ANSI C37.06.1-1997, Trial-Use Guide For High-Voltage Circuit Breakers Rated On A Symmetrical Current
ANSI C37.06.1-1997, Trial-Use Guide For High-Voltage Circuit Breakers Rated On A Symmetrical Current
ANSI C37.06.1-1997, Trial-Use Guide For High-Voltage Circuit Breakers Rated On A Symmetrical Current
1-2000
Approved 03/30/00
ISBN 0-7381-9596-8
ISBN 0-7381-3597-6
SH95094
SS95094
No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior
written permission of the publisher.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on March 16,2016 at 17:48:46 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.06.1-2000
Page i
American
National
Standard
Published by
National Electrical Manufacturers Association
1300 N. 17th Street, Rosslyn, Virginia 22209
Copyright 2000 by the National Electrical Manufacturers Association. All rights including translation into
other languages, reserved under the Universal Copyright Convention, the Berne Convention or the Protection
of Literary and Artistic Works, and the International and Pan American Copyright Conventions.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on March 16,2016 at 17:48:46 UTC from IEEE Xplore. Restrictions apply.
ANSI C37.06.1-2000
Page ii
ANSI C37.06.1-2000
Page iii
FOREWORD
Following reports of circuit breaker failures in applications where very fast TRVs were determined to be the
cause, and after thorough analysis of TRV data gathered from all parts of the world, this guide was
suggested by the IEEE Switchgear Committees Task Force on Transient Recovery Voltages. The task force
suggested that another class of definite purpose circuit breakers was needed for fast TRV applications.
Circuit breakers designated as definite purpose for fast transient recovery voltage rise times applications
would be subjected to special fast TRV parameters during both Test Duty 2 (30% of rated short-circuit
current) and Test Duty 1 (7% of rated short-circuit current) trials, to demonstrate the capability to interrupt
circuits characterized by fast inherent TRVs. A few words of clarification are in order:
No fast T2 values or tests are proposed for fault currents greater than 30% of rated short-circuit
current.
The proposed fast T2 values were chosen to meet 90% of the known fast TRV circuits, but even
these fast values do not meet the requirements of all fast TRV applications.
A circuit breaker that would meet the requirements for definite purpose for fast TRV rise times
applications may or may not also meet the requirements for definite purpose circuit breakers for
capacitor switching.
It is the purpose of this guide to communicate the suggested values to those in the industry who are
interested and who would be in a position to offer comments and suggestions for further revisions.
Table 1B contains values for circuit breakers designed and tested to the circuit breaker ratings contained in
ANSI C37.06-2000, Table 1. These circuit breaker ratings have a rated voltage range factor (K) equal to 1.0.
Tables 2B and 3B contain values for circuit breaker ratings contained in ANSI C37.06-2000, Tables 2 and 3.
This guide was initially approved as a trial-use guide in 1997. Experience with the trial-use document since
then has been favorable, and the document is now approved for more general use as a guide. Only minor
editorial revisions have been made to the guide, plus suitable revisions to the text of this Foreword.
Comments and suggestions relative to the revision of this document should be sent to:
Vice President, Engineering Department
National Electrical Manufacturers Association
1300 N. 17th Street
Rosslyn, VA 22209
This guide was processed and approved for submittal to ANSI by Accredited Standards Committee on Power
Switchgear C37. Committee approval of the guide does not necessarily imply that all committee members
voted for its approval. At the time of its approval, the C37 Committee had the following members:
E. Byron, Chairman
A.K. McCabe, Executive Vice-Chairman, HV Standards
J. Scott, Executive Vice-Chairman, LV Standards
D.L. Swindler, Executive Vice-Chairman, IEC Activities
M. Calwise, Secretary
ANSI C37.06.1-2000
Page iv
Organizations Represented
Name of Representative
G. Montillet
G. Nourse
T. Olsen
G. Sakats
S. Slattery
H.M. Smith
D. Stone
F. Teufel
T. Tobin
J. Wiseman
R. York
ANSI C37.06.1-2000
Page v
CONTENTS
Page
Foreword.....................................................................................................................................................iii
1
Scope..........................................................................................................................................................1
Purpose.......................................................................................................................................................1
References .................................................................................................................................................1
Rated values...............................................................................................................................................1
Tables
Table 1BTransient recovery voltage parameters fast time-to-peak (T2 )
values for definite purpose indoor circuit breakers with voltage range
factor K=1.0 ....................................................................................................................................2
Table 2BTransient recovery voltage ratings fast time-to-peak (T2 ) values
for definite purpose circuit breakers 72.5 kV and below, including
circuit breakers applied in gas insulated substations.....................................................................3
Table 3BTransient recovery voltage ratings fast time-to-peak (T2 ) values
for definite purpose circuit breakers 123 kV and above ................................................................4
ANSI C37.06.1-2000
Page vi
C37.06.1-2000
Scope
This guide is issued as a supplement to C37.06 for high-voltage circuit breaker applications where the
transient recovery voltages (TRV) rise to the crest value much more rapidly than those specified in ANSI
C37.06:
Table 1, Preferred ratings for indoor circuit breakers with voltage range factor K=1.0;
Table 2, Preferred ratings for outdoor circuit breakers 72.5 kV and below; or
Table 3, Preferred ratings for outdoor circuit breakers rated 123 kV and above.
