Partlow MRC 7000 Installation, Wiring, Operational Manual
Partlow MRC 7000 Installation, Wiring, Operational Manual
Partlow MRC 7000 Installation, Wiring, Operational Manual
00
Edition 7 Dec. 1996
Revised February, 1998
MRC 7000
Installation, Wiring, Operation Manual
Brand
NOTE
2
TABLE OF CONTENTS
SECTION 1 - GENERAL
1.1 Product Description
PAGE NUMBER
5
8
8
8
8
9
14
SECTION 3 - CONFIGURATION
3.1
3.2
3.3
3.4
3.5
20
21
21
21
22
SECTION 4 - OPERATION
4.1 Off Control Mode
4.2 Alarm Operation
4.3 Tune Mode Operation
37
41
42
SECTION 5 - SERVICE
5.1 Service
5.2 Changing Charts
5.3 Changing Pens
5.4 Calibration
5.5 Test Mode Procedures
5.6 Troubleshooting and Diagnostics (Error Code Definitions)
45
45
45
46
51
55
APPENDICES
A - Board Layouts and Jumper Positioning
A-1 - Processor Board
A-2 SPST Relay/SSR Driver Output Board
A-3 SPDT Relay/SSR Driver Output Baord
A-4 Current Output Board
B - Glossary
62
63
64
65
66
C- Order Matrix
D- Product Specifications
68
69
72
Inside back page
Recorder Description
Recorder Display
Installation Panel Dimensions Conduit Opening Locations
Noise Suppression
Noise Suppression
Board and Terminal Locations
AC Power Input
Thermocouple Inputs
RTD Inputs
Milliamp, Volt and Millivolt Inputs
Remote Setpoint Input VDC, mADC
Digital Communications
SPST Relay Output
SPDT Relay Output
SSR Output
Current Output
24 VDC Power Supply Option
Position Proportioning Control Output
Keypad Features
Changing Pens
Program Mode Configuration Procedure
Tune Mode Configuration Procedure
Enable Mode Configuration Procedure
Calibration Procedure
Test Procedures and Description
5
7
9
11
11
14
15
15
15
16
16
17
17
18
18
18
19
19
24
45
28
34
36
47
52
FLOW CHARTS
Flow - Calibration
Flow - Enable Mode
Flow - Program Mode
Flow - Setpoint Select
Flow - Standby
Flow - Test
Flow - Tune Mode
46
36
25
38
41
50
33
FIGURE 1-1
Pen 1 Display
Pen 2 Display
The number of keys and LED's will depend upon the configuration of individual unit.
1.1.2 RECORDING
The instrument records the selected process variable on a 10-inch circular chart. One box of
standard charts is provided with each recorder. Charts are available in a wide selection of
ranges. Chart rotation speed is programmable from 0.1 to 999.9 hours per revolution in 0.1
hour increments. The instrument can be ordered with one or two pens. Pen 1 is red and Pen 2
is green. Pens are the disposable fiber-tip type.
1.1.3 DISPLAYS
Each instrument is provided with a digital display and status indicator for each pen provided
(See Figure 1-1, page 5). The display may be configured to display the Process Value,
Process Value and Setpoint, Deviation from Setpoint only, Deviation and Setpoint, or Setpoint
only. During configuration the display(s) is/are used to show the enabled modes of operation
and the parameter codes.
The display in the upper right corner is for Pen 1, the display in the lower right corner is for
Pen 2 (if provided). The display includes status indicators for Manual mode operation, Output
1, Output 2 , Alarm, degrees C, degrees F, engineering units, setpoint and minus sign. See
Figure 1-2 ( page 7).
Display resolution is programmable for 0.1 or 1 degree for thermocouple and RTD inputs, and
none, one, two or three decimal places for other input types.
1.1.4 CONTROL
The instrument can be provided with relay, solid state relay driver and milliamp DC outputs.
Instruments can be programmed for on-off, time proportioning, current proportioning or
position proportioning control depending upon the hardware present. Switching between the
Control mode and the Manual mode of operation is easily accomplished with a dedicated key
on the keypad. Switching is bumpless from the Control to the Manual mode, and while in
manual, manipulation of proportional outputs is possible. Each pen of a dual pen recording
controller is provided with its own AUTO/MANUAL key . Other standard control features
include proportional control output limits, setpoint limits, anti-reset windup and a unique
Automatic Transfer function. If configured, the Automatic Transfer function allows manual
control of the proportional output until the process reaches the setpoint at which time the
instrument will go into the Control (automatic) mode of operation.
1.1.5 ALARM
An Alarm indicator is standard for each pen. Two alarm functions are provided for each pen
and the alarm indicator will light if either alarm for that pen is on. Alarm settings are programmable. Alarm type may be selected as process direct or reverse (high or low), deviation from
setpoint direct or reverse, and deviation band open or closed within the band. Alarm outputs
can be provided by assigning any relay(s) Single Pole/Single Throw (SPST)or Solid State
Relay (SSR) driver to the respective alarm.
FIGURE 1-2
MAN
SP
Setpoint
C
F
U
Minus Sign
Digital Display
CAUTION: The Instrument AC power input is specified in the model number and on the
wiring label affixed to the the top center of the platen. Verify the AC power input required
by the instrument prior to proceeding with installation.
Unpacking 2.2
Remove the instrument from the carton and inspect for any damage due to shipment. If any
damage is noticed due to transit, report and file a claim with the carrier. Write the model
number and serial number of the instrument on the inside of the front cover of this Operation
Manual for future reference.
Location 2.3
Locate the instrument away from excessive moisture, oil, dust, and vibration. Do not subject
the instrument to operating temperatures outside of the 32F to 131F (0C to 55C) range.
Mounting 2.4
Figure 2-1 (page 9) shows an installation view and physical dimensions for a panel mounted
instrument. The panel where the instrument will be mounted must provide rigid support for
the approximately 20 pound instrument. Adjacent instruments may be mounted within a
minimum of 2 inches horizontally and 3 inches vertically, providing that proper panel support
is supplied.
PANEL MOUNTING HARDWARE REQUIRED: (not provided with instrument)
(4) 1/4"-20 x 2" flat head bolts w/nuts
(4) appropriate lock washers
PANEL MOUNTING:
1) Cut panel opening to the dimensions illustrated in Figure 2-1 (page 9).
2) Insert the instrument in the panel opening. Firmly fasten the instrument to the panel using
the nuts, bolts and lock washers.
SURFACE MOUNTING:
1) Install the mounting brackets,ordered separately,, on the vertical sides of
instrument housing. Use the brackets to fasten the instrument to the surface.
