Interlock & Protection Handbook
Interlock & Protection Handbook
INDEX
Sr.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Description
Interlock & Protection of Boiler
Interlock & Protection of ID fan system
Interlock & Protection of FD fan system
Interlock & Protection of APH system
Interlock & Protection of PA fan system
Interlock & Protection of Coal Pulveriser
Interlock & Protection of Coal Feeder
Interlock & Protection of Seal Air Fan
Interlock & Protection of Scanner Air Fan
Interlock of Boiler
Interlock & Protection of FSSS
Interlock test checklist of steam and water
system
Interlock test checklist of fuel oil system
Interlock & Protection of Turbine
Condensate Extraction Pump (CEP)
Circulating water system
Boiler Feed Pump Interlock & Protection
Vacuum system
Lube oil system & EH oil system
Deaerator,HPH & LPH system
Main steam and drainage system
Bypass system
Page
no.
3
4
7
9
13
15
21
22
23
24
25
28
30
37
38
40
42
45
46
47
50
53
2
23
Turbine
54
Boiler& Auxiliaries
Interlock & Protection
WPCL, Warora
Front or rear fan bearing temperature is very high, delay 2 sec (>90c).
Front or rear motor bearing temperature is very high, delay 2 sec (>105c).
Motor coil temperature is very high (<135c).
Corresponding side APH (both main motor & DC motor) stopped, delay 300 sec.
Accident button action.
Outlet damper closed and ID fan running, delay 5 sec.
Outlet flue gas damper has been closed when IDF startup, time delay 60 seconds.
Front bearing (x direction) vibration is very high, time delay 5 seconds (7.1mm/s).
4
Front bearing (y direction) vibration is very high, time delay 5 seconds (7.1mm/s).
Rear bearing (x direction) vibration is very high, time delay 5 seconds (7.1mm/s).
Rear bearing (y direction) vibration is very high, time delay 5 second (7.1mm/s).
Inlet oil pressure of coupler is very low, after IDF is running, time delay 10 seconds (<0.05MPa).
Inlet oil pressure of coupler is very low, when IDF startup, time delay 30 seconds (<0.035MPa).
Inlet oil temperature of coupler is very high, time 5s (>85c).
Outlet oil temperature of coupler is very high, time delay 5 seconds (>95c).
Bearing temperature of coupler is very high, time delay 5 seconds (>95c).
Furnace pressure is low-low (2of3), time delay 25 seconds (-1470Pa).
Furnace pressure is high-high (2of3), time delay 25 seconds (+1470Pa).
This side IDF trip and the other side IDF is running, close damper
All IDF and FDF have been stopped, open damper, time delay 5 minutes(from asking for free ventilation)
Protection
This side FDF tripped and the other FDF is running, close damper
This side FDF trip and the other side FDF is running, close damper
10
APH (main motor and AUX. motor) stopped and no asking for free
Ventilation, delay 300 second, close damper
11
APH (main motor and AUX .motor)stopped and no asking for free
Ventilation, time delay 300 seconds, close damper.
Sequence startup procedures
Outlet Oil pressure of working pump is low (<0.12MPa), start standby pump
Fault of working pump, start standby pump.
Outlet Oil pressure of two pumps operation is high (0.3MPa), stop working pump
Guide bearing temperature is
High (>55C), alarm, start working pump
Guide bearing temperature is
High (>70), alarm
Guide bearing temperature is
Low (<45), stop operating pump
Support bearing temperature is
High (>55), alarm, start pump
Support bearing temperature is
High (>70), alarm
Support bearing temperature is
Low (<45), stop pump
13
22
When two seal air fans is running, outlet main pipe pressure is normal, permit stopping any a fan.
