On Load Tap Changer
On Load Tap Changer
On Load Tap Changer
tHE compact
on-LoaD tap-cHanGEr.
tr a n s fo r mEr controL
vacutap vv
Experience from us
security for you.
The on-load tap-changers of the VACUTAP series combine decades of experience in
vacuum-switching technology with the consistent further development of this technology.
This results in on-load tap-changers with unbeatable reliability and efficiency.
Compact design
ATEX-certified
MR vacuum switches are used in steel and aluminum smelters
around the world as well as on drilling rigs in areas that pose
an explosion hazard or in chemical operations with a corrosive
or dirty environment. This is because MR is the first and only
manufacturer of on-load tap-changers to have VACUTAP V V
and VACUTAP V R tap changers certified in accordance with
Directive 94/9/EC (ATEX) conforms to IEC and NEC 505 in North
America.
vacutap vv
2000
1500
1000
v v 250
v v 400
v v 600
step capacity
500
0
0
50
100
150
200
250
netzbetrieb
300
350
400
450
500
550
600
iu (in a)
Installation lengths
3-phase V V III
Y 40 kV
1-phase V V I
D 40 kV Y 76 kV
D 76 kV
D 145 kV
76 kV
145 kV
250, 400 A
400 A
400 A
h =1,628 mm
h =1,628 mm
h =1,810 mm
h =1,810 mm
h =2,224 mm
h =816 mm
h =978 mm
technical data.
On-load tap-changer
Designation V V III 250 Y V V III 250 D V V III 400 Y V V III 400 D
Number of phases and application
3; at neutral point
3; at any
3; at neutral point
point on winding
3; at any
point on winding
250
400
10
2,000
12.5
2,000 1,700 1
50 60 Hz
Without change-over selector: max. 12, with change-over selector: max. 23
200/350/650
200/350
70/140 70/140/275
200/350/650
70/140 70/140/275
Rated withstand voltages of internal insulation See table 2.3 in technical data for VACUTAP V V (TD 203)
Oil compartment Pressure-tight up to 0.3 bar permanent differential pressure (testpressure 0.6 bar),
head and cover of the on-load tap-changer are vacuum-proof.
Temperature range The VACUTAP V V on-load tap-changer can be operated in the rated load range at oil
temperatures of between -25 C and +105 C.
On-load tap-changer
Designation V V III 600 Y V V III 600 D V V I 401 3 V V I 401 3
Number of phases and application
3; at neutral point
3; at any
point on winding
1; at any
point on winding
600
400
15
2,000 1,000 1
12.5
2,000 1,700 1
50 60 Hz
Without change-over selector: max. 12
With change-over selector: max. 23
200/350/650
350
650
70/140/275
140
275
Rated withstand voltages of internal insulation See table 2.3 in technical data for VACUTAP V V (TD 203)
Oil compartment Pressure-tight up to 0.3 bar permanent differential pressure (test pressure 0.6 bar),
head and cover of the on-load tap-changer are vacuum-proof.
Temperature range The VACUTAP V V on-load tap-changer can be operated in the rated load range at oil
temperatures of between -25 C and +105 C.
1
2
3
4
vacutap vv
ENVIRONMENTALLY FRIENDLY
AND FORWARD-LOOKING.
A future trend in transformer technology has kept our developers busy: the increasing demand for higher fire safety, greater compatibility with the environment and
largely maintenance-free performance. We have found a solution. It is based on the
connection of our VACUTAP technology with alternative insulating fluids.
Fireproof
A variety of fluids is available on the market that fulfill fire protection requirements (class K fluids with a
flashpoint > 300 C to IEC 61100). The natural esters
seem particularly advantageous in this regard.
Water hazard class*
Mineral oil
HMWH
Silicone oil
Synthetic esters
Synthetic esters
Natural esters
Natural esters
VACUTAP
-15 to +115
-10 to +115
VV
Biodegradable
350
300
Silicon oils
50
Natural esters
100
Synthetic esters
150
250
Mineral oil
200
*Classification in accordance
with the German Administrative Regulation on the
Classification of Substances
hazardous to waters into
Water Hazard Classes
(VwVwS), Germany 1999:
WGK 0 = non-hazardous to
water, WGK 1 = low water
hazard
VACUTAP V V
an investment that pays off.
Maintenance-free and long-lasting
I Maintenance-free up to 300,000 tap-change operations with no time
component, therefore maintenance-free for virtually all network applications
I Change of vacuum interrupters only after 600,000 tap-change operations
I Change of the diverter switch insert only after 1.2 million tap-change operations
please note:
the data in our publications may differ from
the data of the devices delivered. We reserve
the right to make changes without notice.
in169/09 En vacutap v v
f0053808 10/13 dp
maschinenfabrik reinhausen GmbH 2013