SM6 range
3 to 24 kV
Presentation
The experience of a world leader
The ranges advantages
The references of a leader
Quality assurance
Schneider Electric
6
8
14
15
16
18
20
24
25
26
28
42
43
46
47
48
50
51
52
53
Connections
Connections selection table
Cable-connection from below
55
56
Cable-connection height
Trenches depth
Trench diagrams example
56
57
58
Installation
Dimensions and weights
Units dimensions
Layout examples
Protecting the environment
A full range of services
60
61
63
64
65
Installation
Appendices
Trip curves for VIP 300 LL or LH relays
Trip curves for VIP 200 and VIP 201 relays
Trip curves for VIP 35 relays
Fusarc CF fuses - Fuse and limitation curves
Solefuse fuses - Fuse and limitation curves
Personal notes
66
67
68
69
70
71
Characteristics of
th f
ti
l
it
SM6 range
SM6 range
Field of application
Units for all functions
Conditions dexploitation
Main characteristics
Factory-built cubicles description
Compartments description
Safety of people
Telecontrol of power distribution networks
A range of FPIs for underground networks
Description of the control/monitoring and protection functions
Appendices
2
3
4
5
Presentation
Contents
Connections
SM6 range
3 to 24 kV
Presentation
MT20140
MT20141
1975: innovation
Sulphur hexafluoride (SF6) is first used in an MV switch for an MV/LV
transformer substation, with the VM6.
1989: experience
Over 300,000 VM6 cubicles equipped networks throughout the world.
1991: innovation and experience
Cumulated with the second generation of SM6 modular SF6 cubicles.
2001: a leading position
b with over 400,000 SM6 cubicles installed around the world,
Schneider Electric consolidates its position as uncontested leader
in the Medium Voltage field.
b development of the offer with the arrival of a range of vacuum type
circuit breaker cubicles.
Schneider Electric
MT20142
Upgradability
SM6, a comprehensive range
b a comprehensive offer covering your current and future requirements;
b a design adapted to the extension of your installations;
b a catalogue of functions for all your applications;
b a product designed to be in compliance with standards constraints;
b options to anticipate the telecontrol of your installations.
MT20143
Compactness
SM6, an optimised range
b compact units, with low increment cubicles;
b rationalised space requirement for switchboard installation;
b reduction of civil works costs;
b easy integration in factory-built outdoor substations for which the SM6
is particularly well designed.
MT20144
Maintenance
SM6, a range with reduced maintenance
b the active parts (breaking and earthing) are integrated in an SF6-filled,
sealed for life unit;
b the control mechanisms, are intented to function with reduced
maintenance under normal operating conditions;
b enhanced electrical endurance when breaking.
MT20145
Ease of installation
SM6, a simple range to incorporate
b reduced dimensions and weights;
b only one civil works layout;
b a solution adapted to cable connection;
b simplified switchboard busbar design.
MT20146
MT20147
MT20148
Schneider Electric
Presentation
Presentation
Presentation
Asia/Middle East
b Pasteur Institute, Cambodia
b Tian he City, China
b Sanya Airport, China
b Bank of China, Beijing, Jv Yanta, China
b Jing Guang Hotel, JGH, China
b Plaza Hotel, Jakarta, Indonesia
b Bali Airport, Indonesia
b Wakasa Control Center, Japan
b Otaru Shopping center, Japan
b New City of Muang, Thong Than, Kanjanapas,
Thailand
b Danang and Quinhon Airport, Vanad, Vietnam
b British Embassy, Oman
b KBF Palace Riyadh, Saudi Arabia
b Raka Stadium, Saudi Arabia
b Bilkent University, Turkey
b TADCO, BABOIL development, United Arab Emirates
Africa
b ONAFEX, Hilton Hotel, Algeria
b Yaounde University, Cameroon
b Karoua Airport, Cameroon
b Libreville Airport, Gabon
b Ivarto Hospital, CORIF, Madagascar
b Central Bank of Abuja, ADEFEMI, Nigeria
b OCI Dakar, Oger international, CGE, Senegal
b Bamburi cement Ltd, Kenya
b Ivory Electricity Company, Ivory Coast
South America/Pacific
b Lamentin Airport, CCIM, Martinique
b Space Centre, Kourou, Guyana
b Mexico City Underground System, Mexico
b Santiago Underground System, Chile
b Cohiba Hotel, Havana, Cuba
b Iberostar Hotel, Bavaro, Dominican Republic
b Aluminio Argentino Saic SA, Argentina
Europe
b EDF, France
b Eurotunnel, France
b Futuroscope, Poitiers, France
b Franois Mitterrand Library, France
b Nestl company headquarters, France
b Stade de France, Paris, France
b Kronofrance, France
b TLM Terminal , Folkestone, Great Britain
b Zaventem Airport, Belgium
b Krediebank Computer Centre, Belgium
b Bucarest Pumping station, Rumania
b Prague Airport, Czech Republic
b Philipp Morris St Petersburg, Russia
b Ligget Ducatt Tobacco Factory, Russia
b Kremlin Moscow, Russia
b Allibert Tarazona, Spain
Schneider Electric
Presentation
Quality assurance
A major advantage
MT55055
MT55054
61002N
61003N
Schneider Electric
Presentation
SM6 range
Field of application
MT20149EN
UTE standard
MV consumer substation
(MV metering)
IM
IM
CM
DM2
QM
PM
IM
incoming
line of
the main
distribution switchboard
MV consumer substation
(LV metering)
IM
IM QM
Substation
GAM
QM
Unit definitions
Below is the list of SM6 range units used in MV/LV
transformer substations and industrial distribution
substations:
b IM, IMC, IMB switch;
b EMB busbar earthing;
b PM fused switch;
b QM, QMC, QMB fuse-switch combination;
b CRM contactor and contactor with fuses;
b DM1-A, DM1-D, DM1-S single-isolation
SF6 type circuit breaker;
b DMV-A, DMV-D, DMV-S single-isolation
vacuum type circuit breaker;
b DM1-W, DM1-Z withdrawable single-isolation
SF6 type circuit breaker;
b DM2 double-isolation SF6 type circuit breaker;
b CM, CM2 voltage transformers;
b GBC-A, GBC-B current and/or voltage
measurements;
b NSM-cables for main incoming and standby;
b NSM-busbars for main incoming and cables
for standby;
b GIM intermediate bus unit;
b GEM extension unit;
b GBM connection unit;
b GAM2, GAM incoming cable connection unit;
b SM disconnector;
b TM MV/LV transformer unit for auxiliaries;
b other units, consult us.