FIGURE 2-1
7/8" Dia hole for
wiring - 3 locations,
EC1, EC2, and EC3
EC3
EC1
13 3
16
(335 mm)
EC2
15 1 (384.2 mm)
8
21
2
4
PLACES
3 43
(64 mm)
11
16
(119.1 mm)
4
WIDTH OF COVER
2 19 (65.9 mm)
32
Mounting Bracket (2)
9
32 DIA.(7.1mm)
Holes to mount
bracket to surface
5
12 8
71
2
(320.7 mm)
(190.5 mm)
1
13 2 (342.5 mm)
15
(
354 mm)
13
16
7
32 (5.5 mm)
14 11/16"
373mm
10
FIGURE 2-2
0.5
mfd
1000V
Coil
220
ohms
115V 1/4W
230V 1W
FIGURE 2-3
MOV
C
Inductive
Load
11
where;
TABLE 1
Temperature error in C per 1000 feet of Leadwire
AWG Thermocouple Type
No.
J
K
T
R
S
10
.68
1.71
.76
2.05
2.12
12
1.08
2.68
1.21
3.30
3.29
14
1.74
4.29
1.95
5.34
5.29
16
2.74
6.76
3.08
8.30
8.35
18
4.44
11.00
5.00
13.52
13.65
20
7.14
17.24
7.84
21.59
21.76
24
17.56
43.82
19.82
54.32
54.59
E
1.15
1.82
2.92
4.60
7.47
11.78
29.67
B
14.00
22.00
35.00
55.50
88.50
141.00
356.50
N
2.94
4.68
7.44
11.82
18.80
29.88
75.59
C
2.53
4.07
6.37
10.11
16.26
25.82
65.27
E
2.07
3.27
5.25
8.28
13.44
21.21
53.40
B
25.20
39.60
63.00
99.90
159.30
253.80
641.70
N
5.30
8.42
13.38
21.28
33.85
53.79
136.07
C
4.55
7.32
11.47
18.20
29.27
46.48
117.49
TABLE 2
Temperature error in F per 1000 feet of Leadwire
AWG Thermocouple Type
No.
J
K
T
R
S
10
1.22
3.07
1.37
3.68
3.81
12
1.94
4.82
2.18
5.93
5.93
14
3.13
7.73
3.51
9.61
9.53
16
4.93
12.18
5.54
14.93
15.04
18
7.99
19.80
9.00
24.34
24.56
20
12.85
31.02
14.12
38.86
39.18
24
31.61
78.88
35.67
97.77
98.26
Example
A recorder is to be located in a control rrom 660 feet away from the process. Using 16 AWG,
Type J thermocouple, how much error is induced?
Terr = TLe * L = 4.93 (F/1000 ft) from Table 2.
Terr = 4.93 (F/1000 ft)
Terr = 3.3 F
12
where;
TABLE 3
3 Wire RTD
AWG No.
10
12
14
16
18
20
24
TABLE 4
AWG No.
10
12
14
16
18
20
24
Error C
+/-0.04
+/-0.07
+/-0.10
+/-0.16
+/-0.26
+/-0.41
+/-0.65
Error F
+/-0.07
+/-0.11
+/-0.18
+/-0.29
+/-0.46
+/-0.73
+/-1.17
2 Wire RTD
Error C
+/-5.32
+/-9.31
+/-13.3
+/-21.3
+/-34.6
+/-54.5
+/-86.5
Error F
+/-9.31
+/-14.6
+/-23.9
+/-38.6
+/-61.2
+/-97.1
+/-155.6
Example
An application uses 2000 feet of 18 AWG copper lead wire for a 3-wire RTD sensor. What is
the worst-case error due to this leadwire length?
Terr = TLe * L
TLE = +/- .46 (F/1000 ft) from Table 1
Terr = +/- .46 (F/1000 ft) * 2000 ft
Terr = +/- 0.92 F
13
FIGURE 2-4
1 2
1 2 3 4
1 2 3 4
1 2 3 4
TB1
TB6
TB7
TB8
RELAY/SSR Driver
Board
TB9
Processor Board
1 2 3 4
TB4
12
1 2 3 4 5
TB5
1 2 3 4 5
TB10
TB11
TB12
TB13
1 2
1 2
1 2
1 2
AC Power Input
Analog input and mADC outputs
SPST relay or SSR driver outputs
SPST relay or SSR driver outputs (provided when > 4 relays & SSR drivers total are
specified)
14
FIGURE 2-5
AC Instrument Power Input
Connect the 115 VAC hot and neutral to terminals 1 and 2 respectively of TB1. See Figure 2-4
(page 14) for Terminal Board locations on the instrument. Connect the 230 VAC one leg to
each terminal, be sure to check the position of the Voltage Selector switch provided with 230
VAC instruments. The switch position must match the voltage input to the instrument.
TB1
Connect the AC
Line
1
Line 2
ground at the
green ground screw
on the left side of
1
2
the inside of the
case
FIGURE 2-6
Thermocouple Inputs
Use TB4 for the Pen 1 input, and TB5 for the Pen 2 input. Connect the positive leg of the
thermocouple to terminal 1, and the negative to terminal 2. Be sure that the input conditioning
jumpers are properly positioned for a thermocouple input. See Appendix A-1 (page 62).
TB4 or TB5
2 3 4
Grounded or
Ungrounded
Thermocouples
may be used
FIGURE 2-7
RTD Inputs
Use TB4 for the Pen 1, and TB5 for the Pen 2 input. Connections are shown for 3 wire and 2
wire RTD inputs. If a three wire device is used, install the common legs to terminals 2 and 3. If
a two wire device is used, install a jumper between terminals 2 and 3. Be sure that the input
conditioning jumpers are properly positioned for an RTD input. See Appendix A-1 (page 62).
+
1
TB4 or TB5
2 3 4
+
1
TB4 or TB5
2 3 4
Jumper
SUPPLIED BY
CUSTOMER
3 Wire RTD
2 Wire RTD
15
FIGURE 2-8
Volt, Millivolt and milliamp Input
Make the volt, millivolt and milliamp connections as shown below. Use TB4 for thePen 1 input,
and TB5 for the Pen 2 input. Terminal 1 is positive and terminal 2 is negative. The milliamp
input requires the installation of an appropriate shunt resistor (ordered separately) between
terminals 1 and 2. Be sure that input conditioning jumpers are in the correct positions for the
input being connected. See Appendix A-1 (page 62).
NOTE: Fault Detection is not functional for 0-5V or 0-20mA inputs.
