Set Communications Port: - Inv600 - Setcomm

This function block sets the communication parameters of a serial port on an OMRON PLC to match the default settings of an OMRON 3G3MV inverter. It initializes the port's mode, data format, stop bits, parity, baud rate, and delay to communicate with the inverter over MODBUS. The block restarts the communication unit for the new settings to take effect.

Uploaded by

Joseph
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
136 views2 pages

Set Communications Port: - Inv600 - Setcomm

This function block sets the communication parameters of a serial port on an OMRON PLC to match the default settings of an OMRON 3G3MV inverter. It initializes the port's mode, data format, stop bits, parity, baud rate, and delay to communicate with the inverter over MODBUS. The block restarts the communication unit for the new settings to take effect.

Uploaded by

Joseph
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

_INV600_SetComm (1/2)

INV
600

Set Communications Port: _INV600_SetComm

Basic
function
Symbol

Sets the communications settings of the serial port on the PLC to the same default settings as those of the
3G3MV.
Start trigger

_INV600_SetComm
Unit selection
Serial port No.

File name
Applicable
models

Conditions
for usage

(BOOL)
EN
(INT)
UnitSelect
(INT)
PortNo

(BOOL)
ENO

Lib\FBL\omronlib\Inverter\INVRT\Serial\_INV600_SetComm11.cxf
Inverters
3G3MV Series, 3G3RV Series
CIMR-V7AZ, CIMR-F7Z, CIMR-E7Z, CIMR-L7Z, CIMR-G7 (Sold by OYMC)
CPU Unit
CS1*-CPU**H Unit version 3.0 or higher
CJ1*-CPU**H Unit version 3.0 or higher
CJ1M-CPU** Unit version 3.0 or higher
CP1H
CP1L (except 10 points CPU)
Serial
CS1W-SCU21-V1, CJ1W-SCU21-V1, CJ1W-SCU41-V1 Unit Version 1.2 or higher
Communications
CS1W-SCB21-V1 and CS1W-SCB41-V1 Unit Version 1.2 or higher
Units/Boards
CP Series CPU serial port
CX-Programmer
Version 5.0 or higher
The inverter is to be connected to the Serial Communications Unit (SCU), Serial Communication Board (SCB),
or a serial port on the CP Series CPU unit.
This FB initialize parameters for serial ports to work with 3G3MV series inverter which have communication
parameters set to factory setting.
If other setting for more performance is needed, use FB
_SCX604SetPortGateway according to Function description below.
Inverter Settings
Slave address(n153/H5-01)= 1 to 31

A unique setting required for all nodes on same MODBUS line.

PLC Parameters
See users manual for RS422/485 wire.
Serial communication unit or board must have serial gateway function to MODBUS line.
Shared Resources
No Special resource to specify
Function
description

FB
precautions
EN input
condition
Restrictions
Input
variables
Output
variables

A EN input would set the specified Serial port for 3G3MV inverter communication parameter on factory setting.
and then restarts Serial Communication unit or board to run with the parameter.
For other communication setting (Non-parity or faster baud-rate=19200) , use _SCX604SetPortGateway.
Communication Parameters
Mode=9:Serial Gateway
3G3MV Factory setting.

Data=8bit

Stop=1bit

Parity (n155/H5-03)=Even (disagree with 3G3RV, CIMR (-F7Z/ -E7Z/ -L7Z/ -G7) Factory setting)

Baud (n154/H5-02)=9600 bit/s

Delay =0 (default)
.
The FB does not check for restart have finished.
An upwardly differentiated signal or a 1 cycle on signal should be used. otherwise, the Serial Communication
unit does not start because of the restart bit stay ON.
When any input variable is out of range, ENO will be turned OFF and the FB will not be executed.
Always use an upwardly differentiated version of input to EN.

_INV600_SetComm (2/2)

Application
example

Initializes the memory area for the Serial Communications Unit (SCU) with the Unit No. 10
Unit No.: 10

&10
CPU

SCU

Serial port No.: 1


Parity
3G3MV, CIMR-V7AZ n155=0(Factory Setting)
3G3RV, CIMR (-F7Z/ -E7Z/ -L7Z/ -G7) H5-03=1(Even)
Speed (Baud Rate)
3G3MV, CIMR-V7AZ n154=2(9600bit/s)
3G3RV, CIMR (-F7Z/ -E7Z/ -L7Z/ -G7) H5-02=3(9600bit/s)

Inverter

Start trigger

_INV600_SetComm
Unit selection
&2
Serial port No.
&1

Related
manuals

(BOOL)
EN
(INT)
UnitSelect
(INT)
PortNo

SYSDRIVE 3G3MV Series Multi-function Compact Inverter Users Manual (I527)


SYSDRIVE 3G3RV Series High-function General-purpose Inverter Users Manual (I532)
CIMR-F7Z Users Manual (YEG-TOE-S616-55.1-OY)
CIMR-E7Z Users Manual (YEG-TOE-S616-56.1-OY)
CIMR-L7Z Users Manual (TOMCC71067600AA-OY)
CIMR-G7 Users Manual (TOE-S616-60.2)

Variable Table
Input Variables
Name
EN

Variable name
EN

Data type
BOOL

Default
FALSE

Range

Unit selection

UnitSelect

INT

&0

&0 to &15,
#BBBB
#CCCC
&1 to &2

Serial port No.

(BOOL)
ENO

PortNo

INT

Description
ON (1): Starts FB
OFF (0): Does not start FB
Specify the connected Unit and serial port.
For CP Series CPU Serial port:
Unit selection
#CCCC
(UnitSelect)
Serial port No.

1: Port 1

(PortNo)

2: Port 2

For SCB:
Unit selection

#BBBB

(UnitSelect)
Serial port No.

1: Port 1

(PortNo)

2: Port 2

For SCU:
Unit selection
(UnitSelect)
Serial port No.

Output Variables
Name
Variable name
ENO
ENO

Data type
BOOL

Revision History
Version
Date
1.00
2005.4.22
1.10
2006.4.28

Range

Unit No. (&0 to &15)


1: Port 1

Description
1 (ON): FB processed normally.
0 (OFF): FB not processed or ended in an error.

Contents
Original production
Support CPU serial port

Note
This document explains the function of the function block.
It does not provide information of restrictions on the use of Units and Components or combination of them. For actual applications,
make sure to read the operation manuals of the applicable products.