NT538
NT538
Introduction...........................................................................................2
Mounting...............................................................................................2
Dimensions ............................................................................................2
Controls .................................................................................................3
Screen Displays ....................................................................................3
Screen Messages ...................................................................................4
Light Test ..............................................................................................5
Control Power .......................................................................................5
Wiring ...................................................................................................5
Inputs.....................................................................................................7
Outputs..................................................................................................7
Programming.........................................................................................8
Technical Specifications .......................................................................11
Testing...................................................................................................12
Warranty................................................................................................12
Troubleshooting ....................................................................................13
Approvals ..............................................................................................14
Options ..................................................................................................14
Ordering ................................................................................................14
Introduction
The NT538 temperature monitor will survey and control up to eight, three-wire
RTD inputs. The RTD sensing range is 40C to 200C. Each input channel may
be user programmed with individual Alarm and Trip set points in a range of 0 to
200C (32 to 392F). Temperatures below 1 to 40C are read only. The unit is
microprocessor based which offers application flexibility, and easy integration to a
variety of applications including electric motors; electric and diesel generators; all
types of transformers; electric cables; and industrial and chemical processes. The
thermal protection provided is covered by ANSI 49.
The unit is intended for semi-flush mounting with hardware provided.
Installation and set-up are simple using the universal power supply 24 to 240V AC
or DC and functional user controls and display.
Mounting
Figure 1
Controls
Screen Displays
All functional controls and displays are located on the front of the unit. The unit
has six input keys, two having dual functions. These are PRG/SET and
ENT/RESET. Keys may be categorized as, programming, screen display, and test.
Programming keys are located at the bottom of the unit and may be identified by
the blue type. These are PRG, ENT, UP (symbol) DOWN (symbol). The screen
display may be changed by the DISPLAY MODE key located to the upper right
and is identified by the yellow type. The TEST key is located on the bottom
between the programming keys. When the test provision is enabled the SET and
RESET keys are activated, with the PRG and ENT keys disabled.
Each active channel has four associated LED's; green, yellow and red. These LED's
provide the channel status information. The LED colors are interpreted as follows:
Green
-The associated channel information is being displayed on screen
-RS Out indicating communications is functioning
Yellow
-The associated channel has exceeded the alarm set point and the alarm output
relay has changed state.
-The fan relay has been energized
Red
-The associated channel has exceeded the trip set point and the trip output relay has
changed state.
-Indication of a fault condition
All messages and operating parameters are displayed on the screen. The DISPLAY
MODE key controls the operating mode of the screen display allowing any one of
four modes to be selected: scan, auto, man, or Tmax. An illuminated LED at the
top left of the display indicates the active mode and pressing the DISPLAY MODE
key toggles the four different modes The different modes display the following
information.
.
Scan
Each channel is scanned for approximately three seconds during which the actual
temperature of that channel is displayed on the screen.
Auto
All active channels are scanned, but only the temperature of the hottest channel is
displayed on the screen. This mode does not affect protection.
Man
The temperature for each channel may be viewed manually by pressing the UP or
DOWN key. The information displayed on the screen will be that of the channel
whose green LED is lit. All active channels are still scanned but only the
temperature of the selected channel is displayed. This mode does not affect
protection.
Tmax
This value is logged in memory and is the maximum historical temperature
recorded on any active input channel. A green LED identifies the channel which
produced this temperature value. If an actual monitored temperature value exceeds
the Tmax value in memory, then the new value is stored as Tmax.. The Tmax value
may be reset by pressing the RESET key in this mode.
NT 538 June 17 04 Temperature Monitor/Controller
Screen Messages
A variety of messages may be displayed on the screen. They may appear during
programming or during normal operation as a result of component or unit failure.
During the course of normal operation the following screen displays indicate fault
conditions:
FOC: Fault open circuit - RTD input to one or more channels has open
circuited. An RTD may be disconnected or wires to it severed. This may also
indicate that the number of active channels programmed does not match the
actual number of RTDs connected or that RTDs have not been consecutively
connected starting with channel 1. Indication is provided by illumination of the
fault LED, operation of the fault output relay and identification of the affected
channel by illumination of that channels green LED.. To reset the fault relay,
push and hold the RESET key until RST appears on the screen.
FCC: Fault short circuit - RTD is short-circuited. The RTD has failed or the
RTD type, and the unit are not compatible. Low resistance across an input
channel causes this problem. Indication is provided by illumination of the fault
LED, operation of the fault relay, and identification of the affected channel by
illumination of that channels green LED. To reset the fault relay, push and hold
the RESET key until RST appears on the screen. If all yellow and red channel
LEDs are simultaneously illuminated with the fault LED, it is likely that the
RTDs are not compatible with the unit..
All other messages that may appear on the screen pertain to program or test
functions. Refer to the programming or test sections for description s of those
messages.
Light Test
Control Power
The NT538 has a universal power supply. It can be supplied with 24 to 240V AC
or DC without respect to polarities.
The ground cable must be fixed to terminal # 41
Wiring
Figure 2
Wiring (Cont.)
Inputs
The NT538 will accept up to eight, three-wire RTD inputs. The standard unit is
calibrated for 100-ohm, platinum RTD's.
The NT538 may also be ordered for use with 100 or 120-ohm, nickel RTD's.
