Table of Contants: Switch Gear & Accessories 5-28
Table of Contants: Switch Gear & Accessories 5-28
Table of Contants: Switch Gear & Accessories 5-28
CHAPTER 1.
1.1
1.2
1.3
1.4
1.5
1.6
CHAPTER 2.
2.1
5-28
5
5
5
5
6
7
11
14
16
18
18
18
18
18
18
20
20
20
22
23
23
25
25
29-58
31
31
33
CHAPTER 3.
Instrument Transformer
3.1
3.2
3.3
3.4
3.5
Introduction
Types of Instrument Transformer
Current Transformer
3.3.1 Construction
3.3.2 Clip On Type Current Transformer
General Information
Type of CT
3.5.1 Wound Type
3.5.2 Bar Type
3.5.3 Dry Type
3.5.4 Ring Type
33
33
33
34
34
34
35
35
35
35
35
35
36
36
36
37
37
38
40
43
45
47
47
49
51
54
55
55
57
57
59-77
59
60
61
62
64
64
65
65
65
65
66
3.6
3.7
3.8
3.9
3.10
3.11
3.12
3.13
3.14
CHAPTER 4.
Winding of CT
3.6.1 Primary Winding
3.6.2 Secondary Winding
Current of CT,S
CT Ratio and Error
Burden
Accuracy
Measurment
Potential Transformer
3.12.1 Construction
General Information
Function of Potential Transformer
CHAPTER 5.
5.1
5.2
5.3
5.4
5.5
5.6
Introduction
Protection
Protection Relay and Protection System
Relay
Operation
Types of Relay
Generator Unit Protection
Control Measurement Regulation
D.C Voltage Supply
Interlocking
Mimic Diagram of Double Bus Bar Substation With
Branch Coupling and Bus Earthing Switch
Control
Devices
Insulator
Insulator
Physics of Conduction in Solid
History
Insulation of Antennas
Insulation in Electrical Apparatus
Class 1 and Class 2 Insulation
66
66
66
66
67
68
69
70
73
74
75
76
78-94
79
80
81
82
82
83
87
90
90
91
92
94
94
95-100
95
97
97
98
99
100
CHAPTER NO. 1
1) WAPDA PANELS
2) PRIVATE PANEL
WAPDA PANELS
INCOMING PANEL.
CONSUMER PANEL
INDUSTRIAL PANEL
CONUMER PANEL
PRIVATE PANELS
1) CHANGE OVER PANEL.
2) OWNER PANEL
INDUSTRIAL PANEL
3) SWITCH BOARD
Main Components
DC supervision Relay
CDG 21 relay
Cos Meter
Volt Meter
Ampere Meter ,
Indication Lights
TOD Meter
Selector 'Switch
Test Block
Terminal Block
Working
First of all supply will comes on current transformers (C.Ts) and PTs
(Potential Transformer).CTs are in series of all the circuit ad PTs are in
parallel. There are 6 'CTs in this panel. 3 for Differential Protections 3 for
Protection & Metering Supply will comes on CTs and Then on PTs and after
that through VCB goes on Outgoing Panel.
There are three, ampere meters in this panel, which are showing currents
separately where as one Voltmeter is used with a selector switch. We can
read volts with the help of selector switch on different phases.
Main Components
O/C & E/F Relay (CDG-61 Relay)
DC Supervision relay
Cos meter
Indicating Lights
ON, Off Push. Buttons
Mcbs
Working
First of all supply comes on CTs and then through VCB goes to users.
This supply is 11 KV So trough; transmission lines this supply comes on
Distribution Transformer for step down from 11 KV to 440 V. This 440 V
are in three-phase four-wire, system. Phase-to- Phase Voltages are 440 V
and Phase to Neutral Voltages is 220 V.
For its control circuit we give DC Supply Individually form a DC source that
would be a Generator or Battery. We also use a DC
Supervision Relay in Outgoing panel to observe DC supply. In case of
low or high voltages that relay will trip all the-'system. In this Panel 3 CTs
are used only for metering. Cable of CTs comes on Ampere meter only.
OUTGOING PANEL
TESTING OF SOLUTION
We get 10 .ML solutions in Flask with help of puppet. After that we
added 100 ML clean .water and mix it. Then we get 10 ML form Flask in a
Beaker. And then we add Indicator no. 9 99hjiyi9993 drops. 1st drop after 15
seconds 2nd drop we add. After we add testing solution in the beaker. Yet the
colors of solution changed in Yellow from Red. Note the used Quantity of
used testing solution in ML.
