Syb Sicam Mic Eng PDF
Syb Sicam Mic Eng PDF
Introduction
System Overview
SICAM RTUs
Function Packages
SICAM MIC
Ambient Conditions
System Description
Order Information
Glossary
MC6-054-2.00
1
2
3
4
5
A
Note
Please take notice of the notes and warnings for your safety in the preface.
Disclaimer of Liability
Although we have carefully checked the contents of this publication
for conformity with the hardware and software described, we cannot
guarantee complete conformity since errors cannot be excluded.
The information provided in this manual is checked at regular
intervals and any corrections that might become necessary are
included in the next releases. Any suggestions for improvement are
welcome.
Copyright
Copyright Siemens AG 2014
The reproduction, transmission or use of this document or its
contents is not permitted without express written authority. Offenders will be liable for damages. All rights, including rights created by
patent grant or registration of a utility model or design, are reserved.
Siemens AG
Preface
Purpose of this manual
This manual describes the characteristics and functions of the system SICAM MIC. It contains
Configuration possibilities
Functional overviews
Technical specifications
Order information
Target Group
The document you are reading right now is addressed to users, who are in charge of the following engineering tasks:
Evaluation of quotation criteria, such as technical specifications of the system or environmental conditions
Preface
Item number
MC6-000-1
DC6-058-2
DC6-041-2
DC0-013-2
DA0-046-2
MC0-043-2
MC0-031-2
MC0-033-2
MC0-035-2
MA0-025-2
MC0-045-2
Further Support
For more information, please contact our Customer Support Center:
Phone: +49 (0)180 524 70 00
Fax: +49 (0)180 524 24 71
(charges depending on provider)
e-mail: [email protected]
The Siemens Power Academy offers a comprehensive program of professional training events
in the fields of power generation, distribution and transmission.
Main training centers are:
Vienna, Austria
Phone: +43 51707 31143
Fax: +43 51707 55243
[email protected]
Preface
Notes on Safety
This manual does not constitute a complete catalog of all safety measures required for operating the equipment (module, device) in question because special operating conditions might
require additional measures. However, it does contain notes that must be adhered to for your
own personal safety and to avoid damage to property. These notes are highlighted with a
warning triangle and different keywords indicating different degrees of danger.
Danger
Means that death, serious bodily injury or considerable property damage will occur, if the appropriate
precautionary measures are not carried out.
Warning
Means that death, serious bodily injury or considerable property damage can occur, if the appropriate
precautionary measures are not carried out.
Caution
Means that minor bodily injury or property damage can occur, if the appropriate precautionary measures
are not carried out.
Note
Is important information about the product, the handling of the product or the respective part of the documentation, to which special attention is to be given.
Qualified Personnel
Commissioning and operation of the equipment (module, device) described in this manual
must be performed by qualified personnel only. As used in the safety notes contained in this
manual, qualified personnel are those persons who are authorized to commission, release,
ground, and tag devices, systems, and electrical circuits in accordance with safety standards.
Preface
Use as Prescribed
The equipment (device, module) must not be used for any other purposes than those described in the Catalog and the Technical Description. If it is used together with third-party devices and components, these must be recommended or approved by Siemens.
Correct and safe operation of the product requires adequate transportation, storage, installation, and mounting as well as appropriate use and maintenance.
During operation of electrical equipment, it is unavoidable that certain parts of this equipment
will carry dangerous voltages. Severe injury or damage to property can occur if the appropriate measures are not taken:
Hazardous voltages can be present on all switching components connected to the power
supply.
Even after the supply voltage has been disconnected, hazardous voltages can still be present in the equipment (capacitor storage).
The limit values indicated in the manual or the operating instructions must not be exceeded; that also applies to testing and commissioning.
Danger
Consider obligatory the safety rules for the accomplishment of works at electrical plants:
1. Switch off electricity all-pole and on all sides!
2. Ensure that electricity cannot be switched on again!
3. Double check that no electrical current is flowing!
4. Discharge, ground, short circuit!
5. Cover or otherwise isolate components that are still electrically active!
Table of Contents
1
Introduction ................................................................................................................. 11
1.1
1.2
1.2.1
Features .................................................................................................... 14
1.2.2
Performance................................................................................................... 16
2.2
2.3
Architecture .................................................................................................... 19
2.3.1
2.3.2
2.3.3
2.3.3.1
2.3.3.1.1
2.3.3.2
2.4
2.4.2
Transmission Modes.................................................................................. 27
2.4.3
Configurations ........................................................................................... 28
Multi-Point Traffic.................................................................................. 29
2.4.3.1.1
Dial-Up Traffic.................................................................................. 30
2.4.3.1.2
LAN/WAN ........................................................................................ 32
2.4.3.1.3
Internet/GPRS ................................................................................. 33
2.5
2.4.1
2.4.3.1
Engineering .................................................................................................... 34
2.5.1
2.5.2
TOOLBOX II .............................................................................................. 34
Function Packages...................................................................................................... 35
3.1
System Services............................................................................................. 36
3.2
Telecontrol ..................................................................................................... 37
3.3
Automation ..................................................................................................... 38
4.2
4.3
4.4
4.4.1
4.4.2
Table of Contents
4.4.3
4.4.4
4.4.5
Communication LAN.................................................................................. 46
5.2
5.2.1
PS-6630 .................................................................................................... 49
5.2.2
PS-6632 .................................................................................................... 50
5.3
5.3.1
CP-6020 .................................................................................................... 51
5.3.2
CP-6040 .................................................................................................... 53
5.4
5.4.1
5.4.1.2
5.4.1.3
5.4.1.4
AI-6310 ................................................................................................ 59
5.4.1.5
TE-6430 ............................................................................................... 59
5.4.2.1
5.4.2.1.1
5.4.2.2
5.4.2.2.1
5.4.2.3
5.4.2.3.1
5.4.2.4
5.4.3
Order Information........................................................................................................ 67
A.1
A.2
A.3
I/O Modules.................................................................................................... 70
A.4
A.5
Accessories .................................................................................................... 74
A.5.1
A.5.2
A.5.3
A.1.1.
A.5.4
A.5.5
Miscellaneous ........................................................................................... 77
A.6
A.6.1
A.6.1.1
8
5.4.1.1
5.4.2
Table of Contents
A.6.1.2
A.6.2
Packages ............................................................................................. 80
Web Engineering ....................................................................................... 80
Table of Contents
10
Introduction
Contents
1.1
1.2
11
Introduction
1.1
Compact performance
SICAM MIC (Terminal Module for microcontrol) is a low-cost, modular, telecontrol substation
and belongs to the proven SICAM RTU automation family.
The devices consist of a master control element and various I/O modules. The master control
element serves for interfacing and supplying the I/O modules and provides a telecommunications interface in accordance with IEC 60870-5-101 for dial-up or multipoint traffic.
Alternatively, LAN/WAN communication can be used according to IEC 60870-5-104 over
Ethernet TCP/IP. All modules are designed for DIN rail mounting.
Practical engineering
Great importance was placed on keeping the engineering process as simple as possible.
Thats why the master control element has an integrated Web server for configuration, diagnostics and testing, so no special tools or additional licenses are needed. The tool is already
integrated in SICAM MIC and is operated with a standard Web browser.
Alternatively, it is also possible to use SICAM TOOLBOX II, the integrated engineering tool for
the entire SICAM RTU family.