Purpose
The purpose of this guide is to provide suggested values of fast transient recovery voltage rise time ratings.
The proposed ratings were suggested by the IEEE Switchgear Committee, and apply ONLY to currents in the
ranges of 7 percent to 30 percent of Rated Short-Circuit Current. The TRVs for currents more than or equal
to 60% of rated short-circuit current remain the same as for general purpose circuit breakers. Circuit
breakers not identified by the manufacturer as "definite purpose for fast transient recovery voltage rise times"
shall be understood to be "general purpose circuit breakers," meeting the C37.06 standard TRV
requirements in table 1, 2, or 3 as appropriate.
References
ANSI/IEEE C37.04-1999, Rating Structure for AC High-Voltage Circuit Breakers Rated on a Symmetrical
Current Basis
ANSI C37.06-2000, AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis - Preferred
Ratings and Related Required Capabilities
ANSI/IEEE C37.09-1999,Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical
Current Basis
ANSI/IEEE C37.011-1994, Application Guide for Transient Recovery Voltage for AC High-Voltage Circuit
Breakers Rated on a Symmetrical Current Basis
Rated values
Circuit breakers identified by the manufacturer to be definite purpose for fast transient recovery voltage rise
times applications shall be capable of interrupting short-circuits with TRV parameters as specified in the
following tables:
Table 1B
Table 2B
TRV parameters for outdoor high-voltage circuit breakers rated 72.5 kV and below,
and designated as definite purpose for fast TRV time-to-peak
Table 3B
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on March 16,2016 at 17:48:46 UTC from IEEE Xplore. Restrictions apply.
Line
No.
Rated
Maximum
Voltage
kV, rms
(1)
Col. 1
Rated
Voltage
Range
Factor K
(1)
Col. 2
Rated
Short-Circuit
and Short-Time
Current
kA, rms
(1)
Col. 3
1
2
3
4
5
4.76
4.76
4.76
8.25
15
1.0
1.0
1.0
1.0
1.0
31.5
40
50
40
20
8.9
8.9
8.9
15.5
28
50
50
50
60
75
9.5
12
15
12
6
10.1
10.1
10.1
17.5
31.6
4
3.9
3.7
4.5
8.3
2.2
2.8
3.5
2.8
1.4
10.4
10.4
10.4
18
32.8
7.2
6.5
6
8
15
6
7
8
9
10
15
15
15
15
27
1.0
1.0
1.0
1.0
1.0
25
31.5
40
50
16
28
28
28
28
51
75
75
75
75
105
7.5
9.5
12
15
4.8
31.6
31.6
31.6
31.6
58
7.7
7
6.6
6.2
13
1.8
2.2
2.8
3.5
1.1
32.8
32.8
32.8
32.8
60
13.5
12
11
10
25
11
12
13
14
15
27
38
38
38
38
1.0
1.0
1.0
1.0
1.0
25
16
25
31.5
40
51
71
71
71
71
105
125
125
125
125
7.5
4.8
7.5
9.5
12
58
80
80
80
80
11
14
12
11
10.5
1.8
1.1
1.8
2.2
2.8
60
83
83
83
83
20
27
21.5
20
17.5
Rated Transient
Recovery Voltage
(1)
Peak
Time to
Voltage E2
Peak T2
KV
sec
Col. 4
Col. 5
Note
(1) See Table 1 of C37.06 for circuit breaker ratings.
