1. SPECIFICATIONS
1.1 Electronic Specifications
Operating Voltage
12 or 24 VDC 20% Select by DIP Switch
Adjustment
Speed, GAIN, and DROOPI
Start-up Fuel Limit
Output Current
Max. 15 A
Power Input
Voltage
Current
12 or 24 VDC 20%
Rated above maximum actuator stall
current
Temp. Stability
Better than 0.5% between -40 ~ 75
Mechanical Vibration
1G @ 18 ~ 30 Hz, 2.5G @ 48 ~ 70 Hz
Relative Humidity
< 95%
Operating Temperature
-40 ~ 85
Speed Band
0.25 % at steady state
Storage Temperature
-40 ~ 85
Dimensions
150mm L * 135mm W * 40mm H
Weight
860g 2%
DYN1-10693-001-0-12/24
1200 ~ 2500 Hz
DYN1-10693-002-0-12/24
1200 ~ 2500 Hz
DYN1-10694-001-0-12/24
2500 ~ 5000 Hz
DYN1-10694-002-0-12/24
2500 ~ 5000 Hz
DYN1-10695-000-0-12/24
2500 ~ 5000 Hz
______________________________________________________________________________________
2
EG1069X
2. FUNCTIONS
2. Fuel Ramp
Desired
Engine RPM
Engine
RPM
lsochronous
Operation Mode
Engine Load
100%
Figure 1
an
______________________________________________________________________________________
EG1069X
No load
Engine RPM
Adjustadle
Desired
Engine RPM
Engine
RPM
ON
O
F
F
OFF
Side View
"on"
ON
OFF
Side View
"off "
1 2
0%
% of Engine Load
100%
Figure 2
3. INSTALLATION
3.1 Mount EG1069X in the control panel.
3.2 Connect the wiring as shown in Section
3.4 or according to other particular
wiring diagram.
1. Choose a hole in actuator arm which causes
actuator to rotate through its maximum rotation to
provide minimum to maximum fuel. (Do not
bottom out the Actuator leave 2 to 3 degrees
before the off position)
CAUTION!!
As a safety measure, the engine should be
equipped with and independent overspeed
shutdown device in the event of failure cutting
power to governor system.
NOTE
For some diesel engines, better operation may
be obtained by placing SW1 in ON position. If
difficulty experience in OFF position, try SW1
ON and recalibrate.
EG1069X
ON
MAX
OFF
SW 1 2 3 4 5 6 7
SW1-OFF-DIESEL
SW1-ON -GAS
SW2-OFF-8000 ACT
SW2-ON -8200,8400 ACT
SW3-ON -12V OFF-24V
START-UP
FUEL
MAX
RAMP
TIME
KUTAI
DROOP
ELECTRONICS
GAIN
REMOTE
SPEED POT
1 2 3 4 5 67
INC
_
2
Black
ACT
8V
4V
ILS
10
MPU
11
Red
TP1 TP2
SPEED
5,
Black
White
Cable A
Red
Red
Black
Cable C
Cable B
_
R
DC Power
Magnetic
Pickup
CCW
5K
Cable C
CW
Wiring Drawing
Actuator
Figure 3
1 2 3 4 5 6 7
DIP SW Positions
______________________________________________________________________________________
EG1069X
250 ~ 1200 Hz
SW5 ON for
1200 ~ 2500 Hz
SW6 ON for
2500 ~ 5000 Hz
SW7 ON for
5000 ~ 9500 Hz
Governor Controls
DROOP
GAIN
SPEED
START-UP FUEL
RAMP TIME
Ramp Time
4. CALIBRATION OF DYN1-1069X
4.1 Connection Information
1 When using an ILS unit, the remote speed
potentiometer may be left connected to the
controller as shown in the Figure 3.
2 When an ILS unit is used, connect 3-wire
shielded cable to terminals 6, 7 and 8. Connect
drain shield wire is to terminal 10 at EG1069X
only. Other end of drain shield wire is to be cut off
and taped.
