CRR40
CRR40
CRR40
CRR DF MPC2000ID
CRR DF MP 3000
TK 50134-4-MM (Rev. 5, 06/02)
TK50262
TK41166
TK40282
TK40612
Tool Catalog
TK5955
The information in this manual is provided to assist owners, operators and service people in the proper
upkeep and maintenance of Thermo King units.
This manual is published for informational purposes only and the information so provided should
not be considered as all-inclusive or covering all contingencies. If further information is required,
Thermo King Corporation should be consulted.
Sale of product shown in this manual is subject to Thermo Kings terms and conditions
including, but not limited to, the Thermo King Limited Express Warranty. Such terms and
conditions are available upon request. Thermo Kings warranty will not apply to any
equipment which has been so repaired or altered outside the manufacturers plants as,
in the manufacturers judgment, to effect its stability.
No warranties, express or implied, including warranties of fitness for a particular
purpose or merchantability, or warranties arising from course of dealing or usage of
trade, are made regarding the information, recommendations, and descriptions
contained herein. Manufacturer is not responsible and will not be held liable in contract
or in tort (including negligence) for any special, indirect or consequential damages,
including injury or damage caused to vehicles, contents or persons, by reason of the
installation of any Thermo King product or its mechanical failure.
Recover Refrigerant
At Thermo King, we recognize the need to preserve the environment
and limit the potential harm to the ozone layer that can result from
allowing refrigerant to escape into the atmosphere.
We strictly adhere to a policy that promotes the recovery and limits
the loss of refrigerant into the atmosphere.
In addition, service personnel must be aware of Federal regulations
concerning the use of refrigerants and the certification of technicians.
For additional information on regulations and technician certification
programs, contact your local Thermo King dealer.
Table of Contents
List of Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
CRR DF Model Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Refrigerant Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
High Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
General Safety Precautions for Servicing Units (or Containers) Equipped with a Microprocessor Controller . . 15
Controller Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Welding of Units or Containers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Unit Decals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Serial Number Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Service Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Full Cool Operation Net Cooling Capacity* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
System Net Defrost Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Evaporator Airflow** . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
R-134a Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
R-23 Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Electrical System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Microprocessor Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Compressor Torque 3D Copeland Compressor Bolt Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Metric Hardware Torque Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Cascade Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Microprocessor Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Datalogger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Three Evaporator Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
USDA Cold Treatment Temperature Recording . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
REFCON Remote Monitoring Modem (RMM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Frozen Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Basic Unit Controls, Instruments and Protection Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Unit Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
MPC2000, MPC2000ID or MP3000 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Other . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
R-134a Refrigeration System Controls, Instruments and Protection Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
R-23 Refrigeration System Controls, Instruments and Protection Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Pretrip Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Power Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Pre-load Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Pre-Trip Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Pre-Trip Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Loading Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Post Load Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Starting the Unit on Ship . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Post Trip Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Table of Contents
Microprocessor Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
General Theory of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Frozen Loads (Setpoint at -10 C [14 F] and Below) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Unit Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Continuous Temperature Control Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Changing the Setpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Initiating a Manual Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Displaying Alternate Controlling (Supply or Return) Air Sensor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Displaying Alternate Fahrenheit (F) or Celsius (C) Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Menu Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Controller Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Data Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Alarm List Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Commands Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Manual function Test, DF units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Misc. Functions Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Configuration Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
MP-3000 Configuration List, DF Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Datalogger Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
RMM State Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
PTI (Pretrip) Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Temperature Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Manual Emergency Mode Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Replacing the EPROM Chip (MPC2000 and MP3000 Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Replacing the Microprocessor Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Flash Loading Controller Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
MPC 2000 ID / MP 3000, Super Freezer "Error message list" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Alarm Codes, Descriptions and Corrective Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Electrical Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Unit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
High Pressure Cutout Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
R-23 High Pressure Cutout Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
R-134a High Pressure Cutout Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Condenser Fan and Evaporator Fan Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Condenser Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Evaporator Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Electric Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Low Pressure Cutout Switch (R-23 System on CRR DF MPC2000ID Units Only) . . . . . . . . . . . . . . . . . . . . . . . 86
Low Pressure Cutout Switch: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Refrigeration Maintenance and Service Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Service Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
R-134a Service Fittings and Gauge Manifold Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Leak Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Vacuum Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
System Cleanup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Refrigerant Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Compressor Oil Acid Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Compressor Discharge and Suction Service Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Gauge Manifold Valve Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
R-134a Gauge Manifold Set (With Low Loss Fittings) Attachment And Purging . . . . . . . . . . . . . . . . . . . . . . . . . 90
R-134a Gauge Manifold Set Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Gauge Manifold Set Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Service Procedure Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Typical R-23 and R-134a System Suction and Discharge Pressure Readings . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Discharge Pressure Regulator Test and Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Table of Contents
Refrigeration Maintenance and Service Operations (continued)
Checking Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Checking the Compressor Oil Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Adding Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Removing Excess Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Refrigerant Leak Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Low Side Pump Down (R-134a Compressor Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Refrigerant Charge Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Checking the R-134a Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Checking the R-23 Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Refrigerant Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
R-23 Recovery for System Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
R-134a Vapor Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
R-134a Liquid Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Evacuation and Cleanup of the Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Contamination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Compressor Oil Color Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Refrigeration System Preparation and Hookup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Unit Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Pressure Rise Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Factors Affecting the Speed of System Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Heat Saves Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
R-134a Refrigeration System Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Charging R-134a System with Liquid Refrigerant by Weight (from an Evacuated Condition) . . . . . . . . . . 102
R-134a Evacuation Station Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
R-134a Final Charging Procedure for Partially Charged Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
R-23 Refrigeration System Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
R-23 Evacuation Station Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Charging R-23 System with Gas Refrigerant Recovered in 40 Liter (42 qt.) Refrigerant Bottle
(from an Evacuated Condition) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
R-23 Final Charging Procedure for Partially Charged Units on Empty Containers . . . . . . . . . . . . . . . . . . 104