Universal assembly
The modules are simply snapped onto a 35-mm DIN rail. Up to eight I/O modules can be
mounted in addition to the power supply module and the master control. The extension cable
CM-6810 enables the I/O modules to be distributed between two DIN rails. The advantage of
this is that even with limited space there is still adequate room for the modules.
12
Introduction
Thanks to its node functionality, the SICAM MIC has many different potential applications,
for example as an ordinary telecontrol substation with any kind of communication to a control center.
If SICAM MIC does not offer adequate signal scope, additional SICAM MIC systems can
be readily connected.
Freely programmable application programs for local control functions complete the allround versatility of the SICAM MIC.
The SICAM MIC can be used optionally in multipoint or dial-up traffic, but also over
LAN/WAN networks. Transmission conforms to IEC 60870-5-101 or IEC 60870-5-104.
Multipoint traffic
External data transmission equipment can be connected via the V.28 interface.
Dial-up traffic
A wide range of connection-oriented transmission media (analog, ISDN, GSM, TETRA) is
supported as standard.
LAN/WAN
IEC 60870-5-104-compliant transmission based on Ethernet TCP/IP is used for communication.
13
Introduction
1.2
1.2.1
Features
Your advantages at a glance:
1.2.2
Integrated node functionality for interfacing additional equipment via various protocols
Alternatively, the engineering process can also be carried out with SICAM TOOLBOX II
Plug & Play for start-up and servicing through use of flash card or SIM card for data storage
14
Hydropower plants
Pipelines
System Overview
Contents
2.1
Performance................................................................................................... 16
2.2
2.3
Architecture .................................................................................................... 19
2.4
Communication .............................................................................................. 26
2.5
Engineering .................................................................................................... 34
15
System Overview
2.1
16
Performance
Loadable firmware
Communication with other automation units according to IEC 60870-5-101 (multipoint traffic, dial-up traffic, point-to-point traffic)
System Overview
2.2
Mechanical Structure
Installation takes place on a 35 mm DIN rail that is mounted horizontally or vertically on a vertical standing rack. The sequence of modules from left to right or top to bottom is prescribed
as follows:
The electrical connection of the modules with the power supply takes place during the process
of latching together, whereby each module can be individually replaced.
Standard Structure
8 I/O-Modules max.
17
System Overview
2-Line Arrangement
18
in total max.
8 I/O modules
System Overview
2.3
Architecture
2.3.1
Product Overview
Type
Designation
Power
PS-6630
8W
PS-6632
8W
19
System Overview
2.3.2
On the master control module CP-6020 reside an interface for the communication (serial), digital inputs and
outputs, as well as a lighted display.
On the master control module CP-6040 resides additionally an interface for the communication via Ethernet.
The master control element contains all the central functions for processing and communication, and it provides the parameter-settable telecontrol function and the open-/closed-loop function.
Furthermore, the master control element is able to store events in an archive (DEAR) in case
of a communication fault. After elimination of the fault the superior control system can demand
the archive of the master control element. By means of this function, a possible data loss will
be prevented.
20
System Overview
6 digital inputs
One common return
Signal voltage 2460 VDC
The states of the inputs are indicated by LEDs
2 relay outputs
1 command output
1 selectable output (command output, watchdog indication or error indication)
With command output, the state of the output is indicated by LED
Loadable firmware
Product Overview
Type
Designation
Power
CP-6020
800 mW
CP-6040
800 mW
CPC60
SIM card
21
System Overview
2.3.3
Peripheral Element
The virtual peripheral element serves for the acquisition or output of process signals. It performs the process-compliant adaptation, monitoring and processing of the process signals at
each point of entrance or exit of the system.
The hardware for the peripheral element is integrated on the master control module, and its
functionality is provided by means of a loadable and parameter-settable firmware.
Features
Acquisition and preprocessing of process data according to IEC 60870-5-101/104 with and
without time tag
Single-point and double-point information items
Count pulses
Actual values
Secured data exchange between the I/O modules and the master control element via the
TM bus
Product Overview
Type
USIO61 *)
USIO60
*)
22
Designation
*)
System Overview
2.3.3.1
I/O Modules
The optional I/O modules support the peripheral element with the process data input and output.
The connection of the process signals (I/Os) happens by
means of removable screw terminals. The screw terminals are enclosed with each I/O module.
When modules are exchanged no connections need to
be detached, since the screw terminals carry the wiring.
Thereby the assembly effort required for the connection is
reduced to a minimum.
Further, a status display resides on the I/O modules.
Features
Product Overview
Type
Designation
Power
DI-6100
170 mW
DI-6101
170 mW
DI-6102
170 mW
DI-6103
170 mW
DI-6104
170 mW
DO-6200
600 mW
DO-6212
800 mW
DO-6220
560 mW
DO-6221
1.38 W
DO-6230
130 mW
AI-6300
480 mW
AI-6307
480 mW
AI-6308
480 m'W
AI-6310
480 mW
AO-6380
1.9 W
TE-6420
790 mW
23
System Overview
2.3.3.1.1
Configuration Notes
Common Rules
With use of the I/O modules please pay attention to the following notes:
AO modules must be equipped at the first slots (up to 3 pieces possible; with 2-line arrangement with CM-6810 only in the first line permitted)
The mixture of current and voltage on the same AI module is not possible
The mixture of binary information and pulse commands on the same DO module is not
possible
The command output via DO-6220 or DO-6221 without a DO-6230 is not possible
The command output via DO-6230 without a DO-6220 or DO-6221 is not possible
On a DO-6230 either 1-, or 1.5- or 2-pole impulse commands can be assigned (mixture on
the same module is not permitted)
with paramerization with the SICAM TOOLBOX II, the I/O modules DO-6220, DO-6221
and DO-6230 must be configured underneath the virtual system element USIO61
24
With the fixed assignment respectively after a module DI-610x a module DO-62xx (refer to
5.4.3, Return Information to Pulse Command Assignment) must be equipped
System Overview
2.3.3.2
TM Peripheral Bus
The TM bus serves for the power supply of the individual modules and for the communication
of the I/O modules with the master control module. The communication takes place in the
master/slave process, wherein the I/O modules are the slaves.
The I/O modules are automatically addressed on the TM bus based on the sequence of physical fitting. The I/O module connected directly to the peripheral control module has the least
significant address.
The I/O modules are checked cyclically for functioning via the TM bus. A failure is detected after max. 200 ms. The "RY" LED goes out on the corresponding I/O module.
25
System Overview
2.4
Communication
2.4.1
Interface
*)
CP-6020/CPC60
RS-232
CP-6040/CPC60
RS-232
Ethernet LAN
*)
Remarks
Process communication and engineering use the serial
interface exclusively, and therefore are not available simultaneously
Process communication is not available simultaneously
using both interfaces
The following transmission facilities can be supplied directly from the power supply module using a special cable.
Designation
Power (typ.)