All primary air fans stopped
MFT tripped
Interlock startup conditions
Main air fan stopped
Outlet manifold pressure is low, time delay 2 second <16 KPa
Interlock stop conditions
All the primary air fans stopped, trip this seal air fan
Front / rear Bearing temperature is very high, delay 2 second >85C
Front /rear motor Bearing temperature is very high, delay 2 second >85C
24
25
Interlock of Boiler
Two airpreheaters tripped after delay 5 minute, trip two induced draft fans, two primary air fans, 4 coal pulverizers, 4 coal
feeders in manner of interlock, close feeding oil quick close valve in manner of interlock, and trip all the oil guns
Two induced draft fans tripped, trip 4 coal pulverizers, 4 coal feeders in manner of interlock, close feeding oil quick close
valve in manner of interlock, and trip all the oil guns
Two induced draft fans tripped, trip two primary air fans, 4 coal pulverizers, 4 coal feeders in manner of interlock, close
feeding oil quick close valve in manner of interlock, and trip all the oil guns
Two primary air fans tripped, trip 4 coal pulverizers, 4 coal feeders
One airpreheater tripped after delay 5 minute, trip this side induced draft fan, one this side primary air fan
One induced draft fan tripped, trip this side forced draft fan, trip this primary air fan
When three or excess three operating coal pulverizers are running. One primary air fan tripped , trip 2 coal pulverizers of A
and D, 2 coal feeders of A and D
Interlock of BTG
Boiler MFT tripped ,trip turbine, trip generator oil
Switch
Turbine tripped and load>40%, trip MFT,trip generator oil
Switch
Generator transformer block protection tripped, trip turbine; when turbine tripped and load >40%,trip MFT
28
Superheater primary desuperheating water control valve of side A is opened (>3%), interlock opens corresponding superheater
desuperheating water sub-electric-valve.
When superheater primary desuperheating water control valve of side B is closed(<3%,or MFT starts, or the load is less than
20%,interlock closes corresponding desuperheating water sub-electric-valve
Superheater primary desuperheating water control valve of side B is opened (>5%), interlock opens corresponding superheater
desuperheating water sub-electric-valve.
When superheater secondary desuperheating water control valve of side A is closed(<5%,or MFT starts, or the load is less than
20%,interlock closes corresponding desuperheating water sub-electric-valve
Superheater secondary desuperheating water control valve of side A is opened (>5%), interlock opens corresponding superheater
desuperheating water sub-electric-valve.
When superheater secondary desuperheating water control valve of side B is closed(<5%,or MFT starts, or the load is less than
20%,interlock closes corresponding desuperheating water sub-electric-valve
Superheater secondary desuperheating water control valve of side B is opened (>5%), interlock opens corresponding superheater
desuperheating water sub-electric-valve.
MFT starts or the load is less than 20%,interlock closes reheating system desuperheating water electric sub-electric-valve, each
desuperheating water control valve automatically changed to manual control, and interlock close
When reheater desuperheating water control valve of side A is closed(<5% or MFT starts, or the load is less than 20%,interlock
closes corresponding reheat desuperheating water sub-electric-valve
Reheater desuperheating water control valve of side A is opened >5% interlock opens corresponding reheater desuperheating
water sub-electric-valve.
When reheater desuperheating water control valve of side B is closed(<5%,or MFT starts, or the load is less than 20%,interlock
closes corresponding reheat desuperheating water sub-electric-valve
Reheater desuperheating water control valve of side B is opened >5% interlock opens corresponding reheater desuperheating
water sub-electric-valve.
Reheater emergency spray water control valve is closed<5% or MFT starts, or the load is less than 20%, interlock close
corresponding reheater emergency spray water electric valve
Reheater emergency spray water control valve is opened >5% interlock open corresponding reheater emergency spray water
electric valve
Boiler (startup) hearth heating steam general electric valve
The temperature of furnace is less than 80 and MFT starts, startup is accessible
30
31
Light oil manifold pressure low: Low pressure of oil manifold (2of 3) lasts for more than 5s, and some oil angle valves still
open (<1.8MPa)
Light oil supply fast valve closed, and some oil angle valves still open;
Low pressure of compressed air (2of 3) lasts for more than 10s, and some oil angle valves still open
Start the following equipments in manner of interlock after OFT
Close all angle valves of light oil
Close light oil stream valve
Close light oil supply cut-off valve
Close light oil return cut-off valve (pulse)
Withdraw light oil ignition gun
OFT reset conditions
All angle valves closed
MFT relay reset
Light oil OFT (soft) trip conditions not available.