R-23 Charging Procedure for Partially Charged Units on Loaded Containers . . . . . . . . . . . . . . . . . . . . . . 105
Using Pressurized Nitrogen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Dehydration, Pressure Testing, Purging and Soldering Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Compressor Replacement (R-134a or R-23 Systems) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Condenser Coil Replacement (R-134a or R-23 Systems) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Dehydrator (Filter Drier) Replacement (R-134a or R-23 Systems) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Expansion Valve Replacement (R-134a or R-23 Systems) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
R-23 System Heat Exchanger Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
R-23 System to R-134a System Plate Heat Exchanger Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Receiver Tank Replacement (R-134a or R-23 System) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
High Pressure Cutout Switch Replacement (R-134a or R-23 System) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Table of Contents
Refrigeration Maintenance and Service Operations (continued)
Liquid Line Solenoid Valve Replacement (R-134a System Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Low Pressure Cutout Switch Replacement (CRR DF MPC2000ID and MP3000 Units Only) . . . . . . . . . . . . . . 113
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Structural/Accessory Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Mounting Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Condenser Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Evaporator Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Defrost Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Evaporator Fan Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Condenser Fan Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Vacuum Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Mechanical Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Refrigeration System Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Electrical, Refrigeration and Controller Menu Flow Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
List of Figures
Figure 1: Unit Nameplate and Decal Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 2: Unit Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 3: Evaporator Section Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 4: Vacuum Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 5: Power Cord Storage Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 6: Control Box and Microprocessor Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 7: MPC2000 or MP3000 Controller and Remote Monitoring Modem . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 8: MPC2000ID and MP3000 Controller, and Remote Monitoring Modem . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 9: Unit Control Box with Door Open . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 10: Low Pressure Cutout Switch in R-23 Refrigeration System (CRR DF MPC2000ID Units Only) . . . . 36
Figure 11: R-23 Compressor Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 12: Additional R-23 Refrigeration System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Figure 13: R-134a Compressor Compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 14: Additional R-134a Refrigeration System Components and Plate Heat Exchanger . . . . . . . . . . . . . . 40
Figure 15: Unit Back View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Figure 16: Unit Back View Pressure Regulators and Buffer Tanks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Figure 17: Unit Back View Electric Heaters and Evaporator Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 18: MPC2000, MPC2000ID and MP3000 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Figure 19: Frozen Load Control Sequence (Setpoints at -10 C [14 F] and Below) . . . . . . . . . . . . . . . . . . . . . . . 56
Figure 20: 3 Fan Evaporator: Evaporator (Defrost) Sensor Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Figure 21: Manual Emergency Control Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Figure 22: R-134a Service Fittings Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Figure 23: Service Valve Back Seated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Figure 24: Service Valve Open to Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Figure 25: Service Valve Front Seated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Figure 26: Balancing R-134a System Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Figure 27: Charging the R-134a System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Figure 28: Gauge Manifold Closed to Center Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Figure 29: Gauge Manifold Open to Center Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Figure 30: Removing R-134a Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Figure 31: Removing Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Figure 32: Purging Gauge Manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Figure 33: Discharge Pressure Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Figure 34: Checking Compressor Oil Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Figure 35: Adjusting Compressor Oil Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Figure 36: Testing for Refrigerant Leaks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Figure 37: R-134a Refrigeration System Receiver Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Figure 38: R-23 Refrigeration System Receiver Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Figure 39: Constant Pressure Rise After Evacuation Indicates System Leak . . . . . . . . . . . . . . . . . . . . . . . . . 101
Figure 40: Pressure Rise Levels Off After Evacuation Indicates Moisture in System . . . . . . . . . . . . . . . . . . . . 101
Figure 41: Typical Pressurized Gas Bottle with Pressure Regulator and Gauges . . . . . . . . . . . . . . . . . . . . . . 106
Figure 42: Mounting Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Figure 43: Evaporator Fan Blade Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Figure 44: Vacuum Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Figure 45: Condenser Fan Blade Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
List of Figures
10
Introduction
Model
CRR-40 DF MPC2000
CRR-40 DF MPC2000ID
CRR-40 DF MP3000
Features
X=Included
X X X 460-380V/3Ph 60-50 Hz, 18.3 m (60 ft) Power Cable and Plug
X X X 32 Amp Main Power Circuit Breaker
X X X Automatic Phase Selection Control
X X X Three Evaporator Fans with 2-Speed Motors
X X X One 1-speed Condenser Fan Motor
X MPC2000 Microprocessor Controller
X MPC2000 Datalogger
X MP3000 Microprocessor Controller
X MP3000 Datalogger
X MP2000ID Microprocessor Controller with Integral Datalogger
X X X Refcon Remote Monitoring Modem (RMM)
X X X USDA Cold Treatment Temperature Recording Three (3) Sensor
X X X D3DS Copeland Discus Compressor w/5.60 kW (7.5 Hp) Motor for R-134a Refrigeration Circuit
X X X Copper Receiver Tank with Moisture Indicating Sight Glass in R-134a Refrigerant Circuit
X X X Suction Pressure Gauge for R-134a Refrigeration Circuit
X X X Discharge Pressure Gauge for R-134a Refrigeration Circuit
X X X Hermetic Scroll Compressor w/4.48 kW (6.0 Hp) Motor for R-23 Refrigeration Circuit
X Low Pressure Cutout Switch for R-23 Refrigeration Circuit
X X X Stainless Steel Receiver Tank with Moisture Indicating Sight Glass in R-23 Refrigerant Circuit
X X X Suction Pressure Gauge for R-23 Refrigeration Circuit
X X X Discharge Pressure Gauge for R-23 Refrigeration Circuit
11
Introduction
12
Safety Precautions
General Practices
Refrigerant
First Aid
In the event of frost bite, the objectives of First
Aid are to protect the frozen area from further
injury, to warm the affected area rapidly, and to
maintain respiration.
Refrigerant Oil
Observe the following precautions when working
with or around refrigerant oil:
13
Safety Precautions
First Aid
Electrical
High Voltage
When servicing or repairing a refrigeration unit,
the possibility of serious or even fatal injury from
electrical shock exists. Extreme care must be used
when working with a refrigeration unit that is
connected to a source of operating power, even if
the unit is not running. Lethal voltage potentials
can exist at the unit power cord, inside the control
box, inside any high voltage junction box, at the
motors and within the wiring harnesses.
Precautions
1. Be certain the unit On/Off switch is turned
OFF before connecting or disconnecting the
unit power plug. Never attempt to stop the unit
by disconnecting the power plug.
2. Be certain the unit power plug is clean and dry
before connecting it to a power source.
3. Use tools with insulated handles that are in
good condition. Never hold metal tools in
your hand if exposed, energized conductors
are within reach.
4. Do not make any rapid moves when working
on high voltage circuits. If a tool or other
object falls, do not attempt to grab it. People
do not contact high voltage wires on purpose.
It occurs from an unplanned movement.
14
Safety Precautions
Low Voltage
Control circuits are low voltage (24 Vac and 12
Vdc). This voltage potential is not considered
dangerous, but the large amount of current
available (over 30 amperes) can cause severe
burns if shorted to ground.
Do not wear jewelry, watch or rings. These items
can short out electrical circuits and cause severe
burns to the wearer.
Controller Repair
When servicing the controller, it is necessary to
ensure that electrostatic discharges are avoided.
Potential differences considerably lower than
those which produce a small spark from a finger
to a door knob can severely damage or destroy
solid-state integrated circuit components. The
following procedures must be rigidly adhered to
when servicing these units to avoid controller
damage or destruction.
1. Disconnect all power to the unit.
2. Avoid wearing clothing that generates static
electricity (wool, nylon, polyester, etc.).
3. Do wear a static discharge wrist strap (TK P/N
204-622) with the lead end connected to the
controllers ground terminal. These straps are
available at most electronic equipment
distributors. DO NOT wear these straps with
power applied to the unit.
15
Safety Precautions
Unit Decals
Serial number decals, refrigerant type decals and
warning decals appear on all Thermo King
equipment. These decals provide information that
may be needed to service or repair the unit.
Service technicians should read and follow the
instructions on all warning decals.
AXA0343
AXA0344
AXA0345
16
AXA0346
Service Guide
Pre-Trip
Every
1,000
Hours
Annual/
Yearly
Check refrigerant charge on both the R-134a and R-23 refrigeration circuits.
Check for proper suction pressure on both the R-134a and R-23 refrigeration
circuits.
Check compressor oil level in both the reciprocating and scroll compressors.
Check discharge and suction pressures of both the R-134a and R-23
refrigeration circuits.
Check dehydrator for a restriction or corrosion on both the R-134a and R-23
refrigeration circuits.
Structural
Clean entire unit including condenser and evaporator coils and defrost
drains.
17
Service Guide
18
Specifications
Full Cool Operation Net Cooling Capacity*
460V, 3 Phase, 60 Hz Power
Return air to
evaporator coil
inlet
Watts
kW @460V
Watts
-25 C (-13 F)
10,000
8,600
34,130
17.0
8,300
7,138
28,325
14.1
-55 C (-67 F)
6,000
5,160
20,475
13.0
4,980
4,284
17,000
10.8
Power Consp
Kcal/hr BTU/hr
Power Consp
Kcal/hr BTU/hr
kW @460V
*System net cooling capacity with a 37.8 C (100 F) ambient air temperature.