Supply 1)
400 mW
5V
2W
5V
MODEM ANALOG
35 mW
10 V
MODEM GSM
300 mW
10 V
Type
CE-0700
CE-0701
26
2)
1)
2)
withdrawn
System Overview
2.4.2
Transmission Modes
Depending on master control module there are different communication methods available:
Multi-point traffic
Dial-up traffic
Features
Transmission Facilities
Multi-Point Traffic
Dial-Up Traffic
Coherent Technologies
Eurocom 24 (analog) 1)
Cinterion MC52iT (GSM
900/1800 MHz) 2)
Siemens M20 Databox, TC35
(GSM 900/1800 MHz) 2)
Westermo TD-36 (analog)
Westermo IDW-90 (ISDN)
Sepura Terminal (TETRA)
Insys GSM 4.1 (GSM)
LAN/WAN
Siemens MD741-1
Dr. Neuhaus Tainy EMOD-V2-IO
(GPRS) 3)
Dr. Neuhaus Tainy EMOD-L1-IO
(GPRS) 3) 4)
GPRS
1)
2)
3)
4)
27
System Overview
2.4.3
Configurations
Depending on master control module and protocol variant there are different communication
methods available:
Multi-point traffic
Dial-up traffic
Single-Master
Multi-Master
Communication via LAN/WAN
Control System
TCP/IP 60870-5-104
28
Multi-Point Traffic
PSTN/ISDN/GSM
IEC 60870-5-101
Dial-up Traffic
System Overview
2.4.3.1
Multi-Point Traffic
Control center
CP-6040
CP-6040
29
System Overview
2.4.3.1.1
Dial-Up Traffic
Single-Master Dial-Up Traffic
Control center
PSTN/ISDN/GSM
IEC 60870-5-1
CP-6040
30
CP-6040
System Overview
PSTN/ISDN/GSM
IEC 60870-5-101
CP-6040
CP-6040
31
System Overview
2.4.3.1.2
LAN/WAN
Control center
CP-6040
32
CP-6040
Dat
a pa
cka
ges
Base station
controller
e
on
Ph
ca
lls
Router
2
3
4
5
X 13
PWR
24-60VDC
X 14
ER
X5
WD
X12
X11
X4
X10
M -PRE/3
SI3
FB
X9
PUSH TO UNLOC K
X8
X7
M -PRE/2
SI2 (F B)
X6
X3
M -PRE/1
SI1 (ETO )
SIM0
TB
M -PRE/0
SI0
PU SH TO
R ELEASE
X16
X15
ER
C PY
X1
COM
/P K / LK
/P K / LK
E Rx RX T X
RE S
RY
S I3
S I2
S I1
S I0
LOC
CP-6014
PUSH TO
RELEAS E
TM 1703 ACP
SICAM
Telecontrol
center
NC
2.4.3.1.3
Corporate
Network
X2
System Overview
Internet/GPRS
Internet
PSTN
Master station
controller
Firewall
Telecontrol
sub station
CP-6040
33
System Overview
2.5
Engineering
2.5.1
2.5.2
TOOLBOX II
Of course SICAM MIC supports also the TOOLBOX II, the integrated engineering system for
the entire SICAM RTUs family. This comprises all stages of plant configuration and maintenance, this means data collection, configuring, parameter setting, expanding, changing, testing, system diagnosis, and documentation.
The introduction of object orientation allows project engineers to describe real units and pieces of equipment in the configuration process (circuit breakers, feeders, etc.).
They can take advantage of these structural advantages especially in cases where systems
are constituted of a plurality of primary units and pieces of equipment of equal type (for example a transformer substation). This yields enormous streamlining effects for the engineering
process.
When configuring via the TOOLBOX II, application programs (open-/closed-loop control function)
can be created as function diagram (FUD) with the tool CAEx plus. Optionally, also an existing
instruction list can be imported into the TOOLBOX II.
In view of its conformity with IEC 61131-3, CAEx plus grants the user access to a wellestablished and generally acknowledged standard. This helps shorten staff training times considerably.
By means of the available standard-conformal module libraries and standard-conformal data
types, the engineering becomes more transparent and is possible with high application quality.
34
Function Packages
Contents
3.1
System Services............................................................................................. 36
3.2
Telecontrol ..................................................................................................... 37
3.3
Automation ..................................................................................................... 38
35
Function Packages
3.1
36
System Services
Integrated webserver
Addressing
Time management
Central clock of the automation unit
Setting and keeping the own clock's time with a resolution of 10 ms
Synchronization via serial communication (with another automation unit), via LAN (NTP
server), or local (minute pulse)
General interrogation
Monitoring functions
Failure management
Function Packages
3.2
Telecontrol
Communications:
Own circular buffer and process image for each connected station (data keeping)
Process Periphery:
Transmission of spontaneous information objects from and to peripheral elements, via the serial TM bus
Archiving of events
37
Function Packages
3.3
Automation
Telecontrol interface
Reception of messages with process information
Handling of commands according to IEC 60870-5-101/104
Change management and generation of messages with time tag
38
Online diagnostics
Ambient Conditions
Contents
4.1
4.2
4.3
4.4
39
Ambient Conditions
4.1
40
Protection Type
Operational Equipment
CP-60xx
IP40
Terminals: IP 20
I/O modules
IP40
Terminals: IP 20
Ambient Conditions
4.2
Parameter
Value
Test standard
3.5 mm
IEC 60068-2-6
Cl.
Product stand.
Cl.
IEC 60870-2-2
>Bm
Harmonic
Amplitude of the excursion
19 Hz
Acceleration
9200 Hz
Acceleration
200500 Hz
10 m/s
Bm
15 m/s
Bm
Shock
Acceleration; 11 ms duration (function)
100 m/s
IEC 60068-2-27
IEC 60870-2-2
Bm
The listed values cover or exceed the required seismic loading according to IEC 60870-2-2 Cl.S3
and IEC 60255-21-3 Cl.1. The values apply in operation and for storage.
The permitted mechanical stresses during transport depend on the transport packaging.
The device packaging is not a transport packaging.
41
Ambient Conditions
4.3
Parameter
Value
Test standard
-25C
72 hs.
Maximum temperature
(dry heat)
Product stand.
Cl.
IEC 60068-2-1
Ad
IEC 60870-2-2
C2
IEC 60654-1
C2
+70C
72 hs.
IEC 60068-2-2
Bd
IEC 60870-2-2
C2
IEC 60654-1
C3
Damp heat
40C
93% RH
48 hs.
IEC 60068-2-78
Temperature gradient
30C/h
IEC 60870-2-2
C2
IEC 60654-1
C2
597%
IEC 60870-2-2
C2
IEC 60654-1
C2
29 g/m
IEC 60870-2-2
C2
IEC 60654-1
C2
IEC 60870-2-2
C2
IEC 60654-1
C2
Air pressure
70106 kPa
(up to 3000 m)
Cl.
The listed values apply for the use in open-air cabinets for bay devices. The products can be exposed to sun and heat. They can be exposed as well to air flow caused by draught in buildings,
e.g. by open windows or influences of technical processes.
Bedewing is possible for a short time, e.g. during the course of maintenance tasks (not in operation). Condensation, precipitations, water and icing are not permitted.
Heating and cooling is used to maintain the necessary conditions, especially in case of great differences between indoor and outdoor climate.
The conditions of this class normally occur in living and working areas, e.g. in production rooms
for electronic and electrotechnical products, telecontrol rooms, storage rooms for valuable and
sensible devices.
42
Ambient Conditions
4.4
Electromagnetic Compatibility
4.4.1
System Properties
Parameter
Value
Test standard
8 kV-L
6 kV-K
IEC 61000-4-2
Electromagnetic fields
10 V/m
IEC 61000-4-3
Cl.
Product stand.
Cl.
