency shutdown
Low water level warning
Low fuel level warning
Generator voltage annormal shutdown
Under speed shutdown
Generator Over frequency shutdown
Start generator
3. Set parameters
The default password is 1234 when it leaves factory. The senior setting
password is fixed as 0318. When setting each item, after selecting this item,
press the key
HGM610/620 MODULE
or
Page 18 of 24
NOTE:
a Please set parameters in stop mode, else shutdown or other event
may occur.
b The over value point must be great than the under value.
c The configurable input 1 to 6 cant set as same item.The
configurable output 1 to 4 allow to set as same item.
d When the crank disconnect has been selected for charge WL,
Run output fail safe must set as Enabled .
e Configurable output2 cant been seted as Energise to stop,
Common alarm, Droop speed , Idle control, Open generator
etc,
because the output supply come from #27 terminal(Emergency
stop).
4. Information
LCD will display the controller software version, issue date. Note: press
the key DOWN will display the states of configurable input 1 to 6.
5. Set language
8. SENSOR CONFIG
1. if the used sensor curve is not same as the standard curve, please adjust in
Sensor curve.
2. When entering the sensor curve, X value (voltage or resistance ) must be from
small value to big value.
3. if the oil pressure sensor is not exist and the oil pressure alarm switch is exist,
please set Oil pressure sensor as not used, else low oil pressure shutdown will
occur.
4. if the sensor curve slope is positive, please according to the below curve Diagram
HGM610/620 MODULE
Page 19 of 24
kgf/cm2
bar
(1b/in2) psi
1Pa
1.0197210-5
110-5
1.4503810-4
1kgf/cm2
9.80665104
0.980665
14.2233
1bar
1105
1.01972
14.5038
1psi
6.89476103
7.030710-2
6.8947610-2
9. COMMUNICATION
10. SPECIFICATION
Operating Voltage
Power Consumption
<3W
(0 to 300)V (Single-Phase) or
(0 to 520)V (Three-Phase)
AC Generator Frequency
50 to 60Hz
1.0 to 70V
Max. 10000Hz
16Amp
DC24V
16Amp
DC24V
10Amp
DC24V
HGM610/620 MODULE
Page 20 of 24
16Amp
DC24V
10Amp
DC24V
16Amp
DC24V
16Amp
DC24V
16Amp
DC24V
Overall Dimension
186mm x139mm
Storage Condition
11. OPERATION
Before operation, inspections that are recommended as follows should be carried out:
a. Check and assure that all connections are correct, and that diameter of wire is
suitable;
b. The DC power supply of controller is equipped with fuse, and the positive supply (+Ve)
and negative supply (-Ve) connected with battery are connected correctly;
c. The emergency stop input is connected with the positive supply (+Ve) of the battery
through the NC terminal and fuse of emergency stop button;
d. The suitable operation should be taken to prevent the engine from crank success
(such as dismantling the connection of fuel), check and assure that it is correct, then
connect with battery, select manual mode, the controller will execute program;
e. Press down the starting button on the panel of controller , the engine will crank, after
starts have been carried out according to setting crank numbers, the controller sends
the signal that indicates crank failure; Press the Stop/Reset key to make the
controller resetting;
f. Restore the measure that prevents the engine from crank success (such as restoring
the connection of fuel), press down the starting button again, the engine will scrank, if
crank is normal, the generator will operate from idle operation (if idle has been set) to
normal operation. In the meantime, observe the operation situation of engine and the
voltage and frequency of the AC generator. If there is abnormal, stop the generator,
then check connections of each part according to this handbook;
g. Select automatic state through front panel, then switch on the mains voltage, the
controller switches over ATS (if it exist) to mains on load after pass through the mains
normal delay, after cooling time, and then shut down to go into standby state until the
mains is abnormal again;
h. After the mains is abnormal again, the Generator will automatically crank into normal
operation state, and then close generator relay, control the ATS to switch transfer to
HGM610/620 MODULE
Page 21 of 24
generator on load. If the situation is not same as described above, check the
connection of control part of the ATS according to this handbook;
i. If there are other questions, please contact the technical personnel of our company in
time.
HGM610/620 MODULE
Page 22 of 24
13. INSTALLATION
The controller is designed to panel installation mode, and it is fixed by clamps when
it is installed. The overall dimension and panel tapping dimension are given as follows:
14. TROUBLESHOOTING
Fault Symptom
Generator stop
Fail to crank
Fail to Start
HGM610/620 MODULE
Page 23 of 24