H2 Type Direct Fire Chiller Operation Manual PDF
H2 Type Direct Fire Chiller Operation Manual PDF
H2 Type Direct Fire Chiller Operation Manual PDF
FOR
H2 TYPE DIRECT-FIRED LITHIUM BROMIDE
ABSORPTION CHILLER/HEATER
DF99~1984
CE
INTRODUCTION
First of all, let us express heartfelt gratitude to you for the application of direct-fired lithium
bromide absorption chiller/heaters, produced by Shuangliang.
The direct-fired lithium bromide absorption chiller/heaters, produced by Shuangliang, had win a
lot of national and province level awards, had been certified for safety protection, environment
friendliness and ISO quality assurance system. The chiller/heaters are good in performance, easy
to operate and durable for life cycle.
The technical manual covers the construction, operation principle, control system and guide to
installation, operation and maintenance of direct-fired lithium bromide absorption chiller/heater.
As very sensitive to maintenance, direct-fired absorption chiller/heater should be maintained
perfectly, otherwise it will be degraded and its operation life will be reduced. Read the technical
manual carefully before You operate it. This will bring benefit to Your Company.
The technical manual did not contain the description of auxiliary equipment, such as burner,
inverter and etc. You can find appropriate reference in the individual technical manuals published
by the manufacturers of auxiliary equipment. For the Chiller/heater, gas, oil, and oil/gas can be
used as fuel, you should pay attention to your order, and can find suitable material in this manual.
Warning: The chiller/heater You purchased from Shuangliang, should be commissioned by
Shuangliang engineering staff, and operated and maintained in accordance with the
provisions of this manual, otherwise the occurred trouble and damage of chiller/heater
should not included in the scope of guarantee offered by Shuangliang Co., Ltd.
Jiangsu Shuangliang Air Conditioning Equipment Co., Ltd, International Trade Department
Add: Shuangliang Industrial Park in Ligang, Jiangyin city, Jiangsu Province,
The Peoples Republic of China
Post code: 214444
Tel: +86-510-86638824
Fax: +86-510-86634678
Table of Contents
CHAPTER 1 DESCRIPTION OF ABSORPTION CHILLER/HEATER......................................... 1
1.1 DESCRIPTION OF FORMATION OF TYPE NUMBER ............................................................................. 1
1.2 THE NOMINAL OPERATION CONDITIONS AND WORKING LIMITS ..................................................... 1
1.3 CONFIGURATION OF CHILLER/HEATER ............................................................................................. 1
1.4 WORKING FLUID ............................................................................................................................. 5
1.5 WORKING PROCESS ......................................................................................................................... 6
1.6 PERFORMANCE OF CHILLER/HEATER ................................................................................................ 8
CHAPTER 2 INSTALLATION OF CHILLER/HEATER ............................................................... 10
2.1 REQUIREMENTS TO MAINTENANCE DURING INSTALLATION........................................................... 10
2.2 REQUIREMENTS TO MACHINE ROOM ............................................................................................. 10
2.3 INSTALLATION OF CHILLER/HEATER .............................................................................................. 11
2.4 ADJUSTMENT OF LEVELNESS OF CHILLER/HEATER ........................................................................ 12
2.5 INSULATION OF CHILLER/HEATER .................................................................................................. 13
CHAPTER 3 INSTALLATION OF EXTERNAL SYSTEMS ....................................................... 15
3.1 WATER SYSTEM (CHILLED AND COOLING WATER) .......................................................................... 15
3.2 LIGHT OIL SYSTEM ........................................................................................................................ 17
3.3 HEAVY OIL SYSTEM ...................................................................................................................... 18
3.4 FUEL GAS SYSTEM ........................................................................................................................ 19
3.5 GAS EXHAUST SYSTEM ................................................................................................................. 20
3.6 ELECTRIC SYSTEM......................................................................................................................... 21
CHAPTER 4 CHILLER CONTROL SYSTEM ................................................................................ 23
4.1 CONFIGURATION OF SYSTEM ......................................................................................................... 23
4.2 FUNCTION OF SYSTEM ................................................................................................................... 24
4.3 CONTROL PANEL ........................................................................................................................... 25
4.4 CONTROL FLOW CHART ................................................................................................................ 25
4.5 OPERATION METHOD ..................................................................................................................... 27
CHAPTER 5 COMMISSIONING OF CHILLER............................................................................. 33
5.1 PREPARING TO COMMISSIONING .................................................................................................... 33
5.2 COMMISSIONING OF BURNER ........................................................................................................ 36
5.3 COMMISSIONING OF CHILLER/HEATER ........................................................................................... 38
CHAPTER 6 OPERATION OF CHILLER/HEATER...................................................................... 40
6.1 SAFETY PROTECTION RULES ......................................................................................................... 40
6.2 PROCEDURE FOR COOLING OPERATION......................................................................................... 42
6.3 PROCEDURE FOR HEATING............................................................................................................. 43
6.4 OPERATION OBSERVATION AND INSPECTION .................................................................................. 44
6.5 PURGE OPERATION ........................................................................................................................ 46
6.6 MANAGEMENT OF REFRIGERANT WATER ...................................................................................... 48
6.7 MANAGEMENT OF LITHIUM BROMIDE SOLUTION .......................................................................... 49
1
Appendix
Attached Table 1 Saturated Steam Table (a) and (b)
Attached Figure 1 Crystallization Temperature Curve for LiBr Solution
Attached Figure 2 Specific Gravity Curve for LiBr Solution
Attached Figure 3 Saturated Steam Curve for LiBr
Attached Figure 4 Pressure -Temperature Curve for LiBr
Attached Table 2 Running Record
Attached Table 3 Chiller Electric Parameter Table
Attached Table 4 Performance Table for Breaker Used on Chiller
SAFETY POINTS
Safety points must be carefully read and fully understood by the operators before operation for
safe and correct use of Shuangliang Chiller.
Safety Warning
1.1 Indication in the manual
The following indication in boldface will be marked in proper positions of the manual to remind
any possible operators.
is to indicate any possible dangers for personal injury. Normally, instruction, brief
explanation and possible results due to neglect of those instruction will be closely followed.
is to indicate useful help information. That information has no relation to safety operation
but may help chiller efficiency and prolong service life of chiller. It also should be noted that help
information will not always be the optimal and will not necessarily bring benefits to chiller.
1.2 Operation Circumstance Warning
Control system should be forbidden to start under conditions below:
z Environment temperature lower 0 or higher 55
z Places of causticity or with flammable gas
z Places with large quantities of dusts, alkaline air or metal powder
z Places where may cause vibration or impacts to control system
z Places where water, oil or chemicals may be splashed over control system
to strong solution, which flows into the absorber. High temperature refrigerant vapor, which flow
through the heat transfer tubes of HP generator, is condensed by the solution outside the tubes, and
1.
2.
3.
4.
5.
6.
7.
Vacuum pump
8.
Gas cylinder
9. (55
Charge
valve
enters condenser through throttle. Pressure in the LP generator is about 7.33KP
mmHg).
10. Solution pump
Class
Purge
valve
Type
Stop
valve
Pressure
measuring
valve
Purge
valve
Stop
valve
Solution
valve
Stop
valve
Refrigerant
valve
Stop
valve
Cold water
valve
Refrigerant
valve
Purge valve
Ball
valve
Solution
valve
Connecting
valve
Stop
valve
Stop
valve
Ball
valve
Stop
valve
Condenser consists of heat transfer tubes and end covers. Cooling water from cooling tower
(about 32), enters heat transfer tuber via end covers, to condense the flashed vapor from HP
generator condensate through throttle and condense the refrigerant vapor from LP generator. Then
cooling water left the condenser at temperature about 38 to the cooling tower. Produced
refrigerant water flows into the flash chamber through U pipe. A part of refrigerant water is
flashed to form vapor, which flows into the re-absorption chamber at the bottom of absorber,
3
another part of refrigerant water is cooled, and enters refrigerant water pan. Condenser and LP
generator is arranged in one shell (upper shell) with identical pressure.
Evaporator consists of heat transfer tubes, end covers, refrigerant water distribution and spraying
piping, refrigerant water pan, refrigerant water chamber and refrigerant pump. Chilled water from
customer (about 12) enters heat transfer tubes through end cover, and evaporates refrigerant
water, which is sprayed over the tubes by the refrigerant pump from water chamber. Rest of water,
which had not been evaporated is collected in the water pan, and is sent to distribution tube again
to evaporate. Thus produced chilled water runs from the evaporator at temperature about 7
into the system of customer. Pressure in the evaporator is about 0.80~0.93Kpa (6-7 mmHg).
Absorber consists of heat transfer tubes, end covers, water distribution pan, solution chamber and
solution pump. Cooling water from cooling tower enters the heat transfer tubes through end cover
to cool the strong solution distributed outside tubes. At a set temperature and concentration (for
instance 50and 63%) lithium bromide solution possesses tremendous water vapor absorbing
capacity, and absorbs considerable refrigerant vapor, produced in the evaporator in the same shell,
and transfers the heat to the cooling water, which is dissipated to the cooling tower. After
absorbing water vapor, solution is diluted, and flows into the re-absorption chamber to absorb the
refrigerant vapor flashed in the flash chamber, then sent to HP and LP generators to be
concentrated. Absorber and evaporator locate in the same shell under the same pressure. Absorber
is divided into two parts, which are arranged in both sides of evaporator.
High temperature heat exchanger consists of two heat exchanger shells, which are composed of
heat transfer tubes, supporting rods and front and rear end covers. Weak solution flows through
internal part of tubes, and intermediate solution pass over the tubes. HT heat exchanger has the
purpose of increasing the temperature of weak solution and reducing that of intermediate solution.
Low temperature heat exchanger consists of two heat exchanger shells, which are composed of
heat transfer tubes, supporting rods and front and rear end covers. Weak solution flows through
internal part of tubes, and strong solution passes over the tubes. LT heat exchanger has the purpose
of increasing the temperature of weak solution and reducing that of strong solution.
Purge unit consists of purge piping and gas box (arranged in evaporator, absorber and condenser),
ejector, gas cylinder, solution return pipe, stop valves, and vacuum pump. It is functioned for
purge non-condensable gas from the chiller/heater to reduce the influence of .gas to the normal
operation of chiller/heater. During its operation, the non-condensable gas is extracted through
purge piping to the pressure reduced area of ejector, which is created by a part of weak solution,
supplied by the solution pump from absorber. Then gas flows with solution into the gas cylinder.
Gas is stored in the gas cylinder and gas box, and solution returns into the absorber through
solution return pipe. Stored gas can be discharged into atmosphere by vacuum pump, or
non-condensable gas can be evacuated directly by the vacuum pump.
Hermetically-sealed pumps (solution pump and refrigerant pump) are used to handling the
working media in the chiller/heater. Solution pump has the purpose to send the lithium bromide
weak solution from absorber to HP and LP generators through LT and HT heat exchangers.
Concentrated strong solution is returned to absorber. Refrigerant pump is used to spray refrigerant
over the tubes in the evaporator by extracting refrigerant from refrigerant pan of evaporator, then
refrigerant is evaporated by heat of chilled water.
Burner is the heat source for the chiller/heater, and can be oil or gas burner dependent the oil or
gas used.
Control panel is the control center of chiller/heater. For details of control panel, see Chapter 4.
1.4 Working Fluid
1.4.1 Refrigerant
As the refrigerant of absorption chiller/heater, water is used. For producing chilled water with 7
, pressure in the evaporator is only 0.9kPa (6.75 mmHg), and saturation temperature under
such pressure is 5.5(for relation of saturated steam and temperature of water, see attached table
1 ), which is the boiling point of water under such conditions. Refrigerant water is handled from
the refrigerant pan of evaporator, and sprayed over the tubes in the evaporator. System water to be
chilled in the evaporator has temperature of 12, which gives heat to refrigerant, and decreases
temperature. In the mean time, the refrigerant water gains heat, and evaporates.
1.4.2 Absorbent
As absorbent for the chiller/heater, lithium bromide solution is used. It can be taken as the carrier
of refrigerant water, and functions as to absorb the refrigerant vapor, produced in the evaporator
by removing heat of chilled water, and carries refrigerant into HP and LP generators. Weak
solution is divided into water and strong solution under the heat of burned fuel. Then the strong
solution returned into absorber to absorb water vapor, produced in the evaporator. Refrigerant
vapor enters condenser to be condensed by dissipating the heat into atmosphere through cooling
water. Refrigerant condensate returns into evaporator to produce cooling effect.