IEC 60870-2-1
IEC 60255-22-2
IEC 60870-2-1
IEC 60255-22-3
3
3
50 Hz magnetic fields
30 A/m
IEC 61000-4-8
IEC 60870-2-1
Pulse-shaped magnetic
fields
300 A/m
IEC 61000-4-9
IEC 60870-2-1
40/47 dBV
CISPR22
IEC 60870-2-1
CISPR22
43
Ambient Conditions
4.4.2
Power Supply DC
Parameter
Value
Test standard
Dielectrical test
UN 60 V (SELV circuit)
1.5 kVeff
2.5 kVeff
IEC 60255-5
1)
Dielectrical test
60 V < U N 125 V against
SELV-circuits
2.0 kVeff
2.5 kVeff
1)
Dielectrical test
125 V < U N 230 V
against SELV-circuits
3.0 kVeff
Voltage tolerance DC
+30/-20%
Cl.
Product stand.
Cl.
IEC 60870-2-1
VW3
IEC 60255-5
IEC 60255-5
IEC 60950-1
VW3
IEC 60950-1
IEC 60255-5
IEC 60950-1
> VW3
IEC 60950-1
IEC 60870-2-1
IEC 60870-2-1
DC3
IEC 60654-2
>DC3
IEC 60870-2-1
VR3
Voltage ripple DC
5%
IEC 60870-2-1
Starting current
S1
IEC 60870-4
IEC 60870-4
1.3 U N
IEC 61000-4-1
IEC 60870-2-1
4.0 kVs
IEC 61000-4-4 2)
IEC 60870-2-1
IEC 60255-22-4
Surge 1.2/50 ms
4.0 kVs
IEC 61000-4-5
IEC 60870-2-1
4.0 kVs
IEC 61000-4-5
IEC 60870-2-1
>4
Induced HF voltage
10 V
IEC 61000-4-6
Interruption time
50 ms
IEC 61000-4-11
IEC 60870-2-1
>1
IEC 60654-2
Impulse voltage
100/1300s 1)
S1
normal
common
Surge 1.2/50 ms
normal
IEC 60255-11
44
2.5 kVs
IEC 61000-4-12
2.5 kVs
IEC 61000-4-12
1)
2)
directly connected
IEC 60870-2-1
IEC 60255-22-1
IEC 60870-2-1
>3
IEC 60255-22-1
Ambient Conditions
4.4.3
Value
Test standard
2.0 kV
IEC 61000-4-4
Cl.
Product stand.
Cl.
IEC 60870-2-1
IEC 60255-22-4
2.0 kV
IEC 61000-4-5
*)
IEC 60870-2-1
2.0 kV
IEC 61000-4-5 *)
IEC 60870-2-1
>4
Induced HF voltage
10 V
IEC 61000-4-6
2.5 kVs
IEC 61000-4-12
IEC 60870-2-1
IEC 60255-22-1
1.0 kV
IEC 60870-2-1
>3
IEC 60255-22-1
Surge 1.2/50 ms
common
Surge 1.2/50 ms
normal
*)
IEC 61000-4-12
Usage of TE-6420
If sensor and TE-6420 reside within a cabinet, the signal lines to the sensor must be carried out
shielded and massed both ways (cabinet feeding, potential equalization of sensor).
With usage of third-party supplied sensors, the signal lines as well as the power supply of the
sensor must be directed in shielded cables. The power supply may be directed max. 1 m unshielded between power supply module and terminal. The corresponding power supply module
may be used exclusively for the sensor feeding, a usage for other plant parts is not allowed.
4.4.4
Value
Test standard
2.0 kV
IEC 61000-4-4
Induced HF voltage
10 V
Cl.
Product stand.
Cl.
IEC 60870-2-1
IEC 60255-22-4
IEC 61000-4-6
45
Ambient Conditions
4.4.5
Communication LAN
Parameter
Value
Test standard
2.0 kV
IEC 61000-4-4
Induced HF voltage
10 V
Cl.
Product stand.
Cl.
IEC 60870-2-1
IEC 60255-22-4
IEC 61000-4-6
46
Contents
5.1
5.2
5.3
5.4
47
5.1
Mechanical Design
Mechanics
Structure
Dimensions (HxWxD)
Per module
Fully equipped
131 x 63 x 73 mm
131 x 630 x 73 mm + 2 x 3.7 mm
Weight
Connectors
48
Ethernet/LAN communication
RS-232 communication
5.2
5.2.1
PS-6630
Power supply
2 system voltage outputs
Operating voltage
Output voltage
system-internal
for external modem 1)
U1
U2
5.15 VDC 2%
5.15.4 VDC switchable
Output power P U1
PU1 min
PU1 max
Output power P U2
PU2 max
2.5 W
PU1+U2 max
PU1+U2 peak
8.0 W
9.0 W
Efficiency
hU1 = P U1/Pin
hU2 = P U2/Pin
approx. 65%
approx. 60%
Power consumption
Pin = PU1/h U1 + PU2/h U2
Pin max
Pin peak
12.3 W
13.8 W
8A
40 A
at 18 VDC
at 78 VDC
910 VDC 2)
600 s
600 s
Output Power
Pout [W]
Uin=60VDC
Uin=48VDC
Uin=24VDC
Yes
Overload protection
No 3)
Short-circuit protection
No 3)
10
20
30
40
50
60
Fault output
max. switching voltage
max. output current
max. short-time current
Mechanics
Terminals
Dimensions
Weight
Approx. 200 g
1)
2)
switching to the higher voltage is induced exclusively by CP-6020/CPC60 and depends on its parameter
setting (without switching, only the lower voltage is available)
3)
49
5.2.2
PS-6632
Power supply
2 system voltage outputs
Operating voltage
Output voltages
system-internal
for external modem 1)
U1
U2
5.15 VDC 2%
5.15.4 VDC switchable
Output power P U1
PU1 min
PU1 max
Output power P U2
PU2 max
2.5 W
PU1+U2 max
PU1+U2 peak
8.0 W
9.0 W
Efficiency
hU1 = P U1/Pin
hU2 = P U2/Pin
approx. 65%
approx. 60%
Power consumption
Pin = PU1/h U1 + PU2/h U2
Pin max
Pin peak
12.3 W
13.8 W
25 A
80 A
at 90 VDC
at 230 VDC
910 VDC 2)
500 s
500 s
Output Power
Pout [W]
Uin=220VDC
at P=4W.....T=1000ms
(Uin=220VDC)
Uin=110VDC
at P=2W.....T=1640ms
(Uin=220VDC)
0 10 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900
Tu [ms]
Interruption Time (typ.)
