BERMAD Fire Protection
Indicating Devices
Explosion-Proof Pressure Switch
Model PS-12
The PS-12 Pressure Switch is for use in conjunction with
BERMAD Deluge or other types of water control valves, to
indicate discharge water pressure. This Pressure Switch
offers reliability, repeatability and durability in a compact
design. It is ideal for operation under the harsh conditions
of DIV.1 or Zone 1 (II 2 G/D EEx d IIC T6 Certified)
hazardous locations.
At the heart of the PS-12 is a snap action Belleville spring
assembly, which transfers motion to a hermetically sealed
5 amp vibration resistant microswitch.
Applications: Chemical plants, refineries, gas and
petroleum installations, offshore and marine vessels.
Features
Stainless Steel construction
Vibration resistant technology
Hermetically sealed switch enclosure
Convenient field adjustments
Global approvals for hazardous locations
Strain relief, high over pressure
Mechanical contact lifecycle: 10 million cycle
Approvals
[7]
[1]
[2]
[3]
[4]
UL Listed for hazardous locations
Class I Div.1 & 2
CENELEC Certified to ATEX directive
II 2 G/D EEx d IIC T6
CSA Certified for Class I, Zone 1, Group IIC
IP66 Certified
Materials
Wetted parts: Stainless Steel 316
Option: Monel 400
Hausing: Stainless Steel 316
Diaphragm: Teflon coated polyamide
O-ring: NBR (Buna-N)
Aluminum terminal box
End Connections
Pressure: NPT (F)
Electric: NPT (M)
[5]
Major Parts
[1] Factory sealed leadwires
[2] Electric port connection
[3] Adjustment access cover
[4] Slotted adjustment screw
[5] Pressure connection (sensor)
[6] Switch housing
[7] Terminal Box (option)
BERMAD Fire Protection
Indicating Devices
Explosion-Proof Pressure Switch, PS-12
Technical Data
Model Selection
Model 12-SHSN3B (standard):
one SPDT, S.S. 316 wetted parts
Model 12-SHDN3C:
two SPDT for DPDT action, S.S. 316 wetted parts
Model 12-SHSN3B/M:
one SPDT for DPDT action, Monel wetted parts
Pressure Setting & Range
Factory Set: 2.5 bar high, 2.1 bar low
Adjustable range: 1.0 to 3.8 bar (15 to 55 psi)
Deadband: 0.2 bar low to 0.6 bar high (3 to 8 psi)
Max. working pressure: 41 bar (600 psi)
Set point repeatability: 1% of adjustable range
Electrical Ratings
5 amp at 250 VAC
5 amp resistive and 3 amp inductive at 28 VDC
Silver contacts
Enclosures Class
NEMA 4X, 7 and 9(1) Classification Explosion-proof
and watertight combination Class I Division 1 & 2
Groups A, B, C, D. Class II Division 1 & 2 Groups E, F, G
ATEX Classification(2)
II 2 G/D EEx d IIC T6 Certified to ATEX directive
IP 66 Certified, CE marked
Note:
(1) UL-Listed for hazardous locations (UL file # E40857), CSA Class I,
Zone 1, Group IIC.
(2) Demko A/S certified to ATEX Directive (94/9 EC) II 2 G/D EEx d IIC
T6, IP 66 EN 50 014, EN 50 018, EN 50 281,EN 60529
(Certificate #DEMKO 03 ATEX 0252466)
Ambient Temperature
Storage and operation:
-50C to +80C (-58F to +176F)
Leadwires
H
L
mm
inch
124
31.7
47/8
11/4
inch
48
70
185
85
17/8
23/4
73/8
33/8
Increasing
System
Pressure
N.C.
N.O.
Signaling
Device
Typical Local Alarm Circuit
Standard wire length: 180 cm (72) when pressure
switch is supplied without terminal box
Weight
P
R
C
W
mm
Typical Electrical Connections
Pressure Switch
with Terminal Box
Pressure Switch
Pressure switch: approx. 0.34 kg (12 oz)
Pressure switch with terminal box: approx. 1.13 kg (40 oz)
The information herein is subject to change without notice. BERMAD shall not be held
liable for any errors. All rights reserved. Copyright by BERMAD. PCGPE71
11
Green Brown Blue Red
Ground COM N.O. N.C.
Typical Waterflow Alarm