Deltapilot M
Deltapilot M
Deltapilot M
14
No. 71260308
Products
Solutions
Services
Technical Information
Deltapilot M
FMB50, FMB51, FMB52,
FMB53
Hydrostatic level measurement
Deltapilot M FMB50/51/52/53
Table of contents
Document information . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Terms and abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Total error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Warm-up period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Function and system design . . . . . . . . . . . . . . . . . . . . . .7
Device selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Level measurement in closed tanks with pressure overlay . . 10
Density measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Level measurement with automatic density correction (with
media changing in the tank) . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Electrical differential pressure measurement with gauge
pressure sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Communication and data processing . . . . . . . . . . . . . . . . . . . . 12
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Signal range 4 to 20 mA HART . . . . . . . . . . . . . . . . . . . . . . .
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Load - 4 to 20 mA HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dead time, time constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dynamic behavior: current output . . . . . . . . . . . . . . . . . . . . . . .
Dynamic behavior: HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dynamic behavior: PROFIBUS PA . . . . . . . . . . . . . . . . . . . . . . .
Dynamic behavior: FOUNDATION Fieldbus . . . . . . . . . . . . . . .
Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Firmware version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Protocol-specific data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14
14
14
14
15
15
15
16
16
16
16
17
17
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start-up current HART. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Residual ripple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Influence of power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overvoltage protection (optional) . . . . . . . . . . . . . . . . . . . . . . .
21
21
22
22
22
22
23
24
24
24
24
25
Performance characteristics . . . . . . . . . . . . . . . . . . . . 26
Reference operating conditions . . . . . . . . . . . . . . . . . . . . . . . . .
Influence of orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Calibration position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Reference accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Thermal change in the zero output and the output span . . . .
Total performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Long-term stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
26
26
26
26
26
27
27
27
28
28
28
29
29
30
31
31
31
31
Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Ambient temperature limits . . . . . . . . . . . . . . . . . . . . . . . . . . .
Storage temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Climate class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electromagnetic compatibility . . . . . . . . . . . . . . . . . . . . . . . . . .
32
32
32
32
32
32
Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Process temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Lateral load FMB51 (static) . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Pressure specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Mechanical construction . . . . . . . . . . . . . . . . . . . . . . . 34
Device height . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
F31 housing, aluminum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
F15 housing, stainless steel (hygienic) . . . . . . . . . . . . . . . . . . . 35
Process connections FMB50, FMB51, FMB52 . . . . . . . . . . . . 35
Process connections FMB50, FMB51, FMB52 . . . . . . . . . . . . 36
Process connections FMB50, FMB51, FMB52 - continued . . 37
Process connections FMB50, FMB51, FMB52 - continued . . 38
Process connections FMB50 - continued . . . . . . . . . . . . . . . . . 39
Process connections FMB50 - continued . . . . . . . . . . . . . . . . 40
Process connections FMB51 (rod version) . . . . . . . . . . . . . . . . 42
Process connections FMB52 (cable version) . . . . . . . . . . . . . . 44
Dimensions of FMB53 with F31 housing, suspension clamp and
mounting bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Dimensions of FMB53 with F15 housing, suspension clamp and
mounting bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Wall and pipe mounting with "Separate housing" version . . . 48
Materials not in contact with process . . . . . . . . . . . . . . . . . . . . 51
Materials in contact with the process . . . . . . . . . . . . . . . . . . . . 54
Operability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Onsite operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating languages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System integration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
57
57
59
59
60
Endress+Hauser
Deltapilot M FMB50/51/52/53
Ordering information . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Configuration data sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Suspension clamp (FMB53 only) . . . . . . . . . . . . . . . . . . . . . . . .
Extension cable shortening kit (FMB53 only) . . . . . . . . . . . . .
M12 connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Welding necks and Weld-in tool flanges . . . . . . . . . . . . . . . . .
Adapter Uni for FMB50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
66
66
66
66
67
Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Brief Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Functional safety manual (SIL) . . . . . . . . . . . . . . . . . . . . . . . . .
Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation/Control Drawings . . . . . . . . . . . . . . . . . . . . . . . . . .
Combination certificate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overfill protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
68
68
68
68
68
69
69
69
Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . . . 70
HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
PROFIBUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
FOUNDATION Fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Endress+Hauser
Deltapilot M FMB50/51/52/53
Document information
Symbols used
Safety symbols
Symbol
Meaning
DANGER
A0011189-EN
WARNING
A0011190-EN
CAUTION
A0011191-EN
NOTICE
A0011192-EN
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.
NOTE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
Electrical symbols
Symbol
Meaning
Direct current
A terminal at which DC voltage is present or through which direct current flows.
A0018335
A0018336
Alternating current
A terminal at which alternating voltage is present or through which alternating current
flows.
A0018337
A0018338
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a
grounding system.
Protective ground connection
A terminal which must be connected to ground prior to establishing any other connections.
A0018339
A0011201
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a
potential equalization line or a star grounding system depending on national or company
codes of practice.
Tool symbols
Symbol
Meaning
Phillips head screwdriver
A0011219
Flat-blade screwdriver
A0011220
Torx screwdriver
A0013442
Hexagon wrench
A0011222
Allen screw
A0011221
Endress+Hauser
Deltapilot M FMB50/51/52/53
Meaning
Permitted
Indicates procedures, processes or actions that are permitted.
A0011182
Preferred
Indicates procedures, processes or actions that are preferred.
A0011183
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011184
Tip
Indicates additional information.
A0011193
Reference to documentation
Refers to the corresponding device documentation.
A0015483
Reference to page
Refers to the corresponding page number.
A0015484
Reference to graphics
Refers to the corresponding graphic number and page number.
A0015486
, ...
Series of steps
Help in the event of a problem
A0015488
Symbols in graphics
Symbol
Meaning
1, 2, 3, 4 etc.
,
Series of steps
A, B, C, D etc.
Views
Sections
Endress+Hauser
, ...
Hazardous area
Indicates the hazardous area.
A0011187
Deltapilot M FMB50/51/52/53
Term/abbreviation
Explanation
MWP
OPL
The OPL (over pressure limit = sensor overload limit) for the
sensor depends on the lowest-rated element, with regard to
pressure, of the selected components, i.e. the process
connection has to be taken into consideration in addition to
the measuring cell. Pay attention to the pressure-temperature
dependence also. For the relevant standards and additional
notes, see section " 33".
LRL
URL
LRV
URV
TD
Turn down
Case 1:
Lower range value (LRV) Upper range
value (URV)
1=2
LRL
Example:
Lower range value (LRV) = 0 mbar
Upper range value (URV) = 40 mbar (0.6 psi)
Nominal value (URL) = 400 mbar (6 psi)
LRV
URV
URL
Turn down:
TD = URL /URV:1
Set span:
URV LRV = 40 mbar (0.6 psi)
This span is based on the zero point.
5
A0019783
Case 2:
Lower range value (LRV) Upper range
value (URV)
1=2
LRL
Example:
Lower range value (LRV) = 200 mbar (3 psi)
Upper range value (URV) = 0 bar
Nominal value (URL) = 400 mbar (6 psi)
LRV
URV
URL
Turn down:
TD = URL /(LRV) = 2:1
Set span:
URV LRV = 200 mbar (3 psi)
This span is based on the zero point.
5
A0016451
Set span
Span based on zero point
Nominal value upper range limit (URL)
Nominal measuring range
Sensor measuring range
Endress+Hauser
Deltapilot M FMB50/51/52/53
FMB51
FMB50
A0023537
Compact version
FMB52
A0023538
Rod version
FMB53
A0023539
Cable version
A0023540
Field of application
Level measurement
Pressure measurement
Industries
Process connections
Thread
Flanges
Flush-mounted hygienic
connections
Measuring ranges
From 0.1 to +0.1 (-1.5 to +1.5 psi) bar to 1 bar to +10 bar (-15 to 150 psi)
OPL
10 to +100 C (+14 to
+212F) (+135 C (275F) for
30 minutes maximum)
Reference accuracy
Supply voltage
Output
Options
Specialties
Endress+Hauser
Thread
Flanges
10 to +85 C
(+14 to +185F)
Thread
Flanges
Environment (freshwater
and wastewater)
Suspension clamp
Deltapilot M FMB50/51/52/53
74 -
TYPE EL
February 2010
A0023536
A0020029
Endress+Hauser
Deltapilot M FMB50/51/52/53
Measuring principle
patm
phydr.
h~p
h
h=
pges
p
rg
patm
1
p = patm + phydr.