Turning potentiometer
DROOP.
NOTE
clockwise
increases
NOTE
Except for the speed adjustment, the
potentiometers have internal stops at the 0 and
100% positions.
6. With the engine unloaded, finalize the settings, I
and GAIN adjustments as follows:
(1) Turn the GAIN adjustment clockwise slowly until
the actuator lever oscillates. (One may need to
disturb the actuator lever to cause oscillation.)
(2) Reduce
the
GAIN
adjustment
slowly
counterclockwise until the lever is stable. Upset
the lever by hand..
(3) If the lever oscillates 3 to 5 diminishing
oscillations and stops, the setting is correct
(4) If system performance to load changes is
satisfactory, omit step (5) and (6).
(5) Reduce the GAIN setting counterclockwise one
division. Next, turn the I adjustment fully
clockwise while observing the actuator lever.
(6) If the lever does not become unstable, upset it by
hand. When the lever slowly oscillates, turn the
adjustment counterclockwise slowly until the
lever is stable.
(7) Upset the lever again; it should oscillate 3 to 5
times and then become stable for optimum
response.
______________________________________________________________________________________
6
EG1069X
5. TROUBLESHOOTING CHART
PROBLEM
CORRECTIVE ACTION
1. Check magnetic pickup leads for proper shielded wire or open shield.
Verify and correct wiring as necessary. Be sure there is no jumper
between terminals 2 and 3.
2. Failsafe circuit in the controller may be damaged or defective. Replace
EG1069X.
3. With DC power OFF remove leads at actuator. Check continuity of
each terminal to case. There should be no continuity between any
terminal and case of EG1069X. If continuity is defected, replace the
controller.
4. If remote speed potentiometer has been connected to terminals 6, 7
and 9 of the controller, disconnect these leads. Turn DC power ON to
the governor if the actuator is now normal. Proceed to corrective
actions for the next problem.
______________________________________________________________________________________
EG1069X
PROBLEM
CORRECTIVE ACTION
Improper
operation
from
remote speed potentiometer
1. Make sure fuel is available. Check fuel to engine. Check for correct
wiring to the automatic shutdown circuits.
2. Air may be trapped in fuel line. Check fuel lines for leaks.
3. Try to operate engine manually.
______________________________________________________________________________________
8
EG1069X
EG1069X
Generator Electronic Governor Controller
Operation Manual
Headquarters : No.3, Lane 201, Chien Fu ST., Chyan Jenn Dist., Kaohsiung, TAIWAN
Tel : + 886-7-8121771
Fax : + 886-7-8121775
URL : http://www.kutai.com.tw
1. SPECIFICATIONS
1.1 Electronic Specifications
Operating Voltage
12 or 24 VDC 20% Select by DIP Switch
Adjustment
Speed, GAIN, and DROOPI
Start-up Fuel Limit
Output Current
Max. 15 A
Power Input
Voltage
Current
12 or 24 VDC 20%
Rated above maximum actuator stall
current
Temp. Stability
Better than 0.5% between -40 ~ 75
Mechanical Vibration
1G @ 18 ~ 30 Hz, 2.5G @ 48 ~ 70 Hz
Relative Humidity
< 95%
Operating Temperature
-40 ~ 85
Speed Band
0.25 % at steady state
Storage Temperature
-40 ~ 85
Dimensions
150mm L * 135mm W * 40mm H
Weight
860g 2%
DYN1-10693-001-0-12/24
1200 ~ 2500 Hz
DYN1-10693-002-0-12/24
1200 ~ 2500 Hz
DYN1-10694-001-0-12/24
2500 ~ 5000 Hz
DYN1-10694-002-0-12/24
2500 ~ 5000 Hz
DYN1-10695-000-0-12/24
2500 ~ 5000 Hz
______________________________________________________________________________________
2
EG1069X
2. FUNCTIONS
2. Fuel Ramp
Desired
Engine RPM
Engine
RPM
lsochronous
Operation Mode
Engine Load
100%
Figure 1
an
______________________________________________________________________________________
EG1069X
No load
Engine RPM
Adjustadle
Desired
Engine RPM
Engine
RPM
ON
O
F
F
OFF
Side View
"on"
ON
OFF
Side View
"off "
