Safety Guidelines
Operate the NI 9401 only as described in these operating
instructions.
This icon denotes that the component may be
hot. Touching this component may result in bodily injury.
Hot Surface
Caution
Caution
Caution
ni.com
Caution
DIO0
NC
DIO1
DIO2
NC
DIO3
DIO4
NC
DIO5
DIO6
NC
DIO7
14 1
15 2
16 3
17 4
18 5
19 6
20 7
21 8
9
22 10
23 11
24 12
25 13
COM
NC
COM
COM
NC
COM
COM
NC
COM
COM
NC
COM
COM
ni.com
Each channel has a DIO pin to which you can connect a digital
input or output device. The eight DIO channels are internally
referenced to COM, so you can use any of the nine COM lines as
a reference for the external signal.
The DIO channels are grouped in two ports, one containing
channels 0, 1, 2, and 3, and one containing channels 4, 5, 6, and 7.
You can independently configure each digital port in software for
input or output. Note that all four channels in the port must share
the same line direction. Refer to the software help for information
about configuring ports on the NI 9401.
Each channel also has a pull-down resistor and includes
overvoltage, overcurrent, and short-circuit protection. Refer to the
Specifications section for more information about input thresholds
and overvoltage protection. Refer to the Overcurrent Protection
section for more information about overcurrent protection.
SS
DIO3:0
Configured
for Output
SCLK
MOSI
MISO
DIO7:4
Configured
for Input
SPI Device
NI 9401
ni.com
DIO0 as Input
Dev 1
TTL Signal
DIO1 as Input
+5 V
Dev 2
+5 V
LED
COM
DIO7 as Output
NI 9401
Dev 3
Overcurrent Protection
Overcurrent protection on the NI 9401 allows only a specified
amount of current for switching DIO channels or sourcing the
output load. If the NI 9401 goes into an overcurrent state, by
exceeding the specified maximum switching frequency or the
output load, the module power supply begins to drop in voltage
until it completely turns off or the overcurrent condition is
removed. When the module is in this state, it can accept new line
direction configuration and output state data but cannot pass valid
input data to the software. Refer to the Specifications section for
more information about the maximum switching frequency and
output load for each channel.
10
ni.com
Sleep Mode
This module supports a low-power sleep mode. Support for sleep
mode at the system level depends on the chassis that the module is
plugged into. Refer to the chassis manual for information about
support for sleep mode. If the chassis supports sleep mode, refer to
the software help for information about enabling sleep mode. Visit
ni.com/info and enter cseriesdoc for information about
C Series documentation.
Typically, when a system is in sleep mode, you cannot
communicate with the modules. In sleep mode, the system
consumes minimal power and may dissipate less heat than it does
in normal mode. Refer to the Specifications section for more
information about power consumption and thermal dissipation.
11
Specifications
The following specifications are typical for the range 40 to 70 C
unless otherwise noted. All voltages are relative to COM unless
otherwise noted.
Input/Output Characteristics
Number of channels.......................... 8 DIO channels
Default power-on line direction ........ Input
Input/output type............................... TTL, single-ended
12
ni.com
13
14
ni.com
Power Requirements
Power consumption from chassis
Active mode ............................... 580 mW max
Sleep mode ................................. 1 mW max
Thermal dissipation (at 70 C)
Active mode ............................... 580 mW max
Sleep mode ................................. 1 mW max
Physical Characteristics
If you need to clean the module, wipe it with a dry towel.
Weight............................................... 145 g (5.1 oz)
15
Safety
Maximum Voltage1
Connect only voltages that are within the following limits.
Channel-to-COM .............................. 30 V max on one channel
at a time, Measurement
Category I
Isolation Voltages
Channel-to-channel........................... None
Channel-to-earth ground
Continuous ................................. 60 VDC, Measurement
Category I
Withstand.................................... 1,000 Vrms, verified by a 5 s
dielectric withstand test
Measurement Category I is for measurements performed on
circuits not directly connected to the electrical distribution system
referred to as MAINS voltage. MAINS is a hazardous live electrical
1
The maximum voltage that can be applied or output between any channel and COM
without damaging the module or other devices.
16
ni.com
Safety Standards
This product is designed to meet the requirements of the following
standards of safety for electrical equipment for measurement,
control, and laboratory use:
17
Hazardous Locations
U.S. (UL) .......................................... Class I, Division 2,
Groups A, B, C, D, T4;
Class I, Zone 2,
AEx nC IIC T4
Canada (C-UL) ................................. Class I, Division 2,
Groups A, B, C, D, T4;
Class I, Zone 2,
Ex nC IIC T4
Europe (DEMKO)............................. EEx nC IIC T4
Environmental
National Instruments C Series modules are intended for indoor use
only but may be used outdoors if installed in a suitable enclosure.
Refer to the manual for the chassis you are using for more
information about meeting these specifications.
Operating temperature
(IEC 60068-2-1, IEC 60068-2-2) ..... 40 to 70 C
Storage temperature
(IEC 60068-2-1, IEC 60068-2-2) ..... 40 to 85 C
Ingress protection.............................. IP 40
NI 9401 Operating Instructions and Specifications
18
ni.com
Operating humidity
(IEC 60068-2-56).............................. 10 to 90% RH,
noncondensing
Storage humidity
(IEC 60068-2-56).............................. 5 to 95% RH,
noncondensing
Maximum altitude............................. 2,000 m
Pollution Degree (IEC 60664) .......... 2
19
Electromagnetic Compatibility
This product is designed to meet the requirements of the following
standards of EMC for electrical equipment for measurement,
control, and laboratory use:
CE Compliance
This product meets the essential requirements of applicable
European directives, as amended for CE markings, as follows:
20
ni.com
Environmental Management
National Instruments is committed to designing and manufacturing
products in an environmentally responsible manner. NI recognizes
that eliminating certain hazardous substances from our products is
beneficial not only to the environment but also to NI customers.
For additional environmental information, refer to the NI and the
Environment Web page at ni.com/environment. This page
contains the environmental regulations and directives with which
NI complies, as well as other environmental information not
included in this document.
21
RoHS
National Instruments
(RoHS)
National Instruments RoHS
ni.com/environment/rohs_china (For information
environment/rohs_china.)
22
ni.com
23
National Instruments, NI, ni.com, and LabVIEW are trademarks of National Instruments Corporation. Refer to the
Terms of Use section on ni.com/legal for more information about National Instruments trademarks. Other
product and company names mentioned herein are trademarks or trade names of their respective companies.
For patents covering National Instruments products, refer to the appropriate location: HelpPatents in your software,
the patents.txt file on your media, or ni.com/patents.
20052008 National Instruments Corp. All rights reserved.
374068D-01
Jun08