Yes
Overload protection
No 3)
Short-circuit protection
No 3)
Fault output
max. switching voltage
max. output current
max. short-time current
Mechanics
50
Terminals
Dimensions
Weight
Approx. 230 g
1)
2)
switching to the higher voltage is induced exclusively by CP-6020/CPC60 and depends on its parameter
setting (without switching, only the lower voltage is available)
3)
5.3
5.3.1
CP-6020
Processor and Memory
Processor
SAF-C161PI-LF
14.7456 MHz
1.0 ppm
Program memory
Main memory
Parameter memory
Program sampling
Decentralized archive
Binary Inputs
6 binary inputs
Galvanical insulation
Common return of selectable polarity
Filter time
3 ms
Nominal voltages
24/48/60 VDC
Operating points
12 V
16 V
Rated current
Input circuits
logical "0"
logical "1"
51
2 outputs, potential-free
Galvanical insulation
Voltage between the two outputs max. 60 VDC +30%
Normally open contacts
When watchdog has timed out or with reset: relay contact is
open
2A
1A
0.77A
24 VDC
60 VDC
78 VDC
Switching cycles
105
104
min. 1 mW
max. 60 W
48 W
60 W
60 W
Output circuits
24 VDC
48 VDC
60 VDC
2.00 A
1.25 A
1.00 A
Communication
Serial interface
Power Supply
Operating voltage
Dimensions
Weight
Approx. 190 g
*)
52
5.3.2
CP-6040
Processor and Memory
Processor
SAF-C161PI-LF
14.7456 MHz
1.0 ppm
Program memory
Main memory
Parameter memory
Program sampling
Decentralized archive
Binary Inputs
6 binary inputs
Galvanical insulation
Common return of selectable polarity
Filter time
3 ms
Nominal voltages
24/48/60 VDC
Operating points
12 V
16 V
Rated current
Input circuits
logical "0"
logical "1"
53
2 outputs, potential-free
Galvanical insulation
Voltage between the two outputs max. 60 VDC +30%
Normally open contacts
When watchdog has timed out or with reset: relay contact is
open
2A
1A
0.77A
24 VDC
60 VDC
78 VDC
Switching cycles
105
104
min. 1 mW
max. 60 W
48 W
60 W
60 W
Output circuits
24 VDC
48 VDC
60 VDC
2.00 A
1.25 A
1.00 A
Communication
Serial interface
Power Supply
Operating voltage
LAN interface
Dimensions
Weight
Approx. 190 g
*)
54
5.4
Note
The functions and the belonging mode of action are described in detail in the manual SICAM RTUs Common Functions Peripheral Elements according to IEC 60870 5 101/104.
Note
You find the technical data of the I/O modules in the manual SICAM TM I/O Modules.
In the following listing, footnotes are used to specify the effect of the functions in detail.
Telecontrol
the function affects process information which is spontaneously transmitted
f1
Telecontrol
the function delivers (acquisition) spontaneously transmitted process information or is controlled
by such information (output); partly, periodically transmitted information is also created/required
a
Automation
the function affects process information which is periodically transmitted
55
5.4.1
5.4.1.1
Single-point information
Inversion ta
Firmware filter t
Bounce suppression t
Determination of the cause of transmission t
Spontaneous transmission of changes t
Periodical transmission a
Double-point information
Acquisition with a resolution of 10 ms t
Update every 10 ms a (in the cycle of the open-/closed-loop control function, if larger)
Revision ta
Power monitoring ta
Inversion ta
Firmware filter t
Bounce suppression t
Monitoring intermediate and faulty positions t
56
5.4.1.2
DI-6102, DI-6103
Single-point information
Inversion ta
Firmware filter t
Bounce suppression t
Determination of the cause of transmission t
Spontaneous transmission of changes t
Periodical transmission a
Double-point information
Acquisition with a resolution of 1 ms t
Update every 10 ms a (in the cycle of the open-/closed-loop control function, if larger)
Revision ta
Power monitoring ta
Inversion ta
Firmware filter t
Bounce suppression t
Monitoring intermediate and faulty positions t
57
5.4.1.3
Revision t
Noise rejection t *)
Automatic calibration t
Smoothing t
Adaptation t
Linear (normalized, technologically scaled or short floating point)
Suppression of zero range
Plausibility check
Change monitoring t
Spontaneous transmission of changes t
______
*)
58
5.4.1.4
AI-6310
Temperatures t1
Acquisition of resistance thermometers via analog inputs of a SM-0571
Connection of the resistance thermometers: 2-, 3-, or 4-wire technique
Update every 400 ms
Settable measuring range
Temperaturwerte
- Input range
Pt100: -50+350C / -58+662F / (80,31229,67 )
Pt100: -100+700C / -148+1292F / (60,25345,13 )
Ni100: -60+250C / -76+482F / (69,5289,2 )
-
Resolution
Pt100: -50+350C 0.15C / 0.28F / (56 m)
Pt100: -100+700C 0.15C / 0.28F / (56 m)
Ni100: -60+250C 0.15C / 0.28F / (56 m)
Update grid
16 Hz <6,8 s
50 Hz < 5,6 s
60 Hz < 5,2 s
Resistance values
- Input range 40400
-
Resolution 56 m
Update grid
HW rev. ="--"
HW rev. "-A"
16 Hz < 6,8 s 16 Hz < 1,68 s
50 Hz
< 5,6 s 50 Hz
< 1,44 s
60 Hz
< 5,2 s 60 Hz
< 1,36 s
Revision
Noise rejection *)
Automatic calibration
Calibration for 2-wire technique
Smoothing
Adaptation
Temperature value (C, F), conversion using implemented curves
Resistance ()
Change monitoring
Spontaneous transmission of changes
______
*)
5.4.1.5
TE-6430
59
5.4.2
5.4.2.1
DO-6200
Pulse commands t1
Checked output of pulse commands
1-pole
Single, double and regulating step commands
Command output (OC)
Application functions and procedures according to IEC 60870-5-101/104
Formal check
Direct command
Select and execute command ("select/execute")
Retry suppression
1-out-of-n check
Control location check
Command locking
Synchronization
Revision
Command output time
Settable
Dependent on the process
5.4.2.1.1
Further Functions
60
5.4.2.2
DO-6212
Pulse commands t1
Checked output of pulse commands
1-pole, 1-pole, 2-pole
Cannot be mixed
Single, double and regulating step commands
Command output (OC)
Application functions and procedures according to IEC 60870-5-101/104
Formal check
Direct command
Select and execute command ("select/execute")
Retry suppression
1-out-of-n check
Control location check
Command locking
Synchronization
Revision
Command output time
Settable
Dependent on the process
5.4.2.2.1
Further Functions
61
5.4.2.3
Pulse commands t1
Checked output of pulse commands
1-pole, 1-pole, 2-pole
Cannot be mixed on one module
Single, double and regulating step commands
Application functions and procedures according to IEC 60870-5-101/104
Formal check
Direct command
Select and execute command ("select/execute")
5.4.2.3.1
Further Functions
62
5.4.2.4
AO-6380
63
5.4.3
64
Predefined Assignment
OUT D00
OUT D01
OUT D07
OUT D10
OUT D11
OUT D17
SI IOM x
SI IOM x
SI IOM x
SI IOM x
SI IOM x
SI IOM x
SI IOM x
SI IOM x
Type
Predefined Assignment
D00/D01
D02/D03
D04/D05
D06/D07
D10/D11
D12/D13
D14/D15
D16/D17
In each case the module DO-62xx must be equipped directly after the module DI-610x.