TB4 or TB5
+ 1 2 3 4 5
SHIELDED
TWISTED
PAIR
MAY BE
+ GROUNDED
SOURCE OR
UNGROUNDED
FIGURE 2-9
Remote Setpoint Input VDC , mADC
If Remote Setpoint option has been specified, make connections as shown. The remote
setpoint input may be selected as either 0 to 5 VDC or 1 to 5 VDC input in the Program mode
section. Make sure the configuration properly matches the input used. Use TB4 for Pen 1, and
TB5 for Pen 2 if Pen 2 is provided and specified with the Remote Setpoint option. Connect
the positive lead to terminal 4, and the negative lead to terminal 3 (Terminal 3 is the ground,
terminal 4 is the input, terminal 5 is 5 VDC.) If a 4 to 20 mADC remote setpoint is to be used,
the instrument remote setpoint input should be configured for 1 to 5VDC in the Program
mode, and a 250 ohm resistor should be installed across terminals 4 and 3. A 250 ohm
resistor is provided with the instrument, one per pen. The resistor(s) are shipped in the plastic
bag that is clipped to the inside of the instrument cover. This is the same bag that contains
the spare pen cartridge(s).
TB4 or TB5
+ 1 2 3 4 5
TB4 or TB5
+ 1 2 3 4 5
SHIELDED
TWISTED
PAIR
SHIELDED
MULTI-CONDUCTOR
CABLE
- +
SOURCE
16
150 OHM
TO 10K OHM
POTENTIOMETER
FIGURE 2-10
Digital Communications Options
Connections are made as shown using TB2. Refer to the Protocol Manual, Form #2878 for
more details regarding the connections and how to use this option. This document is provided
only when this option has been specified. If the communications network continues on to other
instruments, connect the cable shields together, but not to the instrument. A terminating
resistor should be installed at the terminals of the last unit in the communications loop. If the
communications network ends at the instrument, the shield is not connected.
TB2
Serial A
1 2
Serial B
TOWARD THE
COMPUTER
NETWORK
CONTINUATION
(IF APPLICABLE)
FIGURE 2-11A
SPST Relay Output
Connections are made to relays A through F as shown. Terminal connections are made using
TB6 (Relay/SSR Driver A, B), TB7 (Relay/SSR Driver C, D) and TB8 (Relay/SSR Driver E, F).
HOT
NEU
LOAD
1 2
3 4
N.O. C N.O. C
POWER
5 AMPERES
MAXIMUM
AT 115 VAC
17
FIGURE 2-11B
SPDT Relay Output
HOT
NEU
LOAD
1 2
N.O. C N.C.
POWER
5 AMPERES
MAXIMUM
AT 115 VAC
TB6 Relay A
TB7 Relay B
FIGURE 2-12
SSR Driver Output
Connections are made to relays H through A as shown. Terminal connections are made using
TB9, TB8, etc. depending on the number of SSR Driver outputs specified.
1 2 3 4
TB6 THRU TB9
SSR
FIGURE 2-13
Current Output
Connections are made to current outputs A thruough D as shown. Each current output is
programmable as either 4 to 20 mADC or 0 to 20 mADC. Each output must be assigned to the
desired function in the Program mode. Terminal connections are made using TB10 through
TB13 for current output A through D respectively. Connect positive lead (+) to terminal 1 and
the negative lead (-) to terminal 2. Each current output will operate up to a 650 ohms
maximum load.
1 2
SHIELDED
TWISTED
PAIR
LOAD
18
650 OHMS
MAXIMUM
FIGURE 2-14
Transmitter Power Supply Input
If the isolated 24 VDC regulated transmitter power supply has been specified, the connections
should be made as shown. Connections are made using TB3, terminal 1 is positive and
terminal 2 is negative. The power supply is capable of providing the power needed by up to 2
transducers (40 mADC maximum).
TB3
+ 1 2
TB4 or TB5
+ 1 2 3 4 5
TB3
+ 1 2
TB5
TB4
+ 1 2
3 4
+ 1 2
3 4
SHIELDED
TWISTED
PAIRS
+ -
+ -
+ -
TWO WIRE
TRANSMITTERS
TWO WIRE
TRANSMITTERS
TWO WIRE
TRANSMITTERS
FIGURE 2-15
Position Proportioning Control Output
Position Proportioning control requires that two relays (or SSR Drivers) and the Position
Proportioning Auxiliary input be specified. On a dual pen instrument, either pen may be
configured with Position Proportioning control provided the outputs and auxiliary inputs have
been properly specified.
L2
OPEN
L
C
CLOSE
H
Modulating Motor
4
3
2
TB6, TB7
or TB8
TB4
or
TB5
Slidewire
Feedback
Resistance
min. 135
ohms
max. 10K
ohms
5
4
3
L1
19
Configuration 3.1
After completing installation and wiring of the instrument the configuration (set up) procedures
must be performed to prepare the instrument for operation on the intended application. The
procedures include selecting specific parameters, entering data and possible jumper positioning. Once properly configured the instrument will retain the user selections in memory so this
procedure need not be repeated unless required by changes in the application.
Parameter selections and data entry are made via the front keypad. To ease configuration
and operation, user entered data has been divided up into several sections referred to as
modes. Each mode contains a different type of data or may be used for specific operating
functions. For two pen instruments, some modes are common to both pens. These modes are
as follows:
Control
(CtrL)
Test
(tESt)
MODE
Calibrate
(CAL)
DISPLAY CODE
Program
(Prog)
Tune
(tunE)
Setpoint Select
(SPS)
FUNCTION
Standby
(Stby)
OFF
(oFF)
DESCRIPTION
Off
oFF
Operation
Control
CtrL
Control
Test
tESt
Service
Tests Instrument
Operation
Calibration
CAL
Service
Calibrates, Resets
Instrument
Program
Prog
Configuration
Configure Operating
Parameters
Tune
tunE
Configuration &
Operation
Setpoint Selection
SPS
Operation
Selects Remote or
Local Setpoint
Operation (Remote
Setpoint Optional)
Manual
Stby
Operation
Enable
EnAb
Configuration
Mode security
system, can lock out
everything except Off
and Control (See
Appendix A-1, page
62, for hardware
lockout information)
Associated with each mode is a series of unique displays that are accessed via the front
keypad.
Prior to first time operation of the instrument, the configuration procedures for the Program
and Tune modes must be performed as applicable. Calibration and Test modes are not used
as part of the instrument configuration or operation. These are used for service and maintenance functions and are discussed in Section 5.4 & 5.5 of this manual (page 46 - 54).
20
The sensor input jumpers JU4, JU5, JU6 and JU7 condition the sensor input signals
and must be used in conjunction with input type selections made in the Program mode.
(page 28).
