(P Intlk) Instuction

Download as pdf or txt
Download as pdf or txt
You are on page 1of 36

Reference Manual

Rockwell Automation Library of Process Objects:


Interlocks with First Out and Bypass (P_Intlk)
Version 3.1

Important User Information


Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT

Identifies information that is critical for successful application and understanding of the product.

Labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, Rockwell Automation, RSLogix, Logix5000, FactoryTalk, PlantPAx, and ControlLogix are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Table of Contents
Preface

Software Compatibility and Content Revisions . . . . . . . . . . . . . . . . . . . . . . 5


Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Interlocks with First Out and Bypass


(P_Intlk)

Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Functional Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Required Files. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Controller File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Visualization Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Controller Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Interlocks Input Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Interlocks Output Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Interlocks Local Configuration Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Execution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Programming Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Display Elements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Status and Bypass Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Using Display Elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Operator Tab . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Maintenance Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Engineering Tab. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Interlock Faceplate Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Table of Contents

Notes:

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Preface
This manual contains new and updated information. Changes throughout this
revision are marked by change bars, as shown to the right of this paragraph.

Software Compatibility and


Content Revisions

Table 1 - Summary of Changes


Topic

Page

Replaced Programming Example image showing tie back connections.

15

Added Important note concerning selections on page 2 of the Engineering tab and on the
Maintenance tab.

17

Using Display Elements: Modified introductory text concerning navigation to faceplate from
associated objects.

20

Modified image to include P_Motor Global Object Parameter Values table.

21

For the latest compatible software information and to download the Rockwell
Automation Library, see the Product Compatibility and Download Center at
http://www.rockwellautomation.com/rockwellautomation/support/
downloads.page?.
For general library considerations, see Rockwell Automation Library of Process
Objects, publication PROCES-RM002.

Additional Resources

These documents contain more information about related products from


Rockwell Automation.
Resource

Description

PlantPAx Process Automation System Selection Guide,


publication PROCES-SG001

Provides information to assist with equipment


procurement for your PlantPAx system.

PlantPAx Process Automation System Reference Manual,


publication PROCES-RM001

Provides characterized recommendations for


implementing your PlantPAx system.

Rockwell Automation Library of Process Objects,


publication PROCES-RM002

Provides general considerations for the Rockwell


Automation Library of Process Objects.

FactoryTalk View Machine Edition User Manual,


publication VIEWME-UM004

Provides details on how to use this software package for


creating an automation application.

FactoryTalk View Site Edition User Manual,


publication VIEWSE-UM006

Provides details on how to use this software package for


developing and running human-machine interface
(HMI) applications that can involve multiple users and
servers, distributed over a network.

Logix5000 Controllers Add-On Instructions Programming


Manual, publication 1756-PM010

Provides information for designing, configuring, and


programming Add-On Instructions.

You can view or download publications at


http://www.rockwellautomation.com/literature/. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Preface

Notes:

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

The P_Intlk (Interlocks with First Out and Bypass) Add-On Instruction is used
to collect (sum up) the interlock conditions that stop or de-energize a running or
energized piece of equipment and prevent it from starting or being energized.
Interlocks are always evaluated to de-energize equipment. For permissive
conditions that must be made to start the equipment, but are ignored once the
equipment is running, use the Permissives (P_Perm) Add-On Instruction.
Faceplate
Global Object

Add-On Instruction

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

Guidelines

Use this instruction in these situations:


You have multiple interlock conditions or cascaded interlock conditions
(an interlock hierarchy) that stop some equipment (motor, valve, drive) or
keep it from starting. Link the conditions to P_Intlk inputs, and link the
P_Intlk status bits to the Inp_IntlkOK and Inp_NBIntlkOK inputs of the
equipment.
You need a first-out indication of the interlock condition that shuts down
the equipment.
You want configurable text descriptions of shutdown conditions or other
features of the P_Intlk faceplate.
Do not use this instruction in these situations:
You have conditions that prevent the equipment from starting, but are
ignored once the equipment is running. These conditions are permissive,
not interlock conditions. Use the P_Perm instruction instead.
You have only one interlock condition for the equipment. Connect the
condition directly to the interlock input on the device.

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

Functional Description

The following diagram shows the functional characteristics of the P_Intlk AddOn Instruction.

