Eg1069x Manual en PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

EG1069X

Generator Electronic Governor Controller


Operation Manual

Smoke Limit Controller


Compatible with Barber Colman Dyn1-1069X series
*Use for reference purpose only and not a genuine Barber Colman product

Headquarters : No.3, Lane 201, Chien Fu ST., Chyan Jenn Dist., Kaohsiung, TAIWAN
Tel : + 886-7-8121771

Fax : + 886-7-8121775

URL : http://www.kutai.com.tw

1. SPECIFICATIONS
1.1 Electronic Specifications
Operating Voltage
12 or 24 VDC 20% Select by DIP Switch

Adjustment
Speed, GAIN, and DROOPI
Start-up Fuel Limit

Output Current
Max. 15 A
Power Input
Voltage
Current

Ramp Time 10 Sec

12 or 24 VDC 20%
Rated above maximum actuator stall
current

Temp. Stability
Better than 0.5% between -40 ~ 75

Mechanical Vibration
1G @ 18 ~ 30 Hz, 2.5G @ 48 ~ 70 Hz
Relative Humidity
< 95%
Operating Temperature
-40 ~ 85

Speed Band
0.25 % at steady state

Storage Temperature
-40 ~ 85

Remote Speed Adjustment


Build-in speed setting: 20 turn potentiometer.
Connect 5K potentiometer to terminals 6, 7 and 9.
Adjustable range is approximately 5%.

Dimensions
150mm L * 135mm W * 40mm H
Weight
860g 2%

Remote speed adjust terminals 6,7 and 8.

1.2 Compatible Products


Barber Colman P/N

Speed Input Signal Frequency*

DYN1-10693-001-0-12/24

1200 ~ 2500 Hz

DYN1-10693-002-0-12/24

1200 ~ 2500 Hz

DYN1-10694-001-0-12/24

2500 ~ 5000 Hz

DYN1-10694-002-0-12/24

2500 ~ 5000 Hz

DYN1-10695-000-0-12/24

2500 ~ 5000 Hz

*Speed Input Signal Frequency


Engine RPM Number of Fly Wheel Gear Teeth
Speed Input Signal Frequency (Hz) =
60 seconds
Change Switch(s) for the correct Speed Input Signal Frequency range generated by the magnetic pickup at
the maximum engine operated (RPM) speed.

______________________________________________________________________________________
2

EG1069X

2. FUNCTIONS

2. Fuel Ramp

The EG1069X provides smoke control on start up


for diesel engines using the actuator. The controller
also provides isochronous or droop speed control
with both adjustable start up fuel limit and ramp
time.

On warm or hot engines, a specific fuel limit


setting will control start-up smoke, but not
completely. A warm or hot engine does not need
the same fuel limit to start as a cold engine does.

2.1 EG1069X Electronic Controller


EG1069X is the processing (Control) unit for the
Actuator governor assembly.
It contains the electronics which process the signal
from the magnetic pickup which controls the engine
to the desired speed / RPM set by the customer.
The governor system (Actuator & Controller)
receives its power from the batteries or an AC to DC
power supply supplying 12 or 24 VDC 20% to
match the governor voltage. The average operating
current consumption is 2.5 to 3.5 amperes and the
highest consumption is 14.75 amperes during
engine start-up or during a large load change.

Ramp time can be set from 0 to 10 seconds. The


ramp time starts from release of the failsafe,
allowing fuel setting to increase over the selected
ramp time.

2.4 Isochronous Operation


Isochronous operation is obtained by setting droop
potentiometer fully counterclockwise.
EG1069X is normally operated in the isochronous
mode; i.e., engine RPM is constant (0.25%)under
steady state load conditions, up to the engines
maximum capability, regardless of load on the
engine.

Desired
Engine RPM

2.2 Component Location


1. The controller EG1069X is mounted or installed
in the engine control panel or cabinet.
2. The Actuator is mounted on the engine next to
the fuel injection system.
3. The magnetic pickup is normally mounted in the
flywheel housing in such a way that it can count
the teeth on the starter ring gear.

2.3 Smoke Limiting Features

Engine
RPM

lsochronous
Operation Mode

Engine Load

100%

Figure 1

EG1069X has two features for smoke limiting:


1. Restrictive Fuel Limiting
The start-up fuel limit potentiometer will allow the
operator to set a specific fuel limit on start-up.
Before starting the engine, turn the Fuel Limiting
to 0 and turn the Ramp Time to10.
Fuel limit is set by cranking the engine and
turning the fuel limit potentiometer clockwise until
the engine starts.
Repeat step (2) until the engine can start and
keep in the lowest speed.
After engine starts, turn potentiometer
additional 3 to 5% to ensure positive starts.

an

______________________________________________________________________________________
EG1069X

2.5 DROOP Operation


Droop operation is obtained by setting the droop
potentiometer. Clockwise increases the droop. The
amount of droop for a given setting depends on the
magnetic pickup frequency and no load to full load
actuator shaft rotation.
A droop potentiometer setting of 10 oclock will give
about 4% droop, no load to full load when the pickup
frequency is 4260Hz and actuator shaft rotation is
approximately 30 degrees from no load to full load.
Lower pickup frequency or smaller shaft rotation
results in less droop for the system.

No load
Engine RPM

3.3 Proper Procedures for Setting Switches


SW1 and SW2
EG1069X has two response ranges for matching
either the diesel or gas engine dynamics.
Set SW1 to the OFF position for diesel engine
applications.
Set SW1 to the ON position for gas/gasoline
engine applications.
Set SW2 to OFF, this level is nominally 6.3
amperes for actuators with lower current level.
Set SW2 to ON, this level is nominally 7.3
amperes for actuators with lower current level.
Top View
O
N

Adjustadle
Desired
Engine RPM

Engine
RPM

ON
O
F
F

OFF

Side View
"on"

ON

OFF

Side View
"off "

1 2

0%

% of Engine Load

100%

Figure 2

2.6 Remote Speed Adjustment


An optional remote speed selector is available for
adjusting engine RPM from up to 90 meters (300 ft.)
away from the engine. See 3.4 Electrical Wiring
Schematic. The potentiometer can be connected for
a narrow (fine) or wide speed range control.