3
patm
A0023541
g
h
p ges
p atm
p hydr.
p mess
Gravitational acceleration
Level height
Total pressure = hydrostatic pressure + atmospheric pressure
Atmospheric pressure
Hydrostatic pressure
Measured pressure in the measuring cell = hydrostatic pressure
Density of the medium
Due to its weight, a liquid column creates hydrostatic pressure. If the density is constant, the
hydrostatic pressure depends solely on the height h of the liquid column.
The CONTITE measuring cell, which works on the principle of the gauge pressure sensor, constitutes
the core of Deltapilot M. In contrast to conventional gauge pressure sensors, the precision measuring
element (2) in the CONTITE measuring cell is absolutely protected, situated between the process
isolating diaphragm (3) and the rear isolating membrane (1). Thanks to this hermetic sealing of the
measuring element, the CONTITE measuring cell is absolutely insensitive to condensate/
condensation and aggressive gases. The pressure applied is transferred from the process isolating
diaphragm to the measuring element by means of an oil without any loss in pressure.
Any measured errors due to fluctuations in temperature are compensated for in the electronics unit by
means of the sensor temperature.
A linearization function with max. 32 points, based on a table entered either manually or
semi-automatically, can be activated locally or remotely. This function facilitates measurement in
engineering units, and provides a linear output signal for spherical and horizontal cylindrical vessels,
and vessels with a conical outlet.
Endress+Hauser
Deltapilot M FMB50/51/52/53
You can determine the differential pressure in tanks with pressure overlay using two Deltapilot M. The
pressure measured values of the two probes are sent to a signal processing unit such as
Endress+Hauser RMA or a PLC. The signal processing unit or PLC determines the difference in pressure
and uses this to calculate the level and the density where necessary.
1
A0023542
Deltapilot 1 measures the total pressure (hydrostatic pressure and top pressure)
Deltapilot 2 measures the top pressure
Signal processing unit determines the difference in pressure and uses this to calculate the level
NOTICE
Measured errors can occur.
Large measured errors can occur if the ratio of the level to the top pressure is >1:6. This does not affect
reproducibility.
When selecting the measuring cell, make sure you select measuring ranges that are sufficiently
wide ( see example).
Example:
Max. hydrostatic pressure = 600 mbar (9 psi)
Max. top pressure (Deltapilot 2) = 300 mbar (4.5 psi)
Max. total pressure, measured with Deltapilot 1 = 300 mbar (4.5 psi) + 600 mbar (9 psi) = 900 mbar
(13.5 psi) measuring cell to be selected: 0 to 1200 mbar (0 to 18 psi)
Max. pressure, measured with Deltapilot 2: 300 mbar (4.5 psi) measuring cell to be selected:
0 to 400 mbar (6 psi)
NOTICE
Possibility of probe 2 flooding during differential pressure measurement.
Measured errors can occur.
When installing, make sure that probe 2 cannot be flooded.
10
Endress+Hauser
Deltapilot M FMB50/51/52/53
Density measurement
You can measure the density in tanks with pressure overlay using two Deltapilot M and a signal
processing unit or a PLC. The signal processing unit or the PLC calculates the density from the known
distance between the two Deltapilot M devices h and the two measured values p1 and p2.
3
p2
p1
1
A0023544
Level measurement with automatic density correction is possible in conjunction with a limit switch
such as Liquiphant and a PLC. The limit switch always switches at the same level. In the switch point,
the signal processing unit determines the corrected density from the pressure of the Deltapilot M
currently measured and the known distance between Deltapilot M and the limit switch. The signal
processing unit then calculates the level from the new density and the measured pressure of the
Deltapilot M.
1
A0023546
Endress+Hauser
Deltapilot M
Liquiphant
PLC
11
Deltapilot M FMB50/51/52/53
Electrical differential
pressure measurement with
gauge pressure sensors
FXN 520
Deltapilot M
1
Fieldgate
FXA520
Multidrop-Connector
FXN520
2
A0023549
Shut-off valves
e.g. filter
In the example given, two Deltapilot M devices (each with a gauge pressure sensor) are interconnected.
The pressure difference can thus be measured using two independent Deltapilot M devices.
! WARNING
Risk of explosion!
If using intrinsically safe devices, strict compliance with the rules for interconnecting intrinsically
safe circuits as stipulated in IEC60079-14 (proof of intrinsic safety) is mandatory.
12
Endress+Hauser
Deltapilot M FMB50/51/52/53
Input
Measured variable
Hydrostatic pressure
Measuring range
Nominal
value
Range limit
Smallest
calibratable span
(preset at the factory) 1)
MWP
OPL
Vacuum
resistance 2)
Option 3)
lower (LRL) 4)
upper (URL)
[bar (psi)]
[bar (psi)]
[bar (psi)]
[bar (psi)]
[bar (psi)]
[bar (psi)]
[barabs (psiabs)]
0.1 (1.5)
0.1 (-1.5)
+0.1 (+1.5)
0.01 (0.15)
2.7 (40.5)
4 (60)
0.4 (6)
0.4 (-6)
+0.4 (+6)
0.02 (0.3)
5.3 (79.5)
8 (120)
0.01/0.04
(0.145/0.6)
1.2 (18)
1 (-15)
+1.2 (+18)
0.06 (1)
16 (240)
24 (360)
1H
4 (60)
1 (-15)
+4 (+60)
0.2 (3)
16 (240)
24 (360)
1M
10 (150)
1 (-15)
+10 (+150)
0.5 (7.5)
27 (405)
40 (600)
1P
Synthetic oil/
Inert oil
1C
1F
1)
2)
3)
4)
By default, the device is set to a lower range limit of 0 bar. Please specify in the order if the lower range limit is to be set to a different default value.
Endress+Hauser
13
Deltapilot M FMB50/51/52/53
Output
Output signal
Output
4 to 20mA HART
PROFIBUS PA
FOUNDATION Fieldbus
1)
Signal range
4 to 20 mA HART
3.8 to 20.5 mA
Signal on alarm
As per NAMUR NE 43
4 to 20 mA HART
Options:
Max. alarm: can be set from 21 to 23 mA (Factory setting: 22 mA)
Hold measured value: last measured value is held
Min. alarm: 3.6 mA
PROFIBUS PA: can be set in the Analog Input block,
Options: Last Valid Out Value (factory setting), Fail-safe Value, Status Bad
FOUNDATION Fieldbus: can be set in the Analog Input block,
Options: Last Good Value, Fail-safe Value (factory setting), Wrong Value
Load - 4 to 20 mA HART
R Lmax
[W]
1456
1239
804
369
11.5
20
30
40 45 U
[V]
2
3
R Lmax U 11.5 V
23 mA
A0023090
Load diagram
1
2
RLmax
U
When operating via a handheld terminal or via a PC with an operating program, a minimum
communication resistance of 250 must be taken into account.
14
Endress+Hauser
Deltapilot M FMB50/51/52/53
I
100 %
90 %
63 %
t1
t2
t
t3
A0019786
Dynamic behavior:
current output
Type
max.
FMB50
60
90
210
max.
FMB51
FMB52
FMB53
500
250
220
310
370
1020
1110
1170
660
910
1460
1710
Type
min.
max.
min.
max.
FMB50
FMB51
FMB52
FMB53
Reading cycle
Acyclic: max. 3/s, typical 1/s (depends on command # and number of preambles)
Cyclic (Burst): max. 3/s, typical 2/s
The Deltapilot M commands the BURST MODE function for cyclic value transmission via the HART
communication protocol.
Cycle time (update time)
Cyclic (Burst): min. 300 ms
Response time
Acyclic: min. 330 ms, typical 590 ms (depends on command # and number of preambles)
Cyclic (Burst): min. 160 ms, typical 350 ms (depends on command # and number of preambles)
Endress+Hauser
15
Deltapilot M FMB50/51/52/53
Dynamic behavior:
PROFIBUS PA
Type
min.
max.
min.
max.
FMB50
FMB51
FMB52
FMB53
95
185
245
1195
1285
1345
535
785
1635
1885
Reading cycle
Cyclic: max. 30/s (dependent on the number and type of function blocks used in a closed-control
loop)
Acyclic: typical 25/s
Cycle time (update time)
min. 100 ms
The cycle time in a bus segment in cyclic data communication depends on the number of devices, on
the segment coupler used and on the internal PLC cycle time.
Response time
Cyclic: approx. 8 to 13 ms (depends on Min. Slave Interval)
Acyclic: approx. 23 to 35 ms (depends on Min. Slave Interval)
Dynamic behavior:
FOUNDATION Fieldbus
Type
min.
max.
min.
max.