Open main inlet fast shut-off valve of light oil
32
Open the oil return quick close valve of light oil (meanwhile, open the fuel pressure regulation valve), closed after 10s. And
display "light oil fuel leakage test Actual actions proceeding" on operator station screen;
Within 300s, if the manifold pressure after the light oil feeding quick close valve low (difference value <0.05MPa), then the
light oil feed quick close valve leakage test passed; Or else, light oil feeding quick close valve considered leaked, fuel oil
leakage test failed, and it will be displayed on the operator station screen
If the light oil feeding quick close valve leakage test passed, open the light oil feeding quick close valve, charge oil: After the
manifold pressure becomes high
Within 180s, if manifold pressure after the light oil feeding quick close valve high (>2.8MPa, difference value <0.4MPa), then
the light oil return oil quick close leakage test passed; Or else, light oil return oil quick close valve considered leaked, leakage
test failed, and it will be displayed on the operator station screen
Oil leakage test interrupting conditions
34
Heavy oil manifold pressure low: Low pressure of oil manifold (2of 3) lasts for more than 5s, and some oil angle valves still
open;
Heavy oil supply fast valve closed, and some oil angle valves still open;
Low pressure of atomizing steam (2of3) lasts for more than 10s, and some oil angle valves still open
Low temperature of heavy oil, time delayed 1min, and oil angle valve still open
Start the following equipments in manner of interlock after OFT
Close all oil valves of heavy oil
Close all purging valves of oil gun
Close heavy oil supply cutoff valve;
Close heavy oil return cutoff valve (pulse);
Close atomizing valve of heavy oil
OFT reset conditions
All angle valves closed
MFT relay reset
Heavy oil OFT (soft) trip conditions not available.
Open main inlet fast shut-off valve of weight oil
Sequence Start
Forward Heavy oil gun
Open heavy oil atomizing valve
Open heavy oil valve.
Sequence stop
Close heavy oil valve
Close atomization valve
Forward heavy oil gun
Open purge or atomizing valve
Close purge or atomizing valve
Backward heavy oil gun
39
Interlock
When running CWP emergency tripped starts standby CWP in interlock
When Header pressure is low automatically start the standby pump in interlock
Discharge butterfly valve automatically after pump startup
When butterfly valve open 20deg CWP startup
41
After CWP startup 60 sec outlet butterfly valve accident, stop CWP
When CWP outlet valve close to 20 deg, stop CWP
When CWP tripped, outlet butterfly valve automatically closes
42
Protection
Deaerator water level LL (2of3) 380mm
Lube oil pressure LL 0.05 MPa
BFP operating booster pump inlet motor valve closed
Inlet oil temp working oil 130C alarm 110C
BFP thrust bearing temp 95C alarm 80C
Motor bearing temperature of booster pump end 90C alarm 80C delay 3 sec
Motor bearing temperature of hydraulic coupler end 90C alarm 80C delay 3 sec
Booster pump drive/free end bearing temp 90C alarm 75C delay 3
BFP inside /outside radial bearing temp 90C alarm 75C delay 3
BFP hydraulic couples radial bearing temp 95C alarm 85C delay 3 (1-7)
BFP winding temp 130C alarm 110C delay 3 (1 -6)
Local emergency button operated
When BFP operation, flow 128 t/hr and minimum flow valve is closed., delay 15 sec BFP will tripped.
Motorized feed water pump operating and booster pump inlet valve closed
Start Permissives
43
Booster pump inlet motorized valve & Recirculation valve fully opened
Lube oil pressure normal 0.1MPa
Deaerator water level normal
Booster pump inlet valve opened
Scoop tube position5%
Booster pump drive/free end radial bearing temperature <75C
Motor bearing temperature of booster pump end <80C
Motor bearing temp of hydraulic-coupler end <80C
Hydraulic coupling bearing (10th point )< 85C
BFP thrust bearing temp(upside, downside) <85C
BFP winding temperature <110C
Working oil cooler inlet temp<110C
BFP outlet motor valve closed OR standby
Differential pressure of inlet screen for motorized feed water pump and booster pump is abnormal
44
Interlock
Motorized feed water pump operating and lube oil pressure lower than 0.08 MPa, automatic startup
Enable motorized feed water pump as standby and start in manner of interlock
Motorized feed water pump stopped and protection ON
BFP operating and lube oil pressure higher than 0.3 MPa , delay 5 sec and auxiliary oil pump automatically stop
Vacuum system
Vacuum pump startup permissive conditions
Vacuum pump inlet pneumatic valve closed
Control by remote
45
EH oil system
EH oil pump interlock protection
EH oil manifold pressure lower to 11.2 MPa alarm, and start up standby EH oil pump by means of interlock
DEH oil pump emergency trip, interlock start standby pump.