1 2
0%
% of Engine Load
100%
Figure 2
3. INSTALLATION
3.1 Mount EG1069X in the control panel.
3.2 Connect the wiring as shown in Section
3.4 or according to other particular
wiring diagram.
1. Choose a hole in actuator arm which causes
actuator to rotate through its maximum rotation to
provide minimum to maximum fuel. (Do not
bottom out the Actuator leave 2 to 3 degrees
before the off position)
CAUTION!!
As a safety measure, the engine should be
equipped with and independent overspeed
shutdown device in the event of failure cutting
power to governor system.
NOTE
For some diesel engines, better operation may
be obtained by placing SW1 in ON position. If
difficulty experience in OFF position, try SW1
ON and recalibrate.
EG1069X
ON
MAX
OFF
SW 1 2 3 4 5 6 7
SW1-OFF-DIESEL
SW1-ON -GAS
SW2-OFF-8000 ACT
SW2-ON -8200,8400 ACT
SW3-ON -12V OFF-24V
START-UP
FUEL
MAX
RAMP
TIME
KUTAI
DROOP
ELECTRONICS
GAIN
REMOTE
SPEED POT
1 2 3 4 5 67
INC
_
2
Black
ACT
8V
4V
ILS
10
MPU
11
Red
TP1 TP2
SPEED
5,
Black
White
Cable A
Red
Red
Black
Cable C
Cable B
_
R
DC Power
Magnetic
Pickup
CCW
5K
Cable C
CW
Wiring Drawing
Actuator
Figure 3
1 2 3 4 5 6 7
DIP SW Positions
______________________________________________________________________________________
EG1069X
250 ~ 1200 Hz
SW5 ON for
1200 ~ 2500 Hz
SW6 ON for
2500 ~ 5000 Hz
SW7 ON for
5000 ~ 9500 Hz
Governor Controls
DROOP
GAIN
SPEED
START-UP FUEL
RAMP TIME
Ramp Time
4. CALIBRATION OF DYN1-1069X
4.1 Connection Information
1 When using an ILS unit, the remote speed
potentiometer may be left connected to the
controller as shown in the Figure 3.
2 When an ILS unit is used, connect 3-wire
shielded cable to terminals 6, 7 and 8. Connect
drain shield wire is to terminal 10 at EG1069X
only. Other end of drain shield wire is to be cut off
and taped.
Turning potentiometer
DROOP.
NOTE
clockwise
increases
NOTE
Except for the speed adjustment, the
potentiometers have internal stops at the 0 and
100% positions.
6. With the engine unloaded, finalize the settings, I
and GAIN adjustments as follows:
(1) Turn the GAIN adjustment clockwise slowly until
the actuator lever oscillates. (One may need to
disturb the actuator lever to cause oscillation.)
(2) Reduce
the
GAIN
adjustment
slowly
counterclockwise until the lever is stable. Upset
the lever by hand..
(3) If the lever oscillates 3 to 5 diminishing
oscillations and stops, the setting is correct
(4) If system performance to load changes is
satisfactory, omit step (5) and (6).
(5) Reduce the GAIN setting counterclockwise one
division. Next, turn the I adjustment fully
clockwise while observing the actuator lever.
(6) If the lever does not become unstable, upset it by
hand. When the lever slowly oscillates, turn the
adjustment counterclockwise slowly until the
lever is stable.
(7) Upset the lever again; it should oscillate 3 to 5
times and then become stable for optimum
response.