3. INSTALLATION
3.1 Mount EG1069X in the control panel.
3.2 Connect the wiring as shown in Section
3.4 or according to other particular
wiring diagram.
1. Choose a hole in actuator arm which causes
actuator to rotate through its maximum rotation to
provide minimum to maximum fuel. (Do not
bottom out the Actuator leave 2 to 3 degrees
before the off position)

The drawings above should clarify any confusion


about switch settings. The easiest way to set the
switches is to apply pressure with a small pointed
object until the switch clicks into position.

SW1 in the above drawing is in ON position, and


SW2 in the above drawing is in OFF position.

CAUTION!!
As a safety measure, the engine should be
equipped with and independent overspeed
shutdown device in the event of failure cutting
power to governor system.

NOTE
For some diesel engines, better operation may
be obtained by placing SW1 in ON position. If
difficulty experience in OFF position, try SW1
ON and recalibrate.

2. Non-Linear linkage to actuator is proper for best


operation on Gas Engine providing low GAIN at
light loads and high GAIN at heavy loads. But
linear in preferred for Diesel Engines.
______________________________________________________________________________________
4

EG1069X

3.4. Typical Wiring Diagram & Controller Installation Dimensions

ON

MAX

OFF
SW 1 2 3 4 5 6 7

SW1-OFF-DIESEL
SW1-ON -GAS
SW2-OFF-8000 ACT
SW2-ON -8200,8400 ACT
SW3-ON -12V OFF-24V

START-UP
FUEL
MAX

SW4-ON 250 - 1200 Hz

RAMP
TIME

KUTAI

DROOP

ELECTRONICS

SW5-ON 1200 - 2500 Hz

GAIN

SW6-ON 2500 - 5000 Hz

REMOTE
SPEED POT

SW7-ON 5000 - 9500 Hz


SW

1 2 3 4 5 67

INC

_
2

Black

ACT

8V

4V

ILS

10

MPU

11

Red

TP1 TP2

SPEED

5,

Black

White

Cable A
Red

Red

Black

Cable C

Cable B

_
R

DC Power

Magnetic
Pickup
CCW
5K

Cable C

CW

Wiring Drawing
Actuator

*The 5K remote speed potentiometer can be wired


two different ways: See Section 4.1.
1. Connect 5K potentiometer T to terminal #9.
Adjustable range is approximately 5% at 18000
RMP. (See Figure 3)
2. Connect 5K potentiometer through resistor R to
terminal #8. Reducing the value if R (499K)
increases the remote adjustable speed range.
(See Figure 3)

Figure 3

**Cable A, B, C -- should purchase a cable with a


wrapped Mylar supported aluminum foil shield
with a drain wire.
ON
OFF

1 2 3 4 5 6 7
DIP SW Positions

______________________________________________________________________________________
EG1069X

DIP Switch Description


SW1 OFF for Diesel Engine ON for Gas Engine
SW2 OFF for DYNA8000 actuator
ON for DYNA8200 / 8400 actuator

SW3 OFF for 24V I/O, ON for 12V I/O


SW4 ON for

250 ~ 1200 Hz

SW5 ON for

1200 ~ 2500 Hz

SW6 ON for

2500 ~ 5000 Hz

SW7 ON for

5000 ~ 9500 Hz

*When one of the SW4~7 is ON, set others of SW4~7 OFF

Governor Controls
DROOP

Droop Rate Adjustment

GAIN

MPU Output Gain Adjustment

Engine Stability Adjustment

SPEED

Engine Speed Adjustment

START-UP FUEL

Start-Up Fuel Limit

RAMP TIME

Ramp Time

4. CALIBRATION OF DYN1-1069X
4.1 Connection Information
1 When using an ILS unit, the remote speed
potentiometer may be left connected to the
controller as shown in the Figure 3.
2 When an ILS unit is used, connect 3-wire
shielded cable to terminals 6, 7 and 8. Connect
drain shield wire is to terminal 10 at EG1069X
only. Other end of drain shield wire is to be cut off
and taped.

4.2 Calibrations and Adjustments


1. See Figure 3 for a reference guide before making
any adjustments of the potentiometers, DROOP,
I, GAIN and SPEED.
2. Power OFF - engine not operating.
3. Initial potentiometer settings:
Set the I adjustment three divisions from zero
and the GAIN at the second division from zero.
For isochronous operation, set DROOP
counterclockwise to minimum position as shown
in Section 3.3 and 3.4.
For
DROOP
operation,
set
DROOP
potentiometer clockwise to obtain desired
amount of DROOP from no-load to full load.

Turning potentiometer
DROOP.

NOTE

clockwise

increases

If the full 35 rotation of the actuator shaft is


used and the linkage adjusted to use only the
active fuel range, the maximum obtainable
DROOP would be approximately 12% at full
load.
4. If a remote speed potentiometer is used for
narrow range, set it to mid-range. If the remote
speed potentiometer is connected to terminals 6,
7 and 9, a resistor R in the wiper is not needed.
This will provide approximately a 5% adjustable
speed range.
5. Start the engine.
Adjust the controller speed potentiometer until
the engine is operating at the desired engine
RPM. Clockwise increases engine RPM.
If the governor system is unstable, slightly reduce
the GAIN setting.

NOTE
Except for the speed adjustment, the
potentiometers have internal stops at the 0 and
100% positions.
6. With the engine unloaded, finalize the settings, I
and GAIN adjustments as follows:
(1) Turn the GAIN adjustment clockwise slowly until
the actuator lever oscillates. (One may need to
disturb the actuator lever to cause oscillation.)
(2) Reduce
the
GAIN
adjustment
slowly
counterclockwise until the lever is stable. Upset
the lever by hand..
(3) If the lever oscillates 3 to 5 diminishing
oscillations and stops, the setting is correct
(4) If system performance to load changes is
satisfactory, omit step (5) and (6).
(5) Reduce the GAIN setting counterclockwise one
division. Next, turn the I adjustment fully
clockwise while observing the actuator lever.
(6) If the lever does not become unstable, upset it by
hand. When the lever slowly oscillates, turn the
adjustment counterclockwise slowly until the
lever is stable.
(7) Upset the lever again; it should oscillate 3 to 5
times and then become stable for optimum
response.

______________________________________________________________________________________
6

EG1069X

5. TROUBLESHOOTING CHART
PROBLEM

CORRECTIVE ACTION

Governor is completely dead


and actuator lever stays at
minimum position when power
is applied to governor.