Heating Capacity
Heating Capacity
Heater Type
Electric resistance rods
Watts
Kcal/hr
BTU/hr
Watts
Kcal/hr
BTU/hr
8,160
7,018
27,850
6,000
5,160
20,475
Evaporator Airflow**
External Static
Pressure (water
column)
Low Speed
m3/hr
Low Speed
ft3/min
m3/hr
ft3/min
0 mm (0 in.)
3,700
1,835
2,900
1,708
10 mm (0.4 in.)
3,300
1,943
2,350
1,384
20 mm (0.8 in.)
2,800
1,649
1,750
1,031
30 mm (1.2 in.)
2,300
1,355
1,000
589
Refrigerant Charge
High Side
Low Side
High Side
Low Side
High Side
Low Side
19
Specifications
Refrigerant Charge
Evacuated System
Add Partial Charge by Pressure
20 C / 68 F
38 C / 100 F
High Side
Low Side
High Side
Low Side
Cutin
Reset
Cutin
*When the compressor is removed from the unit, oil level should be noted or the oil removed from the compressor should be
measured so that the same amount of oil can be maintained in the replacement compressor.
**Do not use or add standard synthetic or mineral oils to the refrigeration system. If Ester based oil becomes contaminated with
moisture or with standard oils, dispose of properly Do not use!
20
Specifications
Electrical System
R-134a Circuit Compressor Motor:
Type
Semi-hermetic Reciprocating
Voltage
5.60 kW
7.5 hp
1750 rpm
Hermetic Scroll
Voltage
4.48 kW
6.0 hp
3550 rpm
11 amps 460V
70 amps 460V
460/380V, 60/50 Hz
1.5 kW
2.0 hp
749 Watts
1725 rpm
1.25 amps
25 amps 460V
35.7 amps
0.75 hp
1725 rpm
Number
0.75 kW
1.0 hp
Number
12
680 Watts
54 3 C (130 5 F)
Closes
38 4C (100 8 F)
*CRR DF applications operates the two-speed evaporator fan motors continuously on low speed. Evaporator fans stop during
defrost.
21
Specifications
Microprocessor Controller
Temperature Controller:
CRR-40 DF MPC2000
MPC2000 microprocessor
CRR-40 DF MPC2000ID
MPC2000ID microprocessor
CRR-40 DF MP3000
MP3000 microprocessor
Description
Setpoint Range
Defrost Initiation:
Coil must be below 18 C (65 F) to initiate defrost by
demand, timer or manual switch.
- Manual Switch or Demand Defrost Initiation: Defrost
cycle starts when technician or controller request defrost
initiation.
Evaporator Coil Sensor Coil
Demand Defrost
Defrost Termination:
Evaporator Coil Sensor
Interval Timer
Time/Temperature Function
Power Off
22
Specifications
Physical Specifications
Base Unit Weight (net):
CRR-40 DF MPC2000
CRR-40 DF MPC2000ID
CRR-40 DF MP3000
Unit Dimensions
Width
Height
Depth
N.m
In.-lb.
Grade 5
45.2
400
Grade 8
59.3
525
Bottom Plate:
Housing Cover
45.2
400
33.9
300
33.9
300
Grade 5
45.2
400
Grade 8
59.3
525
Cylinder Head
59.3
525
31.1
275
45.2
400
18 (5/16 in.)
25.4
225
13 (1/2 in.)
56.5
500
33.9
300
22.6
200
Grade 5
4.5
40
Grade 8
8.5
75
Stator Cover:
Pipe Plug:
Terminal Plate
33.9
300
5.1
45
9.0
80
23
Specifications
Bolt Size
M6
M8
M10
M12
N.m (Ft.-lb.)
N.m (Ft.-lb.)
N.m (Ft.-lb.)
N.m (Ft.-lb.)
HH CL 5.8
6-9 (4-7)
12-16 (9-12)
27-34 (20-25)
48-61 (35-40)
HH CL 8.8
10-13 (7-10)
20-27 (15-20)
41-47 (30-35)
75-88 (55-65)
HH CL 10.9
14-17 (10-13)
27-34 (20-25)
54-68 (40-50)
102-122 (75-90)
HH CL 12.9
17-21 (12-16)
41-47 (30-35)
68-81 (50-60)
122-149 (90-110)
HH SS (2)
10-13 (7-10)
20-27 (15-20)
41-47 (30-35)
75-88 (55-65)
Bolt Size
M14
M16
M18
M22
N.m (Ft.-lb.)
N.m (Ft.-lb.)
N.m (Ft.-lb.)
N.m (Ft.-lb.)
HH CL 5.8
75-88 (55-65)
115-135 (85-100)
177-216 (130-160)
339-406 (250-300)
HH CL 8.8
115-135 (85-100)
177-216 (130-160)
271-339 (200-250)
475-610 (350-450)
HH CL 10.9
136-176 (100-130)
224-298 (180-220)
393-474 (290-350)
678-813 (500-600)
HH CL 12.9
177-216 (130-160)
285-352 (210-260)
448-542 (330-400)
881-1016 (650-750)
115-135 (85-100)
177-216 (130-160)
271-339 (200-250)
475-610 (350-450)
HH SS (2)
24
Unit Description
General Description
Model CRR DF units are all-electric, single-piece,
refrigeration units with bottom air supply. Each
unit is designed for long distance, shipboard or
overland transport of deep frozen or frozen
cargoes. Each unit mounts in the front wall of the
container. Fork lift pockets are provided for
installation and removal of the unit.
The frame and bulkhead panels are constructed of
aluminum and are treated to resist corrosion. A
hinged, removable vaporator compartment door
provides easy service access. All operating
components except the evaporator coil and buffer
receiver tanks can be replaced from the front of
the unit.
The unit is equipped with an 18.3 m (60 ft) power
cable for operation on 460-380V/3 Ph/60-50 Hz
power. For operation on 460-380V/3 Ph/60-50 Hz
power, plug the 460-380Vpower cable into the
proper power supply.
Each unit is equipped with 460-380V/3 Ph/60-50
Hz electric motors. An automatic phase correction
system provides the proper electrical phase
sequence for condenser fan and evaporator fan
motor operation. Unit power cable is stored below
the control box in the condenser section.
CRR DF MPC2000 units feature MPC2000
microprocessor controller and a MPC2000
Datalogger. CRR DF MP3000 units feature
MP3000 microprocessor controller and a MP3000
Datalogger. CRR DFMPC2000ID units feature a
MPC2000ID microprocessor controller with
integral datalogger. Additional features include
three evaporator fans; USDA Cold Treatment
Temperature Recording; and a Remote
Monitoring Modem (RMM). For additional unit
feature information, see CRR DF Model
Features on page v of the Introduction.
Microprocessor Controller
MPC2000, MPC2000ID and MP3000 controllers
incorporate refrigeration system component
control, thermostat, digital thermometer and fault
indication capabilities into one self-contained
package. Units with a MPC2000 or MP3000
controller are also equipped with a separate
datalogger while the MPC2000ID controller
includes an integral datalogger.
25
Unit Description
Datalogger
Units with a MPC2000 or MP3000 controller are
also equipped with a separate datalogger. The
MPC2000ID controller includes an integral
datalogger. The datalogger can record sensor
temperatures as well as loss of power, alarms, unit
operating modes, sensor failure, setpoint change
and unit shutdown indications. MPC2000 or
MP3000 data recordings are stored in a RAM
memory that is backed by battery. MPC2000ID
data recording are stored in a permanent Flash
RAM memory.
