Partlow MRC 7000 Installation, Wiring, Operational Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 74

Form 2877 Price $32.

00
Edition 7 Dec. 1996
Revised February, 1998

ONE AND TWO PEN CIRCLE CHART RECORDING CONTROLLER

MRC 7000
Installation, Wiring, Operation Manual

Brand

nformation in this installation, wiring, and operation


manual is subject to change without notice. One
manual is provided with each instrument at the time of
shipment. Extra copies are available at the price published
on the front cover.
Copyright December 1996, all rights reserved. No part of
this publication may be reproduced, transmitted, transcribed or stored in a retrieval system, or translated into any
language in any form by any means without the written
permission of The Partlow-West Company.
This is the Seventh Edition of the MRC 7000 Recording
Controller Manual. It was written and produced entirely on
a desk-top-publishing system. Disk versions are available
by written request to The Partlow-West Advertising and
Publications Department.
We are glad you decided to open this manual. It is written
so that you can take full advantage of the features of your
new MRC 7000 microbased chart recording controller.

NOTE
2

It is strongly recommended that factory equipped applications


incorporate a high or low limit protective device which will shut
down the equipment at a preset process condition in order to
preclude possible damage to property or products.

TABLE OF CONTENTS
SECTION 1 - GENERAL
1.1 Product Description

PAGE NUMBER
5

SECTION 2 - INSTALLATION & WIRING


2.1
2.2
2.3
2.4
2.5
2.6

Installation & Wiring


Unpacking
Location
Mounting
Preparation for Wiring
Wiring Connections

8
8
8
8
9
14

SECTION 3 - CONFIGURATION
3.1
3.2
3.3
3.4
3.5

Configuration (Set Up)


Configuration/Jumper Positioning
Operation Summary
Start Up Procedures
Front Panel Operation

20
21
21
21
22

SECTION 4 - OPERATION
4.1 Off Control Mode
4.2 Alarm Operation
4.3 Tune Mode Operation

37
41
42

SECTION 5 - SERVICE
5.1 Service
5.2 Changing Charts
5.3 Changing Pens
5.4 Calibration
5.5 Test Mode Procedures
5.6 Troubleshooting and Diagnostics (Error Code Definitions)

45
45
45
46
51
55

APPENDICES
A - Board Layouts and Jumper Positioning
A-1 - Processor Board
A-2 SPST Relay/SSR Driver Output Board
A-3 SPDT Relay/SSR Driver Output Baord
A-4 Current Output Board
B - Glossary

62
63
64
65
66

C- Order Matrix
D- Product Specifications

68
69

E- Software Record/Reference Sheet


Warranty

72
Inside back page

FIGURES & TABLES


Figure 1-1
Figure 1-2
Figure 2-1
Figure 2-2
Figure 2-3
Figure 2-4
Figure 2-5
Figure 2-6
Figure 2-7
Figure 2-8
Figure 2-9
Figure 2-10
Figure 2-11A
Figure 2-11B
Figure 2-12
Figure 2-13
Figure 2-14
Figure 2-15
Figure 3-1
Figure 5-1
Table 3-1
Table 3-2
Table 3-3
Table 5-1
Table 5-2

Recorder Description
Recorder Display
Installation Panel Dimensions Conduit Opening Locations
Noise Suppression
Noise Suppression
Board and Terminal Locations
AC Power Input
Thermocouple Inputs
RTD Inputs
Milliamp, Volt and Millivolt Inputs
Remote Setpoint Input VDC, mADC
Digital Communications
SPST Relay Output
SPDT Relay Output
SSR Output
Current Output
24 VDC Power Supply Option
Position Proportioning Control Output
Keypad Features
Changing Pens
Program Mode Configuration Procedure
Tune Mode Configuration Procedure
Enable Mode Configuration Procedure
Calibration Procedure
Test Procedures and Description

5
7
9
11
11
14
15
15
15
16
16
17
17
18
18
18
19
19
24
45
28
34
36
47
52

FLOW CHARTS
Flow - Calibration
Flow - Enable Mode
Flow - Program Mode
Flow - Setpoint Select
Flow - Standby
Flow - Test
Flow - Tune Mode

46
36
25
38
41
50
33

Product Description 1.1


1.1.1 GENERAL
The instrument is a microprocessor based circular chart Recorder Controller capable of
measuring, displaying, recording and controlling from a variety of inputs. Applications include
temperature, level, pressure, flow and others. The instruments can be specified as either a
single or as a dual pen model.
Recording, control functions, alarm settings and other parameters are easily entered via the
keypad. All user's data can be protected from unauthorized changes by the Enable mode
security system, and is protected against memory loss, as a result of AC power outage, by
battery back-up.
The process sensor input for each terminal block is user configurable to directly connect to
either thermocouple, RTD, mVDC, VDC, or mADC inputs. Changes in input type can easily be
made by the user. Thermocouple and RTD linearization, as well as thermocouple cold
junction compensation, are performed automatically. The instrument process variable inputs
are isolated. An isolated 24 VDC regulated transmitter power supply can be provided in the
instrument for use with up to two 4 to 20 mADC process sensor transducers.
The instrument can be ordered to operate on either 115 VAC or 230 VAC power at 50/60 Hz.
The 230 VAC option includes a switch for selecting either 230 VAC or 115 VAC operation.
The instrument is housed in a structural foam enclosure suitable for panel or surface
mounting.

FIGURE 1-1
Pen 1 Display

Pen 1 Auto/Man Key


Scroll Key
Up Key
Down Key
Pen 2 Auto/Man Key

Pen 2 Display

The number of keys and LED's will depend upon the configuration of individual unit.

1.1.2 RECORDING
The instrument records the selected process variable on a 10-inch circular chart. One box of
standard charts is provided with each recorder. Charts are available in a wide selection of
ranges. Chart rotation speed is programmable from 0.1 to 999.9 hours per revolution in 0.1
hour increments. The instrument can be ordered with one or two pens. Pen 1 is red and Pen 2
is green. Pens are the disposable fiber-tip type.

1.1.3 DISPLAYS
Each instrument is provided with a digital display and status indicator for each pen provided
(See Figure 1-1, page 5). The display may be configured to display the Process Value,
Process Value and Setpoint, Deviation from Setpoint only, Deviation and Setpoint, or Setpoint
only. During configuration the display(s) is/are used to show the enabled modes of operation
and the parameter codes.
The display in the upper right corner is for Pen 1, the display in the lower right corner is for
Pen 2 (if provided). The display includes status indicators for Manual mode operation, Output
1, Output 2 , Alarm, degrees C, degrees F, engineering units, setpoint and minus sign. See
Figure 1-2 ( page 7).
Display resolution is programmable for 0.1 or 1 degree for thermocouple and RTD inputs, and
none, one, two or three decimal places for other input types.

1.1.4 CONTROL
The instrument can be provided with relay, solid state relay driver and milliamp DC outputs.
Instruments can be programmed for on-off, time proportioning, current proportioning or
position proportioning control depending upon the hardware present. Switching between the
Control mode and the Manual mode of operation is easily accomplished with a dedicated key
on the keypad. Switching is bumpless from the Control to the Manual mode, and while in
manual, manipulation of proportional outputs is possible. Each pen of a dual pen recording
controller is provided with its own AUTO/MANUAL key . Other standard control features
include proportional control output limits, setpoint limits, anti-reset windup and a unique
Automatic Transfer function. If configured, the Automatic Transfer function allows manual
control of the proportional output until the process reaches the setpoint at which time the
instrument will go into the Control (automatic) mode of operation.

1.1.5 ALARM
An Alarm indicator is standard for each pen. Two alarm functions are provided for each pen
and the alarm indicator will light if either alarm for that pen is on. Alarm settings are programmable. Alarm type may be selected as process direct or reverse (high or low), deviation from
setpoint direct or reverse, and deviation band open or closed within the band. Alarm outputs
can be provided by assigning any relay(s) Single Pole/Single Throw (SPST)or Solid State
Relay (SSR) driver to the respective alarm.

1.1.6 PROCESS VALUE RE-TRANSMISSION OUTPUT


If an instrument is specified with mADC current output(s), any of the outputs may be programmed to operate as a process value re-transmission output. The output is scaleable but
can not be used as a control output while assigned as a process value re-transmission output.

1.1.7 DIGITAL COMMUNICATIONS


The instrument can be ordered with a Digital Communications option that provides the
capability of bi-directional communications with a supervisory computer. A dual pen
instrument can have an individual address selected for each pen. Refer to the Communications Protocol Manual (Form 2878) for more details regarding the communications option.
This manual is included with the unit when the communications option is specified.

FIGURE 1-2

Manual Output 1 Output 2 Alarm

MAN

OUT1 OUT2 ALRM

SP

Setpoint

C
F
U

Minus Sign

Digital Display

Installation and Wiring 2.1


Read these instructions carefully before proceeding with installation and operation. Electrical
code requirements and safety standards should be observed. Installation should be performed
by qualified personnel.

CAUTION: The Instrument AC power input is specified in the model number and on the
wiring label affixed to the the top center of the platen. Verify the AC power input required
by the instrument prior to proceeding with installation.

Unpacking 2.2
Remove the instrument from the carton and inspect for any damage due to shipment. If any
damage is noticed due to transit, report and file a claim with the carrier. Write the model
number and serial number of the instrument on the inside of the front cover of this Operation
Manual for future reference.

Location 2.3
Locate the instrument away from excessive moisture, oil, dust, and vibration. Do not subject
the instrument to operating temperatures outside of the 32F to 131F (0C to 55C) range.

Mounting 2.4
Figure 2-1 (page 9) shows an installation view and physical dimensions for a panel mounted
instrument. The panel where the instrument will be mounted must provide rigid support for
the approximately 20 pound instrument. Adjacent instruments may be mounted within a
minimum of 2 inches horizontally and 3 inches vertically, providing that proper panel support
is supplied.
PANEL MOUNTING HARDWARE REQUIRED: (not provided with instrument)
(4) 1/4"-20 x 2" flat head bolts w/nuts
(4) appropriate lock washers
PANEL MOUNTING:
1) Cut panel opening to the dimensions illustrated in Figure 2-1 (page 9).
2) Insert the instrument in the panel opening. Firmly fasten the instrument to the panel using
the nuts, bolts and lock washers.
SURFACE MOUNTING:
1) Install the mounting brackets,ordered separately,, on the vertical sides of
instrument housing. Use the brackets to fasten the instrument to the surface.

FIGURE 2-1
7/8" Dia hole for
wiring - 3 locations,
EC1, EC2, and EC3

EC3

EC1

13 3
16
(335 mm)

EC2
15 1 (384.2 mm)
8

21
2

4
PLACES

3 43

(64 mm)

11
16
(119.1 mm)
4

WIDTH OF COVER

2 19 (65.9 mm)
32
Mounting Bracket (2)

9
32 DIA.(7.1mm)

Holes to mount
bracket to surface

5
12 8

71
2
(320.7 mm)
(190.5 mm)

Screw that mounts to case

1
13 2 (342.5 mm)
15
(
354 mm)
13
16

7
32 (5.5 mm)

Note: Surface Mount


Dimensions
Top edge of case

Panel cut-out for flush mounting


7 3/4"
196.9mm
2.5"
63.5mm

14 11/16"
373mm

Holes should be sized to accommodate screw type


needed to fasten instrument. This is up to the installer.

Preparations for Wiring 2.5


2.5.1 WIRING GUIDELINES
Electrical noise is a phenomenon typical of industrial environments. The following are guidelines that must be followed to minimize the effect of noise upon any instrumentation.

2.5.1.1 INSTALLATION CONSIDERATIONS


Listed below are some of the common sources of electrical noise in the industrial environment:
Ignition Transformers
Arc Welders
Mechanical contact relay(s)
Solenoids
Before using any instrument near the devices listed, the instructions below should be
followed:
1. If the instrument is to be mounted in the same panel as any of the listed devices,
separate them by the largest distance possible. For maximum electrical noise
reduction, the noise generating devices should be mounted in a separate
enclosure.
2. If possible, eliminate mechanical contact relay(s) and replace with solid state
relays. If a mechanical relay being powered by an instrument output device
cannot be replaced, a solid state relay can be interposed to isolate the instrument.
(Continued on next page)

3. A separate isolation transformer to feed only instrumentation should be


considered. The transformer can isolate the instrument from noise found on the
AC power input.
4. If the instrument is being installed on existing equipment, the wiring in the area
should be checked to insure that good wiring practices have been followed.

2.5.1.2 AC POWER WIRING


Earth Ground
The instrument includes noise suppression components that require an earth ground
connection to function. To verify that a good earth ground is being attached, make a resistance check from the instrument chassis to the nearest metal water pipe or proven earth
ground. This reading should not exceed 100 ohms. Each instrument should have a dedicated
earth ground. Do not chain link multiple instrument ground wires.
Neutral (For 115VAC)
It is good practice to assure that the AC neutral is at or near ground potential. To verify this, a
voltmeter check between neutral and ground should be done. On the AC range, the reading
should not be more than 50 millivolts. If it is greater than this amount, the secondary of this
AC transformer supplying the instrument should be checked by an electrician. A proper
neutral will help ensure maximum performance from the instrument.

2.5.1.3 WIRE ISOLATION/SEGRATION


The instrument is designed to promote proper separation of the wiring groups that connect to
the instrument. The AC power wire terminals are located near the top of the instrument
boards. The analog signal terminals are located near the bottom of the instrument boards.
Maintain this separation of the wires to insure the best protection from electrical noise. If the
wires need to be run parallel with any other wiring type(s), maintain a minimum 6 inch space
between the wires. If wires must cross each other, do so at 90 degrees to minimize the
contact with each other and amount of cross talk. Cross talk is due to the EMF (Electro
Magnetic Flux) emitted by a wire as current passes through it.

2.5.1.4 USE OF SHIELDED CABLE


Shielded cable helps eliminate electrical noise being induced on the wires. All analog signals
should be run with shielded cable. Connection lead length should be kept as short as possible, keeping the wires protected by the shielding. The shield should be grounded at one end
only. The preferred grounding location is at the sensor, transmitter or transducer.

2.5.1.5 NOISE SUPPRESSION AT THE SOURCE


Usually when good wiring practices are followed, no further noise protection is necessary.
Sometimes in severe environments, the amount of noise is so great that it has to be suppressed at the source. Many manufacturers of relays, contactors, etc. supply "surge suppressors" which mount on the noise source.
For those devices that do not have surge suppressors supplied, RC (resistance-capacitance)
networks and/or MOV (metal oxide varistors) may be added.
Inductive Coils - MOV's are recommended for transient suppression in inductive soils connected in parallel and as close as possible to the coil. See Figure 2-2. Additional protection
may be provided by adding an RC network across the MOV.
Contacts - Arcing may occur across contacts when the contact opens and closes. This results
in electrical noise as well as damage to the contacts. Connecting a RC network properly
sized can eliminate this arc.
For circuits up to 3 amps, a combination of a 47 ohm resistor and 0.1 microfarad capacitor
(1000 volts) is recommended. For circuits from 3 to 5 amps, connect 2 of these in parallel.
See Figure 2-3.

10

FIGURE 2-2

0.5
mfd
1000V

Coil

220
ohms

115V 1/4W
230V 1W

FIGURE 2-3
MOV

C
Inductive
Load

11

2.5.2 SENSOR PLACEMENT (THERMOCOUPLE OR RTD)


If the temperature probe is to be subjected to corrosive or abrasive conditions, it should be
protected by the appropriate thermowell. The probe should be positioned to reflect true
process temperature:
In liquid media - the mose agitated area.
In air - the best circulated area.

THERMOCOUPLE LEAD RESISTANCE


Thermocouple lead length can affect instrument accuracy, since the size (gauge) and the
length of the wire affect lead resistance.
To determine the temperature error resulting from the lead length resistance, use the following
equation:
Terr = TLe * L

where;

TLe = value from appropriate Table


L = length of leadwire in thousands of feet.