The primary operations of the P_Intlk Add-On Instructions and its faceplate are
the following:
Interlock input OK Check: Each input is compared with its configured
OK state. If the input is not in its OK state, it raises an interlock condition
unless bypassed by Maintenance. (See Interlock Bypass on page 8.)
Interlock Condition Latching: If the input is configured as latched, the
interlock condition is latched in until reset unless the latch defeat input is
true. See Latch Defeat on page 9. If the input is not configured as latched,
the interlock condition clears when the input is again in its OK state.
Interlock Bypass: If the input is configured as able to be bypassed and
interlocks are bypassed, the input does not raise an interlock condition,
even if it is not in its OK state. If the input is configured as not able to be
bypassed or if interlocks are not bypassed, the input raises an interlock
condition.
Engineering configures which interlocks are allowed to be bypassed.
Maintenance then picks the ones to bypass from the interlocks allowed by
Engineering.
First Out: If no interlock conditions are raised (OK to run), the first
interlock condition to be raised is marked as the first out. If multiple such
interlock conditions are raised in the same scan, they are all marked as
first out.

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

Latch Defeat: A latch defeat function is provided to reduce the number of


operator actions that are required to start equipment. The latch defeat
input is set when the equipment is not running. When the latch defeat
input is true, the latched configuration of inputs is ignored, and all
interlock conditions clear when their corresponding inputs are in their OK
states. This action saves the operator from having to reset before starting
the equipment. When the equipment starts, the latch defeat input is
turned off. Then, if an interlock condition configured as latched shuts
down the equipment, it remains latched until reset.
IMPORTANT

To prevent loss of information about what shut down the equipment,


the latch defeat input is not processed until after any latched interlocks
(that occurred when the latch defeat was off) have been reset.

Summary Status: The P_Intlk Add-On Instruction summarizes its 16


interlock input conditions into two primary status bits: Sts_IntlkOK,
which indicates that all interlock conditions are clear (ready to run), and
Sts_NBIntlkOK, which indicates that all interlock conditions that cannot
be bypassed are clear (ready to run if interlocks are bypassed).
IMPORTANT

Whether interlocks are bypassed or not is determined by the


downstream equipment instructions. The P_Intlk instruction simply
provides the two summary status bits. These two bits are to be wired or
mapped to the equipment control logic.

Faceplate: The P_Intlk Add-On Instruction faceplate displays the


interlock condition state of each input and whether it is bypassed, and
shows the overall interlock (summary) status. The Engineering tab of the
faceplate lets you configure the P_Intlk Add-On Instruction for OK state
configuration, latch configuration, configuration of interlocks that can be
bypassed, and the text that is associated with each interlock condition
input. You can also configure a navigation tag for each interlock condition.
If you enable navigation, the condition text on the Operator tab of the
faceplate can be clicked to access the faceplate for the corresponding tag.

10

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

Add-On Instructions are reusable code objects that contain encapsulated logic
that can streamline implementing your system. This code lets you create your
own instruction set for programming logic as a supplement to the instruction set
provided natively in the ControlLogix firmware. An Add-On Instruction is
defined once in each controller project, and can be instantiated multiple times in
your application code as needed.

Required Files

Controller File
The P_Intlk_3_1-00_AOI.L5X Add-On Instruction must be imported into the
controller project to be used in the controller configuration. The service release
number (boldfaced) can change as service revisions
are created.

Visualization Files
The following files for this Add-On Instruction can be downloaded from the
Product Compatibility and Download Center at
http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page.
IMPORTANT

Files must be imported in the following order: image files, then global object
files, and then graphic files. This order is required to configure the visualization
files properly.

Table 2 - P_Intlk Visualization File Types


Application Type

File Type

FactoryTalk View SE Software

FactoryTalk View ME Software

Description

Graphics - Displays

GFX

(RA-BAS) P_Intlk-Faceplate

(RA-BAS-ME) P_Intlk-Faceplate

The faceplate display that is used for the


object.

(RA-BAS) P_IntlkPerm-Help

(RA-BAS-ME) P_IntlkPerm-Help

Interlock/Permissives information that is


accessed from the P_Intlk or P_Perm Help
faceplate.

(RA-BAS) Common Faceplate Objects

(RA-BAS-ME) Common Faceplate Objects

Common global objects that are used on all


Process Object faceplates.