FMB50
FMB51
FMB52
FMB53
105
195
255
1105
1195
1255
545
795
1545
1795
Reading cycle
Cyclic: max. 10/s (dependent on the number and type of function blocks used in a closed-control
loop)
Acyclic: typical 5/s
Cycle time (update time)
Cyclic: min. 100 ms
Response time
Cyclic: max. 20 ms (for standard bus parameter settings)
Acyclic: typical 70 ms (for standard bus parameter settings)
Damping
Firmware version
Designation
Option 1)
76
77
78
1)
16
Endress+Hauser
Deltapilot M FMB50/51/52/53
Galvanic isolation
The following devices have a galvanic isolation between electronic and probe:
FMB51, FMB52, FMB53
FMB50 with separate housing
Protocol-specific data
HART
Manufacturer ID
17 (11 hex)
35 (23 hex)
Device Revision
HART specification
DD Revision
01 (Dutch)
02 (Russian)
HART load
Min. 250
Supported functions
Burst mode
Additional Transmitter Status
Device Locking
Alternative operating modes
PROFIBUS PA
Manufacturer ID
17 (11 hex)
Ident number
1554 hex
Profile Version
3.02
SW Version 01.00.zz
GSD Revision
DD Revision
GSD File
DD Files
Output values
Endress+Hauser
17
Deltapilot M FMB50/51/52/53
Input values
Supported functions
1)
0x1023
Device Revision
01 (hex)
DD Revision
0x01021
CFF Revision
0x000102
ITK Version
5.2.0
IT067500
Yes
Number of VCRs
44
50
40
44
Client VCRs
Server VCRs
Source VCRs
Sink VCRs
Subscriber VCRs
12
Publisher VCRs
19
Link settings
18
Slot time
12
40
Endress+Hauser
Deltapilot M FMB50/51/52/53
Transducer Blocks
Block
Content
Output values
TRD1 Block
Diagnostic
Block
Display Block
No output values
Function blocks
Endress+Hauser
Block
Content
Functionality
Resource
Block
enhanced
Analog Input
Block 1
Analog Input
Block 2
2
The AI Block receives the measuring data from
the Sensor Block, (selectable via a channel
number) and makes the data available to other
function blocks at its output. Enhancement:
digital outputs for process alarms, fail safe mode.
25 ms
enhanced
Digital Input
Block
20 ms
Standard
Digital Output This block converts the discrete input and thus
Block
initiates an action (selectable via a channel
number) in the DP Flow Block or in the TRD1
Block. Channel 20 resets the counter for max.
pressure transgressions value and Channel 21
resets the Totalizer.
20 ms
Standard
PID Block
40 ms
Standard
Arithmetic
Block
35 ms
Standard
30 ms
Standard
19
Deltapilot M FMB50/51/52/53
Block
Content
Functionality
Signal
Characterizer
Block
40 ms
Standard
Integrator
Block
35 ms
Standard
20
YES
20
Endress+Hauser
Deltapilot M FMB50/51/52/53
Power supply
! WARNING
Incorrect connection can limit electrical safety!
When using the measuring device in hazardous areas, installation must comply with the
corresponding national standards and regulations and the Safety Instructions or Installation or
Control Drawings 68 ff, "Safety instructions" and "Installation/Control Drawings" ordering
features.
All explosion protection data are given in separate documentation which is available upon request.
The Ex documentation is provided with all Ex-systems as standard 68 ff, "Safety instructions"
and "Installation/Control Drawings" ordering features.
According to IEC/EN61010 a suitable disconnector has to be installed for the device
HART: Overvoltage protection HAW569-DA2B for the non-hazardous area, ATEX II 2 (1) Ex ia IIC
and IEC Ex ia can be ordered as an option (see "Ordering information" ordering feature).
Protective circuits against reverse polarity, HF influences and overvoltage peaks are installed.
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also
provides the power supply.
Terminal assignment
- +
2
5
4
3
A0023505
Electrical connection
1
2
3
4
5
6
7
Supply voltage
4 to 20 mA HART
Type of protection
Supply voltage
Intrinsically safe
11.5 ... 30 V DC
Endress+Hauser
21
Deltapilot M FMB50/51/52/53
PROFIBUS PA
Version for non-hazardous areas: 9 to 32 V DC
FOUNDATION Fieldbus
Version for non-hazardous areas: 9 to 32 V DC
Current consumption
Electrical connection
Degree of protection
Option 1)
M20 gland
G " thread
M12 plug
7/8" plug
IP65
2)
1)
2)
PROFIBUS PA
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also
provides the power supply. For further information on the network structure and grounding, and for
further bus system components such as bus cables, see the relevant documentation, e.g. Operating
Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and the
PNO Guideline.
FOUNDATION Fieldbus
The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also
provides the power supply. For further information on the network structure and grounding and for
further bus system components such as bus cables, see the relevant documentation, e.g. Operating
Instructions BA00013S "FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus Guideline.
Terminals
Cable entry
Type
Clamping area
Plastic M20x1.5
22
Endress+Hauser
Deltapilot M FMB50/51/52/53
Connector
+
3
1 2 3
Han7D
BN BU GNYE
+
A0023097
Material: PA 6.6
Devices with Harting plug Han7D
6
1
5
3
Han7D
+
A0019990
A
B
4
1
3
2
PIN
Meaning
Signal +
Not assigned
Signal
Earth
A0011175
Endress+Hauser offers the following accessories for devices with an M12 plug:
Plug-in jack M 12x1, straight
Material: body PA; coupling nut CuZn, nickel-plated
Endress+Hauser
23
Deltapilot M FMB50/51/52/53
PIN
Meaning
Signal
Signal +
Not assigned
Shield
A0011176
HART
Endress+Hauser recommends using twisted, shielded two-wire cables.
The cable outer diameter depends on the cable entry used.
PROFIBUS PA
Use a twisted, shielded two-wire cable, preferably cable type A
For further information on the cable specifications, see Operating Instructions BA00034S
"PROFIBUS DP/PA: Guidelines for planning and commissioning", the PNO Guideline 2.092
"PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).
FOUNDATION Fieldbus
Use a twisted, shielded two-wire cable, preferably cable type A
For further information on the cable specifications, see Operating Instructions BA00013S
"FOUNDATION Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).
Start-up current HART
12 mA or 22 mA (selectable)
Residual ripple
0.001 % of URL/V
24
Endress+Hauser
Deltapilot M FMB50/51/52/53
Overvoltage protection
(optional)
The device can be fitted with overvoltage protection. The overvoltage protection is mounted at the
factory on the housing thread (M20x1.5) for the cable gland and is approx. 70 mm (2.76 in) in length
(take additional length into account when installing). The device is connected as illustrated in the
following graphic.
For details refer to TI001013KEN, XA01003KA3 and BA00304KA2.
Ordering information:
Product Configurator, "Mounted accessories" ordering feature, option NA
+
A
1
+
B
rt
sw
+
-
A0023111
A
B
1
2
3
4
Endress+Hauser
25
Deltapilot M FMB50/51/52/53
Performance characteristics
Reference operating
conditions
Influence of orientation
< 2.3 mbar (0.0345 psi) when using synthetic oil (FDA)
< 5 mbar (0.075 psi) when using inert oil
Position-dependent zero point shift can be corrected 28, "General installation instructions"
ordering feature.
Calibration position
A0023545
FMB50
To minimize the effect of the orientation (e.g. in the case of vertical device installation), position offset
is preset at the factory.
Resolution
Current output: 1 A
Display: can be set (factory setting: presentation of the maximum accuracy of the transmitter)
Reference accuracy
The reference accuracy comprises the non-linearity according to limit point setting, hysteresis and
non-reproducibility as per IEC 60770. The data refer to the calibrated span.
Reference accuracy in % of the calibrated span
Measuring cell
TD
"Standard" option1)
"Platinum" option 1)
TD 1:1 to TD 2:1
TD > 2:1 to TD 4:1
< 0.2
< 0.1 x TD
< 0.15
< 0.075 x TD
TD 1:1 to TD 4:1
TD > 4:1 to TD 10:1
< 0.2
< 0.05 x TD
< 0.15
< 0.0375 x TD
TD 1:1 to TD 2:1
TD > 2:1 to TD 12:1
< 0.2
< 0.1 x TD
< 0.1
< 0.05 x TD
TD 1:1 to TD 4:1
TD > 4:1 to TD 20:1
< 0.2
< 0.05 x TD
< 0.1
< 0.025 x TD
TD 1:1 to TD 2.5:1
TD > 2.5:1 to TD 20:1
< 0.2
< 0.08 x TD
< 0.1
< 0.04 x TD
1)
26
Endress+Hauser
Deltapilot M FMB50/51/52/53
Version
Measuring cell
-10 to +60 C
(+14 to +140F)
60 to 85 C
(140 to 185F)
Only FMB50:
85 to 100 C
(185 to 212F)
FMB50/51/52/53
Total performance
The "Total performance" specification comprises the non-linearity including hysteresis, nonreproducibility as well as the thermal change in the zero point.