TABLE 1
Temperature error in C per 1000 feet of Leadwire
AWG Thermocouple Type
No.
J
K
T
R
S
10
.68
1.71
.76
2.05
2.12
12
1.08
2.68
1.21
3.30
3.29
14
1.74
4.29
1.95
5.34
5.29
16
2.74
6.76
3.08
8.30
8.35
18
4.44
11.00
5.00
13.52
13.65
20
7.14
17.24
7.84
21.59
21.76
24
17.56
43.82
19.82
54.32
54.59

E
1.15
1.82
2.92
4.60
7.47
11.78
29.67

B
14.00
22.00
35.00
55.50
88.50
141.00
356.50

N
2.94
4.68
7.44
11.82
18.80
29.88
75.59

C
2.53
4.07
6.37
10.11
16.26
25.82
65.27

E
2.07
3.27
5.25
8.28
13.44
21.21
53.40

B
25.20
39.60
63.00
99.90
159.30
253.80
641.70

N
5.30
8.42
13.38
21.28
33.85
53.79
136.07

C
4.55
7.32
11.47
18.20
29.27
46.48
117.49

TABLE 2
Temperature error in F per 1000 feet of Leadwire
AWG Thermocouple Type
No.
J
K
T
R
S
10
1.22
3.07
1.37
3.68
3.81
12
1.94
4.82
2.18
5.93
5.93
14
3.13
7.73
3.51
9.61
9.53
16
4.93
12.18
5.54
14.93
15.04
18
7.99
19.80
9.00
24.34
24.56
20
12.85
31.02
14.12
38.86
39.18
24
31.61
78.88
35.67
97.77
98.26

Example
A recorder is to be located in a control rrom 660 feet away from the process. Using 16 AWG,
Type J thermocouple, how much error is induced?
Terr = TLe * L = 4.93 (F/1000 ft) from Table 2.
Terr = 4.93 (F/1000 ft)
Terr = 3.3 F

12

RTD LEAD RESISTANCE


RTD lead length can affect instrument accuracy. Size (gauge) and length of the wire used
affects lead length resistance.
To determine the temperature error resulting from the lead length resistance, use the following
equation:
Terr = TLe * L

where;

TABLE 3

3 Wire RTD

AWG No.
10
12
14
16
18
20
24

TABLE 4
AWG No.
10
12
14
16
18
20
24

TLe = value from Table 3 if 3 wire or Table 4 is 2 wire.


L = length of leadwire in thousands of feet.

Error C
+/-0.04
+/-0.07
+/-0.10
+/-0.16
+/-0.26
+/-0.41
+/-0.65

Error F
+/-0.07
+/-0.11
+/-0.18
+/-0.29
+/-0.46
+/-0.73
+/-1.17

2 Wire RTD
Error C
+/-5.32
+/-9.31
+/-13.3
+/-21.3
+/-34.6
+/-54.5
+/-86.5

Error F
+/-9.31
+/-14.6
+/-23.9
+/-38.6
+/-61.2
+/-97.1
+/-155.6

Example
An application uses 2000 feet of 18 AWG copper lead wire for a 3-wire RTD sensor. What is
the worst-case error due to this leadwire length?
Terr = TLe * L
TLE = +/- .46 (F/1000 ft) from Table 1
Terr = +/- .46 (F/1000 ft) * 2000 ft
Terr = +/- 0.92 F

13

Wiring Connections 2.6


All wiring connections are typically made to the instrument at the time of installation. Connections are made at the terminal boards provided, two 12 gauge wires maximum. Terminal
boards are designated TB1 through TB13. See Figure 2-4 for the terminal board locations.
The number of terminal boards present on the instrument depend upon the model number/
hardware configuration.

FIGURE 2-4
1 2

1 2 3 4

1 2 3 4

1 2 3 4

TB1

TB6

TB7

TB8

RELAY/SSR Driver
Board
TB9

Processor Board

1 2 3 4

Current Output Board


TB 2
1 2
TB3

TB4

12

1 2 3 4 5

TB5
1 2 3 4 5

TB10

TB11

TB12

TB13

1 2

1 2

1 2

1 2

2.6.1 ELECTRICAL CONDUIT OPENINGS


The instrument case will have 3 or 4 conduit openings, depending upon the number of outputs
specified. To help minimize electrical noise that may adversely affect the operation of the
instrument the wires indicated below should be routed through the conduit opening specified.
See Figure 2-1 (page 9) for conduit opening locations.
EC1EC2EC3EC4-

AC Power Input
Analog input and mADC outputs
SPST relay or SSR driver outputs
SPST relay or SSR driver outputs (provided when > 4 relays & SSR drivers total are
specified)

Unused conduit openings should be sealed.

2.6.2 AC POWER WIRING CONNECTIONS


WARNING: Avoid electrical shock. AC power wiring must not be connected at the source
distribution panel until all wiring connections are completed.

14

FIGURE 2-5
AC Instrument Power Input
Connect the 115 VAC hot and neutral to terminals 1 and 2 respectively of TB1. See Figure 2-4
(page 14) for Terminal Board locations on the instrument. Connect the 230 VAC one leg to
each terminal, be sure to check the position of the Voltage Selector switch provided with 230
VAC instruments. The switch position must match the voltage input to the instrument.

TB1
Connect the AC
Line
1
Line 2
ground at the
green ground screw
on the left side of
1
2
the inside of the
case

FIGURE 2-6
Thermocouple Inputs
Use TB4 for the Pen 1 input, and TB5 for the Pen 2 input. Connect the positive leg of the
thermocouple to terminal 1, and the negative to terminal 2. Be sure that the input conditioning
jumpers are properly positioned for a thermocouple input. See Appendix A-1 (page 62).

TB4 or TB5
2 3 4

Grounded or
Ungrounded
Thermocouples
may be used

FIGURE 2-7
RTD Inputs
Use TB4 for the Pen 1, and TB5 for the Pen 2 input. Connections are shown for 3 wire and 2
wire RTD inputs. If a three wire device is used, install the common legs to terminals 2 and 3. If
a two wire device is used, install a jumper between terminals 2 and 3. Be sure that the input
conditioning jumpers are properly positioned for an RTD input. See Appendix A-1 (page 62).

+
1

TB4 or TB5
2 3 4

+
1

TB4 or TB5
2 3 4

Jumper
SUPPLIED BY
CUSTOMER

3 Wire RTD

2 Wire RTD

15

FIGURE 2-8
Volt, Millivolt and milliamp Input
Make the volt, millivolt and milliamp connections as shown below. Use TB4 for thePen 1 input,
and TB5 for the Pen 2 input. Terminal 1 is positive and terminal 2 is negative. The milliamp
input requires the installation of an appropriate shunt resistor (ordered separately) between
terminals 1 and 2. Be sure that input conditioning jumpers are in the correct positions for the
input being connected. See Appendix A-1 (page 62).
NOTE: Fault Detection is not functional for 0-5V or 0-20mA inputs.

TB4 or TB5
+ 1 2 3 4 5
SHIELDED
TWISTED
PAIR
MAY BE
+ GROUNDED
SOURCE OR
UNGROUNDED

FIGURE 2-9
Remote Setpoint Input VDC , mADC
If Remote Setpoint option has been specified, make connections as shown. The remote
setpoint input may be selected as either 0 to 5 VDC or 1 to 5 VDC input in the Program mode
section. Make sure the configuration properly matches the input used. Use TB4 for Pen 1, and
TB5 for Pen 2 if Pen 2 is provided and specified with the Remote Setpoint option. Connect
the positive lead to terminal 4, and the negative lead to terminal 3 (Terminal 3 is the ground,
terminal 4 is the input, terminal 5 is 5 VDC.) If a 4 to 20 mADC remote setpoint is to be used,
the instrument remote setpoint input should be configured for 1 to 5VDC in the Program
mode, and a 250 ohm resistor should be installed across terminals 4 and 3. A 250 ohm
resistor is provided with the instrument, one per pen. The resistor(s) are shipped in the plastic
bag that is clipped to the inside of the instrument cover. This is the same bag that contains
the spare pen cartridge(s).

TB4 or TB5
+ 1 2 3 4 5

TB4 or TB5
+ 1 2 3 4 5

SHIELDED
TWISTED
PAIR

SHIELDED
MULTI-CONDUCTOR
CABLE

- +
SOURCE

16

150 OHM
TO 10K OHM
POTENTIOMETER

FIGURE 2-10
Digital Communications Options
Connections are made as shown using TB2. Refer to the Protocol Manual, Form #2878 for
more details regarding the connections and how to use this option. This document is provided
only when this option has been specified. If the communications network continues on to other
instruments, connect the cable shields together, but not to the instrument. A terminating
resistor should be installed at the terminals of the last unit in the communications loop. If the
communications network ends at the instrument, the shield is not connected.

TB2
Serial A

1 2

Serial B

TOWARD THE
COMPUTER

NETWORK
CONTINUATION
(IF APPLICABLE)

2.6.4 OUTPUT CONNECTIONS


Relay output(s), if provided in the instrument, may be assigned to control or alarm output
functions for Pen 1 and/or Pen 2 (if present). Current outputs may be assigned to control and
process value retransmission output for Pen 1 and/or Pen 2 (if present). The assignment of
the output function (s) are/is accomplished in the Program mode. SPST relay and/or SSR
driver output(s) is/are designated as Relay A through Relay H. SPST relays begin with Relay
A designation, then B, C, etc. SSR drivers begin with Relay H designation then G, F, etc.
except when 4 SSR drivers are required in conjunction with SPDT relays, then designation E
& F are not available. SSR driver designation becomes G, H, D, and C. SPDT relay output(s)
are designated as Relay A and Relay B only.

FIGURE 2-11A
SPST Relay Output
Connections are made to relays A through F as shown. Terminal connections are made using
TB6 (Relay/SSR Driver A, B), TB7 (Relay/SSR Driver C, D) and TB8 (Relay/SSR Driver E, F).

HOT
NEU
LOAD
1 2

3 4

N.O. C N.O. C

POWER

5 AMPERES
MAXIMUM
AT 115 VAC

TB6 Relay A & B, Relay A Terminals 1 & 2


TB7 Relay C & D, Relay C Terminals 1 & 2
TB8 Relay E & F, Relay D Terminals 1 & 2

17

FIGURE 2-11B
SPDT Relay Output

HOT
NEU
LOAD
1 2

N.O. C N.C.

POWER

5 AMPERES
MAXIMUM
AT 115 VAC

TB6 Relay A
TB7 Relay B

FIGURE 2-12
SSR Driver Output
Connections are made to relays H through A as shown. Terminal connections are made using
TB9, TB8, etc. depending on the number of SSR Driver outputs specified.

1 2 3 4
TB6 THRU TB9

SSR

FIGURE 2-13
Current Output
Connections are made to current outputs A thruough D as shown. Each current output is
programmable as either 4 to 20 mADC or 0 to 20 mADC. Each output must be assigned to the
desired function in the Program mode. Terminal connections are made using TB10 through
TB13 for current output A through D respectively. Connect positive lead (+) to terminal 1 and
the negative lead (-) to terminal 2. Each current output will operate up to a 650 ohms
maximum load.

1 2
SHIELDED
TWISTED
PAIR

LOAD

18

650 OHMS
MAXIMUM

FIGURE 2-14
Transmitter Power Supply Input
If the isolated 24 VDC regulated transmitter power supply has been specified, the connections
should be made as shown. Connections are made using TB3, terminal 1 is positive and
terminal 2 is negative. The power supply is capable of providing the power needed by up to 2
transducers (40 mADC maximum).

TB3
+ 1 2

TB4 or TB5
+ 1 2 3 4 5

TB3
+ 1 2

TB5

TB4
+ 1 2

3 4

+ 1 2

3 4

SHIELDED
TWISTED
PAIRS

+ -

+ -

+ -

TWO WIRE
TRANSMITTERS

TWO WIRE
TRANSMITTERS

TWO WIRE
TRANSMITTERS

FIGURE 2-15
Position Proportioning Control Output
Position Proportioning control requires that two relays (or SSR Drivers) and the Position
Proportioning Auxiliary input be specified. On a dual pen instrument, either pen may be
configured with Position Proportioning control provided the outputs and auxiliary inputs have
been properly specified.

L2
OPEN
L
C

CLOSE
H
Modulating Motor

4
3
2

TB6, TB7
or TB8

TB4
or
TB5

Slidewire
Feedback
Resistance
min. 135
ohms
max. 10K
ohms
5
4
3

L1

19

Configuration 3.1
After completing installation and wiring of the instrument the configuration (set up) procedures
must be performed to prepare the instrument for operation on the intended application. The
procedures include selecting specific parameters, entering data and possible jumper positioning. Once properly configured the instrument will retain the user selections in memory so this
procedure need not be repeated unless required by changes in the application.
Parameter selections and data entry are made via the front keypad. To ease configuration
and operation, user entered data has been divided up into several sections referred to as
modes. Each mode contains a different type of data or may be used for specific operating
functions. For two pen instruments, some modes are common to both pens. These modes are
as follows:

Control
(CtrL)

Test
(tESt)

MODE

Calibrate
(CAL)

DISPLAY CODE

Program
(Prog)

Tune
(tunE)

Setpoint Select
(SPS)

FUNCTION

Standby
(Stby)

OFF
(oFF)

DESCRIPTION

Off

oFF

Operation

Outputs and Alarms


are Off
Chart may stop
rotating(selectable)

Control

CtrL

Control

Outputs and Alarms


are Active

Test

tESt

Service

Tests Instrument
Operation

Calibration

CAL

Service

Calibrates, Resets
Instrument

Program

Prog

Configuration

Configure Operating
Parameters

Tune

tunE

Configuration &
Operation

Enter Tune and


Alarm Settings

Setpoint Selection

SPS

Operation

Selects Remote or
Local Setpoint
Operation (Remote
Setpoint Optional)

Manual

Stby

Operation

Provides for manual


operation of
proportional output

Enable

EnAb

Configuration

Mode security
system, can lock out
everything except Off
and Control (See
Appendix A-1, page
62, for hardware
lockout information)

Associated with each mode is a series of unique displays that are accessed via the front
keypad.
Prior to first time operation of the instrument, the configuration procedures for the Program
and Tune modes must be performed as applicable. Calibration and Test modes are not used
as part of the instrument configuration or operation. These are used for service and maintenance functions and are discussed in Section 5.4 & 5.5 of this manual (page 46 - 54).

20

Shipped Configuration/Jumper Positioning 3.2


Each instrument is factory shipped ready to accept a thermocouple input on TB 4 and TB 5.
All parameters in each mode are set to default values. These defaults are shown in tabular
form after the description for each mode. Instrument AC power input is as specified in the
instrument model number and is shown on the ratings label. The 230 VAC option includes a
switch in the instrument for selecting either 230 VAC or115 VAC input power. If this feature is
provided, verify AC input and switch position before applying power to the instrument.

3.2.1 JUMPER POSITIONING


Jumpers are used to condition the sensor inputs and to provide a security lockout feature. All
jumpers are located on the instrument Processor board. The instrument board layout and
jumper locations and functions are shown in Appendix A-1 (page 62). Check the jumper
positions in the instrument and verify that they are in the proper position for the intended
application.

The sensor input jumpers JU4, JU5, JU6 and JU7 condition the sensor input signals
and must be used in conjunction with input type selections made in the Program mode.
(page 28).

Operation Summary 3.3


3.3.1 MODE SELECTION
If the instrument is either in the Off mode or the Control mode, repeated pressing and
releasing of the SCROLL key will cause the instrument to display the code corresponding to
each mode that is enabled. To enter a mode while the code is displayed, press the DOWN
key. If a mode does not appear, refer to the Enable mode section for information on how to
determine if the mode is on.
Entry into any mode except the Control, Tune, Manual, Off and Enable modes, will cause the
output(s) to turn off and any process re-transmission value output(s) to be 0 %. Entry into the
Off mode will cause process re-transmission to remain active.