Table 2BTransient recovery voltage ratings fast time-to-peak (T2) values for definite purpose circuit breakers
72.5 kV and below, including circuit breakers applied in gas insulated substations
Rated Transient
Recovery Voltage
(1)
Peak
Time to
Voltage E2
Peak T2
kV, peak
sec
Col 4
Col 5
Line
No.
Rated
Maximum
Voltage
kV, rms (1)
Col 1
Rated
Voltage
Range
Factor (1)
Col 2
Rated
Short-Circuit
and ShortTime Current
kA, rms (1)
Col 3
1
2
3
4
5
15.5
15.5
15.5
15.5
25.8
1.0
1.0
1.0
1.0
1.0
12.5
20
25
40
12.5
29
29
29
29
48.5
36
36
36
36
52
3.8
6.0
7.5
12.0
3.8
33
33
33
33
55
10
8
8
7
13
0.9
1.4
1.8
2.8
0.9
34
34
34
34
57
14
14
14
11
21
6
7
8
9
10
25.8
38.0
38.0
38.0
38.0
1.0
1.0
1.0
1.0
1.0
25
16
20
25
31.5
48.5
71
71
71
71
52
63
63
63
63
7.5
4.8
6.0
7.5
9.5
55
81
81
81
81
10
14
13
12
11
1.8
1.1
1.4
1.8
2.2
57
84
84
84
84
18
25
24
22
20
11
12
13
14
15
38.0
48.3
48.3
48.3
72.5
1.0
1.0
1.0
1.0
1.0
40
20
31.5
40
20
71
91
91
91
136
63
80
80
80
106
12.0
6.0
9.5
12.0
6.0
81
103
103
103
154
11
15
13
12
19
2.8
1.4
2.2
2.8
1.4
84
106
106
106
159
18
28
23
21
35
16
17
72.5
72.5
1.0
1.0
31.5
40
136
136
106
106
9.5
12.0
154
154
16
15
2.2
2.8
159
159
28
25
Note
(1)
See Table 2 of C37.06 for circuit breaker ratings.
Line
No.
Rated
Maximum
Voltage
kV, rms (1)
Col 1
Rated
Voltage
Range
Factor (1)
Col 2
Rated
Short-Circuit
and ShortTime Current
kA, rms (1)
Col 3
1
2
3
4
5
123
123
123
145
145
1.0
1.0
1.0
1.0
1.0
20
40
63
20
40
216
216
216
255
255
275
260
260
330
310
6
12
19
6
12
245
245
245
288
288
28.3
23.5
21.4
30.9
25.8
1.4
2.8
4.4
1.4
2.8
253
253
253
299
299
48.7
36.5
31.0
53.4
40.0
6
7
8
9
10
145
145
170
170
170
1.0
1.0
1.0
1.0
1.0
63
80
16
31.5
40
255
255
299
299
299
310
310
395
360
360
19
24
8
9.5
12
288
288
338
338
338
23.5
22.6
35.2
29.1
27.8
4.4
5.6
1.1
2.2
2.8
299
299
350
350
350
34.0
31.2
63.4
47.0
43.2
11
12
13
14
15
170
170
245
245
245
1.0
1.0
1.0
1.0
1.0
50
63
31.5
40
50
299
299
431
431
431
360
360
520
520
520
15
19
9.5
12
15
338
338
487
487
487
26.4
25.4
34.8
33.3
31.6
3.5
4.4
2.2
2.8
3.5
350
350
505
505
505
35.7
36.7
56.2
51.6
47.4
16
17
18
19
20
245
362
362
550
550
1.0
1.0
1.0
1.0
1.0
63
40
63
40
63
431
637
637
968
968
520
775
775
1325
1325
19
12
19
12
19
487
720
720
1094
1094
30.3
40.7
37.1
49.0
44.7
4.4
2.8
4.4
2.8
4.4
505
745
745
1133
1133
43.8
63.2
55.7
76.1
63.9
21
22
800
800
1.0
1.0
40
63
1408
1408
1530
1530
12
19
1591
1591
60.7
55.3
2.8
4.4
1647
1647
94.1
79.9
Note
(1) See Table 3 of C37.06 for circuit breaker ratings.
Authorized licensed use limited to: UNIVERSIDAD DE GUANAJUATO. Downloaded on March 16,2016 at 17:48:46 UTC from IEEE Xplore. Restrictions apply.