The reading should be under 24.5 ML to 25.5 ML. In case of low
reading we add a 55 KG bag of acid for improve i1 ML reading. We check
this .reading 3 Times in a Day.
Main Components
Contactor scheme
MCB (Miniature Circuit Breaker)
Terminal blocks
Indicating lights
ON, OFF Push Buttons
VCB (Vacuum Circuit Breaker)
Finder Relay '
Bus Bars
BUSCOUPLER PANEL
Working
Normally VCB of Bus Coupler panel .is- in off position. And tow
supplies come on incoming' panels and through Outgoing panels goes to the
users. Whenever any supply switched off we will switch .on the VCB of bus
coupler. We also put a finder relay in the bus coupler. When OFF supply will
come this relay will switch off the VCB if bus coupler. In normal conditions
VCB of bus coupler should be open and no supply passes through it. In the
case of break 'down of any one supply this will be on or in close position.
When the off supply will energized then finder relay works VCB of' 'bus '
coupler will trip with the help of finder-relay.
Main Components
Buckles .Relay.
TJN Relay.
Selector switch.
Ampere meter
Voltage meter
Buzzer
Push Buttons
Indicating lights
CTs (Current Transformer)
PTs (Potential Transformer)
TOD Mete
MCB (Miniature Circuit Breaker)
Terminal Block
CTU (Capacitor Trip Unit)
OWNER PANEL
Working
First of a11 11 KV supply will come on CTs and then on PTs and then
through goes to Outgoing panel. We supplied its control circuit through PTs.
Because these are AC Voltages and we want DC Voltages so connect CTU
(Capacitor Trip Unit) that will work as a converter and convert AC Supply
into DC Supply. In this panel we place Buckles Relay. Which is connected
We use this panel in factories and connected with- a transformerincoming panel by a. bus coupler. At transformer incoming panel supply
comes from Wapda where as generator-incoming panel gets the supply from
generator based in factory.
Main Components
ACB (Air-Circuit Breaker) CTs (Current Transformer) u Voltmeter j
Selector switch
Automatic Transfer Switch (DKG 205 relay)
ON, OFF Push buttons
Indication lights
Emergency off push buttons
Terminal Box
MCB (Miniature Circuit breaker)
Working
First of all supply through bus bars comes on CTs and then comes on Air
Circuit Breaker and goes outgoing panel
He uses this panel with transformer incoming panel. In case of breakdown of
Wapda supply generator will automatically on. And when transformer
incoming will restore generator will automatically off through DKG 205
Relay.
In this panel over voltage under voltage is used. 'This relay sense voltages in
case of fluctuation of voltages this relay will trip all the system.
1.6.1 Disconnections
The classic design of the disconnect or is the knife-contact
disconnected (Fig.4-1). It has become less common with the increasing use
of withdraw able circuit-breakers and switch-disconnections. This
functional principle is now again becoming more frequent in gas-insulated
switchboard technology.
Fig. 4-1 Medium-voltage knife-contact disconnections
1.6.2 Switch-disconnectors
Switch-disconnectors are increasingly being used in distribution
networks for switching cables and overhead lines. Switch-disconnectors in
connection with HV fuses are used for protection of smaller transformers.
Switch-disconnectors are switches that in their open position meet the
conditions specified for isolating distances. General purpose switches can
make and break all types of operating currents in fault-free operation and in
the event of earth fault. They can also make and conduct short-circuit
currents.
16
17
18
The cap-shaped end contacts of the HV fuse link are picked up by the
terminal contacts of the fuse base. HV fuse links can be fitted with indicators
or striker pins, which respond when the band-shaped conductors melt
through. The striker pin is required for mechanical tripping of the switching
device when used in the switch/fuse combination.
Characteristic current values for HV fuse links:
Rated current
The majority of fuse links in operation have a rated current 100 A.
For special applications with smaller service voltages (e.g. 12 kV), fuse links
up to 315 A are available. The associated melt-through times of the fusible
conductors are found from the melting characteristics (manufacturer
information for the range of the interrupting currents)
Rated breaking current
This value must be provided by the manufacturer of the fuse link. It is
influenced by the design for a specified rated current. When selecting fuse
links for transformer protection in distribution systems, the maximum
breaking current is not a critical quantity.