Start up Procedures 3.4


All configuration parameters are listed in Tables 3-1 through 3-5.
For a single pen instrument, parameters for each mode are displayed in the upper right
display. If the instrument being configured is a two pen model, a sequence of applicable
parameters will be displayed in the Pen 2 display after the Pen 1 parameters have been
reviewed and configured. After the Pen 2 parameters have been completed, parameters
common to both pens will be configured and displayed in the Pen 1 display.
The instrument is provided with a time out feature. If the instrument is in any mode (except
while executing a calibration or test procedure) and no keypad activity takes place for 30
seconds, the instrument will time out and exit the mode automatically. The display will become
the code for the respective mode. If a mode code is displayed for 5 seconds with no keypad
activity, then the time out will cause the instrument to proceed to either the Control or Off
mode, depending upon whether the mode entered was an operational mode (Tune, Manual,
Enable) or non operational mode (Test, Program, Cal).

21

3.4.1 POWER UP PROCEDURE


Step 1
Verify that all electrical connections have been properly made before applying power to
instrument.

the

Step 2A - For instruments with software revision R2.99 and below


Upon power up, 7XXX will be displayed (X representing digits), then XXXX, then XXXX,
identifying the twelve digit model number as defined in the order matrix. Next, the EPROM
part number will be indicated P-XX. After the EPROM part number, the software revision level
will be displayed in the format rX.XX then tSt1, tSt2, tSt3 will be displayed while Test 1
through 3 are executed automatically. Upon successful completion of these tests, CtrL or oFF
will be displayed for about three seconds. The mode displayed will be the mode that the
instrument was in when the power was turned off. During this time the operator may select
another mode (Tune, Manual, Enable) or non-operational mode (Test, Program, Cal).
Step 2B - For instruments with software revision R3.00 and above
Upon power up, a brief flash on all displays (upper and, if equipped, lower) will occur to show
the instrument is "alive". Then 7XXX will be displayed (X representing digits), then XXXX,
then XXXX, identifying the twelve digit model number as defined in the order matrix. Next, the
EPROM part number will be indicated P-XX. After the EPROM part number, the software
revision level will be displayed in the format rX.XX followed by P.dn (if Pen Action on Power
Up, PAPu, in Program Mode is set to 0, pens go to "home" position on power up). During this
display, the decimal point after the "P" will blink to show the mode is active. Upon successful
completion of this routine, CtrL or oFF will be displayed for about three seconds. The mode
displayed will be the mode that the instrument was in when the power was turned off. During
this time the operator may select another mode (Tune, Manual, Enable) or non-operational
mode (Test, Program, Cal).
Step 3
If any error messages are displayed, refer to Section 5.6 (page 55) for a definition of the
error message and the required action.

Front Panel Operation 3.5


3.5.1 DIGITAL DISPLAY AND STATUS LEDS
The digital display provided for each pen has 4 digits and a decimal point. Each digit has
seven segments and is capable of producing numeric characters from 0-9 and certain alpha
characters. The digital display is used to provide indication of process variable as well as
displaying codes used for configuration and operation of the instrument. The display includes
the following Status Indicator LEDs;
MAN
OUT1
OUT 2
ALRM
C

Amber
Red
Amber
Red
Red

Red

Red

SP
-

Green
Red

Lights when the Manual StbY mode is on.


Lights when Output 1 is on or mADC output selected.
Lights when Output 2 is on or mADC output selected..
Lights when either Alarm is on.
Lights to indicate that the process value is in degrees C
(Celsius).
Lights to indicate that the process value is in degrees F
(Fahrenheit).
Lights to indicate that the process value is in terms of
Engineering units.
Indicates that the value displayed is the setpoint.
Lights to indicate a negative displayed value.

Refer to Figure 1-2 (page 7) for the display features illustration.

22

3.5.2 KEYPAD CONTROLS


The keys on the keypad functions include:
SCROLL: Used to :

1. Display the enabled modes.


2. While in a mode, used to sequence the parameter codes and
values.
3. Exit some Test and Calibration functions
4. Work in conjunction with other keys:
a. With the UP key to display proportional output %
b. With the DOWN Key;
1) On power up to alter model #
2) Enter Cal/Test functions

UP: Used to:

1.
2.
3.
4.
5.
6.

Exit a mode.
Turn a mode On in the Enable mode
Increase a parameter numerical value
View the setpoint for Pen 1 (Press release)
Increase the setpoint value (Press hold)
Work in conjunction with other keys:
a. With the SCROLL key to display proportional output %
b. With the DOWN key;
1) Lamp test (Press release)
2) Enter the Enable mode (Press and hold for 11
seconds)

DOWN: Used to:

1.
2.
3.
4.
5.
6.
7.

Enter a mode
Turn a mode Off in the Enable mode
Decrease a parameter numerical value
View the setpoint for Pen 2 (if provided)
Decrease the setpoint value (Press hold)
Step display through parameter codes in a mode
Work in conjunction with other keys:
a. With the SCROLL key;
1) On power up to alter the model number
displayed
2) Enter Cal/Test functions
b. With the UP key;
1) Lamp test (Press release)
2) Enter the Enable mode (Press and hold for
11 seconds)

AUTO/MAN: Used to:


The upper key is for
Pen 1, the lower key
is for Pen 2 (if provided)

1. In the Control mode to enter the Manual mode if proportional


output(s) selected
2. In the Manual mode to enter the Control mode if proportional
AUTO
output(s) selected
MAN

AUTO
MAN

23

FIGURE 3-1

Pen 1
AUTO/MAN
Key

SCROLL
Key

UP
Key

Pen 2
AUTO/MAN
Key

DOWN
Key

LAMP TEST
From the Off or Control modes, all display and status LEDs can be illuminated simultaneously
by depressing the UP and DOWN keys at the same time. Any defective LEDs will not light.
CHANGE CHART (also see Changing Charts, Section 5.2)
If the UP and DOWN keys are held depressed for more than 2 seconds but less than 4
seconds, the display will show CChg momentarily. The pen(s) will move to and remain at a
point above the top graduation on the chart and the chart will stop rotating to allow the chart to
be changed. The pens will remain fully upscale with the chart OFF; otherwise, the unit will
continue to operate normally in the current mode. To restore pen(s) position and chart
rotation, press the UP and DOWN keys for more than 2 seconds, but less than 4 seconds.
PEN RESYNCHRONIZATION
To resynchronize the pen(s), depress the UP and DOWN keys for 4 seconds, the display will
show P dn momentarily, the pen(s) are driven to the "Pen Home" position below the bottom
graduation on the chart while the unit resynchronizes their position. After about 14 seconds,
the pen(s) will return to their correct position. All other functions of the unit's present mode
continue to operate normally.

24

PROGRAM MODE FLOW CHART

Prog

A
inPS

AL2

iCor

diSP

out1

dPoS

o1uL

Euu

o1LL

EuL

out2

HyCo

o2uL

HyAo

o2LL

KEY

rSP

Actual Display

AL1

rSPu

ON
OFF

On/Off Display Use arrow keys


to turn on or off

Scroll Key

Numeric Display Use arrow keys


to change value
Up Arrow Key

Down Arrow

25

rSPL

PoL

SPuL

Cru

SPLL

CrL

AtFr

P1EC

Prnd

P2EC

dFF

PAEC

PFF

rLyA

Actual Display

Pout

rLyb

On/Off Display Use arrow keys


to turn on or off

Pou

rLyC

KEY

ON
OFF

Scroll Key

C
Numeric Display Use arrow keys
to change value
Up Arrow Key

Down Arrow

26

rLyd

Cobr

rLyE

CoCr

rLyF

Codr

rLyg

Crt

rLyH

PAPu

CurA

C00

Com (Optional)
Curb

CCon

CurC

Cbs

Curd

CAd1

CoAr

CAd2

27

TABLE 3-1 PROGRAM MODE CONFIGURATION PROCEDURE


Press the SCROLL key until Prog is displayed. Press the DOWN key to enter the Program
mode. Pen 1 will be displayed in the upper display. To enter the Pen 1 parameter, press the
DOWN key. To enter the Pen 2 parameter, if provided, press the SCROLL key, then the
DOWN key. To enter the unit parameter, press the SCROLL key with either Pen 1 or Pen 2
displayed until unit is displayed, then press the DOWN key. Press the SCROLL key to
advance the display through the parameter codes and their values. Use the UP and DOWN
keys to adjust the values. After adjusting a parameter, press the SCROLL key to proceed to
the next parameter. After all selections have been made, press the UP key with a parameter
in the display (not a setting) to exit the mode. For two pen instruments the parameters and
values which are applicable to Pen 1 will appear in the upper display, then the parameters
and values which are applicable to Pen 2 will appear in the lower display. Then the unit
parameters and values will appear in the upper display.
For illustration purposes all available Program mode parameters have been listed. The
parameters that will appear on the specific instrument will depend upon the model number
(hardware configuration) of the instrument and on the parameter selections previously made.
For future reference, record the parameter selections for the application in the Your Setting
column and on the Software Reference Sheet in Appendix E (Page 72). Use the Software
Reference Sheet to program the instrument.
To prevent unauthorized changes to the Program mode, the mode can be disabled (turned
off) in the Enable mode.

STEP

DESCRIPTION

Input Select

DISPLAY AVAILABLE
CODES SETTINGS
inPS

0=J T/C degrees C


1=J T/C degrees F
2=K T/C degrees C
3=K T/C degrees F
4=T T/C degrees C
5=T T/C degrees F
6=R T/C degrees C
7=R T/C degrees F
8=S T/C degrees C
9=S T/C degrees F
10=E T/ C degrees C
11=E T/C degrees F
12=B T/ C degrees C
13=B T/C degrees F
14=N T/ C degrees C
15=N T/C degrees F
16=C T/ C degrees C
17=C T/C degrees F
20=RTD degrees C
21=RTD degrees F
30=0 to 5 VDC
31=1 to 5 VDC
32=0 to 50 mVDC
33=10 to 50 mVDC
34=0 to 25 mVDC

NOTE:
Fault Detection is not functional
for 0-5V or 0-20mA inputs.

28

FACTORY
SETTING

Input Correction

iCor

-300 to 300 degrees/units

Output 1

out1

0 = None
0
1=On-Off- Direct
2=On-Off- Reverse
3=Time Proportioning- Direct
4=Time Proportioning -Reverse
5=Current Proportioning -Direct
6=Current Proportioning -Reverse
7=Position Proportioning (open)

YOUR
SETTING

DISPLAY AVAILABLE
CODES SETTINGS

FACTORY
SETTING

YOUR
SETTING

STEP

DESCRIPTION

Output 1 Percent
Upper Limit
(o1uLand o1LL will
not be seen if out1 = 0,1,2)

o1uL

0 to 100 percent

100

Output 1 Percent
Lower Limit

o1LL

0 to 100 percent

Output 2

out2

0 = None (Position
0
Proportioning - Direct Closed)
1=On-Off- Direct
2=On-Off- Reverse
3=Time Proportioning- Direct
4=Time Proportioning-Reverse
5=Current Proportioning- Direct
6=Current Proportioning -Reverse
7=Position Proportioning
(Reverse/Closed)

Output 2 Percent
Upper Limit (o2uL and
o2LL will not been seen if
out2 = 0,1,2,7)

o2uL

0 to 100 percent

100

Output 2 Percent
Lower Limit

o2LL

0 to 100 percent

Alarm 1
the Alarm Point
is selected in the
Tune mode

AL1

0 to 6
0
0 = None
1=Process Alarm-Direct
2=Process Alarm-Reverse
3=Deviation Alarm-Direct
4=Deviation Alarm-Reverse
5=Deviation Band Alarm-Open within band
6=Deviation Band Alarm-Closed within band

10

Alarm 2

AL2

Same selections as Alarm 1

11

Display Select

diSP

1=Process value only


2=Process value/setpoint
3=Deviation only
4=Deviation and setpoint
5=Setpoint only

12

Decimal Position

dPoS

0 to 3
0
0=None
1=One decimal place
2=Two decimal places
3=Three decimal places
RTD and thermocouple inputs
are limited to either 0 or1 decimal positions

13

Engineering Units
Euu
Upper Value (Euu and
EuL will be seen if the pen
input select = 30,31,32,33,34)

-9999 to 9999

1000

14

Engineering Units
Lower Value

EuL

-9999 to 9999

15

Hysteresis for
Control Outputs

HyCo

0 to 300
Width of Hysteresis Band
(See page 66 for definition)

29

30

DISPLAY AVAILABLE
CODES SETTINGS

FACTORY
SETTING

STEP

DESCRIPTION

16

Hysteresis for
Alarm Outputs

HyAo

0 to 300
Width of Hysteresis Band
(see page 66 for definition)

17

Remote Setpoint
If rSP is set to zero
then rSPu and rSPL
are not seen

rSP

0 to 2
0=Not Used
1=1 to 5 VDC
2=0 to 5 VDC

18

Remote Setpoint
Upper Value

rSPu

-9999 to 9999

1400

19

Remote Setpoint
Lower Value

rSPL

-9999 to 9999

20

Setpoint Upper Limit

SPuL

-9999 to 9999

1400

21

Setpoint Lower Limit

SPLL

-9999 to 9999

22

Automatic Transfer

AtFr

0 to 2
0
0 = No Automatic Transfer
1=Transfers when the process
value goes below the setpoint
2=Transfers when the process
value goes above the setpoint

23

Process Rounding
of Displayed Value

Prnd

0 to 100
0 = No rounding

24

Display Filter Factor

dFF

1 to 20
1
1= no filtering
(number of values averaged)

25

Process Filter Factor

PFF

Same selection as dFF

26

Process Value Output


Retransmission
(If Pout =0 then Pou and
PoL will not be displayed)

Pout

0=Not selected
1=Selected

27

Process Output
Upper Value

Pou

-9999 to 9999

2000

28

Process Output
Lower Value

PoL

-9999 to 9999

29

Chart Range
Upper Value

Cru

-9999 to 9999

200

30

Chart Range
Lower Value

CrL

-9999 to 9999

31

Proportional
Output 1 Action
on Error Condition
(If out1= 0,1,2 then
P1EC will not be displayed)

P1EC

0 to 100%

32

Proportional
Output 2 Action
on Error Condition
(If out2 = 0,1,2,7 then
P2EC will not be displayed)

P2EC

0 to 100%

YOUR
SETTING

STEP

DESCRIPTION

33

Pen Action on
Error Condition

DISPLAY AVAILABLE
CODES SETTINGS
PAEC

FACTORY
SETTING

YOUR
SETTING

0 or 1
1
0 = Pen goes to 0 % of chart
1 = Pen goes to 100 % of chart

Pressing the SCROLL key with the PAEC parameter value displayed in the Pen 1 window will
advance the display of a single pen instrument to the unit parameters. Pressing the SCROLL
key with the PAEC parameter displayed in the Pen 1 window of a two pen instrument will
advance the display to be PEns in the Pen 2 window. The Pen 2 Program mode parameter
selections can be made now. Pressing the SCROLL key with the PAEC parameter value
displayed in the Pen 2 window will cause the display to advance to the unit parameters
displayed in the Pen 1 window.
UNIT PARAMETERS
34

Relay A Assignment

rLyA

0 to 8
0
1=Assigned to Alarm 1-Pen 1
2=Assigned to Alarm 2-Pen 1
3=Assigned to Alarm 1-Pen 2
4=Assigned to Alarm 2-Pen 2
5=Assigned to Output 1-Pen 1
6=Assigned to Output 2-Pen 1
7=Assigned to Output 1-Pen 2
8=Assigned to Output 2-Pen 2

35

Relay B Assignment

rLyb

Same selection as rLyA

36

Relay C Assignment

rLyC

Same selection as rLyA

37

Relay D Assignment

rLyd

Same selection as rLyA

38

Relay E Assignment

rLyE

Same selection as rLyA

39

Relay F Assignment

rLyF

Same selection as rLyA

40

Relay G Assignment

rLyg

Same selection as rLyA

41

Relay H Assignment

rLyH

Same selection as rLyA

42

Current Output A
Assignment

CurA

0 to 6
0
0=Not Assigned
1=Assigned to Process
Value Output-Pen 1
2=Assigned to Process
Value Output-Pen 2
3=Assigned to Output 1-Pen 1
4=Assigned to Output 2-Pen 1
5=Assigned to Output1-Pen 2
6=Assigned to Output 2-Pen 2