(RA-BAS) Process Interlock Objects

(RA-BAS-ME) Process Interlock Objects

Global objects that are used for managing


interlocks and permissives on Process Object
faceplates.

Graphics - Global
Objects

GGFX

Graphics - Images

PNG

All .png files in the images folder

All .png files in the images folder

The common icons that are used in the global


objects and faceplates for all Process Objects.
When PNG graphic formats are imported,
they are renamed like a BMP file but retain a
PNG format.

HMI Tags

CSV

N/A

FTVME_PlantPAxLib_Tags_3_1_00.csv(1)

These tags must be imported into the


FactoryTalk View ME project to support
switching tabs on any Process Object
faceplate.

Macros

MCR

NavToObject

N/A

This macro must be imported into the


FactoryTalk View SE project to support
faceplate-to-faceplate navigation by
tagname.

(1) The service release number (boldfaced) can change as service revisions are created.

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

11

Interlocks with First Out and Bypass (P_Intlk)

This section describes the parameter references for this Add-On Instruction.

Controller Code

Interlocks Input Structure


Input parameters include the following:
Input data elements (Inp_) are typically used to connect field inputs from
I/O modules or signals from other objects.
Configuration data elements (Cfg_) are used to set configurable
capabilities and features of the instruction.
Commands (PCmd_, OCmd_, MCmd_) are used by program logic,
operators, and maintenance personnel to request instruction actions.
Settings (PSet_, OSet_, MSet_) are used by program logic, operators, and
maintenance personnel to establish runtime setpoints, thresholds, and so
forth. A Setting (without a leading P, O, or M) establishes runtime settings
regardless of role or mode.
Table 3 - P_Intlk Input Parameters
Input Parameter

Data
Type

EnableIn

BOOL

Inp_Intlk00Inp_Intlk15

BOOL

Inp_BypActive

Default

Description

Ladder Diagram:
If the rung-in condition is true, the instructions Logic routine executes. If the rungin condition is false, the instructions EnableInFalse routine executes.
Function Block Diagram:
If true, or not connected, the instructions Logic routine executes. If the parameter
is exposed as a pin and wired, and the pin is false, the instructions EnableInFalse
routine executes.
Structured Text:
No effect. The instructions Logic routine executes.

Interlock condition inputs - If Input is not in the OK state defined by Cfg_OKState


and not bypassed (if able to be bypassed per Cfg_Bypassable), then the
appropriate interlock status (Sts_IntlkOK and Sts_NBIntlkOK) are set to 0 to stop
the equipment.

BOOL

1 = Interlock Bypassing is currently active.

Inp_LatchDefeat

BOOL

Latch Defeat 1 = Do not latch inputs even if configured for latching.

Inp_Reset

BOOL

Input parameter that is used to programmatically reset latched interlocks. When


set to 1, all latched interlocks that require a reset are reset.

Cfg_OKState

INT

2#0000_0000_
0000_0000

Bits determine the state (0 or 1) of each input that is OK to run.

Cfg_Latched

INT

2#0000_0000_
0000_0000

Set bits determine the conditions that are latched (sealed in).

Cfg_Bypassable

INT

2#0000_0000_
0000_0000

Set bits determine the conditions that can be bypassed.

Cfg_HasNav

INT

2#0000_0000_
0000_0000

Set bits determine the Navigation buttons that are enabled.

Cfg_PCmdClear

BOOL

When this parameter is 1, program commands are cleared once they are acted
upon. When set to 0, program commands remain set until cleared by the
application program logic.
IMPORTANT: Clearing this parameter online can cause unintended program
command execution.

12

Alias For

Wrk_Inp.0Wrk_Inp.15

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

Table 3 - P_Intlk Input Parameters


Input Parameter

Data
Type

Alias For

Default

Description

MSet_Bypass00
MSet_Bypass15

BOOL

Wrk.MSet.0Wrk.MSet.15

Maintenance Bypass Toggle for Interlock Cond. 00Cond.15: 1 = Bypass.


Maintenance uses these bits to determine which individual interlocks are
bypassed.

PCmd_Reset

BOOL

Set PCmd_Reset to 1 to reset latched interlocks


This parameter is reset automatically if Cfg_PCmdClear = 1

OCmd_Reset

BOOL

Operator Command to reset latched interlocks.