1. Check battery voltage at terminals 1 and 2 on controller. Terminal 1 is


positive. Check battery connections and contacts for turning power
ON to the controller.
2. Check for proper linkage setup. Correct and free linkage.
3. Magnetic pickup signal absent or too low. Measure AC voltage across
terminals 10 and 11 while cranking the engine. Voltage should be min.
2.5 VAC.
NOTE:
The voltmeter should have an impedance of 5000 ohms / volts or
higher. Check pole tip gap over gear tooth. Should be 0.037 mm ~ / 0.127 mm.
4. Measure the resistance of the magnetic pickup coil. This should be
above 150 ohm. If there is an open or shorted coil, replace the
magnetic pickup.
5. Measure the resistance of each pin to the metal case of the magnetic
pickup. No continuity should be evident. If there is continuity to the
case, replace the magnetic pickup.
6. DC supply OFF. Place an insulated jumper between terminals 2 and 3
(TP1 and TP2). With DC ON, the actuator should go to full stroke. DC
voltage at terminals 4 and 5 should be within 3voltas of the supply. If
the actuator still does not move to full stroke, continue with steps
below.
7. Measure actuator coil resistance:
If actuator coil is open or shorted to case, replace the actuator.
If governor still does not operate, continue with steps below.
8. Measuring the resistance of each coil lead to the actuator case should
indicate an open circuit on a low scale of the ohm meter. If continuity is
defected, replace the actuator.
9. With DC to the governor ON and the engine OFF, measure the DC
voltage from terminal 6(+) to terminal 2(-). This should be approx.
8VCD. If 8 VCD is not present, replace the controller.
10. Between terminal 7(+) and terminal 2(-), the voltage should be
approx. 4 VDC. If 4VDC is not present, replace the controller.

Actuator goes to full stroke


when DC power is turned on
(Engine is not operating)

1. Check magnetic pickup leads for proper shielded wire or open shield.
Verify and correct wiring as necessary. Be sure there is no jumper
between terminals 2 and 3.
2. Failsafe circuit in the controller may be damaged or defective. Replace
EG1069X.
3. With DC power OFF remove leads at actuator. Check continuity of
each terminal to case. There should be no continuity between any
terminal and case of EG1069X. If continuity is defected, replace the
controller.
4. If remote speed potentiometer has been connected to terminals 6, 7
and 9 of the controller, disconnect these leads. Turn DC power ON to
the governor if the actuator is now normal. Proceed to corrective
actions for the next problem.

______________________________________________________________________________________
EG1069X

PROBLEM

CORRECTIVE ACTION

Improper
operation
from
remote speed potentiometer

1. Investigate wiring to remote speed potentiometer for open or shorted


circuits. Checking wiring.
2. If the leads at terminals 6 and 7 to the remote speed potentiometer are
reversed, speed control by the remote speed potentiometer will be
reversed. Correct wiring.
3. Lead wire to remote speed setting potentiometer should be 3-wire
shielded cable. Verity that the drain shield wire is isolated from ground
at the potentiometer. If terminal 7 lead to the remote speed
potentiometer is open, engine speed will go high. Correct the wiring.
4. If lead 9 (wiper lead to remote potentiometer) is open, there will be no
control by the remote speed potentiometer. Verify and correct wiring.
5. If lead 6 to the clockwise terminal of the remote speed potentiometer
is open, speed will remain at the value set in EG1069X.

Erratic governor operation

1. Measure DC voltage at 1 and 2 on controller terminal strip. Normal


battery voltage should be indicated. If nominal voltage is present,
wiring is correct.
2. Low battery voltage 20% below rated can cause erratic operation.
Check battery and charging system.
3. RFI noise due to incorrect shielding. Correct wiring.
4. RFI noise fed through power supply leads. Connect power leads
directly to the battery.

Slow, small amplitude hunting


of speed or frequency

Sticking or very loose linkage. Correct linkage.

Fast oscillation of governor


linkage

Verity calibration setting of the controller. Readjust setting as necessary.

Engine will not start Actuator


goes to full fuel during cranking

1. Make sure fuel is available. Check fuel to engine. Check for correct
wiring to the automatic shutdown circuits.
2. Air may be trapped in fuel line. Check fuel lines for leaks.
3. Try to operate engine manually.

P.S. Please use the fuse of the original plant.

______________________________________________________________________________________
8

EG1069X

EG1069X
Generator Electronic Governor Controller
Operation Manual

Smoke Limit Controller


Compatible with Barber Colman Dyn1-1069X series
*Use for reference purpose only and not a genuine Barber Colman product

Headquarters : No.3, Lane 201, Chien Fu ST., Chyan Jenn Dist., Kaohsiung, TAIWAN
Tel : + 886-7-8121771

Fax : + 886-7-8121775

URL : http://www.kutai.com.tw

1. SPECIFICATIONS
1.1 Electronic Specifications
Operating Voltage
12 or 24 VDC 20% Select by DIP Switch

Adjustment
Speed, GAIN, and DROOPI
Start-up Fuel Limit

Output Current
Max. 15 A
Power Input
Voltage
Current

Ramp Time 10 Sec

12 or 24 VDC 20%
Rated above maximum actuator stall
current

Temp. Stability
Better than 0.5% between -40 ~ 75

Mechanical Vibration
1G @ 18 ~ 30 Hz, 2.5G @ 48 ~ 70 Hz
Relative Humidity
< 95%
Operating Temperature
-40 ~ 85

Speed Band
0.25 % at steady state

Storage Temperature
-40 ~ 85

Remote Speed Adjustment


Build-in speed setting: 20 turn potentiometer.
Connect 5K potentiometer to terminals 6, 7 and 9.
Adjustable range is approximately 5%.

Dimensions
150mm L * 135mm W * 40mm H
Weight
860g 2%

Remote speed adjust terminals 6,7 and 8.

1.2 Compatible Products


Barber Colman P/N

Speed Input Signal Frequency*

DYN1-10693-001-0-12/24

1200 ~ 2500 Hz

DYN1-10693-002-0-12/24

1200 ~ 2500 Hz

DYN1-10694-001-0-12/24

2500 ~ 5000 Hz

DYN1-10694-002-0-12/24

2500 ~ 5000 Hz

DYN1-10695-000-0-12/24

2500 ~ 5000 Hz

*Speed Input Signal Frequency


Engine RPM Number of Fly Wheel Gear Teeth
Speed Input Signal Frequency (Hz) =
60 seconds
Change Switch(s) for the correct Speed Input Signal Frequency range generated by the magnetic pickup at
the maximum engine operated (RPM) speed.