The new charged solution should meet the following technical requirements:
(1) Concentration: 50%0.5%;
(2) Alkalinity: pH value in the limits of 9.5~10.5;
(3) Lithium chromate content: 0.10%0.02%
Conditions:
Chilled water outlet temperature 7
Chilled water flow
100%
Cooling water flow 100%
Scale coefficient 0.086 m2.K/kW
Cooling water inlet temperature is changed
(lineally in relation to load)
100%load 32
60%load 28
20%load 24
Cooling water flow 100%
Scale coefficient 0.086 m2.K/kW
Cooling capacity
Fig. 1-6 Curve of cooling capacity in relation to fuel consumption
Cooling capacity
(%)
Conditions:
Chilled water flow 100%
Cooling water flow 100%
Scale coefficient 0.086 m2.K/kW
Cooling capacity
(%)
Conditions:
Chilled water outlet temperature 7
Chilled water flow 100%
Cooling water inlet temperature 32
Scale coefficient 0.086 m2.K/kW
Conditions:
Hot water outlet temperature 60
Hot water flow
100%
Heating capacity
(%)
Fig.1-9 Curve of heating capacity in relation to fuel consumption
Conditions:
Hot water flow 100%
Air leaks in the chiller/heater, causes corrosion of internal parts, affects its operation
life, and prevents it from normal operation under severe conditions.
During shipping, handling and installation, chiller/heater should be protected from man-made
damage and unauthorized operation of valves and instruments. In order to protect the chiller/heater
from leaks, the personnel is forbidden to climb the chiller/heater by the piping and valves. Control
panel, electric instrument and wiring should be protected from damage, control panel is not
allowed be opened and wiring be removed by uncertified operator. Protection means from
dampness and rain should be adopted.
All the outlet openings of chiller/heater should be covered to protect it from ingression of dirty
and foreign matter.
With original openings covered and protections provided chiller/heater should be covered by a
tarpaulin, but not plastic sheeting (which will permeate damp and speed up its corrosion), when it
is left in the open air. Chiller/heater or its parts, stored for long time in the room or in the open air,
should be covered carefully.
Box with bulk of parts is recommended to store at dry and safe place to ensure its intact.
2.2 Requirements to Machine Room
1. Machine room should be designed in accordance with the provisions of fire-fighting rules for
buildings, design rules for gas and oil fuel supply system, and other standards and
specifications.
2. Machine room should be provided with good ventilation and lighting facility. Discharge fans
should be installed with air change rate of 6-10 times in hour to meet the needs of combustion,
heat dissipation and safety.
3. Temperature in the room should be kept in the limits of 5-40, and humidity less than 90%.
4. Machine room should be supplied with power voltage of 380VAC10%, and without
accidental failure of power.
5. Machine room is provided with perfect drain system. Machine room should be constructed
against fire and water flood.
6. Machine room with gas-fired chiller/heater should be provided with gas leakage detection and
warning device, which should be designed with perfect functioning in the installed positions,
and interlocked with air discharging fans and gas quick shut-down valves.
10
7. Machine room should be arranged in such a way, that the chiller/heater is accessible to handling,
install, maintain, repair, replace the parts and modernize chiller/heater. Space and height should
be reserved for handling and transport the chiller/heater.
8. Minimum space with the dimensions shown in the Table2-1 should be reserved. Space for
changing tubes should be provided in axial direction from any one side of chiller/heater.
Chiller/heater can be installed with the ends against window or door for pulling the leaking
tubes.
9. Machine room should be designed with due considerations of its vibration and noise to the
surrounding rooms, and provided with good sound isolation, attenuation and vibration
absorbing means.
10. Machine room should be able to carry the total weight of whole package of chiller/heater and
its auxiliary equipment such as water pumps during their operation.
11. Machine room should be equipped with locks and screens for doors and windows to protect
from the entrance of unauthorized people.
12. Machine room should be provided with tools, spare parts and materials for maintenance of
chiller/heater and systems.
Table2-1 Minimum space, reserved around the chiller/heater
Axial direction
1.0m
Above chiller/heater
0.2m
From control panel
0.8m
Rear side
0.8m
2.3 Installation of Chiller/heater
The foundation for chiller/heater should be designed to carry the chiller/heater with operation
weight. as static load, because of its stable operation and minor vibration. The foundation should
be raised from the floor with dimensions in accordance with installation drawings provided by our
Company. During installation the transportation rack should be removed. The installation work of
chiller/heater is essential to its successful operation, especially the levelness should be ensured,
though the installation of chiller/heater is not so complicated.
In general, the chiller/heater is installed in the machine room, but it can be installed outside it, if
the conditions not allowed. But, the unit cannot be installed in the open air, when the lowest
circumstance temperature in the year is less than 5.When installed outside the room, means
should be taken to protect the chiller/heater body, control panel, measuring and control instrument,
burner and piping valves from rain, wind, corrosion and heat dissipation. Chiller/heater should be
installed with consideration of daily operation, and provision of space for withdraw of heat
transfer tubes from any end of chiller/heater. In the mean time, it can be installed with one end
oriented to the window. Drainage should be provided around the chiller/heater and covered with
perforated plate made from cast iron.
Before positioning the chiller/heater on the fundament, which should be cleaned from dirty, be
kept level and with dimensions in accordance with the design requirements. On the support area of
fundament, hard rubber plates with area bigger than supporting foot and thickness of about 10mm
should be covered.
1. Installation Of Assembled Chiller/heater
During installation of chiller/heater, it should be handled carefully with steel ropes placed on the
marked area. Every steel rope should have capacity to carry whole weight of chiller/heater.
Chiller/heater should be handled with care to be protected from damage of any parts. The position
of contact of ropes with the chiller/heater should be adjusted to avoid the damage of parts, such as
11
small diameter pipes, connecting wires and instrument. Chiller/heater should be handled in
horizontal position with slow movement in order to be protected from drop of unit owing to
deviation of center of gravity, when solution in chiller/heater is moved. Chiller/heater should be
lowered with all feet contacted with the surface of floor or fundament.
12
13
circuits shall not be damaged, and sight glass, temperature-measuring tubes, valves and drainage
cocks shall not be covered.
Insulation parts are shown in Fig.2-2.
14
Chapter 3
Chiller/heater is provided with external systems, such as water system (including chilled and
cooling water), fuel system and electric system.
3.1 Water System (chilled and cooling water)
Filters must be installed at water pump inlet and at chilled water inlet to protect the
heat transfer tubes from clogging by the foreign matters, to protect the chiller/heater from
degradation of performance and rupture of tubes by freezing.
Chiller/heater and pumps (including spare pumps) should be provided with pressure gauges (or
gauge common for measuring pressure at different locations by switching from location to
location, if it desirable). At the inlets and outlets of chiller/heater thermometers shall be installed.
For water systems of unit, flow meters with scale covering the nominal water requirements should
be installed in manner accessible for reading and maintenance.
Inlets and outlets of chilled (hot) water shall be connected with chiller/heater by short pipe of
15
about 800 mm in length to remove the end cover of evaporator and clean heat transfer tubes. At
inlets of chilled (hot) water, detachable filter with element of large area of 5-8meshes should be
installed. Water piping should be provided with drain valve at its lowest point, drain piping led to
channel, and vent at its highest point.
Pressure setting device shall meet the requirements for constant pressure and water drainage when
expansion and water makeup when leakage, if closed water system is used.
Cooling tower shall conform to the requirements of chiller/heater in water flow and
thermodynamic performance. Cooling tower with water collecting tank should be selected, if no
reservoir is provided for the cooling water system. Cooling tower shall be installed at place far
from source of heat and dust, especially from chimney, with good ventilation, taking consideration
of noise and water drift. Regulating valve and instantaneous water flow meter should be installed
at the make up and drain piping to keep the quality of cooling water. Cooling tower should be
operated by thermostatic control at the outlet of cooling water from tower, or fan of tower is
connected with the control system of chiller/heater, and on/off controlled from control panel.
Bypass piping with two-way or three-way valves can be connected between the inlet and outlet of
tower to maintain constant temperature of cooling water, while part of cooling water is bypassed
tower into chiller/heater in case of too low temperature of cooling water.
Pump can be installed at the outlet of chiller/heater to reduce the water pressure working on the
chiller/heater, when water system is operated under higher pressure.
16
Water system must be flushed completely before connecting with chiller. Otherwise,
heat transfer tube will be blocked, which will lower chiller efficiency and lead to serious
problems such as rupture of heat transfer tube.
When system installation is done without any leakage, please insulate chilled water piping
3.2 Light Oil System
17
tank should be provided with oil level control means and high and low level alarm devices, and
interlocked with oil supply equipment. No glass level gauge should be installed on the tank.
Filter (80 meshes) should be installed before oil entry into chiller/heater, in order to protect oil
pump, solenoid valves and nozzles from damage due to slag. The active area of filter should not
less than 20 times of piping outlet area, and a by-pass piping with valve should be connected in
parallel with the filter in order to clean the filter, when the unit is in operation.
It is preferred to use copper piping as fuel oil piping, but steel piping also can be used. Piping is
welded, leak-proof tested with pressure of 0.2MPa. Piping should be cleaned from debris before
its installation. The fuel oil should have velocity in the piping less than 0.2m/s.
It is prohibited to use oil with flash point 40 (for instance the gasoline, made by
local indigenous method).
3.3 Heavy Oil System
18
Heavy fuel oil should be heated to 50 by heating coil in the tank, then to 70 by the piping
jacket hot water or low pressure steam, when oil passing through piping, and to 100-130 by
electric heater in the burner in order to have a good atomizing.
Before shutdown the burner, heavy fuel oil in the burner should be replaced by light oil in order to
have reliable start operation. Light oil tank should be installed higher than the heavy fuel oil tank
by 0.5m to 1m, and heavy fuel oil tank should be installed higher than burner by 1-5m, but the
highest level in tank should not higher than burner by 10m. Daily tank, which is located in the
machine room, should be of closed type, not more 5m3 in volume for heavy fuel oil, and 1m3 in
volume for light fuel oil, and strictly prohibited to be located above the water heater unit or
horizontal section of flue gas channel.
Oil tank should be provided with venting piping, which is equipped with fire trap and rain
protecting means. Emergency discharging piping with easy to access and operate valves should be
installed on the oil tank to discharge oil outside the room into a specially mounted reservoir. Oil
tank should be provided with oil level control means and high and low level alarm devices, and
interlocked with oil supply equipment. No glass level gauge should be installed on the tank.
Filter (60 meshes) should be installed before oil entry into chiller/heater, in order to protect oil
pump, solenoid valves and nozzles from damage due to slag. The active area of filter should not
less than 20 times of piping outlet area, and a by-pass piping with valve should be connected in
parallel with the filter in order to clean the filter, when the unit is in operation.
It is preferred to use copper piping as fuel oil piping, but steel piping also can be used. Oil is
flowing through piping with speed not more than 0.2m/s.
Piping should be cleaned from debris before its installation. Piping is welded, leak-proof tested
with pressure of 0.2MPa to ensure no leakage of oil to outside or between piping and jacket.
It is prohibited to use oil with flash point 40 (for instance the gasoline, made by
local indigenous method).
3.4 Fuel Gas System
Gas piping in the machine room should be installed overhead. Gas piping for transporting gas with
density less than air, should be mounted in the high place with good ventilation; where as piping
for gas with density more than air, should be installed along the wall outside the machine room
with good accessibility.
Gas piping cannot be laid to machine room through bed room, stores with flammable and
explosive matters, electric distribution room, transformer room, cable trench, ventilation channel,
duct, flue gas channels and places, where piping is easy to be corroded.
Gas main should have dissipating piping, sampling and flushing ports, which are placed to purge
the gas and air from the piping. Dissipating piping should be led to outside of machine room. Its
discharge port should be rain protected, and located higher than the building roof by more than 2m
Discharged gas is not allowed to enter neighbor building, and be sucked by ventilation fans.
Dissipating piping should be designed to have purge capacity more than 10 to 20 times of section
volume to be purged, and with purge time 15 to 20 min. Gas piping should have lightning means
with grounding resistance less than 10 ohm, if it locates outside the lightning protection zone.
Gas piping should be air proof tested. As shown in Fig.3-5 the piping section, which locates
upstream pressure regulating valve, should be tested by 1.5 times working pressure and leak
checked by soap solution.
In order to ensure the gas supply to the chiller/heater, gas piping should be constructed with round
bends to decrease the pressure drop. Gas piping diameter should be at least one size bigger than
the diameter of burner.
Pressure at the gas inlet (the outlet of ball valve) should be in the limits prescribed in the catalog
of company. The pressure deduction valve should be installed, where the gas inlet pressure is
higher than high limit in the catalog.
In order to keep gas valve group, piping and fittings intact during transportation, they should be
packed in boxes, and installed on site of customer. For ensuring the tightness of connections, gas
valve fittings should be installed to meet the following requirements:
For flange connections, high quality sealing gaskets (asbestos-rubber gaskets) are used, and then
bolts tightened.
For threading connections used for gases, threading is to be sealed by following means:
For connections used for city gas, connections should be sealed by white lead compound with
linen packing
For connections used for natural gas, connections should be sealed by PTFE tape
Corrugate pipe should be installed between ball valve outlet and filter inlet.
3.5 Gas Exhaust System
Flue gas channel and chimney should be designed to keep the pressure at the outlet between
50Pa~0Pa (-50 to 0 Pa).