65
66
Order Information
Contents
A.1
A.2
A.3
I/O Modules.................................................................................................... 70
A.4
A.5
Accessories .................................................................................................... 74
A.6
67
Order Information
A.1
68
Designation
Item Number/MLFB
GC6-630
GC6-632
6MF11130GG300AA0
6MF11130GG320AA0
Order Information
A.2
Designation
Item Number/MLFB
GC6-020
GC6-040
6MF11130GA200AA0
6MF11130GA400AA0
69
Order Information
A.3
70
I/O Modules
Designation
Item Number/MLFB
GC6-100
GC6-101
GC6-102
GC6-103
GC6-104
6MF11130GB000AA0
6MF11130GB010AA0
6MF11130GB020AA0
6MF11130GB030AA0
6MF11130GB040AA0
Order Information
Designation
Item Number/MLFB
GC6-200
GC6-212
GC6-220
GC6-221
GC6-230
GC6-300
6MF11130GC000AA0
6MF11130GC120AA0
6MF11130GC200AA0
6MF11130GC210AA0
6MF11130GC300AA0
6MF11130GD000AA0
71
Order Information
72
Designation
Item Number/MLFB
GC6-307
GC6-308
GC6-310
GC6-380
GC6-420
6MF11130GD070AA0
6MF11130GD080AA0
6MF11130GD100AA0
6MF11130GD800AA0
6MF11130GE200AA0
Order Information
A.4
Interface Modules
Designation
Item Number/MLFB
GA0-819
6MF11112AJ100AF0
GA0-821
GA0-822
GA0-823
GA0-827
6MF11110AJ270AA0
GA0-829
6MF11110AJ210AA0
6MF11110AJ220AA0
6MF11110AJ230AA0
6MF11112AJ200AA0
73
Order Information
A.5
Accessories
A.5.1
Proprietary Modems
*)
A.5.2
Designation
Item Number/MLFB
G21-200
G22-081
6MF11020BC000AA0
6MF11020CA810AA0
withdrawn
Item Number/MLFB
Westermo TD-36AV
(22264 VAC/18300 VDC)
Westermo TD-36LV
(1030 VAC/1060 VDC)
www.westermo.com
Westermo IDW-90
www.westermo.com
74
Coherent Eurocom 24
G21-014
6MF11020BA140AA0
G21-030
6MF11020BA300AA0
Order Information
Designation
Item Number/MLFB
G21-031
6MF11020BA300AA0
www.siemens.com
www.neuhaus.de
or
Dr. Neuhaus Tainy EMOD-L1-IO
A.5.3
Item Number/MLFB
TC6-210-6MF13130GC100AA1
TC6-211
6MF13130GC110AA1
TC6-212
6MF13130GC120AA1
T41-255
6MF13040BC550AA0
T41-251
6MF13040BC510AA0
T41-252
6MF13040BC520AA0
T41-253
6MF13040BC530AA
T41-254
6MF13040BC540AA0
TF5-200
6MF13140FC000AA0
TF5-201
6MF13140FC010AA0
TF5-202
6MF13140FC020AA0
TF5-010
6MF13140FA100AA0
75
Order Information
Fibre optics
length: max. 0.5 km
Designation
Item Number/MLFB
TF5-204
FO-INDOORCABLE-50-DUP-LSOH
TF7-027
6MF13140HA270AA1
TF7-028
6MF13140HA280AA1
FO-OUTDOORCABLE-50-2FIB-ARM
Fibre optics
length: max. 1.5 km
FO-INDOORCABLE-62-DUP-LSOH
FO-OUTDOORCABLE-62-2FIB-ARM
A.1.1.
6MF13140FC040AA0
TF7-006
6MF13140HA060AA1
TF7-007
6MF13140HA070AA1
FO-CONNECTOR-ST-50/62
TF7-016
6MF13140HA160AA1
TF5-101
6MF13140FB010AA1
GC6-810
6MF11130GJ100AA0
Item number/MLFB
www.mtm-power.com
www.syko.de
76
Order Information
A.5.4
SIM Card
Designation
Item Number/MLFB
SIM card 32 kB
CC6-093
6MF12131GA030AA0
CC6-092
6MF12131GA020AA0
A.5.5
Miscellaneous
Designation
Item Number/MLFB
Bus termination
TC6-050
6MF13130GA500AA0
TC6-055
6MF13130GA550AA0
TC6-200
6MF13130GC000AA0
PHOENIX CR-MSTB
Coding section, is inserted on the
multi-pin connector directly on the
terminal module, red insulating material, 6 pcs.
PHO+1734401
WEI+147220
WEI+168551-1044
77
Order Information
Designation
Item Number/MLFB
PHO+0807216
78
WAG+249-117
www.wago.de
Order Information
A.6
Engineering Tools
A.6.1
SICAM TOOLBOX II
A.6.1.1 Toolsets
Engineering Manager
Object-Oriented Process
Data Manager
Designation
Item Number/MLFB
TBII_EMII_V5_Licence
S32-000-5
6MF14030CA000AA5
TBII_EMII-Light_V5_Licence
S32-010-5
6MF14030CA100AA5
TBII_EMII-Light-to-FULL_V5_Licence
S32-011-5
6MF14030CA110AA5
TBII_PSRII_V5_Licence
S34-000-5
6MF14030EA000AA5
TBII_PSRII-Light_V5_Licence
S34-010-5
6MF14030EA100AA5
TBII_PSRII-Light-toFULL_V5_Licence
S34-011-5
6MF14030EA110AA5
TBII_OPMII_V5_Licence
S35-000-5
6MF14030FA000AA5
TBII_OPMII-Light_V5_Licence
S35-010-5
6MF14030FA100AA5
TBII_OPMII-Light-toFULL_V5_Licence
S35-011-5
6MF14030FA110AA5
TBII_CAExplus_V5_Licence
S36-100-5
6MF14030GB000AA5
TBII_CAExplus-Light_V5_Licence
S36-110-5
TBII_CAExplus-Light-toFULL_V5_Licence
S36-111-5
TBII_CAEx_safety_V5_Licence
S36-200-5
TBII_CAEx_safety-Light_V5_Licence
S36-210-5
TBII_CAEx_safety-Light-toFull_V5_Licence
S36-211-5
TBII_CAExplus_Hardlock-USB
G95-521-Z
6MF11100FF210AZ0
The Engineering Manager is the basic toolset, on that all the other toolsets are based. To
each toolset is also a corresponding light version available. The light versions are restricted to
the processing of maximal 100 system elements and maximal 2000 data points.
79
Order Information
A.6.1.2 Packages
Designation
Contents
TBII_Standard_V5
alle Toolsets
TBII_Basic_V5
TBII_Administration_V5
EM II
TBII_Maintenance_V5
EM II, PSR II
TBII_Standard-LIGHT_V5
alle Toolsets
TBII_Basic-LIGHT_V5
TBII_Administration-LIGHT_V5
EM II
TBII_Maintenance-LIGHT_V5
EM II, PSR II
The SICAM TOOLBOX II is supplied on DVD-ROM. For the usage of the single tools software
licenses are required.
An extensiv selection of software licenses, depending on need and configuration, is available:
Local PC configuration
Server-client configuration
Web engineering
Update
The order of the software licenses takes place via the MLFB that starts for V5.0 always with
6MF7050 and for V5.1 always with 6MF7051. Through the selection of the options results the
corresponding variant of the software license.
You find the exact order information in the SICAM TOOLBOX II V5 License Catalog.
A.6.2
80
Web Engineering
Designation
Item Number/MLFB
SC6-900-1.XX86
SC6-060-1.XX86
Glossary
SICAM RTUs Glossary
A
Adress type
The address type defines if a system-technical or a process-technical address is entered as address of a
datapoint in a message
Analog input
Hardware for the acquisition of an analog signal via measuring transformer (measured value via current,
voltage, temperature, resistance)
Analog input module
Module (submodule, I/O module, etc.) to acquire analog signals. Task of an "analog input" is the evaluation of analog signals, and consequently the recuperation of the analog process information items. Depending on the comprehension of the term, the adaptation is also included or not.
Analog output
Hardware for the output of an analog signal to a display equipment (measured value) or to the setpointvalue input to an actuator (current, voltage)
Analog output module
Module (submodule, I/O module, etc.) for the output of analog signals. Task of an "analog output" is the
transformation of arithmetical values to currents or voltages, and consequently for the output of analog
process information items.
