Features:

CBI2410A
DC UPS

INPUT

OUTPUT

PROTECTION

LOAD
OUTPUT

BATTERY
OUTPUT

OTHERS

Input: Single-phase 115 - 277 VAC


Output Load: power supply 24 VDC; 10 A
Output: Battery charging 24 VDC; 10 A
Suited for the following battery types:
Open Lead Acid, Sealed Lead Acid, lead Gel and Ni-Cd (option)
Automatic diagnostic of battery status.
Switching technology, output voltage 22-28.8 VDC
Three charging levels: Boost, trickle and recovery
Protection degree IP20 - DIN rail mountable

Cat. No.

CBI2410A

Nominal Input Voltage


Voltage range
Inrush Current ( Vn In nom. Load). I2t
Frequency
Input Current (115 230 VAC)
Internal fuse (factory replaceable)
External Fuse (recommended) MCB curve B

115 / 230 ~ 277 VAC


90-135 / 180-305 VAC
16 A 5 msec
47 63 Hz
3.3 ~ 2.2 A
6.3 A
16 A

Output Voltage (Vn) / Nominal Current (In)


Output Current In
Efficiency (at 50% of rated current)
Turn-On delay after applying input voltage
Start up with Strong Load (capacitive load)
Dissipation power load max

24 VDC / 10A
10 A
83 %
1.5 sec. (max)
Yes, Unlimited
28 W

Short-circuit protection
Over Load protection
Over Voltage Output protection
Over Temperature protection

Yes
Yes
Yes (typ. 35 VDC)
Yes

Output voltage (at In)


Nominal current Iload
Continuous current (without battery) Iload= In
Continuous current (with battery) Iload= In+ Ibatt
Max. Current Output Load (Main) Iload (4 sec.)
Max. Current Output Load (Back Up) Iload (4 sec.)
Push Button or Remote Input Control (RTCONN cable)
Time Buffering; min (switch output off without main input)
Protection alarm against total discharge
Threshold alarm for battery almost flat

22 ~ 28.8 VDC
1.1 x In A 5%
10 A
20 A
30 A max.
20 A max.
Start From Battery Without Main
: standard 5 min.: Require SW
19-20V DC battery
20-21 V DC battery

Boost charge (25 C) (at In)


Max. time Bust Charge
Min. time Bust Charge
Trickle charge (25 C) (at In)
Jumper Configuration battery type (V cell) Ni-Cd (optional)
Recovery Charge
Charging current max Ibatt
Charging current limiting Iadj
Reverse battery protection
Sulfated battery check
Detection of element in short circuit
Quiescent Current
Charging Curve automatic: IUoUo
Remote Input Control (RTCONN cable)

28.8 VDC
15 h
1 min.
27.5 VDC
2.23; 2.25; 2.27; 2.30; NiCd: 1.50 (20 elem.)
2 ~ 16 VDC
10 A 5%
20 100 % / Ibatt
Yes
Yes by Jumper
Yes
5 mA
3 stage
Boost /Trickle / Recovery

Ambient temperature (operation)


De Rating Ta > 50C
Ambient temperature Storage
Humidity at 25C no condensation
Cooling
MTBF (IEC 61709)

-25 +70C
- 2.5%(In) / C
-40 +85C
95%
Auto convention
> 300.000 h

For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.

154

CBI2410A
DC UPS
The Altech DC-UPS system is built to optimize power
management. The available power is automatically allocated
between load and battery, supplying power to the load is the first
priority. For high inrush applications the charging power will
reroute automatically to the load. In this case the maximum
available current on the load output is two times the value of the
device rated current.

Jumper for
Battery Type Selection

1 2 3 4

1 2 3 4

Signal Output Contacts

1 2 3 4

1 2 3 4

LOW BATTERY
OR BATTERY
REPLACEMENT

DIAGNOSIS
BATTERY
BRIDGE ONLY
START

115Vac

NiCd NiMh (1)

L N

Jumper for Functional Setting


Battery Life
Test On1
1 2 3 4

1
2
3

Fast Charge
Enable2
1 2 3 4

Jumper present: life test enabled.


Jumper present: fast test enabled.
Jumper present: fast recovery charge
enabled only for size 3. Possibility to
recharge the battery also when the
voltage is close to zero with the
maximum power of the device.

Yes - Optional
Yes - Optional
No

Environment
Insulation voltage (IN/OUT)
Insulation voltage (input / ground)
Insulation voltage (Output / ground)
Protection Class (EN/IEC 60529)
Pollution Degree Environment
Connection TB, Screw Terminal
Protection class (Ground Connected)
Dimensions (WxHxD)
2.95x4.53x5.32 in
Weight (approx.)

MAINS
OR
BACKUP

Gel
Battery (1)
1 2 3 4

MAINS
LOW BATTERY
OR
OR BATTERY
BACKUP REPLACEMENT

ADJ.

Gel
Battery

RJ45 Connection Input/Output


Temp. Comp. Battery (with ext. probe)
Remote monitoring display
Can Bus

1 2 3 4 5 6 7 8 9 10
+ +

Sealed
Lead High
1 2 3 4

Yes
Yes
Yes
1A 30 VDC/60 VAC
1mA @ 5 VDC

Open
Lead
Sealed
Lead Low

The Battery Care concept based on algorithms that achieve rapid


and automatic charging, battery optimization during charging
time, flat batteries recovery and real time diagnostic The Real
Time Auto-diagnostic system, monitors battery faults, sulfated
battery, short circuit battery elements, reverse polarity connection,
battery disconnect. This conditions are detected and identified by
the number of blinks of the diagnosis Led.

Main or Backup Power


Battery Power Low
Battery Fault
Max. Current Rating (Resistive Load)
Minimum Permissible Current Rating

3000 VAC
1605 VAC
500 VAC
IP20
2
2,5 mm (2414AWG)
Class I
100x115x135 mm

Battery

Out 1

CBI

In Vac

Load
Mains or Backup

Out 2

Battery Low or
Battery Replacement
Start From Battery

0.85 kg (1.9 Lbs)

Safety and EMC


IEC/EN 60335-2-29
EN60950 / UL1950 / CE
EN54-4
89/336/EEC
DIN41773
IEC 61000-6-4
IEC 61000-6-2

The Altech DC-UPS system is designed to charge and monitor all


battery types, by selecting the battery type via jumpers. The
predefined curves include Open Lead Acid, Sealed Lead Acid, Gel,
Ni-Cd (optional) battery types. The charging curve are
programmed to automatically switch between Recovery Charge,
Boost charge and Trickle charge. The continuous battery efficiency
monitoring, reduces battery damage risk and allows a safe
operation in permanent connection.

Voltage

Voltage / Current

Battery charger standard compliance


Safety standards compliance:
Fire Detection and alarm compliance
EMC Directive
Charging cycle
Emission
Immunity

Current

Recovery Charge

Fast / Boost Charge

Tickle / Float Charge

A compact and rugged metal case with DIN rail mounting bracket
provide an easy installation and an IP20 protection.

Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490