______________________________________________________________________________________
2

EG1069X

2. FUNCTIONS

2. Fuel Ramp

The EG1069X provides smoke control on start up


for diesel engines using the actuator. The controller
also provides isochronous or droop speed control
with both adjustable start up fuel limit and ramp
time.

On warm or hot engines, a specific fuel limit


setting will control start-up smoke, but not
completely. A warm or hot engine does not need
the same fuel limit to start as a cold engine does.

2.1 EG1069X Electronic Controller


EG1069X is the processing (Control) unit for the
Actuator governor assembly.
It contains the electronics which process the signal
from the magnetic pickup which controls the engine
to the desired speed / RPM set by the customer.
The governor system (Actuator & Controller)
receives its power from the batteries or an AC to DC
power supply supplying 12 or 24 VDC 20% to
match the governor voltage. The average operating
current consumption is 2.5 to 3.5 amperes and the
highest consumption is 14.75 amperes during
engine start-up or during a large load change.

Ramp time can be set from 0 to 10 seconds. The


ramp time starts from release of the failsafe,
allowing fuel setting to increase over the selected
ramp time.

2.4 Isochronous Operation


Isochronous operation is obtained by setting droop
potentiometer fully counterclockwise.
EG1069X is normally operated in the isochronous
mode; i.e., engine RPM is constant (0.25%)under
steady state load conditions, up to the engines
maximum capability, regardless of load on the
engine.

Desired
Engine RPM

2.2 Component Location


1. The controller EG1069X is mounted or installed
in the engine control panel or cabinet.
2. The Actuator is mounted on the engine next to
the fuel injection system.
3. The magnetic pickup is normally mounted in the
flywheel housing in such a way that it can count
the teeth on the starter ring gear.

2.3 Smoke Limiting Features

Engine
RPM

lsochronous
Operation Mode

Engine Load

100%

Figure 1

EG1069X has two features for smoke limiting:


1. Restrictive Fuel Limiting
The start-up fuel limit potentiometer will allow the
operator to set a specific fuel limit on start-up.
Before starting the engine, turn the Fuel Limiting
to 0 and turn the Ramp Time to10.
Fuel limit is set by cranking the engine and
turning the fuel limit potentiometer clockwise until
the engine starts.
Repeat step (2) until the engine can start and
keep in the lowest speed.
After engine starts, turn potentiometer
additional 3 to 5% to ensure positive starts.

an

______________________________________________________________________________________
EG1069X

2.5 DROOP Operation


Droop operation is obtained by setting the droop
potentiometer. Clockwise increases the droop. The
amount of droop for a given setting depends on the
magnetic pickup frequency and no load to full load
actuator shaft rotation.
A droop potentiometer setting of 10 oclock will give
about 4% droop, no load to full load when the pickup
frequency is 4260Hz and actuator shaft rotation is
approximately 30 degrees from no load to full load.
Lower pickup frequency or smaller shaft rotation
results in less droop for the system.

No load
Engine RPM

3.3 Proper Procedures for Setting Switches


SW1 and SW2
EG1069X has two response ranges for matching
either the diesel or gas engine dynamics.
Set SW1 to the OFF position for diesel engine
applications.
Set SW1 to the ON position for gas/gasoline
engine applications.
Set SW2 to OFF, this level is nominally 6.3
amperes for actuators with lower current level.
Set SW2 to ON, this level is nominally 7.3
amperes for actuators with lower current level.
Top View
O
N

Adjustadle
Desired
Engine RPM

Engine
RPM

ON
O
F
F

OFF

Side View
"on"

ON

OFF

Side View
"off "

1 2

0%

% of Engine Load

100%

Figure 2

2.6 Remote Speed Adjustment


An optional remote speed selector is available for
adjusting engine RPM from up to 90 meters (300 ft.)
away from the engine. See 3.4 Electrical Wiring
Schematic. The potentiometer can be connected for
a narrow (fine) or wide speed range control.

3. INSTALLATION
3.1 Mount EG1069X in the control panel.
3.2 Connect the wiring as shown in Section
3.4 or according to other particular
wiring diagram.
1. Choose a hole in actuator arm which causes
actuator to rotate through its maximum rotation to
provide minimum to maximum fuel. (Do not
bottom out the Actuator leave 2 to 3 degrees
before the off position)

The drawings above should clarify any confusion


about switch settings. The easiest way to set the
switches is to apply pressure with a small pointed
object until the switch clicks into position.

SW1 in the above drawing is in ON position, and


SW2 in the above drawing is in OFF position.

CAUTION!!
As a safety measure, the engine should be
equipped with and independent overspeed
shutdown device in the event of failure cutting
power to governor system.

NOTE
For some diesel engines, better operation may
be obtained by placing SW1 in ON position. If
difficulty experience in OFF position, try SW1
ON and recalibrate.

2. Non-Linear linkage to actuator is proper for best


operation on Gas Engine providing low GAIN at
light loads and high GAIN at heavy loads. But
linear in preferred for Diesel Engines.
______________________________________________________________________________________
4

EG1069X

3.4. Typical Wiring Diagram & Controller Installation Dimensions

ON

MAX

OFF
SW 1 2 3 4 5 6 7

SW1-OFF-DIESEL
SW1-ON -GAS
SW2-OFF-8000 ACT
SW2-ON -8200,8400 ACT
SW3-ON -12V OFF-24V

START-UP
FUEL
MAX

SW4-ON 250 - 1200 Hz

RAMP
TIME

KUTAI

DROOP

ELECTRONICS

SW5-ON 1200 - 2500 Hz

GAIN

SW6-ON 2500 - 5000 Hz

REMOTE
SPEED POT

SW7-ON 5000 - 9500 Hz


SW

1 2 3 4 5 67

INC

_
2

Black

ACT

8V

4V

ILS

10

MPU

11

Red

TP1 TP2

SPEED

5,

Black

White

Cable A
Red

Red

Black

Cable C

Cable B

_
R

DC Power

Magnetic
Pickup
CCW
5K

Cable C

CW

Wiring Drawing
Actuator

*The 5K remote speed potentiometer can be wired


two different ways: See Section 4.1.
1. Connect 5K potentiometer T to terminal #9.
Adjustable range is approximately 5% at 18000
RMP. (See Figure 3)
2. Connect 5K potentiometer through resistor R to
terminal #8. Reducing the value if R (499K)
increases the remote adjustable speed range.
(See Figure 3)