43

Current Output B
Assignment

Curb

Same selection as CurA

44

Current Output C
Assignment

CurC

Same selection as CurA

45

Current Output D
Assignment

Curd

Same selection as CurA

46

Current Output A
Range

CoAr

0 to 1
0=0-20 mA
1=4-20 mA

31

DISPLAY AVAILABLE
CODES SETTINGS

FACTORY
SETTING

STEP

DESCRIPTION

47

Current Output B
Range

Cobr

Same selection as CoAr

48

Current Output C
Range

CoCr

Same selection as CoAr

49

Current Output D
Range

Codr

Same selection as CoAr

50

Chart Rotation Time

Crt

0.1 to 999.9 hours per


rotation

1.0

51

Pen Action on Power Up

PAPu

0=Pen(s) go to the "home"


0
posistion (toward chart
cetner) when powered up
1=Pen(s) remain in last
position prior to power down

52

Chart Operation
in Off Mode

Coo

0 to 1
0=Chart continues rotating
in the Off mode
1=Chart stops rotating while
in the Off mode

COMMUNICATIONS OPTIONS PARAMETERS

32

53

Communication
Configuration

CCon

0 to 4
3
0=Off
1=Monitor Mode (Read Only)
2=Normal Mode (Read and Write)
3=Total Access with Limit Checking
4=Total Access without Limit Checking

54

Communication Bit
Rate Selection
Will not be seen if
Con=0

CbS

1 to 6
1=300
2=600
3=1200
4=2400
5=4800
6=9600

55

Communications
Address-Pen 1
Will not be seen if
Con=0

CAd1

0 to 99

56

Communications
Address-Pen 2
(If provided)
Will not be seen if
Con=0

CAd2

0 to 99

YOUR
SETTING

TUNE MODE FLOW CHART

tunE

A
SoP

rSEt

PAL1

ArSt

dAL1

rAtE

bAL1

Ct1

PAL2

Ct2

dAL2

SEnS

bAL2

FoP

Key
Pb1

Actual Display

ON
OFF

Pb2

On/Off Display Use arrow keys


to turn on or off

Scroll Key

Numeric Display Use arrow keys


to change value
Up Arrow Key

Down Arrow

33

TABLE 3-2 TUNE MODE CONFIGURATION PROCEDURE


The Tune mode allows the entry, review or altering of the process control Tune adjustments
and alarm setting(s).
To enter the Tune mode, press and release the SCROLL key until tunE is displayed, then
press the DOWN key. Press the SCROLL key to advance the display through the parameters
and their values. Use the UP and DOWN keys to select (adjust) the values. Each time the
DOWN key is pressed while a parameter code is being displayed, such as SoP, the next
parameter code in the sequence will be displayed (PAL1).
After selecting a parameter, press the SCROLL key to proceed to the next parameter. Pen 1
selections will appear in the Pen 1 window and the Pen 2 ( if provided) selections will appear
in the Pen 2 window after the Pen 1 parameters have been displayed. After all selections
have been made, press the UP key with a parameter in the display (not a setting) to exit the
mode.
For illustration purposes, all available Tune mode parameters have been listed. The
parameters that will appear on the specfic instrument will depend upon the parameter
selections previously made in the Program mode.
For future reference, record the parameter selections for the application in the "Your Setting"
column and on the Software Reference Sheet in Appendix E (page 72). Use the Software
Reference Sheet to program the instrument.
To prevent unauthorized changes to the Tune mode, the mode can be disabled (turned off) in
the Enable mode.

The Tune mode is adjusted on-line. The instrument will react to changes as they are
made.

34

DISPLAY AVAILABLE
CODES SETTINGS

FACTORY
SETTING

STEP

DESCRIPTION

Second Output Position


SoP
(Will not be seen if out2=0,7)

-1000 to 1000 units

Process Alarm 1
PAL1
(The Alarm setting seen
will depend upon the Alarm
selected in the Program mode)

-9999 to 9999 units

Deviation Alarm 1

dAL1

-3000 to 3000 units

Deviation Band Alarm 1

bAL1

1 to 3000 units

Process Alarm 2

PAL2

-9999 to 9999 units

Deviation Alarm 2

dAL2

-3000 to 3000 units

Deviation Band Alarm 2

bAL2

1 to 3000 units

Proportional Band
Output 1 (Will only be seen
if out1=3,4,5,6,7)

Pb1

1 to 3000 units

100

Proportional Band
Output 2 (Will only be
seen if out2=3,4,5,6)

Pb2

1 to 3000 units

100

10

Manual Reset
(Will only be seen if
Pb1/Pb2 were shown)

rSEt

-1500 to 1500 units

YOUR
SETTING

DISPLAY AVAILABLE
CODES SETTINGS

FACTORY
SETTING

STEP

DESCRIPTION

11

Automatic Reset
Integration
(Will be seen if Pb1 or
Pb2 was shown)

ArSt

0.0 to 100.0 repeats


per minute

0.0

12

Rate Derivative
(Wll be seen if
Pb1 or Pb2 was seen)

rAtE

0.0 to 10.0 minutes

0.0

13

Cycle Time Output 1


(Will be seen if out1=3,4,7)

Ct1

1 to 240 seconds

30

14

Cycle Time Output 2


(Will be seen if out2=3,4)

Ct2

1 to 240 seconds

30

15

Position Proportioning
Sensitivity (Will be seen
if out1=7 and/or out2=0,7)

SEnS

0.0 to 50.0 percent

1.0

16

First Output Position

FoP

-1000 to 1000 units

YOUR
SETTING

35

TABLE 3-3 ENABLE MODE CONFIGURATION PROCEDURE


To enter the Enable mode, press the UP and DOWN keys while in CtrL or oFF modes. All the
display lamps will light. After 2 seconds, the display will show Cchg and the pen(s) will move
to and remain at a point above the top graduation on the chart. Continue to press the UP and
DOWN keys, after 2 additional seconds, the display will show P dn and the Pen(s) are driven
below the bottom graduation on the chart. After 6 more seconds, the display will show EnAb.
Release the keys and the display will change to EtSt. Press and release the DOWN key and
each mode to be enabled/disabled will be displayed. With the enable mode prompt for the
desired mode displayed press the SCROLL key to verify that the displayed mode is either on
(enabled) or oFF (disabled). Press the DOWN key to turn off the mode, press the UP key to
turn on the mode or press the SCROLL key to advance the display to the next enable mode
prompt. Use the "Your Setting" column in the table to record your settings.
A hardware jumper located on the Processor Board (See Appendix A-1, Page 62) can be
used to lock/unlock the Enable mode. When the jumper is moved to the locked position, entry
into the Enable mode is not possible until the jumper is moved to the unlocked position.

STEP

DESCRIPTION

1
2
3
4
5
6

Test Mode
Calibration Mode
Program Mode
Tune Mode
Manual (Stby) Mode
Setpoint Select mode
(Optional)
Setpoint Change

DISPLAY AVAILABLE
CODES SETTINGS
EtSt
ECAL
EPro
Etun
ESby
ESPS

on or oFF
on or oFF
on or oFF
on or oFF
on or oFF
on or oFF

ESPC on or oFF

ENABLE MODE FLOW CHART


EnAb

Key

EtSt

ON
OFF

ECAL

ON
OFF

EPro

ON
OFF

Etun

ON
OFF

ESbY

ON
OFF

ESPS

ON
OFF

ESPC

ON
OFF

Actual Display

ON
OFF

On/Off Display Use arrow keys


to turn on or off

Scroll Key

Numeric Display Use arrow keys


to change value
Up Arrow Key

Down Arrow

36

FACTORY
SETTING
oFF
oFF
on
on
on
on
on

YOUR
SETTING

Operation 4.1
4.1.1 OFF MODE
In the Off mode, the instrument control and alarm function (s) are turned off. Process
Retransmission signal(s) remain active. The chart rotation can be selected in the Program
mode to stop or continue to rotate when the instrument is in the Off mode. The pen(s) will
remain active. The Off mode can be entered by pressing and releasing the SCROLL key until
the display reads oFF, then pressing the DOWN key. The display will read oFF and then
current process variable at two second intervals. Entering the Off mode of a dual pen
instrument will cause both pens to enter the Off mode. The second pen display will be blank
as the upper display reads oFF and displays the process value for the second pen at the
same time as the upper display.

4.1.2 CONTROL MODE


In the Control mode, the instrument control function(s) and alarm(s) are actively responding to
the process variable as selected in the Program and Tune modes and the chart will be
rotating at the rate selected. The Control mode allows setpoint changes form either local
setpoint (standard) adjustment by an operator at the front keypad or from remote setpoint
source (optional). Other operations in the Control mode include a lamp test and proportional
output display.

4.1.2.1 LOCAL SETPOINT OPERATION


Single Pen Instruments: The instrument must be in the Control mode to allow setpoint value
to be displayed and adjusted. In the Control mode, to view the setpoint, press and release the
UP and DOWN key. The green LED under the SP label will light to indicate that the displayed
value is the setpoint. To change the setpoint value, press and hold the appropriate key.
Press and hold the UP key to increase the setpoint or press and hold the DOWN key to
decrease the setpoint. The setpoint will change slowly at first, then faster as the key is held.
If the setpoint will not increase, check the Program mode to see that you are not trying to
increase the setpoint above the setpoint upper limit SPuL. If the setpoint will not decrease,
check the Program mode to see that you are not trying to decrease the setpoint below the
setpoint lower limit SPLL. If the setpoint will not increase or decrease, check that the Setpoint
Change mode is On in the Enable mode.
Dual Pen Instruments: The setpoint of each instrument can be reviewed separately. Pen 1:
To review and change the local setpoint for Pen 1, press the UP key. The green LED in the
upper display will light indicating that the setpoint value is displayed. The setpoint can now be
raised by pressing and holding the UP key or decreasing by pressing the DOWN key. Pen 2:
The setpoint for Pen 2 is viewed and changed in the same manner, except the DOWN key
must be pressed to access the Pen 2 setpoint. The setpoint will change slowly at first, then
faster as the key is held. If the setpoint will not increase, check the Program mode to see that
you are not trying increase the setpoint above the setpoint upper limit SPuL. If the setpoint
will not decrease, check the Program mode to see that you are not trying to decrease the
setpoint below the setpoint lower limit SPLL. If the setpoint will not increase or decrease,
check that the Setpoint change mode is On in the Enable mode.

4.1.2.2 REMOTE SETPOINT OPERATION


Single Pen Instruments: If the instrument is specified and provided with Remote Setpoint
capability (auxiliary input of 0-5VDC or 1-5VDC), and the Remote Setpoint has been properly
configured in the Program mode, the Setpoint Select mode will be accessible, if enabled.
Press and release the SCROLL key until SPS appears in the display, then press the DOWN
key. The display will show Loc if the local (keypad entered) setpoint is being used or rSP if
the remote setpoint is in use. Press the SCROLL key to select the setpoint mode that will be
used by the instrument. Press the UP key to exit the Setpoint Select mode.

37

Dual Pen Instruments: If the instrument is specified and provided with the Remote Setpoint
capability for either or both pens and the Remote Setpoint has been properly configured in the
Program mode for either or both pens, the Setpoint Select mode will be accessible, if enabled.
Press and release the SCROLL keys until SPS appears in the display, then press the DOWN
key. The upper display will light and the lower display will blank if pen 1 is selected for a
remote setpoint. If only pen 2 is selected as a remote setpoint, then the upper display will
blank and the lower display will light. If both pens are selected for remote setpoint, the lower
display is accessed by pressing the DOWN key while the upper display shows the setpoint
mode selected for that pen. The display(s) will show Loc if the local (keypad entered) setpoint
is being used or rSP if the remote setpoint is in use. Press the SCROLL key to select the
setpoint mode that will be used by the instrument. Press the UP key to exit the Setpoint Select
mode. If a problem develops with the remote setpoint signal for either pen, the upper display
will show rSEr, the remote setpoint error code.
Digital Communications: The setpoint can be adjusted from a supervisory computer system.
Dual pen instruments are capable of having independent setpoint adjustments for each pen.

SETPOINT SELECT FLOW CHART

SPS

KEY
Actual Display

ON
OFF

LOC

On/Off Display Use arrow keys


to turn on or off

Scroll Key

rSP

Numeric Display Use arrow keys


to change value
Up Arrow Key

Down Arrow

4.1.2.3 ON-OFF CONTROL


On-Off control can only be implemented on controllers provided with SPST relay or SSR driver
output's. On-Off operation can be assigned to either or both output 1 and 2 for each pen. The
On-Off control can be selected as direct or reverse acting. Direct action is typically used in
cooling applications. The output device will turn On when the process value is greater than the
setpoint. Reverse action is typically a heating application. The output device will turn On if the
process value is below the setpoint. A hysteresis adjustment is provided for On-Off outputs on
each pen. This adjustment is in terms of degrees/engineering units and defines the width of
the hysteresis band about the setpoint. This parameter may also be referred to as a
deadband. Relay chatter can be eliminated by proper adjustment of this parameter. When
operating in On-Off control, the control algorithm will turn the output On or Off depending upon
the setpoint, the relative position of the process value, and the hysteresis adjustment. The
respective OUT1 or OUT2 indicator for the respective pen will illuminate to indicate that the
output device is On.

38

4.1.2.4 TIME PROPORTIONING CONTROL


Time Proportioning Control can be implemented on controllers provided with SPST relay or
SSR driver output(s). Time proportioning can be programed for output 1 and/or 2 for each
pen. Time proportioning control is accomplished by cycling the output On and Off when the
process value is within the proportional bandwidth selected at a prescribed time period. The
time period is selected in the Tune mode by adjusting Ct1 and/or Ct2. The On time is a
percentage of the Cycle Time.
Example: Calculated output % = 40%;

Cycle Time adjustment = 20 seconds


Output On Time = .4 x 20 = 8 seconds
Output Off Time = .6 x 20 = 12 seconds

4.1.2.5 CURRENT PROPORTIONING CONTROL


Current Proportioning control provides a proportional current output in response to process
value and setpoint. The current output can be selected for direct or reverse operation. Direct
current output control is typically used for cooling applications. The current output will
increase as the process value increases within the proportional bandwidth selected. The
reverse current output control is typically used in heating applications. The current output
will decrease as the process value increases within the proportional bandwidth selected.
The instrument can be programmed to provide 0 to 20mADC or 4-20mADC current output(s).
The output selected is dependent upon the final control element being used in the process.
The output 1 and/or output 2 LED will be lighted whenever the Current Proportional outputs
are selected.

4.1.2.6 POSITION PROPORTIONING CONTROL


Position Proportioning control can be implemented on those controllers provided with two
SPST relay outputs or two SSR Driver outputs and Slidewire Feedback option for the
respective pen. This control implementation can be performed on each pen.
Position proportioning control permits the use of PID control where the final control element is
a modulating device such as a motorized valve. In this form, each of the two required relays
or SSR Drivers will be used to control the valve. One output will be used to open the valve,
the other is used to close the valve. The slidewire feedback is used to provide a signal
relative to the valve armature position to the instrument.
As with the other proportioning control forms, the process input, tuning parameters and the
setpoint are used by the control algorithm to calculate the output % required to correct for the
deviation between setpoint and process.
Proportional Output 1 Action P1EC on error condition does not apply to position proportioning
control. In an error condition, the unit goes only to 0% output (fully closed).
With Position Proportioning control, it may be necessary to adjust the Sensitivity Tune SEnS
mode parameter to reduce or eliminate oscillations of the motor around setpoint. If oscillation
occurs, increase the SEnS value until the motor stops oscillating. If the differential between
the Open and Closed rotation is too large, then decrease the SEnS value. Also, for proper
Position Proportioning operation, it is necessary to specify the actuation time of the valve or
damper from full open to full closed. If the motor has a stroke duration of 60 seconds, change
the value in the Cycle Time parameter Ct1 to 60. This ensures that controller will move the
motor for the proper amount of time when making adjustments.