Logging intervals are selectable from 1 minute
and 1/2, 1, 2 or 4 hours. When a 1 hour logging
interval is selected, the datalogger memory can
store approximately 512 days of information. The
logging of USDA sensors is fixed at 1 hour
intervals to comply with USDA requirements.
26
Operating Modes
NOTE: See Microprocessor Controller chapter
for complete sequence of operation.
A sequence start of the required loads occurs
during initial start-up of the unit and when a
control mode shift requires the compressors to
start. As the controller relays and unit loads
energize, the controller LCD display shows the
setpoint temperature. The controller LED display
shows the controlling (return) air sensor
temperature.
Unit Description
Frozen Loads
Temperature control by the controller is based on
the return air sensor temperature. The evaporator
fans operate continuously on low speed (except
during defrost).
27
Unit Description
3
4
7
6
AXA0346
1.
6.
2.
7.
3.
Condenser Fan
8.
Control Box
4.
9.
5.
28
Unit Description
AXA0347
1.
4.
2.
5.
3.
Evaporator Coil
Figure 3: Evaporator Section Front View
29
Unit Description
AXA0346
1
2
AXA0421
AXA0348
1.
2.
30
Unit Description
AXA0349
1.
Control Box
4.
2.
5.
3.
31
Unit Description
AXA0422
6
7
8
AXA0351
1.
5.
2.
6.
7.
3.
8.
Circuit Breaker
4.
32
Unit Description
5
6
10
7
8
11
12
13
9
AXA0419
14
15
16
17
AXA0353
1.
10.
2.
11.
Heat Relay
3.
12.
4.
13.
5.
14.
6.
15.
7.
16.
8.
17.
9.
MPC2000 Datalogger
Figure 7: MPC2000 or MP3000 Controller and Remote Monitoring Modem
33
Unit Description
1
2
3
9
5
10
11
12
13
14
AXA0354
15
16
AXA0353
1.
9.
2.
3.
11.
4.
5.
6.
7.
8.
34
Unit Description
4
5
AXA0355
1.
5.
2.
6.
3.
7.
4.
8.
12 Vdc Battery
35
Unit Description
2
3
AXA0357
AXA0423
1.
2.
3.
Figure 10: Low Pressure Cutout Switch in R-23 Refrigeration System (CRR DF MPC2000ID Units Only)
36
Unit Description
2
12
11
3
10
9
8
7
5
6
AXA0423
1.
7.
2.
8.
3.
9.
4.
10.
5.
11.
6.
12.
37
Unit Description
AXA0359
3
4
5
AXA0423
AXA0424
1.
4.
Receiver Tank
2.
5.
3.
6.
38
Unit Description
2
10
3
9
4
8
5
AXA0425
1.
6.
2.
7.
3.
8.
4.
9.
5.
R-134a Compressor
10.
39
Unit Description
AXA0363
1.
5.
2.
6.
3.
7.
4.
8.
Figure 14: Additional R-134a Refrigeration System Components and Plate Heat Exchanger
40
Unit Description
1
2
9
5
AXA0364
AXA0365
1.
Evaporator Grille
6.
2.
Unit Gasket
7.
3.
8.
4.
9.
5.
41
Unit Description
AXA0366
AXA0367
4
1
AXA0368
1.
3.
2.
4.
Figure 16: Unit Back View Pressure Regulators and Buffer Tanks
42
Unit Description
AXA0369
AXA0370
AXA0368
1.
Electric Heaters
2.
3.
Figure 17: Unit Back View Electric Heaters and Evaporator Coil
43
Unit Description
44
Operating Instructions
Basic Unit Controls,
Instruments and Protection
Devices
Unit Control Box
ON/OFF Switch: ON position. Unit will operate on
cool or null depending on the controller setpoint
temperature and the container air temperature.
OFF position. The unit will not operate.
Control System Circuit Breaker: A 7 ampere
manual reset circuit breaker protects the control
circuit. This circuit breaker is located in the
control box beside the On/Off switch.
Main Circuit Breaker: A 32 ampere manual reset
circuit breaker protects the 460/380V power
supply circuit to the unit electric motors and
control system transformer. The main power
circuit breaker is located in the control box.
Fuses: A number of fuses are located on the main
the On/Off
switch is turned ON, phase sensors on the main
relay board determine the incoming power phase
to ensure proper condenser fan, evaporator fan
and compressor rotation.
to change the
setpoint. Cursor in the LCD display automatically
appears in the TEMP SETP line of the Data
menu. See Changing the Setpoint in the
Microprocessor Controller chapter for complete
instructions.
display signal:
Defrost
In-Range (Temperature)
Alarm
45
Operating Instructions
LCD Display: A
Other
discharge pressure
gauge indicates the refrigerant pressure in the
discharge line leaving the compressor.
the
compressor discharge pressure rises above 2410
68 kPa, 24.1 0.68 bar, 350 10 psig, the high
pressure cutout opens to interrupt the ground
circuit to the compressor contactor:
46
fusible
plug is installed in the R-134a receiver tank to
avoid excessive pressure build-up within the
refrigeration system from extraordinary and
unforeseen circumstances. The plug blows when
the plug temperature reaches 100 C (212 F). The
plug is located so that refrigerant pressure
expelled from the valve would be directed away
from anyone servicing the unit. The plug is
non-repairable and requires no adjustment. If the
plug blows, recover the remaining refrigerant
charge and replace the fusible plug.
compressor oil
sight glass indicates the relative level of
compressor oil in the compressor sump.
Operating Instructions
High Pressure Cutout (HPCO) Switch: If
the
compressor discharge pressure rises above 3250
50 kPa, 32.5 0.5 bar, 470 7 psig, the high
pressure cutout opens to interrupt the ground
circuit to the compressor contactor:
suction pressure
gauge indicates the refrigerant pressure in the
suction line returning to the compressor.
Discharge Pressure Gauge: A
discharge pressure
gauge indicates the refrigerant pressure in the
discharge line leaving the compressor.
Receiver Tank Sight Glass: Two
sight glasses on
the R-23 receiver tank contains three small balls
that indicate the level of refrigerant in the tank for
checking the refrigerant charge. A moisture
indicator in the sight glass changes color to
indicate the level of moisture in the system. Check
the color of the indicator against the color decal in
the sight glass. The dry eye in the sight glass is
LIGHT GREEN when the system is dry and
YELLOW when the system is wet (contains
excessive moisture).
compressor oil
sight glass indicates the relative level of
compressor oil in the compressor sump.
High Pressure Relief Valve: A
Pretrip Inspection
The following inspections should be made before
the container is loaded:
1. Visually check the unit for physical damage.
2. Check the electrical connections in the unit
control box, making sure they are fastened
securely.
3. Check the conditions of wires and terminals.
Repair or replace if necessary.
47
Operating Instructions
Pre-load Operation
Pre-Trip Conditions
To properly perform a Full Pretrip Test on units
equipped with the MPC2000 or MPC2000ID
controller, the following conditions must exist:
Pre-Trip Checks
1. With unit connected to the proper power
supply, turn the power supply On/Off switch
to ON.
2. Switch refrigeration unit On/Off switch to ON
position. A sequence start of the required
loads occurs during initial start-up on cooling:
Power Selection
CAUTION: Power supply connections
from the unit to the power source should
always be made with the refrigeration unit
On/Off switch and the power supply
On/Off switch in the OFF position. Never
attempt to start or stop the refrigeration
unit using the power cord.