The section of flue gas channel and chimney should be not less than the section of discharge port
of unit. The main flue gas piping should have section not less than the sum of sections of branches
with valves which should have opening indicating means, no matter the valve is automatic or
manual driven.
It is recommended to adopt flue gas channel with round section. The turns of piping should be
rounded, and the construction shown in Fig.3-6 should be adopted for the branches joining
20
together, and converging and expanding construction for the changing sections.
Chimney height should be not less than (0.6L+ N) m, where L is the length of horizontal section of
flue gas channel in m, N is the number of turns of flue gas channel. The chimney should be higher
than the surrounding buildings by more than 3 m, if they are in the limits of 200m around the
chimney. On the outlet of chimney a rain protecting cap, lightning rod and wind protecting cover
should be mounted. Rain protecting cap should have diameter equal to two times of that of
chimney. The place of outlet of chimney should be chosen to make observations of smoke
emission easily.
The horizontal section of flue gas channel should have trap on its lowest section above the
equipment, which shall connected with the drain piping led from flue gas box of chiller/heater unit,
and through 200mm U-shaped trap discharged to the canalization.
Chimney should be constructed with bricks and concrete in order to avoid corrosion. The pipe
thickness should be not less than 4mm, if the steel construction is adopted.
For compensation the heat expansion of chimney, the expansion joint should be provided on the
straight section, and fire retarded and heat resisted soft material should be placed, when the flue
gas pipe passes through wall and when flange is installed.
Flue gas channels should be insulated, when they are checked to have good air-tightness.
Insulation material ( such as rock wool felt or cement-perlite plate ) can withstand working
temperature of 350
21
Failure of special grounding pole or using zero line instead of grounding pole will
cause severe damage of chiller/heater or injury or death of personnel.
The standard supplied chiller/heater is provided with interlocked control of cooling water pump,
chilled water pump and fans for cooling tower. The pumps (including standby ones) and fans for
cooling tower must be connected with the control system of chiller/heater. The electric distribution
panel should have terminals for connecting control lines for pumps and fans. If more than one
chiller/heaters share one cooling water system, electric driven valves must be set at cooling water
inlets of each chiller/heater to realize interlocked function of control system. The control lines
should be laid and marked by customer. For a chiller/heater, 14 control lines of 0.75mm2 should be
provided. Power lines should be laid separately from control ones.
Chilled water and cooling water pumps (including standby pumps) and fans for
cooling tower must be interlocked with control system of chiller/heaters. At cooling water
inlets of each chiller/heater, electric driven valves must be set to interlock with control
system, if more than one chiller/heaters have to share one cooling water system. Otherwise,
Shuangliang Air-conditioning will not take any responsibility for malfunction and other bad
results such as rupture of tubes.
Signals from gas leakage and fire alarm should be interlocked with the control system of
chiller/heater.
Chiller/heater with remote control and monitoring should be installed by the customer in
accordance with the requirements of Installation and operation manual for remote on/off and
monitoring system.
22
Output
Signal
Input
Signal
Level of HP generator
Pressure of HP generator
Evaporation temperature
Condensation temperature
23
Remote,
Concentrated
Control
Touch
Screen
PLC
Controller
Extendible
Functions
24
Middle concentrated
solution temperature
De-crystallizing pipe
temperature
Flue gas exhaust
temperature
166
13
65
14
The safety
Set value
128KPa
(960mmHg)
60%
of
nominal value
100%
of
nominal value
100%
of
nominal value
100%
of
nominal value
100%
of
nominal value
250
15
25
DESCRIPTION OF TOUCH SCREEN. Press this key and on the screen will show the
descriptions of keys and give the user the instruction to operate the touch screen.
WORKING PRINCIPLE OF CHILLER/HEATER Press this key, on the screen will show the
flow chart of chiller/heater for refrigeration and heating, and working principle for refrigeration
and heating also.
OPERATION INSTRUCTION OF CHILLER/HEATER Press this key, on the screen will be show
the more than 10 methods of operation, such as sampling of refrigerant water, charge of solution,
inspection of chiller/heater for air-tightness.
OPERATION HISTORY OF CHILLER/HEATER Press this key, on the screen will show the last
three troubles and the operation data during week.
OPERATION MODE SELECTION Press this key to select the mode of operation (Auto or
Manual, the chiller/heater cannot be changed to manual operation, while the unit is operated under
AUTO control).
CHILLER/HEATER MONITORING Press this key, the screen will show the figure of monitoring,
which is dependent to the control mode. Operator can operate the chiller/heater, solution,
refrigerant and vacuum pumps, and set the data, such as outlet temperature of chilled water. The
current information on the different parts of chiller/heater can be shown also.
DATA SETTING Press this key the adjustable data, such as the outlet temperature of chilled water
27
can be set, and diminish the deviation of displayed value and actual value of operation data.
MIANTENANCE GUIDENCE Press this key the screen will show the contents and methods of
maintenance.
1) The screen protection function is provided, which will stop display (blacken), if no
operations of screen occurred during 1h. For this period the control function of
chiller/heater is maintained, and the screen will continue work, if it is touched lightly.
2) The screen can be cleaned by soft wet rag, no volatile solvent (such as benzene) can be
used.
3) Internally set values and positions of external toggle switches are fixed in the factory, and
not allowed be changed by customer.
4.5.2 Operation Mode and Control Selection
The Graph of Operation Mode selection can be selected by pressing the Key OPERATION MODE
SELECTION of main menu, or pressing the Key MENU to have display the menu graph, then to
select operation mode by pressing the appropriate key. On the Graph of OPERATION MODE
there are two operation modes (refrigeration and heating), and two types of control (Auto and
Manual). You can select the operation mode and control type, and then to press the key
CONFIRMATION to get the appropriate chiller/heater operation monitoring graph.
For changing the operation mode between the refrigeration and heating modes, you should
open/close the appropriate switching valves.
4.5.3 Data Setting
The Data setting graph can be selected by pressing the Key DATA SETTING of main menu on the
touch screen, or by pressing the Key MENU on the right upper angle of screen. In later case, touch
screen will display menu graph, then to select Data setting graph by pressing the appropriate key,
when the screen is displaying other graph. There are two kinds of data can be set, namely the
regulating data setting and setting of deviation for displayed data.
4.5.3.1Regulating Data Setting
The regulating data should be changed, while the chiller/heater will be operated on the new
conditions. Regulating data include set values for chilled (hot) water outlet temperature, cooling
water inlet temperature, pressure in HP generator, and appropriate P,I D values. P,I,D values
should be set by certified personnel.
28
There will be regulating data display graph by pressing the key of setting of regulating data under
the data setting graph. Pressing the key of Password for data setting, input the correct password on
numerical keyboard, and press the key Enter to have the graph of setting data. At this time, the
data can be changed. The graph remains unchanged, while the password is erroneous. The input
deviation will be cleaned by pressing the key CLR on the numerical keyboard.
During changing the data, touch screen will display numerical keyboard by pressing the
push-button on the left side of data to be changed. The data will be changed by input new values
and pressing the key of confirmation. The setting of data is finished by pressing the key OFF on
the numerical keyboard.
4.5.3.2 Setting of Deviation for Displayed Data
The deviation between the value measured by calibrated standard instruments and displayed value
on the touch screen can be removed by changing the set deviation of displayed data. For example,
the value of chilled water outlet temperature measured by calibrated thermometer is 7, and
displayed value of this temperature is 6.5, then the deviation of displayed data should be
increased by 0.5 on the basis of set deviation. Changing of set deviation is similar to that of
changing of set value of operation data.
During changing the data, touch screen will display numerical keyboard by pressing the
push-button on the left side of data to be changed. The data will be changed by input new values
and pressing the key CONFIRMATION. The data are set by pressing the key OFF on the
numerical keyboard.
4.5.4 Operation of Chiller/heater
4.5.4.1 Start/stop of Vacuum Pump
Vacuum pump can be started or stopped at any time. But before attempting to start vacuum pump,
it should be checked for oil level, and operated in accordance of paragraph 6.9 of Chapter 6
Management of vacuum pump.
The graph of chiller/heater monitoring is displayed by pressing the key CHILLER/HEATER
MONITORING of main menu; or pressing key MENU on the upper right angle to display the
content of main menu, then pressing the key CHILLER/HEATER MONITORING to display the
graph of chiller/heater monitoring, when touch screen displays other graph; or to display the graph
of chiller/heater monitoring after selecting the operation conditions.
Purge is realized by pressing key VACUUM PUMP START to start the vacuum pump, then open
the lower purging valve and related purge valves. Before shutdown of vacuum pump, close lower
and upper purging valves then press the key VACUUM PUMP STOP.
The lower purging valve of vacuum pump should be closed, before the vacuum
pump is to be stopped.
4.5.4.2 Start/Stop of Solution and Refrigerant Pump
Solution and refrigerant pumps are started and stopped automatically, when the automatic
operation mode is selected. The only work to be done by the operational personnel is to start and
stop chiller/heater in accordance with the following procedure.
29
Solution and refrigerant pumps should be started or stopped by the operational personnel in the
following procedure manually, when the manual control mode is selected:
The graph of chiller/heater monitoring is displayed by pressing the key CHILLER/HEATER
MONITORING of main menu; or pressing key MENU on the upper right angle to display the
content of main menu, then pressing the key CHILLER/HEATER MONITORING to display the
graph of chiller/heater monitoring, when touch screen displays other graph; or to enter the
operation monitoring by selecting the mode of operation and control during the chiller/heater shut
down. Solution and refrigerant pumps can be started or stopped by pressing the keys SOLUTION
PUMP START, REFRIGERANT PUMP START, or SOLUTION PUMP STOP , REFRIGERANT
PUMP STOP.
1) Before startup of solution pump, it is essential to ensure that solution has been charged.
2) Prior to startup of refrigerant pump, strong solution concentration shown on touch screen
should be ensured above 56% and chilled water system is to be checked to protect heat
transfer tubes from freezing.
3) During manual control the solution pump is not allowed be operated under manual mode,
and be controlled by the control system according to the solution level and temperature.
4.5.4.3 Start/Stop of Chiller/heater
The chiller/heater monitoring graph is displayed by the operation mode selection and data setting.
Graph of trouble monitoring will be displayed by pressing key TROUBLE MONITORING. The
following ope4ations can be done, when the chiller/heater trouble-free indicating red LED lights
(except failure of chilled/hot water)
The positions of heating solution and vapor valves should be confirmed. They will be closed for
cooling mode, and opened for heating mode.
The chilled/hot water pump is to be started with its outlet valve closed. Then the outlet valve is
opened step by step to get the nominal flow rate. Cooling water pump is started in the same way as
for chilled/hot water pump. After the ventilation fan for machine room and fuel input valve is
opened, and chiller/heater will be started and stopped in the following way according selected
operation mode.
A. Automatic Control (Cooling Mode)
Chiller/heater will be started and come to normal operation by pressing the key SYSTEM START,
and then pressing the keys CONFIRMATION, and RE-CONFIRMATION, which appears in the
graph of chiller/heater operation monitoring on the touch screen. During cooling operation cooling
water inlet temperature should be controlled by operational personnel in the limits of 36-38.
Chiller/heater is stopped by pressing the key SYSTEM STOP on the graph of chiller/heater
operation monitoring. Following this operation, the chiller/heater will be operated with automatic
dilution, and burner will stop firing (The fuel inlet valve is closed by operational personnel
manually). When solution concentration detected reaches 58%, stop refrigerant pump and after 5
minutes when solution is diluted to 56%, stop solution pump and shut off cooling water pump
automatically. Afterward chilled water pump will be stopped automatically 3 min later.
30
But it is limited to work on small fire, when the cooling water inlet temperature is
less than 28, or chilled water outlet temperature is less than nominal value.
During refrigeration operation, when cooling water inlet temperature less than 28,cooling water
outlet temperature should be controlled by operational personnel in the range of 36-38.
Chiller/heater is stopped by pressing the key SYSTEM STOP on the graph of chiller/heater
operation monitoring. Following this operation, the chiller/heater will be operated with automatic
dilution, and burner will stop firing (The fuel inlet valve is closed by operational personnel
manually). When solution concentration detected reaches 58%, stop refrigerant pump and after 5
minutes when solution is diluted to 56%, stop solution pump and shut off cooling water pump
automatically. Afterward chilled water pump will be stopped automatically 3 min later.
D. Manual Control (Heating Mode)
On the graph of chiller/heater operation monitoring the key SYSTEM START is pressed, then the
key CONFIRMATION and RE-CONFIRMATION is pressed in the following graph, then the
graph chiller/heater operation monitoring is displayed again. The solution pump is started and
solution circulation is controlled automatically by pressing the key SOLUTION PUMP START.
Burner will work at small fire by pressing the key BURNER IGNITION and BURTNER SMALL
FIRE.
During operation chiller/heater can be work on big fire or small fire by the pressing the BURNER
BIG FIRE OR BURNER SMALL FIRE.