Total performance in % of the URL
Version
Measuring cell
-10 to +60 C
60 to 85 C
(+14 to +140F) (140 to 185F)
85 to 100 C
(185 to 212F)
FMB50
FMB51/52/53 snap-on
< 0.35
< 0.45
< 0.6
FMB51/52/53 welded
< 0.8
<1
< 1.4
< 0.35
< 0.45
< 0.6
< 0.2
< 0.25
FMB50/51/52/53
Long-term stability
Total error
Measuring cell
The total error comprises the long-term stability and the total performance:
Measuring cell
Warm-up period
Endress+Hauser
Snap-on: 0.63
Welded: 1.0
0.61
0.27
0.25
4 to 20 mA HART:
FMB50 = 5 s
FMB51/FMB52/FMB53 = 8 s
PROFIBUS PA: 8 s
FOUNDATION Fieldbus: 20 s (after a TOTAL-reset 45 s)
27
Deltapilot M FMB50/51/52/53
Installation
General installation
instructions
Level measurement
Always install the device below the lowest measuring point.
Do not install the device at the following positions:
in the filling curtain
in the tank outflow
or at a point in the tank that can be affected by pressure pulses from the agitator
The calibration and functional test can be carried out more easily if you mount the device
downstream of a shutoff device.
Deltapilot M must be included in the insulation for media that can harden when cold.
Pressure measurement in gases
Mount Deltapilot M with shutoff device above the tapping point so that any condensate can flow into
the process.
Pressure measurement in steams
Mount Deltapilot M with siphon above the tapping point.
Fill the siphon with liquid before commissioning.
The siphon reduces the temperature to almost the ambient temperature.
Pressure measurement in liquids
Mount Deltapilot M with the shutoff device below or at the same level as the tapping point.
28
When mounting rod and cable versions, make sure that the probe head is located at a point as free
as possible from flow. To protect the probe from impact resulting from lateral movement, mount the
probe in a guide tube (preferably made of plastic) or secure it with a clamping fixture.
In the case of devices for hazardous areas, comply strictly with the safety instructions when the
housing cover is open.
The length of the extension cable or the probe rod is based on the planned level zero point.
The height of the protective cap must be taken into consideration when designing the layout of the
measuring point. The level zero point (E) corresponds to the position of the process isolating
diaphragm.
Level zero point = E; top of the probe = L.
17 (0.67)
FMB51/FMB52/FMB53
Endress+Hauser
Deltapilot M FMB50/51/52/53
238 (9.37)
61 (2.4)
A0023566
Supplementary installation
instructions
Endress+Hauser offers a mounting bracket for installing the device on pipes or walls. The mounting
bracket is
included in the delivery for the FMB50/51/52 with a separate housing (available for order via
feature 600) and for the FMB53
available for order as a separate accessory (Part No.: 71102216).
For the dimensions, see 48.
Endress+Hauser
29
Deltapilot M FMB50/51/52/53
With the "separate housing" version, you are able to mount the housing with the electronics insert at a
distance from the measuring point. This allows for trouble-free measurement:
Under particularly difficult measuring conditions (at installation locations that are cramped or
difficult to access)
If rapid cleaning of the measuring point is required
If the measuring point is exposed to vibrations
You can choose between different cable versions:
PE (2 m (6.6 ft), 5 m (16 ft) and 10 m (33 ft))
FEP (5 m (16 ft)).
Ordering information:
Product Configurator, "Separate housing" ordering feature
Product Configurator, "Enclosed accessories" ordering feature, option PA
For the dimensions, see 48.
4
3
r 120 (4.72)
A0023567
Process connection with sensor - see the following section for the degrees of protection
Cable, both ends are fitted with a socket
Mounting bracket provided, suitable for pipe and wall mounting (for pipes from 1 1/4" up to 2" diameter)
Housing with electronic insert - degrees of protection 32 ff
Degree of protection for the process connection and sensor with the use of
FEP cable:
IP 69K
IP 66 NEMA 4/6P
IP 68 (1.83 mH2O for 24 h) NEMA 4/6P
PE cable:
IP 66 NEMA 4/6P
IP 68 (1.83 mH2O for 24 h) NEMA 4/6P
Technical data of the PE and FEP cable:
Minimum bending radius: 120 mm (4.72 in)
Cable extraction force: max. 450 N (101 lbf)
Resistance to UV light
Use in hazardous area:
Intrinsically safe installations (Ex ia/IS)
FM/CSA IS: for Div.1 installation only
30
Endress+Hauser
Deltapilot M FMB50/51/52/53
Oxygen applications
Oxygen and other gases can react explosively to oils, grease and plastics. As a result, the following are
some of the precautions that must be taken:
All components of the system, such as measuring devices, must be cleaned in accordance with the
BAM (DIN 19247) requirements.
Depending on the materials used, a certain maximum temperature and maximum pressure must not
be exceeded for oxygen applications. The maximum temperature Tmax for oxygen applications is
60 C (140F).
The devices suitable for gaseous oxygen applications are listed in the following table with the
specification pmax.
Order code for devices1) cleaned for
oxygen applications
FMB50 2)
FMB51 )
1)
2)
3)
13, "Measuring range" ordering feature and 34 ff, "Mechanical construction" ordering feature
4)
PWIS cleaning
Special cleaning of the transmitter to remove paint-wetting substances, for use in paint shops, for
instance.
Ordering information:
Product Configurator, "Service" ordering feature, option HC
The stability of the materials used must be checked before using them in the medium.
The protective cap of the process isolating diaphragm must be removed if necessary (FMB51/FMB52/
FMB53).
With regard to materials in which hydrogen formation takes place (e.g. digested sludge), hydrogen
atoms can diffuse through the metal process isolating diaphragm. This can result in incorrect
measurement results.
Endress+Hauser offers process isolating diaphragms with a gold/rhodium coating for such instances.
Ordering information:
Product Configurator, "Process isolating diaphragm material" ordering feature, option L
NOTICE
To reduce the formation of hydrogen, you should not use galvanized assemblies.
For acids, alkalis or sea water, Endress+Hauser offers process isolating diaphragms with a gold/
platinum coating.
NOTICE
With temperature exposure (up to 85C(185F)) there is an additional zero point deviation of 1.1
mbar (0.0165 psi).
Ordering information:
Product Configurator, "Process isolating diaphragm material" ordering feature, option N
Endress+Hauser
31
Deltapilot M FMB50/51/52/53
Environment
Ambient temperature limits
Version
Without LCD display
FMB50
FMB51
40 C to +85 C
(-40F to +185F)
FMB53
-25 C to +85 C
(-13F to +185F)
FMB52
Extended temperature application range (-40 C to +85 C (40F to +185F)) with restrictions in optical
properties such as display speed and contrast
Version
FMB50
FMB51
40 C to +90 C
(-40F to +194F)
40 C to +85 C
(-40F to +185F)
-25 C to +90 C
(-13F to +194F)
FMB52
FMB53
Climate class
Class 4K4H (air temperature: 20 to 55 C (4 to +131F), relative humidity: 4 to 100%) satisfied as per
DIN EN 60721-3-4 (condensation possible)
Degree of protection
Vibration resistance
Electromagnetic
compatibility
32
Device/accessory
Test standard
Vibration resistance
GL VI-7-2
Part 7: Guidelines for the Performance of
Type Approvals
Chapter 2: Test Requirements for Electrical /
Electronic Equipment and Systems
Guaranteed for:
5 to 25 Hz: 1.6 mm (0.06 in);
25 to 100 Hz: 4 g
in all 3 planes
IEC 61298-3
Guaranteed for:
10 to 60 Hz: 0.15 mm (0.01 in);
60 to 500 Hz: 2 g
in all 3 planes
FMB51
IEC 60068-2-6
Guaranteed for:
10 to 60 Hz: 0.075 mm (0.003 in)
60 to 150 Hz 1g in all 3 planes
Electromagnetic compatibility as per all the relevant requirements of the EN 61326 series and
NAMUR Recommendation EMC (NE21). Details can be found in the Declaration of Conformity (in
the Download area of "www.de.endress.com", "search area - Approvals and Certificates", "Manufact.
Declaration").
Max. deviation during EMC-tests < 0.5% of the span
All tests were performed with full measurement range (TD 1:1).
Endress+Hauser
Deltapilot M FMB50/51/52/53
Process
Process temperature range
FMB50
FMB51
10 C to +85 C
(+14F to +185F)
FMB52
FMB53
1)
30 Nm
! WARNING
The maximum pressure for the measuring device depends on the lowest-rated element with
regard to pressure 13 ff, "Measuring range" ordering feature and 34 ff "Mechanical
construction" ordering feature
Only operate the measuring device within the prescribed limits!