Application program
Logical arrangement of all program language elements and constructs, that are required for the intended
signal processing for the control of a machine or of a process with a PLC system (acc. to
IEC 61131-12.1).
With CAEx plus application programs for open-/closed-loop control functions are created. An application
program comprises the task(s) and the related program instances and type instances. An application program is executed by a resource ( CPU).
Application service data unit
The application service data unit (ASDU) is composed of a data unit identifier and a information object.
The data unit identifier has always the same structure for all ASDUs and consists of 4 octets. Its structure
is as follows:
Type identification
Variable structure qualifier
Cause of transmission
Common address of ASDU
The common address of ASDU shall normally be identical to the address used in the link layer. The information object consists of an information object identifier, a set of information elements and, if present, a
time tag. The information object identifier consists of 2 octets. Its structure is as follows:
Function type
Information number
ASDU
Application Service Data Unit
Assign
Linking of datapoint-related information with the object, with that the functions process such information.
At data sources and data sinks of a data stream, datapoint-related information is inserted to or extracted
from the datastream by means of messages. At a source, this information is provided by a function, at a
sink it is utilized by a function.
AU
Automation Unit
81
Glossary
Autonomy
An autonomous basisc system element and its supplementary system elements (protocol and peripheral
elements) continue working during a failure of the master control unit
Automation unit
An automation unit is a modular structured device for the acquisition, processing and output of process information. It communicates in automation networks via a serial or Ethernet protocols with other automation units or control center systems.
An automation unit consists of at least 1 mounting rack or 1 DIN rail (depending on system), 1 power supply and 1 basic system element, as well as optional peripheral elements and optional protocol elements.
Automatic dataflow routing
The routing of individual process information items is not necessary. Simply only the direction (monitoring
direction, control direction, both directions) the messages are to be transmitted must be parameterized.
The type identification of each message gives information about to which class a message belongs and
with which methods it is to be distributed.
Messages with process information in monitoring direction are distributed by means of an entry in the topology. Messages with process information in control direction are distributed to their target that is determined by their CASDU and via interfaces that are defined in the topology. The CASDU is interpreted as
target address.
Ax 1703 peripheral bus
Enables the secured (hamming distance 4), serial, system-internal communication between the basic system element and the peripheral elements
Ax PE Bus
Ax 1703 peripheral bus
B
Basic system element
System element for processing of information according to different criterions (e.g. automation,
telecontrol, etc.) and for the administration of system functions (e.g. parameter, diagnosis, etc).
Binary
Representation of information by means of 2 different states or 2 discreet values (=digital)
Binry signal
Electrical signal that is used for the transport of a binary process information; as well as the digital signal,
2 different and not coherent ranges of the electrical signals are defined, for each a status/value that the
binary process information can receive. Therefore, in the technical data of digital inputs that are designed
fort he acquisition of binary signals, voltage ranges for "logical 0" and "logical 1", the universal designation
for the both states/values.
Binary input
Designation for a module, a submodule, an I/O module etc. fort he acquisition of binary signals; task of a
"binary input" is the evaluation of binary signals and therefore the recovery of the binary process information
Binary input
Hardware for the acquisition of a binary signal (single-point information, double-point information)
Binary output
Hardware for the output of a binary signal (information or command)
Binary process information
Process information of type "binary", e.g. circuit breaker position ON/OFF
BSE
Basic System Element (master control element, processing and communication element)
82
Glossary
C
CAEx plus
Tool for the creation of application programs (Computer Aided Engineering), based on the tool logiCAD
from the company logi.cals
CASDU
Common Adress of the ASDU, that part of the ASDU, that is common for all ASDUs of a station
Cause of transmission
Spontaneous transmission, general interrogation data, periodical data, command preparation, command
command activation (acc. to IEC 60870-5-101)
Class 1 data
If several data points are to be transmitted to the central station (spontaneous or on request) at the same
time, the Class 1 data will be sent before the Class 2 data (priority).
With dial-up traffic, data of the Class 1 lead to a spontaneous connection setup and data transmission.
Class 2 data
If several data points are to be transmitted to the central station (spontaneous or on request) at the same
time, the Class 2 data will be sent after the Class 1 data.
With dial-up traffic, the connection setup and the data transmission takes place only upon interrogation by
the central station.
Command direction
Transmission facility from the central station to a substation
Command return information
The command return information is an additional information for the double-point information, displays the
reason for the status change (breaker tripping or switching operation in progress)
Configuration
Configuration is used in a multiple meaning:
a) engineering of the configuration of an automation unit in the engineering tool
b) physical aligning and mounting of the configured hardware
plugging in the slot defined by the configuration (slot addressing), or
setting the address defined by the configuration, and plugging in an arbitrary slot (adjustable address)
COT
Cause of Transmission
CPU
Central Processing Unit
CTS
Clear to Send, handshake control line of an RS-232 interface
Cyclic transmission
Periodical transmission according to the scan rate of the application program
D
Data class
This assignment is specified in the standard IEC 60870-5-101/-104, and serves for the priorization of information objects for the transmission by the communication function:
Class 1 data
Class 2 data
Dataflow routing
Functions and methods for distribution of messages to ist targets:
83
Glossary
84
Glossary
DTR
Data Terminal Ready; control line of an RS-232 interface
E
EM II
Confiugration tool of SICAM TOOLBOX II (Engineering Manager II)
Ethernet
Wired local network according to IEEE 802.3
External error
Error that is detected through monitoring the information from sensors and actuators.
Can concern the peripheral element, the wiring, and sensors or actuators, insofar as the source of error
can not be unequivocally localized to the peripheral element; otherwise it would be an internal error.
Externally managed parameter
Parameter that is required on a module (e.g. supplementary module), however, is managed and stored on
the higher-level module
F
FAT
File system on storage media (File Allocation Table); FAT16 up to 2 GB, FAT32 as of 32 GB capacity
Fieldbus interface processor
The fieldbus interface processor serves for the serial connection of SICAM RTUs systems to a Profibus
(Profibus Master); Profibus Slaves are connected acc. to EN 50170-2
FIP
Fieldbus interface processor
Firewall
Blockage of a local network or computer against not allowed access from a supraregional network. Function for the filtering of data from the internet for the protection against invaders and malicious software.
Firmware
Program that is not changeable by the user, that adds a predefined and parameter-settable functionality to
the hardware
FPU
Floating Point Unit
FUD
Function diagram
Function diagram
Graphical program for open-/closed-loop control functions according IEC 61131-3
FW
Firmware
G
Global parameter
Parameter that is managed and stored on the system element (central system function) but used also on
other system elements of the automation unit
85
Glossary
GPRS
Global Package Radio Service. Data rates up to 171 kbps, usually up to 85 kbps. Package-oriented connection based on TCP/IP and UDP/IP. Billing usually according to data volume. Network expansion areawide.
GSM
Global System for Mobile Communication with the services speech, SMS, direct data connections
H
I
IL
Instruction list
Instruction list
Line-oriented program for open-/closed-loop control functions acc. to IEC 61131-3
Internal errors
Internal errors are errors which are unambiguously caused by the system element
IOA
Information Object Address
ISDN
Integrated Standard for Digital Network
K
L
LAN
Local Area Network
Load share operation
Redundant communication via 2 interfaces, whereby the messages are partitioned in undisturbed operation on both interfaces according to particular rules (dependent on load or priority)
Local parameter
Parameter that is managed on the own module (firmware) and is used only there
M
MDI
Media-Dependent Interface, adaptation to the cable type
MIB
Management Information Base; description file for SNMP
Modem
Data transmission device for connecting date end devices to the telephone network
Module
Hardware that is equipped in a mounting rack or on a carrier module; hardware of a system element
Module failure
Signals that the internal communication with a module is no more possible and is commonly replicated by
the supervising basic system element.