But it is limited to work on small fire, when hot water outlet temperature is higher
31
32
33
installed properly according to the piping drawing. Piping shall be installed correctly. Sensing
and alarm means against the gas leakage shall be installed in the machine room, and
interconnected with the forced draft fan of machine room. Connected piping and elements shall
be proved tightly. Check the gas supply pressure by closing the cut-off valve at the inlet of gas
flow meter. The piping shall be purged by gas before ignition occurs, if it is worried, that the
gas in the piping is mixed with air.
3) Inspection of Burner. The burner shall be inspected according to the operation manual, wiring
drawing and piping installation as follows: (1) Check the burner for correct installation
according to the technical manual of burner. (2) Check the connections on the terminals of three
phased motor for correct direction of rotation. (3) Check, that the control wiring and power
supply cables are connected properly with the control panel according to the drawing. (4) All
the combustion control and safety protection means are connected and functioned properly.
4) Inspection of Flue Gas Piping. Check the flue gas piping against the provisions of installation
manual.
It is prohibited to use the fuel oil with flash point 40C (such as the gasoline or fuel
oil manufactured with indigenous method)
5.1.3 Inspection of Vacuum Pump
1) Check vacuum pump oil for its correct type; check vacuum pump oil for its appearance, oil will
be emulsified, if it contains water.
2) Check vacuum pump for its correct rotation. Ensure the low purge valve of vacuum pump is
closed. Remove the plug from the sampling and purge valve, and cover the valve opening by
finger. Put the vacuum pump into operation. The pump is operated in the correct direction, if air
is socked through the valve opening. Change the motor cable connections, if it is rotated in the
wrong direction.
5.1.4 Inspection of Chiller for Air Tightness
The chiller has been tested for air tightness strictly before shipping. However, leakage is likely to
occur at some locations due to vibration and impact during transportation handling, and
installation. Chiller should be rechecked for air tightness prior to starting the commissioning first
under vacuum, and then under pressure, if the former is not satisfactory. The inspection of air
tightness is repeated to get the satisfactory results.
5.1.4.1 Leakage Detection under Vacuum
Close all valves, which are exposed to atmosphere. The chiller is evacuated by vacuum pump to a
pressure below 30Pa, if it is not tested in factory. Stop the vacuum pump, record local ambient
temperature t1 and read the absolute pressure P1 by McLeod gage. Record ambient temperature t2
and absolute pressure P2 in chiller after 24h. Calculate the pressure increase ( P ) in the chiller
by the following formula, and shall not exceed 5Pa:
P = P 2 P1
273 + t 2
273 + t1
Chiller/heater, which had been tested in the factory, shall be tested for air-tightness by the air
34
bubbles, that a rubber or plastic hose shall be connected with the discharge opening of vacuum
pump at one end, and inserted into the vacuum oil in a vessel at the another end. a) The vacuum
pump is tested for the limit of evacuation. b) If the limit of evacuation meets the requirements,
open the purge valves for condenser and absorber, then the upper and lower purge valves of
vacuum pump slowly to evacuate for 2 minutes, close the ballast valve of pump, and count the
number of bubbles per minute. The air-tightness of chiller/heater is normal, if the number of
bubbles in a minute is equal or less than 7. Repeat the test, if the number of bubbles in a minute is
more than 7. The chiller/heater shall be pressure tested for air-tightness, if the number of bubbles
not reduced in the interval of 2 hours, and kept in a rather big number.
5.1.4.2 Leakage Detection under Pressure
The chiller/heater is charged with nitrogen (for LiBr solution charged chiller only nitrogen is used)
to the pressure of 0.1~0.12Mpa (760-910mmHg)or oil free compressed air, and possible locations
of leakage for welds, valves, flange seals, sight glasses etc is covered by soap solution. Leakage
takes place while bubbling. Then vent nitrogen from chiller and repair by welding. After that, the
chiller/heater is rechecked under vacuum as mentioned earlier.
Gas is charged and vented normally by refrigerant sampling valve (refrigerant is bypassed, then
gas charged), or other valves, which communicate with atmosphere, if chiller/heater is not filled
with solution and refrigerant.
Before filling gas the purge valve of condenser and upper purge valve of vacuum
pump shall be opened.
5.1.5 Inspection of Control Elements and Electric Equipment
During transportation and installation of chiller the control elements and electric equipment is easy
to be damaged. So after installation, the chiller is checked for its completeness by the personnel of
Shuangliang Service Co.
1) Inspection of Field Wiring
Check the power and interlocking wiring of power source and its equipment (such as cooling
tower, pumps, and etc.)
2) Inspection of Chiller Control
Inspect the control panel for its intact, and correct wiring, data setting and installation of sensors
and flow switch.
5.1.6 Charging of Solution
LiBr solution is supplied with (0.100.02)% of lithium chromate or (0.010~0.0018)% of lithium
molybdate as corrosion inhibitor. pH value for LiBr solution mixed with lithium chromate has
been adjusted to 9-10.5, and concentration of (500.5)%. Alkalinity for LiBr solution mixed with
lithium molybdenum has been adjusted to 0.01~0.02, and concentration of (500.5)%. These data
should be reconfirmed before their charging into the chiller.
Solution is charged under negative pressure through solution charging valve at the discharge side
of solution pump. Before solution is charged, the weak solution regulating valve and intermediate
solution valve is opened. Evacuate the chiller down to absolute pressure in the chiller is lower than
35
100 Pa (or to the water vapor saturation pressure, equivalent to the ambient temperature, if the
chiller is charged with solution or water). Then, as shown in Fig. 5-1, connect the vacuum or
reinforced rubber hose to the connection of solution charging valve with vacuum grease from one
end, and hose is filled with solution. Emerge the hose into a vessel with solution of 0.6m3 from
another end. Open the solution charging valve and solution will be suck into the chiller. Keep the
end of hose under the solution surface in the vessel constantly, and adjust the valve opening to a
normal flow rate of solution.
Solution is charged in three portions. First charged solution about half the required amount. Then
the solution charging valve is closed and operate the solution pump to transfer solution into the HP
generator. Stop the solution pump, when the solution level in the HP generator is up to the high
level (inverter reduces its frequency output to 10Hz). Then charge the solution additionally 1/3,
and start the burner and solution pump make the solution circulated. Stop the burner and solution
pump, and charge the rest of solution, when the solution concentration shown on touch screen is
56%.
After charging of solution, start the vacuum pump to purge the chiller.
The commissioning of burner is dependent upon the type of burner. Here only the
36
37
burner should be stopped, and the flame of first stage should be re-adjusted by register (opening
will be increased or reduced accordingly), if the smoke is discharged or flame is not stable. For
gas-fired chiller/heater, the gas to air ratio can be adjusted during combustion of gas.
For primary start up of burner, the fuel pipe may be left with some air. So the
ignition should be repeated for several times. It should be re-adjusted, if it cannot be
ignited after several trials of ignition. During primary ignition or normal operation of
chiller/heater, the ignition will fail to work, if the flame detector cannot detect the flame.
Then the safety protection cutout switch and the interlocking switch operate, and
indicator FLAME CUTOUT lights. The chiller/heater can be started again, only when the
cause of trouble is determined, and reset switch is pressed manually. The chiller/heater
shall stop work at once to prevent the heat transfer tube bundles and flue gas channel
from carbon settling, if thick smoke occurs. The commissioning of chiller/heater can be
restarted, if fuel flow is reduced or air flow is increased.
10)After the small fire is ignited, the small fire should be changed to big fire. The register for big
fire should be adjusted, if the big fire is abnormal. The maximum gas and oil flow is adjusted
during big fire.
12)The burner should be stopped, and commissioning is finished.
For gas-fired chiller/heater, the air pressure switch, maximum and minimum gas pressure
switches should be set before the burner stops operation.
Setting of air pressure switch: During the burner operation with small fire, air pressure switch is
set by turning slowly the knob clockwise to cut the flame. Make reading of the position of knob,
and turn the knob anti-clockwise to about 20% of last reading. Then the burner is re-ignited to
check the correct setting. Turn the knob anti-clockwise a little further, if the burner cannot work
normally.
Setting of maximum gas pressure switch: During the burner operation with big fire, maximum
gas pressure switch is set by turning the knob of pressure switch anti-clockwise to cut the flame.
Make reading of the position of knob, and turn the knob clockwise by about 2mbar. Then the
burner is re-ignited. Turn the knob clockwise further by 1mbar, if the burner cannot work
normally.
Setting of minimum gas pressure switch: During the burner operation with big fire, minimum
gas pressure switch is set by turning the knob clockwise to cut the flame. Make reading of the
position of knob, and turn the knob anti-clockwise by about 2 mbar. Then the burner is
re-ignited. Turn the knob anti-clockwise further by 1 mbar, if the burner cannot work normally.
5.3 Commissioning of Chiller/heater
Chiller/heater shall be commissioned by trained personnel from Shuangliang Service Co. Ltd.
For the heating mode the commissioning of chiller/heater or its primary firing shall be
done with the heat transfer tubes and water heads of absorber filled by water. That means,
close the valves on the inlet and outlet of cooling water piping, open the connecting valves on
the water heads of evaporator-absorber and venting valves for the water heads of absorber
38
and condenser to fill the heat transfer tubes of absorber and condenser. Close the venting
valves, when air discharged. Close the connecting valve of evaporator-absorber, when
pressure reaches about 0.3kg/cm2.
39
40
12.The machine room should be kept with good ventilation without clogged intake and discharge
openings. Open the damper in the fume piping, if it is provided.
13.For oil-fired chiller/heater, the oil filter should be washed once a day successively for three
days.
14.The nominated power supply should be used. No contact with switches, wires, elements and
high-tension wires for igniter of burner to prevent from electric shock. Power supply can be
cutout only when the chiller/heater is in standstill.
15.The chiller/heater is kept from risk by dripping water on the electric elements.
16.The operation of chiller/heater is forbidden with control panel opened.
17.The operation of chiller/heater is protected from harm the operational personnel by keeping
them from touching the high temperature parts, such as the HP generator, HT heat exchanger
and its piping (with temperature of 160) and the LP generator, LT heat exchanger, and its
associated piping.(with temperature of 90)
18.No heating operation of chiller/heater is allowed, if it has not operated for cooling mode before
19.No hot water of temperature up to 60 is permitted to flow through the chiller/heater, which
is in standstill, if several units are in parallel operation..
20.The chiller/heater should be checked and maintained strictly with the provisions of chapter 8
Maintenance and Service
21.Lithium bromide solution is not poisonous, but irritant, when it is mixed with other chemicals.
The machine room should be kept with good ventilation. The place dripped with solution
should be washed.
22.The machine room should be kept with temperature in the limits of 5-40, and relative
humidity less than 90%.
23.Before operation of vacuum pump the oil trap should be drained to empty once a month.
24.The battery for PLC and touch screen should be changed periodically (once for 3 years).
Change of battery should be finished in 5 minutes. For PLC, the battery should be changed in
the interval of 7 days of total standstill conditions of PCL to avoid loss of program, if the
ALARM on CPU lights, but the chiller/heater can be operated further. For touch screen, the
battery should be changed in the interval of 5 days of total standstill conditions of touch screen
to avoid loss of program, if the LOW BATTERY (in Japanese) lights, but the chiller/heater can
be operated further.
25.The chiller/heater is supplied with the interlocking functions, and it is recommended, that the
customer connect the start/stop circuits of chilled and cooling water pumps and cooling tower
fans with the control system of chiller to control the start/stop of pumps and fans by the control
system of chiller. At least the chilled and cooling water pump should be interlocked to stop the
cooling water pump first and then the chilled water pump, if they do not interlocked with the
chiller.
26.The chilled and cooling water piping should be designed and installed with valves at the piping
inlets and outlet from the chiller, and a piping with a valve bypassing the chiller is provided
before the valve to the inlet of chiller and after the valve from the chiller. In order to flushing
the piping, the valves at the inlets and outlets should be closed and valve on the bypassing
piping opened. After the operation, the inlet and outlet valves should be opened, and valve on
the bypassing piping closed.
27.The chiller/heater and pumps should be installed with filters at their inlets to be prevented from
41
the entering of foreign matters to the tubes of chiller, otherwise the degrading of performance
of chiller/heater and freezing of tubes will occur.
28.The chiller/heater should be installed on the fundament after the transport rack is removed. If
the conditions required that the chiller/heater will be installed with the rack, then the welded
angle sections or plates, which fixed the heat exchangers to the transporting rack, should be
removed. For some chiller/heaters, the low temperature heat exchanger welded to the rack by
angle section only at one end, and fixed to the evaporator-absorber from the another end. In
this instance, only the angle section should be removed.
29.Solution should be charged or transferred with less loss of it. The solution traces should be
cleaned from the ground and the chiller. The chiller should be repainted at the parts, where
paint is damaged.
