Cbi2410a PDF
Cbi2410a PDF
Cbi2410a PDF
CBI2410A
DC UPS
INPUT
OUTPUT
PROTECTION
LOAD
OUTPUT
BATTERY
OUTPUT
OTHERS
Cat. No.
CBI2410A
24 VDC / 10A
10 A
83 %
1.5 sec. (max)
Yes, Unlimited
28 W
Short-circuit protection
Over Load protection
Over Voltage Output protection
Over Temperature protection
Yes
Yes
Yes (typ. 35 VDC)
Yes
22 ~ 28.8 VDC
1.1 x In A 5%
10 A
20 A
30 A max.
20 A max.
Start From Battery Without Main
: standard 5 min.: Require SW
19-20V DC battery
20-21 V DC battery
28.8 VDC
15 h
1 min.
27.5 VDC
2.23; 2.25; 2.27; 2.30; NiCd: 1.50 (20 elem.)
2 ~ 16 VDC
10 A 5%
20 100 % / Ibatt
Yes
Yes by Jumper
Yes
5 mA
3 stage
Boost /Trickle / Recovery
-25 +70C
- 2.5%(In) / C
-40 +85C
95%
Auto convention
> 300.000 h
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
154
CBI2410A
DC UPS
The Altech DC-UPS system is built to optimize power
management. The available power is automatically allocated
between load and battery, supplying power to the load is the first
priority. For high inrush applications the charging power will
reroute automatically to the load. In this case the maximum
available current on the load output is two times the value of the
device rated current.
Jumper for
Battery Type Selection
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
LOW BATTERY
OR BATTERY
REPLACEMENT
DIAGNOSIS
BATTERY
BRIDGE ONLY
START
115Vac
L N
1
2
3
Fast Charge
Enable2
1 2 3 4
Yes - Optional
Yes - Optional
No
Environment
Insulation voltage (IN/OUT)
Insulation voltage (input / ground)
Insulation voltage (Output / ground)
Protection Class (EN/IEC 60529)
Pollution Degree Environment
Connection TB, Screw Terminal
Protection class (Ground Connected)
Dimensions (WxHxD)
2.95x4.53x5.32 in
Weight (approx.)
MAINS
OR
BACKUP
Gel
Battery (1)
1 2 3 4
MAINS
LOW BATTERY
OR
OR BATTERY
BACKUP REPLACEMENT
ADJ.
Gel
Battery
1 2 3 4 5 6 7 8 9 10
+ +
Sealed
Lead High
1 2 3 4
Yes
Yes
Yes
1A 30 VDC/60 VAC
1mA @ 5 VDC
Open
Lead
Sealed
Lead Low
3000 VAC
1605 VAC
500 VAC
IP20
2
2,5 mm (2414AWG)
Class I
100x115x135 mm
Battery
Out 1
CBI
In Vac
Load
Mains or Backup
Out 2
Battery Low or
Battery Replacement
Start From Battery
Voltage
Voltage / Current
Current
Recovery Charge
A compact and rugged metal case with DIN rail mounting bracket
provide an easy installation and an IP20 protection.
Altech Corp. 35 Royal Road Flemington, NJ 08822-6000 Phone (908)806-9400 FAX (908)806-9490
155