Figure 3

**Cable A, B, C -- should purchase a cable with a


wrapped Mylar supported aluminum foil shield
with a drain wire.
ON
OFF

1 2 3 4 5 6 7
DIP SW Positions

______________________________________________________________________________________
EG1069X

DIP Switch Description


SW1 OFF for Diesel Engine ON for Gas Engine
SW2 OFF for DYNA8000 actuator
ON for DYNA8200 / 8400 actuator

SW3 OFF for 24V I/O, ON for 12V I/O


SW4 ON for

250 ~ 1200 Hz

SW5 ON for

1200 ~ 2500 Hz

SW6 ON for

2500 ~ 5000 Hz

SW7 ON for

5000 ~ 9500 Hz

*When one of the SW4~7 is ON, set others of SW4~7 OFF

Governor Controls
DROOP

Droop Rate Adjustment

GAIN

MPU Output Gain Adjustment

Engine Stability Adjustment

SPEED

Engine Speed Adjustment

START-UP FUEL

Start-Up Fuel Limit

RAMP TIME

Ramp Time

4. CALIBRATION OF DYN1-1069X
4.1 Connection Information
1 When using an ILS unit, the remote speed
potentiometer may be left connected to the
controller as shown in the Figure 3.
2 When an ILS unit is used, connect 3-wire
shielded cable to terminals 6, 7 and 8. Connect
drain shield wire is to terminal 10 at EG1069X
only. Other end of drain shield wire is to be cut off
and taped.

4.2 Calibrations and Adjustments


1. See Figure 3 for a reference guide before making
any adjustments of the potentiometers, DROOP,
I, GAIN and SPEED.
2. Power OFF - engine not operating.
3. Initial potentiometer settings:
Set the I adjustment three divisions from zero
and the GAIN at the second division from zero.
For isochronous operation, set DROOP
counterclockwise to minimum position as shown
in Section 3.3 and 3.4.
For
DROOP
operation,
set
DROOP
potentiometer clockwise to obtain desired
amount of DROOP from no-load to full load.

Turning potentiometer
DROOP.

NOTE

clockwise

increases

If the full 35 rotation of the actuator shaft is


used and the linkage adjusted to use only the
active fuel range, the maximum obtainable
DROOP would be approximately 12% at full
load.
4. If a remote speed potentiometer is used for
narrow range, set it to mid-range. If the remote
speed potentiometer is connected to terminals 6,
7 and 9, a resistor R in the wiper is not needed.
This will provide approximately a 5% adjustable
speed range.
5. Start the engine.
Adjust the controller speed potentiometer until
the engine is operating at the desired engine
RPM. Clockwise increases engine RPM.
If the governor system is unstable, slightly reduce
the GAIN setting.

NOTE
Except for the speed adjustment, the
potentiometers have internal stops at the 0 and
100% positions.
6. With the engine unloaded, finalize the settings, I
and GAIN adjustments as follows:
(1) Turn the GAIN adjustment clockwise slowly until
the actuator lever oscillates. (One may need to
disturb the actuator lever to cause oscillation.)
(2) Reduce
the
GAIN
adjustment
slowly
counterclockwise until the lever is stable. Upset
the lever by hand..
(3) If the lever oscillates 3 to 5 diminishing
oscillations and stops, the setting is correct
(4) If system performance to load changes is
satisfactory, omit step (5) and (6).
(5) Reduce the GAIN setting counterclockwise one
division. Next, turn the I adjustment fully
clockwise while observing the actuator lever.
(6) If the lever does not become unstable, upset it by
hand. When the lever slowly oscillates, turn the
adjustment counterclockwise slowly until the
lever is stable.
(7) Upset the lever again; it should oscillate 3 to 5
times and then become stable for optimum
response.

______________________________________________________________________________________
6

EG1069X

5. TROUBLESHOOTING CHART
PROBLEM

CORRECTIVE ACTION

Governor is completely dead


and actuator lever stays at
minimum position when power
is applied to governor.

1. Check battery voltage at terminals 1 and 2 on controller. Terminal 1 is


positive. Check battery connections and contacts for turning power
ON to the controller.
2. Check for proper linkage setup. Correct and free linkage.
3. Magnetic pickup signal absent or too low. Measure AC voltage across
terminals 10 and 11 while cranking the engine. Voltage should be min.
2.5 VAC.
NOTE:
The voltmeter should have an impedance of 5000 ohms / volts or
higher. Check pole tip gap over gear tooth. Should be 0.037 mm ~ / 0.127 mm.
4. Measure the resistance of the magnetic pickup coil. This should be
above 150 ohm. If there is an open or shorted coil, replace the
magnetic pickup.
5. Measure the resistance of each pin to the metal case of the magnetic
pickup. No continuity should be evident. If there is continuity to the
case, replace the magnetic pickup.
6. DC supply OFF. Place an insulated jumper between terminals 2 and 3
(TP1 and TP2). With DC ON, the actuator should go to full stroke. DC
voltage at terminals 4 and 5 should be within 3voltas of the supply. If
the actuator still does not move to full stroke, continue with steps
below.
7. Measure actuator coil resistance:
If actuator coil is open or shorted to case, replace the actuator.
If governor still does not operate, continue with steps below.
8. Measuring the resistance of each coil lead to the actuator case should
indicate an open circuit on a low scale of the ohm meter. If continuity is
defected, replace the actuator.
9. With DC to the governor ON and the engine OFF, measure the DC
voltage from terminal 6(+) to terminal 2(-). This should be approx.
8VCD. If 8 VCD is not present, replace the controller.
10. Between terminal 7(+) and terminal 2(-), the voltage should be
approx. 4 VDC. If 4VDC is not present, replace the controller.

Actuator goes to full stroke


when DC power is turned on
(Engine is not operating)

1. Check magnetic pickup leads for proper shielded wire or open shield.
Verify and correct wiring as necessary. Be sure there is no jumper
between terminals 2 and 3.
2. Failsafe circuit in the controller may be damaged or defective. Replace
EG1069X.
3. With DC power OFF remove leads at actuator. Check continuity of
each terminal to case. There should be no continuity between any
terminal and case of EG1069X. If continuity is defected, replace the
controller.
4. If remote speed potentiometer has been connected to terminals 6, 7
and 9 of the controller, disconnect these leads. Turn DC power ON to
the governor if the actuator is now normal. Proceed to corrective
actions for the next problem.