30.For direct fired chiller/heater, the change-over from heating to cooling mode or from cooling to
heating should be realized, in addition to open/close the vapor and solution valves, by
regulating the fuel flow with the working condition of chiller/heater (the adjusting of burner
should be done in accordance with the instruction). For the chiller/heater with generator
enlarged for more than two sizes (including two sizes), the burners are supplied with two stage
nozzles. For cooling mode the small nozzle should be installed, and for the heating operation,
the big nozzle should be used.
31.For direct fired chiller/heater, the commissioning of burner should be done by Shuangliang
engineers. The burner should be adjusted with the gas analyzer to measure the CO and O2
contents in the gas to make the appropriate ratio of air to the fuel. The sensor of analyzer
should be put into the chimney from the chiller high pressure generator, and check the CO and
O2 content, while adjusting the fuel and air ratio. The CO volume content0.02%, and O2
volume content 3%-5% should be maintained. The operation instruction of gas analyzer
should be followed.
6.2 Procedure For Cooling Operation
6.2.1 Procedure of starting
1. The air breaker in the control panel is closed, and on the graph of TROUBLE
MONITORING the NO TROUBLE indicator lights (except the trouble of failure of chilled
water), and the graph can be switched to the CHILLER/HEATER MONITORING.
2. The chilled/hot water pump is started when the valve on the chilled/hot water pump outlet is
closed, and then to open the valve slowly to adjust the flow or pressure drop to the nominal
value.
3. The cooling water pump is started when the valve on the cooling water pump outlet is closed,
and then to open the valve slowly to adjust the flow or pressure drop to the nominal value.
4. Open the fuel inlet valve.
5. Press the key SYSTEM START, then the key CONFIRMATION, and finally the key
RECONFIRMATION on the CHILLER/HEATER MONITORING, to put the chiller/heater
into the operation condition.
6. Start the fan of cooling tower, and adjust the cooling water flow to control the cooling water
outlet temperature in the limits of 36-38.
7. Check the chiller/heater operation periodically, and take records every 2h.
42
To decrease the flowrate of cooling water in case low cooling water temperature or
running at low load conditions
6.2.2 Procedure of shutdown
1. Press the key SYSTEM STOP, and chiller/heater will be put into operation of dilution.
2. Automatically shut down burner and manually close the fuel inlet valve for chiller/heater.
3. Automatically stop refrigerant pump when solution concentration detected is 58%.
4. When solution is diluted to 5%, delay 5min to automatically stop solution pump and cooling
water pump and afterward delay 3min to automatically stop chilled water pump
5. Cut the power supply from the control panel.
1. All refrigerant water should be bypassed from evaporator to the absorber during
shutdown, when the ambient temperature is less than 20, and the chiller/heater will
stand longer than 8h.
2. The chiller/heater is operated normally, when the safety device is checked periodically
and its normal working is guaranteed.
3. Check the chiller/heater in accordance with the provisions of this technical manual.
6.3 Procedure for Heating
6.3.1 Procedure of Starting
1. The air breaker in the control panel is closed, and on the graph of TROUBLE
MONITORING the NO TROUBLE indicator lights (except the trouble of failure of
chilled/hot water), and the graph can be switched to the CHILLER/HEATER
MONITORING.
2. The chilled/hot water pump is started when the valve on the chilled/hot water pump outlet is
closed, and then to open the valve slowly to adjust the flow or pressure drop to the nominal
value.
3. Open the fuel inlet valve.
4. Press the key SYSTEM START, then the key CONFIRMATION, and finally the key
RECONFIRMATION on the CHILLER/HEATER MONITORING, to put the chiller/heater
into the operation condition.
5. Check the chiller/heater operation periodically, and take records every 2h.
6.3.2 Procedure of shutdown
1. Press the key SYSTEM STOP, and chiller/heater will be put into operation of dilution.
2. Automatically shut down burner and manually close the fuel inlet valve for chiller/heater.
3. Delay 15min to automatically stop solution pump and afterward delay 3min to automatically
stop hot water pump
4. Cut the power supply from the control panel.
43
1. All refrigerant water should be bypassed from evaporator to the absorber during shutdown,
when the ambient temperature is less than 20, and the chiller/heater will stand longer than
8h.
2. The chiller/heater is operated normally, when the safety device is checked periodically and its
normal working is guaranteed.
3. Check the chiller/heater in accordance with the provisions of this technical manual.
6.4 Operation Observation and Inspection
In order to ensure the normal operation of chiller/heater constantly, observation of chiller/heater is
required during its operation. All abnormalities should be removed, when their potential risk
occurs.
6.4.1 Cooling Mode
6.4.1.1 Observation of chilled/hot water outlet temperature
The chilled/hot water outlet temperature should be checked constantly. The cause should be fund,
if the chilled/hot water outlet temperature rises, and it is not the influence of ambient conditions.
The causes for poor performance of chiller/heater, such as the poor air tightness, the presence of
non-condensable gases, contaminated refrigerant water, crystallization of solution, less surfactant
additive (ethanol), scale formation on tubes, crack on the separator plates in the water boxes and
so on, should be closely analyzed.
6.4.1.2 Observation of cooling water
The cooling water outlet temperature from the chiller/heater should be measured, and controlled in
the limits of 36-38 by means of starting or stop the fan for cooing tower, adjusting the bypass
water valve or water flow.
Cooling water should be carefully be controlled for its pressure and temperature difference in the
inlet and outlet during operation. Analyze the cause, if they changed greatly. It may be the scale
formed on tubes or clogged tubes, if the other parameters are not changed significantly.
6.4.1.3 Observation of de-crystallization pipe
The de-crystallization pipe should be touched by the operational personnel to test is it hot. In
normal conditions, the piping end, which close to the absorber, can be touched by hand for a long
time period. The cause would be checked, if this end can be touched, but not for long time. This
cause should be removed, if this is the mark of potential crystallization. De-crystallizing measures
should be taken, if it is very hot, and there is potential crystallization on the strong solution side.
6.4.1.4 Inspection of vacuum condition of chiller/heater
The conditions should be analyzed, if the vacuum pump evacuates non-condensable gas constantly.
If the cause cannot be determined, then the air tightness of chiller/heater should be checked. The
heat transfer tube may be burst, or abnormal leakage occurs, if the pressure inside chiller/heater is
increased considerably. In this case the chiller/heater should be stopped immediately, and
chilled/hot water and cooling water system should be checked, and the chilled/hot and cooling
water system to be isolated from the chiller/heater, and the air tightness should be checked.
6.4.1.5 Inspection of firing
44
Check the burner for normal combustion, flue gas and percentage of fuel to air; the start and stop
of burner in accordance with the program and without abnormal noise; stop the operation and
check the fuel system and burner immediately, if abnormality occurs (smoke and flame with
abnormal noise.). Check constantly the safeguard device for its normal working, the spark
clearance for ignition electrodes, the nozzles for absence of clogging, and no shock and explosion
during ignition. Clean constantly the receiving surface of flame detector and the insulation cable
between the detector and monitoring relay. Check regularly the gas stop valve for its tightness.
6.4.1.6 Inspection of noise and amperage of running hermetically sealed pumps
Contact with Shuangliang Service company to analyze the cause, if abnormal noise and amperage
is fund.
6.4.1.7 Adjusting the deviation of displayed values
Check if there is deviation in the displayed value with the actual value, and reset, if the deviation
occurs.
6.4.1.8 Other observations
1. Checking vacuum pump for absence of emulsification and dirty.
2. Checking the water pumps for absence of vibration and motors for overheating.
3. Checking the refrigerant water density in the first two weeks of cooling operation in a year.
4. Confirmation of the normal operation of safety devices at least once a year, and repair them, if
something happened with them.
6.4.2 Heating Mode
6.4.2.1 Observation of hot water outlet temperature
The hot water outlet temperature should be checked constantly. The cause should be fund, if the
hot water outlet temperature rises, and it is not the influence of ambient conditions. The causes for
poor performance of chiller/heater, such as scale formation on tubes, crack on the separator plates
in the water boxes and so on, should be closely analyzed.
6.4.2.2 Inspection of vacuum condition of chiller/heater
The chiller/heater should be purged before its put into operation, and the vacuum is checked
before operation of chiller/heater. The conditions should be analyzed, if the vacuum pump
evacuates non-condensable gas constantly. The heat transfer tube may be burst, or abnormal
leakage occurs, if the pressure inside chiller/heater is increased considerably. In this case the
chiller/heater should be stopped immediately, and the air tightness should be checked.
6.4.2.3 Inspection of firing
Check the burner for normal combustion, flue gas and percentage of fuel to air; the start and stop
of burner in accordance with the program and without abnormal noise; stop the operation and
check the fuel system and burner immediately, if abnormality occurs (smoke and flame with
abnormal noise.). Check constantly the safeguard device for its normal working, the spark
clearance for ignition electrodes, the nozzles for absence of clogging, and no shock and explosion
during ignition. Clean constantly the receiving surface of flame detector and the insulation cable
between the detector and monitoring relay. Check regularly the gas stop valve for its tightness.
6.4.2.4 Inspection of noise and amperage of running hermetically sealed pumps
Contact with Shuangliang Service company to analyze the cause, if abnormal noise and amperage
is fund.
6.4.2.5Adjusting the deviation of displayed values
45
Check if there is deviation in the displayed value with the actual value, and reset, if the deviation
occurs.
6.4.2.6 Other Checks
1. Check vacuum pump for absence of emulsification and dirty
2. Check water pumps for absence of vibration and motors for overheating
6.5 Purge Operation
Vacuum is vital for normal operation of chiller/heater. The vacuum (the quantity of
non-condensable gas) of chiller/heater determines the operation performance and the life cycle of
chiller/heater. The purge units are provided to improve the vacuum keeping capacity of
chiller/heater. As shown in Fig.6-1, purge unit is operated automatically and manually. Purge is
carried out with the sampling purge valves and pressure measuring valve is closed, and other
valves operated in the following manner.
1- Purge valve for condenser
2- Purge valve for evaporator
3- Purge valve for absorber
4- Auto-purging unit
5- Upper purge valve of vacuum pump
6- Pressure measuring valve
7- Lower purge valve of vacuum pump
8- Sampling purge valve
9- Vacuum pump
10- Auto-purging discharge pipe
11- Gas box connection pipe
12- Pressure sensor 13- Gas box
14- Oil trap
15- Oil drain plug
16- Cooler water inlet valve
Fig. 6-1 Purging System
6.5.1 The purge of new chiller/heater or chiller/heater after service and maintenance
The new chiller/heater or chiller/heater just after maintenance, which has the internal pressure
higher than the atmospheric pressure, should be vented to the atmosphere through pressure
sampling valve until the internal pressure is equal to atmospheric. The chiller/heater can be vented
to atmosphere through other valves, if there is no LiBr solution and water in it.
The first starting-up of new or maintained chiller/heater is carried out with evacuation of
non-condensable gases by vacuum pump. (1) Confirm that the pressure measuring valve,
refrigerant sampling valve, solution charge valve and sampling valve for strong solution, which
are vented to atmosphere, are closed. (2) Measure the limiting capacity of vacuum pump. (3)
When the requirements are met, close sampling purge valve, open fully the purge valves of
condenser and upper purge valve of vacuum pump, open slowly the lower purge valve of vacuum
pump, and start vacuum pump to evacuate the chiller/heater. Open fully the lower purge valve,
when the vacuum is created in the chiller/heater. (4) Close purge valves of condenser, upper purge
valve of vacuum pump and lower purge valve of vacuum pump, and stop the operation of vacuum
pump, when the vacuum in the chiller/heater is lower than 100Pa, and no solution is left in the
chiller/heater. (5) If the chiller/heater is left with solution, a rubber or plastic hose shall be
connected with the discharge opening of vacuum pump at one end, and inserted into the vacuum
46
oil in a vessel at the another end. Then close the ballast valve of pump, and count the number of
bubbles per minute from the oil. Close purge valves of condenser and upper purge valve of
vacuum pump, lower purge valve of vacuum pump and stop the operation of vacuum pump, if the
number of bubbles in a minute is equal or less than 7. (6) During evacuation of non-condensable
gases from chiller/heater under its cooling mode, the purge valve of condenser shall be closed,
when condensation temperature is lowered to less 1C than that of cooling water outlet
temperature from condenser. Close the upper and lower purge valves of vacuum pump, and
shutdown the vacuum pump, when weak solution inlet temperature to LT heat exchanger is 1C
higher than that of cooling water outlet temperature from absorber.
Evacuate the chiller/heater in the same manner, when the chiller/heater is purged not for the first
time, and the vacuum is not as fair as normal.
6.5.2 The purge of chiller/heater during normal operation
During the operation of chiller/heater, usually the automatic purge unit is operating.
Non-condensable gases will be purged and stored in the gas cylinder (The purge valve for
absorber is normally closed). Open the purge valve for condenser, when condensation temperature
defers from the cooling water outlet temperature from condenser more than 1.5-2 C, and close
that valve, if the temperature difference is 1C only.
47
In cooling mode, cooler water inlet valve shall be always open and evaporator purge valve shall be
always closed.
