EEE. 2mark and 16 Marks Quest-With Answer
EEE. 2mark and 16 Marks Quest-With Answer
EEE. 2mark and 16 Marks Quest-With Answer
UNIT I INTRODUCTION
Importance of protective schemes for electrical apparatus and power system. Qualitative
review offaults and fault currents - relay terminology definitions - and essential qualities of
protection.Protection against over voltages due to lightning and switching - arcing grounds Peterson Coil -ground wires - surge absorber and divertersPower System earthing neutral
Earthing - basic ideas of insulation coordination
PART- A
(i)
Va = IaZf
(ii)
Ib = I c = 0
21The methods commonly used for grounding the neutral point of a 3-phase
systems are:
i)
ii)
iii)
iv)
PART- B
1. Discuss in detail of symmetrical components of a power system?
The analysis of unsymmetrical poly phase network by the method of
symmetrical components was introduced by Dr. C Fortesque. He proved that an
unbalanced system of n related vectors can be resolved into n system of
balanced vectors called symmetrical components are original vectors. The n
vectors of each set of components are equal in length and the phase angles
between adjacent vectors of the set are equal.
In a three phase system, the three unbalanced vectors [either V a1Vb&Vcor
Ia1Ib&Ic] can be resolved into three balanced system of vectors. The vectors of
the balanced system are called symmetrical components of the original system.
The symmetrical components of three phase system are,
1. Positive sequence components
2. Negative sequence components
3. Zero sequence components.
The positive sequence components consists of three vectors equal in
magnitude is placed from each other by 120 0 in phase, and having the same
phase sequence as the original vectors.
The negative sequence components consists of three vectors equal in
magnitude, displaced from each other by 1200 in phase, and having the phase
sequence opposite to that of the original vectors.
The zero sequences components consists of three vectors equal in
magnitude and with zero phase displacement from each other.
Let Va1 Vb and Vc be the set of unbalanced voltage vectors with phase
sequence abc. Each voltage vector can be resolved into positive, negative and
zero sequence components.
Let
Va1 Vb1 and Vc1= Positive sequence components of Va
Vb and Vc respectively with phase sequence abc.
Va2 Vb2 Vc2 = Negative sequence components of Va
======================================
==========================
2. Explain in detail of Computation of unbalanced vectors from their
symmetrical components
Each of the original unbalanced vector is the sum of its positive, negative
and zero sequence component. Therefore the original unbalanced three phase
voltage vectors can be expressed in terms of their components as shown below.
Va =Va1+ Vb1 + Vc1(1.87)
Vb =Vb0+ Vb1 + Vb2(1.88)
Vc =Vc0+ Vc1 + Vc2(1.89)
Various symmetrical components.
Vbo Vbo : Vb1 a 2Vb1 :
Vb 2 Vb 2 ........(1.90)
Vc 0 Vc 0 : Vc1 aVc1 :
Vc 2 Vc 2 ........(1.91)
Using equations (1.90) and (1.91), the equations (1.87) to (1.89) can be written
as shown below.
Va =Va0+ Va1 + Va2(1.92)
Vb =Vb0+ a 2Vb1 + aVb2(1.93)
Vc =Vc0+ aVc1 + a 2Vc2(1.94)
The equations (1.92) to (1.94) can be arranged in the matrix form as shown in
equ(1.95).
1 1 1
Va
V 1 a 2 a
b
1 a a 2
Vc
V a 0
V a1 .......(1.95)
V a 2
The equation (1.95) can be used to compute the unbalanced vectors from the
Knowledge of symmetrical components.
======================================
==========================
3.Write short notes on symmetrical components of unbalanced current
vectors.
b
3
1 a a 2
I c
I a 0
I a1 .......(1.109)
I a 2
1 1 1
I a 0
I 1 1 a a 2
a1
3
1 a 2 a
I a 2
Ia
I .......(1.113)
b
I c
======================================
=========================
4. The symmetrical components of phase-a fault current in a 3-phase
unbalanced system are Ia0 = 350 900 AIa1=900 -90Aand Ia2=250 900A.
Determine the phase currents Ia,Ib and Ic.
Solution:
The current Ia,Ib and Ic are given by the following matrix equations.
1 1 1
I a
I 1 a2 a
b
1 a a 2
I c
I a 0
I a1
I a 2
I a I a 0 I a1 I a 2
I b I a 0 a 2 I a1 aI a 2
I c I a 0 aI a1 a 2 I a 2
Given that
I a 0 350 900 0 j350
I a1 600 900 0 j 600
I a 2 250 900 0 j 250
========================================================
5. Discuss about solid Grounding?
When the neutral point of a 3-phase system (e.g. 3- phase generator, 3phase transformer etc.) is directly connected to earth (i.e. soil) through a wire of
negligible resistance and reactance, it is called solid grounding or effective
grounding. Since the neutral point is directly connected to earth through a wire,
the neutral point is held at earth potential under all conditions. Therefore, under
fault conditions, the voltage of any conductor to earth will not exceed the
normal phase voltage of the system.