Other standards
MV consumer substations
(MV metering)
IM
IM
DM1-D
GBC-A
QM
DM1-S
Schneider Electric
SM6 range
MT20150EN
CM
QMC
IM
IM
DM1-D
GBM DM1-A
QMC
CM
incoming line
of private MV substation
incoming line
of private MV substation
NSM-busbars GBM SM
TM
NSM-cables QM
standby
generator source
standby
utility source
Distribution switchboard
CM
QM
QM
IMC
incoming line
of private MV substation
Schneider Electric
IMB
GBM IMC
QM
CM
incoming line
of private MV substation
SM6 range
Field of application
SM6 range
28
Switch unit
IM (375 or 500 mm)
MT20153
MT20152
MT20151
page
Switch unit
IMC (500 mm)
Switch unit
with or without
earthing disconnector
right or left outgoing line
IMB (375 mm)
MT20154
Fuse-switch protection
30
Fuse-switch
combination unit
QM (375 mm)
MT20157
MT20156
Fused-switch unit
PM (375 mm)
MT20155
29
Fuse-switch
combination unit
QMC (625 mm)
Fuse-switch
combination unit
right or left outgoing line
QMB (375 mm)
Schneider Electric
SM6 range
Contactor protection
SM6 range
MT20159
MT20158
page
31
Contactor unit
CRM (750 mm)
Fused-contactor unit
CRM (750 mm)
33
Schneider Electric
Single-isolation
circuit breaker unit
right or left outgoing line
DM1-D (750 mm)
MT20163
Single-isolation
circuit breaker unit
DM1-A (750 mm)
MT20162
32
MT20161
MT20160
Single-isolation
circuit breaker unit with
autonomous protection
DM1-S (750 mm)
Double-isolation
circuit breaker unit
right or left outgoing line
DM2 (750 mm)
SM6 range
34
MT20165
MT20164
page
Withdrawable single-isolation
circuit breaker unit
DM1-W (750 mm)
Withdrawable single-isolation
circuit breaker unit
right outgoing line
DM1-Z (750 mm)
Single-isolation
circuit breaker unit
DMV-A (625 mm)
Single-isolation
circuit breaker unit
right outgoing line
DMV-D (625 mm)
MT20168
35
MT20167
MT20166
36
10
Single-isolation
circuit breaker unit with
autonomous protection
DMV-S (625 mm)
Schneider Electric
SM6 range
MV metering
37
Schneider Electric
SM6 range
MT20172
MT20171
36
MT20170
MT20169
page
11
SM6 range
Casings
39
12
MT20175
Extension unit
VM6/SM6
GEM (125 mm)
Connection unit
right or left outgoing line
GBM (375 mm)
MT20177
MT20176
38
MT20173
MT20173
page
Incoming
cable-connection unit
GAM2 (375 mm)
Incoming
cable-connection unit
GAM (500 mm)
Schneider Electric
SM6 range
Other functions
SM6 range
MT20180
MT20179
MT20178
page
41
Schneider Electric
Busbar earthing
compartment
EMB (375 mm)
MT20182
Disconnector unit
SM (375 or 500 mm)
MT20181
40
13
Operating conditions
61000N
SM6 range
Standards
SM6 units meet all the following recommendations, standards and specifications:
b recommendations:
IEC 60298, 60265, 60129, 60694, 60420, 60056, 61958;
b UTE standards:
NFC 13.100, 13.200, 64.130, 64.160;
b EDF specifications:
HN 64-S-41, 64-S-43.
Designation
SM6 units are identified by a code including:
b an indication of the function, i.e. the electrical diagram code: IM, QM, DM1, CM,
DM2, etc.
b the rated current: 400 - 630 - 1250 A;
b the rated voltage: 7.2 - 12 - 17.5 - 24 kV;
b the maximum short-time withstand current values:
12.5 - 16 - 20 - 25 kA.1 s;
b the colour is of RAL 9002 type (frosted satin white).
Example for a unit designated: IM 400 - 24 - 12.5
b IM indicates an incoming or outgoing unit;
b 400 indicates the rated current is 400 A;
b 24 indicates the rated voltage is 24 kV;
b 12.5 indicates the short-time withstand current is 12.5 kA.1 s.
14
Schneider Electric
61005N
Main characteristics
25
20
16
12.5
7.2
12
17.5
24
20
23
60
70
28
32
75*
85
38
45
95
110
50
60
125
145
16
25
630 - 1250 A
630 - 1250 A
630 - 1250 A
400 - 630 - 1250 A
SM6 range
SM6 range
The making capacity is equal to 2.5 times the short-time withstand current.
* 60 kV peak for the CRM unit.
General characteristics
7.2
12
17.5
24
630 A
25 kA
10 kA
25 kA
20 kA
8 kA
12.5 kA
25 kA
20 kA
25 kA
20 kA
Endurance
Units
Electro-magnetic compatibility:
b relays: 4 kV withstand capacity,
as per recommendation IEC 60801.4;
b compartments:
v electrical field:
- 40 dB attenuation at 100 MHz,
- 20 dB attenuation at 200 MHz;
v magnetic field: 20 dB attenuation below 30 MHz.
Temperatures:
The cubicles must be stored in a dry area free
from dust and with limited temperature variations.
b for stocking: from -40C to +70C,
b for working: from -5C to +40C,
b other temperatures, consult us.
mechanical
endurance
IEC 60265
1000 operations
class E3
electrical
endurance
IEC 60265
100 breaks
at In, p.f. = 0.7
class M1
IEC 60056
100000 breaks at 320 A
300000 breaks at 250 A
100000 breaks at 200 A
IEC 60056
40 breaks at 12.5 kA
10000 breaks
at In, p.f. = 0.7
IEC 60056
100 breaks at 25 kA
Schneider Electric
15
SM6 range
2
1
2 busbars: all in the same horizontal plane, thus enabling later switchboard
extensions and connection to existing equipment.
4 operating mechanism: contains the elements used to operate the switchdisconnector and earthing switch and actuate the corresponding indications
(positive break).
5 low voltage: installation of a terminal block (if motor option installed), LV fuses and
compact relay devices.
If more space is required, an additional enclosure may be added on top of the cubicle.
Optional, switch cubicles (IM) can also be fitted with:
b control motorisation;
b surge arrestors.
2
1
16
Schneider Electric
SM6 range
satisfying and one vacuum circuit breaker, sealed pressure system requirements.
2 busbars: all in the same horizontal plane, thus enabling later switchboard
extensions and connection to existing equipment.
5
4
Contactor cubicles
61056N
2
1
Schneider Electric
17
SM6 range
2
1
SM6 range
Compartments description
61006N
MT20187
Switchgear compartment
This compartment is separated from the busbar compartment and the connection
compartment by the enclosure surrounding the switch, the disconnector and
the earthing switch.
61007N
MT20188
Busbar compartment
The three insulated busbars are parallel-mounted. Connection is made to the upper
pads of the enclosure using a field distributor with integrated captive screws.
Ratings 400 - 630 - 1250 A.
MT20189
MT20200
18
Schneider Electric
SM6 range
Compartments description
Low-voltage compartment
MT20202
SM6 range
61008N
MT20201
Operating-mechanism compartments
This compartment enables the cubicle to be equipped with low voltage switchgear
providing protection, control, status indication and data transmission.
This compartment is available in 3 versions: cover, compartment and housing.
B
A
In all cases, these volumes are accessible, with cables and busbars energised,
without de-energising the substation.
61009N
A - Cover
B - Compartment
h = 1600 mm h = 1690 mm
Schneider Electric
19
SM6 range
Safety of people
By switchgear
b Gas tightness
The three rotating contacts are placed in an enclosure filled with gas to a relative
pressure of 0.4 bar (400 hPa). It satisfies sealed pressure system requirements
and seal tightness is always checked in the factory.
b Operating safety
v the switch may be in one of three positions: closed, open, or earthed,
representing a natural interlocking system that prevents incorrect operation.