______________________________________________________________________________________
EG1069X

PROBLEM

CORRECTIVE ACTION

Improper
operation
from
remote speed potentiometer

1. Investigate wiring to remote speed potentiometer for open or shorted


circuits. Checking wiring.
2. If the leads at terminals 6 and 7 to the remote speed potentiometer are
reversed, speed control by the remote speed potentiometer will be
reversed. Correct wiring.
3. Lead wire to remote speed setting potentiometer should be 3-wire
shielded cable. Verity that the drain shield wire is isolated from ground
at the potentiometer. If terminal 7 lead to the remote speed
potentiometer is open, engine speed will go high. Correct the wiring.
4. If lead 9 (wiper lead to remote potentiometer) is open, there will be no
control by the remote speed potentiometer. Verify and correct wiring.
5. If lead 6 to the clockwise terminal of the remote speed potentiometer
is open, speed will remain at the value set in EG1069X.

Erratic governor operation

1. Measure DC voltage at 1 and 2 on controller terminal strip. Normal


battery voltage should be indicated. If nominal voltage is present,
wiring is correct.
2. Low battery voltage 20% below rated can cause erratic operation.
Check battery and charging system.
3. RFI noise due to incorrect shielding. Correct wiring.
4. RFI noise fed through power supply leads. Connect power leads
directly to the battery.

Slow, small amplitude hunting


of speed or frequency

Sticking or very loose linkage. Correct linkage.

Fast oscillation of governor


linkage

Verity calibration setting of the controller. Readjust setting as necessary.

Engine will not start Actuator


goes to full fuel during cranking

1. Make sure fuel is available. Check fuel to engine. Check for correct
wiring to the automatic shutdown circuits.
2. Air may be trapped in fuel line. Check fuel lines for leaks.
3. Try to operate engine manually.

P.S. Please use the fuse of the original plant.

______________________________________________________________________________________
8

EG1069X

EG1069X
Generator Electronic Governor Controller
Operation Manual

Smoke Limit Controller


Compatible with Barber Colman Dyn1-1069X series
*Use for reference purpose only and not a genuine Barber Colman product

Headquarters : No.3, Lane 201, Chien Fu ST., Chyan Jenn Dist., Kaohsiung, TAIWAN
Tel : + 886-7-8121771

Fax : + 886-7-8121775

URL : http://www.kutai.com.tw

1. SPECIFICATIONS
1.1 Electronic Specifications
Operating Voltage
12 or 24 VDC 20% Select by DIP Switch

Adjustment
Speed, GAIN, and DROOPI
Start-up Fuel Limit

Output Current
Max. 15 A
Power Input
Voltage
Current

Ramp Time 10 Sec

12 or 24 VDC 20%
Rated above maximum actuator stall
current

Temp. Stability
Better than 0.5% between -40 ~ 75

Mechanical Vibration
1G @ 18 ~ 30 Hz, 2.5G @ 48 ~ 70 Hz
Relative Humidity
< 95%
Operating Temperature
-40 ~ 85

Speed Band
0.25 % at steady state

Storage Temperature
-40 ~ 85

Remote Speed Adjustment


Build-in speed setting: 20 turn potentiometer.
Connect 5K potentiometer to terminals 6, 7 and 9.
Adjustable range is approximately 5%.

Dimensions
150mm L * 135mm W * 40mm H
Weight
860g 2%

Remote speed adjust terminals 6,7 and 8.

1.2 Compatible Products


Barber Colman P/N

Speed Input Signal Frequency*

DYN1-10693-001-0-12/24

1200 ~ 2500 Hz

DYN1-10693-002-0-12/24

1200 ~ 2500 Hz

DYN1-10694-001-0-12/24

2500 ~ 5000 Hz

DYN1-10694-002-0-12/24

2500 ~ 5000 Hz

DYN1-10695-000-0-12/24

2500 ~ 5000 Hz

*Speed Input Signal Frequency


Engine RPM Number of Fly Wheel Gear Teeth
Speed Input Signal Frequency (Hz) =
60 seconds
Change Switch(s) for the correct Speed Input Signal Frequency range generated by the magnetic pickup at
the maximum engine operated (RPM) speed.

______________________________________________________________________________________
2

EG1069X

2. FUNCTIONS

2. Fuel Ramp

The EG1069X provides smoke control on start up


for diesel engines using the actuator. The controller
also provides isochronous or droop speed control
with both adjustable start up fuel limit and ramp
time.

On warm or hot engines, a specific fuel limit


setting will control start-up smoke, but not
completely. A warm or hot engine does not need
the same fuel limit to start as a cold engine does.

2.1 EG1069X Electronic Controller


EG1069X is the processing (Control) unit for the
Actuator governor assembly.
It contains the electronics which process the signal
from the magnetic pickup which controls the engine
to the desired speed / RPM set by the customer.
The governor system (Actuator & Controller)
receives its power from the batteries or an AC to DC
power supply supplying 12 or 24 VDC 20% to
match the governor voltage. The average operating
current consumption is 2.5 to 3.5 amperes and the
highest consumption is 14.75 amperes during
engine start-up or during a large load change.

Ramp time can be set from 0 to 10 seconds. The


ramp time starts from release of the failsafe,
allowing fuel setting to increase over the selected
ramp time.

2.4 Isochronous Operation


Isochronous operation is obtained by setting droop
potentiometer fully counterclockwise.
EG1069X is normally operated in the isochronous
mode; i.e., engine RPM is constant (0.25%)under
steady state load conditions, up to the engines
maximum capability, regardless of load on the
engine.

Desired
Engine RPM

2.2 Component Location


1. The controller EG1069X is mounted or installed
in the engine control panel or cabinet.
2. The Actuator is mounted on the engine next to
the fuel injection system.
3. The magnetic pickup is normally mounted in the
flywheel housing in such a way that it can count
the teeth on the starter ring gear.