Rated minimum breaking current
Classification of fuse links into three categories
Back-up fuses smallest breaking current (manufacturer information) in
19
general at 2.5 to 3.5 times rated current. Suited for application in switch/fuse
combinations. Very common!
General purpose fuses The minimum breaking current is that which results
in melt-through after 1 hour or more of exposure time (generally twice the
rated current).
Full-range fuses every current that results in a melt-through can be
interrupted.
Cut-off current characteristic
The maximum value of the current let-through by the fuse depends on its
rated current and the prospective short-circuit current of the system. Fig. 8-7
shows a characteristic field.
In capacitor banks the rated current of the HV fuse links should be at least
1.6 times the rated current of the capacitors. Experience has demonstrated
that this covers also the influences of possible system harmonics and
increased voltage.
When selecting fuse links for protection of high-voltage motors, the starting
current and the starting time of the motors must be taken into account. The
frequency of startups must also not be neglected if this is frequent enough to
prevent the fuses from cooling down between starts.
20
integration of the supply systems. This can also result in the permissible
short-circuit currents of the equipment being exceeded and the equipment
being dynamically or thermally destroyed.
It is often not technically possible or not economical for the user to replace
switchboards and cable connections with new equipment with increased
short-circuits current capability. The implementation of Is-limiters when
expanding existing installations and constructing new installations reduces
short-circuit currents and costs.
A circuit-breaker does not provide protection against impermissibly high
peak short-circuit currents, because it is too slow. Only the Is-limiter is
capable of detecting and limiting a short-circuit current in the initial rise, i.e.
in less than one millisecond. The maximum instantaneous current value that
occurs remains well below the peak value of the short-circuit current of the
system.
Typical Is-limiter applications
In couplings,
In coupling the public system with a private supply,
parallel to reactor coils, (avoids copper losses and voltage drop at the
reactor coils)
In transformer or generator feeders,
In outgoing feeders.
The Is-limiter is a current-limiting switching device, which detects and limits
the short-circuit current in the initial rise. The short-circuit current through
the I-limiter is limited so
Quickly that it does not contribute in any way to the peak value of the shortcircuit current at the fault site.
a) Current path total current without Ilimiter
21
b) Basic layout
22
achieve the desired short switching delay, a small charge is used as energy
storage for opening the switching device (main current path). Once the main
current path has been opened, the current still flows through the parallel fuse,
where it is limited within 0.5 ms and then is finally interrupted in the next
voltage zero.
Rated current
....
....
....
....
....
A
4.500
4.000
4.000
2.500
2.500
23
CHAPETER NO. 2
VCB
2)
MOCB
3)
OCB
4)
SF6
24
25
26
27
28
OFF
2.2.2 Unpacking
When opening the package, also avoid turning it over and special care
should be taken to not damage the breaker. Handle carefully disconnecting
unit, front panel and so on.
29
3) Check all accessories and spares supplied. Also, check to see if these parts
are damaged.
2.2.4 Installation
Before installing the circuit breaker into the switchgear, check the type rating
and for any signs of damage again. Wipe the breaker with a dry cloth to
remove dirt and dust. Mount the draw-out unit (if it is used) on a level floor
by means of screwing through the mounting holes on the bottom. Then, the
tolerance on the level should be within 1 mm. If required, adjust the level
using a liner.
Wipe the connecting surface with a dry cloth to remove dirt and dust before
connecting main circuit bus-bars and earth terminal and be careful not to
shock the draw-out unit and breaker.
Note
Breaker" for mounting whole size of the each draw-out unit and earth
terminal's size.
30
2) Press the "ON" button. Be sure to check that the breaker is closed and the
ON/OFF indicator displays "CLOSE".
3) Press the "OFF" button. And be sure to check that the breaker is opened
and the ON/OFF indicator displays "OPEN".
4) Operate 2-3 times as mentioned sequence. Finally, check that no tools and
materials are left near the breaker.