Figure
* This is a metallic connection made form the neutral of the system to one or
more earth electrodes consisting of plates, rods or pipes buried in the ground.
ii)
When earth fault occurs on any phase, the resultant capacitive current I C
is in phase opposition to the fault current IF. the two current completely
cancel each other. Therefore, no arcing ground or over-voltage
conditions can occur. Considering a line to ground fault in line B, the
Applications.
Solid grounding is usually employed where the circuit impedance is
sufficiently high so as to keep the earth fault current within safe limit. This
system of grounding is used for voltages upto 33 kV with total power capacity
not exceeding 5000 kVA.
Discuss about Resistance Grounding?
In order to limit the magnitude of earth fault current, it is a common
practice to connect the neutral point of a 3-phase system to earth through a
resistor. This is called resistance grounding.
When the neutral point of a 3-phase system (e.g. 3-phase generator, 3phase transformer etc.) is connected to earth (i.e. soil) through a resistor, it is
called resistance grounding.
i)
ii)
iii)
The earth fault current is small due to the presence for earthing
resistance. Therefore, interference with communication circuits is
reduced.
It improves the stability of the system.
Disadvantages.
The following are the disadvantages of resistance grounding:
i)
When the value of L of arc suppression coil is such that the fault current
IF exactly balances the capacitive current IO it is called resonant grounding.
The reactor is provided with tappings to change the inductance of the coil. By
adjusting the tappings on the coil, the coil can be tuned with the capacitance of
the system i.e. resonant grounding can be achieved.
Figure
Operation. Fig. (i) shows the 3-phase system employing Peterson coil
grounding. Suppose line to ground fault occurs in the line B at point F. the
fault current IF and capacitive currents IR and IY will flow as shown in Fig. Note
that IF flows through the Peterson coil (or Arc suppression coil) to neutral and
back through the fault. The total capacitive current I C is the phasor sum of IR
and IY as shown in phasor diagram in Fig. The voltage of the faulty phase is
applied across the arc suppression coil. Therefore, fault current I F lags the faulty
phase voltage by 900. the current IF is in phase opposition to capacitive current
IC [See Fig(ii)]. By adjusting the tappings on the Peterson coil, the resultant
current in the fault can be reduced. If inductance of the coil is so adjusted that
IL = IC, than resultant current in the fault will be zero.
Value of L for resonant grounding.
For resonant grounding the system behaves as an ungrounded neutral
system. therefore, full line voltage appears across capacitors CR and Cr.
IR IY
IC
3Vph
XC
3 IR
3Vph
XC
3Vpv
XC
Fault current,
Vph
XL
Or
XL
XC
XL
XC
3
1
3C
Or
Or
L
3Vph
1
3 2C
IL IC
Exp. (i) gives the value of inductance L of the arc suppression coil for resonant
grounding.
Advantages:
i)
ii)
Disadvantages:
disadvantages:
i)
ii)
The
Peterson
coil
grounding
has
the
following
========================================================
7. What are the Fundamental Requirements of Protective Relaying (or
Essential qualities of protection.
The principal function of protective relaying is to cause the prompt
removal from service of any element of the power system when it starts to
operate in an abnormal manner or interfere with the effective operation of the
rest of the system. In order that protective relay system may perform relay
system may perform this function satisfactorily, it should have the following
qualities.
(i) selectivity
(ii)speed
(iv) reliability
(v) simplicity
(iii) sensitivity
(vi) economy
(a) generators
(b) low-tension switchgear
(c) transformers
(d) high-tension switchgear
(e) transmission lines
There is certain amount of overlap between the adjacent protection zones
in transmission lines. For a failure within the region where two adjacent zones
overlap, more breakers will be opened than the minimum necessary to
disconnect that faulty section. But if there were no overlap, a failure in the
religion between zones would not lie in either region and, therefore, no breaker
would be opened. For this reason, a certain amount of overlap* is provided
between the adjacent zones.
(ii) Speed: The relay system should disconnect the faulty section as fast as
possible for the following reasons:
(a) Electrical apparatus may be damaged if they are made to carry the fault
currents for a long time
(b) A failure on the system leads to a great reduction in the system voltage. If
the faulty section is not disconnected quickly, then the low voltage
created by the fault may shut down consumers motors and generators on
the system may become unstable.
(c) The high speed relay system decreases the possibility of development of
one type of fault into the other more severe type.
(iii) Sensitivity: It is the ability of the relay system to operate with low value
of actuating quantity.
(iv) Reliability:
(v) Simplicity:
================================================
======================