Start-up permissive
Oil tank level normal
Oil temperature is >20 deg C.
Deaerator system
Interlock
Deaerator water level HH (.2550mm), Deaerator overflow valve opened in manner of interlock,
Deaerator water level not high,(<2350mm) Deaerator overflow valve closed in manner of interlock
When water level is high II, close MOV of extraction # 3 , check valve of extraction # 3 , close drain control valve of HP
heater # 2 to dearator.(>2650mm)
Close 1 to 5 extraction check valve & close 1 to 6 Extraction MOV
Turbine trips
Generator tripping
OPC acts
HP heater system
Interlock
HPH # 1 water level is high II, open emergency drain control valve. (>600mm)
HPH # 1 water level is low I, close emergency drain control valve. (<250mm)
47
LP heater system
Startup procedures for sequence control of LP heater
Close LP heater emergency drain valve
Open pipe drain valve after steam extraction electric valve/before check valve of LP heater
Open the LP heater outlet electric valve
Open the LP heater inlet electric valve
Close the LP heater bypass electric valve
Open the LP heater steam-extraction electric valve,
Open the LP heater steam-extraction electric valve
48
10s delay and load larger than 30% , close pipe drain valve after electric valve/before check valve for 4th stage steam
extraction
Stop procedures for sequence control of LP heaters
Close the LP heater steam extraction electric valve
Close the LP heater steam-extraction check valve
Open pipe drain valve after steam extraction electric valve of LP heater
Open the pipe drain valve before check valve of LP heater
Open LP heater bypass electric valve
Close LP heater inlet electric valve
Close LP heater outlet electric valve
Open LP heater emergency drain valve
5s delay, open pipe drain valve after steam extraction electric valve/before check valve of LP heater
Inspection of LP heater quitting conditions
Steam turbine tripping
Generator quitting
LP heater water level HHH (1050mm)
Manual quitting
> OPC action
Interlock
LPH # 4 water level is high II, open emergency drain control valve, close extraction # 4 check valve & MOV , open extraction
# 4 drain valve, Water side bypass MOV open & i/l & o/l MOV closed. (>1050mm)
LPH # 4 water level is high I , open emergency drain control valve .(>900mm)
LPH # 4 water level is low I, close emergency drain control valve to condenser. (<600 mm)
LPH # 5 water level is high II, open emergency drain control valve, close extraction # 5 check valve & MOV, open extraction
# 5 drain valve, Water side bypass MOV open & i/l & o/l MOV closed. (>1050mm)
LPH # 5 water level is high I , open emergency drain control valve to LPH # 6 & close normal drain control valve from LPH #
4 to LPH # 5.(>900mm)
LPH # 5 water level is low I, close emergency drain control valve to condenser. (<600 mm)
LPH # 6 water level is high I, choose any one of the CDP (drain water pump) as standby , then interlock starts the drain pump
& opens the pump outlet control valve. (>900mm)
49
LPH # 6 water level is high II, open emergency drain control valve, close LPH # 5 normal drain to LPH # 6 control valve ,
close extraction #6 MOV , open extraction # 6 drain valve, Water side bypass MOV open & i/l & o/l MOV closed.