Item
10
Housing Box
11
Closing Mechanism
12
Closing spring
13
Trip Spring
14
Link
15
Coupling Bar
16
Breaker Shaft
17
Dash Pot
18
Counter
19
On/Off Indicator
20
21
Closing Button
22
Trip Button
23
Name Plate
24
31
Motor
31
32
Closing Solenoid
33
Trip Solenoid
34
35
36
41
Vacuum Interrupter
42
43
44
45
Flexible Terminal
46
Upper Insulator
47
Lower Insulator
48
Insulator Coupler
49
50
Cross Arm
51
Struts
52
Earthling Terminal
53
Centering Ring
60
61
Interlock Handle
Housing Box
11
Closing Mechanism
32
12
Closing Spring
13
Tri Spring
14
Link
15
Coupling Bar
16
Breaker Shaft
17
Dash Pot
18
Counter
19
ON/Off Indicator
20
21
Closing Button
22
Trip Button
23
Name Plate
24
31
Motor
32
Closing Solenoid
33
Trip Solenoid
34
35
36
41
Vacuum Interrupter
33
42
43
44
45
Flexible Terminal
49
54
Female Contact
55
Insulation Frame
56
57
Insulation Rod
58
Spring Guide
59
Coupling Bolt
62
Position Indicator
63
CHARGING
When the charging mechanism is activated by hand or motor
(31), the charging shaft (11-1) turns by the gears and the driver
(11-2) so that the closing spring (12) is tensioned. When the
closing spring is fully tensioned, the closing pawl (11-3) makes th3
closing spring be latched.
34
2.
CLOSING
When closing command is applied, the closing spring s
35
3.
RECHARGING
After the closing operation, the closing spring can be
36
4.
OPENING
When opening command is applied, the tripping spring is
unlaced by the activation of the trip pawl, and the breaker shaft is
returned to the open position.
1.
37
cradle check first whether the link is horizontal as show in Fig 410, if not, put the handle not the hole and turn it any direction to
set the link horizontal after that, check to see if the breaker is
open.
2.
3.
38
HVF
Vacuum
Circuit
Breaker
has
several
39
2.
3.
With drawing the breaker first of all, open the breaker and
put the handle into the flexing screw head and turn in a count
clockwise direction to withdraw the breaker, the position indicator
will display DISCONNECTION, when the breaker reaches the
disconnection position.
40
To withdraw the breaker fully from the cradle, put the manual
locker to the unlock state and pull the breaker out slowly.
Inspection Item
General Check
Operation Test
Description
1. Clean the insulated
surface with a dry cloth
to remove dusty and
moisture.
2. 2. Check the exterior
for damage.
3. Check the exterior for
damage
4. Check stop ring and
stop
retainer
for
damage.
5. Check the connection
between
1. Operate a few times
manually
and
electrically and check
each part for proper
function.
2. Check
NO/OFF
indicator and counter
for proper function.
3. Check the compressed
length of contact press
sp.
According
to
Interval Remark
3 years
2,000 operations
or 10 operations
of short circuit
currents
41
1.
Insulation resistance
2.
Withstand
Test
Voltage
1.
1.
Lubrication
1.
Vacuum Interrupter
2.
appendix A and B
Measure
insulations
resistance
between
phase and between
phases and between
pole-earth with 100 V
megger, if the measured
value is less than 500m,
3 years
Check the cause.
Check
insulation
resistance
between
control circuit and earth
500v megger. If the
measured value is less
than 2M, Check the
cause.
Test the breaker with
power
withstand
voltage test according
to appendix A and B.
Lubricate each part of
operating mechanism.
5,000 Operations
Clean
disconnection
unit with a dry cloth
and a small amount of
grease
(conductive
grease. Lithium soap
based grease
With
the
circuit
opened, check vacuum
degree.
42
43
Installation space.
44
45
1-Upper terminal
2-Main contact
3-Nozzle
4-Arcing contact
5-Moving chamber
6-Valves
7-Lower chamber
8-Insulating housing left: closed right: open
Auto puffer-arc quenching system
46
47
48
49
CHAPTER NO.3
INSTRUMENT TRANSFORMER
3.1 Introduction
In d.c. circuits when large circuits when large currents are to be
measured, it is usual to use low-range used with high resistances connected
in series with them. But it is neither convenient nor practical to use this
method with alternating current and voltage instruments. For this purpose,
specially constructed accurate ration instrument transformers are employed
in Conjunction with standard low range a.c. instruments.
50
Their purpose is to reduce the line current or supply voltage to a value small
enough to be easily measured with meters of moderate size and capacity. In
other words, they are used for extending the range of a.c. ammeters and
voltmeters.
for
measuring
large
alternating
for
measuring
high
alternating
currents.