21
the
Amber
Red
Amber
Red
Red
Red
Red
SP
-
Green
Red
22
1.
2.
3.
4.
5.
6.
Exit a mode.
Turn a mode On in the Enable mode
Increase a parameter numerical value
View the setpoint for Pen 1 (Press release)
Increase the setpoint value (Press hold)
Work in conjunction with other keys:
a. With the SCROLL key to display proportional output %
b. With the DOWN key;
1) Lamp test (Press release)
2) Enter the Enable mode (Press and hold for 11
seconds)
1.
2.
3.
4.
5.
6.
7.
Enter a mode
Turn a mode Off in the Enable mode
Decrease a parameter numerical value
View the setpoint for Pen 2 (if provided)
Decrease the setpoint value (Press hold)
Step display through parameter codes in a mode
Work in conjunction with other keys:
a. With the SCROLL key;
1) On power up to alter the model number
displayed
2) Enter Cal/Test functions
b. With the UP key;
1) Lamp test (Press release)
2) Enter the Enable mode (Press and hold for
11 seconds)
AUTO
MAN
23
FIGURE 3-1
Pen 1
AUTO/MAN
Key
SCROLL
Key
UP
Key
Pen 2
AUTO/MAN
Key
DOWN
Key
LAMP TEST
From the Off or Control modes, all display and status LEDs can be illuminated simultaneously
by depressing the UP and DOWN keys at the same time. Any defective LEDs will not light.
CHANGE CHART (also see Changing Charts, Section 5.2)
If the UP and DOWN keys are held depressed for more than 2 seconds but less than 4
seconds, the display will show CChg momentarily. The pen(s) will move to and remain at a
point above the top graduation on the chart and the chart will stop rotating to allow the chart to
be changed. The pens will remain fully upscale with the chart OFF; otherwise, the unit will
continue to operate normally in the current mode. To restore pen(s) position and chart
rotation, press the UP and DOWN keys for more than 2 seconds, but less than 4 seconds.
PEN RESYNCHRONIZATION
To resynchronize the pen(s), depress the UP and DOWN keys for 4 seconds, the display will
show P dn momentarily, the pen(s) are driven to the "Pen Home" position below the bottom
graduation on the chart while the unit resynchronizes their position. After about 14 seconds,
the pen(s) will return to their correct position. All other functions of the unit's present mode
continue to operate normally.
24
Prog
A
inPS
AL2
iCor
diSP
out1
dPoS
o1uL
Euu
o1LL
EuL
out2
HyCo
o2uL
HyAo
o2LL
KEY
rSP
Actual Display
AL1
rSPu
ON
OFF
Scroll Key
Down Arrow
25
rSPL
PoL
SPuL
Cru
SPLL
CrL
AtFr
P1EC
Prnd
P2EC
dFF
PAEC
PFF
rLyA
Actual Display
Pout
rLyb
Pou
rLyC
KEY
ON
OFF
Scroll Key
C
Numeric Display Use arrow keys
to change value
Up Arrow Key
Down Arrow
26
rLyd
Cobr
rLyE
CoCr
rLyF
Codr
rLyg
Crt
rLyH
PAPu
CurA
C00
Com (Optional)
Curb
CCon
CurC
Cbs
Curd
CAd1
CoAr
CAd2
27
STEP
DESCRIPTION
Input Select
DISPLAY AVAILABLE
CODES SETTINGS
inPS
NOTE:
Fault Detection is not functional
for 0-5V or 0-20mA inputs.
28
FACTORY
SETTING
Input Correction
iCor
Output 1
out1
0 = None
0
1=On-Off- Direct
2=On-Off- Reverse
3=Time Proportioning- Direct
4=Time Proportioning -Reverse
5=Current Proportioning -Direct
6=Current Proportioning -Reverse
7=Position Proportioning (open)
YOUR
SETTING
DISPLAY AVAILABLE
CODES SETTINGS
FACTORY
SETTING
YOUR
SETTING
STEP
DESCRIPTION
Output 1 Percent
Upper Limit
(o1uLand o1LL will
not be seen if out1 = 0,1,2)
o1uL
0 to 100 percent
100
Output 1 Percent
Lower Limit
o1LL
0 to 100 percent
Output 2
out2
0 = None (Position
0
Proportioning - Direct Closed)
1=On-Off- Direct
2=On-Off- Reverse
3=Time Proportioning- Direct
4=Time Proportioning-Reverse
5=Current Proportioning- Direct
6=Current Proportioning -Reverse
7=Position Proportioning
(Reverse/Closed)
Output 2 Percent
Upper Limit (o2uL and
o2LL will not been seen if
out2 = 0,1,2,7)
o2uL
0 to 100 percent
100
Output 2 Percent
Lower Limit
o2LL
0 to 100 percent
Alarm 1
the Alarm Point
is selected in the
Tune mode
AL1
0 to 6
0
0 = None
1=Process Alarm-Direct
2=Process Alarm-Reverse
3=Deviation Alarm-Direct
4=Deviation Alarm-Reverse
5=Deviation Band Alarm-Open within band
6=Deviation Band Alarm-Closed within band
10
Alarm 2
AL2
11
Display Select
diSP
12
Decimal Position
dPoS
0 to 3
0
0=None
1=One decimal place
2=Two decimal places
3=Three decimal places
RTD and thermocouple inputs
are limited to either 0 or1 decimal positions
13
Engineering Units
Euu
Upper Value (Euu and
EuL will be seen if the pen
input select = 30,31,32,33,34)
-9999 to 9999
1000
14
Engineering Units
Lower Value
EuL
-9999 to 9999
15
Hysteresis for
Control Outputs
HyCo
0 to 300
Width of Hysteresis Band
(See page 66 for definition)
29
30
DISPLAY AVAILABLE
CODES SETTINGS
FACTORY
SETTING
STEP
DESCRIPTION
16
Hysteresis for
Alarm Outputs
HyAo
0 to 300
Width of Hysteresis Band
(see page 66 for definition)
17
Remote Setpoint
If rSP is set to zero
then rSPu and rSPL
are not seen
rSP
0 to 2
0=Not Used
1=1 to 5 VDC
2=0 to 5 VDC
18
Remote Setpoint
Upper Value
rSPu
-9999 to 9999
1400
19
Remote Setpoint
Lower Value
rSPL
-9999 to 9999
20
SPuL
-9999 to 9999
1400
21
SPLL
-9999 to 9999
22
Automatic Transfer
AtFr
0 to 2
0
0 = No Automatic Transfer
1=Transfers when the process
value goes below the setpoint
2=Transfers when the process
value goes above the setpoint
23
Process Rounding
of Displayed Value
Prnd
0 to 100
0 = No rounding
24
dFF
1 to 20
1
1= no filtering
(number of values averaged)
25
PFF
26
Pout
0=Not selected
1=Selected
27
Process Output
Upper Value
Pou
-9999 to 9999
2000
28
Process Output
Lower Value
PoL
-9999 to 9999
29
Chart Range
Upper Value
Cru
-9999 to 9999
200
30
Chart Range
Lower Value
CrL
-9999 to 9999
31
Proportional
Output 1 Action
on Error Condition
(If out1= 0,1,2 then
P1EC will not be displayed)
P1EC
0 to 100%
32
Proportional
Output 2 Action
on Error Condition
(If out2 = 0,1,2,7 then
P2EC will not be displayed)
P2EC
0 to 100%
YOUR
SETTING
STEP
DESCRIPTION
33
Pen Action on
Error Condition
DISPLAY AVAILABLE
CODES SETTINGS
PAEC
FACTORY
SETTING
YOUR
SETTING
0 or 1
1
0 = Pen goes to 0 % of chart
1 = Pen goes to 100 % of chart
Pressing the SCROLL key with the PAEC parameter value displayed in the Pen 1 window will
advance the display of a single pen instrument to the unit parameters. Pressing the SCROLL
key with the PAEC parameter displayed in the Pen 1 window of a two pen instrument will
advance the display to be PEns in the Pen 2 window. The Pen 2 Program mode parameter
selections can be made now. Pressing the SCROLL key with the PAEC parameter value
displayed in the Pen 2 window will cause the display to advance to the unit parameters
displayed in the Pen 1 window.