The refrigeration unit is designed to operate on
460/380V, 3 Phase, 60-50 Hz electric power from
a 4-wire power source.
48
Operating Instructions
Loading Procedure
1. Make sure the Unit On/Off switch is OFF
before opening the container doors. (The unit
may be operating when loading the container
from a warehouse with door seals.)
2. Spot check and record load temperature while
loading. Especially note any off-temperature
product.
49
Operating Instructions
50
Microprocessor Controller
General Description
Defrost
In-Range (Temperature)
Alarm
1.
2.
3.
4.
51
Microprocessor Controller
Alarm
Code
Type
Description
00
Check
01
Check
02
Check
03
Check
04
Check
05
Check
06
Check
07
Check
10
Check
11
Check
14
Check
15
Check
16
Check
17
Check
18
Log
19
Check
20
Check
22
Check
23
Check
32
Check
33
Check
34
Check
35
Check
43
Check
52
Check
Probe Error
56
Shutdo
wn
58
Check
59
Check
97
Log
98
Log
112
Check
52
Microprocessor Controller
53
Microprocessor Controller
54
Microprocessor Controller
Compressor operation
Electric heaters
Phase selection
Sequence Of Operation
Ambient sensor
Unit Start-up
A 60 second sequence start of the required loads
occurs during initial start-up of the controller. If
cooling is required, the unit operates in the cool
mode until the controlling sensor reaches 1.0 C
(1.8 F) below setpoint.
55
Microprocessor Controller
Cool mode
Null mode
Defrost mode
Cool
A.
B.
C.
In-Range
1.
Decrease Temperature
2.
Setpoint
3.
Increasing Temperature
Figure 19: Frozen Load Control Sequence
(Setpoints at -10 C [14 F] and Below)
56
Null
Microprocessor Controller
Defrost
During the Cool or Null modes, the controller
initiates the Defrost mode when the evaporator
coil sensor temperature is below 18 C (65 F) and:
Microprocessor Controller
Initiating a Manual
Defrost
With the unit On/Off switch ON:
1. Press the DEFROST key.
Displaying Alternate
Controlling (Supply or
Return) Air Sensor
Temperature
The controller can show either the supply or
return air temperature in the LED Display. With
the unit On/Off switch ON and the controller
showing the standard LED Display:
58
Displaying Alternate
Fahrenheit (F) or Celsius
(C) Temperature
The controller can display temperatures in
Fahrenheit or Celsius. With the unit On/Off
switch ON and the controller showing a standard
LED Display:
1. Press and hold the C/F key. The controller will
show the LED display temperature in the
alternate temperature scale (Fahrenheit or
Celsius) from the temperatures shown on the
display as long as the C/F key is depressed.
2. The display then returns to the original display
when the C/F key is released.
NOTE: To change the default temperature scale
display, see Changing the Temperature Display
Value (C/F) under MISC. FUNCTIONS in the
Menu Operating Instructions section in this
chapter.
Microprocessor Controller
Controller Menu
Navigating the Controller Menu:
The controller Main Menu is divided into seven
major menus:
Data
Alarm List
Commands
Misc. Functions
Configuration
Datalogger
Data Menu
NOTE: Information can ONLY be displayed
using the Data menu. Items can NOT be
changed.
The Data menu displays general unit operating
information including sensor temperatures, unit
electrical data, etc.
Viewing the Data menu:
With the unit On/Off switch ON and the LCD
display showing the standard display (setpoint):
1. Press F4 key for directly enter the Data menu.
Menu items appear in LCD display.
Setpoint Temperature
Ambient Temperature
Battery Voltage
Zero Current
59
Microprocessor Controller
flashes until
alarm is acknowledged. Check alarms indicate
corrective action should be taken before a
problem becomes severe. Alarm codes 00-17, 18,
19, 20, 22, 23, 34, 35, 43, 52, 58, 112 are Check
alarms.
is recorded in
datalogger only (inspect event log). Alarm LED
does not flash or turn on. Alarm codes 59, 97, 98
are Log alarms.
Alarm Code States
There are three alarm code states for Shutdown
and Check alarms:
60
Commands Menu
The Commands menu displays a list of tasks that
can be activated. The following commands are
available:
Microprocessor Controller
Condenser Fan:
Compressor:
Evaporator Fan:
R-23 Compressor
Sensor Check.
Heat:
Sensor Check:
Defrost
PTI (Pretrip)
c. Component Test:
61
Microprocessor Controller
Condenser Fan:
Compressor:
Evaporator Fan:
R23 Compressor:
Sensor Check.
Heat:
Sensor Check:
62
Date Time
C/F Mode
Cargo Data
Program Version
Run Time
Microprocessor Controller
CONTENTS
VOYAGE
SHIP
COMMENTS
63
Microprocessor Controller
64
R-134a COMPRESSOR
EVAPORATOR LOW
CONDENSER
TOTAL
Microprocessor Controller
Configuration Menu
The Configuration menu displays a list of
functions that identifies unit operating features
and current settings. The following functions are
available:
Description
Default
Range
In range limit
1,5C
0,5C - 5C
Container Id
LOSUxxxxxxx
Must be valid
CONTRAST
45
0 - 255
LANGUAGE
GB
GB
ZERO CURR
On
On/Off
USDA TYPE
3 PT100
Not Present
On
On/Off
---------
9x any char
IN RANGE
CONT ID
CHART R.
AUTO CONFIG
UNIT #
65
Microprocessor Controller
Datalogger Menu
The Datalogger menu contains a list of functions
that display unit operating information recorded in
the MPC2000 Datalogger or MPC2000ID Integral
Datalogger. The following functions are available:
1 Minute
1/2 Hour
1 Hour
2 Hour
4 Hour
66
Microprocessor Controller
LCD Display
(Shows Approx. Amps for
460V, 60 Hz Unit)
Test Description
Possible
Alarms
Duration
(Time)
P1.00
Display Test
Activated
0.1 A 0.0 A 0.1 A
None
10 Seconds
P1.01
Sensor Test
Activated
0.1 A 0.0 A 0.1 A
10 Seconds
67
Microprocessor Controller
P1.02
LCD Display
(Shows Approx. Amps for
460V, 60 Hz Unit)
Test Description
Heat Test
Activated
10.4 A 10.3 A 10.4 A
Possible
Alarms
Duration
(Time)
10, 11
10 Seconds
20
1 Hour
Maximum
12, 13
10 Seconds
52
60 to 600
Seconds
P1.03
P1.04
Defrost
Activated
10.4 A 10.3 A 10.4 A
P1.05
Probe Test
Activated
1.6 A 1.5 A 1.6 A
P1.06
Condenser Fan
Activated
2.2 A 2.1 A 2.2 A
16, 17
10 Seconds
Reverse Phase
Activated
2.2 A 2.1 A 2.2 A
58
30 Seconds
06, 07
14 Seconds
22
4 Hours
Maximum
P1.07
P1.08
Compressor Test
Activated
9.2 A 9.1 A 9.2 A
Return
Temp.
68
PTI Running
Setpoint: -30 C (-22 F)
Microprocessor Controller
LCD Display
(Shows Approx. Amps for
460V, 60 Hz Unit)
Test Description
PTI Running
Defrost activated:
-55 C (-67 F)
Return
Temp.
Possible
Alarms
Duration
(Time)
20
90 Minutes
Maximum
23
6 Hours
Maximum
None
PTI Running
Setpoint: -55 C (-67 F)
Return
Temp.
PTI PASS:
Press (Any) Key
Temperature Sensors
Thermistor type temperature sensors are used.