Interlocks Output Structure


Output parameters include the following:
Status data elements (Sts_) are bit outputs of the instruction for use by the
HMI. Status bits can also be used by other application logic.
Ready data elements (Rdy_) are bit outputs of the instruction that are used
by the HMI to enable or disable command buttons and entry fields.
Table 4 - P_Intlk Output Parameters
Output Parameter

Data Type

Description

EnableOut

BOOL

Enable Output: The EnableOut signal is not manipulated by this instruction. Its output state always reflects EnableIn input
state.

Sts_IntlkOK

BOOL

Overall Interlock Status:


1 = OK to run
0 = Stop

Sts_NBIntlkOK

BOOL

Interlock (cannot be bypassed) Status (1 = All NB interlocks OK to run).

Sts_BypActive

BOOL

1 = Interlock Bypassing Active (interlocks that can be bypassed are ignored).

Sts_Intlk

INT

Individual Interlock Status:


bit = 1 = Stop
bit = 0 = OK

Sts_FirstOut

INT

Interlock First Out Status (bit = 1 is First Not-OK condition).

Rdy_Reset

BOOL

1 = Ready to receive OCmd_Reset (reset required).

P_Intlk

BOOL

Unique Parameter Name for auto-discovery.

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

13

Interlocks with First Out and Bypass (P_Intlk)

Interlocks Local Configuration Tags


Configuration parameters that are array, string, or structure data types cannot be
configured as parameters for Add-On Instructions. Configuration parameters of
these types appear as local tags to the Add-On Instruction. Local tags can be
configured through the HMI faceplates or in RSLogix 5000 software. Open the
instruction logic of the Add-On Instruction instance and then open the Data
Monitor on a local tag to accomplish this configuration. These parameters
cannot be modified by using controller logic or RSLogix 5000 software export/
import functionality.
Table 5 - P_Intlk Local Configuration Tags
Tag Name

Data Type

Cfg_CondTxt
Cfg_CondTxt[0]
Cfg_CondTxt[1]
Cfg_CondTxt[15]

STRING_20[16]

Cfg_Desc

STRING_40

'Interlocks with First Out' Description for display on HMI. This string is shown in the title bar of the faceplate.

Cfg_Label

STRING_20

'Interlocks'

Label for graphic symbol that is displayed on HMI. This string appears on the graphic symbol.

Cfg_NavTag

STRING_20[16]

''

Tag names for destinations of 16 navigation buttons.

Cfg_Tag

STRING_20

'P_Intlk'

Tag name for display on the HMI. This string is shown in the title bar of the faceplate.

Operations

Default

Description
Short HMI descriptions of 16 interlock conditions.

'Enter Description #0'


''

This section describes the primary operations for Add-On Instructions.

Modes
The P_Intlk Add-On Instruction does not have modes and does not contain a
P_Mode instruction instance. The Operator and Program reset commands for
the latched inputs are accepted at any time.

Alarms
The P_Intlk Add-On Instruction does not generate any alarms. The individual
input conditions can be alarmed, if necessary, in other logic before they are sent
to the inputs of the P_Intlk instruction. In many applications, status bits from
P_AIn Analog Input or P_DIn Discrete Input instructions are sent to the
P_Intlk inputs, and those instructions provide alarms.
ATTENTION: Status bits are normally used as interlock conditions. Use alarm
bits as interlock conditions only if you intend that the interlock condition be
ignored when the corresponding alarm is disabled, suppressed, or shelved.

14

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

Simulation
The P_Intlk Add-On Instruction does not have a Simulation capability.

Execution
The following table explains the handling of instruction execution conditions.
Condition

Description

EnableIn False (false rung)

Processing for EnableIn False (false rung) is handled by setting the


summary All interlocks OK and All interlocks (cannot be bypassed) OK
status outputs to false (0). The individual interlock bit status and first out
outputs are left in their last state.

Powerup (prescan, first scan)

The latch and first out states of the P_Intlk Add-On Instruction are
maintained through a power-down/power-up or Run/Program/Run cycle.
Any commands that are received before first scan are discarded.

Postscan (SFC transition)

No SFC postscan logic is provided.

See the Logix5000 Controllers Add-On Instructions Programming Manual,


publication 1756-PM010, for more information.