UNIT PARAMETERS
34
Relay A Assignment
rLyA
0 to 8
0
1=Assigned to Alarm 1-Pen 1
2=Assigned to Alarm 2-Pen 1
3=Assigned to Alarm 1-Pen 2
4=Assigned to Alarm 2-Pen 2
5=Assigned to Output 1-Pen 1
6=Assigned to Output 2-Pen 1
7=Assigned to Output 1-Pen 2
8=Assigned to Output 2-Pen 2
35
Relay B Assignment
rLyb
36
Relay C Assignment
rLyC
37
Relay D Assignment
rLyd
38
Relay E Assignment
rLyE
39
Relay F Assignment
rLyF
40
Relay G Assignment
rLyg
41
Relay H Assignment
rLyH
42
Current Output A
Assignment
CurA
0 to 6
0
0=Not Assigned
1=Assigned to Process
Value Output-Pen 1
2=Assigned to Process
Value Output-Pen 2
3=Assigned to Output 1-Pen 1
4=Assigned to Output 2-Pen 1
5=Assigned to Output1-Pen 2
6=Assigned to Output 2-Pen 2
43
Current Output B
Assignment
Curb
44
Current Output C
Assignment
CurC
45
Current Output D
Assignment
Curd
46
Current Output A
Range
CoAr
0 to 1
0=0-20 mA
1=4-20 mA
31
DISPLAY AVAILABLE
CODES SETTINGS
FACTORY
SETTING
STEP
DESCRIPTION
47
Current Output B
Range
Cobr
48
Current Output C
Range
CoCr
49
Current Output D
Range
Codr
50
Crt
1.0
51
PAPu
52
Chart Operation
in Off Mode
Coo
0 to 1
0=Chart continues rotating
in the Off mode
1=Chart stops rotating while
in the Off mode
32
53
Communication
Configuration
CCon
0 to 4
3
0=Off
1=Monitor Mode (Read Only)
2=Normal Mode (Read and Write)
3=Total Access with Limit Checking
4=Total Access without Limit Checking
54
Communication Bit
Rate Selection
Will not be seen if
Con=0
CbS
1 to 6
1=300
2=600
3=1200
4=2400
5=4800
6=9600
55
Communications
Address-Pen 1
Will not be seen if
Con=0
CAd1
0 to 99
56
Communications
Address-Pen 2
(If provided)
Will not be seen if
Con=0
CAd2
0 to 99
YOUR
SETTING
tunE
A
SoP
rSEt
PAL1
ArSt
dAL1
rAtE
bAL1
Ct1
PAL2
Ct2
dAL2
SEnS
bAL2
FoP
Key
Pb1
Actual Display
ON
OFF
Pb2
Scroll Key
Down Arrow
33
The Tune mode is adjusted on-line. The instrument will react to changes as they are
made.
34
DISPLAY AVAILABLE
CODES SETTINGS
FACTORY
SETTING
STEP
DESCRIPTION
Process Alarm 1
PAL1
(The Alarm setting seen
will depend upon the Alarm
selected in the Program mode)
Deviation Alarm 1
dAL1
bAL1
1 to 3000 units
Process Alarm 2
PAL2
Deviation Alarm 2
dAL2
bAL2
1 to 3000 units
Proportional Band
Output 1 (Will only be seen
if out1=3,4,5,6,7)
Pb1
1 to 3000 units
100
Proportional Band
Output 2 (Will only be
seen if out2=3,4,5,6)
Pb2
1 to 3000 units
100
10
Manual Reset
(Will only be seen if
Pb1/Pb2 were shown)
rSEt
YOUR
SETTING
DISPLAY AVAILABLE
CODES SETTINGS
FACTORY
SETTING
STEP
DESCRIPTION
11
Automatic Reset
Integration
(Will be seen if Pb1 or
Pb2 was shown)
ArSt
0.0
12
Rate Derivative
(Wll be seen if
Pb1 or Pb2 was seen)
rAtE
0.0
13
Ct1
1 to 240 seconds
30
14
Ct2
1 to 240 seconds
30
15
Position Proportioning
Sensitivity (Will be seen
if out1=7 and/or out2=0,7)
SEnS
1.0
16
FoP
YOUR
SETTING
35
STEP
DESCRIPTION
1
2
3
4
5
6
Test Mode
Calibration Mode
Program Mode
Tune Mode
Manual (Stby) Mode
Setpoint Select mode
(Optional)
Setpoint Change
DISPLAY AVAILABLE
CODES SETTINGS
EtSt
ECAL
EPro
Etun
ESby
ESPS
on or oFF
on or oFF
on or oFF
on or oFF
on or oFF
on or oFF
ESPC on or oFF
Key
EtSt
ON
OFF
ECAL
ON
OFF
EPro
ON
OFF
Etun
ON
OFF
ESbY
ON
OFF
ESPS
ON
OFF
ESPC
ON
OFF
Actual Display
ON
OFF
Scroll Key
Down Arrow
36
FACTORY
SETTING
oFF
oFF
on
on
on
on
on
YOUR
SETTING
Operation 4.1
4.1.1 OFF MODE
In the Off mode, the instrument control and alarm function (s) are turned off. Process
Retransmission signal(s) remain active. The chart rotation can be selected in the Program
mode to stop or continue to rotate when the instrument is in the Off mode. The pen(s) will
remain active. The Off mode can be entered by pressing and releasing the SCROLL key until
the display reads oFF, then pressing the DOWN key. The display will read oFF and then
current process variable at two second intervals. Entering the Off mode of a dual pen
instrument will cause both pens to enter the Off mode. The second pen display will be blank
as the upper display reads oFF and displays the process value for the second pen at the
same time as the upper display.