Each sensor is connected to a cable and placed in
a sealed stainless steel tube. The temperature
signal from the sensor is transmitted through the
cable. Temperature sensors include:
Supply Air
Return Air
Evaporator Coil
Ambient Air
69
Microprocessor Controller
36
60752
222.8
106
4623
100.4
38
55668
226.4
108
4348
104
40
51058
230
110
4092
107.6
42
46873
233.6
112
3854
111.2
44
43071
237.2
114
3631
114.8
46
39613
240.8
116
3423
118.4
48
36465
244.4
118
3229
122
50
33598
248
120
3047
125.6
52
30983
251.6
122
2877
AXA0171
A.
129.2
54
28595
255.5
124
2718
B.
Unit front.
132.8
56
26413
258.8
126
2569
C.
136.4
58
24419
262.4
128
2430
140
60
22593
266
130
2299
143.6
62
20921
269.6
132
2176
147.2
64
19388
273.2
134
2118
150.8
66
17961
276.8
136
1953
154.4
68
16689
280.4
138
1852
OHMS
Temp. Temp.
F
C
OHMS
32
351017
158
70
15502
35.6
315288
161.6
72
14410
39.2
283558
165.2
74
13405
42.8
255337
168.8
76
12479
46.4
230210
172.4
78
11625
50
10
207807
176
80
10837
53.6
12
187803
179.6
82
10110
57.2
14
169924
183.2
84
9438
60.8
16
153923
186.8
86
8817
64.4
18
139588
190.4
88
8242
68
20
126729
194
90
7710
71.6
22
115179
197.6
92
7216
75.2
24
104796
201.2
94
6759
78.8
26
95449
204.8
96
6335
82.4
28
87023
208.4
98
5941
86
30
79428
212
100
5574
89.6
32
72567
215.6
102
5234
93.2
34
66365
219.2
104
4917
70
Temp.
F
Temp.
C
OHMS
-40
-40
21309
53.6
12
1680
-31
-35
16099
57.2
14
1547
-22
-30
12266
60.8
16
1426
-13
-25
9425
64.4
18
1316
-4
-20
7309
68
20
1215
-15
5691
71.6
22
1173
10.4
-12
4919
75.2
24
1040
14
-10
4470
78.8
26
962
17.6
-8
4066
82.4
28
893
21.2
-6
3703
86
30
828
24.8
-4
3376
89.6
32
770
28.4
-2
3082
93.2
34
715
32
2817
96.8
36
665
35.6
2577
100.4
38
619
39.2
2360
104
40
577
Microprocessor Controller
2165
107.6
42
538
46.4
1953
111.2
44
502
50
10
1826
113
45
485
Temp. OHMS
C
Temp.
F
Temp. OHMS
C
-40
-40
42618
53.6
12
3360
-31
-35
32198
57.2
14
3094
-22
-30
24532
60.8
16
2852
-13
-25
18850
64.4
18
2632
-4
-20
14618
68
20
2431
-15
11383
71.6
22
2347
10.4
-12
9838
75.2
24
2079
14
-10
8941
78.8
26
1925
17.6
-8
8132
82.4
28
1785
21.2
-6
7406
86
30
1657
24.8
-4
6752
89.6
32
1539
28.4
-2
6164
93.2
34
1430
32
5634
96.8
36
1330
35.6
5155
100.4
38
1239
39.2
4721
104
40
1154
42.8
4329
107.6
42
1076
46.4
3907
111.2
44
1004
50
10
3652
113
45
970
Microprocessor Controller
72
Microprocessor Controller
73
Microprocessor Controller
Error Message
Controller Action
Indicates:
Indicates:
15
74
Microprocessor Controller
Description
Corrective Action
Indicates:
Open circuit to sensor
Defective or wrong sensor
Defective relay board
Defective cable No. 1
Defective controller
02
Indicates:
Open circuit to sensor
Defective or wrong sensor
Defective relay board
Defective controller
75
Microprocessor Controller
Code
03
Description
Corrective Action
Indicates:
Open circuit to sensor
Defective or wrong sensor
Defective relay board
Defective cable No. 1
Defective controller
04
Indicates:
Open circuit to sensor
Defective or wrong sensor
Defective relay board
Defective cable No. 1
Defective controller
06*
76
Microprocessor Controller
Code
07*
Description
Corrective Action
10*
Indicates:
*If both alarms 10 and 11 are activated, the alarms are caused by a large difference in measured amps. Start Manual
Function Test and energize the heaters. Check the heater amps measurement. If necessary, isolate and check the resistance
of each individual heater element.
77
Microprocessor Controller
Code
14*
Description
Corrective Action
Indicates:
Indicates:
78
Microprocessor Controller
Code
16*
Description
Corrective Action
Condenser fan power consumption is lower than Check power supply volts and amps.
approximately 0.7 amps, depending on voltage).
Indicates:
Defective condenser fan motor relay
Defective or open fan motor internal over
temperature protection switch
Defective volt or amp meter on relay board
18
Indicates:
*If both alarms 16 and 17 are activated, the alarms are caused by a large difference in measured amps. Start Manual
Function Test and start the condenser fan. Check the condenser fan amps measurement. If necessary, check the resistance
in the motor between L1 and L2, L2 and L3, and L1 and L3. Resistance readings should be equal (approximately 10 Ohms).
79
Microprocessor Controller
Code
19
Description
Corrective Action
20
22
80
Microprocessor Controller
Code
34
Description
Corrective Action
Indicates:
Open circuit to sensor
Defective or wrong sensor
Defective relay board
Defective cable No. 1
Defective controller
35
Indicates:
Short circuit to sensor
Defective or wrong sensor
Defective relay board
Defective cable No. 1
Defective controller
43
Indicates:
Defective return air or evaporator coil sensor
Return air and evaporator coil sensor
connections are reversed
52
Probe Error
(Check Alarm)
Occurs during Pretrip (PTI) test only.
Temperature difference between supply air,
return air or evaporator coil sensor is too high (3
C maximum)
Indicates:
Indication error on one of the sensors
Supply air sensor not placed in airflow stream
81
Microprocessor Controller
Code
56
Description
Corrective Action
Indicates:
Defective relay board
Defective relay board cable No. 2
Defective phase relay
59
Indicates:
Open connection on one phase of power
supply to a 3-phase unit component including
R-134a compressor or R-23 compressor.
97
Indicates:
Open circuit to sensor
Defective or wrong sensor
Defective relay board
Defective cable No. 1
Defective controller
82
Microprocessor Controller
Code
98
Description
Corrective Action
Indicates:
Short circuit to sensor
Defective or wrong sensor
Defective relay board
Defective cable No. 1
Defective controller
112
Indicates:
Defective motor or heater insulation to ground
83
Microprocessor Controller
84
Electrical Maintenance
Unit Wiring
Condenser Fan
Check for proper condenser fan rotation by
placing a small cloth or sheet of paper against the
condenser fan grille on the front of the unit.
Proper rotation will blow the cloth or paper away
from the grille. Improper rotation will hold the
cloth or paper against the grille.
If the condenser fan is rotating backwards, refer to
the unit wiring diagram to correct fan motor
wiring at the fan motor junction box or condenser
fan contactor. To correct improper fan rotation,
reverse any two fan power cord leads at the
condenser fan contactor (disconnect power supply
before reversing leads). DO NOT move the CH
ground wire.
Evaporator Fans
Visually inspect the evaporator fan blades for
proper rotation. Arrows located on the underside
of the fan deck indicate the correct direction of
rotation.