Moving-contact rotation is driven by a fast-acting mechanism that is independent
of the action of the operator.
v the device combines the breaking and disconnection functions.
v the earthing switch placed in the SF6 has a short-circuit making capacity,
in compliance with standards.
v any accidental over-pressures are eliminated by the opening of the safety membrane,
in which case the gas is directed toward the back of the unit, thus avoiding projection
or other related phenomena in front.
MT20184
Switch-disconnector
Contacts closed
Contacts open
Contacts earthed
b Gas tightness
The three phases are placed in an enclosure filled with SF6 gas to a relative pressure
of 2.5 bars (2500 hPa). It satisfies sealed pressure system requirements and seal
tightness is always checked in the factory.
MT20185
b Operating safety
Accidental over-pressures are eliminated by the opening of the safety membrane.
Rollarc contactor
Contacts closed
20
Main contacts
separated
Arcing period
Contacts open
Schneider Electric
SM6 range
Safety of people
By switchgear
b Gas tightness
The SF1 or SFset circuit breaker is made up of three separate poles mounted
on a structure supporting the operating mechanism. Each pole-unit houses
all the active elements in an insulating enclosure filled with gas to a relative pressure
of 0.5 bar (500 hPa). It satisfies sealed pressure system requirements and seal
tightness is always checked in the factory.
SM6 range
MT20186
b Operating safety
As for switch-units, accidental over-pressures are eliminated by the opening
of the safety membrane.
Contacts closed
Precompression
Arcing period
Contacts open
b Gas tightness
The Evolis circuit breaker comprises three separate pole units fixed on a structure
supporting the control mechanism. Each pole encloses all of the active parts in an
insulating enclosure, under vacuum, and its gas tightness is systematically checked
in the factory.
b Operating safety
v the magnetic field is applied along the contact axis of the vacuum type
circuit breaker.
This process diffuses the arc in a regular manner with high currents.
It ensures optimum distribution of the energy along the compact surface
so as to avoid local hot spots.
The advantages of this technique:
v a simplified vacuum type circuit breaker which is consequently very reliable,
v low dissipation of arcing energy in the circuit breaker,
v highly efficient contacts which do not distort during repeated breaking,
v significant reduction in control energy.
Schneider Electric
21
SM6 range
Safety of people
By operating mechanism safety
22
Schneider Electric
SM6 range
Safety of people
By internal arc protection
Consequently:
The SM6 is designed to offer a good level of safety
SM6 range
MT20299
MT20298
Choice of exhaust
The choice depends on the civil engineering:
b Upwards exhaust:
A ceiling height greater than 2300 mm is necessary.
b Downwards exhaust:
Civil engineering with an adequate volume is necessary.
Schneider Electric
23
SM6 range
Telecontrol
of power distribution networks
SM6 switchgear is perfectly suited to a telecontrol environment due to options such as:
b Easergy T200 I telecontrol interface;
b independent power supply of electrical controls;
b auxiliary contacts for position and fault signalling;
b current sensors for fault detection.
61015N
Control command
24
Foolproof connectors
Local information
61021N
61020N
61019N
61018N
61017N
Ready to connect
b Easergy T200 I is delivered with a kit for easy connection to motorization and data
acquisition terminals.
b the telecontrol unit connectors are foolproof to avoid any errors during installation
or maintenance.
b data acquisition core balance CTs for current measurement are of the opening
type for easier installation.
Power unit
Schneider Electric
SM6 range
The Easergy FPI range completes the expertise and leadership of Merlin Gerin
in the MV field.
It is the widest range available on the market place and covers all types of MV
networks with their neutral grounding arrangements. Holding several key patents in
this technology, Merling Gerins Easergy directional or ammeter FPIs are available
for both overhead and underground MV lines, with various power supplies and
packages. Backed by Schneider Electric international organization and experience
of 40 years in Medium Voltage applications, Easergy puts its know how at the service
of utilities striving for a better quality.
61022N
Bright outdoor
The Easergy range is designed for the tracking of permanent faults on MV cable
networks. Thanks to an ammeter or directional fault detection scheme it covers the
needs of all types of MV networks. Available in weatherproof or non-weatherproof
enclosures, LV battery back, DC, or battery-only power supplies, the Easergy range
is very versatile and offers more than 15 versions.
Benefits
Thanks to its programmability, the lineman is sure to be able to select the tripping
parameters (current reset, timer reset, Low Voltage reset, manual reset) that match
the one of the protection devices on a given feeder.
Easergy F279
electronic detector unit
MV telecontrol system
All members of the Easergy family come equipped with a dry contact output for
connection to a Remote Terminal Unit as Easergy T200 I Merlin Gerin, capable
of tele-signalling the passage of the fault current. In addition, a cost-effective
tele-signalling device is available.
MV/LV substation
MV/LV substation
MT20183EN
MV/LV substation
Flashing
Flashing
Not flashing
MV feeder substation
The fault is located here
Schneider Electric
25
SM6 range
Usage
SM6 range
61023N
Sepam 1000+
Sepam 2000
Sepam 1000+
The Sepam 1000+ is suited to applications such as:
b substation;
b transformer;
b motor;
b busbar.
It allows measurement of current or voltage. It has a pre-programmed, settable
control logic. As an option it has a ModBus communication module.
Sepam 2000
The Sepam 2000 is adapted to all types of applications:
b substation;
b transformer;
b motor;
b busbar;
b capacitor;
b generator.
It enables the measurement of current and voltage (and therefore power and energy).
It has a pre-programmed settable control logic which is entirely programmable
(in ladder form) enabling all automatic control functions to be handled.