37
Dual Pen Instruments: If the instrument is specified and provided with the Remote Setpoint
capability for either or both pens and the Remote Setpoint has been properly configured in the
Program mode for either or both pens, the Setpoint Select mode will be accessible, if enabled.
Press and release the SCROLL keys until SPS appears in the display, then press the DOWN
key. The upper display will light and the lower display will blank if pen 1 is selected for a
remote setpoint. If only pen 2 is selected as a remote setpoint, then the upper display will
blank and the lower display will light. If both pens are selected for remote setpoint, the lower
display is accessed by pressing the DOWN key while the upper display shows the setpoint
mode selected for that pen. The display(s) will show Loc if the local (keypad entered) setpoint
is being used or rSP if the remote setpoint is in use. Press the SCROLL key to select the
setpoint mode that will be used by the instrument. Press the UP key to exit the Setpoint Select
mode. If a problem develops with the remote setpoint signal for either pen, the upper display
will show rSEr, the remote setpoint error code.
Digital Communications: The setpoint can be adjusted from a supervisory computer system.
Dual pen instruments are capable of having independent setpoint adjustments for each pen.
SPS
KEY
Actual Display
ON
OFF
LOC
Scroll Key
rSP
Down Arrow
38
39
Output 1% value
Output 2% value
Actual Process Value
Each code and output value will be displayed only if the corresponding proportional output is
present. Each code or value will be displayed for 1 second. This sequence of displays will
continue until the SCROLL key is pressed, which will then return the display to the normal
mode. Displays will sequenced for both Pen 1 and 2 as applicable on dual pen instruments.
40
Stby
KEY
Actual Display
Po1
ON
OFF
Scroll Key
Po2
Numeric Display Use arrow keys
to change value
Up Arrow Key
Down Arrow
41
42
These values obtained for Ultimate Proportional Band (UPB) and Ultimate Time Period (UTP)
are used to calculate ideal P, PI, PD, PID tuning parameters using the following ZieglerNichols equations:
Proportional only control (P)
43
Period
C
B
A
Curve A : unstable
Curve B : stable
Curve C : continuously cycling, ultimate PB and period
44
Service 5.1
This section contains information regarding calibration and test procedures that can be
performed in the field as well as items concerning the normal maintenance of the instrument.
Changing Charts
5.2
CAUTION: The chart flange assembly pin is sharp to perforate the chart. Use caution
while installing the chart to avoid coming into contact with the pin.
1. Depress and hold the UP and DOWN keys for between 2 and 3 seconds. Immediately
after depressing the keys, the unit will do a Lamp Test with all LED segments and indicators
lighted on the upper (and lower) display.
2. After 2-3 seconds, the display will show Cchg, the pen(s) will move to and remain at a
point above the top graduation on the chart and the chart will stop rotating. All other functions
remain active (Control, Display, etc).
3. Open the instrument door, snap up the chart hold down lever on the chart flange assembly,
gently lift the pen(s) and remove old chart.
4. With the pen(s) held up, install new chart. Be sure to line up the chart time line so that the
current time is aligned with the time setting mark on the chart platen.
5. Snap down chart hold down lever and close the instrument door.
6. Depress and hold the UP and DOWN keys for between 2 and 3 seconds. Immediately
after depressing the keys, the unit will do a Lamp Test with all LED segments and indicators
lighted on the upper (and lower) display.
7. After 2-3 seconds, the display will show Cchg momentarily, then the pen(s) position and
chart rotation will be restored.
Changing Pens
5.3
Open the instrument door. Refer to Figure 5-1 for pen changing procedure. This procedure is
also provided on a label on the instrument chart platen. Be sure to replace the pen cartridge
with the same type (color) that was removed. Be careful not to bend the pen arm while
changing the pen.
FIGURE 5-1
Changing Pens
To install pen, slide pen into
holder (1) and push down (2)
as shown by arrows
1
45
Calibration 5.4
CAUTION: Do not attempt any calibrations without the proper test equipment that meets or
exceeds the specifications listed.
Press and release the SCROLL key until CAL appears on the display , then press the DOWN
key to enter the mode. The display will change to CAL1. Press the SCROLL key to advance
the display to the other calibration modes available. For two pen units, CAL5 will only need
to be required on TB4 to calibrate Pen 1 and Pen 2 inputs. Both TB 4 and TB 5 inputs must
be calibrated for thermocouple inputs. Table 5-1, page 47, provides a listing of field calibration routines. All instruments are calibrated prior to shipment from factory.
CAL
CAL1
CAL2
CAL3
CAL4
KEY
CAL5
Actual Display
ON
OFF
CAL6
Scroll Key
CAL7
Numeric Display Use arrow keys
to change value
Up Arrow Key
Down Arrow
46
CAL9
Prog
Description
Reinitialization of program and tuning values.
CAL 2
CAL 3
CAL 4
CAL 5
CAL 6
CAL 7
CAL 9
47
Error recovery:
See section 5.6 (page 55) for details. Ensure that the millivolt source is connected correctly
and functioning properly.
The calibration can be exited when hLd1 or the calibration reference number is displayed by
pressing the SCROLL key.
CAL2 QUICK CALIBRATION
This routine will allow the operator to execute a rough calibration on their unit via the keypad
with no other equipment or disturbance to established wiring. It is intended to provide a partial
recovery from a calibration corruption where the necessary equipment indicated may not be
available. It should be noted that this is not intended as a substitution to the main calibration
procedure described earlier and may considerable deter from the accuracy of the instrument.
With CAL2 displayed, press and hold the DOWN ARROW key, then press the SCROLL key.
Release both keys and the instrument will display hLd1. Press and hold the UP ARROW key,
then press the SCROLL key. The display will momentarily blank and then CAL1 will be
displayed. Release both keys and depress the UP ARROW key. CAL will be displayed.