39

4.1.2.7 PROPORTIONAL OUTPUT PERCENTAGE DISPLAY


While in the Control mode, pressing the UP and the SCROLL keys at the same time will
cause the display to sequence through a series of display codes and values:
Po1
Po2
Proc

Percent Output (if applicable)


Percent Output (if applicable)
Process Value

Output 1% value
Output 2% value
Actual Process Value

Each code and output value will be displayed only if the corresponding proportional output is
present. Each code or value will be displayed for 1 second. This sequence of displays will
continue until the SCROLL key is pressed, which will then return the display to the normal
mode. Displays will sequenced for both Pen 1 and 2 as applicable on dual pen instruments.

4.1.3 MANUAL MODE FOR PROPORTIONAL OUTPUTS


Manual adjustment of the proportional output(s) can be used to test the operation of the
output(s), while tuning to establish basic process control, or to provide control of the proportional output(s) during the occurrence of certain error conditions.
Note: The proportional outputs do not change automatically in response to changes in
the process while in the Manual mode. Be sure to pay close attention to the process to
avoid damage.
To enter the Manual mode, pres and release the AUTO/MAN key for the specific pen. If the
Standby mode is On in the Enable mode and a control output is selected for proportional
control, the instrument will enter the Manual mode. The Manual mode status LED will light for
that pen to indicate that the Manual mode is in use. Shifting from the Control to the Manual
mode is bumpless. The proportional output(s) will stay at the last value(s) calculated by the
control algorithm. Po1 will appear on the display if output 1 is a proportional output or Po2 if
output 1 is not a proportional control.
In order to vary a proportional output value, press and release the SCROLL key until the
display code for the output is displayed, Po1 or Po2. Press the SCROLL key again to see the
percentage of output value. Press the UP key to increase the output percentage value. Press
the DOWN key to decrease the output percentage value.
If no keys are pressed, the display will sequence through the following displays:
Po1 if output 1 is 3, 4, 5, 6, 7 then the output 1 percentage of output value
Po2 if output 2 is 3, 4, 5, 6, 7 then the output 2 percentage of output value
Proc will be displayed then current process value for that pen
In order to change a proportional value once the cyclic display begins, press and release the
UP or DOWN key then press the SCROLL key until the display code for the output displayed
is Po1 or Po2. Press the SCROLL key again to see the percentage of output value. Press
the UP key to increase the output percentage value. Press the DOWN key to decrease the
output percentage value.
To return to the Control mode of operation from the Manual mode, press the specified AUTO/
Man key. If the Automatic Transfer feature is selected in the Program mode, the instrument
will switch from Manual mode to the Control mode when process value reaches the setpoint
value.

40

STANDBY MODE FLOW CHART

Stby

KEY
Actual Display

Po1
ON
OFF

On/Off Display Use arrow keys


to turn on or off

Scroll Key

Po2
Numeric Display Use arrow keys
to change value
Up Arrow Key

Down Arrow

Alarm Operation 4.2


There are two alarms available per pen. The type of alarm is selected in the Program mode
as follows:
1. Process Alarm Direct - the alarm will be On if the process value is greater than the process
value selected.
2. Process Alarm Reverse - the alarm will be On if the process value is less than the process
value selected.
3. Deviation Alarm Direct - the alarm will be On if the process value is greater than the
setpoint plus the deviation value selected.
4. Deviation Alarm Reverse - the alarm will be On if the process value is less than the
setpoint plus the deviation value selected.
5. Deviation Band Alarm Open Within - the alarm will be On if the process value is greater
than one half the deviation band alarm values selected above or below the setpoint.
6. Deviation Band Alarm Close Within - the alarm will be On if the process value is less than
one half the deviation band value selected above or below the setpoint.
The alarms will be active while the instrument is in the Control mode. Relay and solid state
relay drivers can be assigned to provide output capability for the alarm functions.
The alarm value (Process deviation or bandwidth) is selected in the Tune mode.
Alarm outputs chatter can be reduced by using the hysteresis for the alarm output adjustable
in the Program mode to create a deadband around the alarm point.

41

Tune Mode Operation 4.3


Proportional output controllers may require the adjustment (tuning) of the PID and other
related parameters. This provides a means for the instrument's control algorithm to be
adjusted to meet specific application requirements.

4.3.1 SYSTEMATIC TUNING METHOD


1. Changes in tuning parameters should be made one at a time.
2. After making any changes in tuning parameters, a disturbance should be introduced into
the process so that the process reaction may be observed. This process reaction, or
recovery, will tell whether the tuning parameters provide the desired control. It is usually
easiest to make a step change in setpoint to introduce this disturbance.
3. The change in setpoint or disturbance, referenced above should be large enough to cause
an observable deviation of process from setpoint. However, this change should not be so
large that it will cause the controller output to proceed to either extreme limit.
4. Controller tuning for optimal control is not hard and fast, BE PATIENT: The process will
take a certain amount of time to react to the setpoint changes during tuning. The amount
of time depends upon the specific process, however, a period of 8 to 12 minutes should
be allowed between changes. The important point to remember is to allow the process to
react completely, do not rush through tuning of the controller. If the complete process
reaction is not observed, optimum control may never be achieved.
5. Time Proportioning control output(s) require the cycle time to be adjusted for the
application. Short cycle times typically result in the most accurate process control, but will
cause the quickest "wear out" of any mechanical components.
6. Leave all other tuning parameters (except for the alarm settings) at the factory default
settings. Obtain the best possible process reaction by adjusting the Proportional Band
width parameter. The setting that achieves the best response for the process should be
left in the controller programming, and should be noted on the Software Reference Sheet
in Appendix E (page 72).
7. If there are to be no setpoint or load changes in the process, the Proportional Band
adjustment may be all that is necessary for proper control. If an offset still exists (the
process does not settle out at setpoint for the best possible proportional band adjustment),
Manual Reset may be added to eliminate this offset.
8. Auto Reset may be added to eliminate process offsets with respect to setpoint. Increase
Auto Reset from 0 to 0.2 increments. Start with a small amount. Increase this increment if
there is no apparent reaction. Remember to allow the process 8 to 12 minutes to react to
any changes.
9. If necessary, Rate may be added. Rate is a dynamic tuning parameter. Rate may be
required to compensate for load changes or to inhibit process oscillations that occur when
a large amount of auto reset (4 or 5 repeats/minute) is being used.
10. Controller tuning is not hard and fast. It may be necessary to adjust the tuning
parameters over a period of time to obtain optimal control of the process.

42

4.3.2 ZIEGLER NICHOLS TUNING METHOD


This procedure has been determined empirically to yield ideal 1/4 amptitude decay tuning
parameters that are determined by watching the system in a sustained oscillation (curve C,
page 44, the ultimate proportional band and ultimate time period) and then using these values
from this sustained oscillation to calculate ideal parameters.
To aid in determining the process oscillation, the instrument configuration parameters can be
adjusted. By reducing the chart upper value Cru and increasing the chart lower value CrL,
the resolution of the oscillation can e better observed. Also the chart rotation time Crt can be
reduced to improve the observation of the oscillation cycle time.
Determining Ultimate Proportional Band and Ultimate Time Period
1. Set Manual Reset rSet to 0.0, set ArSt to 0.0 and set rAtE to 0.0.
2. Enter the Control mode of operation, observe the process reaction.
3. Set the Proportional Band (PB) at 100 and upset the process and observe the response.
One easy method for imposing the upset is to move the setpoint for a few seconds and
then return it to its original value.
4. Achieve a response curve similar to the sustained oscillation (curve C), this is the Ultimate
Proportional Band (UPB) and Ultimate Time Period (UTP).
a) If the response curve from step 3 does not damp out, as in curve A from the
drawing, the PB is too low. The PB should be increased and step 3 repeated.
b) If the response in step 3 damps out, the PB is too high. The PB should be
decreased and step 3 repeated.

These values obtained for Ultimate Proportional Band (UPB) and Ultimate Time Period (UTP)
are used to calculate ideal P, PI, PD, PID tuning parameters using the following ZieglerNichols equations:
Proportional only control (P)

P (Pb) = 2 x UPB (degrees or units)

Proportional plus automatic reset (PI)

P (Pb) = 2.2 x UPB (degrees or units)


I (ArSt) = 1.2 / UTP (repeats per minute)

Proportional-plus-derivative (or rate) (PD)

P (Pb) = 1.7 x UPB (degrees or units)


D (rAtE) = UTP / 8 (minutes)

Proportional-plus automatic reset-plus


derivative (PID)

P (Pb) = 1.7 x UPB (degrees or units)


I (ArSt) = 2 / UTP (repeats per minute)
D (rAtE) = UTP / 8 (minutes)

If an over damped response is desired, multiply the proportional band by two.


(Referenced illustration on next page)

43

Period
C
B
A

Curve A : unstable
Curve B : stable
Curve C : continuously cycling, ultimate PB and period

44

Service 5.1
This section contains information regarding calibration and test procedures that can be
performed in the field as well as items concerning the normal maintenance of the instrument.

Changing Charts

5.2

Chart changes may be done while in the normal operating mode.

CAUTION: The chart flange assembly pin is sharp to perforate the chart. Use caution
while installing the chart to avoid coming into contact with the pin.
1. Depress and hold the UP and DOWN keys for between 2 and 3 seconds. Immediately
after depressing the keys, the unit will do a Lamp Test with all LED segments and indicators
lighted on the upper (and lower) display.
2. After 2-3 seconds, the display will show Cchg, the pen(s) will move to and remain at a
point above the top graduation on the chart and the chart will stop rotating. All other functions
remain active (Control, Display, etc).
3. Open the instrument door, snap up the chart hold down lever on the chart flange assembly,
gently lift the pen(s) and remove old chart.
4. With the pen(s) held up, install new chart. Be sure to line up the chart time line so that the
current time is aligned with the time setting mark on the chart platen.
5. Snap down chart hold down lever and close the instrument door.
6. Depress and hold the UP and DOWN keys for between 2 and 3 seconds. Immediately
after depressing the keys, the unit will do a Lamp Test with all LED segments and indicators
lighted on the upper (and lower) display.
7. After 2-3 seconds, the display will show Cchg momentarily, then the pen(s) position and
chart rotation will be restored.

Changing Pens

5.3

Open the instrument door. Refer to Figure 5-1 for pen changing procedure. This procedure is
also provided on a label on the instrument chart platen. Be sure to replace the pen cartridge
with the same type (color) that was removed. Be careful not to bend the pen arm while
changing the pen.

FIGURE 5-1

Changing Pens
To install pen, slide pen into
holder (1) and push down (2)
as shown by arrows
1

For five replacement


pens order:
Green #60500401
Red #60500402

To remove pen for


replacement, pull up at back
end (1) and push out.
2

45

Calibration 5.4
CAUTION: Do not attempt any calibrations without the proper test equipment that meets or
exceeds the specifications listed.
Press and release the SCROLL key until CAL appears on the display , then press the DOWN
key to enter the mode. The display will change to CAL1. Press the SCROLL key to advance
the display to the other calibration modes available. For two pen units, CAL5 will only need
to be required on TB4 to calibrate Pen 1 and Pen 2 inputs. Both TB 4 and TB 5 inputs must
be calibrated for thermocouple inputs. Table 5-1, page 47, provides a listing of field calibration routines. All instruments are calibrated prior to shipment from factory.

CALIBRATION FLOW CHART

CAL

CAL1

CAL2

CAL3

CAL4

KEY

CAL5

Actual Display

ON
OFF

On/Off Display Use arrow keys


to turn on or off

CAL6

Scroll Key

CAL7
Numeric Display Use arrow keys
to change value
Up Arrow Key

Down Arrow

46

CAL9

Prog

TABLE 5-1 CALIBRATION PROCEDURES


Calibration
Procedure
CAL 1

Description
Reinitialization of program and tuning values.

CAL 2

Main calibration necessary for all input types.

CAL 3

Cold Junction Compensation calibration used to correct for component


variation in the CJC circuit. Necessary for thermocouple inputs.

CAL 4

Cold Junction Utility, displays temperature the cold junction compensator


is sensing. No adjustment is made with this procedure.

CAL 5

RTD input calibration. Necessary to be performed on both terminal boards.

CAL 6

Cold Junction Compensation on/off. Used for validating thermocouple


inputs with a millivolt source. (Non temperature compensating)

CAL 7

Factory use only.

CAL 9

Pen position calibration used to calibrate pens to chart.

5.4.1 CAL 1 PARAMETER RE-INITIALIZATION


This routine is used to clear all information in the Program and Tune modes. All parameters
will be reset to default values. Before performing this procedure, make sure that the
Program and Tune values are written down so that they can be re-entered after Calibration 1 is completed. No test equipment required.
With CAL 1 displayed, while pressing the DOWN key, press the SCROLL key. The display
will momentarily blank while the initialization is in progress. Upon completion of the routine, a
Pen Home function is automatically performed; P.dn is displayed during this period, with the
decimal point flashing to indicate this mode. Once the pen(s) reach Pen Home, CAL1 will be
displayed.

5.4.2 CAL 2 MAIN CALIBRATION


This routine determines and saves calibration values which correct for component variations
relating to the basic measuring function of the unit. A 50.00 mVDC .01mVDC source is
required for testing. Make sure that the Processor board jumpers JU4 and JU5 are in the
non-volt positions. See Appendix A-1 (page 62) for proper positioning. After completing
CAL2, be sure to re-position these jumpers to the appropriate position for your input.
With CAL 2 displayed, press and hold the DOWN key, then press the SCROLL key. Release
the keys when the instrument displays hLd1. Short the input terminals or apply 0.00, .01
mVDC to TB 4 terminals 1 and 2. Press the DOWN key and dELy will appear for 10 seconds, then SCAn will appear for 10 seconds. A calibration reference number will then appear,
this should be 0 50. If this number falls outside these limits, press the SCROLL key and
CAL 2 will be displayed. Perform the calibration again. Repeat the calibration until the number
falls within the tolerance limits. If the number remains outside the limits, check the connections and try the calibration again. If the number does not approach the tolerance limits
contact the nearest representative or the factory for assistance. With an acceptable reference
number on the display, remove the short and connect a 50.00, .01 mVDC source to the TB
4 terminals 1 and 2. Be sure to observe the proper polarity when connecting the source.
Terminal 1 is positive and terminal 2 is negative. Press the DOWN key, deLy will be displayed for 10 seconds and then SCAn for 10 seconds. When the calibration is complete CAL
2 will reappear.
(Continued on next page)

47

Error recovery:
See section 5.6 (page 55) for details. Ensure that the millivolt source is connected correctly
and functioning properly.
The calibration can be exited when hLd1 or the calibration reference number is displayed by
pressing the SCROLL key.
CAL2 QUICK CALIBRATION
This routine will allow the operator to execute a rough calibration on their unit via the keypad
with no other equipment or disturbance to established wiring. It is intended to provide a partial
recovery from a calibration corruption where the necessary equipment indicated may not be
available. It should be noted that this is not intended as a substitution to the main calibration
procedure described earlier and may considerable deter from the accuracy of the instrument.
With CAL2 displayed, press and hold the DOWN ARROW key, then press the SCROLL key.
Release both keys and the instrument will display hLd1. Press and hold the UP ARROW key,
then press the SCROLL key. The display will momentarily blank and then CAL1 will be
displayed. Release both keys and depress the UP ARROW key. CAL will be displayed.

5.4.3 CAL 3 COLD JUNCTION COMPENSATION


This routine determines and saves calibration values which correct for component variations
relating to the cold junction compensation. This calibration must be preceded by CAL 2 the
main calibration, to properly calibrate the instrument. These two calibrations are all that is
needed for proper operation with thermocouple inputs
Test equipment: 1-type J thermocouple
1-mercury thermometer +/-.25 degrees F for equivalent
Allow 30 minutes of warm up time for the instrument with the thermocouple
connected before proceeding with calibration.
Operation:
With CAL 3 displayed press and hold the DOWN key, then press the SCROLL key . The
instrument will display hoLd. Release both keys. Press the DOWN key , deLy will be displayed for up to 10 seconds, then SCAn for 10 seconds. If SCAn remains in the display for
much longer than ten seconds, refer to the note below. The instrument will compute and
display the cold junction temperature to the nearest tenth of a degree C. Compare the display
reading with thermometer and use the UP and DOWN keys to correct the reading. To exit,
press the SCROLL key and CAL 3 will be displayed again.
NOTE: If the display stays in SCAn for more than 10 seconds press the SCROLL key.
CAL3 should be displayed. With CAL3 displayed, while pressing the DOWN key, press the
SCROLL key. The instrument will display hoLd. Press the UP key. The instrument will
begin the calibration procedure with a default value and proceed to dELy as described
above.
Error recovery:
See section 5.6 (page 55) for details on specific errors. The calibration can be exited if hoLd
or the CJC temperature is displayed by pressing the SCROLL Key.