61024N
61025N
26
Schneider Electric
SM6 range
61026N
VIP 35
61028N
VIP 300 LL
Selection table
Protection type
Schneider Electric
three-phase overcurrent
zero-sequence overcurrent
directional zero-sequence current
undervoltage
overvoltage
thermal image
zero-sequence overvoltage
negative sequence overcurrent
long start-up and rotor blocking
maximum number of start-ups
single-phase undercurrent
Code
50 - 51
50N - 51N
67N
27
59
49
59N
46
51LR
66
37
Protection units
Sepam
Statimax
2000 1000+
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
VIP
200
b (1)
b (1)
201
b (1)
b (1)
35
b (2)
b (3)
300
b (1)
b (1)
27
SM6 range
Characteristics of
the functional units
MT20206
MT20205
MT20204
Electrical characteristics
MT20241
kA
25
20
630 A
16
12.5
400 - 630 A
7.2
12
17.5
24
kV
Basic equipment:
b switch and earthing switch
b three-phase busbars
b CIT operating mechanism
b voltage indicators
b connection pads for dry-type cables
Versions:
b CI2 operating mechanism
b CI1 operating mechanism
b 630 A or 1250 A three-phase busbars
Optional accessories:
b motor for operating mechanism
b auxiliary contacts
b additional enclosure or connection enclosure for cabling from above
b key-type interlocks
b 50 W heating element
b stands footing
b release units
b phase comparator
b fault indicators
b surge arrestors (for 500 mm cubicle)
28
Schneider Electric
Characteristics of
the functional units
MT20208
PM (375 mm)
Fused-switch unit
Electrical characteristics
Characteristics of
the functional units
MT20242
kA
25
20
200 A
16
12.5
7.2
12
17.5
24
kV
Basic equipment:
b switch and earthing switch
b three-phase busbars
b CIT operating mechanism
b voltage indicators
b connection pads for dry-type cables
b downstream earthing switch
b equipment for three UTE or DIN fuses
Versions:
b CI1 operating mechanism
b 630 A or 1250 A three-phase busbars
Optional accessories:
b motor for operating mechanism
b auxiliary contacts
b enlarged low-voltage compartment
b additional enclosure or connection enclosure for cabling from above
b key-type interlocks
b 50 W heating element
b stands footing
b mechanical indication system for blown fuses
b UTE or DIN fuses
b release units
Schneider Electric
29
Characteristics of
the functional units
MT20210
MT20209
QM (375 mm)
Fuse-switch
combination unit
Electrical characteristics
MT20242
kA
25
20
200 A
16
12.5
7.2
12
17.5
24
kV
Basic equipment:
b switch and earthing switch
b three-phase busbars
b CI1 operating mechanism
b voltage indicators
b equipment for three UTE or DIN striker fuses
b mechanical indication system for blown fuses
b connection pads for dry-type cables
b downstream earthing switch
b three-phase bottom
busbars for outgoing
lines (right or left)
b one to three CTs
Versions:
b 630 A or 1250 A three-phase busbars
b CI2 operating mechanism
Optional accessories:
b motor for operating mechanism
b auxiliary contacts
b additional enclosure or connection enclosure for cabling from above
b key-type interlocks
b 50 W heating element
b stands footing
b indication contact for blown fuses
b UTE or DIN striker fuses
b release units
30
Schneider Electric
Characteristics of
the functional units
MT20213
MT20212
Electrical characteristics
MT20244
MT20243
10
Characteristics of
the functional units
kA
kA
25
20
250 A
8
16
400 A
12.5
7.2
12
kV
7.2
12
kV
Basic equipment:
b Rollarc 400 or 400D contactor
b disconnector and earthing switch
b three-phase busbars
b contactor operating mechanism R400 with magnetic holding or contactor R400D with mechanical latching
b disconnector operating mechanism CS
b one to three current transformers
b auxiliary contacts on contactor
b connection pads for dry-type cables
b voltage indicators
b downstream earthing switch
b additional enclosure
b operation counter
b equipment for three DIN fuses
Version:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b cubicle:
v auxiliary contacts on the disconnector
v protection using Sepam programmable electronic unit
v one to three voltage transformers
v key-type interlocks
v 50 W heating element
v stands footing
b contactor:
v mechanical interlocking
b DIN fuses
Schneider Electric
31
Characteristics of
the functional units
MT20215
MT20214
Electrical characteristics
MT20245
kA
25
20
630 - 1250 A
16
12.5
12
17.5
24
kV
Basic equipment:
b SF1or SFset circuit breaker (only for the 400-630 A performances)
b disconnector and earthing switch
b three-phase busbars
b circuit breaker operating mechanism RI
b disconnector operating mechanism CS
b voltage indicators
b three CTs for SF1 circuit breaker
b auxiliary contacts on circuit breaker
b connection pads for dry-type cables
b downstream earthing switch
Version:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b cubicle:
v auxiliary contacts on the disconnector
v additional enclosure or connection enclosure for cabling from above
v protection using Statimax relays, or Sepam programable electronic unit for SF1 circuit breaker
v three voltage transformers for SF1 circuit breaker
v key-type interlocks
v 50 W heating element
v stands footing
v surge arrestors
b circuit breaker:
v motor for operating mechanism
v release units
v operation counter on manual operating mechanism
32
Schneider Electric
Characteristics of
the functional units
MT20218
MT20217
Electrical characteristics
Characteristics of
the functional units
MT20241
kA
25
20
630 A
16
12.5
400 - 630 A
7.2
12
17.5
24
kV
Basic equipment:
b SF1 circuit breaker
b disconnector and earthing switch
b three-phase busbars
b circuit breaker operating mechanism RI
b disconnector operating mechanism CS
b auxiliary contacts on circuit breaker
b three CR sensors for VIP relay protection
b voltage indicators
b connection pads for dry-type cables
b downstream earthing switch
b three CTs
Version:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b cubicle:
v auxiliary contacts on disconnectors
v additional enclosure or connection
enclosure for cabling from above
v three voltage transformers
v key-type interlocks
v 50 W heating element
v stands footing
b circuit breaker:
v motor for operating mechanism
v release units
v operation counter on manual operating mechanism
Schneider Electric
33
Characteristics of
the functional units
MT20221
MT20220
Electrical characteristics
kA
MT20246
MT20245
kA
25
25
20
20
1250 A
630 - 1250 A
16
16
12.5
12.5
12
17.5
24
kV
7.2
12
17.5
24
kV
Basic equipment:
b SF1 circuit breaker
b disconnector and earthing switch
b three-phase busbars
b circuit breaker operating mechanism RI
b disconnector operating mechanism CS
b voltage indicators
b three CTs
b auxiliary contacts on circuit breaker
b earthing switch operating mechanism CC
b connection pads for dry-type cables
b downstream earthing switch
b three-phase busbars
Version:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b cubicle:
v auxiliary contacts on the disconnector
v additional enclosure or connection
enclosure for cabling from above
v protection using Statimax relays
or Sepam programable electronic unit
v three voltage transformers
v key-type interlocks
v 50 W heating element
v stands footing
v withdrawable circuit breaker cradle
b circuit breaker:
v motor for operating mechanism
v release units
v operation counter on manual operating mechanism
v surge arrestors
34
Schneider Electric
Characteristics of
the functional units
MT20223
MT20222
Electrical characteristics
25
20
16
12.5
Characteristics of
the functional units
kA
MT20248
MT20247
kA
25
20
630 1250 A
630 A
16
17.5
12.5
kV
400 - 630 A
12
17.5
kV
Basic equipment:
b Evolis circuit breaker
b disconnector and earthing switch
b three-phase busbars
b circuit breaker operating mechanism Proxima
b disconnector operating mechanism CIT
b voltage indicators
b auxiliary contacts on circuit breaker
b Sepam programable electronic unit
b three CTs
Version:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b cubicle:
v auxiliary contacts on the disconnector
v additional enclosure or connection enclosure
for cabling from above