The MWP (maximum working pressure) is specified on the nameplate. This value refers to a
reference temperature of +20 C (68F), (100F (38 C) for ANSI flanges), and may be applied to the
device for an unlimited time. Pay attention to pressure-temperature dependencies.
Please refer to the following standards for pressure values permitted at higher temperatures
EN 1092-1: 2001 Tab. 18 1)
ASME B 16.5a 1998 Tab. 2-2.2 F316
ASME B 16.5a 1998 Tab. 2.3.8 N10276
JIS B 2220.
The MWP applies for the temperature ranges indicated in the "Ambient temperature limits"
( 32) and "Process temperature limits" ordering features (see above).
The test pressure corresponds to the over pressure limit of the device (OPL = 1.5 x MWP) and may
be applied for only a limited time period in order to avoid permanent damage.
The Pressure Equipment Directive (EC Directive 97/23/EC) uses the abbreviation "PS". The
abbreviation "PS" corresponds to the MWP (maximum working pressure) of the measuring device.
In the case of sensor range and process connection combinations where the OPL (over pressure
limit) of the process connection is smaller than the nominal value of the sensor, the device is set at
the factory, at the very maximum, to the OPL value of the process connection. If you want to use
the entire sensor range, select a process connection with a higher OPL value (1.5 x PN; PN = MWP).
In oxygen applications, the values for "pmax and Tmax for oxygen applications" as per 31,
"Oxygen applications" ordering feature may not be exceeded.
With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together under 13EO in EN 1092-1 Tab. 18. The
chemical composition of the two materials can be identical.
Endress+Hauser
33
Deltapilot M FMB50/51/52/53
Mechanical construction
Device height
Page
Height
Housing height
34 ff
Process connections
35 ff
Installation distance
Device height
115 (4.53)
103 (4.06)
112 (4.41)
1
2
127 (5)
94 (3.7)
A0023569
Material
Aluminum
Aluminum with glass viewing window
1)
34
Option 1)
Weight kg (lbs)
With display
Without display
1.1 (2.43)
1.0 (2.21)
I
J
Endress+Hauser
Deltapilot M FMB50/51/52/53
95 (3.74)
1
2
114 (4.49)
100 (3.94)
76 (3)
A0023570
Material
Option 1)
Weight kg (lbs)
With display
Without display
Stainless steel
1.1 (2.43)
1.0 (2.21)
50
1
2
59 (2.32)
25 (0.98)
50
59 (2.32)
25 (0.98)
G 1" A
55 (2.17)
G 1" A
55 (2.17)
A0023582
A0023581
Item
Designation
Material
B
1)
Weight kg (lbs)
Option 1)
GGJ
0.8 (1.76)
GGC
Endress+Hauser
35
Deltapilot M FMB50/51/52/53
25 (0.98)
54 (2.13)
50
NPT 1"
55 (2.17)
A0023584
Designation
Material
Weight kg (lbs)
Option 1)
0.8 (1.76)
RGJ
1)
41
g2
dM = 35.8
g
k
D
A0020004
Engineering unit mm
Flange 1)
Material
Boltholes
3)
Nominal Nominal
diameter pressure
Shape
4)
Diameter Thickness
Diameter Height
Quantof raised of raised ity
face
face
Weight
Diameter
Hole
circle
g2
[mm]
[mm]
[mm]
[mm]
[mm]
[mm]
[kg (lbs)]
Option
2)
AISI 316L
DN 40
PN 10/16
B1 (C)
150
18
88
18
110
3.05 (6.72)
CEJ
AISI 316L
DN 50
PN 10/16
B1 (C)
165
18
102
18
125
3.75 (8.27)
CFJ
AISI 316L
DN 80
PN 10/16
B1 (C)
200
20
138
18
160
AISI 316L
DN 100
PN 10/16
B1 (C)
220
20
158
18
180
1)
The roughness of the surface in contact with the medium, including the sealing surface of the flanges, is < Ra 0.8 m (31.5 in). Lower surface
roughness available on request.
2)
3)
Endress+Hauser supplies DIN/EN stainless steel flanges as per AISI 316L (DIN/ EN material number 1.4404 or 14435). With regard to their
stability-temperature property, the materials 1.4404 and 1.4435 are grouped together under 13E0 in EN 1092-1: 2001 Tab.18. The chemical
composition of the two materials can be identical.
4)
36
Endress+Hauser
Deltapilot M FMB50/51/52/53
1.61
g2
dM = 1.41
g
k
D
A0022644
Engineering unit in
Flange 1)
Material 3)
Boltholes
Nominal Class
diameter
Quantity
Weight
Diameter Thickness
Diameter Height of
of raised raised face
face
g2
[in]
[in]
[kg (lbs)]
Option 2)
Diameter Hole
circle
[in]
[in]
[in]
[in]
AISI 316/316L
150
0.69
2.88
0.06
0.62
3.88
2.55 (5.62)
AEJ
(not
FMB51/52)
AISI 316/316L
150
0.75
3.62
0.06
0.75
4.75
3.45 (7.61)
AFJ
AISI 316/316L
150
7.5
0.94
0.06
0.75
AISI 316/316L
150
0.94
6.19
0.06
0.75
7.5
1)
The roughness of the surface in contact with the medium, including the sealing surface of the flanges, is < Ra 0.8 m (31.5 in). Lower surface
roughness available on request.
2)
3)
Combination of AISI 316 for required pressure resistance and AISI 316L for required chemical resistance (dual rated)
Endress+Hauser
37
Deltapilot M FMB50/51/52/53
JIS flanges, connection dimensions as per JIS B 2220 BL, raised face RF
41
g2
dM = 35.8
g
k
D
A0020004
Engineering unit mm
Flange 1)
Material
AISI 316L
(1.4435)
Boltholes
Nominal
diameter
Nominal Diameter
pressure
Option 2)
Weight
Thickness
Diameter of
raised face
Height of Quantity
raised
face
g2
[mm]
[mm]
[mm]
[mm]
[mm]
[mm]
[kg (lbs)]
40 A
10 K
140
16
81
19
105
2.55 (5.62)
KEJ
50 A
10 K
155
16
96
19
120
2.95 (6.50)
KFJ
80 A
10 K
185
18
126
19
150
4.25 (9.37)
KGJ
100 A
10 K
210
18
151
19
175
5.35 (11.79)
KHJ
1)
The roughness of the surface in contact with the medium, including the sealing surface of the flanges (all standards), is < Ra 0.8 m (31.5 in).
Lower surface roughness available on request.
2)
38
Endress+Hauser
Deltapilot M FMB50/51/52/53
Universal adapter
A
68.5 (2.7)
179.5 (7.07)
dM = 36 (1.42)
43.5 (1.71)
43.5 (1.71)
A0020013
A0020014
Item1)
Designation
Material
Approval
Weight
kg (lbs)
UPJ3)
EHEDG, 3A
1: top section
AISI 316L (1.4404)
2: bottom section
AISI 316L (1.4435)
0.8 (1.76)
UNJ )
UQJ )
EHEDG, 3A
1.7 (3.75)
Option 2)
UOJ )
1)
Surface roughness of the surfaces in contact with the medium Ra 0.76m (30 in) as standard. Surface roughness Ra<0.38 m electropolished
(wetted) Ordering information: Product Configurator, "Service" ordering feature, option "HK".
2)
3)
Endress+Hauser supplies these slotted nuts in stainless steel AISI 304 (1.4301) or in AISI 304L (1.4307).
78 (3.07)
188 (7.4)
2"
2"
3"
3"
A0020015
A0020016
Item1)
Designation
Material
Approval
Weight
kg (lbs)
Option 2)
3A
1.5 (3.31)
USJ
3A
2.9 (6.39)
UTJ
1)
Surface roughness of the surfaces in contact with the medium Ra 0.76m (30 in) as standard. Lower surface roughness available on request.
2)
Endress+Hauser
39
Deltapilot M FMB50/51/52/53
56 (2.2)
68.5 (2.7)
Rd 65 x 1/6
68.5 (2.7)
Rd 78 x 1/6
Rd 78 x 1/6
A0020006
A0020007
23.5 (0.93)
20.5 (0.81)
59.5 (2.34)
4x
11.5 (0.45)
56.5 (2.22)
59.5 (2.34)
A0020005
20.5 (0.81)
59.5 (2.34)
10.2 (0.4)
59.5 (2.34)
Hygienic connections
11.2 (0.44)
59.5 (2.34)
65-1.2 (2.56-0.05)
64 (2.52)
84 (3.31)
105 (4.13)
A0020008
A0020009
Item1)
Designation
Approval
Weight
kg (lbs)
Option 2)
DIN 11851 DN 40 PN 25
EHEDG, 3A
0.7 (1.54)
MZJ3)
DIN 11851 DN 50 PN 25
EHEDG, 3A
0.9 (1.98)
MRJ )
EHEDG, 3A
1 (2.21)
NDJ )
Material
EHEDG, 3A
0.7 (1.54)
TDJ )
1.1 (1.98)
TIJ
1)
Surface roughness of the surfaces in contact with the medium Ra 0.76m (30 in) as standard. Lower surface roughness available on request.