5.4.4 CAL 4 COLD JUNCTION UTILITY


This procedure displays the temperature the cold junction compensator is sensing. No test
equipment is required.
With CAL 4 displayed, press and hold the DOWN key, then press the SCROLL key . Release
both keys and SCAn will be displayed for 10 seconds while the instrument senses the CJC
temperature. The result will then be displayed to a tenth of a degree C. The input terminals
must be shorted. CAL 3 must first be performed. The displayed temperature is not the
ambient temperature. It is the temperature of the CJC . To exit, press the SCROLL key
and CAL 4 will be displayed.

48

5.4.5 CAL 5 RTD INPUT


This procedure determines and saves calibration values relating to RTD inputs. This calibration must be preceded by CAL 2 to properly calibrate the instrument. Both RTD inputs must
be calibrated and both inputs must have valid inputs during the calibration. Decade boxes
with .01% resolution or equivalent are required. Make sure that the Processor board
jumpers JU4, JU6 and JU5, JU7 are in the proper positions. See Appendix A-1 (page
62).
With CAL 5 displayed, press and hold the DOWN key and then press the SCROLL key. The
display will now be PEn1 to indicate that the instrument is set to calibrate the RTD input on
TB 4 . Press the DOWN key to change the display to PEn2 to calibrate the RTD input at TB
5. Choose the input TB to be calibrated and press the SCROLL key, hLd1 will then be
displayed. Connect the decade box at 100 ohm setting across the input terminals 1 and 2 and
a jumper wire from terminal 2 to 3. Press the DOWN key and dELy will be displayed for 10
seconds, then SCAn for ten seconds. When hLd2 is displayed, change the decade box
setting to 277 ohms to the input terminals (do not disturb the wiring) and press the DOWN
key. The display will change to dELy for 10 seconds, followed by SCAn for ten more
seconds. CAL 5 will be displayed after the calibration is completed.
Error recovery:
See section 5.6 (page 55) for details on specific errors.
The calibration can be exited when the instrument displays hLd1 by pressing the SCROLL
key.

5.4.6 CAL 6 COLD JUNCTION UTILITY


This routine provides selection of operating modes for the cold junction compensation used
for thermocouple inputs.
With CAL 6 displayed, press and hold the DOWN key, then press the SCROLL key. The
instrument will display C6 and the number of the mode in effect. Press the UP or DOWN key
to change the mode selection, indicated by the number to the right of the C6. Pressing the
SCROLL key will exit the calibration with the last mode number displayed in effect.
The selected mode will remain in effect if power is interrupted. To return the instrument to
normal operation, CAL 6 must be exited, with mode zero selected, or CAL 1 must be executed to initialize all parameters.
Mode 0: Normal operating mode.
Mode 1: Cold Junction Compensation temperature will be internally fixed at 0 degrees C by
the software to facilitate linearization testing when using an uncompensated millivolt source to
simulate the thermocouple millivolt input signal .

49

5.4.7 CAL 9 PEN CALIBRATION


This procedure is used to calibrate the pen(s). No special test equipment required.
Valid inputs must be connected to TB 4 and TB 5 before performing this calibration. With CAL
9 displayed, push and hold the DOWN key, then press the SCROLL key . Release both keys
and the display will indicate PEn1. For 2 Pen instruments, press the DOWN key to toggle the
display between pen 1 and pen 2. With desired pen displayed, press the SCROLL key.

FOR INSTRUMENTS WITH SOFTWARE REVISION R2.99 AND BELOW:


dELY will be displayed as the pen selected moves toward the center chart hub. PEnL will be
displayed; use the UP and/or DOWN keys to adjust the pen to the low end or 0% of the chart.
When adjusted, press the SCROLL key, SCAn will appear for 10 seconds and the pen
location value will be saved in memory. Next dELY will appear as the pen moves to the outer
edge or, 100% mark on the chart. PEnh will appear, use the UP and/or DOWN keys to adjust
the pen position to the proper 100% of chart position. Press the SCROLL key and SCAn will
be displayed as the pen position value is saved. Then dELy will be displayed as the pen
moves to about mid-scale. CAL9 will be displayed showing that the calibration is complete.
When the calibration is complete, with CAL9 displayed, press the UP key twice to properly
exit the calibration mode. CAL9 can now be repeated on the other pen of a 2 pen instrument
or another routine can be selected.

FOR INSTRUMENT WITH SOFTWARE REVISION R3.00 AND ABOVE:


P.dn will be displayed while the selected pen is moved to it's "HOME" position (toward the
chart hub) with the decimal point flashing to indicate this mode. Once "Pen Home" is found,
the pen will move to the inner ring and PEnL will be displayed. At this point, one of two
adjustments may be made; Pen Arc or Zero and Span.
Pen Arc - To adjust the pen arc, the UP and DOWN keys are pressed simultaneously to draw
an arc for visual reference. The display will show P uP while the selected pen moved upscale
to the top stop position. The pen then moves back downscale to nominally place the pen at
the outer ring (100%) of the chart. The display will now display ArC. The pen arm may be
loosened and the length adjusted to a position and angle to place the pen tip near the outer
ring then re-tighten the pen arm. Press any key and the pen will drive to "HOME", then back
to the inner ring (0%) and PEnL will be displayed.
Zero and Span - To begin a pen zero, with PEnL in the display, the UP or DOWN key may be
pressed to move the pen to the low end of the chart span (0%). When adjusted, press the
SCROLL key and P uP is displayed while the pen is moved to the outer edge (100%) of the
chart, then PEnh is displayed. To adjust pen span, use the UP and DOWN keys to adjust the
pen for the high end (100%) of the chart. When adjusted, press the SCROLL key and P dn
will be displayed for about 5 seconds while the pen is moved to the 50% point on the chart,
then PEn1 is displayed. Calibration may now be performed again to verify the accuracy, or
press the UP key twice to exit back to the CAL mode.

50

Test Mode 5.5


To enter the Test mode, press and release the SCROLL key until tESt appears on the
display then press the DOWN key. tSt1 will be displayed, press and release the SCROLL key
to advance the display to the desired test. Tests 1, 2 and 3 are performed as a unit so the
display will advance directly to tSt4 from tSt1. Listed in Table 5-2, page 52, are the test
procedures available. Test 1, 2 and 3 are performed on start up, periodically during operation,
and on entry into the Test mode. Test 4 is executed on entry into and periodically during the
Operation mode. These tests can be used as a trouble shooting aid.

TEST MODE FLOW CHART


tESt

tSt1

tSt4

tSt5

tSt6

tSt7

KEY
Actual Display

tSt8

ON
OFF

On/Off Display Use arrow keys


to turn on or off

tSt9
Scroll Key

tStA

Numeric Display Use arrow keys


to change value
Up Arrow Key

Down Arrow

51

TABLE 5-2 TEST PROCEDURES AND DESCRIPTION


Test
Test 1

Description
Microprocessor internal RAM test. Used to check the processor RAM to
make sure it is functioning correctly.

Test 2

External RAM test, used to test the RAM chip for proper function.

Test 3

EPROM checksum test, used to check that the EPROM program is correct.

Test 4

External RAM checksum test; instrument test and identifies how many
times Errors16 or 17 have occurred.

Test 5

Verifies that all keys are functional and all LEDs are working.

Test 6

Used to verify that all relays and solid state relay driver outputs are working
correctly.

Test 7

This procedure will allow operator to adjust the current output value to
check the output and to test the operation of the external device.

Test 8

Pen and chart motor operational check.

Test 9

Verifies that the auxiliary inputs are functioning properly.

Test A

Communications Hardware Test.

5.5.1 TEST 1 INTERNAL RAM TEST


Tests the Random Access Memory internal to the microprocessor. No special test equipment
is required.
With tSt1 displayed, press and hold the DOWN key, then press the SCROLL key. tSt1 will be
displayed momentarily while the test is in progress. Upon successful completion, the instrument will proceed to Test 2.

5.5.2 TEST 2 EXTERNAL RAM TEST


Tests the battery backed-up RAM external to the microcomputer. No special test equipment is
required.
After completion of Test 1, tSt2 will be displayed momentarily while the test is in progress.
Upon successful completion, the instrument will proceed to Test 3.

5.5.3 TEST 3 PROGRAM EPROM TEST


This is a checksum test to verify data integrity of the stored program. No special test equipment is required.
After completion of Test 2, tSt3 will be displayed momentarily while the test is in progress.
Upon successful completion of Test 3 tst1 will be displayed.

5.5.4 TEST 4 EXTERNAL RAM CHECKSUM TEST


This is a checksum test to verify the integrity of data stored in RAM and indicate the number
of times the instrument has had an Error 16 or 17. The unit may have automatically recovered
from these errors. No special test equipment is required.
With tst4 displayed, press and hold the DOWN key then press the SCROLL key. The display
will blank momentarily, then momentarily display two numbers, and then tst4 will be displayed. These numbers indicate the number of times Error 16 and 17 have occurred respectively. Test 4 can be executed again, or another test may be selected.

52

5.5.5 TEST 5 KEYPAD/DISPLAY TEST


This test allows the operator to verify that the keys work and that all display elements can be
lighted. No special test equipment is required.
With tSt5 displayed, press and hold the DOWN key, then press the SCROLL key and then
release both keys. The display will go blank. The following code will be displayed while the
corresponding key is pressed:
Key
SCROLL
UP
DOWN
AUTO/MAN (Pen 1)
AUTO/MAN (Pen 2)
UP and DOWN
SCROLL and UP

Display
SCrL
uAro
dAro
Autu
AutL
(All LEDs and segments lit)
(exit)

To exit, press the SCROLL and UP keys simultaneously, tSt5 will be displayed.

5.5.6 TEST 6 RELAY/ SOLID STATE RELAY DRIVER OUTPUT TEST


Allows the operator to verify that the Relay and /or the Solid State Relay Driver output(s) are
working. A volt/ohm meter will be required to test the output.
With tSt6 displayed, press and hold the DOWN key, then press the SCROLL key. oFF will be
displayed. For SPST Relay outputs, connect the meter across the relay output in the ohm
scale. For SPDT Relay outputs, connect the meter across the N.O. and COM output in the
ohm scale. The meter should read continuity with the relay On and infinity when the relay is
Off. For SSR Driver outputs, connect the meter across the output in the Volt DC scale. The
meter should read 5 VDC when the SSR driver is On and 0 VDC when the driver is Off. Press
and release the DOWN key to advance through the following sequence:

DISPLAY
rLYA
rLYb
rLYC
rLYd
rLYE
rLYF
rLYg
rLYH
oFF

RELAY ON
SPST
A
B
C
D
E
F
G
H
None

RELAY ON
SPDT
A
B
C
D
None
None
G
H
None

To exit, press the SCROLL key and tSt6 will be displayed. The existence of Relay and
Solid State Relay Driver output(s) is dependent upon the hardware configuration.

5.5.7 TEST 7 CURRENT OUTPUT TEST


This test allows the operator to verify that the current output(s) are functioning properly or will
allow the selection of an output value for testing of associated equipment. A milliamp meter is
required for testing.
With tSt7 displayed press and hold the DOWN key, then press the SCROLL key. The display
will indicate CurA, for the first current output. By pressing the DOWN key, the instrument will
advance through the selection sequence of Curb, CurC, Curd, and then back to CurA.
Choose the desired output to be tested and connect the milliamp meter across the output
terminals being tested. Be sure to observe the proper polarity when connecting the meter.
Terminal 1 is positive and terminal 2 is negative. Press the SCROLL key and the display will
indicate 4 milliamps. Use the UP and/or DOWN key to increase or decrease the current
output in 1 mADC steps from 0 to 20 mADC. (Continued on next page)

53

The current output reading should be 0.1 mADC at any output value. A 5 % of span
adjustment for the current output(s) is provided by using the potentiometer adjacent to the
current output on the Current Output board. See Appendix A-4 (page 65). To exit the test,
press the SCROLL key and tSt7 will be displayed. The existence of a mADC current
output is dependent upon the hardware configuration.

5.5.8 TEST 8 PEN/CHART MOTOR TEST


This test allows the operator to verify that pen and chart motors are functioning properly. No
special test equipment is required.
With tSt8 displayed press and hold the DOWN key, then press the SCROLL key. The display
will show ALL while the test is in progress. This test functions automatically. The chart speed
will be at maximum, 72 seconds per revolution. Starting at the current pen position, pen 1 will
move (sweep) upscale for about 5 seconds, then downscale for about 5 seconds. Pen 2 (if
provided) will sweep in the opposite direction. The pens will continue to cycle until the test is
exited. To exit, press the SCROLL key. The display will show tSt8.

5.5.9 TEST 9 AUXILIARY INPUT TEST


This test allows the operator to verify that the auxiliary input(s), if specified, pen position
feedback input(s) are functioning properly.
Auxiliary inputs are the remote setpoint and position proportioning options. With tSt9 displayed, press and hold the DOWN key, then press the SCROLL key. The display will show
Ai1, Auxiliary Input 1. By pressing the DOWN key, the instrument will sequence through the
selections for testing: PF1, Ai2, PF2, then back to Ai1 (PF=Pen Feedback). With the desired
input selected, press the SCROLL key. The corresponding value will be displayed. For
software revision R2.99 and below only, the pen position feedback input voltage will be
displayed to the nearest tenth of a millivolt. Manually move the pen up and down scale and
verify that the displayed reading changes from about 0 to 50 millivolts. For software revision
R3.00 and above, the pen position feedback input voltages are disabled and will display a
fixed value of zero. To terminate a particular test, press the SCROLL key. The display will
show tSt9.

5.5.10 TEST A COMMUNICATIONS HARDWARE TEST


(COMMUNICATIONS OPTIONAL)
This test allows the operator to verify that the communications hardware is functioning
properly.
With tStA displayed, press and hold the DOWN key then press the SCROLL key. The display
will indicate SEnd. Press the DOWN key to toggle the display between SEnd and rEC . With
the desired function selected, press the SCROLL key. In the SEnd (send or transmit) mode,
the instrument will repeat the following sequence. First the transmitter will output a logic 1 on
the line for one second. Next the transmitter will change the logic level to 0 for one second.
Then the transmitter will disable for one second. In the rEC (receive) mode, the transmitter is
continuously disabled. In either mode, the instrument will monitor the line and display rEC1
when a logic 1 is on the line or rEC0 when a logic 0 is on the line . In the SEnd mode, the
instrument will display rEC when the transmitter is disabled. To perform an internal test and
verify the basic operation of the hardware, place the instrument in the Send mode and verify
that the display cycles through rEC1, rEC0, and rEC. To verify that the transmitter functions
properly, two LEDs, each with a current limiting resistor, can be connected with opposite
polarity observed to the TB 2 terminals 1 and 2. The following three states should be observed: one LED On, then the other LED On, then both Off. Alternately, a load resistor can be
placed on the terminals, and observe that the voltage generated across the load resistor is as
follows: >+3 VDC, then >-3 VDC, and then 0 VDC.

54

Another method, to test the communications hardware, would be to connect one or more
instruments in the Receive mode to an instrument in the Send mode. All of the instruments in
the Receive mode should have their displays alternating in sync with the instrument in the
Send mode. When the sending instrument displays rEC, the receiving instruments should
display rEC1. To terminate the test, press the SCROLL key for one second. Upon exit, tStA
will be displayed. The existence of the communications hardware is dependent on the
hardware configuration.

Trouble-shooting and Diagnostics 5.6


The Trouble-shooting Guidelines Section consists of two columns. The first column is a list of
some possible instrument conditions. The second column is a list of steps that should improve
the condition. The steps should be performed in order until the condition improves or all the
steps have been completed. If the instrument condition has not improved, contact the nearest
representative or the factory for assistance.
Trouble-shooting should be performed by qualified personnel using the proper equipment and
following all safety precautions. Whenever possible the trouble-shooting should be accomplished with the electrical power disconnected. The instrument contains static sensitive
components so care should be taken to observe anti-static procedures.