v three voltage transformers
v key-type interlocks
v stands footing
v surge arrestors
Schneider Electric
b circuit breaker:
v motor for operating mechanism
v release units
v operation counter on manual
operating mechanism
v surge arrestors
v protection by VIP relays
35
Characteristics of
the functional units
MT20226
MT20225
CM (375 mm)
Voltage transformers
for mains with earthed
neutral system
Electrical characteristics
MT20249
kA
25
20
50 A
16
12.5
7.2
12
17.5
24
kV
Basic equipment:
b disconnector and earthing switch
b three-phase busbars
b operating mechanism CS
b LV circuit isolation switch
b LV fuses
b three 6.3 A UTE or DIN type fuses
b three-voltage transformers
(phase-to-earth)
Version:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b auxiliary contacts
b additional enclosure or connection enclosure for cabling from above
b 50 W heating element
b stands footing
b indication contact for blown fuses
36
Schneider Electric
Characteristics of
the functional units
MT20229
MT20228
MT20227
Electrical characteristics
Characteristics of
the functional units
MT20245
kA
25
20
630 - 1250 A
16
12.5
12
17.5
24
kV
Basic equipment:
b one to three CTs
b connection bars
b three-phase busbars
Optional accessories:
b additional enclosure
b three voltage transformers (phase-to-earth), or two voltage transformers (phase-to-phase)
b stands footing
Schneider Electric
37
Characteristics of
the functional units
MT20231
MT20230
MT20230
Electrical characteristics
MT20241
kA
25
20
630 A
16
12.5
400 - 630 A
7.2
12
17.5
24
kV
Basic equipment:
b three-phase busbars
b connection bars
b three-phase busbars
for outgoing lines
right or left
Optional accessories:
b stands footing
b additional enclosure
38
Schneider Electric
Characteristics of
the functional units
MT20233
MT20232
Electrical characteristics
kA
25
20
25
Characteristics of
the functional units
MT20245
MT20241
kA
20
630 A
630 - 1250 A
16
16
12.5
12.5
400 - 630 A
7.2
12
17.5
24
kV
12
17.5
24
kV
Basic equipment:
b three-phase busbars
b voltage indicators
b connection pads for dry-type cables
b connection bars
b operating mechanism CC
b earthing switch
Optional accessories:
b enlarged low-voltage compartment
b key-type interlocks
b stands footing
b 50 W heating element
b auxiliary contacts
b surge arrestors
Schneider Electric
39
Characteristics of
the functional units
MT20236
MT20235
MT20234
TM (375 mm)
MV/LV transformer unit
for auxiliaries
Electrical characteristics
25
20
kA
MT20241
kA
MT20249
MT20245
kA
25
20
20
630 - 1250 A
50 A
16
12.5
12
17.5
25
24
kV
630 A
16
16
12.5
12.5
7.2
12
17.5
24
kV
400 - 630 A
7.2
12
17.5
24
kV
Basic equipment:
b disconnector and earthing switch
b three-phase busbars
b operating mechanism CS
b connection pads for dry-type cables
b voltage indicators
Version:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b auxiliary contacts
b auxiliary contacts
b additional enclosure
b key-type interlocks
b stands footing
b 50 W heating element
b connection enclosure for cabling from above
40
Schneider Electric
Characteristics of
the functional units
MT20238
MT20237
Electrical characteristics
Characteristics of
the functional units
MT20241
kA
25
20
630 A
16
12.5
400 - 630 A
7.2
12
17.5
24
kV
Basic equipment:
b manual version:
v switches and earthing switches
v three-phase busbars
v connection pads for dry-type cables
v voltage indicators
v mechanical interlocking
v operating mechanism CI2
b automatic version:
v switches and earthing switches
v three-phase busbars
v connection pads for dry-type cables
v voltage indicators
v mechanical interlocking
v motorised operating mechanism CI2 with 24 Vdc shunt trips
v additional enclosure
v automatic-control equipment
Version:
b 630 A or 1250 A three-phase busbars
Optional accessories:
b manual version:
v motor for operating mechanism
v release units
v auxiliary contacts
v additional enclosure
v key-type interlocks
v 50 W heating element
v stands footing
Schneider Electric
b automatic version:
v auxiliary contacts
v key-type interlocks
v 50 W heating element
v stands footing
41
Characteristics of
the functional units
Ua
MT20250
Ua
t
Us
Us
t
U
tr
T1
t
U
Fig. 2
T2
tr
Fig. 3
Ua
MT20251
Ua
t
Us
t
Us
t
U
T1
Fig. 4
T2
tr
t
tr
T3
Fig. 5
T4
42
Schneider Electric
Characteristics of
the functional units
Operating mechanisms
Units
61029N
b Switch function
Independent-operation opening or closing by lever or motor.
b Earthing-switch function
Independent-operation opening or closing by lever.
Operating energy is provided by a compressed spring which, when released,
provokes closing or opening of the contacts.
b Auxiliary contacts
v switch (2 O + 2 C),
v switch (2 O + 3 C) and earthing switch (1 O + 1 C),
v switch (1 C) and earthing switch (1 O + 1 C) if motor option.
b Mechanical indications
Fuses blown in unit PM.
b Motor option
b Switch function
v independent-operation closing by lever or motor.
Operating energy is provided by a compressed spring which, when released,
provokes closing of the contacts.
v independent-operation opening by push-button (O) or trip units.
b Earthing-switch function
Independent-operation closing and opening by lever.
Operating energy is provided by a compressed spring which, when released,
provokes closing or opening of the contacts.
b Auxiliary contacts
v switch (2 O + 2 C),
v switch (2 O + 3 C) and earthing switch (1 O + 1 C),
v switch (1 C) and earthing switch (1 O + 1 C) if motor option,
v fuses blown (1 C).
b Mechanical indications
Fuses blown in units PM, QM.
b Opening releases
v shunt trip,
v undervoltage for unit QM.
b Motor option
Schneider Electric
43
Characteristics of
the functional units
Operating mechanisms
b Switch function
v independent-operation closing in two steps:
1 - operating mechanism recharging by lever or motor,
2 - stored energy released by push-button (I) or trip unit.
v independent-operation opening by push-button (O) or trip unit.
b Earthing-switch function
Independent-operation closing and opening by lever.
Operating energy is provided by a compressed spring which, when released,
provokes closing or opening of the contacts.
b Auxiliary contacts
v switch (2 O + 2 C),
v switch (2 O + 3 C) and earthing switch (1 O + 1 C),
v switch (1 C) and earthing switch (1 O + 1 C) if motor option.
b Opening release shunt trip
b Closing release shunt trip
b Motor option
44
Schneider Electric
Characteristics of
the functional units
Operating mechanisms
61034N
SFset
combinations
1
2
3
b
b
b
b
61035N
Schneider Electric
45
Characteristics of
the functional units
Characteristics of
the functional units
Auxiliaries
(V)
(W)
(VA)
response time
undervoltage
pick-up
hold
response time
Closing release
shunt trip
response time
DC
24
48
110
125
220
AC (50 Hz)*
120 230
200
200
1 to 2 (s)
4 to 7 (s)
(W)
(VA)
(ms)
(W)
(VA)
(W)
(VA)
(ms)
(W)
(VA)
(ms)
200
250
300
300
300
400
750
280
550
50
40
400
750
35
160
4
45
200
250
300
300
300
55
arming time
Opening releases
Mitop (low energy)
response time
shunt trip
response time
undervoltage
pick-up
hold
response time
Closing release
shunt trip
response time
(V)
DC
24
(W)
(VA)
(s)
15
(W)
(ms)
3
30
(W)
(VA)
(ms)
85
(W)
(VA)
(W)
(VA)
(ms)
(W)
(VA)
(ms)
48
110
125
220
AC (50 Hz)*
120 230
300
380
15
180
45
160
280
550
50
40
10
55
85
180
65
46
Schneider Electric
Characteristics of
the functional units
The MCH unit arms and rearms the energy storage springs as soon as
the circuit breaker is closed. This enables instant reclosing of the device
after opening. The arming lever is only used as back up control in the absence
of an auxiliary voltage.
The MCH is equipped as standard with a CH limit switch.
This contact indicates the armed position of the mechanism (spring armed).
Characteristics
power supply Vac 50/60 Hz
Vdc
threshold
consumption (VA or W)
motor overcurrent
arming time
switching rate
mechanical endurance
CH contact
48/60
100/130
200/240
24/30
48/60
100/125
200/250
0.85 to 1.1 Un
180
2 to 3 In during 0.1 s
4 s max.
3 cycles per minute max.