______________________________________________________________________________________
6
EG1069X
5. TROUBLESHOOTING CHART
PROBLEM
CORRECTIVE ACTION
1. Check magnetic pickup leads for proper shielded wire or open shield.
Verify and correct wiring as necessary. Be sure there is no jumper
between terminals 2 and 3.
2. Failsafe circuit in the controller may be damaged or defective. Replace
EG1069X.
3. With DC power OFF remove leads at actuator. Check continuity of
each terminal to case. There should be no continuity between any
terminal and case of EG1069X. If continuity is defected, replace the
controller.
4. If remote speed potentiometer has been connected to terminals 6, 7
and 9 of the controller, disconnect these leads. Turn DC power ON to
the governor if the actuator is now normal. Proceed to corrective
actions for the next problem.
______________________________________________________________________________________
EG1069X
PROBLEM
CORRECTIVE ACTION
Improper
operation
from
remote speed potentiometer
1. Make sure fuel is available. Check fuel to engine. Check for correct
wiring to the automatic shutdown circuits.
2. Air may be trapped in fuel line. Check fuel lines for leaks.
3. Try to operate engine manually.
______________________________________________________________________________________
8
EG1069X
EG1069X
Generator Electronic Governor Controller
Operation Manual
Headquarters : No.3, Lane 201, Chien Fu ST., Chyan Jenn Dist., Kaohsiung, TAIWAN
Tel : + 886-7-8121771
Fax : + 886-7-8121775
URL : http://www.kutai.com.tw
1. SPECIFICATIONS
1.1 Electronic Specifications
Operating Voltage
12 or 24 VDC 20% Select by DIP Switch
Adjustment
Speed, GAIN, and DROOPI
Start-up Fuel Limit
Output Current
Max. 15 A
Power Input
Voltage
Current
12 or 24 VDC 20%
Rated above maximum actuator stall
current
Temp. Stability
Better than 0.5% between -40 ~ 75
Mechanical Vibration
1G @ 18 ~ 30 Hz, 2.5G @ 48 ~ 70 Hz
Relative Humidity
< 95%
Operating Temperature
-40 ~ 85
Speed Band
0.25 % at steady state
Storage Temperature
-40 ~ 85
Dimensions
150mm L * 135mm W * 40mm H
Weight
860g 2%
DYN1-10693-001-0-12/24
1200 ~ 2500 Hz
DYN1-10693-002-0-12/24
1200 ~ 2500 Hz
DYN1-10694-001-0-12/24
2500 ~ 5000 Hz
DYN1-10694-002-0-12/24
2500 ~ 5000 Hz
DYN1-10695-000-0-12/24
2500 ~ 5000 Hz
______________________________________________________________________________________
2
EG1069X
2. FUNCTIONS
2. Fuel Ramp
Desired
Engine RPM
Engine
RPM
lsochronous
Operation Mode
Engine Load
100%
Figure 1
an
______________________________________________________________________________________
EG1069X
No load
Engine RPM
Adjustadle
Desired
Engine RPM
Engine
RPM
ON
O
F
F
OFF
Side View
"on"
ON
OFF
Side View
"off "
1 2
0%
% of Engine Load
100%
Figure 2
3. INSTALLATION
3.1 Mount EG1069X in the control panel.
3.2 Connect the wiring as shown in Section
3.4 or according to other particular
wiring diagram.
1. Choose a hole in actuator arm which causes
actuator to rotate through its maximum rotation to
provide minimum to maximum fuel. (Do not
bottom out the Actuator leave 2 to 3 degrees
before the off position)
CAUTION!!
As a safety measure, the engine should be
equipped with and independent overspeed
shutdown device in the event of failure cutting
power to governor system.
NOTE
For some diesel engines, better operation may
be obtained by placing SW1 in ON position. If
difficulty experience in OFF position, try SW1
ON and recalibrate.