2)
3)
Endress+Hauser supplies these slotted nuts in stainless steel AISI 304 (DIN/EN material number 1.4301) or in AISI 304L (DIN/EN material
number 1.4307).
40
Endress+Hauser
27 (1.06)
59.5 (2.34)
20.5 (0.81)
59.5 (2.34)
9 (0.35)
68 (2.68)
59.5 (2.34)
Deltapilot M FMB50/51/52/53
49.9 (1.96)
84 (3.31)
65 (2.56)
70 (2.76)
Rd 70 x 1/6
84 (3.31)
A0020010
90 (3.54)
A0020011
Item1)
Designation
SMS 2", PN 25
A0020012
Material
Approval
Weight
kg (lbs)
Option 2)
EHEDG, 3A
1 (2.21)
TRJ
EHEDG
0.7 (1.54)
TXJ3)
3A
0.8 (1.76)
S4J
1)
Surface roughness of the surfaces in contact with the medium Ra 0.76m (30 in) as standard. Lower surface roughness available on request.
2)
3)
Endress+Hauser supplies these slotted nuts in stainless steel AISI 304 (DIN/EN material number 1.4301) or in AISI 304L
(DIN/EN material number 1.4307).
Endress+Hauser
41
Deltapilot M FMB50/51/52/53
21,3 (0.84)
208 (8.19)
42,4 (1.67)
43,5 (1.71)
A0023592
H
L
Weight
Housing weight
34 ff
35 ff
Flange connection incl. measuring cell tube and sensor, without a flange
42
Endress+Hauser
Deltapilot M FMB50/51/52/53
21,3 (0.84)
208 (8.19)
42,4 (1.67)
43,5 (1.71)
A0023593
H
L
Weight
Housing weight
34 ff
35 ff
Flange connection incl. measuring cell tube and sensor, without a flange
Endress+Hauser
43
Deltapilot M FMB50/51/52/53
10,4 (0.41)
236 (9.29)
42,4 (1.67)
43,5 (1.71)
A0023594
H
L
Weight
Housing weight
34 ff
35 ff
PE cable
FEP cable
Flange connection incl. measuring cell tube and sensor, without a flange
44
Endress+Hauser
Deltapilot M FMB50/51/52/53
10,4 (0.41)
236 (9.29)
42,4 (1.67)
43,5 (1.71)
A0023597
H
L
Weight
Housing weight
34 ff
35 ff
PE cable
FEP cable
Flange connection incl. measuring cell tube and sensor, without a flange
Endress+Hauser
45
Deltapilot M FMB50/51/52/53
181 (7.13)
194 (7.64)
156 (6.14)
137 (5.39)
169 (6.65)
1
2
222 (8.74)
2
0
(7
.8
7
1
2
235 (9.25)
238 (9.37)
61 (2.4)
10,4 (0.41)
236 (9.29)
42,4 (1.67)
43,5 (1.71)
A0023598
FMB53 with suspension clamp and mounting bracket (mounting bracket without marine approval)
1
2
3
4
5
L
Weight
Housing weight
34 ff
PE cable (cable length > 120 m (394 ft) = Delivery on cable reel)
FEP cable (cable length > 120 m (394 ft) = Delivery on cable reel)
Mounting bracket
Suspension clamp
46
Endress+Hauser
Deltapilot M FMB50/51/52/53
174 (6.85)
187 (7.36)
146 (5.75)
159 (6.26)
1
2
127 (5)
1
2
211 (8.31)
2
0
(7
.8
7
224 (8.82)
238 (9.37)
61 (2.4)
10,4 (0.41)
236 (9.29)
42,4 (1.67)
43,5 (1.71)
A0023600
FMB53 with suspension clamp and mounting bracket (mounting bracket without marine approval)
1
2
3
4
5
L
Weight
Housing weight
34 ff
PE cable (cable length > 120 m (394 ft) = Delivery on cable reel)
FEP cable (cable length > 120 m (394 ft) = Delivery on cable reel)
Mounting bracket
Suspension clamp
Endress+Hauser
47
Deltapilot M FMB50/51/52/53
42...60 (1.65...2.36)
6 (0.24)
140 (5.51)
122 (4.8)
158 (6.22)
50 (1.97)
52 (2.05)
112 (4.4)
1
2
127 (5)
69 (2.72)
70 (2.76)
86 (3.39)
175 (6.89)
81 (3.19)
6 (0.24)
95 (3.74)
1
2
114 (4.49)
63 (2.48)
52 (2.05)
20 (0.79)
A0023601
1
2
L
Item
Designation
1)
Option 1)
Weight
Housing (F31 or F15)
Mounting
bracket
34 ff
0.5 kg (1.10)
48
Endress+Hauser
Deltapilot M FMB50/51/52/53
1
2
36 (1.42)
F15
81 (3.19)
1
2
r 120 (4.72)
17 (0.67)
F31
44 (1.73)
r 120 (4.72)
29 (1.14)
If the separate housing is used, the mounting height of the process connection is reduced compared to
the dimensions of the standard version.
54.1 (2.13)
A0023601
Endress+Hauser
49
Deltapilot M FMB50/51/52/53
1
20
(4
.
72
121,7 (4.79)
L1
54.1 (2.13)
A0023603
Connecting cable with process connection adapter and mounting bracket, here shown with an FMB52
1
2
3
L1
L
Mounting bracket for pipe and wall mounting (for pipes from 1 1/4" up to 2" diameter)
Process connection adapter
Measuring cell tube
PE cable = 2 m (6.6 ft), 5m (16 ft) or 10 m (33 ft)
FEP cable = 5 m (16 ft)
Probe length = 0.5 to 400 m (1.6 to 1312 ft)
Weight
Mounting bracket
Ordering information for FMB50, FMB51, FMB52: Product Configurator, "Separate housing" ordering
feature
50
Endress+Hauser
Deltapilot M FMB50/51/52/53
F31 housing
14
15
16
13
6
8
9
12
11
10
2
3
4
7
A0023615
Item
number
Component part
Material
Cover seal
EPDM
Sight glass
Mineral glass
Silicone (VMQ)
Nameplates
Plastic film
10
VMQ or EPDM
11
Sealing ring
EPDM
12
Snap ring
PC Plastic
13
EPDM/NBR
Cable gland
Blind plug
PBT-GF30 FR
1
2
14
15
Endress+Hauser
Cover clamp
51
Deltapilot M FMB50/51/52/53
F15 housing
14
7
6
2
3
11
13
12
10
4
A0023616
52
Item
number
Component part
Material
F15 housing
Cover
Cover seal
Polycarbonate (PC)
Silicone (VMQ)
VMQ or EPDM
10
Nameplates
lasered
11
Cable gland
12
NBR/Silicone/EPDM
13
Sealing ring
EPDM
14
Screw
A4-50
Endress+Hauser
Deltapilot M FMB50/51/52/53
Connecting parts
4
4
4
4
1
1
5
5
2
2
1
1
3
3
6
6
10
10 11
11
7
7
8
8
9
9
5
5
6
6
A0023617
Item
number
Component part
Material
Mounting bracket
FKM, EPDM
10
Housing adapter
11
Cable gland:
Sealing insert:
O-ring:
CuZn nickel-plated
TPE-V
NBR
A2
Fill fluid
Designation
Option 1)
Inert oil
1)
Endress+Hauser
53
Deltapilot M FMB50/51/52/53
The wetted device components are listed in the "Mechanical construction" ( 34 ff) and "Ordering
information" ( 64 ff) sections.
FMB51
FMB53
9
2
10
11
12
13
6
7
8
14
15
8
FMB52
16
17
10
2
3
11
12
13
6
7
8
14
15
8
6
7
8
A0023619
54
Item
number
Component part
Material
Process connection
34 ff
Socket
Endress+Hauser
Deltapilot M FMB50/51/52/53
Item
number
Component part
Material
Rod
PE cable
PE cable
(Usage in drinking water)
FEP cable
Socket
Probe tube
Item
number
Component part
Material
64 ff
Seals
64 ff
Protection cap
PPO
Process connection
10
Socket
Alloy C4 (2.4610)
11
Rod
Alloy C4 (2.4610)
12
Socket
Alloy C4 (2.4610)
13
Probe tube
14
64 ff
15
Seals
64 ff
16
Suspension clamp
17
Clamping jaw
PA-GF
DIN/EN flanges
Endress+Hauser supplies DIN/EN flanges made of stainless steel AISI 316L as per material numbers
1.4435 or 1.4404. With regard to their stability-temperature property, the materials 1.4435 and
1.4404 are grouped together under 13EO in EN 1092-1 Tab. 18. The chemical composition of the two
materials can be identical.