10000 remote controlled opening operations Evolis P1
10 A at 240 V
UC1
UC2
UC3
UC4
M2C
SDE2 SDE1
/RES
This specific coil actuates the opening mechanism of the poles to trip the circuit
breaker. It comprises a low energy consumption electromagnet.
Characteristics
power supply
direct current
threshold
0.6 A < I < 3 A
response time
of the circuit breaker at Un 11 ms
Any tripping caused by the Mitop release is indicated momentarily by an SDE type
changeover contact. This release unit also includes a coil enabling the remote
rearming of the SDE contact.
Comment: to use the MITOP release requires the adjustment of a time delay to be set
by the protection relay in order to ensure a circuit breaker operating time of 45-50 ms.
Schneider Electric
24/30
48/60
24/30
48/60
0.7 to 1.1 Un
pick-up: 200
hold: 4.5
50 ms 10
100/130
100/130
200/250
200/250
47
Characteristics of
the functional units
MT55166
Characteristics of
the functional units
Current transformers
Transformer ARM2/N2F
b single primary winding;
b double secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
I1n (A)
50
75
Ith (kA)
12.5
16
t (s)
1
measurement 5 A 7.5 VA - class 0.5
and protection 1 A 1 VA - 10P30
5 A 10 VA - 5P10
100
25
150
25
400
25
600
25
100
8
200
12.5
Transformer ARM1/N1F
b single primary winding;
b single secondary winding for measurement or protection.
Short-time withstand current Ith (kA)
I1n (A)
15
20
Ith (kA)
1.2
1.6
t (s)
1
measurement 5 A 15 VA - class 0.5
or protection
5 A 5 VA - 5P15
25
2
50
4
Transformer ARJP1/N2F
b single primary winding;
b double secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
I1n (A)
50
100
Ith (kA)
4
10
t (s)
1
measurement 5 A 7.5 VA - class 0.5
and protection 5 A 5 VA - 5P10
150
200
61041N
5 VA - 5P15
* for 5 A protection
48
7.5 VA - 5P15
15 VA - 5P10
Schneider Electric
Characteristics of
the functional units
Current transformers
61042N
200
400
600
15 VA
class 0.5
5 VA
5P20
15 VA
class 0.5
5 VA
5P20
15 VA
class 0.5
5 VA
5P20
15 VA
class 0.5
5 VA
5P20
20 VA
class 0.5
7.5 VA
5P20
20 VA
class 0.5
7.5 VA
5P20
61042N
Transformer ARJP2/N2F
b single primary winding;
b double secondary winding for measurement and protection.
Short-time withstand current Ith (kA)
I1n (A)
600
750
Ith (kA)
25
t (s)
1
measurement 1 A 20 VA - class 0.5
and protection 1 A 7.5 VA - 5P20
measurement 5 A 20 VA - class 0.5
and protection 5 A 7.5 VA - 5P20
61044N
Schneider Electric
49
Characteristics of
the functional units
Voltage transformers
24
10/3
100/3
250
0.5
30
15/3
15-20/3 20/3
30
30
30-50
17.5
10/3
100/3
250
0.5
30
15/3
24
10
100
500
0.5
50
15
20
15
20
2500
4000
2500
4000
For unit TM
61047N
24
10
220
2500
Surge arrestor
For units IM500, DM1-A, DM1-W, GAM, DMV-A*, DMV-S*
In (A) (unit)
Un (kV) (unit)
400/630
7.2
10
12
17.5
24
Note: the rated voltage of the surge arrestor is according to units rated voltage.
(*) limited up to 17.5 kV for DMV-A and DMV-S circuit breaker cubicles.
50
Schneider Electric
Transformers protection
By fused switch
35
MT55097
55
450
35
6
23
45
33
33
6
23
(mm)
55
weight
(kg)
2
(mm)
86
50.5
57
78.5
50.5
57
78.5
86
weight
(kg)
3.3
1.2
1.5
2.8
1.6
2.2
4.1
5.3
(mm)
85
85
67
85
85
85
85
85
weight
(kg)
3.8
3.8
2
3.8
3.8
5.4
5.4
5.4
L
(mm)
292
292
292
292
292
442
442
442
Selection table
The color code is linked to the rated voltage of the fuse.
Rating in A - no overload at -5C < t < 40C.
Please consult us for overloads and operation over 40C.
Type of
fuse
Service
Transformer rating (kVA)
voltage
25
50
100 125 160
(kV)
Solefuse (UTE NFC standards 13.100, 64.210)
5.5
6.3 16
31.5 31.5 63
10
6.3 6.3 16
16
31.5
15
6.3 6.3 16
16
16
20
6.3 6.3 6.3 6.3 16
Solefuse (general case, UTE NFC standard 13.200)
3.3
16
16
31.5 31.5 31.5
5.5
6.3 16
16
31.5 31.5
6.6
6.3 16
16
16
31.5
10
6.3 6.3 16
16
16
13.8
6.3 6.3 6.3 16
16
15
6.3 6.3 16
16
16
20
6.3 6.3 6.3 6.3 16
22
6.3 6.3 6.3 6.3 16
Fusarc CF (DIN standards)
3.3
16
25
40
50
50
5.5
10
16
31.5 31.5 40
6.6
10
16
25
31.5 40
10
6.3 10
16
20
25
13.8
6.3 10
16
16
20
15
6.3 10
10
16
16
20
6.3 6.3 10
10
16
22
6.3 6.3 10
10
10
Schneider Electric
800
Rated
1000 1250 1600 2000 2500 voltage
(kV)
200
250
315
400
500
630
63
31.5
16
16
63
31.5
16
16
63
63
43
16
63
63
43
43
63
43
43
63
43
43
43
43
63
63
31.5
31.5
16
16
16
16
63
63
43
31.5
16
16
16
16
100
63
43
31.5
31.5
31.5
16
16
100
80
63
43
31.5
31.5
31.5
16
80
80
43
31.5
31.5
31.5
31.5
100
100
63
43
43
31.5
31.5
125
125
80
63
43
43
31.5
125
80
63
63
43
43
100
80
80
63
63
80
50
50
31.5
25
20
16
16
80
50
50
40
31.5
25
25
20
100
63
63
50
31.5
31.5
25
25
125
80
80
50
40
40
31.5
25
125
100
80
63
50
50
40
31.5
160
125
100
80
50
50
40
40
200
125
125
80
63
63
50
40
160
125
100
80
80
50
50
160
160
100
80
80
63
50
7.2
63
43
63
24
7.2
12
17.5
24
63
7.2
125
100
100
80
80
200
125
125
100
80
125
125
125
100
12
17.5
24
51
Characteristics of
the functional units
Characteristics of
the functional units
Characteristics of
the functional units
Selection of fuses
Example:
Consider a 950 kW motor at 5 kV.
P
In = --------------------------------- = 130A
3 U pf
Id = 6 x In = 780 A
Then select the next higher value, i.e. 790 A.
For six 5-second starts per hour, select fuses
rated 200 A.
