Solar System Design Guide
Solar System Design Guide
Solar Basics
PV power generation systems are made up of interconnected components, each with a specific function. One of the major
strengths of PV systems is modularity. As your needs grow, individual components can be replaced or added to provide
increased capacity. Following is a brief overview of a typical PV system.
Solar Array – The solar array consists of one or more PV modules which convert sunlight into electric energy. The
modules are connected in series and/or parallel to provide the voltage and current levels to meet your needs. The array is
usually mounted on a metal structure and tilted to face the sun.
Charge Controller – Although charge controllers can be purchased with many optional features, their main function is
to maintain the batteries at the proper charge level, and to protect them from overcharging.
Battery Bank – The battery bank contains one or more deep-cycle batteries, connected in series and/or parallel
depending on the voltage and current capacity needed. The batteries store the power produced by the solar array and
discharge it when required.
Inverter – An inverter is required when you want to power AC devices. The inverter converts the DC power from the solar
array/batteries into AC power.
AC and DC Loads – These are the appliances (such as lights or radios), and the components (such as water pumps
and microwave repeaters), which consume the power generated by your PV array.
Balance of System – These components provide the interconnections and standard safety features required for any
electrical power system. These include: array combiner box, properly sized cabling, fuses, switches, circuit breakers and
meters.
List all of the electrical appliances to be powered by your PV system. Separate AC and DC devices and enter them in
the appropriate table. Record the operating wattage of each item. Most appliances have a label on the back that lists the
wattage. Local appliance dealers and the product manufacturers are other sources of this information. Specify the number
of hours per day each item will be used. Multiply the first three columns to determine the watt-hour usage per day. Enter
the number of days per week you will be using each item to determine the total watt-hours per week each appliance will
require.
Total the numbers in the last column. This is your DC power requirement. Total _______
Multiply the total by 1.2 to compensate for system losses during battery charge/discharge cycle. DC WH/WK _______
3
/06 99
Design Guide
AC Appliance Watts X Qty X Hrs/Day = Wh/Day X Days/Wk = Wh/Wk
A. _____________________________________________________________ _______________________ ______
B. _____________________________________________________________ _______________________ ______
C. _____________________________________________________________ _______________________ ______
D. _____________________________________________________________ _______________________ ______
E. _____________________________________________________________ _______________________ ______
Total the numbers in the last column. This is your AC power requirement. Total ______
Multiply the total by 1.2 to compensate for system losses during battery charge/discharge cycle. AC WH/WK ______
1. Add AC WH/WK and DC WH/WK together. This is your total power requirement per week. Total _______
2. Enter the voltage of your battery bank (usually 12 or 24 volts) VOLTS _______
3. Divide line 1 by line 2. This is your amp-hour requirement per week. AH/WK _______
4. Divide line 3 by 7 days. This is your average amp-hour requirement per day
that will be used to size your battery bank and your PV module array. AH/DAY _______
Characteristics of Batteries
Temperature Effects
Batteries are sensitive to temperature extremes, and you cannot take as much energy out of a cold battery as a warm one. Use
the chart on the Battery-Sizing Worksheet to correct for temperature effects. Although you can get more than rated capacity
from a hot battery, operation at hot temperatures will shorten battery life.
1
00 3/06
Design Guide
Depth of Discharge
Depth of Discharge is the percentage of the rated battery capacity that is withdrawn from the battery. The capability of
a battery to withstand discharge depends on its construction. Two terms, shallow-cycle and deep-cycle, are commonly
used to describe batteries. Shallow-cycle batteries are lighter, less expensive and have a short lifetime. For this reason, we
do not sell shallow-cycle batteries. Deep-cycle batteries should always be used for stand-alone PV systems. These units
have thicker plates and most will withstand daily discharges up to 80% of their rated capacity. Most deep-cycle batteries
are flooded electrolyte which means the plates are covered with the electrolyte and the level of fluid must be monitored
and distilled water added periodically to keep the plates fully covered. We also offer sealed, lead-acid batteries that do not
require liquid refills. There are other types of deep-cycle batteries such as nickel cadmium used in special applications. The
maximum depth of discharge value used for sizing should be the worst case discharge that the battery will experience. The
system control should be set to prevent discharge below this level.