In heating mode, during normal operation auto-purging system will function to purge
non-condensable gas and cooler water inlet valve and other valves in purging system except
evaporator purge valve shall keep always open. When pressure inside gas cylinder reaches set
valve (saturated pressure at hot water outlet temp. +2.666KPa (20mmHg)) of auto-purging system
in heating mode, control system will show a graph to remind operator to start vacuum pump for
gas evacuation and close cooler water inlet valve. After 15min start vacuum pump. Operation
procedure as follows: start vacuum pump and 1min later slowly open vacuum pump lower purge
valve and 5min later close vacuum pump lower purge valve and shut down vacuum pump.
Afterward, open cooler water inlet valve and continue to use auto-purging unit.
When draining water from chilled/hot and cooling water system via methods described in clause
8.2, traps equipped on inlet/outlet of solution cooler should be open to drain water from solution
cooler and its water inlet/outlet piping.
When purging operation in heating mode, cooler water inlet valve must be closed
before start of vacuum pump to prevent solution being evacuated outside.
1. During purge operation, the lower and upper purge valves of vacuum pump shall be
opened slowly to protect the vacuum pump from spraying of oil or other failure due to
high evacuation rate.
2. During purge operation the ballast valve for vacuum pump should be opened, to avoid
the emulsification of oil. Emulsified white oil for vacuum pump should be changed.
3. The oil trap shall be thoroughly drained in predetermined period
6.6 Management of Refrigerant Water
During operation of chiller/heater the LiBr solution droplets from HP generator or LP generator
may be carried into the refrigerant water into the condenser or evaporator by the refrigerant vapor.
The refrigerant is contaminated, if it contains LiBr. The chiller/heater performance will be
degraded with the contamination of refrigerant water, and even had to be shutdown, when a lot of
LiBr is carried into the refrigerant. So the refrigerant density should be measured periodically
during operation of chiller/heater. Refrigerant needs to be regenerated, when it contaminated.
48
1)
2)
3)
4)
5)
Sampling and density measuring of refrigerant is preferred to use the sampler and
cylinder, which is not used for solution. Or the sampler and cylinder had to be washed by
clean water and no drop of water is left, when the same sampler and cylinder is used for both
refrigerant and solution. Sampled refrigerant water should be placed separately.
6.6.2 Regeneration of refrigerant water
The regeneration of refrigerant is carried out, when the chiller/heater is operating.
The refrigerant is to be regenerated, while it is contaminated to density of 1.04g/ml. In this case,
the chiller/heater is operated with part opening of bypass valve, i.e. the chiller/heater is working
for refrigeration and regeneration of refrigerant water at the same time. The process is repeated to
the normal density (1.002g/ml) of refrigerant water.
6.7 Management of Lithium Bromide Solution
Lithium bromide solution is corrosive to the construction material of absorption chiller/heater. For
protection of chiller/heater from corrosion, the solution should be added with inhibitor, and
controlled in the limits of 9-10.5 for its pH value. Contamination of solution with products of
corrosion will cause clogging of holes in distributor of absorber, and the lubricating and cooling
piping for the pumps, which will bring influence to the operation performance and life cycle of
absorption chiller/heater. So the solution should be sampled and measured periodically during the
49
operation of chiller/heater, and measures should be taken to treat the solution in accordance with
the results of measures. The weak solution is sampled normally, and strong solution is sampled
only when its concentration is measured.
6.7.1 Sampling of LiBr solution
Sampling of solution is carried out for weak and strong ones in the similar way as for the
refrigerant water. The solution sample is taken from the charging valve at the discharge side of
solution pump and the sampling valve at the solution distribution box located at the bottom of
shell of chiller/heater.
The weak solution sample is taken with the sealing plug removed from the charging valve, and the
Rubber hose connection, which is delivered with the chiller/heater, shall be installed. The
connection shall be removed, when the solution sample had been taken. Then the sealing plug
shall be installed to ensure the secondary sealing of valve.
6.7.2 Inspection of LiBr solution
6.7.2.1 Inspection of concentration of solution
Pour the solution in the 250mL cylinder. Measure the concentration of solution by Baume
hydrometer. The concentration of solution can be determined by the graph with the measured
temperature and specific gravity, measured thermometer and hydrometer respectively. Contact
with Shuangliang Co., if solution concentration is considerably different in comparison with the
primary measured value.
6.7.2.2 Visual inspection
The solution quality i.e. the foreign matter and consumption of inhibitor, can also be determined
visually by the color of solution. The visual inspection will be carried out after sampling by
several hours. The inspection results should be compared with the Table 6-1. The final results shall
be given by Shuangliang Service Co.
Table 6-1 Visual control
Item
Condition
Result
Color
Light yellow
A lot of inhibitor is consumed.
Colorless
Inhibitor consumed considerably.
Black
A lot of ferric oxide is in the solution, and
inhibitor consumed.
Green
The corrosion product copper oxide is in
the solution
Floating matter
Very few
No problem
Rust scale
A lot of ferric oxide
Precipitate matter
Considerable
A lot of ferric oxide
6.7.3 pH value
In order to control the corrosion in the chiller/heater, the pH value should be controlled in the
limits of 9-10.5. The solution with pH value not in these limits should be adjusted. The solution is
shipped from factory with the pH value in the above limits. With the operation of chiller/heater,
the pH value will be increased. The pH value of solution should be checked periodically by
universal pH value test paper, and the results should be recorded. If the pH value is too high,
hydrobromic acid (HBr) may be added; if it is too low, lithium hydroxide (LiOH) may be added.
The hydrobromic acid and lithium hydroxide shall be suitably diluted prior to their additions to the
chiller/heater, and with appropriate rate. They can be added in such a way: take a part of solution
and pour it in a vessel, then add the lithium hydroxide or hydrobromic acid, which is diluted with
50
The adjustment of pH value and addition of this matter is rather complex, and is
preferred under the instruction of qualified engineer from Shuangliang Service Co.
6.7.4 Inhibitor
In order to control the corrosion of LiBr solution to the chiller/heater, the solution is added with
inhibitor in the predetermined concentration of (0.100.02%) for lithium chromate and of
(0.010~0.018%) for lithium molybdate. In the process of operation, especially in the beginning
period, the inhibitor is consumed rather rapidly. The Content of inhibitor in the solution should be
checked periodically by the special laboratory. The inhibitor content should be kept in the set
limits, when its content is out the limits.
Direct addition of inhibitor in the chiller/heater is forbidden. It is added by taking a part of
solution (10 times of inhibitor) from the chiller/heater, mixed with the inhibitor slowly to even
distribution, and then the mixture is added to the chiller/heater. After the inhibitor is added, the
chiller/heater should be operated to make its even distribution in the solution.
The addition of inhibiter is rather complex, and is preferred under the instruction of
qualified engineer from Shuangliang Service Co.
6.7.5 Ethanol
Ethanol is used to improve the chiller/heater performance. The content of ethanol in the solution is
0.1-0.3%. Ethanol should be added, when the content in the solution is lower than this value. The
inadequate ethanol can be determined by two ways: the one is the chiller/heater performance is
deteriorated; the second is absence of irritant odor from the solution, or no irritant odor from the
vacuum pump discharge.
Ethanol is added in the similar way as for solution through the charging valve or sampling valve
under negative pressure.
6.7.6 Regeneration of LiBr solution
The LiBr solution should be regenerated, when the content of solution is changed from the normal
value. The regeneration of solution should be done with the assistance of Shuangliang Co. During
regeneration of solution the chiller/heater is charged by nitrogen to positive pressure to discharge
the solution from the chiller/heater. The solution is treated by sediment or filtering outside the
chiller/heater, or filtered in the chiller/heater, while it is in operation.
6.8 Management of Water Quality
6.8.1 Management of cooling water
During operation of chiller/heater, cooling water outlet temperature is preferred be kept in the
limits of 36-38. Cooling water temperature can be regulated by variation of speed of pump
motor, or by changing the opening of valve on the bypass pipe between the water inlet and outlet
of cooling tower.
51
Dirty in cooling water causes not only reduction the performance of chiller/heater by the scaling of
heat transfer tubes, but also shortening the life cycle of tubes by their corrosion. During operation
of chiller/heater, cooling water should be sampled and analyzed. The quality of cooling and
makeup water should meet the requirements of Table 6-2. Water should be treated, if it cannot
meet the requirements.
Table 6-2 Water quality standard
Item
Unit
Makeup water Cooling water
Tendency
Corrosion Scaling
Basic
6.5~8.0
6.5~8.0
pH value(25)
Items
S / cm
<200
<800
electric
conductivity(2
5)
chloric ion Clmg Cl-/L
<50
<200
2
<50
<200
sulfuric
acid mg SO4 /L
radical
ion
SO42
acid
<50
<100
mg CaCO3/L
consumption
rate(pH4.8)
Total hardness mg CaCO3/L
<50
<200
Reference Iron Fe
mg Fe/L
<0.3
<1.0
Items
sulfuric ion S2mg S2-/L
undetectable
undetectable
<0.2
<1.0
ammoniac ion mg NH 4+ /L
NH 4+
<30
<50
silicon dioxide mg SiO2/L
SiO2
Bad cooling water quality not only causes scale formation in heat transfer tubes,
influences heat exchange efficiency and reduces the performance of chiller/heater, but also
corrodes heat transfer tubes and leads to major failure of chiller/heater.
6.8.2 Management of Chilled/Hot Water
Chilled/hot water system can be opened or closed. Soft water is preferred, if closed system is
adopted. For opened chilled/hot water system, it is managed as for the cooling water system.
6.9 Operation of Vacuum Pump
Vacuum pump is vital equipment to keep the chiller/heater under vacuum condition. It is important
to ensure the reliability of vacuum pump. The vacuum pump should be maintained in the
following manner. For more information, see Operation manual of vacuum pump.
1. Before the primary startup of vacuum pump, it should be started for very short period to
determine whether the direction of rotation of pump meets the indicated direction. This can be
determined also by the gas, discharged from the pump outlet. The checking of pump rotation
can be done after the vacuum pump oil is charged.
2. Vacuum pump oil is charged or changed while the pump is shutdown to avoid the damage of
pump and splashing of oil.
3. The vacuum pump should be start/stop repeatedly for short time to avoid damage the pump by
52
4.
5.
6.
7.
8.
53
123456-
2
3
4
Upper hood
Press cup
O ring
Valve stem
Valve plug
Valve body
5
6
1
2
3
4
1- Upper hood
2- Press cup
3- O ring
4- Valve stem
5- Valve plug
6- Valve body
5
6
1. For the purging, charging, refrigerant probe, concentrated solution probe and
pressure measuring valves, which led to the atmosphere, block is inserted into the
valve. Operate these valves after taking out the block, and insert the block on the
Loctite after operation.
2. For probing the weak solution through the charging valve, after the block had been
taken away, the valve outlet should be connected with intermediate part supplied
with the chiller, and then operate. After the probe had been taken, remove the
intermediate part, and install the block on the Loctite.
3. Method of Changing The Sealing Ring or Valve Plug
1) Remove the upper hood.
2) Turn clockwise the press-cup to remove it. (Loosen the fitting screw, if it is provided.)
54
3) Take out the valve stem from the valve body, and change the O-ring or under part of stem (with
valve plug).
4) Install the valve stem into the valve body with the O-rings covered with vacuum grease.
5) Tighten the press-cup anti-clockwise, and turn the valve stem by torque wrench to adjust the
valve by closing and opening it.
6) Install the press-cup on place with the Loctite at the threads, and tighten the hood.
4. Troubleshooting
No
Trouble
Cause
Measure
The valve stem Seizing of upper driving thread Remove press-cup, take out
cannot be turned.
of valve stem
valve stem, repair the driving
1
thread. Change the valve stem, if
the thread cannot be repaired.
Scratch at the surface of valve Change the under part of valve
plug
stem (with the valve plug).
2
Leaking of sealing
Damage at the hole surface of Change the valve.
scratch at the sealing surface.
3
Leaking of O-ring
Damage or aging of O-ring
Change O-ring.
6.10.2.2 The Operation of Torque Wrench
The FDN 100 type torque wrench is used with overall length of 380mm, torque limits of
20-100Nm, torque tolerance of 4%. The overall view of torque wrench is shown on the Fig.6-4.
55
Chapter 7 TROUBLESHOOTING
7.1 Shutdown of Chiller/heater due to Troubles
During operation of chiller/heater, control system will check the running conditions of different
parts of chiller to judge if chiller is running in normal conditions. The control system will
automatically solve the 3 type troubles shown below. For troubleshooting process, see Fig.4-4.
1) If any abnormal phenomena below occurs, chiller will be unloaded firstly. If chiller system still
does not turn well after 10-minute unloading, control system will alarm immediately and
automatic shut down chiller after turning into dilution operation.