CONDITION

CORRECTION STEPS

Display(s) is/are blank

1. Verify that the correct instrument power, as indicated


on the wiring label on the platen, is supplied to TB 1
terminals 1 & 2. Check the position of the power select
switch, on 230 VAC models, correctly indicates the
power that is connected to the instrument. If the switch
does not indicate the correct voltage, reposition as
necessary. If the voltage is not correct, check the
power source.
2. Turn off the instrument power. Wait about 5 seconds
then turn the power on again.
3. Turn off the instrument power, open the cover, loosen
the platen hold down screw, and swing the platen out
of the way. Inspect the instrument for poor
connections.
a. The white ribbon cables that connect the
Processor board (Appendix A-1, page 62) to
the platen must be properly aligned and
seated in the sockets.
b. The display board(s) white ribbon cable(s)
pins should be properly aligned and seated in
the sockets on the platen board.
c. Inspect the EPROM (U7), RAM (U8) and
microprocessor chips (U5)to see that the legs
are properly seated in their sockets on the
Processor Board (page 62).
d. Close the platen and tighten the hold down
screw. Close the cover and turn on the power
to see if the display(s) will now light.
4. Turn off the instrument power. Press and hold the UP
and DOWN keys. Turn on the power. Hold the keys
pressed for about 10 seconds. If the display(s) light
the model number, Program and Tune mode
parameters will need to be re-entered (pages 28 thru
35 or Software Ref. Sheet, page 72, if already filled
out).

55

56

Model Number Displayed


during power up is
incorrect

1. Turn off the instrument power, wait 5 seconds then


re-apply the power. Verify that the number displayed
during the power up sequence is the same as
indicated on the label affixed to the platen. If the
number displayed is incorrect, perform the following
steps:
a. Turn off the power to the instrument. Press
and hold the UP and DOWN keys. Turn on
the power and keep the keys pressed until
the model number displayed resets to 72X00000-0X21 where the digits X are determined
by the firmware installed. Release the keys
and turn off the power.
b. To enter the correct model number, press
and hold the SCROLL and DOWN keys and
turn on the instrument power. 72X0 should
be displayed. Wait about 5 seconds and
release the keys. The display should stay
72X0. Use the UP/DOWN keys as necessary
to change the displayed number to match
the first 4 digits of the model number as
indicated on the label on the platen. After
adjusting the first 4 digits to the proper
values, press the SCROLL key and the
display will change to 0000. Use the UP/
DOWN keys to set the next 4 digits of the
model number to the correct values. Press
the SCROLL key and the display will be
0X21. Use the UP/DOWN keys as necessary
to adjust the last 4 digits of the number.
Press the SCROLL key and the power up
sequence will complete. The Program and
Tune mode parameters will need to be
re-entered (pages 28 thru 35 or Software Ref.
Sheet, page 72, if already filled out).

Relay/SSR Driver
Malfunction

1. Verify that the Program and Tune mode


parameters are correctly set (pages 28 thru 35 or
Software Ref. Sheet, page 72, if already filled out).
2. Turn off the power to the instrument. Wait about 5
seconds and turn the power on again. Confirm that
the model number displayed during the power up
sequence indicates that the output(s) is/are present in
the instrument. See Appendix C (page 68) for the
model number explanation/decoding. This number
should match the number on the label affixed to the
platen.
3. Turn off the power to the instrument. Open the cover.
Loosen the platen hold down screw and swing the
platen open. Inspect the instrument Relay/SSR Driver
board (See Figure 2-4, page 14) for the presence of
the output device(s). A relay output will appear to be a
cube. The SSR Driver will appear as a resistor and a
jumper wire. The output will not work if the hardware is
not present. Inspect that the output terminal
connections are present and firmly attached.
4. Check the output(s) operation by performing Test 6 as
described in the Test section (page 53). If the
output(s) function in the Test mode re-examine the
Program and Tune mode parameters settings
(pages 28 thru 35 or Software Ref. Sheet, page 72, if
already filled out).

5. If the output appears not to turn off remove the power


to the instrument. Open the cover and loosen the
platen hold down screw. Swing the platen open. Clip
the resistor located on the Relay Board adjacent to
the output(s) that seem to stay on (See Appendix A-2,
page 63). A .01 microfarrad, 1 KV capacitor should
be connected from the terminal listed below, for the
output where the resistor indicated was removed, to
the AC ground.
Relay A
R1
TB 6
Terminal 1
Relay B
R2
TB 6
Terminal 3
Relay C
R3
TB 7
Terminal 1
Relay D
R4
TB 7
Terminal 3
Relay E
R5
TB 8
Terminal 1
Relay F
R6
TB 8
Terminal 3
Close the platen and tighten the hold down screw. Close
the cover and turn the power on to the instrument.
Check the operation of the output(s).
mADC Output(s)
Malfunction

1. Verify that the Program mode parameters are


correctly set (page 72).
2. Turn Off the power to the instrument. Wait about 5
seconds and turn the power on again. Confirm that
the model number displayed during the power up
sequence indicates that the output(s) is/are present in
the instrument. See Appendix C ( page 68) for the
model number explanation/decoding. This number
should match the number on the label affixed to the
platen.
3. Turn off the power to the instrument. Open the
cover. Loosen the platen hold down screw and swing
the platen open. Inspect the instrument Current
Output board (See Figure 2-6, page 15) for the
presence of the output device(s). The output will not
work if the hardware is not present.
Inspect that the output terminal connections are
present and firmly attached. Close the platen and
tighten the hold down screw. Close the cover and turn
on the power.
4. Refer to the Test section and carry out the procedure
for the Current Output(s) Test 7 (page 53). If the
current output operates properly in the Test mode
re-check the Program mode parameters (page 28 or
Software Ref. Sheet, page 72, if already filled out).

Pen(s) do not operate

1. Verify that the Program mode parameters are properly


set (page 28 or Software Ref. Sheet, page 72, if
already filled out)
2. If the process value in the display exceeds the chart
upper or the chart lower values selected in the
Program mode, the pen will appear stuck at the chart
upper or lower edge respectively. Re-configure values
as needed by the application (May require a new
chart).
3. Perform Test 8 as described in the Test section of the
manual (page 54). If the pen(s) operate in Test 8,
perform the pen calibration, Cal 9, as described in the
Calibration section of the manual (page 50). Return
the instrument to the oPEr and check the operation of
the pen(s).
(Continued on next page)

57

4. For software revision R2.99 and below, perform Test


9 as described in the Test Section of the manual
(page 54). If the pen feedback voltage does not vary,
check the pen Potentiometer Segment board for
proper ribbon cable connection to the Processor
board (Appendix A-1, page 62) and that the pen
position fingers are making contact with Potentiometer
Segment board.
5. For software revision R2.99 and below, inspect to see
that the Potentiometer Segment of the pen feed back
is clean. Use a non-residue type cleaner that does
not affect the plastic to clean the segment if
necessary.
6. Verify the instrument is not in Change Chart function.

ERROR CODE DISPLAYED

58

SnSr - Sensor Break or


Over Range

1. Inspect the sensor for proper operation and


connection to the instrument. Acceptable sensor
ranges for the instrument are listed in the
Specifications section of Appendix D (page 69).
2. Verify that the Program mode input selection matches
the sensor input connected (page 28 or Software Ref.
Sheet, page 72, if already filled out).
3. Check that the input conditioning jumpers on the
Processor board (Appendix A-1, page 62) are in the
proper position for the sensor input. Check that the
jumpers are in the proper position for the Terminal
Board where the sensor is connected.
4. Perform the calibration procedure(s), as described in
the Calibration section (page 46), for the sensor input
type.

FbEr - Slidewire Feedback


Error

1. Inspect the Slidewire Feedback connections at


terminals 8, 7, and 5. Be sure that the connections
are the same as shown in the position proportioning
illustration (page 19).
2. Measure the resistance of the slidewire segment. The
minimum resistance must be 135 ohm, the maximum
10K ohms.
3. Perform the Auxiliary Input Test, Test 9 as described
in the Test section (page 54). The voltage indicated
should be between 0 and 5 VDC .

Hi - Input more than 10%


Over Span

1. Perform the steps listed for the SnSr Error Condition.


(above)

Lo - Input more than 10%


Under Span

1. Perform the steps listed for the SnSr Error Condition.


(above)

o - display overranged
(the broken 6
appears on the left
segment of the display)

1. If this error code is displayed as a Program or Alarm


Set mode parameter perform the CAL 1 procedure as
described in the Calibration section of the manual
(page 46).
2. If this error code appears as part of the model number
during the power up sequence, follow the steps listed
for the "Model Number is not correct" condition
(page 56).

3. If this error appears, check the Program mode


parameter dPos, if not 0, change to 0 and see if the
error clears.
Er 1 - Microprocessor RAM
Failure

1. Turn off the power to the instrument. Wait 5 seconds,


and turn the power on.
2. Turn off the power to the instrument. Open the
cover, and loosen the platen hold down screw. Swing
open the platen and inspect that the microprocessor
chip is properly seated in the socket located on
the Processor board (Appendix A-1, page 62). Close
the platen and tighten the screw. Close the cover and
turn on the power.

Er 2 - External RAM
Failure

1. Turn off the power to the instrument. Wait 5 seconds,


and turn the power on.

Er 3 - EPROM Checksum
Failure

1. Perform the steps listed for Er 1 except that


the EPROM (U7) on the Processor board should be
inspected.

Er 4 - RTD Mismatch Error

1. Check the connections to the instrument for the RTD


Input Calibration (CAL5) as described in the
Calibration section (page 49). Repeat the RTD Input
Calibration.

Er 5 - No Zero Crossings
Detected

1. Turn off the power to the instrument. Wait 5 seconds,


and turn the power on.
2. Connect the instrument to another AC power source.

Er 6 - AC line below 43 HZ

1. Turn off the power to the instrument. Wait 5 seconds,


and turn the power on.
2. Connect the instrument to another AC power source.

Er 7 - AC line over 64 HZ

1. Turn off the power to the instrument. Wait 5 seconds,


and turn the power on.
2. Connect the instrument to another AC power source.

Er 8 - Cal 2 Volt Input


Error

1. Check that 50 mVDC is properly connected to the


instrument and is within the tolerance limits as
indicated in the CAL2 procedure of the Calibration
section (page 47).
2. Turn off the power to the instrument and open the
cover. Loosen the platen hold down screw and swing
the platen open. Inspect the Processor board
(Appendix A-1, page 62) to insure that the input
conditioning jumper JU4 is in the non-volt position.
The jumper must be in the non-volt position to perform
the CAL 2 procedure properly. Close the platen
and tighten the hold down screw. Close the cover and
turn on the power to the instrument.
3. Perform the CAL2 procedure as described in the
Calibration section (page 47).

59

60

Er 9 - ADC Reference
Number Error

1. Perform the CAL2 procedure as described in the


Calibration section (page 47).

Er10 - ADC Reference


Voltage Error

1. Perform the CAL2 procedure as described in the


Calibration section (page 47).

Er11 - Cold Junction


Compensation Error

1. Perform the CAL3 procedure as described in the


Calibration section (page 48).

Er12 - CAL2 Voltage Error

1. Check that 50 mVDC is properly connected to the


instrument and is within the tolerance limits as
indicated in the CAL2 procedure of the Calibration
section (page 47).
2. Turn off the power to the instrument and open the
cover. Loosen the platen hold down screw and swing
the platen open. Inspect the Processor board
(Appendix A-1, page 62) to insure that the input
conditioning jumper JU4 is in the non-volt position.
3. Perform the CAL2 procedure as described in the
Calibration section (page 47).

Er13 - RTD CAL5 Input


Error

1. Check that resistance device is of the correct value


and properly connected to the instrument and is
within the tolerance limits as indicated in the CAL5
procedure of the Calibration section (page 49).
2. Turn off the power to the instrument and open the
cover. Loosen the platen hold down screw and swing
the platen open. Inspect the Processor board
(Appendix A-1, page 62) to insure that the input
conditioning jumpers are in the correct position for the
RTD input for the Terminal Board being calibrated.
For TB 4, JU4 should be in the non-volt position and
JU6 in the RTD position. For TB 5, JU5 should be in
the non-volt position and JU7 in the RTD position.
3. Perform the CAL5 procedure as described in the
Calibration section (page 49).

Er14 - Cold Junction


Compensation Error

1. Perform the CAL3 procedure as described in the


Calibration section (page 48).

Er15 - Ground Reference


Tolerance Error

1. Perform the CAL2 procedure as described in the


Calibration section (page 47).

Er16 - Program/ASEt Mode


Checksum Error

1. Record all Program and Tune mode parameters.


Perform CAL 1 procedure as described in the
Calibration section (page 47). Re-enter the
Program and ASEt mode parameters.

Er17 - Calibration
Checksum Error

1. Perform the calibration procedures that are


needed for the input sensors that will be used (page
46).

Er21 - Pen Feedback


Error

1. Perform the steps listed for pens not moving.

Er36 - Incorrect Crystal


For Digital Comm.

1. Turn off the power to the instrument, wait 5 seconds,


then turn the power on.

Er37 - Incorrect Micro.


For Digital Comm.

1. Turn off the power to the instrument wait 5 seconds,


then turn the power on.

Er38 - Incorrect RAM


for profiler

1. Turn off the power to the instrument, wait 5 seconds,


then turn the power on.
2. Re-configure for non-profiler.

Momentary ER 70 Controller unable to respond


within 250 milliseconds

1. May occur when incrementing or decrementing a


value. Error clears itself.

Momentary ER 71 Byte received before the


response was transmitted

1. Computer program must wait longer for a response


from the instrument.

Momentary Er 72 Incorrect Block Check


character was received

1. Data received not valid, possible corruption on the


comm line. Possible noise problems. Check baud
rates, instrument addresses, line connections, and
termination.

Momentary Er 73 Byte received with incorrect


parity.

1. Check baud rate.


2. Possible noise problems. Check instrument
addresses, line connections, and termination.

61

Appendix A
Board Layouts
FIGURE A-1 - PROCESSOR BOARD

Top
SWI for Rev. Y and above

UNLOCKED

230

JU1
ENABLE MODE

SWI for Rev. X and below

TB1

LOCKED

230

JU3
EPROM SIZE
32K

230/115 VAC
SWITCH 230 VAC
MODEL ONLY

64K

U5

JU3

U7

JU4 PEN 1 INPUT


T/C,mV, RTD
VOLT/mA

JU1
JU5 PEN 2 INPUT
(REVERSE OF JU4)

T/C,mV, RTD

Battery
VOLT/mA

JU6
JU4

JU5

TB2
JU6 /JU7
RTD
INPUT

TB3
NONRTD

62

RTD

TB4

TB5

JU7

FIGURE A-2 - SPST RELAY/SSR DRIVER OUTPUT BOARD

TB6

TS1 R1

TB7

TS2

R2

TS3

R3

TB8

TS4

R4

TS5 R5

TS6 R6

C1

C2

C3

C4

C5

C6

K1

K2

K3

K4

K5

K6

(rlyA)

(rlyB)

(rlyC)

(rlyD)

(rlyE)

(rlyF)

P7

TB9
(rlyG)

If the relay is connected to a


high impedance AC device,
the snubber network used to
protect the relay contact may
cause the output to appear
to be activated when the
relay is off. To cure the
problem, cut the snubber
resistor for the output that is
being affected.

Resistor
R1
R2
R3
R4
R5
R6

(rlyH)

Relay
Relay A
Relay B
Relay C
Relay D
Relay E
Relay F

63

FIGURE A-3 - SPDT RELAY/SSR DRIVER OUTPUT BOARD

TB6

TS1 R1

TB7

TS2

C1

R2

C2

TS3

R3

TB8

TS4

C3

R4

C4

K1

K2

(rlyA)

(rlyB)

TS5

R5

TS6

R6

C5

C6

K3

K4

(rlyC)

(rlyD)

P7

TB9
(rlyG)

If the relay is connected to a


high impedance AC device,
the snubber network used to
protect the relay contact may
cause the output to appear
to be activated when the
relay is off. To cure the
problem, cut the snubber
resistor for the output that is
being affected.