(ii)
51
3.3.1 Construction
A current transformer takes the place of shunt in d.c. measurements
and enables heavy alternating currents to be measured with the help of a
standard 5-A range a.c. ammeter,
52
53
bars or feeders whereupon the trigger is released and the core is tightly
closed by a spring. The current carrying conductor or feeder acts as a single.
Turn primary where the secondary is connected. Across the standard
ammeter conveniently mounted in the handle itself.
3.5.1
Wound Type
3.6
W I N DING OF CTs
56
3.9 BURDEN
The out put is composed of the individual burdens of the instruments and for
meters and connecting leads. When the length of the connecting leads is such
that the output at SA secondary current would be excessive consideration
should be given to the use of a rated secondary current would be excessive,
58
3.10 ACCURACY
The accuracy of the CT required would depend on connected equipment i.e.
approximate indication like Ammeter, say class 5 for industrial metering like
kilo watt hour meter, say class 1 and for precision grade for laboratory use
say class 0.2. The required class of accuracy for various metering application
use as follows
APPLICATION
CLASS OF
ACCURACY
0.1
testing Laboratory current transformers
For laboratory and test work in conjunction
with high Accuracy indicating instruments
0.2
integrating meters And who substandard for
testing industrial CT's
For precision industrial metering for
0. 5 or 1.0
commercial Industrial metering
59
3.11
MEASUREMENT OF CURRENT
TRANSFORMERS
The output of current transformer is derived from the primary input
ampere turns (Primary current X primary turns) and therefore the number of
primary ampere - turns available limits the accuracy and related burden of
the CT. Due to single turn primary on ring type CT's the ampere turns are
limited by primary current rating and hence the burden and accuracy
available on ring type CT are limited, especially for low ratios. For higher
burden and accuracy classes required on lower ratios current transformers
with wound primary, i.e. primary winding with adequate number of turns
would be required. Generally ring type CT's are used for ratios 100/5amp
above and wound primary CT's are usually used for ratios below 100/5amp.
The tables below show the burden guide, selection of accuracy class and
limits of error for measurement CT's (extract from IS 2705 19
60
3.3/6.6/11 KV Indoor
Current Transformer
3.3/6.6/11 KV
Indoor
1 Phase Voltage
Transformer
with Fuse
11KV
Metering/Protection
Transformer
11KV 3 Phase
Horizontal
Type
Voltage
Transformer
11KV Auxiliary
11/22/33 KV Bar Type
Current Transformer
Transformer
With Fuses
Primary
E nc ap sula ted
11KV
Current Transformer
Metering
Cubicle
2Pole
61
11/22/33 KV
11/22KV
Bus duct
Ring Type
Current
Current
Transformer
Transformer
33KV
33KV
Metering/protectio
Voltage
Transformer
Current
Earthed
Transformer
Type
Without
11KV
3Phase
Vertical
11KV
Auxiliary
Type
Voltage
Transformer
Transformer
With
Fuses
Totally
11KV
Phase
11KV
Generator
Neutral
Grounding
Transformer
62
63
PHASE DISPLACEMENT
The difference in phase between the primary and secondary current
vectors, the direction of the vectors being so chosen that the angle is
zero for a perfect transformer. The phase displacement is said to be
positive when the secondary current vector leads the primary current
vector. It is usually expressed in minutes.
ROUTINE TEST
The Tests carried out on each current transformer to check
requirements likely to very during production.
64
3.14
FUNCTION OF POTENTIAL
TRANSFORMER
First of all, the HV experimenter who wants to work in the range of tens or
hundreds of kilovolts is confronted with the problem that suitable parts are
not readily available in electronic stores. In general, they are manufactured
by specialized companies, and they are very expensive, sometimes
unaffordable, when purchased new. With some luck, used parts or NOS (new
old stock) parts can be acquired through junk yards, recycling facilities,
surplus stores, or EBay. Prices vary over a wide range. The following is a
display of some of the various HV components I was able to procure in
recent years. My experimental HV power supplies described later are based
on some of these components.
65
66
CHAPTER NO.4
67
that the conventional control rooms with mimic displays as used in the past
for controlling the processes directly have been virtually superseded by
management systems with computers and video terminals, and are employed
only to depict the networks geographical layout or for emergencies.