If an evaporator fans rotate backwards, refer to the
unit wiring diagram to correct motor wiring at the
fan motor junction box or evaporator fan
85
Electrical Maintenance
Electric Heaters
86
Service Tools
CAUTION: R-134a and R-23 are HFC
(Hydrofluoro-carbon) refrigerants. When
servicing the CRR DF refrigeration
systems, use only those service tools (i.e.,
vacuum pump, refrigerant recovery
equipment, gauge hoses, and gauge
manifold set) certified for and dedicated to
HFC refrigerants and Polyol Ester based
compressor oils. Residual non-HFC
refrigerants or non-Ester based oils will
contaminate HFC systems. Separate
service tools should be dedicated to
R-134a and R-23 refrigerant systems.
Leak Detection
1.
2.
3.
Vacuum Pump
A two-stage (P/N 204-725), three-stage or
five-stage pump is recommended for evacuation.
Purging the system with dry nitrogen is
recommended before evacuation. Because
residual refrigerant may be present in used
vacuum pumps, a new vacuum pump should be
87
System Cleanup
Cleanup devices such as suction line filters and
compressor oil filters may be used if they are
properly cleaned and new filters and cartridges are
used. All standard petroleum and synthetic
compressor oils must be removed to prevent the
contamination of R-134a or R-23 refrigeration
systems.
1.
Full Counterclockwise
Refrigerant Recovery
Use only refrigerant recovery equipment
approved for and dedicated to HFC refrigeration
recovery.
1.
1/2 Turn In
88
1.
Full Clockwise
1.
1.
2.
3.
1.
1.
2.
3.
1.
2.
In
3.
4.
Out
5.
6.
89
90
AMA295
A.
B.
Reclaimer
B.
Procedure
Repair/Service Action
Reclaim
Refrigerant
Reclaim
Refrigerant
Reciprocating Compressor
(R-134a Refrigeration System)
Procedure
Repair/Service Action
Reclaim
Refrigerant
Low Side
Pump Down
91
Ambient
Temp.
0 to 38 C
Standby
(Unit OFF, (32 to 100 F)
Empty box)
Suction
Pressure
Suction
Pressure
Discharge
Pressure
1600 kPa
16.0 bar
232 psig
1600 kPa
16.0 bar
232 psig
1700 kPa
17.0 bar
247 psig
1700 kPa
17.0 bar
247 psig
1800 kPa
18.0 bar
261 psig
0 C (32 F)
20 C (68 F)
Cooling:
-30 C
(-22 F)
Cooling:
-60 C
(-76 F)
250 - 280
kPa
2.5-2.8 bar
36 - 41 psig
900 - 1100
kPa
.9 - 1.1 bar
13 - 16 psig
92
Cooling:
-30 C
(-22 F)
27 to 38 C
60-90 kPa
(80 to 100 F) 0.6-0.9 bar
9-13 psig
1500-1800
kPa
15.0-18.0
bar
218-261
psig
Cooling:
-60 C
(-76 F)
27 to 38 C
20-50 kPa
(80 to 100 F) 0.2-0.5 bar
3-7 psig
1380-1500
kPa
13.80-15.0
bar
200-218
psig
Discharge
Pressure
= Inches of Hg Vacuum
1
2
3
4
5
6
7
8
1.
Protective cap
2.
Adjustment
3.
Spring
4.
Bellows
5.
Inlet
6.
7.
Seat
8.
Outlet
1.
93
1.
94
95
1.
1.
96
20 C (68 F)
38 C (100 F)
O C (32 F)
Refrigerant Recovery
CAUTION: Use only refrigerant recovery
equipment approved for and dedicated to
HFC refrigerants.
When removing any refrigerant from a Thermo
King refrigeration system, use a recovery process
that prevents or absolutely minimizes the
refrigerant that can escape to the atmosphere.
Typical service procedures that require removal of
refrigerant from the unit include:
97
Contamination
98
Unit Evacuation
1. Turn on the Vacuum Pump. Open the Gas
Ballast Valve located on top of the pump
housing behind the handle (the valve is fully
open at two turns counterclockwise). Evacuate
the system to 500 microns to achieve a final
equilibrium pressure of 2000 microns or less.
The final equilibrium pressure is determined
with the Thermo King Evacuation Station
using the following procedure (called a
pressure-rise test):
99
100
System size
Ambient temperature
1.
2.
Time
3.
Pressure (Vacuum)
4.
Atmospheric Pressure
Figure 40: Pressure Rise Levels Off After
Evacuation Indicates Moisture in System
1.
2.
Time
3.
Pressure (Vacuum)
4.
Atmospheric Pressure
Figure 39: Constant Pressure Rise After
Evacuation Indicates System Leak
101
102
103
104
O C (32 F)
20 C (68 F)
38 C (100 F)
Safety Precautions
Observe the proper handling of cylinders:
1. Always keep protective cap on cylinder when
not in use.
2. Secure cylinder in proper storage area or
fastened to cart.
3. DO NOT expose to excessive heat or direct
sun light.
4. DO NOT drop, dent, or damage cylinder.
5. Use a pressure regulator and a safety pressure
relief valve as part of the pressure testing
equipment. The safety pressure relief valve
should be of the non-adjustable,
non-tempering type. The valve should bypass
any time the pressure exceeds its setting.
6. Open valve slowly; use regulators and safety
valves that are in good working order.
7. The regulator should have two gauges; one to
read tank pressure, the other to read line
pressure. Properly maintained equipment will
allow leak testing, purging, or dehydration to
be done safely.
CAUTION: Nitrogen (N2) is under 15,170
kPa, 151.70 bar, 2200 psig, or greater.
Pressure is for full cylinder at 21 C (70 F).
DO NOT use Oxygen (O2), acetylene or
any other types of pressurized gas on
refrigeration systems or any component of
a system.
105
1.
Line Pressure
2.
Tank Pressure
3.
Tank
4.
5.
Safety Valve
6.
Pressure Regulator
106
Compressor Replacement
(R-134a or R-23 Systems)
Removal
1. Close the suction service valve and pump
down the compressor:
Installation
107
Installation
1. Clean the tubes for soldering.
2. Slide the coil into the unit and install the bolts
in the mounting brackets.
108
Installation
1. Remove the sealing caps from the new
dehydrator.
2. Do one of the following:
R-134a System:
R-23 System:
Installation
1. Clean the liquid lines and equalizer lines for
soldering.
2. Place new expansion valve in position in
liquid line.
3. Solder liquid line inlet and outlet line
connections to valve.
4. Solder equalizer line to expansion valve.
109
R-134a System:
R-23 System:
Installation
1. Clean the tubes for soldering.
2. Place the heat exchanger assembly in the unit
and install the mounting hardware.
3. Solder the suction line connections.
110
Installation
1. Clean the tubes for soldering.
Installation
111
Installation
1. Apply a refrigeration locktite (sealant) to the
threads of the switch (or sensor).
2. Install and tighten the switch (or sensor).
Connect the leads to the wire harness.
3. Open discharge service valve slightly to
pressurize the compressor head and tube
assembly. Check for leaks (see Refrigerant
Leak Test Procedure in this chapter). Front
seat the discharge service valve.
4. If no leaks are found, recover the leak test gas
(see Refrigerant Recovery in this chapter).
5. Open the suction service valve and
compressor discharge service valve and place
the unit in operation.
Installation
1. Clean the tubes for soldering.
2. Place the new valve in position and solder the
connections.
112
Installation
CAUTION: Use a heat sink or wrap the
valve with wet rags to prevent damage to
the new valve.