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

15

Interlocks with First Out and Bypass (P_Intlk)

Programming Example

This example uses the P_Intlk instruction to concentrate the interlock conditions
that allow the functioning of the refiner plates that are used for grinding wood as
part of the pulp manufacturing process.
Perform the following steps to import an Add-On Instruction to your project.
1. Right-click 'Add-On Instructions' and select 'Import Add-On
Instruction'
2. On the Import Add-On Instruction dialog box, select the P_ Intlk
instruction and click Import.
3. Add the P_ Intlk instruction to your project:
a. Click the Add-On tab on the Language Element toolbar.
b. Click the P_ Intlk instruction.
c. Also add the P_ Motor instruction that controls the refiner plates.
4. Double-click the interlock instruction name and create the tag name for it.
The naming convention that makes navigation from the motor faceplate
work automatically is to use the motors tag name followed by _Intlk.
5. Create the input references necessary to ensure the appropriate operation
of the refiner plates and create their appropriate tags.
6. Expose the Sts_BypActive pin on P_Motor. Wire this pin back to
Inp_BypActive on P_Intlk, and mark this wire 'Assume Data Available'.
The following image is what the instruction looks like when connected
correctly.

7. Save, download, and run your Logix application.

16

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

8. In your HMI application, add a P_Motor motor graphic object from


P_Motor Graphics Library.ggfx and right-click it.
9. From the list, select Global Object Parameter Values
10. Associate the created tag for P_Motor of the Refiner Plates in the
controller with the graphic object in the HMI:
a. On the first line of the Global Object Parameter Value table, type its
name.
b. On the second line, type the name of the shortcut to the controller
enclosed by brackets.
c. Fill in additional parameters as desired.
Because of the naming convention, the connection will be made
automatically and the interlock settings will be associated with the
refiner plates motor.

11. Save and your HMI application.


12. Run your HMI application and click the motor graphic object. If the
Quick display appears, click the 'go to faceplate' button.
13. On the P_Motor faceplate, click the Engineering tab and go to page 2.

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

17

Interlocks with First Out and Bypass (P_Intlk)

14. Check Enable navigation to interlock object.

The Interlock button is enabled.


15. On the P_Motor faceplate, click the Interlock button to open the P_Intlk
faceplate. On the P_Intlk faceplate, click the Engineering tab, and perform
the following:
a. Name the interlocks accordingly.
b. Select the appropriate state under 'OK State'.
c. Indicate which interlocks can be bypassed.

18

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

d. Indicate which interlocks must be reset.

IMPORTANT

Specific inputs can be bypassed on the maintenance tab based on selections on


page 2 of the Engineering tab (see Engineering Tab Page 2 on page 30).
When bypass is enabled, it bypasses only those set on the Maintenance tab
(Maintenance Tab on page 26).

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

19

Interlocks with First Out and Bypass (P_Intlk)

Display Elements

A display element (global object) is created once and can be referenced multiple
times on multiple displays in an application. When changes are made to the
original (base) object, the instantiated copies (reference objects) are
automatically updated. Use of global objects, with tag structures in the
ControlLogix system, aid consistency and save engineering time.
Display Element Name

Display Element

GO_P_Intlk

Description
Standard Interlock Global Object.

Graphic symbols are provided for use on end-user process graphic displays.
Interlock graphic symbols have the following common attributes.
Status Indicator

Bypass Indicator

The Interlock graphic symbol displays the current summary state of the
interlocks and whether interlocks that can be bypassed are bypassed. These
indicators are described in detail in Status and Bypass Indicators on page 19.
The overall graphic symbol includes a touch field that opens the instructions
faceplate. In the SE version of the library, pausing the pointing device over the
graphic symbol displays a tooltip that describes the symbols function.

20

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

Status and Bypass Indicators


The Status Indicator icon changes color and shape that is based on the state of the
interlock input conditions, and the Bypass Indicator shows whether interlock
conditions that can be bypassed are currently being bypassed.
Background

Description
Not ready to run or energize. One or more interlock
conditions are not OK.

Ready to run or energize. One or more conditions that can


be bypassed are not OK, but these conditions are
bypassed. All conditions that cannot be bypassed are OK.
Ready to run or energize. All interlock conditions are OK.

Ready to run or energize, and all interlock conditions are


OK, but be aware that conditions that can be bypassed are
being bypassed and the equipment is not shut down.