2.3 Smoke Limiting Features

Engine
RPM

lsochronous
Operation Mode

Engine Load

100%

Figure 1

EG1069X has two features for smoke limiting:


1. Restrictive Fuel Limiting
The start-up fuel limit potentiometer will allow the
operator to set a specific fuel limit on start-up.
Before starting the engine, turn the Fuel Limiting
to 0 and turn the Ramp Time to10.
Fuel limit is set by cranking the engine and
turning the fuel limit potentiometer clockwise until
the engine starts.
Repeat step (2) until the engine can start and
keep in the lowest speed.
After engine starts, turn potentiometer
additional 3 to 5% to ensure positive starts.

an

______________________________________________________________________________________
EG1069X

2.5 DROOP Operation


Droop operation is obtained by setting the droop
potentiometer. Clockwise increases the droop. The
amount of droop for a given setting depends on the
magnetic pickup frequency and no load to full load
actuator shaft rotation.
A droop potentiometer setting of 10 oclock will give
about 4% droop, no load to full load when the pickup
frequency is 4260Hz and actuator shaft rotation is
approximately 30 degrees from no load to full load.
Lower pickup frequency or smaller shaft rotation
results in less droop for the system.

No load
Engine RPM

3.3 Proper Procedures for Setting Switches


SW1 and SW2
EG1069X has two response ranges for matching
either the diesel or gas engine dynamics.
Set SW1 to the OFF position for diesel engine
applications.
Set SW1 to the ON position for gas/gasoline
engine applications.
Set SW2 to OFF, this level is nominally 6.3
amperes for actuators with lower current level.
Set SW2 to ON, this level is nominally 7.3
amperes for actuators with lower current level.
Top View
O
N

Adjustadle
Desired
Engine RPM

Engine
RPM

ON
O
F
F

OFF

Side View
"on"

ON

OFF

Side View
"off "

1 2

0%

% of Engine Load

100%

Figure 2

2.6 Remote Speed Adjustment


An optional remote speed selector is available for
adjusting engine RPM from up to 90 meters (300 ft.)
away from the engine. See 3.4 Electrical Wiring
Schematic. The potentiometer can be connected for
a narrow (fine) or wide speed range control.

3. INSTALLATION
3.1 Mount EG1069X in the control panel.
3.2 Connect the wiring as shown in Section
3.4 or according to other particular
wiring diagram.
1. Choose a hole in actuator arm which causes
actuator to rotate through its maximum rotation to
provide minimum to maximum fuel. (Do not
bottom out the Actuator leave 2 to 3 degrees
before the off position)

The drawings above should clarify any confusion


about switch settings. The easiest way to set the
switches is to apply pressure with a small pointed
object until the switch clicks into position.

SW1 in the above drawing is in ON position, and


SW2 in the above drawing is in OFF position.

CAUTION!!
As a safety measure, the engine should be
equipped with and independent overspeed
shutdown device in the event of failure cutting
power to governor system.

NOTE
For some diesel engines, better operation may
be obtained by placing SW1 in ON position. If
difficulty experience in OFF position, try SW1
ON and recalibrate.

2. Non-Linear linkage to actuator is proper for best


operation on Gas Engine providing low GAIN at
light loads and high GAIN at heavy loads. But
linear in preferred for Diesel Engines.
______________________________________________________________________________________
4

EG1069X

3.4. Typical Wiring Diagram & Controller Installation Dimensions

ON

MAX

OFF
SW 1 2 3 4 5 6 7

SW1-OFF-DIESEL
SW1-ON -GAS
SW2-OFF-8000 ACT
SW2-ON -8200,8400 ACT
SW3-ON -12V OFF-24V

START-UP
FUEL
MAX

SW4-ON 250 - 1200 Hz

RAMP
TIME

KUTAI

DROOP

ELECTRONICS

SW5-ON 1200 - 2500 Hz

GAIN

SW6-ON 2500 - 5000 Hz

REMOTE
SPEED POT

SW7-ON 5000 - 9500 Hz


SW

1 2 3 4 5 67

INC

_
2

Black

ACT

8V

4V

ILS

10

MPU

11

Red

TP1 TP2

SPEED

5,

Black

White

Cable A
Red

Red

Black

Cable C

Cable B

_
R

DC Power

Magnetic
Pickup
CCW
5K

Cable C

CW

Wiring Drawing
Actuator

*The 5K remote speed potentiometer can be wired


two different ways: See Section 4.1.
1. Connect 5K potentiometer T to terminal #9.
Adjustable range is approximately 5% at 18000
RMP. (See Figure 3)
2. Connect 5K potentiometer through resistor R to
terminal #8. Reducing the value if R (499K)
increases the remote adjustable speed range.
(See Figure 3)

Figure 3

**Cable A, B, C -- should purchase a cable with a


wrapped Mylar supported aluminum foil shield
with a drain wire.
ON
OFF

1 2 3 4 5 6 7
DIP SW Positions

______________________________________________________________________________________
EG1069X

DIP Switch Description


SW1 OFF for Diesel Engine ON for Gas Engine
SW2 OFF for DYNA8000 actuator
ON for DYNA8200 / 8400 actuator

SW3 OFF for 24V I/O, ON for 12V I/O


SW4 ON for

250 ~ 1200 Hz

SW5 ON for

1200 ~ 2500 Hz

SW6 ON for

2500 ~ 5000 Hz

SW7 ON for

5000 ~ 9500 Hz

*When one of the SW4~7 is ON, set others of SW4~7 OFF

Governor Controls
DROOP

Droop Rate Adjustment

GAIN

MPU Output Gain Adjustment

Engine Stability Adjustment

SPEED

Engine Speed Adjustment

START-UP FUEL

Start-Up Fuel Limit

RAMP TIME

Ramp Time

4. CALIBRATION OF DYN1-1069X
4.1 Connection Information
1 When using an ILS unit, the remote speed
potentiometer may be left connected to the
controller as shown in the Figure 3.
2 When an ILS unit is used, connect 3-wire
shielded cable to terminals 6, 7 and 8. Connect
drain shield wire is to terminal 10 at EG1069X
only. Other end of drain shield wire is to be cut off
and taped.

4.2 Calibrations and Adjustments


1. See Figure 3 for a reference guide before making
any adjustments of the potentiometers, DROOP,
I, GAIN and SPEED.
2. Power OFF - engine not operating.
3. Initial potentiometer settings:
Set the I adjustment three divisions from zero
and the GAIN at the second division from zero.
For isochronous operation, set DROOP
counterclockwise to minimum position as shown
in Section 3.3 and 3.4.
For
DROOP
operation,
set
DROOP
potentiometer clockwise to obtain desired
amount of DROOP from no-load to full load.