3. Release a small amount of refrigerant from the
receiver tank to pressurize the liquid line.
Check for leaks (see Refrigerant Leak Test
Procedure in the Refrigeration Maintenance
chapter of this manual).
4. If no leaks are found, recover the leak test gas
(see Refrigerant Recovery in the
Refrigeration Maintenance chapter of this
manual).
113
114
Structural/Accessory Maintenance
Mounting Bolts
Check and tighten all unit, compressor, and fan
motor mounting bolts during pretrip inspections
and every 1,000 operating hours. Unit mounting
bolts should be tightened to a torque value of 204
N.m (150 ft-lb). Compressor and fan motor
mounting bolts should be tightened to a torque
value of 20 to 21 N.m (15 to 20 ft-lb).
Unit Inspection
Inspect the unit during unit pretrip inspection and
every 1,000 operating hours for loose or broken
wires or hardware, compressor oil leaks, or other
physical damage which can affect unit
performance and require repair or replacement of
parts.
Evaporator Coil
2
AXA0346
1.
Defrost Drains
2.
Condenser Coil
Clean the condenser coil by blowing low pressure
compressed air or a medium pressure warm water
spray from the inside of the coil outward (opposite
direction of normal airflow). Inspect coil and fins
for damage and repair if necessary.
115
Structural/Accessory Maintenance
AXA0421
AXA0426
1.
2.
AXA0404
1.
2.
Airflow Direction
3.
Evaporator Coil
4.
Evaporator Motor
5.
13 mm (0.5 in.)
Vacuum Valve
The vacuum valve draws outside air into the
container to prevent the container from
developing negative atmospheric pressure as the
cargo temperature decreases toward -60 C (-76 F).
Check the vacuum valve during the pretrip
inspection to make sure the ball inside the valve
moves freely.
AXA0196
1.
Airflow Direction
2.
10 mm (0.4 in.)
3.
Condenser Coil
4.
5.
Condenser Motor
116
Mechanical Diagnosis
Condition
Possible Cause
Remedy
Wait at least 1 minute for both
compressors to start
Locate fault and repair: power source,
power plug, main circuit breaker, motor
contactor, motor terminals, motor
Unit on defrost
Replace compressor
Controller shut unit down on Compressor Let compressor cool and controller will
Over Temperature (fault code 56)
reset automatically. Check compressor
temperature sensor, R-134a refrigerant
charge, R-23 refrigerant charge
Compressor motor internal thermal
overload protection open
Replace compressor
Improperly wired
Open circuit in compressor motor winding Check motor stator connections. Check
stator winding for continuity. If open,
replace compressor
Defective compressor motor internal
thermal overload protector
R 23 compressor not running Auxiliary contact on R134a open
117
Mechanical Diagnosis
Condition
Possible Cause
Remedy
Compressor contactor
burned out
Short cycling
Noisy unit
Faulty compressor
Tighten connections
Defective motor
Replace motor
Unit on defrost
Tighten connections
Defective motor
Replace motor
No low speed evaporator fan output signal Diagnose and replace evaporator fan
from controller
relay, main relay board or controller
118
Possible Cause
Remedy
Shortage of refrigerant
Compressor inefficient
(R-134a compressor only)
119
Possible Cause
Remedy
See "Mechanical Diagnosis" and unit
wiring schematic
Shortage of refrigerant
(R-134a or R-23 system)
Overcharge of refrigerant
(R-134a or R-23 system)
Purge system
Air in system
(R-134a or R-23 system)
Clear restriction
Plugged dehydrator
(R-134a or R-23 system)
Change dehydrator
Compressor inefficient
(R-134a system only)
Shortage of refrigerant
No remedy
Replace gauge
Refrigerant overcharge
Purge system
No remedy
Refrigerant leak
Short cycling
120
Possible Cause
Remedy
Short cycling
Shortage of refrigerant
Repair or recharge
Liquid line service valve partially closed or Open valve or remove restriction
restricted
Restricted dehydrator
Replace dehydrator
Overcharge of refrigerant
Purge system
Shortage of refrigerant
No remedy
Restricted lines
Plugged dehydrator
Replace dehydrator
121
122
Dwg No.
Drawing Title
Rev.
Page
2C33056H01
125
2C33057H01
126
2C33059H01
127
5D52336
128
5D52338
129
5D52335
131
132
133
134
135
136
137
138
139
140
141
123
124
125
126
127
128
129
130
131
A. Evaporator Section
B. Condenser Section
41. Distributor
132
133
Legend for CRR DF Off Cycle Standby Flow and Pressure Diagram Page 1 of 2
R-134a Refrigeration Circuit Components
41. Distributor
Legend for CRR DF Off Cycle Standby Flow and Pressure Diagram
Unit Compartments
A. Evaporator Section
B. Condenser Section
Controller and Temperature Sensors
5. R-134a Compressor Discharge Line Temperature Sensor
29. R-23 Compressor Discharge Line Temperature Sensor
48. MPC2000 or MPC2000ID Controller
49. Return Air Sensor
50. Evaporator Coil Sensor
51. Supply Air Sensor
134
135
Legend for CRR DF Full Cool Flow and Pressure Diagram Page 1 of 2
Legend for CRR DF Full Cool Flow and Pressure Diagram
Unit Compartments
A. Evaporator Section
B. Condenser Section
41. Distributor
136
137
NOTE: Special, self-sealing quick disconnect couplers are required for R-134a systems
and R-23 systems.
41. Distributor
Unit Compartments
A. Evaporator Section
B. Condenser Section
138
139
140
RMM STATE
DATALOGGER
CONFIGURATION
MISC FUNCTIONS
COMMANDS
ALARMS
DATA
MAIN MENU
Display shows
current status:
Offline
Zombie
On-line
RMM Status
Datalogger Menu
Run Time
Program Version
Cargo Data
C/F Mode
Date Time
Misc. Functions
Menu
To acknowledge an alarm,
press F4 key with alarm code in
display.
Function Test
Defrost
Commands Menu
Datalogger
Submenu
Zero Current
Contrast
Container ID
In-Range
Configuration
Menu
Configuration
Submenu
Manual Function
Test Submenu
To Activate a Command
Misc Functions
Submenu
Current Phase 3
Current Phase 2
Zero Current
Current Phase 1
Frequency
Voltage 3
Voltage 1
Voltage 2
Alarms Menu
Voltage Average
Battery Voltage
Ambient Temp
Data Menu
Standard Display
141
RMM STATE
DATALOGGER
CONFIGURATION
MISC FUNCTIONS
COMMANDS
ALARMS
DATA
MAIN MENU
Display shows
current status:
Offline
Zombie
On-line
RMM Status
Datalogger Menu
Run Time
Program Version
Cargo Data
C/F Mode
Date Time
Misc. Functions
Menu
To acknowledge an alarm,
press F4 key with alarm code in
display.
Function Test
Defrost
Commands Menu
Configuration
Submenu
Manual Function
Test Submenu
To Activate a Command
Press F4 key.
Type the new setpoint.
Press and hold F4 key until
cursor stops flashing.
Enter a Temperature or
Humidity Setpoint
Datalogger
Submenu
Zero Current
Contrast
Container ID
In-Range
Configuration
Menu
Misc Functions
Submenu
Current Phase 3
Current Phase 2
Zero Current
Current Phase 1
Frequency
Voltage 3
Voltage 1
Voltage 2
Voltage Average
Battery Voltage
Ambient Temp
Data Menu
Setpoint Temperature
Setpoint Menu
Alarms Menu
Standard Display