Load management consists in directly influencing the system load,
possibly with the aid of ripple control which, acting via the normal power
network, can selectively disconnect and re-connect consumers or consumer
categories. On the basis of current figures and forecasts, it is possible to even
out the generating plants load curves and make better use of available power
reserves.
It would be beyond the scope of this book to consider in detail all the
subsystems and components relating to network control. This chapter can
therefore serve only as an introduction to the complex tasks, fundamentals,
problems and solutions encountered in power network control and its
systems. Closer attention is paid, however, to all components and interfaces
which directly concern the switching installation and the switchgear
engineer, and which must be considered in the planning, erection and
operation of substations.
4.2 PROTECTION
Various protection devices in systems with rated voltages > 1kV
are available to protect generators, transformers, cables, bus bars and
consumers. The purpose of these devices is to detect faults and isolate them
selectively and quickly from the network as a whole so that the
consequences of the fault are limited as much as possible. With todays high
fault levels and highly integrated networks, faults have far-reaching
consequences, both direct (damaged equipment) and indirect (loss of
production). Protection relays must therefore act very fast with the greatest
possible reliability and availability.
Relays can be divided into various categories. A basic distinction is made with
respect to function between contactor relays and measuring relays. Other
distinguishing characteristics are the relays construction the relays construction
the relays construction (e.g. circuit-board relays, reed relays, miniature relays,
mercury-wetted relays); the relays operating principle (e.g. attracted-armature
relays, immersed-armature relays, moving-coil relays); the relays location (e.g.
telephone relays, antenna relays, generator protection relays, network protection
relays); the relays specific function. (E.g. signaling relays, time-delay relays,
control relays, momentary-contact relays, auxiliary relays); the relays required
performance (e.g. heavy-current relays, high/low temperature relays, d.c. relays).
The relays used for protection purposes, together with supervisory relays, fall into
the category of measuring relays, and as electronic relays become more
68
widespread, of solid-state measuring relays. All the types of relays mentioned are
used to transmit clearly defined, fast and carefully isolated indication and control
signals from low-energy electronic circuits to external circuits.
4.3
Todays standard protection relays and protection systems are in some cases
still preferably static but are designed to be numerically controlled (with
microprocessors). Electromechanical relays are practically never specified in
new systems. They have to meet the following international specifications:
TJN-316 RELAY
69
4.4 RELAY
A relay is an electrical switch that opens and closes under the control of
another electrical circuit. In the original form, the switch is operated by an
electromagnet to open or close one or many sets of contacts.
It was invented by Joseph Henry in 1835. Because a relay is able to control
an output circuit of higher power than the input circuit, it can be considered
to be, in a broad sense, a form of an electrical amplifier.
4.5 OPERATION
When a current flows through the coil, the resulting magnetic field
attracts an armature that is mechanically linked to a moving contact. The
movement either makes or breaks a connection with a fixed contact. When
the current to the coil is switched off, the armature is returned by a force
approximately half as strong as the magnetic force to its relaxed position.
Usually this is a spring, but gravity is also used commonly in industrial
motor starters. Most relays are manufactured to operate quickly. In a low
voltage application, this is to reduce noise. In a high voltage or high current
application, this is to reduce arcing.
If the coil is energized with DC, a diode is frequently installed across
the coil, to dissipate the energy from the collapsing magnetic field at
deactivation, which would otherwise generate a spike of voltage and might
cause damage to circuit components. Some automotive relays already
include that diode inside the relay case. Alternatively a contact protection
network, consisting of a capacitor and resistor in series, may absorb the
surge. If the coil is designed to be energized with AC, a small copper ring
can be crimped to the end of the solenoid. This "shading ring" creates a small
70
71
consumes power only for an instant, while it is being switched, and it retains
its last setting across a power outage.
Reed Relay
A reed relay has a set of contacts inside a vacuum or inert gas filled
glass tube, which protects the contacts against atmospheric corrosion. The
contacts are closed by a magnetic field generated when current passes
through a coil around the glass tube. Reed relays are capable of faster
switching speeds than larger types of relays, but have low switch current and
voltage ratings. See also reed switch.