Note: the same motor could not be protected for 12 starts
per hour since the maximum service voltage for the required
250 A rated fuses is 3.3 kV.
1410
1290
1140
1030
890
790
710
640
610
540
480
440
310
280
250
240
230
210
180
170
Maximum service
voltage (kV)
20
12
250
250
250
250
250
200
200
200
200
160
160
160
160
125
125
125
125
100
100
100
250
250
250
250
250
200
200
200
200
160
160
160
160
125
125
125
100
250
250
250
250
250
200
200
200
200
160
160
160
160
125
125
125
125
100
100
250
250
250
250
250
200
200
200
200
160
160
160
160
125
125
125
125
100
100
250
250
250
250
250
200
200
200
200
160
160
160
160
125
125
125
100
100
250
250
250
250
250
200
200
200
200
160
160
160
160
125
125
125
100
100
5.5
2590
240
1060
3.3
6.6
11
6
2830
260
1155
6.6 10
11
3110 4710 5180
285 435 480
1270
Access to fuses
Access is via the front with the front panel removed.
Fuses may be removed without tools by simply pulling them forward.
The field deflector pivots and automatically returns to its position.
Replacement of fuses
When fault clearance results in one or two blown fuses, it is still common practice
to replace only the blown fuses.
However, though the remaining fuse(s) may apparently be in good condition,
their operating characteristics are generally reduced due to the short-circuit.
If non-blown fuses remain in service, they may blow even at very low
over-current values.
In systems where continuity of service is of importance, it is recommended
to replace all three fuses, in compliance with IEC recommendation 60282.1.
Please note: all three fuses must come from the same range:
Fusarc or Fusarc CF (they have different fusion curves).
52
Schneider Electric
Characteristics of
the functional units
Interlocks
Switch units
Functional interlocks
These comply with IEC recommendation 60298 and EDF specification HN 64-S-41.
Circuit-breaker units
units
Unit interlock
interlock
A1 A3 A4
b
b
b
C1
C4
P1
b
P2
P3
P5
b
b
b
b
Key-type interlocks
A1 type
O
MT20252
Characteristics of
the functional units
Outgoing units
Aim:
b to prevent the closing of the earthing switch on a transformer protection unit
unless the LV circuit breaker is locked in open or disconnected position.
b to prevent the access to the transformer if the earthing switch for transformer
protection has not first been closed.
MT20253
C1 type
MT20254
C4 type
b to prevent the closing of the earthing switch on a transformer protection unit unless
the LV circuit breaker is locked in open or disconnected position.
b to prevent the access to the transformer if the earthing switch for transformer
protection has not first been closed.
S
O
MT20240EN
Schneider Electric
no key
free key
captive key
panel or door
53
Characteristics of
the functional units
Interlocks
A3 type
Ring units
MT20255
Aim:
b to prevent the closing of the earthing switch of a load-side cubicle
unless the line-side switch is locked open.
O
A4 type
MT20256
P1 type
MT20257
b to prevent the closing of an earthing switch if the switch of the other unit
has not been locked in the open position.
P2 type
MT20258
b to prevent on-load operation of the disconnector unless the switch is locked open;
b to prevent the closing of the earthing switches unless the disconnector and
the switch are locked open.
P3 type
MT20259
AX
b to prevent on-load operation of the disconnector unless the switch is locked open;
b to prevent the closing of the earthing switches with the unit energised, unless
the disconnector and the switch are locked open;
b to allow off-load operation of the switch.
MT20260
P5 type
b to prevent the closing of the earthing switch of the incoming unit unless
the disconnector and the switch is locked open.
MT20240EN
54
no key
free key
captive key
panel or door
Schneider Electric
Connections
61048N
X-section mm2
50 to 300 mm2
3 to 24 kV
1250 A
round connector
50 to 630 mm2
square connector
> 300 mm2
admissible
Supplier
all cold fitted cable end
suppliers: Silec, 3M, Pirelli,
Raychem, etc.
all cold fitted cable end
suppliers: Silec, 3M, Pirelli,
Raychem, etc.
Number of cables
1 or 2 per phase
1 or 2 per phase
400 mm2
400 < 1 630 mm2
per phase
Comments
for larger x-sections, more
cables and other types of
lugs, please consult us
for larger x-sections, more
cables and other types of
lugs, please consult us
Performance
3 to 24 kV
400 A - 630 A
Lug type
round connector
X-section
50 to 300 mm2
3 to 24 kV
1250 A
round connector
50 to 630 mm2
Supplier
all cold fitted cable end
suppliers: Silec, 3M, Pirelli,
Raychem, etc.
all cold fitted cable end
suppliers: Silec, 3M, Pirelli,
Raychem, etc.
Number of cables
1 per phase
1 per phase
Comments
for larger x-sections, more
cables and other types of
lugs, please consult us
for larger x-sections, more
cables and other types of
lugs, please consult us
Note:
b the lugs, covered by a field distributor, can be square;
b PM/QM type cubicle, round end connections 30 mm max.
Schneider Electric
55
Connections
Connections
Cable-connection height H
measured from floor (mm)
IM,NSM-cables, NSM-busbars
SM
IMC
PM, QM
QMC
CRM
DM1-A SF1
DM1-A SFset, DM1-S
DMV-A, DMV-S
DM1-W
GAM2
GAM
1250 A
630 A
950
950
450
400
340
430
370
430
324
360
760
470
MT20261
IM,NSM-cables, NSM-busbars, SM
950
650
324
650
200 200
420
200 200
420
620
MT20265
GAM
MT20264
GAM2
MT20263
CRM
200 200
420
200 200
420
MT20267
MT20266
200 200
420
H
185 185
312
338
200 200
420
789
330
200 200
420
56
Schneider Electric
Connections
Cabling
from above
Cables position
in front
Single-core cables
bending
cable
x-section radius
(mm)
(mm2)
625
500
375
50
70
95
120
150
185
240
400
630
MT20273
61049N
370
400
440
470
500
540
590
800
940
1250 A units
PM,
SM,
DM1-A(3)
QM,
GAM DM1-W(3)
QMC(2)
DMV-A
P3
350
350
350
P4
P5
1000
1000
1350
1350
187.5
630 A units
100
DM1-A, DM1-W
for single and tri-core cables
MT20272
100
DMV-A
for single-core cables
MT20271
DMV-A, DMV-S
for single and tri-core cables
MT20270
MT20269
SM, GAM
for single and tri-core cables
140
100
60
50
50
50
740
740
50
740
740
250
350
P4
P4
P5
P5
480
600
Schneider Electric
600
840
600
57
Connections
All units:
b through trenches
The trench depth P is given in the table opposite for commonly used types of cables.
b with stands
To reduce P or eliminate trenches altogether by placing the units on 400 mm footings.
b with floor void
The trench depth P is given in the table opposite for commonly used types of cables.
Connections
P2
MT20276
630 A units
front entry or exit
with conduits
MT20275
630 A units
rear entry or exit
with conduits
MT20274
630 A units
cable entry or exit
through right or left side
P1
200
P2
P3
P1
200
600
600
600
20
IM
70
200
IM
20
20
70
70
QMC
IM
200
200
IM
IM
DM1
DM1
IM
100
60
140
58
60
140
Note: for connection with conduits, the bevel must correspond to the following
trench dimensions: P1 = 75 mm or P2/P3 = 150 mm.
Schneider Electric
Connections
Downwards exhaust
Upwards exhaust
MT20278
Installation with
trench diagram
MT20277
Installation with
technical pit
220
100
P1
200
600
220
220
740
740
1060
1060
20
20
Connections
200
IM
IM
200
IM
DM1-A
IM
DM1-A
Note: to evacuate gases through the bottom, the technical pit volume must be over
or equal to 6 m3 for a switchboard width of 1125 mm maximum.
