Voltage Transducer LV 25-600 600 V

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Voltage Transducer LV 25-600

For the electronic measurement of voltage: DC, AC, pulsed...,


with galvanic separation between the primary circuit and the secondary
circuit.

Features

Electrical data

dCI

VPN
Primary nominal rms voltage
VPM
Primary voltage, measuring range
IPN
Primary nominal rms current
RM
Measuring resistance

with 12 V
@ 600 V max

@ 900 V max

with 15 V
@ 600 V max

@ 900 V max
ISN
Secondary nominal rms current
K N
Conversion ratio
U C
Supply voltage ( 5 %)
IC
Current consumption

600
V
0 .. 900
V
10
mA
RM min RM max
30
200

30
100

100 320

100 180

25
mA
600 V : 25 mA
12 .. 15
V
10 (@ 15 V) + IS mA

Accuracy - Dynamic performance data


XG
L

IO
IOT

tr

Overall accuracy @ VPN, TA = 25 C


0.8
Linearity error
< 0.2

Typ Max
Offset current @ VP = 0, TA = 25 C
0.15
Temperature variation of IO
- 25 C .. + 25 C 0.10 0.60

+ 25 C .. + 70 C 0.10 0.35
Step response time to 90 % of VPN
< 15

%
%
mA
mA
mA
us

General data
TA
TS
NP/NS
PP
RP
RS
m

VPN = 600 V

Ambient operating temperature


Ambient storage temperature
Turns ratio
Total primary power loss
Resistance of primary @ TA = 25 C
Resistance of secondary winding @ TA = 70 C
Mass
Standards

- 25 .. + 70
- 40 .. + 85
2500 : 1000
6
60
110
60
EN 50178: 1997
UL 508: 2010

C
C
W
k

Advantages

Excellent accuracy
Very good linearity
Low temperature drift
High immunity to external
interference.

Applications
AC variable speed drives and
servo motor drives
Static converters for DC motor
drives
Uninterruptible Power Supplies
(UPS)
Power supplies for welding
applications.

Application Domain
Industrial.

N 97.28.52.000.0
13March2014/version 6

dCp

Closed loop (compensated)


voltage transducer using the Hall
effect
I
R
Insulating plastic case recognized
HT
according to UL 94-V0
U
Primary resistor and transducer
U
HT mounted on printed circuit board
128 60 mm.

Page 1/3
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice

www.lem.com

Voltage Transducer LV 25-600


Insulation coordination
U d

dCp
dCI
CTI

Rms voltage for AC insulation test 1), 50 Hz, 1 min



Creepage distance
Clearance
Comparative tracking index (group IIIb)

4.1
Min
13.8
13.8
< 175

kV
mm
mm

Note: 1) Between primary and secondary.

Applications examples
According to EN 50178 and IEC 61010-1 standards and following conditions:
Over voltage category OV 3
Pollution degree PD2
Non-uniform field

dCp, dCI,

EN 50178

IEC 61010-1

Rated insulation voltage

Nominal voltage

Basic insulation

1500 V

NA

Reinforced insulation

600 V

600 V

Safety
This transducer must be used in limited-energy secondary circuits according to
IEC 61010-1.

This transducer must be used in electric/electronic equipment with respect to


applicable standards and safety requirements in accordance with the manufacturers
operating instructions.

Caution, risk of electrical shock


When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).Ignoring this warning can lead to injury
and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.A protective housing or additional shield could be used.
Main supply must be able to be disconnected.

Page 2/3

13March2014/version 6

LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice

www.lem.com

Dimensions LV 25-600 (in mm)

dCI

dCp

Connection
HT

dCI

Is

RM

dCp

UC
UC

HT

Is

HT

RM

HT

Mechanical characteristics
General tolerance
Transducer fastening




Connection of primary
Connection of socondary

Remarks
0.3 mm
4 holes 4.2 mm the
mounting must be
done on a adapted
holder with four M4
screws
Faston 6.3 0.8 mm
Faston 6.3 0.8 mm

IS is positive when VP is applied on terminal + HT.


The primary circuit of the transducer must be linked to the
connections where the voltage has to be measured.
Installation of the transducer must be done unless
otherwise specified on the datasheet, according to LEM
Transducer Generic Mounting Rules. Please refer to
LEM document NANE120504 available on our Web site:
Products/Product Documentation.
This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.

Page 3/3

13March2014/version 6

LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice

www.lem.com

You might also like