The P_Intlk instruction does not have bypass commands, as they are in the
associated device instruction. If you would like the graphic symbol and faceplate
to display the equipments bypass state, connect the equipments bypass status to
the P_Intlk instructions Inp_BypActive input.

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

21

Interlocks with First Out and Bypass (P_Intlk)

Using Display Elements


Normally, navigation to the P_Intlk faceplate is included on the faceplate for the
associated motor, drive, or other object. However, a graphic symbol for the
P_Intlk instruction can be found in the global object file (RA-BAS) Process
Interlock Objects.ggfx. Follow these steps to use the graphic symbol.
1. Copy the global object from the global object file and paste it in the
display file.

22

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

2. In the display, right-click the global object and choose Global Object
Parameter Values.
The Global Object Parameter Values dialog box appears.

The global object parameters are as follows.


Parameter

Required

Description

#102

Object tag to point to the name of the associated object Add-On


Instruction in the controller.

#103

Path that is used for display navigation features to other objects. Include
program scope if tag is a program scope tag.

#120

Additional parameter to pass to the display command to open the


faceplate. Typically used to define position for the faceplate.

#121

Additional parameter to pass to the display command to open the


faceplate. When you define the X and Y coordinate, separate parameters so
that #120 defines X and #121 defines Y. This definition lets these same
parameters to be used in subsequent display commands that originate
from the faceplate.

3. Type the tag or value in the Value column as specified in the Description
column.
TIP

Click the ellipsis () to browse and choose a tag.


Values for items marked (optional) can be left blank.

4. Click OK.

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

23

Interlocks with First Out and Bypass (P_Intlk)

Faceplate

The P_Intlk faceplate consists of three tabs and each tab consists of one or more
pages.
Each faceplate contains the value of local configuration tags Cfg_Tag and
Cfg_Desc in the title bar.

The Operator tab is displayed when the faceplate is initially opened. Click the
appropriate icon at the top of the screen to access a specific tab.
Exit

Maintenance

Operator

Engineering

Help

The faceplate provides the means for operators, maintenance workers, engineers,
and others to interact with the P_E300Ovld instruction instance. You can also
view its status and values and manipulate it through its commands and settings.
When a given input is restricted via FactoryTalk View security, the required user
Security Code letter is shown in the faceplate description tables.

24

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

Operator Tab
The Faceplate initially opens to the Operator (Home) Tab. From here, an
operator can monitor the device status.
The Operator tab shows the following information:
A status indicator, identical to the one on the graphic symbol, shows the
current interlock state (all conditions met, non-bypassed conditions met,
or some conditions not met)
Interlock Bypass status indicator
Each configured interlock along with the current state of the interlock
Latch Defeat status indicator
The following figure shows the Operator tab in a non-bypassed condition.

Status Indicator

Latch Defeat Status


Indicator

Bypass Status Indicator

Reset Button

Condition OK

Condition Not OK

First-Out Indicator

If navigation is enabled, click a condition to open the faceplate of the object that
is associated with the condition.

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

25

Interlocks with First Out and Bypass (P_Intlk)

The following figure shows the Operator tab in a bypassed condition.

Bypass Indicator

Condition Bypassed, Input OK

Condition Bypassed, Input Not OK

The following table lists the functions on the Operator tab.


Table 6 - Operator Tab Description
Function

Click Interlock Condition text

26

Action

Security Required

Resets interlocks that are latched.

Normal Operation of
Devices (Code A)

Click to open the faceplate for the


associated tag.
See Engineering Tab Page 3 on page 31 for
information on how to enable navigation
for interlock conditions.

None

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

Table 7 - Operator Tab Status Indicators


Indicator

Description
Condition OK
Condition Not OK
Bypassed, but OK
Not OK, but bypassed

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

27

Interlocks with First Out and Bypass (P_Intlk)

Maintenance Tab
Maintenance personnel use the information and controls on the Maintenance tab
to make adjustments to device parameters. They also troubleshoot and
temporarily work around device problems, and disable the device for routine
maintenance.
IMPORTANT

Only interlocks with white checkboxes can be individually bypassed. These


interlocks are set up using the 'Can Bypass' column on page 2 of the
Engineering tab. (See Engineering Tab Page 2 on page 30.)

Individual Enable
Bypass Checkboxes

Interlocks

28

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

The following table lists the functions on the Maintenance tab.