Battery Life
The lifetime of any battery is difficult to predict, because it is dependent on a number of factors such as charge and
discharge rate, depth of discharge, number of cycles and operating temperature extremes. It would be unusual for a lead-
acid battery to last longer than fifteen years in a PV system but many last for five to eight years.
Maintenance
Batteries require periodic maintenance. Even the sealed battery should be checked to make sure connections are tight and
there is no indication of overcharging. For flooded batteries, the electrolyte level should be maintained well above the plates
and the voltage and specific gravity of the cells should be checked for consistent values. Wide variations between readings
may indicate cell problems. The specific gravity of the cells should be checked with a hydrometer particularly before the
onset of winter. In cold environments, the electrolyte in lead-acid batteries may freeze. The freezing temperature is a function
of a battery state of charge. When a battery is completely discharged, the electrolyte becomes water and the battery may
freeze.
1. Enter your daily amp-hour requirement. (From the Load Sizing Worksheet, line 4) AH/Day ______________
3. Multiply the amp-hour requirement by the number of days. This is the amount of amp-hours
your system will need to store. AH ______________
4. Enter the depth of discharge for the battery you have chosen. This provides a safety factor
so that you can avoid over-draining your battery bank.
(Example: If the discharge limit is 20%, use 0.2.) This number should not exceed 0.8. ______________
DESIGN
GUIDE
3
/06 101
Design Guide
Battery-Sizing Worksheet
6. Select the multiplier below that corresponds to the average wintertime ambient temperature
your battery bank will experience. ______________
Ambient Temperature Multiplier
80ºF 26.7ºC 1.00
70ºF 21.2ºC 1.04
60ºF 15.6ºC 1.11
50ºF 10.0ºC 1.19
40ºF 4.4ºC 1.30
30ºF -1.1ºC 1.40
20ºF -6.7ºC 1.59
7. Multiply line 5 by line 6. This calculation ensures that your battery bank will have
enough capacity to overcome cold weather effects. This number represents the total battery
capacity you will need. AH ______________
8. Enter the amp-hour rating for the battery you have chosen. ______________
9. Divide the total battery capacity by the battery amp-hour rating and round off to the next highest
number. This is the number of batteries wired in parallel required. ______________
10. Divide the nominal system voltage (12V, 24V or 48V) by the battery voltage and round off
to the next highest number. This is the number of batteries wired in series. ______________
11. Multiply line 9 by line 10. This is the total number of batteries required. ______________
State, City Summer Avg. Winter Avg. Yr. Round Avg State, City Summer Avg. Winter Avg. Yr. Round Avg
AL, Montgomery 4.69 3.37 4.23 CA, La Jolla 5.24 4.29 4.77
AK, Bethel 6.29 2.37 3.81 CA, Los Angeles 6.14 5.03 5.62
AK, Fairbanks 5.87 2.12 3.99 CA, Riverside 6.35 5.35 5.87
AK, Mantanuska 5.24 1.74 3.55 CA, Santa maria 6.52 5.42 5.94
AZ, Page 7.30 5.65 6.36 CA, Soda Springs 6.47 4.40 5.60
DESIGN
1
02 3/06
Design Guide
Sun Hours Per Day - National continued
State, City Summer Avg. Winter Avg. Yr Round Avg. State, City Summer Avg. Winter Avg. Yr Round Avg.