Schneider Electric
59
Installation
Add to height:
(1) 450 mm for low-voltage enclosures for control/
monitoring and protection functions. To ensure uniform
presentation, all units (except GIM and GEM) may be
equipped with low-voltage enclosures.
(2) depending on the busbar configuration in the VM6
unit, two types of extension units may be used:
b to extend a VM6 DM12 or DM23 unit,
use an extension unit with a depth of 1060 mm;
b for all other VM6 units, a depth of 920 mm is required.
(3) for the 1250 A unit.
Type of unit
height
(mm)
IM,IMB
1600(1)
IMC
1600(1)
PM, QM, QMB
1600(1)
QMC
1600(1)
CRM
2050
DM1-A, DM1-D, DM1-W, DM1-Z, 1600(1)
DM1-S, DM2
DMV-A, DMV-D, DMV-S
1600(1)
CM
1600(1)
CM2
1600(1)
GBC-A, GBC-B
1600
NSM-cables, NSM-busbars
2050
GIM
1600
GEM(2)
1600
GBM
1600
GAM2
1600
GAM
1600
SM
1600(1)
TM
1600
width
(mm)
375
500
375
625
750
750
depth
(mm)
940
940
940
940
940
1220
weight
(kg)
120
200
130
230
390
400
625
375
500
750
750
125
125
375
375
500
375/500(3)
375
940
940
940
1020
940
840
920/1060
870
870
1020
940
940
320
190
210
290
260
30
30/35
120
120
120
120
190
Floor preparation
Units may be installed on ordinary concrete floors, with or without trenches
depending on the type and cross-section of cables.
Required civil works are identical for all 400 - 630 A units.
To reduce the depth of trenches by 400 mm (for the 400 - 630 A units),
which in many cases is sufficient to eliminate trenches altogether,
units may be installed on a concrete footing prepared when pouring the floor.
Installation of 400 - 630 A units on a footing:
b enables installation in rooms where trenches are not possible;
b in no way affects substation switching operation;
b for the 1250 A units DM1-A and DM1-W, a floor void must be foreseen.
Fixing of units
MT55108
a
15
15
50
740
840
12.3 x 12.3
60
a (mm)
b (mm)
125
95
375
345
500
470
625
595
750
720
Schneider Electric
Installation
Units dimensions
1600
1600
30
70
840
GBM, GAM2
1600
840
30
70
1600
30
70
80
30
70
MT20287
1600
Schneider Electric
840
GBC-A, GBC-B
MT20286
GEM
MT20285
GIM
840
30
70
GAM
1600
840
840
Installation
MT20282
450
30
70
MT20283
NSM-cables, NSM-busbars
1600
MT20284
840
450
MT20281
450
MT20280
MT20279
450
CRM
1600
1600
140
920
80
840
100
61
Installation
Units dimensions
MT20289
MT20288
450
1600
80
1600
200
100
840
330
MT20291
DMV-D
MT20290
DMV-A, DMV-S
200
100
832
840
80
1600
1600
100
150
100
840
100
840
600
MT20293
MT20292
25
1600
220
62
840
30
70
1600
220
840
30
70
Schneider Electric
Layout examples
61050N
MT20294
Installation
B
A
940
200
20
1200
without
circuit breaker
630/1250 A
100
with
circuit breaker
630/1250 A
60
140
MT20296
MT20295
Installation
1160
200
1200
Schneider Electric
63
Installation
61051N
61016N
Ferrous metal
71%
Non-ferrous metal
10.5%
Thermohardening
15%
Thermoplastics
3.35%
0.15%
Fluid
MT55145
01
ISO 140
64
Schneider Electric
Installation
61052N
Installation
61053N
Schneider Electric
65
Appendices
MT20301
t>
t>
t >>
t >>
Is 1.2 Is
10 Is
I >>
Is 1.2 Is 10 Is
I >>
VI curve
t (s)
MT20302
t (s)
100
100
10
10
1
0.6
0.4
0.3
0.2
0.15
0.1
0.07
0.05
0.1
0.1
I/Is
0.01
1 1.2
10
I/Is
0.01
1 1.2
100
EI curve
10
100
RI curve
t (s)
MT20303
0.6
0.4
0.3
0.2
0.15
0.1
0.07
0.05
t (s)
1000
10
100
1
10
0.6
0.4
0.3
0.2
0.15
1
0.1
0.6
0.4
0.3
0.2
0.15
0.1
0.07
0.05
0.1
0.01
1 1.2
66
10
I/Is
100
0.1
0.07
0.05
I/Is
0.01
1
10
100
Schneider Electric
Appendices
MT20304
td (s)
1000
1000
500
500
200
200
100
100
50
50
12
20
20
10
10
2
1
1
13
0.5
14
0.2
0.2
0.1
0.1
0.05
0.05
0.02
0.02
0.01
I/Is
0.005
0.5
1 1.2
10
20
30
14
0.01
I/Is
0.005
50 60
0.5
13
0.5
1 1.2
10
20
30
50 60
20
30
50 60
td (s)
td (s)
1000
1000
500
500
200
200
100
100
50
50
20
20
10
10
0.5
0.5
13
0.2
0.2
0.1
0.1
0.05
0.05
0.02
13
0.02
14
0.01
I/Is
0.005
0.5
1 1.2
10
20
30
50 60
20
30
50 60
14
0.01
I/Is
0.005
0.5
1 1.2
10
td (s)
1000
500
200
100
50
20
10
Appendices
MT20306
5
2
1
13
0.5
0.2
0.1
0.05
0.02
14
0.01
I/Is
0.005
0.5
1 1.2
Schneider Electric
10
67
Appendices
MT20307
s
100
10
0.1
type
0.01
I/Is
0 1.2
68
10
15
20
25
30
Schneider Electric
Appendices
Fusarc CF fuses
Fuse and limitation curves
250 A
160 A
125 A
100 A
31.5 A
40 A
50 A
63 A
80 A
10 A
16 A
20 A
25 A
6.3 A
1000
8
6
4
4A
MT20012
Time (s)
8
1000
2
100
8
6
4
2
10
8
6
4
2
1
8
6
4
2
0.1
8
6
4
2
0.01
2
10
100
8
10000
Current (A)
8
6
4
Ia
8
1.
Ik
Is
Ik
250 A
200 A
160 A
125 A
100 A
80 A
63 A
50 A
40 A
10
8
31.5 A
25 A
20 A
16 A
6
4
10 A
6.3 A
2
1
8
4A
Appendices
6
4
0.1
0.1
10
100
Schneider Electric
69
Appendices
Solefuse fuses
Fuse and limitation curves
1000
8
6
4
16 A
20 A
25 A
31.5 A
43 A
63 A
80 A
6.3 A
10 A
MT20015
Time (s)
2
100
8
6
4
2
10
8
6
4
2
1
8
6
4
2
0.1
8
6
4
2
0.01
2
10
100
8
1000
8
10000
Current (A)
8
6
4
Ia
8
1.
Ik
Is
Ik
2
125 A
100 A
80 A
63 A
10
43 A
31.5 A
25 A
20 A
16 A
10 A
8
6
4
6.3 A
2
1
8
6
4
0.1
0.1
10
100
70
Schneider Electric
Personal notes
Appendices
Appendices
Schneider Electric
71
Appendices
72
Personal notes
Schneider Electric