04B-Tutorial CT Selection
04B-Tutorial CT Selection
Xct
CT Ratio = 400/5A
N = 80 Turns
RCT is ignored in this example.
3VA
Material = CROSS
Kv = 272 V/tesla
Ki = 2.08 mm/turn
R = 0.7
Find the primary fault setting and the minimum stabilising
resistor value. Assume relay burden is 1VA. Use magnetising
curve supplied, scale the Kv and Ki factors to calculate the
magnetising current.
500/1
Rs
500/1
MCAG14
Solutions:
1.
60
= 0.003378 m 2
222 80
6 cm
16 cm
6 + 16
= 11cm
2
10.76 cm
20 cm
2 cm
AN
1
10 4 =
4.44 50
Kv = 60 V/ tesla
AN 33.78 80
=
= 60
4.5
45
V. Calculation of Ki factor
Employing metric units with mean magneetic length in mm
Mean magnetic length = D = x 11 x 10 = 346 mm
Ki = Mean magnetic length/ N
=
346
= 4.32mm / Turn
80
2.
400/5
O/C
Earth Fault
Relay Impedances:
Phase Overcurrent = 3 VA at 125% of 5 A
Z = 3/6.252 = 0.077
E/F = 2.4 VA at 40% of 5 A
Z = 2.4/22 = 0.6
Full equivalent circuit, including magnetising impedances
O/C
0.077 Ohms
Rct
0.2 Ohms
Z mag
0.077 Ohms
0.2 Ohms
0.077 Ohms
0.2 Ohms
E/F
0.6 Ohms
1.73 V
0.2
6.25 A
In = 0
4V
1.73 V
0.08 A
II.
Step A
Step B
4V
1.2 V
0.16 A
0.08 A
Step C
0.2 Ohm
Faulted Phase
2.032 A
Sound Phase
Imag = 0.016 A
Sound Phase
Imag = 0.016 A
2A
Step D
1.2 V
0.6 Ohm
Step E
8V
4V
1.76 V
0.02 A
0.08 A
Step F
0.2 Ohm
Faulted Phase
2.032 A
0.02 A
Sound Phase
Imag = 0.016 A
Sound Phase
Imag = 0.016 A
2A
1.2 V
0.6 Ohm
3.
Step A
Step B
3500
3 = 1166.67 = 15.3kA
132
76.2
3
I P 15300 A
30.6 A
=
n
500
Step C
Rloop
0.7
2.0
Rstab
Fault Is = 30.6 A
If other CT's Saturate
Step D
Step E
108.8 V
82.6 V
54.4 V
0.025 A
Step F
0.0416 A
0.025
0.025
0.025
0.025
Setting
Current
= 0.4 A
CAG14
set 0.4 A
Re laySettingVoltage 82.6
=
= 206.5
Re laySettingCurrent
0.4