High Current Measurements
High Current Measurements
MALAYSIA
FACULTY OF ELECTRICAL AND ELECTRONIC
ENGINEERING
BEF 20903
BEF 23903
ELECTRICAL MEASUREMENTS
Written By
Date
Version
Contents
1. Introduction
2. Types of Current Transformers
3. Equivalent Circuit of a current transformer
4. Current Transformer Ratios
5. Phasor Diagram of Current Transformer
6. Errors in current transformer
7. Phase angle error
8. Methods to minimize errors
9. Types of current transformer construction
10. Clamp meter
LEARNING OUTCOMES
After completing this module you will be able to:
1.0 INTRODUCTION
High AC currents can be measured with shunts under special circumstances, but most
often such direct connections to AC lines are extremely dangerous to humans. One
way to get around the hazard is to use current transformers (CT) that isolate AC line
voltages and reduce input current by a specified ratio. A current transformer produces
a scaled down replica of the input quantity to the accuracy expected for the particular
measurement. The common laws for transformers are valid for current transformers.
1. The measuring instruments can be placed for away from the high voltage side
by connecting long wires to the current transformer. This ensures the safety of
instruments as well as the operator.
Shunt
Current
transformer
Meter cost
Clamp-on CT
This is a C.T., in which the core can be opened with the help of a clamp and
the conductor (whose current is to measured) can be inserted into the core.
This conductor acts as a primary winding. The secondary winding is wound on
the laminated core. A low range ammeter is connected across the secondary,
which measures current of the conductor. It is a portable instrument, which
can be used in laboratories.
Figure 1. Clamp-on CT
5
2)
Bar type CT
A bar type CT has a circular ring type core over which secondary winding is
wound, across which a direct reading ampere meter is connected. When a bar
conductor or a Bus bar whose current, is to be measured is inserted in to the
ring, the ampere meter reads the current (Figure 2).
Ip
Rp
Xp
Is
Rs
Np:Ns
Xs
Is
Io
Ie
Vp
Re
Im
Xm Ep
Es
ZL = RL + jX L
Ideal
CT
Figure 3. Equivalent circuit of a current transformer.
where
Vp
Primary voltage
Ip
Primary current
Rp
Xp
Io
Exciting current
Ie
Re
Im
Magnetizing current
Xm
Magnetizing reactance
Ep
p, s
Is
Es
Rs
Xs
RL
Vs
XL
KT
It can be seen from the equivalent circuit diagram shown in Figure 3 that the primary
current contains two components:
An exciting current, which magnetizes the core and supplies the eddy current
and hysteresis losses, etc.
The secondary internal impedance, however, must be taken into account, but only the
winding resistance Rs. The leakage reactance is negligible where continuous ring
cores and uniformly distributed secondary windings are concerned. The exciting
impedance is represented by an inductive reactance in parallel with a resistance. Im
and Ie are the reactive and loss components of the exiting current. The resulting
simplified equivalent circuit is shown in Figure 4.
Is
Ip
Rs
Np:Ns
Is
Io
Ie
Vp
Re
Im
Xm
Ep
Es
ZL = RL + jX L
Ideal
CT
Figure 4. Simplified equivalent circuit of a current transformer.
8
Vs
Is
Io
Ie
Es
Im
Re
Xe
ZL = RL + jX L
Vs
Turns ratio - This is the ratio of the turns of the transformer windings.
Kt
Ns
Np
where
Ns = No. of turns in secondary winding
Np = No. of turns in primary winding
ii.
K act
iii.
Ip
Is
Nominal ratio - This is the ratio of the rated primary winding current
(Ip(rated)) to the rated secondary winding current (Is(rated)) of the
transformer.
K nom
iv.
I p (rated )
I s (rated )
Ns
Kt
Np
R.C.F
K act
K nom
Thus,
and
K nom
R.C.F
K act
Note
If the exciting current Io could be neglected the transformer should reproduce the
primary current without errors and the following equation should apply to the primary
and secondary currents:
Ip
Ns
I s Kt I s
Np
Worked Example 1
A bar-type current transformer which has 1 turn on its primary and 160 turns on its
secondary is to be used with a standard range of ammeters that have an internal
resistance of 0.2 . The ammeter is required to give a full-scale deflection when the
10
Worked Example
Solution
Secondary current:
Np
I s I p
Ns
1
800
5A
160
Worked Example 2
A current transformer has a rating of 50 VA, 400 A/5 A, 36 kV, 50 Hz. It is connected
into an a.c. line having a line-to-neutral voltage of 14.4 kV. The ammeters, relays and
connecting wires on the secondary side possess a total impedance (burden) of 1.2 .