The RTD's must be terminated consecutively starting with channel 1, and the relay
must be programmed for the number of active channels. (maximum eight)
Outputs
The standard version of the NT538 incorporates four output relays; Trip, Alarm
Fault and Fan
All relays are single -pole, double throw except Fan which is SPST
The trip and alarm relays are independently programmable for fail-safe
operation. The relay contacts will change state when the unit is energized,
(control power applied) and no trips or alarms are present
Each individual active channel can be programmed with trip and alarm
temperature setpoints that are independent of other channels.
The alarm and trip relays will change contact state when the respective set
point temperature value is reached. The unit selfresets automatically when the
actual temperature value declines 1C (2F) below the set point values. The
unit will only reset when all actual temperature values have declined below the
programmed values. Illuminated LEDs for alarm (yellow) and trip (red) flash
coincidentally with the channel LED of the same color, when a set- point is
exceeded. The channel indication ceases when the temperature falls below the
set point value.
The Fault relay is activated when the unit senses a defective RTD or
component failure of the relay. This will also occur if temperatures are out of
range. Max 40 to 200C. If the fault relay can not be reset the unit must be
replaced.
Programming
Getting started
Programming the NT538 is simple and requires no special tools. The set point
values for alarm and trip for each active channel should be at hand.
The unit will automatically step through each program sequence and upon
completion will resume normal operation.
The program sequence is as follows;
1) Set the number of active channels, maximum 8.
2) Input alarm temperature value for channel 1, range 0-200C (32-392F).
3) Input trip temperature value for channel 1, range 0-200C (32-392F).
4) Repeat steps 2 and 3 for all active channels.
5) Select fan operation Yes or No
Input fan variables if above is programmed Yes
6) Select N.O. or N.C. for alarm relay
7) Select N.O. or N.C. for trip relay
8) Select FCD operation Yes or No
9) Press ENT to return to normal operating mode
Unit will perform light test and return to normal operation.
Programming Sequence
1) To begin programming, press the PRG key for approximately
five to seven seconds . The screen message will change to PRG and the
PROG light above the PRG key will illuminate. The unit will then advance
to the first program selection, NCH. In the event program access is blocked the
display will show noP. This indicates an internal jumper has been removed
and programming is not possible To gain access, the internal jumper
must be reinstalled. This involves removing the exterior case and locating the
removable jumper situated on the PC board. The jumper is installed from the
factory to allow programming. For jumper location refer to item 20 page 10.
2) After each selection press the PRG key to advance to the next selection. At
any time during the program sequence you may discontinue by pressing the
ENT key. To enter programming again you must repeat the sequence above.
3) To review the entered values, momentarily press the PRG key and continue to
do so advancing to each programmed value.
4) After advancing to any program selection, use the up/down keys to enter your
selection, or set point value.
During the programming sequence a timer allows 60 seconds for any input. If time
elapses and no input is made the unit reverts to normal operation.
As the unit advances to each of the program selections the main LED screen will
display a message or set point value.
When entering set point values for channels 1 to 8, a green LED will illuminate
indicating the channel being programmed. To the right of the display, are trip relay
status indicators. As values for each relay as being entered the respective LED will
illuminate The fault relay is not programmable and provides status indication only.
Programming (Contd)
Programming (Contd)
10
TECSYSTEM S.r.i
Power Supply
TECHNICAL SPECIFICATIONS
Communication
Inputs
Outputs
Burden 3VA
Data storage 10 years minimum
Digital linearity of sensors signa l
Self-diagnostic circuit
Opt. Protection treatment of
electronic part
Opt. front plastic protection
Dimensions
96 x 96mm (3.78 x 3.78 in.) -DIN N43700Prof. 140mm Deep (with rear terminals)
panel cutout 92 x 92mm (3.62 x 3.
11
Testing
Temperature Simulation.
Warranty
12
Troubleshooting
Problem
The unit will not switch on, with
control power energized
The sensor is damaged
Causes / Solution
Check the terminal block for correct
installation
Check for voltage at terminal block
The fault relay closes and the fault LED
switches on. The green LED of the respective
channel is illuminated. A message is
displayed.
FOC- sensor open
FCC- sensor is short circuited
13
Options
All options available with the NT538 are offered as accessory modules.
Optional modules are connected to the NT538 via the proprietary Tecsystem
communications bus.
The connection is two wire twisted pair, with no set up required.
The NT538 has an indicator that illuminates when connected to an optional
module
Modules may be mixed allowing complete flexibility
Optional modules
Communication Modbus RS485 protocol
Analog outputs up to 8 channels
Switched contact up to 8 channels
Programming of modules is via DIP switches located on the respective
module
Documentation of module feature will be forwarded under separate cover
Approvals
Ordering
To order, select the basic model and the desired features from the selection
Guide below.
NT538
100 ohm platinum RTD
100 ohm nickel RTD
120 ohm nickel RTD
RTD
* 100PT
100 N
120 N
Busmod 8A
*
DIG
DIG
DIG
Conv8/420/A
*
ANAL
ANAL
ANAL
Switch 8x
Mod RL8-A
Mod RL8-A
Mod RL8-A
* Specify the NT538 model based on the RTD type and add suffix for
optional modules
Optional Module
Parts number
Description
Busmod 8A
Modbus RS485 protcol
Conv /420/8/A
8 channel 4-20 ma output
MOD RL 8-A
8 switch outputs
Note
The NT 538 basic unit and optional modules will be shipped as separate units,
with individual part numbers shown.
Any item may be ordered by part number reference
.
14