(>1050mm)
LPH # 6 water level is low I close emergency drain control valve (<700mm)
LPH # 6 water level is low II , interlock stop drain water pump. (550mm)
Drain valve in front of LPH # 4 extraction MOV interlock open
Turbine load is <20%
Check valve of extraction # 4 is close
MOV of extraction # 4 is close
Drain valve in front of LPH # 5extraction MOV interlock open
Turbine load is <20%
Check valve of extraction # 5 is close
MOV of extraction # 5 is close
Steam turbine HP main steam valve (right) upper seat drain valve
Steam turbine HP main steam valve (right) lower seat drain valve
Steam turbine HP casing steam exhaust pipe (left) drain valve
Steam turbine HP casing steam exhaust pipe (right) drain valve
Steam turbine HP casing steam exhaust manifold drain valve
Drain valve before 1st stage steam extraction electric valve
Drain valve before 1st stage steam extraction check valve
Drain valve after 1st stage steam extraction electric valve
Drain valve after 1st stage steam extraction check valve
HP bypass pipe drain valve
Bypass system
HP Bypass
Automatic opening
53
Turbine trip
Automatic closing
Temperature behind HP bypass is High (360C)
Desuperheating water pressure is low (switch)
Interlock
HP bypass valve open, open desuperheating isolating valve
HP bypass closes, interlock close desuperheating isolated valve
HP bypass closed, interlock close desuperheating control valve
Relief valve is close, desuperheating control valve is forbidden to open
LP bypass
Automatic opening
Turbine trip
Automatic closing
Condenser vacuum low -70Kpa (2/3)
Condenser temperature high 70C
After-LP bypass valve temperature high 170C
LP bypass spray water pressure low
Interlock
LP Bypass open, open desuperheating control valve is open
LP Bypass control valve open, open desuperheating isolating valve
LP Bypass control valve close, close desuperheating isolating valve
Turbine
54
55
Status
In message screen 1) Trip 2) Auto 3) All control valve closed
All solenoids should be green ( Discharged )
Click on ' LATCH' ( Gray )
Solenoid 5, 6, 7 and 8 turn ' RED'.
Check ' LATCH ' turned ' RED'
With above sequence Latching get completed. Now turbine ready to roll, If all parameters built up as per Turbine condition
Auto Control
Solenoid
monitor
Auto Control
Click on 'RUN'
Main steam and Reheat steam stop valve will open.
For starting Rolling ( Increasing speed )
Auto Control
Auto Control
Click on ' SPEED RATE ' and give a value ( Exa.- 100 - 200 RPM/Minute)
Click on ' TARGET ' and give a value ( Exa- 500 RPM )
Click on ' GO/HOLD ' and select 'GO' and watch the speed rise.
Then as per the Turbine temperature diffrence between top and bottom, Diffrencial Expansion,Bearing Vibration soak the turbine .
56
BLACKOUT CHECKLIST
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
12)
13)
14)
15)
16)
57
AUTO SYNCHRONIZATION
: 1 /2
Operation task:generator Unit-1 voltage up through auto excitation; auto synchronization
Seq.
Operation Item
safety measures
Implement operation supervision system strictly. The supervisor should be experienced operator or
above.
Wear insulation gloves and proper working tools.
The staff is both physically and psychologically well and familiar with the system.
operation measures
Unit-1 Check the cooling water system of generator Unit-1 air cooler is working normally.
# 1 Check the rotation speed of turbine Unit-1 is steady. Maintain the rotation speed of the turbine be
the same with grid frequency.
Unit-1 Verify that generator transformer Unit-1 is put into service correctly.(only
one set of rotor earthing protection is to be put into service)
Close power to operation box 4QFand power to operation box 5QF
Unit-1 CH1 AVR ON REMOTE Check AVR of generator Unit-1 excitation room(small) is
running at "CH1", "AVR ON" lamp is on and "REMOTE" lamp is off.
DCS # 1 Excitation Launch Click AVR Unit-1 on the DCS panel and enter its
interface. Close excitation suppression switch and take Excitation Launch.
Unit-1 Check the generator excitation system of Unit Unit-1 is put into service normally.
Unit-1 13.11kV 13.8*0.95Check the voltage of generator Unit-1 automatically rises to around 13.11kV.
13.8*0.95
INC EXC 13.8 kVUg=U220KVg13.8235
3
4
5
6
7
8
9
10
ti
m
e
58
11
12
13
14
15
16
17
18
Use INC EXCbutton to increase the generator voltage to the rated value of 13.8kv;
(follow busbar voltage regulating and slightly higher than busbar voltage)
Ug=U220KVg13.8235
Unit-1 75.4v 567.4A) Verify that 3 phases voltage of generator Unit-1 is balanced
and no-load excitation parameters such as voltage and current are correct.( compare
to no-load rated parameters 75.4v 567.4A)
# 1 DCS Verify that there is no abnormal signal in generator Unit-1 protection
panel, excitation room and DCS.
SELF Confirm that synchronization select switch is at SELFposition.
1 SWJ 2ZK Confirm that the SWJ power 22K of mazaic control panel #1 is already
closed and synchronization is put into service.
3 1MCB Confirm that the power MCB of synchronizing unit of mazaic control panel #3
is already closed.