Table 8 - Maintenance Tab Descriptions
Function

Action

Security

Enable Bypass

Click an interlock condition that can


be bypassed, one that has a white
checkbox, to enable bypass of that
individual interlock.
See Engineering Tab Page 2 on
page 30 for information on how to
make interlock conditions active.

Bypass
Cfg_Bypassable
Permissives
and Interlocks
(Code H)

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Configuration Parameters

29

Interlocks with First Out and Bypass (P_Intlk)

Engineering Tab
The Engineering tab provides access to device configuration parameters and
ranges, options for device and I/O setup, displayed text, and
faceplate-to-faceplate navigation settings, for initial system commissioning or
later system changes.
The Engineering tab is divided into three pages.

Engineering Tab Page 1


On page 1 of the Engineering tab, you can configure the description, label, and
tag for the device.

Configure Description,
Label, and Tag

30

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

The following table lists the functions on page 1 of the Engineering tab.
Table 9 - Engineering Tab Page 1 Descriptions
Function

Action

Security

Configuration Parameters

Description

Type the text description of the


interlock set. It appears on the title
bar of the faceplate.

Engineering
Configuration
(Code E)

Cfg_CondTxt[0]Cfg_CondTxt[15]

Label

Type the label to show on the graphic


symbol.

Cfg_Label

Tag

Type the tag name to show on the


faceplate and Tooltip.
IMPORTANT: Pausing the mouse
over this field displays a tool tip with
the configured Logix tag/path.

Cfg_Tag

Clear Program
Commands on
Receipt

Check to clear Program commands on


receipt.

Cfg_PCmdClear

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

31

Interlocks with First Out and Bypass (P_Intlk)

Engineering Tab Page 2

Up to 16 interlock inputs can be configured on page 2 of the Engineering tab. For


each interlock, the following can be configured.
Table 10 - Engineering Tab Page 2 Descriptions

32

Function

Action

Security
Required

Configuration Parameters

Descriptions

Type the text description of each


interlock condition used. The
interlocks with text entered appear
on the Operator tab of the faceplate.
If the text for a condition is empty
(null), that interlock is not shown.

Engineering
Configuration
(Code E)

Cfg_Desc

OK State

Selects the state of the corresponding


interlock that is the OK to Run state.

Cfg_OKState

Can Bypass

Check to indicate that the


corresponding interlock can be
bypassed.
See Maintenance Tab on page 26 for
information on bypassing interlocks.

Cfg_Bypassable

Must Reset

Check to indicate that the


corresponding interlock is latched
and must be reset.

Cfg_Latched

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Interlocks with First Out and Bypass (P_Intlk)

Engineering Tab Page 3

Navigation for the 16 interlock inputs is configured on page 3 of the Engineering


tab. For each interlock, the following can be configured.
Table 11 - Engineering Tab Page 3 Descriptions
Function

Action

Security
Required

Configuration Parameters

Allow Navigation to
Interlock Input
Objects

Check to enable navigation for the


corresponding interlock input object.

Engineering
Configuration
(Code E)

Cfg_HasNav

Navigation Tag

Type the name of the tag to navigate


to when the interlock description on
the Operator tab is clicked.

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Cfg_NavTag[0]Cfg_NavTag[15]

33

Interlocks with First Out and Bypass (P_Intlk)

Interlock Faceplate Help

34

Rockwell Automation Publication SYSLIB-RM004F-EN-E - April 2015

Rockwell Automation Support


Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support you can find technical and application notes, sample code, and links to
software service packs. You can also visit our Support Center at https://rockwellautomation.custhelp.com/ for software
updates, support chats and forums, technical information, FAQs, and to sign up for product notification updates.
In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more
information, contact your local distributor or Rockwell Automation representative, or visit
http://www.rockwellautomation.com/services/online-phone.

Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this
manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada

1.440.646.3434

Outside United States or Canada

Use the Worldwide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local


Rockwell Automation representative.

New Product Satisfaction Return


Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the
manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States

Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
distributor to complete the return process.

Outside United States

Please contact your local Rockwell Automation representative for the return procedure.

Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this
document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

Rockwell Automation maintains current product environmental information on its website at


http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page.

Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400

Publication SYSLIB-RM004F-EN-E - April 2015


Supersedes Publication SYSLIB-RM004E-EN-E - August 2014

Copyright 2015 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like