Turning potentiometer
DROOP.

NOTE

clockwise

increases

If the full 35 rotation of the actuator shaft is


used and the linkage adjusted to use only the
active fuel range, the maximum obtainable
DROOP would be approximately 12% at full
load.
4. If a remote speed potentiometer is used for
narrow range, set it to mid-range. If the remote
speed potentiometer is connected to terminals 6,
7 and 9, a resistor R in the wiper is not needed.
This will provide approximately a 5% adjustable
speed range.
5. Start the engine.
Adjust the controller speed potentiometer until
the engine is operating at the desired engine
RPM. Clockwise increases engine RPM.
If the governor system is unstable, slightly reduce
the GAIN setting.

NOTE
Except for the speed adjustment, the
potentiometers have internal stops at the 0 and
100% positions.
6. With the engine unloaded, finalize the settings, I
and GAIN adjustments as follows:
(1) Turn the GAIN adjustment clockwise slowly until
the actuator lever oscillates. (One may need to
disturb the actuator lever to cause oscillation.)
(2) Reduce
the
GAIN
adjustment
slowly
counterclockwise until the lever is stable. Upset
the lever by hand..
(3) If the lever oscillates 3 to 5 diminishing
oscillations and stops, the setting is correct
(4) If system performance to load changes is
satisfactory, omit step (5) and (6).
(5) Reduce the GAIN setting counterclockwise one
division. Next, turn the I adjustment fully
clockwise while observing the actuator lever.
(6) If the lever does not become unstable, upset it by
hand. When the lever slowly oscillates, turn the
adjustment counterclockwise slowly until the
lever is stable.
(7) Upset the lever again; it should oscillate 3 to 5
times and then become stable for optimum
response.

______________________________________________________________________________________
6

EG1069X

5. TROUBLESHOOTING CHART
PROBLEM

CORRECTIVE ACTION

Governor is completely dead


and actuator lever stays at
minimum position when power
is applied to governor.

1. Check battery voltage at terminals 1 and 2 on controller. Terminal 1 is


positive. Check battery connections and contacts for turning power
ON to the controller.
2. Check for proper linkage setup. Correct and free linkage.
3. Magnetic pickup signal absent or too low. Measure AC voltage across
terminals 10 and 11 while cranking the engine. Voltage should be min.
2.5 VAC.
NOTE:
The voltmeter should have an impedance of 5000 ohms / volts or
higher. Check pole tip gap over gear tooth. Should be 0.037 mm ~ / 0.127 mm.
4. Measure the resistance of the magnetic pickup coil. This should be
above 150 ohm. If there is an open or shorted coil, replace the
magnetic pickup.
5. Measure the resistance of each pin to the metal case of the magnetic
pickup. No continuity should be evident. If there is continuity to the
case, replace the magnetic pickup.
6. DC supply OFF. Place an insulated jumper between terminals 2 and 3
(TP1 and TP2). With DC ON, the actuator should go to full stroke. DC
voltage at terminals 4 and 5 should be within 3voltas of the supply. If
the actuator still does not move to full stroke, continue with steps
below.
7. Measure actuator coil resistance:
If actuator coil is open or shorted to case, replace the actuator.
If governor still does not operate, continue with steps below.
8. Measuring the resistance of each coil lead to the actuator case should
indicate an open circuit on a low scale of the ohm meter. If continuity is
defected, replace the actuator.
9. With DC to the governor ON and the engine OFF, measure the DC
voltage from terminal 6(+) to terminal 2(-). This should be approx.
8VCD. If 8 VCD is not present, replace the controller.
10. Between terminal 7(+) and terminal 2(-), the voltage should be
approx. 4 VDC. If 4VDC is not present, replace the controller.

Actuator goes to full stroke


when DC power is turned on
(Engine is not operating)

1. Check magnetic pickup leads for proper shielded wire or open shield.
Verify and correct wiring as necessary. Be sure there is no jumper
between terminals 2 and 3.
2. Failsafe circuit in the controller may be damaged or defective. Replace
EG1069X.
3. With DC power OFF remove leads at actuator. Check continuity of
each terminal to case. There should be no continuity between any
terminal and case of EG1069X. If continuity is defected, replace the
controller.
4. If remote speed potentiometer has been connected to terminals 6, 7
and 9 of the controller, disconnect these leads. Turn DC power ON to
the governor if the actuator is now normal. Proceed to corrective
actions for the next problem.

______________________________________________________________________________________
EG1069X

PROBLEM

CORRECTIVE ACTION

Improper
operation
from
remote speed potentiometer

1. Investigate wiring to remote speed potentiometer for open or shorted


circuits. Checking wiring.
2. If the leads at terminals 6 and 7 to the remote speed potentiometer are
reversed, speed control by the remote speed potentiometer will be
reversed. Correct wiring.
3. Lead wire to remote speed setting potentiometer should be 3-wire
shielded cable. Verity that the drain shield wire is isolated from ground
at the potentiometer. If terminal 7 lead to the remote speed
potentiometer is open, engine speed will go high. Correct the wiring.
4. If lead 9 (wiper lead to remote potentiometer) is open, there will be no
control by the remote speed potentiometer. Verify and correct wiring.
5. If lead 6 to the clockwise terminal of the remote speed potentiometer
is open, speed will remain at the value set in EG1069X.

Erratic governor operation

1. Measure DC voltage at 1 and 2 on controller terminal strip. Normal


battery voltage should be indicated. If nominal voltage is present,
wiring is correct.
2. Low battery voltage 20% below rated can cause erratic operation.
Check battery and charging system.
3. RFI noise due to incorrect shielding. Correct wiring.
4. RFI noise fed through power supply leads. Connect power leads
directly to the battery.

Slow, small amplitude hunting


of speed or frequency

Sticking or very loose linkage. Correct linkage.

Fast oscillation of governor


linkage

Verity calibration setting of the controller. Readjust setting as necessary.

Engine will not start Actuator


goes to full fuel during cranking

1. Make sure fuel is available. Check fuel to engine. Check for correct
wiring to the automatic shutdown circuits.
2. Air may be trapped in fuel line. Check fuel lines for leaks.
3. Try to operate engine manually.

P.S. Please use the fuse of the original plant.

______________________________________________________________________________________
8

EG1069X

You might also like