64

Resistor
R1, R2
R3, R4
R5
R6

Relay
Relay A
Relay B
Relay C
Relay D

(rlyH)

FIGURE A-4 - CURRENT OUTPUT BOARD

R50

R51

R52

R53

U2

U4

U6

U8

U3

U5

U7

U9

U1

TB10

TB11

TB12

TB13

If this option board was ordered, you will find it located in the lower right hand corner of the
instrument.

65

Appendix B
Glossary
Automatic Reset (Integral)
This parameter is used so that the instrument will compensate for process variable deviations
from setpoint that occur when the process load characteristics change. Instructions for
determining the automatic reset settings are given in Table 3-2 (Page 34). Factory default
is.0.0. Display code ArSt.
Automatic Transfer
This feature, if configured, allows manual control of the process until setpoint is reached, at
which point the controller automatically transfers from manual to automatic control. Factory
default value is 0 = no auto transfer. Display code AtFr.
Bumpless Transfer
This feature prevents step changes in proportional outputs when changing from automatic to
manual control only.
Cycle Time
This Tune mode parameter is used to select the on/off cycle time for time proportioning
outputs (Ct1 for Output 1 and/or Ct2 for Output 2).
When usng the Position Proportioning option, Ct1 must be selected for the stroke time of the
motor.
Display Filter Factor
This parameter is adjustable from 1 to 20 which represents the number of scans per second
of the process variable that are averaged together before updating the displayed and recorded value. The factory default value is 1 = no filtering. Display code dFF.
Engineering Units Upper and Engineering Units Lower
These Program mode parameters are used with volt, millivolt, and milliamp inputs. The
Engineering Units Upper Euu should be selected as the value to be displayed when the input
is at maximum. The Engineering Units Lower EuL should be selected as the value to be
displayed when the input is at minimum.
First Output Position
This parameter is adjustable from -1000 to 1000 units and represents a shift or offset of the
on-off actuation points or proportional band for the first output relative to the normal position.
For example, a negative value could be used to offset an expected overshoot. First Output
Position also shifts the proportional band with respect to the process value range outside of
which integral action is inhibited. Factory default is 0. Display code FoP.
Hysteresis
This parameter is adjustable from 0 to 300 units representing the width of the band (half
above and half below setpoint). Used with ON/OFF or Alarm outputs to reduce cycling. For
instance, with a value of 4 and a setpoint of 70 the output will turn ON when the process
variable drops to 68 and stay ON until 72 is reached, then turn OFF the output. Factory
default = 3. Display code HyAo for Alarm outputs. Display code HyCo for ON/OFF Control
outputs.
Input Correction
This parameter is adjustable from -300 to 300 units and is used as a method to compensate
for a linear sensor error. Factory default is 0 = no correction. Display code iCi1, iCi2.

66

Manual Reset
This parameter is adjustable from -1500 to 1500 units representing a manual shift of proportional band(s) relative to the normal position which is an even strattle of the setpoint. Manual
reset is intended to be used when automatic reset is not used to allow compensation for
deviations from setpoint which remain after the process has stabilized. Factory default is 0.
Increasing the value increases the process variable, i.e. if the process variable stabilizes too
low, increase the manual set. Integral action, and conversely reset-windup inhibit apply over
the same process value range regardless of the manual reset value. Display code rSEt.

Pen Action on Power Up


This parameter specifies whether the pen, on a power-up will drive to the "Home Position"
(center of chart), then return to its correct postion. This is done as a cal check. Settings are
0=go to "home" and 1=remain in last position prior to power down. Default is 0.
Platen
The flat surface in the instrument upon which the chart rotates.
Position Proportioning Sensitivity
A percentage of the first output proportional band width (Pb1).
Process Filter Factor
This parameter is adjustable from 1 to 20 which represents the number of scans per second
of the process variable that are averaged together before updating the process value used for
control purposes. The factory default value is 1 = no filtering. Display code PFF.
Process Retransmission Output
Allows re-transmission of the process variable. Factory default is 0 = not selected. Display
code Pout. If selected, must be assigned to a current output and scaled using Process Output
upper and lower values.
Process Output Upper and Lower Values
(Used in conjunction with process retransmission output)
These parameters specify the process value range over which the assigned current output will
vary in a linear manner from 100% to 0%. If the process value is greater than Pou the output
will be 100%. If the process value is less than PoL the output will be 0%. Factory default
values are 2000 for the upper value and 0 for the lower value. Display codes Pou (upper) and
PoL (lower).
Process Rounding
This parameter is adjustable from 0 to 100 units and is used to round the process value to the
nearest value specified. This is for display only and does not affect the recorded value or
control action. Intended for use where the engineering units span is large, to reduce display
fluctuation. Factory default is 0 = no rounding. Display code Prnd. (e.g. Prnd = 3, Process
Value = -6, -3, 0, 3, 6, 9....)
Proportional Band (PB)
This parameter is adjustable from 1 to 3000 units (not Percent of span) and represents the
process value range where the proportional output is at a percentage of the full output.
Instructions for determining Pb are given in Section 4.3 (page 42) . Factory default is 100
units. Display code Pb1 and Pb2.
Rate (Derivative)
This parameter is adjustable from 0.0 to 10.0 minutes and specifies how the control action
responds to the rate of change in the process variable. For example, if the process variable is
rising rapidly to setpoint, power is turned off sooner than it would be if the rise were slow. In
effect, derivative action anticipates lags within the system and shifts the proportioning band by
an amount determined by the rate of change of the input sensor.
Magnitude of the shift is determined by a derivative time constant. If the time constant is, say,
.1 minute (6 seconds), for every unit per second rate of change of the process variable at the
sensor, the proportiong band is moved 7 units in the direction that helps control. Likewise, if
the time constant is 1 minute (60 seconds), for every unit per second rate of change of the
process variable at the sensor, the proportioning band is moved 60 units in the direction that
helps control. Factory default is 0.0 Display code rAtE.
Second Output Position (SoP)
This parameter is adjustable from -1000 to 1000 units and represents a shift or offset of the
on-off actuation points or proportional band for the second output relative to the normal
position. A positive value creates a gap where no control outputs are on, a negative value
creates an overlap of control outputs (if the first output position is at the normal position).
Second Output Position also shifts the proportional band with respect to the process value
range outside of which integral action is highlighted (reset-windup inhibit). Factory default is 0.
Display code SoP.

67

Appendix C Order Matrix


7
Pen 1

Option Suffix

2 Recording Controller

00 None
N3 - NEMA3

Pen 2
0 None
1 Recorder Only
2 Recorder Controller

Voltage

*Relay (SPST) Outputs

CSA Approved
4 115VAC Input
5 115/230VAC Input

0
1
2
4
6
7
8
9

None
One
Two
Four
Six
One SPDT
Two SPDT
Two SPDT and Two SPST

*SSR Driver Outputs


0
1
2
4
6
8

None
One
Two
Four
Six
Eight

4 to 20mA Outputs
0
1
2
3
4

None
One
Two
Three
Four

1 115VAC Input
2 115/230VAC Input

Enclosure Options
2 Standard Cover
(Plastic Windows)
4 Door Lock**
6 Sealed Conduit Conn.
7 Combination of 4& 6**

Communications
0 None
2 RS-485 Total Access

Pen 2 Auxiliary Input


0 None
1 Position Proportioning
2 Remote Setpoint

Pen 1 Auxiliary Input


0 None
1 Position Proportioning
2 Remote Setpoint

Transmitter Power Supply


0 None
1 24VDC Regulator/Isolated

*Total quantity of SPST Relays and SSR Drivers must be less than or equal to (8) eight.
**This option comes with a structural foam cover.
N3 - NEMA3 Equivalent Spray Resistant Enclosure

68

Appendix D Product Specifications


Measurement Error Limit

Type J,K,T,E,N,C T/Cs and RTD +/-0.25% of reading


plus 1 degree @ 25 degrees C
Type R,S, B T/Cs +/-0.25% of span @ 25 degrees C
mA, mV and VDC +/-0.25% of scaled span plus 1 Whole
Digit @ 25 degrees C

Ambient Temperature Error

0.01% of span per degree C deviation from 25 degrees C

Scan Rate

1 scan/second

Display Decimal Positions

One, two or three decimal places (0.1 or 1 degrees for


T/C or RTD)

Noise Rejection

Normal mode, 85dB minimum at 60 Hz or greater.


Common mode, 90dB minimum, 115 VAC maximum.

Line Voltage

115/230VAC +/-10% 50/60 Hz

Power Consumption

25VA maximum

Operating Temperature

32 degrees to 131 degrees F


0 degrees to 55 degrees C (ambient)

Storage Temperature

-40 degrees to 149 degrees F


-40 degrees to 65 degrees C

Humidity

0 to 90% RH, noncondensing

Dimensions

13.19H x 15.13"W x 3.63" Deep

Weight

20 pounds maximum

Sensor Fault Detection

Displays SnSr for sensor or transmitter break. Outputs go


off. PV Out to 100%. Fault detection is not functional for
0-5V or 0-20mA inputs

Agency Approvals

UL Spec. 1092 File# E67237


CSA Spec. C22-2 File# LR39885

Transmitter Power Supply

Provides up to 40mA of current at 24 VDC

Warranty

3 years, see back cover for details.

69

Input Specifications
THERMOCOUPLE
TYPE

RANGE

TYPE

RANGE

0 to 760C
0 to 1400F

0 to 750C
0 to 1400F

0 to 1360C
0 to 2500F

200 to 1800C
400 to 3300F

-220 to 400C
-330 to 750F

0 to 1300C
0 to 2370F

200 to 1650C
400 to 3000F

200 to 2300C
390 to 4170F

200 to 1650C
400 to 3000F

MILLIAMPS

MILLIVOLTS

RTD

4-20 mADC
(with resistor)

0 TO 25 mV
0 to 50 mV
10 to 50 mV

100 OHM
(.00385 OHMS/OHM/C)
-140 to 400C

VOLTS

REMOTE SETPOINT

0 to 5 VDC
1 to 5 VDC

0 to 5 VDC
1 to 5 VDC

CONTROL ADJUSTMENTS

70

Proportional Band

1 to 3000 units

Manual Reset

-1500 to 1500 units

Auto Reset (Integral)

0.0 to 100.0 repeats per minute

Rate (Derivative)

0.0 to 10.0 minutes

Cycle Time

1 to 240 seconds

Position Proportioning
Sensitivity

0.0 to 50.0%

On/Off Hysteresis
(width of hysteresis band)

0 to 300 units

First Output Position

-1000 to 1000 units

Second Output Position

-1000 to 1000 units

Automatic
Transfer Function

User selectable to transfer from manual to


automatic control when setpoint is reached
Can be disabled.

Auto/Manual

Bumpless transfer from automatic to manual.

Manual Output

0 to 100%

ALARM ADJUSTMENTS
Process Alarm
Deviation Alarm
Deviation Band Alarm
Hysteresis

-9999 to 9999 units


-3000 to 3000 units
1 to 3000 units
0 to 300 units

CONTROL OUTPUTS
Relay

SPST

SSR Driver

mADC Current

115 VAC: 5.0A Resistive, 1/8HP or 250VA


230 VAC: 2.5A Resistive, 1/8HP or 250VA
Open collector output
Short circuit protected @ 100mA maximum
Provides 4VDC at 20mA or 3VDC at 40mA
4-20 or 0-20 mADC into 650 ohms maximum load

DISPLAY
Digital Display
Status Indicators

Two possible; one per installed pen. Red LEDs 0.56" high.
LED indicators for Output 1, Output 2, Manual Operation, Alarm,
Setpoint, minus sign and process value units (C, F, or E).

RECORD
Chart
Chart Range
Chart Drive
Chart Rotation
Pen Type
Pen Color
Pen Response Time
Accuracy
Chart Rotation Accuracy

10 in circular chart; 100 charts furnished with each instrument if


standard range
-9999 to 9999 / units
DC stepper motor
User configurable from 0.1 to 999.9 hours per revolution
Disposable Fiber-tip
Pen 1-Red, Pen 2-Green
< 9 seconds over chart span
1.0% of chart span max. error from displayed value
0.5% of Chart Rotation Time

DIGITAL COMMUNICATIONS
Type
Character Format
Protocol
Configuration
Bit Rate
Address

RS-422/485 serial communications port. Half-duplex bi-directional


communications.
ASCII
Per ANSI X3.28 subcategories 2.5 & A4
User configurable to Monitor (read only) or Normal (read and write)
User configurable to 300, 600, 1200, 2400, 4800, or 9600 bits per
second
User configurable for each pen; 0 to 99

71

Appendix E
Software Reference/Record Sheet
Pen 1

inPS
iCor
out1
o1uL
o1LL
out2
o2uL
o2LL
AL1
AL2
diSP
dPoS
Euu
EuL
HyCo
HyAo
rSP
rSPu
rSPL
SPuL
SPLL
AtFr
Prnd
dFF
PFF
Pout
Pou
PoL
Cru
CrL
P1EC
P2EC
PAEC

72

PROGRAM MODE
Pen 2

rLyA
rLyb
rLyC
rLyd
rLyE
rLyF
rLyg
rLyh
CurA
Curb
CurC
Curd
CoAr
Cobr
CoCr
Codr
Crt
PAPu
Coo
CCon
CbS
CAd1
CAd2

unit

TUNE MODE
Pen 1

Pen 2

SoP
PAL1
dAL1
bAL1
PAL2
dAL2
bAL2
Pb1
Pb2
rSEt
ArSt
rAtE
Ct1
Ct2
SEnS
FoP

ENABLE MODE

EtSt
ECAL
EPro
Etun
ESby
ESPS
ESPC

Warranty and Return Statement


These products are sold by The Partlow-West Company under the warranties set forth in the
following paragraphs. Such warranties are extended only with respect to a purchase of these
products, as new merchandise, directly from The Partlow-West Company or from a PartlowWest Company distributor, representative or reseller, and are extended only to the first buyer
thereof who purchases them other than for the purpose of resale.

Warranty
These products are warranted to be free from functional defects in materials and workmanship at the time the products leave The Partlow-West Company factory and to conform at that
time to the specifications set forth in the relevant Partlow-West instruction manual or manuals,
sheet or sheets, for such products for a period of three years.
THERE ARE NO EXPRESSED OR IMPLIED WARRANTIES WHICH EXTEND BEYOND
THE WARRANTIES HEREIN AND ABOVE SET FORTH. THE PARTLOW-WEST COMPANY MAKES NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE PRODUCTS.

Limitations
The Partlow-West Company shall not be liable for any incidental damages, consequential
damages, special damages, or any other damages, costs or expenses excepting only the cost
or expense of repair or replacement as described above.
Products must be installed and maintained in accordance with The Partlow-West Company
instructions. Users are responsible for the suitability of the products to their application.
There is no warranty against damage resulting from corrosion, misapplication, improper
specifications or other operating condition beyond our control. Claims against carriers for
damage in transit must be filed by the buyer.
This warranty is void if the purchaser uses non-factory approved replacement parts and
supplies or if the purchaser attempts to repair the product themselves or through a third party
without factory authorization.

Returns
Partlow-West's sole and exclusive obligation and buyers sole and exclusive remedy under the
above warranty is limited to repairing or replacing (at Partlow-West's option), free of charge,
the products which are reported in writing to The Partlow-West Company at its main office
indicated below.
The Partlow-West Company is to be advised of return requests during normal business hours
and such returns are to include a statement of the observed deficiency. The buyer shall prepay shipping charges for products returned and The Partlow-West Company or its representative shall pay for the return of the products to the buyer.
Approved returns should be sent to:

THE PARTLOW-WEST COMPANY


2 CAMPION ROAD
NEW HARTFORD, NY 13413 USA

73

THE PARTLOW-WEST COMPANY


2 CAMPION ROAD NEW HARTFORD, NY 13413 USA
1-800-866-6659 315-797-2222 FAX 315-797-0403

74

You might also like