86
Glossary
Module number
System-technical identification of a system element within an automation unit, part of the IOA in a message with system-technical addressing. The other parts of the IOA are the value number and the
subaddress.
Mounting rack
Device wherein that modules and instruments are installed
N
Network interface processor
The network interface processor serves for the connection of SICAM systems to the Ethernet LAN according to IEEE 802.3
NIP
Network interface processor
Non-volatile
Function: also with/after voltage failure further available (no defect)
Information in a memory: not transient, undetachably
Normally open contact
Relay contact that is open when the relay is not activated; the contact closes when the relay is activated
O
OPM II
Central SICAM TOOLBOX II configuration tool (Object-oriented Processdata Manager)
Output active
If the output pulse is set and a command output (binary output) is already selected (relay activated), the
command is output to the process
P
PBA
Peripheral Module Address
PCM
Puls Code Modulation
PE
Peripheral Element
Peridocal control circuit check
The periodical control circuit check detects if the command circuits are ready to function correctly, without
activating the actuator.Control circuits are checked one by one, by activating all its relays, one by one,
thus closing the control circuit with high restistance.
Periodical datapoint
A periodical datapoint is used for the exchange of a process signal or a derived information between the
peripheral element and the higher-level open-/closed-loop control function.
Periodical information
A periodical information has a deterministic transmission behavior and is used for the exchange of a process signal or a derived information between the peripheral element and the higher-level open-/closedloop control function.
A periodical information is always transmitted in groups and consequently with the transmission already
have a chronologically consistent interrelationship.
87
Glossary
Periodical transmission
Exchange of a process signal or a derived information between the peripheral element and the higherlevel open-/closed-loop control function.
Peripheral element
The peripheral element is a supplementary system element for process data acquisition and/or control of
actuators. It comunicates via the Ax-PE-Bus with the basic system element.
PLC
Programmable Logic Controller
PRE
Protocol Element
Programmable logic controller
Digitally operating electronic system, designed for use in an industrial environment, which uses a programmable memory for the internal storage of user-oriented instructions for implementing specific functions such as logic, sequencing, timing, counting and arithmetic, to control, through digital or analog inputs
and outputs, various types of machines or processes. Both the PC (PLC) and its associated peripherals
are designed so that they can be easily integrated into an industrial control system and easily used in all
their intended functions (IEC 61131-1, chapter 2.50).
Protocol element
The protocol element is a supplementary system element for communication with other automation units
or control systems. It comunicates via the internal bus (ZBG-Bus) with the basic system element.
PSR
SICAM TOOLBOX II configuration tool
PSTN
Public Switched Telephone Network
PT 100
Temperature-dependent resistance element with PT 100 characteristic
Q
R
Routing
Routing of data streams: Messages are "routed" from their sources to their sinks. This works similar to directing railroad cars by setting track switcher. Messages contain data point related information.
Retained variables
Variables in a non-volatile memory. The value of the variable is retained during a power failure.
Router
Network device for connecting two independent network segments as internet and LAN
RS-232
Standard for serial data transmission
RS-485
Standard for serial data transmission
RTS
Request to Send (switch on transmit device), control line of an RS-232 interface
S
SD card
Secure Digital Memory Card; up to 2 GB storage capacity
88
Glossary
SD-HC
Secure Digital High Capacity Memory Card; up to 32 GB storage capacity
SD-XC
Secure Digital Extended Capacity Memory Card; up to 2 TB storage capacity
Selective dataflow routing
Routing of individual process information items. In simple applications the messages are distributed by
means of an entry in the topology. For more complex applications, the messages can be distributed selectively by means of dataflow filters: for each communication interface, band-pass filters or blocking filters
can be set. Also wildcards can be used for all address attributes of the message, to direct the dataflow
very specific.
SI
Single-point information
Serial interface module
Hardware of a protocol element that can be installed on a basic system element
Serial interface processor
The serial interface processor serves for the serial connection of SICAM RTUs systems via a transmission
facility or via a direct connection
SIM
Serial interface module
SIP
Serial interface processor
Single command
A command used to cause a change of state of operational equipment in one direction
Single-point information
Monitored information represented by only one bit characterizing two determined states of operational
equipment
SMS
Short Message Service, transmission of up to 160 characters
SNMP
Simple Network Management Protocol
SNMP is a network protocol to monitor and control network components (e.g. router, switches, server, printer)
from a central station.
SNTP
Simple Network Time Protocol
Spontaneous datapoint
Binary information that is transmitted upon change spontaneously in a message. It is always transmitted
individually, and usually has a time tag in order to be able to establish a chronologically consistent interrelationship afterwards.
With the current, voltage and counting pulse acquisition a spontaneous transmission of the information
takes place threshold value controlled (exception:class 2 data with dial-up traffic).
Spontaneous information object
A spontaneous information object that is transmitted upon change spontaneously in a message, and is
used for the exchange of a process signal or a derived information (including status) between the peripheral element and the particular automation unit, another automation unit or a control system.
A spontaneous information object is always transmitted individually and normally has a time stamp, in order to be able to establish a chronologically consistent interrelationship later.
89
Glossary
Spontaneous transmission
Serves for the exchange of a process signal or a derived information (inclusive status) between the peripheral element and the own automation unit, another automation unit or a control center system
SSE
Supplementary system element
SSM
Tool for the administration of SICAM TOOLBOX II data (Siemens Stammdaten Manager); reserved for
developer of Siemens AG.
Supplementary system element
Supplementary system elements are situated hierarchically below basic system elements; there are peripheral elements, and protocol elements
Switch
Network device for connetion and distribution in ethernet
System element
Functional unit consisting of hardware and firmware
System-internal information
Information that is used exclusively for the exchange of control information between peripheral elements
and system functions, and that is not available to the user. It can be transported through the system like a
periodical information or like a spontaneous information object.
A system-internal information is only mentioned in order to explain the behavior of the described functions.
T
TAP
Telocator Alphanumeric Protocol
TCP/IP
Transmission Control Protocol/Internet Protocol
TETRA
Terrestrial trunked radio, universal platform for different mobile radio services, time multiplex system with
4 time slots
TM
Terminal Module; Module for mounting on a DIN-rail
TM bus
Bus between peripheral control module (Master) and I/O-module (Slave)
SICAM TOOLBOX II
PC-based set of tools for configuration and service of SICAM automation units
U
User diagnostic classes
Serve for the classification of the individual diagnosis information items additionally to the system diagnostic classes. The are freely allocatable (maximal 8 classes).
User diagnostic records
Diagnosis information items, that are formed by means of application-specific routings from the diagnosis
bits of the detailed diagnostic table. Maximal 8 user diagnostic classes can be allocated.
90
Glossary
V
VAC
Volts of Alternating Current
VDC
Volts of Direct Current
VPN
Virtual Private Network (logical connection for secure transmission of data via internet)
W
WAN
Wide Area Network
Web services
Web standard for function calls between independent devices
X
Z
91
Glossary
92