4 STK "AUTO" Confirm "AUTO" is selected at mosaic control panel #4 STK.
4 ATRESIAQK Exit atresia Confirm Exit atresia is selected at mosaic control
panel #4 ATRESIAQK
1 #1 1DL CLOSE
DCS 1DL START Change outlet breaker 1DL of generator transformer Unit-1 on mosaic control
panel Unit-1 over to CLOSEand put synchronization into service.(or click "START" at the interface
of DCS generator transformer outlet breaker 1DL to put synchronization into service)
59
25
DEH AUTO Control sync Check the interface of DEH AUTO Control and verify that
synclamp is on (RED)
DEH AUTO Control syncDEH Click "sync" in the interface of DEH AUTO Control to put
DEH synchronization into service.
DEH Check DEH to send synchronization permission signal and the synchronization meter
should be charged.
Manually adjust the generator frequency and voltage to be the same with those of grid system.
3 START UP Press close button of auto sync "START UP" breaker on mosaic control panel
#3.
Verify that synchronization unit is working normally.(it automatically regulate the generator frequency and
voltage be the same with those of the grid system.
# 1 1DLVerify that the auto closing of generator Unit-1 breaker 1DL is normal. (Red lamp on)
26
27
DEH sync Verify the DEH synchronisation request is cancelled.sync becomes grey
DCS 1DL Exit Click "EXIT" on the interface of DCS generator transformer outlet breaker 1DL to cancel
synchronization.
1 SWJ DEH Confirm the SWJ on the control panel 1 should be reset.(sync out and withdraw
from "request sync from DEH" signal)
# 1 1DL Confirm that synchronization of 1DL breaker of generator transformer Unit-1 is cancelled.(lamp of
synchronization meter dies)
4 MANUAL HANDLE(STK)"UNCHAN"
Select "UNCHAN" of MANUAL HANDLE(STK) switch on mosaic control panel #4.
# 1 A 19XP Disconnect 19XP GENERATOR START\STOP EARTH FAULT protection on
protection panel A of generator transformer Unit-1.
# 1 A 28XP Disconnect 28XP ACCIDENTAL ENERGISATION RELAY protection on protection
panel A of generator transformer Unit-1.
# 1 A 31XP Disconnect 31XP FLASH OVERprotection on protection panel A of generator
transformer Unit-1.
# 1 A 4XB CLOSE MAIN VALVE I Put 4XB CLOSE MAIN VALVE I protection into service
on protection panel A of generator transformer #1.
# 1 A 23XB CLOSE MAIN VALVE II Put 23XB CLOSE MAIN VALVE II protection into
service on protection panel A of generator transformer #1.
# 1 B 19XP Disconnect 19XP GENERATOR START\STOP EARTH FAULT protection on protection
panel B of generator transformer Unit-1.
# 1 B 19XP Disconnect 19XP GENERATOR START\STOP EARTH FAULT protection on protection
panel B of generator transformer Unit-1.
# 1 B 31XP Disconnect 31XP FLASH OVERprotection on protection panel B of generator
transformer Unit-1.
Unit-1 Verify that generator Unit-1 is working normally.
# 1 B 4XB CLOSE MAIN VALVE I Put 4XB CLOSE MAIN VALVE I protection into service
on protection panel B of generator transformer #1.
# 1 B 23XB CLOSE MAIN VALVE II Put 12XB CLOSE MAIN VALVE II protection into
service on protection panel B of generator transformer #1.
19
20
21
22
23
24
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
60
ETS Protection
TURBINE TRIP
ALARAM
Action
Axial position
+1.2mm,1.65mm
(+0.6/-1.05)
Auto
Shaft Vibration
>0.25mm
(>0.125mm)
Auto
<7.8Mpa
<12MPA
Auto
<0.049MPA
Auto
19.7Kpa
14.4KPA
Auto
6
7
TSI overspeed
DEH Over speed
3300 RPM
3300rpm
3240RPM
Auto
Auto
DEH Failure
10
11
12
13
LP exhaust temp.HI
14
<0.0392Mpa
Auto
TURBINE TRIP
>110 C
>100 C
>115 C
>105 C
>120 C
>80 C
Auto
Auto
Auto
Auto
Auto
Auto
Auto
TURBINE TRIP
61
15
+6.2mm/-3.2mm
+6mm/-3mm
Auto
16
LP Differential expansion
+7.2mm/-6.2mm
+7.2mm/-6mm
Auto
0.08mm
17
18
19
20
Eccentricity of rotor
21
Auto
>65 C
>16.4 MPAC
Manual
>30Um
>0.13MPA&<0.02MPA
ALL CVs & ICVs AUTO CLOSE Over speed protection Control(OPC) act)
1
62
These responses will be slow when compared to turbine responses. So it may be reemphasized that this mode of operation gives
maximum stability to unit operations with slow response to grid
Contd.2/-
64
::02::
requirements by initiating combustion controls first and turbine valves positioning after steam production. However the combustion
controls will be responding to grid requirements if frequency influence in CMC console is in ON position only.