Process isolating diaphragm
Material
Option 1)
Alloy C
Rhodium>Gold>AlloyC
1)
Endress+Hauser
55
Deltapilot M FMB50/51/52/53
Seals
Designation
Option 1)
FKM Viton
A2)
EPDM
J )
Kalrez 6375
L )
1)
2)
Not FMB50
56
Endress+Hauser
Deltapilot M FMB50/51/52/53
Operability
Operating concept
Commissioning
Operation
Diagnostics
Expert level
5
4
3
2
1
A0016498
1
2
3
4
5
Operating keys
Bar graph
Symbol
Header
Parameter ID number
Ordering information:
Product Configurator, "Output; operation" ordering feature
Endress+Hauser
57
Deltapilot M FMB50/51/52/53
Function
PROFIBUS PA
FOUNDATION Fieldbus
Setting lower range value and upper range value - reference pressure present
at the device
Device reset
Span
Zero
on
damp
not used
delta p on:
off:SW
only on:P2= High off:SW
HAR T
delta p only
damping
SW / Alarm min
SW /
SW / P2=High
Display
3
on
TM
off
off
FOUNDATION
SW
HW
Address
on
off
1
damping
8 7 6 5 4
on
off
SW /
SW / P2=High
Zero
on
off
damping
SW / Alarm min
SW /
SW / P2=High
1
2
3
4
5
on
on
2
2
1
off
Display
damping
simulation
SW /
SW / P2=High
delta p only
2
1
Display
Zero
8 7 6 5 4
10 9 8 7 6
A0023125
A0023126
A0023127
1
2
2
3
4
5
6
7
8
3
4
5
6
7
8
9
10
Function
off
damping
Simulation
SW /
SW / P2=High
2
3
4
5
6
7
8
PROFIBUS PA
FOUNDATION Fieldbus
Setting lower range value and upper range value - reference pressure present
at the device
Device reset
58
Endress+Hauser
Deltapilot M FMB50/51/52/53
Ordering information:
Product Configurator, "Display, operation" ordering feature
Operating languages
You can also choose another language in addition to the standard language "English":
Option 1)
Designation
English
AA
German
AB
French
AC
Spanish
AD
Italian
AE
Dutch
AF
Chinese
AK
Japanese
AL
1)
Remote operation
All software parameters are accessible depending on the position of the write protection switch on the
device.
Hardware and software for remote
operation
HART
PROFIBUS PA
FOUNDATION Fieldbus
1)
2)
FieldXpert SFX100 59 ff
NI-FBUS Configurator 60 ff
FieldCare 59 ff
1)
2)
FieldCare
FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you
can configure all Endress+Hauser devices as well as devices from other manufacturers that support the
FDT standard.
FieldCare supports the following functions:
Configuration of transmitters in offline and online mode
Loading and saving device data (upload/download)
HistoROM/M-DAT analysis
Documentation of the measuring point
Connection options:
HART via Commubox FXA195 and the USB port on a computer
PROFIBUS PA via segment coupler and PROFIBUS interface card
Service interface with Commubox FXA291 and ToF adapter FXA291 (USB).
For further information please contact your local Endress+Hauser Sales Center.
Field Xpert SFX100
Field Xpert is an industrial PDA with integrated 3.5" touchscreen from Endress+Hauser based on
Windows Mobile. It offers wireless communication via the optional VIATOR Bluetooth modem or via
WiFi and Endress+Hauser's Fieldgate FXA520. Field Xpert also works as a stand-alone device for asset
management applications. For details refer to BA00060S/04/EN.
Endress+Hauser
59
Deltapilot M FMB50/51/52/53
Commubox FXA195
For intrinsically safe HART communication with FieldCare via the USB interface. For details refer to
TI00404F/00/EN.
Commubox FXA291
The Commubox FXA291 connects Endress+Hauser field devices with a CDI interface
(= Endress+Hauser Common Data Interface) and the USB port of a computer or laptop.
For details, see TI00405C/07/EN.
For the following Endress+Hauser devices, you also need the "ToF adapter FXA291" accessory:
Cerabar S PMC71, PMP7x
Deltabar S PMD7x, FMD7x
Deltapilot S FMB70
ToF adapter FXA291
The ToF adapter FXA291 connects the Commubox FXA291 to devices in the ToF platform, pressure
devices and Gammapilot via the USB port of a computer or laptop. For details, see KA00271F.
Profiboard
For connecting a PC to PROFIBUS.
Proficard
For connecting a laptop to PROFIBUS.
FF configuration program
FF configuration program, such as NI-FBUS Configurator, to
connect devices with "FOUNDATION Fieldbus signal" into an FF-network
set FF-specific parameters
Remote operation via:
Operation with NI-FBUS Configurator:
The NI-FBUS Configurator is an easy-to-use graphical environment for creating linkages, loops, and
a schedule based on the fieldbus concepts.
You can use the NI-FBUS Configurator to configure a fieldbus network as follows:
Set block and device tags
Set device addresses
Create and edit function block control strategies (function block applications)
Configure vendor-defined function and transducer blocks
Create and edit schedules
Read and write to function block control strategies (function block applications)
Invoke Device Description (DD) methods
Display DD menus
Download a configuration
Verify a configuration and compare it to a saved configuration
Monitor a downloaded configuration
Replace a virtual device by a real device
Save and print a configuration
System integration
Option 1)
Z1
Z2
1)
60
Endress+Hauser
Deltapilot M FMB50/51/52/53
C-tick symbol
The measuring system complies with the EMC requirements of the "Australian Communications and
Media Authority (ACMA)".
Ex approvals
ATEX
FM
CSA
Also combinations of different approvals
All explosion protection data are given in separate documentation which is available upon request. The
Ex documentation is supplied as standard with all devices approved for use in explosion hazardous
areas.
68 ff, "Safety Instructions" and "Installation/Control Drawings" ordering features.
Suitability for hygienic
processes
All materials in contact with foodstuffs comply with framework Regulation (EC) 1935/2004.
The Deltapilot is available with hygienic process connections (overview: see order code).
! CAUTION
Contamination in the process!
Risk of contamination if incorrect seals and parts are used!
To avoid the risk of contamination, when installing the device comply with the design principles of
EHEDG, Guideline 37 "Hygienic Design and Application of Sensors" and Guideline 16 "Hygienic Pipe
Couplings".
Suitable assemblies and seals must be used to ensure hygienic design in accordance with 3-A SSI
and EHEDG specifications.
The leak-proof connections can be cleaned with the cleaning methods typical of this industry (CIP
and SIP). Attention must be paid to the pressure and temperature specifications of the sensor and
process connections for CIP and SIP processes (clean in place/sterilize in place).
74 -
TYPE EL
February 2010
A0024005
A0020029
Gap-free connections can be cleaned without residue using the usual cleaning methods.
Pharma (CoC) (FMB50 only)
Endress+Hauser
The Deltapilot M with 4 to 20 mA output signal has been developed to assessed and certified by
TV NORD CERT as per IEC 61508 Edition 2.0 and IEC 61511. These devices can be used to monitor
the process level and pressure up to SIL 2. For a detailed description of the safety functions with
Deltapilot M, settings and functional safety data, see the "Functional safety manual - Deltapilot M"
SD00347P.
Ordering information:
Product Configurator, "Additional approval:" ordering feature, option "LA".
61
Deltapilot M FMB50/51/52/53
Overfill protection
AD2000
The Deltapilot M device corresponds to Article 3 (3) of the EC directive 97/23/EC (Pressure Equipment
Directive) and has been designed and manufactured according to good engineering practice.
Marine approval
Designation
FMB51
FMB52
FMB53
GL
LE
ABS
LF
LR
LG
BV
LH
DNV
LI
1)
Option 1)
FMB50
Product Configurator, "Additional options 1" and "Additional options 2" ordering feature
Designation
Option 1)
KTW
LQ
NSF61
LR
LS
1)
Classification of process
sealing between electrical
systems and (flammable or
combustible) process fluids in
accordance with ANSI/
ISA 12.27.01
Inspection certificate
62
Product Configurator, "Additional options 1" and "Additional options 2" ordering feature
Endress+Hauser instruments are designed according to ANSI/ISA 12.27.01 either as single seal or
dual seal devices with annunciation, allowing the user to waive the use and save the cost of installing
external secondary process seals in the conduit as required by the process sealing sections of ANSI/
NFPA 70 (NEC) and CSA 22.1 (CEC). These instruments comply with the North-American installation
practice and provide a very safe and cost-saving installation for pressurized applications with
hazardous fluids.