(1) Failure of cooling water;
(2) High HP generator pressure;
(3) Low cooling water temperature;
(4) High de-crystallization pipe temperature;
(5) High flue gas temperature;
(6) High HP generator solution temperature
2) When overflow of refrigerant water pump occurs, chiller will alarm immediately and shut down
after turning into dilution operation. When overflow of vacuum pump occurs, chiller will alarm
immediately. When cylinder gas pressure reaches set valve, a graph will appear automatically on
the graph of operation monitoring on the touch screen showing High pressure in chiller
auto-purging unit, please start vacuum pump. The operator may start purge according to methods
introduced in 6.5 Purge Operation.
3) When any following severe trouble occurs, chiller will alarm instantly and shut down
emergently.
(1) Failure of chilled water
(2) Trouble in inverter;
(3) Low chilled water temperature
(4) Low refrigerant water temperature;
During automatic shutdown of chiller/heater, the operator should press key TROUBLE
MONITORING on the graph of operation monitoring on the touch screen to make the alarm
silent and search for the cause of trouble and its shooting. Operator should remove the cause of
trouble immediately after the trouble occurs, and then start again the chiller/heater.
7.2 Common Troubles and Their Shooting
7.2.1 Troubleshooting for Electrical System
Table 7-1 Troubleshooting for Electrical System
No
Trouble
Measure
1
No power supply for 1. Check the availability of power to the chiller.
control system
2. Check the air breaker of the control panel to the power at its
input and output sides.
3. Check the single-pole switch of control loop for the control
panel to the power at its input and output sides.
4. Check the power supply of control elements and apparatus in
accordance with the electrical principal circuit.
56
Trouble of
elements
apparatus
Trouble
screen
Trouble
of
PLC
(ERROR light up)
Trouble of external
measuring elements
Trouble of external
actuating elements
of
control
and
touch
Poor vacuum
1) Leakage in chiller/heater.
2) Poor performance of vacuum
pump and trouble in purge
system
1) Poor vacuum
2) High cooling water inlet
temperature.
3) Less cooling water flow.
4) Scale or clogging of heat
transfer tubes by foreign
matter
5) Inadequate fuel combustion.
6) Heating solution valve and
heating vapor valve closed not
completely.
7) Refrigerant
water
contaminated.
8) Too much or too less sprayed
refrigerant water.
57
Troubleshooting
1) Check main power supply
and air breaker
2) Put the control switch and
main air breaker ON.
1) Leak test and remove the
leakage.
2) Check the vacuum pump for
performance, and remove the
trouble in the purge system.
1) See No.2
2) Regulate cooling water bypass
valve, check the controller for
cooling
water
inlet
temperature, check cooling
tower and its fan.
3) Check the valve opening and
filter cleanness in the cooling
water system, check the
cooling water pump.
4) Clean heat transfer tubes.
5) Check
fuel
combustion
system, and increase heat
supply.
6) Check these valves.
No
Trouble
Cause
9) Too much refrigerant water.
10) Inadequate
Ethanol
in
solution.
11) Less charge of solution.
12) Less circulating rate of
solution.
13) Low chilled/hot water outlet
temperature.
14) Less cooling load for user.
Chilled/hot
water
temperature difference is
less than nominal value.
Contaminated refrigerant
water
(for cooling mode)
Troubleshooting
7) Sampling refrigerant water,
and regenerate it, if density is
greater than 1.04.
8) Close refrigerant bypass valve,
reduce or increase the opening
of spray valve.
9) Drain refrigerant water.
10) Add ethanol.
11) Add appropriate amount of
solution.
12) Regulate weal solution
regulating valve to meet the
requirements.
13) Cooling capacity will be
reduced with the reduction of
chilled
water
outlet
temperature. Set the nominal
chilled
water
outlet
temperature.
14) It is normal for automatic
control of cooling capacity.
1) Increase fuel combustion.
2) Clean tubes.
3) Normal for automatic control
of chiller/heater.
4) Increase hot water flow.
1) See No.3 or No4.
2) Reduce the flow accordingly.
Correct the display deviation.
1)
2)
3)
4)
5)
6)
Crystallization
startup
during
1)
load
No
Trouble
Crystallization
shutdown
Crystallization
operation
10
Cause
chiller/heater.
2) Too low cooling water inlet
temperature.
3) Overloaded.
during
Inadequate dilution
during
1) Non-condensable gas in
chiller/heater.
2) Too less solution circulation
rate.
3) Too big heat supply.
1) Failure of power supply or
loss of phase line.
2) Safety protection system
works.
a. Abnormal inverter.
b. Failure of chilled water
c. Other troubles
11
12
13
Abnormal
burner
14
15
Black smoke
flame
from
Troubleshooting
2) Regulate
cooling
water
bypass valve to increase
temperature. Check controller
of cooling water inlet
temperature.
3) Increase load slowly for
startup.
Check the set value for dilution
and actual situation.
1) Purge
chiller/heater
by
vacuum pump.
2) Regulate
weak
solution
regulating valve.
3) Reduce heat supply.
1) Check power supply to
restore it.
2) Remove the cause of
troubles, and restore the
normal operation:
a. Check and repair inverter and
solution pump. See No. 25
b. See No. 19
c.
Press
TOUBLE
MONITORING
button
on
operation monitoring graph on
chiller touch screen to know
trouble reasons and ways of
troubleshooting.
1) Open the fuel supply valve.
2) Check fuel supply and
pressure regulating valves.
3) Check and regulate.
4) Open more the flap.
5) See the technical manual of
burner.
1)Adjust
the
combustion
carefully by increasing the
opening of air flap and see the
technical manual of burner.
No
Trouble
Cause
3) Not the correct nozzle had
been chosen.
4) The type of fuel is not correct.
16
High
HP
generator
temperature and pressure.
17
Cavitation
pump
18
Cavitation of refrigerant
pump
19
of
solution
20
21
Abnormal increase of
pressure
in
the
chiller/heater, pressure in
the auto purge unit equal
or above the atmospheric
pressure
22
23
1) Poor grounding.
2) Poor sensors for temperature
and etc.
3) Troubles in touch screen.
1) Pump
motor
overload
protected.
60
Troubleshooting
2)Contact Shuangliang Service
Company to readjust the
combustion.
3)Chose the other ones, or
contact Shuangliang Service
company.
4)Change the sort of fuel after
examination.
5)It is required to stabilize the
gas supply pressure and heat
value.
1) Purge the chiller/heater by
vacuum pump and remove
the leakage.
2) Regulate heat input.
3) Regulate cooling water
bypass valve, check cooling
tower and fan, or regulate
cooling water flow.
4) Clean heat transfer tubes.
5) Regulate weak solution
regulating valve.
1) Charge solution.
2) De-crystallization.
3) Regulate solution circulation
rate.
1) Add refrigerant water.
2) Regulate
cooling
water
temperature or add refrigerant
water.
1) Repair or startup standby
pump.
2) Add a big amount of water.
1) Same as for failure of
chilled/hot water.
2) Addition of water storing
capacity (for water collecting
type cooling tower)
Urgent measures should be taken:
1) Cut the power to shutdown
the chiller/heater.
2) Close valve and stop the
chilled and cooling water
pumps.
3) Drain the chiller/heater.
4) Transfer
solution
from
chiller/heater to tank; open the
end covers to test the air
tightness.
1) Re-grounding.
2) Repair or replace.
3) Replace.
1) Find the cause of overload
and reset.
No
Trouble
24
25
26
27
Cause
2) Troubles in the control
circuit.
3) Trouble in pump itself.
4) Automatic protection of
chiller/heater works.
1) Trouble in control circuit of
inverter.
2) Erroneous setting of function
code for inverter.
3) Low voltage of power supply.
4) Trouble in inverter.
5) Over
current
protected
inverter.
1) Buzzer damaged.
2) Fuse blown.
1) The automatic protecting
system is working due to
abnormal
operation
of
systems.
2) The auto capacity regulation
is working.
3) Trouble in burner.
Leakage
Troubleshooting
2) Check the circuit.
3) Replace.
4) Find the cause.
firing of burner.
2) Stop the supply of cooling water to raise the temperature of weak solution to about 60, but
not above 70.Shut the chilled/hot water, when its outlet temperature is higher than inlet
temperature.
3) Open the refrigerant bypass valve slowly to bypass part of refrigerant to absorber to dilute the
solution and not lower the solution level in the absorber considerably. The solution will
de-crystallize, if the chiller/heater is operated under such conditions continuously.
4) Heat the crystallized parts by steam or condensate, if they are difficult to be de-crystallized.
5) Put the chiller/heater into operation, when it is de-crystallized. The purge piping is also to be
de-crystallized, if it had been crystallized also.
6) Find the cause of crystallization, and appropriate measures are taken.
The chiller/heater is normal, if the de-crystallization pipe is not hot even under the full load of
chiller/heater.
7.3.3 Crystallization during Shutdown
During shutdown the solution is crystallized, if it is not adequately diluted during shutdown, or the
cooling water temperature is low. The solution pump cannot work for solution crystallization. It
can be de-crystallized by heating the pump casing and its inlet and outlet by steam to run the pump.
The caution should be taken to avoid the steam and its condensate into the motor and its control
means. No direct heating of motor is permitted.
7.4 Freezing of Refrigerant Water
Refrigerant water is frozen by low chilled/hot water outlet temperature or small flow, or failures in
the safety protection means. So, the safety protection should be inspected and calibrated
periodically, or the chilled/hot water system should be checked and cleaned.
For de-freezing the refrigerant water, the cooling tower fan should be stopped, the cooling water
flow should be reduced, and the chiller/heater is put into operation in the normal manner. If the
refrigerant water still is frozen, then close the burner, solution pump.
7.5 Treatment of Emergency
7.5.1 Fire and earthquake
Cut the power supply, close all the valves, and fire protection measures should be taken.
7.5.2 Water flooding
Remove the control panel and vacuum pump, and handle them to safe place. All the hermetically
sealed pumps, sensors and electric wires should be covered by plastic films to be protected from
water leakage.
7.5.3 Freezing or cracking of heat transfer tubes (abnormal rising of pressure and liquid
level in the chiller/heater)
Stop chiller/heater operation (stop immediately the burner, refrigerant and solution pumps), stop
the chilled/hot water and cooling water pumps after shutoff their valves, and transfer the solution
from chiller/heater to the tank. Drain water from the chiller/heater, check the chiller/heater for air
tightness and change the broken tubes by opening the end covers.
7.5.4 Failure of Power Supply
When the power supply is failed, close the valves at the discharge of cooling and chilled/hot water
pumps and stop the pumps. If before the power failed, the sampling or purge process is taken place,
62
then the sampling valve and lower and upper purge valves should be closed.
7.5.4.1 Treatment for Short Period (less Than 1h) Failure of Power Supply
In general the solution will not tend to be crystallized, if the power supplied is failed only for
limited time, and solution remains hot. In such case, the chiller/heater can be put into operation, as
the power supply recovered.
1) If the chilled and cooling water pumps had been shut as the power failed, then these pumps are
to be started by confirming that the valves at their discharge had been closed. Then these valves
opened and adjusted to the flow required.
2) Control the chiller/heater manually, start the solution pump and refrigerant pumps, and stop the
chiller/heater with dilution operation.
3) Control the chiller/heater automatically, start it in the normal procedure.
4) Check the refrigerant water for its density; regenerate it, if its value is above 1.04g/ml.
7.5.4.2 Treatment for Long Period (more than 1h) Failure of Power Supply
The crystallization of solution tends to occur, if the chiller/heater is shutdown for long period
under high solution concentration. Operate the chiller/heater in the following ways, when the
power recovered:
1) Start the chiller/heater manually for operation with dilution as above mentioned for short
shutdown.
2) Operate the chiller/heater under light load for 30 min in trial manner. Stop the chiller/heater for
de-crystallization, if the cavitation for solution pump occurs in 30 min. If no crystallization
occurs, then stop the chiller/heater, and re-start the chiller/heater in automatic mode.
3) Check the refrigerant water for its density after de-crystallization; regenerate it, if its value is
above 1.04g/ml.
7.6 Troubles of Burners
7.6.1 Common Troubles of Oil Burners and Their Shooting
The common troubles of oil burner and their shooting measures are listed in the Table 7-3, For
adjusting, see technical manual of burner.
Table 7-3 Common Troubles of Oil Burner and Their Shooting Measures
No.
Trouble
Cause
Measure
1
No spark from 1) Gap
between
the 1) Adjust the gap between the
ignition
electrodes is not correct.
electrodes.
electrodes
2) Electrodes contaminated 2) Clean and adjust the electrodes.
or wet.
3) Replace.
3) Insulation cracked.
4) Find the cause, repair or replace.
4) Ignition
cables
are 5) Replace.
carbonated.
5) Ignition
transformer
damaged.
2
Burner
motor 1) Overload protection.
1) Check the set value, and find the
cannot
be 2) Trouble in contactor.
cause for overload, if no problem
started.
3) Trouble in thermal relay.
for set value.
4) Trouble in burner motor.
2) Replace.
5) No
output
from 3) Replace.
programmable controller.
