ATV 312 Quick Start
ATV 312 Quick Start
ATV 312 Quick Start
ENGLISH
S1A1094202
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read and understand this quick start guide before performing any procedure with this drive.
The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all
equipment.
Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools.
DO NOT touch unshielded components or terminal strip screw connections with voltage present.
DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.
Before servicing the drive:
- Disconnect all power, including external control power that may be present.
- Place a "DO NOT TURN ON" label on all power disconnects.
- Lock all power disconnects in the open position.
- WAIT 15 MINUTES to allow the DC bus capacitors to discharge.
- Measure the voltage of the DC bus between the PA/+ and PC/- terminals to ensure that the voltage is less than 42 Vdc.
- If the DC bus capacitors do not discharge completely, contact your local Schneider Electric representative. Do not repair or operate
the drive
Install and close all covers before applying power or starting and stopping the drive.
Failure to follow these instructions will result in death or serious injury.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider
Electric for any consequences arising out of the use of this product.
Information below is designed to use single drive connected to single motor with a motor cable length less than 50 meters (164 ft).
In any other case, consult the ATV312 installation manual (BBV46391) and programming manual (BBV46385) on www.schneider-electric.com.
Remove ATV312 from the packaging and check that it has not been damaged.
WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Check that the drive reference printed on the label matches the delivery note and corresponding purchase order.
Write the drive Model Reference: _____________ ___________and Serial Number: ____________________________
Check that the line voltage is compatible with the supply range of the drive.
Line voltage _______ Volts / Drive voltage range _______ Volts
Drive range: ATV312
M2 = 200/240 V single phase / ATV312
M3=200/240 V three-phase
ATV312
N4 = 380/500 V three-phase / ATV312
S6 = 525/600 V three-phase
8B0917121134
(a)
(a)
(a)
(b)
(a) 50 mm (2 in.)
(b)
10 mm (0.4 in.)
www.schneider-electric.com
1/4
S1A10942 - 02/2012
[REMOTE configuration]
AI 1
+10 v
CONF
M2
COM
REF
MON
200/240 V
ATV312
or
200/240 V
ATV312
2.2 K
See
SCCR annex
M3
ATV 312
OR
24 V
LI1
LI2
LI1
24 V
LI2
LIx
380/500 V
ATV312
N4
LI1: forward
LI2: reverse
525/600 V
ATV312
LI1: stop
LI2: forward
LIx: reverse
6 + 7 + 8 +
9.1
S6
[LOCAL configuration]
RUN
CAN
ERR
Do:
6 + 7 + 8 + 9.2
Ensure that Logic Inputs are not active (see Li1, Li2, Lix ).
ENT
Apply power to the drive.
At first power up, the drive displays nSt (3-wire control) or rdY (2 -wire control), after pushed
drive displays bFr.
On next start-ups, the drive displays nSt or rdY .
Code
bFr
UnS
drC[MOTOR CONTROL]
FrS
nCr
nSP
COS
www.schneider-electric.com
Description
Factory setting
50.0
2/4
Customer
setting
drive rating
50.0
drive rating
drive rating
drive rating
S1A10942 - 02/2012
Code
tUn
Description
Factory setting
[Auto Tunning]:
Auto-Tunning for UnS, FrS, nCr, nSP, nPr and COS
nO
DANGER
Customer
setting
DANGER
The Nominal Motor Parameters UnS, FrS, nCr, nSP, nPr and
COS must be correctly configured before starting auto-tuning.
If one or more of these parameters is modified after auto-tuning has
been performed, tUn will return to nO and the procedure must be
repeated.
Code
Description
Factory setting
ACC
[Acceleration]:
Acceleration time (s)
[Deceleration]:
Deceleration time (s)
[Low speed]:
Motor frequency at minimum reference (Hz)
[High speed]:
Motor frequency at maximum reference (Hz)
[Mot. therm. current]:
Nominal current on motor nameplate (A)
[Reverse assign.]:
Reverse assignment
[2 preset speeds]:
Preset speeds
[4 preset speeds]:
Preset speeds
[Summing ref. 2]
Analog input
3.0
dEC
SEt[SETTINGS]
LSP
HSP
ItH
rrS
PS2
PS4
SA2
Customer
setting
3.0
0.0
50.0
drive rating
LI2
LI3
LI4
AI2
Menu
CtL[COMMAND]
I-O[INPUTS / OUTPUTS CFG]
Code
Fr1
tCC
Description
[Ref.1 channel]:
Reference control
[2/3 wire control]:
Command control
Customer Setting
AlU1
LOC
3s
LOC
rdY
35.
1
[Output frequency] (Hz)
10
www.schneider-electric.com
3/4
S1A10942 - 02/2012
Menus structure
= ENT
MODE
ESC
3s
rEN
LOC
rdY
2s
ESC
3s
bFr
35.
Fr1
rdY
MODE
ENT
tCC
[SPEED REFERENCE]
rEF-
[SETTINGS]
SEt-
[MOTOR CONTROL]
drC-
I-O-
[COMMAND]
CtL-
[APPLICATION FUNCT.]
FUn-
[FAULT MANAGEMENT]
FLt-
[COMMUNICATION]
COM-
[MONITORING]
SUP-
MODE
Parameter selection
= ENT
ESC
SEt-
ESC
15.
ACC
ENT
ESC
ENT
dEC
26.
ENT
SFr
www.schneider-electric.com
A dash appears after menu codes to differentiate them from parameter codes.
Example:
[SETTINGS] (SEt-), ACC parameter.
26.
1 flash
(save)
4/4
S1A10942 - 02/2012