In Boiler follow mode Turbine maintains MW demands and Boiler maintains main steam pressure. Turbine will be responding
to grid requirement fastly because of droop characteristic set in EHC and Boiler will be following to maintain main steam pressure if
combustion controls are in Auto. This mode of operation gives maximum stability to network because MW requirements are met by
Turbine fastly and lesser importance to unit stability, because the action by Turbine will be disturbing main steam pressure. If all units
in the network do not implement 5% regulation then the network disturbances will be passed on to the units in Boiler follow mode
disturbing their MW level of operation often. Boiler combustion controls must be kept in Auto in this mode of operation which will be
taking main steam flow and main steam pressure error as inputs for control. The main steam pressure is the final trimming signal to
boiler for boiler follow mode of operation. Response of Turbine to grid requirements is quickly perceived by boiler controls through
main steam flow variations. Finally Boiler controls ensure the set throttle pressure.
In coordinated mode of operation unit/master control station sets MW set point which will be pursued by combustion controls
by taking main steam pressure error as final trimming input signal. Turbine will be controlling the MW at the set point or changes in
grid frequency will be leading to changes in the MW. Main steam pressure error will have proportional influence for stability of the
unit. Boiler will be trying to control main steam pressure. Coordinated mode and boiler follow mode are similar in response except
that base signal required for boiler combustion control is MW set point in coordination mode and main steam flow signal in Boiler
follow mode.Sustained throttle pressure controller output will be the result due to calorific value deviation from design calorific value
and this output will be getting added to unit demand going to boiler master .the calorific value correction controller in auto mode takes
the output of throttle pressure controller as input and works as long time integrator to produce output to represent calorific value
which works as multiplier for fuel demand to boiler .In the process of this long time action, the throttle pressure controller output
returns to almost zero. The advantages in this control action are better transient response since the calorific value is as per actual
calorific value of coal going to the boiler and the throttle pressure controller has margins all the time on both positive and negative
sides.
Unit capability is capacity of the unit to produce the MW at that time. Unit capability signal depends on the number of
Auxiliaries in service and their contribution is expressed as MW signal which they can support. For example if six mills are required
to produce 500MW each mill capability will be taken as 85 MW approximately. The capability will be computed from each type of
Auxiliaries and minimum of all these will be the unit capability. On any running Auxiliary tripping, unit capability signal will be
dependent on the type of auxiliary tripped.
65
::03::
In Runback mode Boiler combustion controls give commands in proportion to unit capability and boiler will be coming to the state
of steady combustion and hence will be stabilizing. Turbine will be controlling main steam pressure as this will give maximum
stability to the unit. Runback mode gives highest stability to
unit because unit has gone to instability (ex.Mill/BFP/ID/FD tripped) this Runback mode gets selected automatically and ensures
stability. Whenever unit capability is less than unit master command the Runback mode sets in automatically.
The four modes of operation described above can be summarized in the following way.
Boiler Controls
Turbine Controls Input to Boiler
Input to Turbine
Controls
Controls
Turbine
MW
Pressure
MW Set point
Pressure error
follow
(base signal)
MW error signal
Boiler
Pressure
MW
Steam Flow
MW error
follow
(base signal)
Pressure error
Coordinated Pressure
MW
MW set point
MW error
Mode
(base signal)
Pressure error
Runback
Produces steam
Pressure
Unit capability
Pressure error
mode
as per unit
signal
capability
(computed)
Mode
The Coordinated Master Control is written with a view to bring all concepts in it together to give a complete view of it.
Emphasis is given on concepts rather than on the CMC scheme.
66
67