48
49
50
tSt1
tSt4
tSt5
tSt6
tSt7
KEY
Actual Display
tSt8
ON
OFF
tSt9
Scroll Key
tStA
Down Arrow
51
Description
Microprocessor internal RAM test. Used to check the processor RAM to
make sure it is functioning correctly.
Test 2
External RAM test, used to test the RAM chip for proper function.
Test 3
EPROM checksum test, used to check that the EPROM program is correct.
Test 4
External RAM checksum test; instrument test and identifies how many
times Errors16 or 17 have occurred.
Test 5
Verifies that all keys are functional and all LEDs are working.
Test 6
Used to verify that all relays and solid state relay driver outputs are working
correctly.
Test 7
This procedure will allow operator to adjust the current output value to
check the output and to test the operation of the external device.
Test 8
Test 9
Test A
52
Display
SCrL
uAro
dAro
Autu
AutL
(All LEDs and segments lit)
(exit)
To exit, press the SCROLL and UP keys simultaneously, tSt5 will be displayed.
DISPLAY
rLYA
rLYb
rLYC
rLYd
rLYE
rLYF
rLYg
rLYH
oFF
RELAY ON
SPST
A
B
C
D
E
F
G
H
None
RELAY ON
SPDT
A
B
C
D
None
None
G
H
None
To exit, press the SCROLL key and tSt6 will be displayed. The existence of Relay and
Solid State Relay Driver output(s) is dependent upon the hardware configuration.
53
The current output reading should be 0.1 mADC at any output value. A 5 % of span
adjustment for the current output(s) is provided by using the potentiometer adjacent to the
current output on the Current Output board. See Appendix A-4 (page 65). To exit the test,
press the SCROLL key and tSt7 will be displayed. The existence of a mADC current
output is dependent upon the hardware configuration.
54
Another method, to test the communications hardware, would be to connect one or more
instruments in the Receive mode to an instrument in the Send mode. All of the instruments in
the Receive mode should have their displays alternating in sync with the instrument in the
Send mode. When the sending instrument displays rEC, the receiving instruments should
display rEC1. To terminate the test, press the SCROLL key for one second. Upon exit, tStA
will be displayed. The existence of the communications hardware is dependent on the
hardware configuration.
CONDITION
CORRECTION STEPS
55
56
Relay/SSR Driver
Malfunction
57
58
o - display overranged
(the broken 6
appears on the left
segment of the display)
Er 2 - External RAM
Failure
Er 3 - EPROM Checksum
Failure
Er 5 - No Zero Crossings
Detected
Er 6 - AC line below 43 HZ
Er 7 - AC line over 64 HZ
59
60
Er 9 - ADC Reference
Number Error
Er17 - Calibration
Checksum Error
61
Appendix A
Board Layouts
FIGURE A-1 - PROCESSOR BOARD
Top
SWI for Rev. Y and above
UNLOCKED
230
JU1
ENABLE MODE
TB1
LOCKED
230
JU3
EPROM SIZE
32K
230/115 VAC
SWITCH 230 VAC
MODEL ONLY
64K
U5
JU3
U7
JU1
JU5 PEN 2 INPUT
(REVERSE OF JU4)
T/C,mV, RTD
Battery
VOLT/mA
JU6
JU4
JU5
TB2
JU6 /JU7
RTD
INPUT
TB3
NONRTD
62
RTD
TB4
TB5
JU7
TB6
TS1 R1
TB7
TS2
R2
TS3
R3
TB8
TS4
R4
TS5 R5
TS6 R6
C1
C2
C3
C4
C5
C6
K1
K2
K3
K4
K5
K6
(rlyA)
(rlyB)
(rlyC)
(rlyD)
(rlyE)
(rlyF)
P7
TB9
(rlyG)
Resistor
R1
R2
R3
R4
R5
R6
(rlyH)
Relay
Relay A
Relay B
Relay C
Relay D
Relay E
Relay F
63
TB6
TS1 R1
TB7
TS2
C1
R2
C2
TS3
R3
TB8
TS4
C3
R4
C4
K1
K2
(rlyA)
(rlyB)
TS5
R5
TS6
R6
C5
C6
K3
K4
(rlyC)
(rlyD)
P7
TB9
(rlyG)
64
Resistor
R1, R2
R3, R4
R5
R6
Relay
Relay A
Relay B
Relay C
Relay D
(rlyH)
R50
R51
R52
R53
U2
U4
U6
U8
U3
U5
U7
U9
U1
TB10
TB11
TB12
TB13
If this option board was ordered, you will find it located in the lower right hand corner of the
instrument.
65
Appendix B
Glossary
Automatic Reset (Integral)
This parameter is used so that the instrument will compensate for process variable deviations
from setpoint that occur when the process load characteristics change. Instructions for
determining the automatic reset settings are given in Table 3-2 (Page 34). Factory default
is.0.0. Display code ArSt.
Automatic Transfer
This feature, if configured, allows manual control of the process until setpoint is reached, at
which point the controller automatically transfers from manual to automatic control. Factory
default value is 0 = no auto transfer. Display code AtFr.
Bumpless Transfer
This feature prevents step changes in proportional outputs when changing from automatic to
manual control only.
Cycle Time
This Tune mode parameter is used to select the on/off cycle time for time proportioning
outputs (Ct1 for Output 1 and/or Ct2 for Output 2).
When usng the Position Proportioning option, Ct1 must be selected for the stroke time of the
motor.
Display Filter Factor
This parameter is adjustable from 1 to 20 which represents the number of scans per second
of the process variable that are averaged together before updating the displayed and recorded value. The factory default value is 1 = no filtering. Display code dFF.
Engineering Units Upper and Engineering Units Lower
These Program mode parameters are used with volt, millivolt, and milliamp inputs. The
Engineering Units Upper Euu should be selected as the value to be displayed when the input
is at maximum. The Engineering Units Lower EuL should be selected as the value to be
displayed when the input is at minimum.
First Output Position
This parameter is adjustable from -1000 to 1000 units and represents a shift or offset of the
on-off actuation points or proportional band for the first output relative to the normal position.
For example, a negative value could be used to offset an expected overshoot. First Output
Position also shifts the proportional band with respect to the process value range outside of
which integral action is inhibited. Factory default is 0. Display code FoP.
Hysteresis
This parameter is adjustable from 0 to 300 units representing the width of the band (half
above and half below setpoint). Used with ON/OFF or Alarm outputs to reduce cycling. For
instance, with a value of 4 and a setpoint of 70 the output will turn ON when the process
variable drops to 68 and stay ON until 72 is reached, then turn OFF the output. Factory
default = 3. Display code HyAo for Alarm outputs. Display code HyCo for ON/OFF Control
outputs.
