Paper 4 - Energy Auditor - Set B Answer Key: General Instructions
Paper 4 - Energy Auditor - Set B Answer Key: General Instructions
Paper 4 - Energy Auditor - Set B Answer Key: General Instructions
Duration: 2 HRS
General instructions:
o
o
o
o
o
Section - I:
Marks: 10 x 1 = 10
While using pitot tubes for airflow measurement in large ducts, series of traverse
readings are recommended. Why?
Velocity of air stream is not uniform across the cross section of the duct. Friction
slows the air moving closes to the wall, so the velocity is greater in the center of the
duct. Therefore, average of velocity measurement readings are required
S-2
S-3
Installing the capacitor near motor terminals will increase the design power factor of
the motor - True / False
False
S-4
Between back pressure turbine and condensing turbine which will have more power
generation efficiency?
Condensing turbine
_________________________
Bureau of Energy Efficiency
The active power consumed by a pure inductive or capacitive load will be zero.
State -True or False.
True
S-6
In a shell and tube heat exchanger, engaged in heat transfer between fouling fluid
and clear fluid, the fouling fluid should be put on shell side or tube side?
Tube side
S-7
What is the power factor for electrical loads having only incandescent lamps?
Unity
S-8
S-9
S-10
While reducing excess air in a boiler what two parameters should be closely
monitored in the exit flue gases ?
CO, O2
Section - II:
Marks: 2 x 5 = 10
Ans.
In energy efficient motor the slip is less compared to standard motor. Hence
the RPM of energy efficient motor will increase.
Power is proportional to cube of speed for centrifugal fan. Hence the power
consumption will increase
L-2
_________________________
Bureau of Energy Efficiency
Cooling
Tower
Cooling
Tower
50m
2m
Condenser
Pump
Condenser
Pump
Numerical Questions
Marks: 4 x 20 = 80
_________________________
Bureau of Energy Efficiency
x 82 x 60
4
x 10
302 m3/hr
3 x v x I x cos
3 x 0.415 x 93 x 0.89
59.5 kW
Total head
Friction head
Velocity (flow/cross sectional area of
pipe) metre/ second
Friction head
_________________________
Bureau of Energy Efficiency
4flv2/2gD
(302/3600)/( x 0.302/4)
1.19 m/s
4 x 0.005 x 1.192 x 8000
2 x 9.81 x 0.3
38.5 metres
38.5 ( -2)
40.5 m
(302/3600) x 40.5 x 9.81
33.3 kW
59.5 x 0.91
54.15 kW
33.3 /54.15
61.5 %
N-2
Conde nsate
Make-up wa ter
Quantity = 3 TPH
Temp. = 28 C
Boiler
Capacity
10 TPH
Feed Water
Tank
Bare Pipe
Feed
Pu mp
: 186 kCal/kg
: 478 kCal/kg
:
:
:
:
:
0.95
840 kg/ hr
6269 kCal/kg
3.5%
4%
Answer
i. Average Feed water temperature at feed water tank:
(4000x 94 + 3000x 28)
7000
=65.7 C
ii boiler efficiency by direct method on GCV basis
_________________________
Bureau of Energy Efficiency
_________________________
Bureau of Energy Efficiency
Year
0.0
1.0
2.0
3.0
4.0
5.0
6.0
Capital
investment,
Rs
-650000
Maintenance,
Rs
Savings,
Rs
Real
Savings,
Rs
10000
10000
110000
12000
12000
12000
NPV
140000
140000
140000
200000
200000
300000
130000
130000
30000
188000
188000
288000
Profitability index
Profitability index
Discount
factor
9%
1
0.917431
0.84168
0.772183
0.708425
0.649931
0.596267
Present
Value, Rs
-650000
119266.1
109418.4
23165.5
133183.9
122187.1
171725
28945.99
NPV/Investment
0.04453
N-4 A process industry invites an energy auditor to suggest ways and means to
reduce the maximum demand on the grid supply. The process industry has a
contract demand of 3940 kVA with Electricity Supply Company. The average
monthly maximum demand is recorded as 3250 kVA at the power factor of 0.9.
The process industry has to pay minimum demand charges of 75% of the
contact demand to the electricity supply company.
After analyzing the electricity bill, the auditor studies the existing PF capacitors
installation at the plant LT substation bus bar and observes the following
connections arrangement.
_________________________
Bureau of Energy Efficiency
R
Operating line
to line voltage
415 V,
AC,3 Phase
B
N
PF capacitors PF capacitors
PF capacitors
The auditor observes that, there are 10 capacitor banks per phase, each bank
comprises of 5 units of PF capacitors and each unit is rated for 10 kVAr at 415 V.
Give your answer on the following:
a)
b)
c)
d)
e)
What is the optimum limit of Power factor improvement, so that plant avoids
paying demand charges over and above the minimum demand charges?
What would be the annual maximum demand charge saving if the existing
power factor is improved to optimum power factor (MD charges @ Rs. 250/- per
kVA per month) ?
What is the additional PF capacitors kVARs requirement to achieve the
desired PF?
What is the present operating capacity of PF capacitors installation at the LT
substation bus bar?
Whether energy auditor would still recommend installation of extra power
factor capacitors in the above situation to achieve the additional PF capacitors
kVARs requirement with the existing capacitors installation at the LT bus bar?
Support your answer with reasons.
Answer
a) Optimum limit of PF improvement:
Desirable MD= 3940x0.75=2955kVA
Desired PF = 3250x0.90/2955= 0.99
b) Annual MD Charge saving = Rs. 250 x 12 x (3250 2955) = Rs. 885000
c) Additional PF capacitors kVARs requirement
= kW( tan cos inv PF1- tan cos inv PF2)
= 3250x0.9( tan cos inv 0.9- tan cos inv 0.99)
= 2925(tan25.84193276-tan 8.109614456)
=2925(0.484322104-0.142492782)
=2925(0.341829821)
= 1000kVAR
_________________________
Bureau of Energy Efficiency
= 10 x 3 = 30
= 30 x 5 = 150
= 150 x 10 = 1500 kVAr at 415 V
As operating voltage of the capacitors in the existing arrangement is 415/ 1.73 = 239.6
V, the actual operating kVAr of the capacitor unit will reduce from 10 kVAr to 10 x
(239.6/415 V)^2 = 3.333 kVAr
Total operating kVAr of the existing installation
R
415 V,
3 Phase
B
N
--10 capacitor banks per phase
--Each capacitor bank having 5 units
--Each unit rated for 10 kVAr at 415V
-- Neutral potential is zero volt
_________________________