EG1069X
ON
MAX
OFF
SW 1 2 3 4 5 6 7
SW1-OFF-DIESEL
SW1-ON -GAS
SW2-OFF-8000 ACT
SW2-ON -8200,8400 ACT
SW3-ON -12V OFF-24V
START-UP
FUEL
MAX
RAMP
TIME
KUTAI
DROOP
ELECTRONICS
GAIN
REMOTE
SPEED POT
1 2 3 4 5 67
INC
_
2
Black
ACT
8V
4V
ILS
10
MPU
11
Red
TP1 TP2
SPEED
5,
Black
White
Cable A
Red
Red
Black
Cable C
Cable B
_
R
DC Power
Magnetic
Pickup
CCW
5K
Cable C
CW
Wiring Drawing
Actuator
Figure 3
1 2 3 4 5 6 7
DIP SW Positions
______________________________________________________________________________________
EG1069X
250 ~ 1200 Hz
SW5 ON for
1200 ~ 2500 Hz
SW6 ON for
2500 ~ 5000 Hz
SW7 ON for
5000 ~ 9500 Hz
Governor Controls
DROOP
GAIN
SPEED
START-UP FUEL
RAMP TIME
Ramp Time
4. CALIBRATION OF DYN1-1069X
4.1 Connection Information
1 When using an ILS unit, the remote speed
potentiometer may be left connected to the
controller as shown in the Figure 3.
2 When an ILS unit is used, connect 3-wire
shielded cable to terminals 6, 7 and 8. Connect
drain shield wire is to terminal 10 at EG1069X
only. Other end of drain shield wire is to be cut off
and taped.
Turning potentiometer
DROOP.
NOTE
clockwise
increases
NOTE
Except for the speed adjustment, the
potentiometers have internal stops at the 0 and
100% positions.
6. With the engine unloaded, finalize the settings, I
and GAIN adjustments as follows:
(1) Turn the GAIN adjustment clockwise slowly until
the actuator lever oscillates. (One may need to
disturb the actuator lever to cause oscillation.)
(2) Reduce
the
GAIN
adjustment
slowly
counterclockwise until the lever is stable. Upset
the lever by hand..
(3) If the lever oscillates 3 to 5 diminishing
oscillations and stops, the setting is correct
(4) If system performance to load changes is
satisfactory, omit step (5) and (6).
(5) Reduce the GAIN setting counterclockwise one
division. Next, turn the I adjustment fully
clockwise while observing the actuator lever.
(6) If the lever does not become unstable, upset it by
hand. When the lever slowly oscillates, turn the
adjustment counterclockwise slowly until the
lever is stable.
(7) Upset the lever again; it should oscillate 3 to 5
times and then become stable for optimum
response.
______________________________________________________________________________________
6
EG1069X
5. TROUBLESHOOTING CHART
PROBLEM
CORRECTIVE ACTION
1. Check magnetic pickup leads for proper shielded wire or open shield.
Verify and correct wiring as necessary. Be sure there is no jumper
between terminals 2 and 3.
2. Failsafe circuit in the controller may be damaged or defective. Replace
EG1069X.
3. With DC power OFF remove leads at actuator. Check continuity of
each terminal to case. There should be no continuity between any
terminal and case of EG1069X. If continuity is defected, replace the
controller.
4. If remote speed potentiometer has been connected to terminals 6, 7
and 9 of the controller, disconnect these leads. Turn DC power ON to
the governor if the actuator is now normal. Proceed to corrective
actions for the next problem.
______________________________________________________________________________________
EG1069X
PROBLEM
CORRECTIVE ACTION
Improper
operation
from
remote speed potentiometer
1. Make sure fuel is available. Check fuel to engine. Check for correct
wiring to the automatic shutdown circuits.
2. Air may be trapped in fuel line. Check fuel lines for leaks.
3. Try to operate engine manually.
______________________________________________________________________________________
8
EG1069X