Input Correction
This parameter is adjustable from -300 to 300 units and is used as a method to compensate
for a linear sensor error. Factory default is 0 = no correction. Display code iCi1, iCi2.
66
Manual Reset
This parameter is adjustable from -1500 to 1500 units representing a manual shift of proportional band(s) relative to the normal position which is an even strattle of the setpoint. Manual
reset is intended to be used when automatic reset is not used to allow compensation for
deviations from setpoint which remain after the process has stabilized. Factory default is 0.
Increasing the value increases the process variable, i.e. if the process variable stabilizes too
low, increase the manual set. Integral action, and conversely reset-windup inhibit apply over
the same process value range regardless of the manual reset value. Display code rSEt.
67
Option Suffix
2 Recording Controller
00 None
N3 - NEMA3
Pen 2
0 None
1 Recorder Only
2 Recorder Controller
Voltage
CSA Approved
4 115VAC Input
5 115/230VAC Input
0
1
2
4
6
7
8
9
None
One
Two
Four
Six
One SPDT
Two SPDT
Two SPDT and Two SPST
None
One
Two
Four
Six
Eight
4 to 20mA Outputs
0
1
2
3
4
None
One
Two
Three
Four
1 115VAC Input
2 115/230VAC Input
Enclosure Options
2 Standard Cover
(Plastic Windows)
4 Door Lock**
6 Sealed Conduit Conn.
7 Combination of 4& 6**
Communications
0 None
2 RS-485 Total Access
*Total quantity of SPST Relays and SSR Drivers must be less than or equal to (8) eight.
**This option comes with a structural foam cover.
N3 - NEMA3 Equivalent Spray Resistant Enclosure
68
Scan Rate
1 scan/second
Noise Rejection
Line Voltage
Power Consumption
25VA maximum
Operating Temperature
Storage Temperature
Humidity
Dimensions
Weight
20 pounds maximum
Agency Approvals
Warranty
69
Input Specifications
THERMOCOUPLE
TYPE
RANGE
TYPE
RANGE
0 to 760C
0 to 1400F
0 to 750C
0 to 1400F
0 to 1360C
0 to 2500F
200 to 1800C
400 to 3300F
-220 to 400C
-330 to 750F
0 to 1300C
0 to 2370F
200 to 1650C
400 to 3000F
200 to 2300C
390 to 4170F
200 to 1650C
400 to 3000F
MILLIAMPS
MILLIVOLTS
RTD
4-20 mADC
(with resistor)
0 TO 25 mV
0 to 50 mV
10 to 50 mV
100 OHM
(.00385 OHMS/OHM/C)
-140 to 400C
VOLTS
REMOTE SETPOINT
0 to 5 VDC
1 to 5 VDC
0 to 5 VDC
1 to 5 VDC
CONTROL ADJUSTMENTS
70
Proportional Band
1 to 3000 units
Manual Reset
Rate (Derivative)
Cycle Time
1 to 240 seconds
Position Proportioning
Sensitivity
0.0 to 50.0%
On/Off Hysteresis
(width of hysteresis band)
0 to 300 units
Automatic
Transfer Function
Auto/Manual
Manual Output
0 to 100%
ALARM ADJUSTMENTS
Process Alarm
Deviation Alarm
Deviation Band Alarm
Hysteresis
CONTROL OUTPUTS
Relay
SPST
SSR Driver
mADC Current
DISPLAY
Digital Display
Status Indicators
Two possible; one per installed pen. Red LEDs 0.56" high.
LED indicators for Output 1, Output 2, Manual Operation, Alarm,
Setpoint, minus sign and process value units (C, F, or E).
RECORD
Chart
Chart Range
Chart Drive
Chart Rotation
Pen Type
Pen Color
Pen Response Time
Accuracy
Chart Rotation Accuracy
DIGITAL COMMUNICATIONS
Type
Character Format
Protocol
Configuration
Bit Rate
Address
71
Appendix E
Software Reference/Record Sheet
Pen 1
inPS
iCor
out1
o1uL
o1LL
out2
o2uL
o2LL
AL1
AL2
diSP
dPoS
Euu
EuL
HyCo
HyAo
rSP
rSPu
rSPL
SPuL
SPLL
AtFr
Prnd
dFF
PFF
Pout
Pou
PoL
Cru
CrL
P1EC
P2EC
PAEC
72
PROGRAM MODE
Pen 2
rLyA
rLyb
rLyC
rLyd
rLyE
rLyF
rLyg
rLyh
CurA
Curb
CurC
Curd
CoAr
Cobr
CoCr
Codr
Crt
PAPu
Coo
CCon
CbS
CAd1
CAd2
unit
TUNE MODE
Pen 1
Pen 2
SoP
PAL1
dAL1
bAL1
PAL2
dAL2
bAL2
Pb1
Pb2
rSEt
ArSt
rAtE
Ct1
Ct2
SEnS
FoP
ENABLE MODE
EtSt
ECAL
EPro
Etun
ESby
ESPS
ESPC
Warranty
These products are warranted to be free from functional defects in materials and workmanship at the time the products leave The Partlow-West Company factory and to conform at that
time to the specifications set forth in the relevant Partlow-West instruction manual or manuals,
sheet or sheets, for such products for a period of three years.
THERE ARE NO EXPRESSED OR IMPLIED WARRANTIES WHICH EXTEND BEYOND
THE WARRANTIES HEREIN AND ABOVE SET FORTH. THE PARTLOW-WEST COMPANY MAKES NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE PRODUCTS.
Limitations
The Partlow-West Company shall not be liable for any incidental damages, consequential
damages, special damages, or any other damages, costs or expenses excepting only the cost
or expense of repair or replacement as described above.
Products must be installed and maintained in accordance with The Partlow-West Company
instructions. Users are responsible for the suitability of the products to their application.
There is no warranty against damage resulting from corrosion, misapplication, improper
specifications or other operating condition beyond our control. Claims against carriers for
damage in transit must be filed by the buyer.
This warranty is void if the purchaser uses non-factory approved replacement parts and
supplies or if the purchaser attempts to repair the product themselves or through a third party
without factory authorization.
Returns
Partlow-West's sole and exclusive obligation and buyers sole and exclusive remedy under the
above warranty is limited to repairing or replacing (at Partlow-West's option), free of charge,
the products which are reported in writing to The Partlow-West Company at its main office
indicated below.
The Partlow-West Company is to be advised of return requests during normal business hours
and such returns are to include a statement of the observed deficiency. The buyer shall prepay shipping charges for products returned and The Partlow-West Company or its representative shall pay for the return of the products to the buyer.
Approved returns should be sent to:
73
74