Polarized Relay
A Polarized Relay placed the armature between the poles of a
permanent magnet to increase sensitivity. Polarized relays were used in
middle 20th Century telephone exchanges to detect faint pulses and correct
72
Contactor Relay
A contactor is a very heavy-duty relay used for switching electric
motors and lighting loads. With high current, the contacts are made with
pure silver. The unavoidable arcing causes the contacts to oxidize and silver
oxide is still a good conductor. Such devices are often used for motor
starters. A motor starter is a contactor with overload protection devices
attached. The overload sensing devices are a form of heat operated relay
where a coil heats a bi-metal strip, or where a solder pot melts, releasing a
spring to operate auxiliary contacts. These auxiliary contacts are in series
with the coil. If the overload senses excess current in the load, the coil is de-
73
Buchholz Relay
A Buchholz relay is a safety device sensing the accumulation of gas in
large oil-filled transformers, which will alarm on slow accumulation of gas
or shut down the transformer if gas is produced rapidly in the transformer
oil.
74
75
76
The DC output from the rectifier and also the battery can be connected
independently to the DC bus bars, so giving greater flexibility. It is best to
use 220 V and 110 V for direct control, with 60 V, 48 V and 24 V for
remote control and signal circuits. With the aid of inverters, a secure AC
bus bar can then be created from the DC bus bar if necessary.
The DC network must be carefully planned. The auxiliary circuits must be
assigned to each function and branch so that only one function or one bay is
affected by a fault. Faults in the signal circuit, for example, do not then
influence the control circuit, and vice versa.
4.10 INTERLOCKING
To ensure reliable control, the high voltage switching devices within each bay,
and at a higher level within the entire installation, are interlocked with respect to
each other. The interlock conditions depend on the circuit configuration and
status of the installation at any given time. The interlocks must in particular
prevent an isolator from operating while under load. The interlock conditions must
be defined according to the station layout, such as in the following example for a
double bus bar with branch, coupling and bus earthlng switch, see Fig.
4
When the bus-tie is closed, a second bus disconnect or (Q1 or Q2)
belonging to the tied system can be closed. One of the two closed
77
6
Disconnect or Q9 can be operated only when earthling switch Q8 is
open (taking account of other end if necessary).
7
Earthling switch Q8 can be operated only when disconnect or Q9 is
open (taking account of other end of outgoing line if necessary).
8
Disconnections Q1, Q2 and Q9 can be operated only when
maintenance earthling switches Q51/Q52 are open.
9
Maintenance earthling switches Q51/Q52 can be operated only when
disconnections Q1, Q2 and Q9 are open.
10
The tie-breaker Q0 can be opened only if not more than one bus
isolator in each branch is closed (tie-breaker lock-in).
11
One bus earthling switch Q15 or Q25 can be operated if in the
respective bus section all bus disconnections of the corresponding bus
system are open.
12
13
An interlock release switch cancels the interlock conditions. Switching
operations are then the responsibility of the person authorized.
4.12 CONTROL
The purpose of a control device in a switchgear installation is to change a
defined actual condition into a specified desired condition.
The operating sequences of controlling, interlocking and signaling can be
performed either by simple contact-type electromechanical and
electromagnetic devices such as discrepancy switches, auxiliary contactors
78
4.13 DEVICES
When drawing up the control system concept, it must be considered whether the
substation is to be largely manned or unmanned, or remotely monitored and
controlled. The kinds of control system can be broadly defined as follows.
79
CHAPTER NO.5
INSULATOR
5.1 INSULATORS
Insulator is a material that resists the flow of electric current. It is an
object intended to support or separate electrical conductors without passing
current through itself.
An insulation material has atoms with tightly bonded valence electrons. The
term electrical insulation has the same meaning as the term dielectric.
Some materials such as silicon dioxide or Teflon are very good electrical
insulators. A much larger class of materials, for example rubber-like
polymers and most plastics are still "good enough" to insulate electrical
wiring and cables even though they may have lower bulk resistivity. These
materials can serve as practical and safe insulators for low to moderate
voltages (hundreds, or even thousands, of volts).
80
5.3 HISTORY
The first electrical systems to make use of insulators were telegraph lines;
direct attachment of wires to wooden poles was found to give very poor
results, especially during damp weather.
The first glass insulators used in large quantities had an unthreaded pinhole.
These pieces of glass were positioned on a tapered wooden pin, vertically
extending upwards from the poles cross arm (commonly only two insulators
to a pole and maybe one on top of the pole itself). Natural contraction and
expansion of the wires tied to these "thread less insulators" resulted in
insulators unseating from their pins, requiring manual reseating.
81
82
83
84