FL, Belle Island 5.31 4.58 4.99 PA, Pittsburgh 4.19 1.45 3.28
FL, Gainsville 5.81 4.71 5.27 PA, State College 4.44 2.78 3.91
FL, Miami 6.26 5.05 5.62 RI, Newport 4.69 3.58 4.23
FL, Tampa 6.16 5.26 5.67 SC, Charleston 5.72 4.23 5.06
GA, Atlanta 5.16 4.09 4.74 SD, Rapid City 5.91 4.56 5.23
GA, Griffin 5.41 4.26 4.99 TN, Nashville 5.20 3.14 4.45
HI, Honolulu 6.71 5.59 6.02 TN, Oak Ridge 5.06 3.22 4.37
IA, Ames 4.80 3.73 4.40 TX, Brownsville 5.49 4.42 4.92
ID, Twin Falls 5.42 3.41 4.70 TX, El Paso 7.42 5.87 6.72
ID, Boise 5.83 3.33 4.92 TX, Port Worth 6.00 4.80 5.83
IL, Chicago 4.08 1.47 3.14 TX, Midland 6.33 5.23 5.83
IN, Indianapolis 5.02 2.55 4.21 TX, San Antonio 5.88 4.65 5.30
KS, Dodge City 4.14 5.28 5.79 UT, Flaming Gorge 6.63 5.48 5.83
KS, Manhattan 5.08 3.62 4.57 UT, Salt Lake City 6.09 3.78 5.26
KY, Lexington 5.97 3.60 4.94 VA, Richmond 4.50 3.37 4.13
LA, Lake Charles 5.73 4.29 4.93 WA, Prosser 6.21 3.06 5.03
LA, New Orleans 5.71 3.63 4.92 WA, Pullman 6.07 2.90 4.73
LA, Shreveport 4.99 3.87 4.63 WA, Richland 6.13 2.01 4.43
MA, Blue Hill 4.38 3.33 4.05 WA, Seattle 4.83 1.60 3.57
MA, Boston 4.27 2.99 3.84 WA, Spokane 5.53 1.16 4.48
MA, E. Wareham 4.48 3.06 3.99 WV, Charleston 4.12 2.47 3.65
MA, Lynn 4.60 2.33 3.79 WI, Madison 4.85 3.28 4.29
MA, Natick 4.62 3.09 4.10 WY, lander 6.81 5.50 6.06
MD, Silver Hill 4.71 3.84 4.47
ME, Caribou 5.62 2.57 4.19 Province, City
ME, Portland 5.2 3.56 4.51 Alberta, Edmonton 4.95 2.13 3.75
MI, E. Lansing 4.71 2.70 4.00 Alberta, Suffield 5.19 2.75 4.10
MI, Sault Ste. Marie 4.83 2.33 4.20 British Columbia,
MN, St. Cloud 5.43 3.53 4.53 Kamloops 4.48 1.46 3.29
MO, Columbia 5.5 3.97 4.73 British Columbia,
MO, St. Louis 4.87 3.24 3.78 Prince George 4.13 1.33 3.14
MS, Meridian 4.86 3.64 4.44 British Columbia,
MT, Glasgow 5.97 4.09 5.15 Vancouver 4.23 1.33 3.14
MT, Great Falls 5.70 3.66 4.93 Manitoba, The Pas 5.02 2.02 3.56
MT, Summit 5.17 2.36 3.99 Manitoba, Winnipeg 5.23 2.77 4.02
NC, Cape Hatteras 5.81 4.69 5.31 New Brunswick,
NC, Greensboro 5.05 4.00 4.71 Fredericton 4.23 2.54 3.56
ND, Bismark 5.48 3.97 5.01 Newfoundland,
NE, Lincoln 5.40 4.38 4.79 Goose Bay 4.65 2.02 3.33
NE, North Omaha 5.28 4.26 4.90 Newfoundland,
NJ, Sea Brook 4.76 3.20 4.21 St. Johns 3.89 1.83 3.15
NM, Albuquerque 7.16 6.21 6.77 Northwest Territory,
NV, Ely 6.48 5.49 5.98 Fort Smith 5.16 0.88 3.29
NV, Las Vegas 7.13 5.83 6.41 Northwest Territory,
NY, Bridgehampton 3.93 1.62 3.16 Norman Wells 5.04 0.06 2.89
NY, Ithaca 4.57 2.29 3.79 Nova Scotia,
NY, New York 4.97 3.03 4.08 Halifax 4.02 2.16 3.38
NY, Rochester 4.22 1.58 3.31 Ontario, Ottawa 4.63 2.35 3.70
NY, Schenectady 3.92 2.53 3.55 Ontario, Toronto 3.98 2.13 3.44
OH, Cleveland 4.79 2.69 3.94 Prince Edward Isl.,
OH, Columbus 5.26 2.66 4.15 Charlottetown 4.31 2.29 3.56
OK, Oklahoma City 6.26 4.98 5.59 Quebec, Montreal 4.21 2.29 3.50
OK, Stillwater 5.52 4.22 4.99 Quebec, Sept-Isles 4.29 2.33 3.50
DESIGN
GUIDE
3/06 103
Design Guide
World Insolation Map
This map divides the world into six solar performance regions based on winter peak sun hours in the worst case month. A larger map
in full color is located on the back cover of this catalog.
9. Multiply line 7 by line 8. This is the nominal power output of your system. W ______________
1
04 3/06