Further information can be found in the control drawings of the relevant devices.
Designation
Option 1)
FMB50
FMB51
FMB52
FMB53
JA
JB
JE
JF
KB
Endress+Hauser
Deltapilot M FMB50/51/52/53
Designation
FMB50
FMB51
FMB52
FMB53
1)
Calibration; unit
KF
KG
Option 1)
Sensor range; %
Option 1)
Designation
F1
2)
2)
F2
Option 1)
Designation
Oil and grease removed 2)
Cleaned for oxygen service
HA
)
Endress+Hauser
KE
Service
KD
Designation
1)
Calibration
Option 1)
HB
)
HC
IA
IB
1)
2)
63
Deltapilot M FMB50/51/52/53
Ordering information
Detailed ordering information is available from the following sources:
In the Product Configurator on the Endress+Hauser website: www.endress.com Select country
Products Select product Product page function: Configure this product
From your Endress+Hauser Sales Center: www.endress.com/worldwide
Product Configurator - the tool for individual product configuration
Up-to-the-minute configuration data
Depending on the device: direct input of information specific to measuring point, such as measuring
range or operating language
Automatic verification of exclusion criteria
Automatic creation of the order code and its breakdown in PDF or Excel output format
Ability to order directly in the Endress+Hauser Online Shop
Configuration data sheet
Pressure
The following configuration data sheet has to be filled in and included with the order if the option J Customized pressure has been selected in feature 90 "Calibration; unit" in the ordering information.
Pressure Engineering Unit
mbar
bar
psi
mmHO
mHO
ftHO
inHO
mmHg
Pa
kgf/cm2
kPa
MPa
_______________
_______________
Display Information
1)
Damping
Damping:
64
Endress+Hauser
Deltapilot M FMB50/51/52/53
Level
The following configuration data sheet has to be filled in and included with the order if the option K Customized level has been selected in feature 90 "Calibration; unit" in the ordering information.
mbar
bar
psi
mmHO
mHO
ftHO
inHO
mmHg
kgf/cm2
Pas
kPa
MPa
Mass
Length
Volume
Volume
Percent
kg
t
lb
m
dm
cm
mm
l
hl
gal
Igal
m3
ft3
in3
ft
inch
Example
Empty pressure [a]:
Low pressure value (empty) ______________
[pressure
engineering unit]
______________
[pressure
engineering unit]
______________
[Scaled Unit]
A0023621
0 mbar / 0m
Display Information
1)
Damping
Damping:
Endress+Hauser
65
Deltapilot M FMB50/51/52/53
Accessories
Suspension clamp
(FMB53 only)
29 ff
M12 connector
23 ff
Ordering information:
Product Configurator, "Enclosed accessories" ordering feature, option "RL, RM, RN".
66
Endress+Hauser
Deltapilot M FMB50/51/52/53
44 (1.73)
47.5 (1.87)
Rd 52 x 1/6 "
39.5 (1.56)
47.5 (1.87)
44 (1.73)
39.5 (1.56)
Rd 52 x 1/6 "
29.5 (1.16)
26.5 (1.04)
25.5 (1)
The following adapters can be used to create a connection between the customer's process connection
and the Deltapilot S FMB50 with a universal adapter:
28.5 (1.12)
51.6 (2.03)
51.6 (2.03)
61 (2.4)
56 (2.2)
68 (2.68)
Rd 65 x 1
78 (3.07)
Rd 78 x 1
92 (3.62)
44 (1.73)
Rd 52 x 1/6 "
44 (1.73)
39.5 (1.56)
Rd 52 x 1/6 "
A0020038
39.5 (1.56)
6 (0.24)
31.5 (1.24)
A0020037
51.6 (2.03)
65 (2.56)
51.6 (2.03)
84 (3.31)
64 (2.52)
105 (4.13)
A0020039
39.5 (1.56)
A0020040
Rd 52 x 1/6 "
44 (1.73)
68 (2.68)
84 (3.31)
A0020041
Weight
kg (lbs)
Order number
Option 1)
DIN11851 DN40
0.2 (0.44)
71114172
71114178
RA / R1
DIN11851 DN50
0.3 (0.66)
71114173
71114205
RB / R2
DRD DN50
0.6 (1.32)
71114174
71114206
RC / R3
Clamp 2"
0.2 (0.44)
71114176
71114207
RD / R4
Varivent
0.5 (1.1)
71114177
71114208
RF / R6
Item
Designation
1)
Material
Endress+Hauser
67
Deltapilot M FMB50/51/52/53
Documentation
Technical Information
Operating Instructions
Safety Instructions
Directive
ATEX
1)
Category
Type
Electronics
Documentation
Option 1)
Ex ia IIC
II 1/2 G
4 to 20 mA HART
XA00474P/00
BA
Ex t IIC
II 1/2 D
FMB50, FMB51
4 to 20 mA HART
XA00475P/00
BB
Ex nA
II 3 G
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA00477P/00
BD
Ex ia IIC
II 2 G
4 to 20 mA HART
XA00474P/00
BE
Ex ic IIC
II 3 G
4 to 20 mA HART
XA00494P/00
BG
Ex ia IIC
Ex ia IIC
II 1/2 G
II 1/2 D
FMB50, FMB51
4 to 20 mA HART
XA00476P/00
B1
Directive
IECEx
1)
Approval
Approval
EPL
Type
Electronics
Documentation
Option 1)
Ex ia IIC
Ga/Gb
4 to 20 mA HART
XA00478P/00
IA
Ex ia IIC
Gb
FMB52, FMB53
4 to 20 mA HART
XA00478P/00
IC
Ex t IIIC
Da/Db
FMB50, FMB51
4 to 20 mA HART
XA00479P/00
ID
Ex ic IIC
Gc
4 to 20 mA HART
XA00493P/00
IE
Ex ia IIC
Ex ia IIIC
Ga/Gb
Da/Db
FMB50, FMB51
4 to 20 mA HART
XA00480P/00
I1
Directive
Approval
Type
Electronics
Documentation
Option 1)
NEPSI
Ex ia IIC
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA00535P/00
NA
1)
68
Endress+Hauser
Deltapilot M FMB50/51/52/53
Directive
Approval
Electronics
Documentation
Option 1)
TIIS
Ex ia IIC T4
4 to 20 mA HART
TA
1)
Directive
Approval
Type
Electronics
Documentation
Option 1)
INMETRO
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
XA01304P/00
MA
1)
Installation/Control
Drawings
Directive
FM
Approval
Type
Electronics
Documentation
FMB50
4 to 20 mA HART
PROFIBUS PA, FOUNDATION Fieldbus
ZD00236P/00
XA00566P/00
1)
FA
FMB51
4 to 20 mA HART
PROFIBUS PA, FOUNDATION Fieldbus
XA00566P/00
FMB50, FMB51
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
FC
FMB50, FMB51
4 to 20 mA HART
PROFIBUS PA
FOUNDATION Fieldbus
FD
FMB52, FMB53
4 to 20 mA HART
PROFIBUS PA. FOUNDATION Fieldbus
ZD00236P/00
XA00566P/00
FE
FMB50, FMB53
4 to 20 mA HART
PROFIBUS PA, FOUNDATION Fieldbus
ZD00239P/00
XA00560P/00
FMB51, FMB52
4 to 20 mA HART
PROFIBUS PA, FOUNDATION Fieldbus
XA00560P/00
FMB50
4 to 20 mA HART
FMB51
4 to 20 mA HART
CSA
Option 1)
CA
CC
Combination certificate
Directive
Approval
ATEX II Ex ia + FM/CSA IS
ATEX II 1/2G Ex ia IIC T6 +
KEMA/
FM / CSA FM/CSA IS CL.I Div.1 Gr.A-D,
FM/CSA: Zone 0,1,2
1)
Overfill protection
Endress+Hauser
Electronics
Documentation
4 to 20 mA HART
ZD00236P/00
ZD00239P/00
PROFIBUS PA,
FOUNDATION Fieldbus
XA00474P/00
Option 1)
8C
69
Deltapilot M FMB50/51/52/53
Registered trademarks
HART
PROFIBUS
FOUNDATION Fieldbus
70
Endress+Hauser
Deltapilot M FMB50/51/52/53
Endress+Hauser
71
71260308
www.addresses.endress.com