If the transmission line current is 280 A, calculate:
1. The secondary current
2. The voltage across the secondary terminals
3. The voltage drop across the primary.
11
Figure 7.
Solution
(a)
Np
Ns
Is
5
1
I p 400 80
Is I p
(b)
Ns
1
280
3.5 A
Np
80
(c)
Np
Ns
4.2
5
52.5 mV
400
Exercise
A toroidal transformer has a ratio of 1000 A/5 A. The line conductor carries a current
of 600 A.
(a) Calculate the voltage across the secondary winding if the ammeter has an
impedance of 0.15 .
(b) Calculate the voltage drop the transformer produces on the line conductor.
(c) If the primary is looped four times through the toroidal opening, calculate the new
current ratio.
12
Figure 8.
13
Ip
-Ep
Is-Secondary Current
KTIs
Ie
Ip - primary Current
Ep - primary induced emf
Io
Im
Is
Es
14
I s'
Ns
I s I o KT I s I o
Np
Io
Is = KTIs
Ip
15
I p (measured ) I p (actual)
I p (actual)
KT I s I p
Ip
100 %
100 %
KN KA
100 %
KA
According to the definition above, the current error is positive if the secondary
current is too high, and vice versa.
Current error is an error that arises when the current value of the actual transformation
ratio is not equal to rated transformation ratio.
Current error %
I s ' I p
Ip
100%
KN Is I p
Ip
Worked Example 3
In case of a 2000/5A class 1 5VA current transformer
KN
2000
400 K T
5
Ip = 2000 A
16
100%
Is = 4.9 A
Current error
KT I s I p
Ip
100%
400 5 2000
2%
2000
Worked Example 4
An application requires a 20:5 CT ratio, but only a 50:5 CT is available. Given that
the number of primary turns (Np) is 3, determine the number of secondary turns that
need to be added so that a 20:5 actual ratio will be obtained.
Solution
Given:
20
4
5
We require
KA
Therefore,
giving
Nsa = 2 turns
10 N sa
3
17
50
10
5
I s' I p
The phase angle error is usually expressed in minutes, and if the reversed
current phasor leads the primary current phasor then the phase angle error is
defined as positive; otherwise it is taken as negative.
It will be seen that with a moderately inductive burden, resulting in Is and Io
approximately in phase, there will be little phase error and the exciting
component will result almost entirely in ratio error. A reduction of the
secondary winding by one or two turns is often used to compensate for this.
18
Worked Example 5
The exciting current of a transformer (of ratio 1000A:5A) with a burden of 1 is 1 A
at a p.f. = 0.4. Calculate actual transformation ratio and ratio error.
Solution
Given :
Is
1000A:5A
ZL = 1
ES
Is
Ip
1000A:5A
Is
Io
Ie
Im
Ep
Es
ZL = 1
19
Therefore,
and
90 o 90 o 66.42 o 23.58 o
Io
Ie
Im = 80 A
Figure 14. Phasor diagram showing phase relationships between Io, Ie, and Im.
Turns ratio
KN
1000 A
200
5A
I s' K N I s
1000 A
5 A 1000 A
5A
20
Ip
Is
Io
Figure 15. Phasor diagram showing phase relationships between Ip, Io, and Is.
Ip
'
s
I o sin
cos
o 2
1000.4 A
KA
Ip
Is
1000 .4
200 .8
5
Ratio error,
%e
0.04% Ans.
K actual
200.8
21
Worked Example 6
A CT has a single turn primary and 400 secondary turns. The magnetizing curent is 90
A while core loss current is 40 A. Secondary circuit phase angle is 28o. Calculate the
actual primary current and ratio error when secondary current carries 5 A current.
Solution
The information given is only sufficient to be applied to the simplified equivalent
circuit of a current transformer shown in Figure x.