4) Replace.
6) Motor bearings failed.
5) Check the cause for absence of
output from controller.
6) Replace bearing or motor.
3
No oil supply 1) Gear damaged.
1) Replace.
63
No.
Trouble
from oil pump
Mechanical
noise
from
pump.
No
even
atomization of
oil from nozzle.
Abnormal noise
of fan
No
feedback
from
flame
detector.
Abrupt cutout
firing of burner.
Solenoid valve
cannot open.
Solenoid valve
cannot be closed
tightly.
Burner head is
contaminated by
oil
or
carbonization
10
11
12
Oil pre-heater
cannot
work
(for heavy fuel
oil)
2)
3)
4)
5)
1)
2)
Cause
Air in oil piping.
Oil inlet valve closed.
Filter clogged.
No oil for oil pump.
Air in pump.
Filter clogged.
64
2)
3)
4)
5)
1)
2)
Measure
Tighten the connections.
Open the oil inlet valve.
Clean the filter.
Charge oil.
Vent the pump.
Clean filter.
1. Clean the fan motor, ignition electrodes, flame detector and air inlet in accordance with
the requirements.
2. Check and repair failed motor bearings to protect the burner from damage.
3. Check immediately, if the fan motor noisy.
4. Clean the oil filter timely to protect the burner oil pump and solenoid valves from
damage.
7.6.2 Common Troubles of Gas Burners and Their Shooting
Common troubles of gas burner and their shooting are listed in table 7-4.
Table 7-4 Common Troubles of Oil Burner and Their Shooting Measures
No.
Trouble
Cause
Measure
1
Burner fan not work. 1) Power
supply
not 1) Connect power supply.
connected.
2) Fan overload protected. 2) Find the cause of overload, and
correct.
3) Trouble in fan.
3) Replace.
4) Trouble in control 4) Check and repair circuit.
circuit.
5) Gas supply shut or with 5) Restore gas supply.
less pressure.
6) Trouble
in
burner 6) Replace burner controller.
controller.
2
Burner fan started, 1) Air breaker is failed or set 1) Adjust or replace.
but burner is locked
wrong value.
after pre-purge.
2) Foreign matters in the 2) Clean the piping.
pressure piping to the
pressure switch.
3
Burner fan is locked Air supply solenoid valve Correct the leakage.
in about 20 sec after leaks.
starting
4
Burner is started, but 1) Air pressure switch is not 1) Set the correct value for the
locked in 10sec after
working at the working
pressure switch, and replace it,
full load pre-purge.
position.
if damaged.
2) Fan blades were dirty.
2) Clean from dirt.
3) Fan rotation reversed.
Correct rotation.
5
No spark between 1)
Gap
between
the 1) Adjust in accordance with the
electrodes.
electrodes is too big.
burner technical manual.
2)
Ignition electrode or its 2) Replace damaged electrodes
insulation damaged, or
and wires, correct the short
short circuit against
circuit against the ground and
ground,
or
poor
improve the contact.
contact.
3) Replace.
3)
Trouble in ignition 4) Re-adjust.
transformer.
4)
Flame detector not
installed correctly.
6
Fan started, spark 1) Gas supply solenoid valve 1) Replace solenoid valve, and
takes place, but no
cannot be opened due to
connect the control circuit.
ignition.
failed coil or broken
control circuit.
2) Seal the solenoid valve.
65
No.
Trouble
10
11
Flap
regulating
mechanism cannot
rotate.
Cause
2) Protection due to leakage
of solenoid valve.
3) Gas supply filter is
clogged.
4) Air flap is set incorrect.
1) Gas supply filter is
clogged.
2) Trouble in gas pressure
regulator.
3) Trouble
in
gas
instruments or water in
the lowest points of gas
piping.
4) The ratio of gas with air
is not correct.
5) Flame detector is too
dirty.
6) Gas supply pressure is
low.
7) Poor grounding.
High limit pressure switch
protection is working for
increased pressure.
Low limit pressure switch
protection is working for
reduced pressure.
Gas pressure low and air
flow too great.
Gas butterfly valve is
clogged for its blade.
Measure
3) Clean or replace filter.
4) Re-adjust.
1) Clean filter.
2) Check and repair gas pressure
regulator.
3) Contact the local gas company.
4) Re-adjust.
5) Clean the head of flame
detector.
6) Increase the gas supply
pressure.
7) Re-grounding.
Same as above.
Solution
1) Add oil to the level in the limits of
5mm under middle line.
2) Change to correct type vacuum
pump oil.
3) Drain the emulsified oil or water
droplets from the drain plug on the
bottom of oil box, and add oil;
change oil, if it is too dirty.
4) Check for tightness, and remove
leakage.
5) Check and repair vacuum solenoid
valve.
6) Change to new spring.
7) Drain the oil, remove the oil box,
lose the press plate of oil nozzle,
and withdraw the oil nozzle and
clean the oil holes. The
No
Trouble
Cause
Rubber components for
suction pipe and ballast
valve not assembled
correctly, broken or aged.
10) Vacuum system, including
piping,
contaminated
severely.
1) Broken oil drain plug and
gasket.
2) Broken or assembled not
correctly the gasket for oil
box cover.
3) Deformed thermally the
plexiglass.
4) Lost spring for oil seal.
5) Not closed the ballast valve
during shutdown of pump.
6) Oil seal is worn due to error
assembling.
1) Too high oil level.
2) No oil or oil contaminated
in oil separator.
3) Lost or assembled not
correctly the oil trapping
plate.
1) Broken the springs for
revolving
plates,
and
increased oil supply.
2) Worn bearings.
3) Broken parts.
Solution
components are cleaned, not using
gauze as far as possible.
8) Check, repair and replace.
9) Adjust and change.
10) Clean.
1) Replace.
2) Check and repair.
3) Replace.
9)
Oil leakage
Oil spray
Noise
b. Abnormal contact in bearings. Check and replace the bearing, sleeves and thrust plate. Remove
the cause for increased friction.
c. Abnormal contact between the rotor and stator. Check the surface for abnormalities of
expansion deformation. Remove the cause for abnormal wear.
d. Poor contact between the impeller and casing of pump. Check the assembly of pump shaft and
impeller and deflection of shaft. Adjust or replace the shaft, if it is out of normal limits.
e. Foreign matter in the pump casing. Disassemble the pump casing to remove the foreign matter.
f. Reduced motor insulation resistance and unbalance of resistance of coil for three phases.
Restore, or otherwise, replace the stator. Dry the motor slowly by torch, if it is damped.
g. Motor operates under absence of any phase current. Check the fixing of wire connection of
motor. Tighten it, if it is slack.
h. The voltage and frequency of power supply is fluctuating. Check the power supply line.
4) Thermal relay protection is working frequently
a. Pump motor overloaded and overheated. Check the flow and temperature of working medium.
Check and clean filter.
b. Trouble in thermal relay. Check and replace the thermal relay.
5) Pump noisy and vibrated severely
a. Reversed rotation of pump. Change the connection of leads to pump motor to correct rotation
direction.
b. Too great or small pump flow. Check the pump operation to make the operation of pump in the
determined limits.
c. Cavitation in pump. See Table 7-2.
d. Foreign matter in pump. Check and remove foreign matter from pump.
e. Contact of casing with the impeller or inducer. Check and repair.
f. The fixing of bolts is slack. Check and repair pump.
g. Unbalanced rotor of pump. Check and balance pump dynamically.
68
No
Group
4)
Item
wires
on
terminals.
Electric control
and protections
5)
Level sounding
6)
Electric wires
and cables.
Flow switch.
7)
8)
Electric
elements, such
as
sensors,
inverters.
Content
additionally.
4) Check the electric control
and protections for their set
points and actual working,
check for wear of contacts
and malfunction.
5) Clean the elements, if aged.
Replace the corroded.
6) Check and replace, if aged
and corroded.
7) Check switch for its
sensitivity, adjust it to
normal function.
Check, repair or replace based
upon the actual results (for
inverter, see its
technical
manual )
Time
4) Before starting
5) Before starting
6) Before starting
7) Before starting
8) Before starting
1) The solution in the chiller/heater should be diluted fully. Refrigerant water from evaporator
should bypass into the absorber to dilute solution and prevent crystallization, when the ambient
temperature is lower than 20, and chiller/heater is stopped for more than 8h. Operate the
solution pump and stop refrigerant pump, connect the solution charging valve at the discharge
of solution pump and refrigerant sampling valve together and open them, to prevent the
refrigerant pump from freezing-up by forcing the solution into refrigerant pump, when the
ambient temperature is lower than 5.
2) Maintain the vacuum in chiller/heater, operate vacuum pump, if absolute pressure in the
chiller/heater is increased.
3) Check the chiller/heater for air tightness, if absolute pressure in the chiller/heater is increased
too rapidly.
4) Drain the chilled/hot and cooling water systems (including chiller/heater), if the local ambient
temperature will be lower than 0 in the interval of shutdown.
5) It is forbidden to expose the chiller/heater to atmosphere for long time during inspection,
replacing and repairing valves or pumps. The maintenance work should be planed carefully,
and the chiller/heater is evacuated immediately after the work finished.
8.2.2 Maintenance during Long Shutdown
During long time shutdown, all refrigerant should bypass into the absorber, and mixed with
solution fully to prevent chiller/heater from crystallization and heat transfer tubes from freezing up.
In order to protect the refrigerant pump from freezing up during shutdown period, part of solution
should be bypassed into the refrigerant pump in the procedure shown in the above first paragraph
for Maintenance during short shutdown
During the long time shutdown the chiller/heater should be under supervision by special appointed
personnel. The chiller/heater should be checked for air tightness, which is kept for good operation
of chiller/heater.
The solution can be left in the chiller/heater, if it has good air tightness and solution is clear.
Solution is preferred be kept in special tank to be settled, if it is turbid, and the chiller/heater is
rather severe corroded. Solution may be treated outside the chiller/heater, and then recharged into
it.
Clean the chilled/hot and cooling water systems (including the chiller/heater), and dry them during
the long time shutdown in the following manner:
1) From water systems drain water, which flows during the operation of chiller/heater.
2) Clean and blow the internal surface of tubes and pipes from rust and settlings (or by aid
cleaning, if they cannot be removed by usual cleaning).
3) Drain the cleaned tubes and keep them dry (the drainage piping is left opened)
8.3 Inspection of Air Tightness
Attention should be paid to the air tightness during operation and shutdown. Inspect the
chiller/heater for air tightness, if abnormality occurs. Inspection for air tightness is carried out for
chiller/heater under pressure or under vacuum in the procedure shown in the paragraph 5.1.4
Inspection of chiller/heater for air tightness of chapter 5.
8.4 Inspection, Cleaning and Change of Heat Transfer Tubes
8.4.1 Inspection of Heat Transfer Tubes
72
1) Inspection of scale. Open end cover of water box to check, if there is scale and sludge in the
tubes. Scale is analyzed and measures should be taken, if it occurs in the tubes.
2) Inspection of air tightness Chiller/heater is charged with nitrogen up to 0.1-0.12MPa. Tubes are
plugged from one side, and covered by a film of solution from another end. The tube is broken,
if there is bubble at the its end, or if the plug is expanded off, when tubes are plugged from both
sides. The broken tube can be observed also, if bubble comes from the tube, when water funnel
is installed instead of end cover.
8.4.2 Cleaning of Heat Transfer Tubes
Tubes are cleaned once a year based upon the scale and sludge formation inside tubes.
1) Mechanical cleaning. Mechanical cleaning is effective to remove the sludge from the tubes.
Remove the end cover, blow the tubes with nitrogen or oil-less air under pressure of
0.7-0.8MPa. Then the nylon brushes (not metal wire brushes) with rubber heads and air plugs
are inserted into the tubes, moved from one end of tube to another under high water pressure
for 2-3 times, and then dried by high pressure nitrogen or air, or cotton balls. Cleaned tubes are
protected by end covers.
2) Chemical cleaning. Chemical cleaning is used to remove scale, which contains salt with
calcium, magnesium, and other hard salts. Tubes are cleaned by chemical dosage, method and
timed in accordance with the content and thickness of scale formed.
73
Attached Table 1
Operator:
Strong Solution %
Intermediate Temp. %
Weak Solution %
Outlet Temp.
Inlet Temp.
Outlet Temp.
Inlet Temp.
Outlet Temp.
Inlet Temp.
Outlet Temp.
Note
Outlet temperature of Absorber: The front is the side near to purging unit. Another side is the rear
Inlet Temp.
12
11
kW
10
Heat Load
Outlet Temp.
Condensation Temp.
Total Load kw
Flow Rate m3/h
Rear
Front
Total Inlet Temp.
kW
Weak
Solution
Weak Intermediate
Solution
Solution
Strong
Solution
Fuel
Outlet
Temp.
Time
No.
Concentration
HT Heat Exchanger
LT Heat Exchanger
HPG
LPG
Condensor
Absorber
Evaporator
Time:
Model: