I/A Series Remote Terminal Unit (RTU)
RTU50 Input/Output Modules
The I/A Series RTU50 product line includes an extensive family of input/output modules that provide
connections to a wide range of field devices. From oil and gas applications to electricity monitoring and
control, the I/A Series RTU50 provides an I/O solution tailored to the demanding needs of the SCADA user.
Key features of the I/O modules include:
Software configurable digital inputs
High security control output logic boards with
versions)
20 Channel Analog Input Module (standard,
isolated)
PSS 21H-8C6 B4
Page 2
FUNCTIONAL DESCRIPTION
Digital Inputs:
6 analog inputs
Plug-in resistors for current loops
12 bits plus sign analog-to-digital converter
2 V dc range
Continuous auto input calibration/check
Control Outputs:
Digital Inputs
variations.
Features
Key features include:
Removable plug-connected termination board
RUN/FAIL LED indicator
Module operating conditions available as RTU
database points
PSS 21H-8C6 B4
Page 3
MULTIPLE
INPUT/OUTPUT
TERMINAL
BOARD
0303448
0303449
MULTIPLE
INPUT/OUTPUT
TERMINAL
BOARD
0303450
0303449
MULTIPLE
INPUT/OUTPUT
TERMINAL
BOARD
0303451
0303449
PSS 21H-8C6 B4
Page 4
Features
Key features include:
20 analog inputs
12 bits plus sign analog-to-digital converter
2 V dc ranges
RUN/FAIL LED indicator
Plug in current loop resistors that use screw type
20 CHANNEL
ANALOG
INPUT BOARD
1 KV
STANDARD
0303349
20 CHANNEL
ANALOG INPUT
NON-ISOLATED
TERMINAL
BOARD
0303350
20 CHANNEL
ANALOG INPUT
TERMINAL
BOARD
0303440
0303443
PSS 21H-8C6 B4
Page 5
WARNING
In this module, the jumpers J3 to J34 must
be removed when using digital input voltages
in the range 60129 V (dc) or 72144 V RMS
(ac). Failure to do so may result in permanent
damage to the module and possible electric
hazard.
The Analog/Digital Input Module has 1 KV isolation
on its analog inputs.
Features
Key features include:
Removable plug-connected termination board
1 KV isolated analog inputs
Plug in current loop resistors that use screw type
Module Description
The digital input subsystem processes contact type
inputs to the I/A Series RTU50. The module optically
isolates, filters, and protects against surge transients;
it also interfaces the contact information to the onboard microprocessor.
All digital input circuits employ contact bounce
elimination circuitry, which rejects noisy contact
transitions until the input signal has been stable for a
period of 2 msec.
PSS 21H-8C6 B4
Page 6
Constituent Assemblies
4 ANALOG/32
DIGITAL INPUT
MODULE
24 V to 129 V
4 ANALOG/32
DIGITAL INPUT
TERMINAL
BOARD
0303480
0303442
PSS 21H-8C6 B4
Page 7
Features
12 independent relays
RUN/FAIL LED indicator
Relays configurable as ON/OFF (individual),
Module Description
The 12 Relay Digital Output subsystem provides
security and control for all digital outputs. The
12 Relay Digital Output Module consists of an onboard microprocessor and security circuits mounted
on a logic board with a plug and terminal assembly.
The relay outputs are determined by a customers
selection of relay platform boards. Among the
available options is a choice between electrically
latched relays, magnetically latched relays, and high
current (10 Amp) relays.
A control ISOLATE/ENABLE switch on the front panel
allows servicing of the controlled equipment without
risking remote operation. An external switch can also
be wired from the power supply to simultaneously
disable all digital output boards.
The 12 Relay Digital Output Module contains an onboard microprocessor with associated RAM and
ROM. Configuration data from the I/A Series RTU50
Master Processor Module determines the treatment
of each output port by the on-board processor.
Two-Pass Operation
During pass 1, the on-board microprocessor accepts
command data from the I/A Series RTU50 Master
Processor Module through shared memory. The
validity of the command is confirmed and then the
hardware is checked on the output driver circuits. If
all tests succeed, feedback of the command is sent
to the I/A Series RTU50 Master Processor Module.
During pass 2, the I/A Series RTU50 Master
Processor Module sends the execute command and
the 12 Relay Digital Output Module drives the
required relays. The 12 Relay Digital Output Module
automatically times the duration of pulse outputs and
turns the necessary relay off.
Constituent Assemblies
The following board assemblies combine to form the
12 Relay Output Module (Part Number SY-0399008).
12 CHANNEL
DIGITAL
OUTPUT
BOARD
PILOT
RELAY
OUTPUT
PLATFORM
CONTROL
OUTPUT
TERMINAL
BOARD
0303383
0303385
0303355
PSS 21H-8C6 B4
Page 8
12 CHANNEL
DIGITAL
OUTPUT
BOARD
MAG
LATCH
RELAY
PLATFORM
CONTROL
OUTPUT
TERMINAL
BOARD
0303383
0303386
0303355
12 CHANNEL
DIGITAL
OUTPUT
BOARD
10 AMP
RELAY
OUTPUT
PLATFORM
CONTROL
OUTPUT
TERMINAL
BOARD
0303383
0303360
0303355
PSS 21H-8C6 B4
Page 9
4 CHANNEL
ANALOG
OUTPUT
BOARD
ANALOG
OUTPUT
TERMINAL
BOARD
0303342
0303338
PSS 21H-8C6 B4
Page 10
M U LT I P L E I / O M O D U L E F U N C T I O N A L S P E C I F I C AT I ON S
PSS 21H-8C6 B4
Page 11
M U LT I P L E I / O M O D U L E F U N C T I O N A L S P E C I F I C AT I O N S ( C O N T I N U E D )
DIGITAL INPUTS (CONT.)
Transient Protection
IEEE C37.90-1989
IEC 255-22-4
Impulse Voltage Withstand
Common mode 5 KV (input to frame)
Differential mode 5 KV (input to common
return)
High Frequency Disturbance
Common mode 2.5 KV (input to ground)
Differential mode 1 KV (input to common
return)
Fast Transient (IEC 61000-4-4)
2 KV 5 kHz Capacitive Coupling
CONTROL OUTPUTS
Relays are mounted on the rear of termination
board
Output Types
Outputs can be configured as: Trip/Close
pairs, Raise/Lower pairs, Single Variable
Pulse Relay, Latched or Setpoint
Security
One or more than one relay energized test
Check before execute
Control to pulse
CONTROL OUTPUTS
Removable block of 16 terminals
2 Terminals per relay
Terminals sized for 1.5 mm2 wire
NUMBER OF RELAYS
Eight
RELAY COIL CURRENT
45 mA
CONTACT ARRANGEMENT
Two-pole N/O relays with contacts connected in
series to boost dc rating (output is single pole)
CONTACT RATING
5 A 30 V dc resistive or 250 V ac (105 operations)
1 A 50 V dc inductive
130 V dc 200 mA L/R 40 msec 30,000
operations
ISOLATION
2 KV RMS for 1 minute output to frame
1 KV RMS for 1 minute across open contact
2 KV RMS for 1 minute between outputs
TRANSIENT PROTECTION
IEC 60255-4 Class 3
ANSI/IEEE C37.90.1 - 1989
Impulse Voltage Withstand
Common mode 2.5 KV (output to frame)
Across output contact 12.5 KV
High Frequency Disturbance
Common mode 1 KV (output to frame)
Fast Transient (IEC 61000-4-4)
2 KV 5 kHz capacitively coupled
MONITORS/INDICATORS
Red/green RUN/FAIL LED
PSS 21H-8C6 B4
Page 12
2 0 CH A N N EL AN A L O G I N PU T M OD U L E ( S T A N DA R D)
F U N C T I O N A L S P E C I F I C AT I O N S
PSS 21H-8C6 B4
Page 13
20 C HA N N EL AN A L O G I N P U T M O DU L E ( I SO L AT ED )
F U N C T I O N A L S P E C I F I C AT I O N S
PROCESSOR
Z80 interfaces to Electrobus via dual access RAM
ANALOG INPUTS
Input Circuit
20 independently isolated analog inputs
Analog-to-digital Converter Type
Sigma Delta
Resolution
Common mode 2 KV (input to ground)
12 bits plus sign
Differential mode 1 KV (across input
Input Update Rate (Data Age)
terminals)
<600 ms includes calibration cycle
High Frequency Disturbance
Input Signal Range
Common mode 2 KV (input to ground)
2 V dc
Differential mode 0.5 KV (across input
terminals)
Input Signal Scaling
Fast Transient (IEC 61000-4-4)
Current loop resistor
2 KV 5 kHz Capacitive Coupling
Full Scale Range
Reference
Voltages
4000 counts (over range 4095 counts)
Auto calibration on individual channels does
Maximum Error at 25C
not require external check voltages.
0.1% full scale
20 Channel Analog Terminal Board (Standard
Common Mode Error
and Isolated)
0.0001% per Volt to a maximum of 1000 V
ac (120 dB)
PRINTED CIRCUIT BOARD
Temperature Error
261.8 mm x 71 mm attached to frame by screws
0.002% per C to Minimum of 0C
TERMINALS
2 Terminals per point each with test points and
Maximum of 60C
isolation link
Maximum Error Over Temperature and
1 chassis terminal per four input channels with
Common Mode Range
test point
0.25% full scale
Loop drop resistor and voltage divider terminals
Differential Mode Rejection
mounted on rear side of terminal board.
60 dB minimum at 60 Hz
MONITORS/INDICATORS
Differential Mode Voltage Without Damage
Red/green RUN/FAIL LED
24 V dc or peak ac
PSS 21H-8C6 B4
Page 14
A N A L O G / DI GI TAL I N P U T M O D U L E ( I S O L AT E D )
F U N C T I O N A L S P E C I F I C AT I O N S
DIGITAL INPUTS
Input Circuits
32 per input module in 4 groups of 8 inputs
Input Types
Any input can be used as: Status,
Momentary Change Detect, Sequence of
Events, Accumulator (1 or 2 inputs per
accumulator)
Circuit Types
Common return per group of 8 inputs
Common positive or common negative
Input Voltage
24 V to 129 V, selected individually per input
by jumper setting; factory default range is
48-129 V; field configurable to 24-48 V.
Input Current
5 mA per input (nominal)
Isolation Type
Opto-coupler
Insulation
2 KV RMS for 1 minute input to frame
(ground)
PSS 21H-8C6 B4
Page 15
A N A L O G / DI GI TAL I N P U T M O D U L E ( I S O L AT E D )
F U N C T I O N A L S PE CI F I C AT I O N S ( C O N T I N U E D )
DIGITAL INPUTS (C0NT.)
Transient Protection
IEC 60255-22-4
Impulse Voltage Withstand
Common mode 5 KV (input to frame)
Differential mode 5 KV (input to common
return)
4 A N A L O G / 3 2 D I G I TAL I N P U T T E R M I N AT I O N M OD U L E ( I S O L AT ED ) F U N C T I O N A L
S P E C I F I C AT I ON S
STATUS INPUTS
4 Groups of 8 status inputs
1 Terminal per point each with test points and
isolation link
1 Common terminal with test point for each
group of 8 inputs
Suppression device across each input to its
common
MONITORS/INDICATORS
Red/green RUN/FAIL LED
PSS 21H-8C6 B4
Page 16
1 2 C H A N N E L D I G I TAL O U T P U T M OD U L E S F U N C T I O N A L S P E C I F I C AT I O N S
PSS 21H-8C6 B4
Page 17
1 2 C H A N N E L D I G I TAL O U T P U T M OD U L E S F U N C T I O N A L S P E C I F I C AT I O N S
( C O N T I N U E D)
PSS 21H-8C6 B4
Page 18
4 C H A N N E L A N A L O G O U T P U T M O D U L E F U N C T I O N A L S P E C I F I C AT I O N S
PROCESSOR
Z80 interfaces to Electrobus via dual access
memory
OUTPUTS
Each output is configurable:
TRANSIENT PROTECTION
IEC 255-4 Class 3 5 KV impulse, 2.5 KV HFD
ANSI/IEEE C37.90.1 - 1989
Fast Transient (IEC 61000-4-4)
2 KV 5 kHz capacitive coupling (current loop)
CHANNEL ISOLATION
50 V dc channel to chassis
50 V dc channel to channel
Range
Counts
Output Steps
4 to 20 mA
0 to 4000
4000
4 to 20 mA
800 to 4000
3200
0 to 10 mA
0 to 4000
2560(a)
0 to 16 mA
0 to 4000
4000
4 to 20 mA
0 to 2000
2000
4 to 20 mA
400 to 2000
1600
Terminal 1
+24 V (maximum 36 V)
0 to 10 mA
0 to 2000
1280(a)
Terminal 2
24 V common
0 to 16 mA
0 to 2000
2000
Terminal 3
+I (current out)
Terminal 4
I (current return)
ACCURACY (4 TO 20 MA)
0.1% full scale at 25C
0.25% full scale 0 to 60C
ACCURACY (0 TO 16 MA)
1% full scale at 0 to 60C
EXTERNAL LOOP POWER
24 V (maximum 36 V, minimum 19 V)
LOOP LOAD RESISTANCE
0 ohms minimum, 600 ohms maximum
MONITORS/INDICATORS
Red/Green RUN/FAIL LED
PSS 21H-8C6 B4
Page 19
P H Y S I C A L S P E C I F I C AT I O N S
Physical Size
Each plug-in module requires frame space of 71.12
mm. Modules are assemblies of one or more printed
circuit boards. These modules plug into a backplane
(Electrobus) via a DIN 41612 connector and are
double Eurocard size (233.4 mm x 149 mm).
DIN 41612 connectors are also fitted to the front
edge of the PCB to provide connection to the
terminal board assembly.
E N V I R O N M E N TA L S P E C I F I C AT I O N S
Ambient Temperature
STANDARD
0C to +60C (32F to 140F)
EXTENDED(1)
-20C to +70C (-4F to +158F)
Humidity
10 to 95% (noncondensing)
PSS 21H-8C6 B4
Page 20
OR D E R I N G I N F O RM AT I ON
Part Number(a)
Description
Multiple I/O Module
SY-0399075
SY-0399076
SY-0399077
SY-0399007
SY-0399071
SY-0399161
SY-0399008
SY-0399009
SY-0399010
SY-0399012
MB 021
0910