Is
Ip
Is
Np:Ns
Io
Ie
Vp
Re
Im
Ep
Xm
Es
Ideal
CT
KT
I s'
N s 400
400 K N
Np
1
Ns
I s 400 5 2000 A
Np
22
ZL
Vs
Ip
Is
= 28o
Io
Figure 15. Phasor diagram showing phase relationships between Ip, Io, and Is.
Y- component of primary-referred secondary current,
I s' y I s' cos 2000 cos 28 o 1766 A
23
I p (measured ) I p (actual)
I p (actual)
I s' I p
Ip
2000 2079
100 % 3.8%
2079
Therefore,
% 3.8% Ans.
ii.
iii.
24
Figure 16. Current transformer cores. (a) rectangular core; (b) ring core.
Keeping the rated burden to the nearer value of the actual burden.
3.
4.
accidentally opened, the primary current Ip continues to flow unchanged because the
impedance of the primary is negligible compared to that of the electrical load. The
line current thus becomes the exciting current of the transformer because there is no
further bucking effect due to the secondary ampere-turns. Because the line current
may be 100 to 200 times greater than the normal exciting current, the flux in the core
reaches peaks much higher than normal. The flux is so large that the core is totally
saturated for the greater part of every cycle. Referring to Figure 17, as the primary
current rises and falls during the first half cycle, flux in the core also rises and falls,
but remains at a fixed saturation level sat for most of the time.
ip
sat
d
N
dt
3000 V
secondary
voltage
Figure 17. Primary current, flux, and secondary voltage when a CT is open-circuited.
The same thing happens during the second half-cycle. During these saturation
intervals, the induced voltage across the secondary winding is negligible because the
flux changes very little. However, during the unsaturated intervals, the flux changes at
an extremely hig rate, inducing voltage peaks of several thousand volts across the
26
Thus, for reasons of safety, if a meter or relay in the secondary circuit of a CT has to
be disconnected, we must first short-circuit the secondary winding and then remove
the component. Short-circuiting a current transformer does no harm because the
primary current remains unchanged and the secondary current can be greater than that
determined by the turns ratio. The short-circuit across the secondary may be removed
after the secondary circuit is again closed.
Note:
27
Worked Example
Current is to be measured in a single-phase line which supplies a 240-V, 20 kW load
with a 0.8 power factor. Select an appropriate ammeter and current transformer.
Direct reading ammeters are available with full-scale reading ranging from 2 to 20 A.
Figure 19
Solution
P
V pf
20,000
240 0.8
Therefore,
I 104 A
Step 2. Select Ammeter.
Step 3
L
Current
transformer
AC ammeter
Single-phase
power line
Figure 20.
1.
2.
29
3.
4.
Bar Type CT
Bushing Type CT
30
Window Type CT
Wound Type CT
Figure 21: Type of current transformers
Outdoor CTs
Current Transformer could either be:
1. Indoor current transformer: One that, because of its construction, must be
protected from the weather.
2. Outdoor current transformer: One of weather-resistant construction, suitable
for service without additional protection from the weather.
Figure 22
31
Outdoor CTs
32
CLAMP METER
A clamp meter is an electrical tester that combines a basic digital multimeter with a
current sensor. A common form of current sensor comprises a split ring made of
ferrite or soft iron and hinged at one one to form a pair of jaws that can be opened to
clamp around the conductor whose current is to be measured. A wire coil is wound
round one or both halves, forming one winding of a current transformer. The
conductor around which it is clamped forms the other winding. This allows properties
of the electric current in the conductor to be measured, without having to make
physical contact with it, or to disconnect it for insertion through the probe.
Types Of Current Clamps
The output of the current clamp can be read by any AC ammeter whose input
impedance is compatible with the specifications of the current clamp. Current clamps
are also available that convert the current input signals into a voltage signal for
measurement by a voltmeter.
Some current clamps incorporate a rectifier circuit whose output is a DC voltage that
is proportional to the average current being measured. Such clamps facilitate the use
of strip chart recorders for obtaining real time trends of current loads. To obtain a
TRUE RMS output, a DC-to-RMS converter is attached to output of the dc current
clamp.
1.
(a)
33
(b)
2.
(a)
34
Resistive
shunt
(b)
200 mA. Per Figure 26, the burden resistor should be:
Ro
Vo
0 .5
2 .5
I s 0.200
Figure 26
35
Figure 27. Current clamp incorporating a rectifier and filter circuit to convert the ac
current signal into a voltage signal.
36
37
38
39