HVDC Offshore Wind Farm
HVDC Offshore Wind Farm
HVDC Offshore Wind Farm
DIgSILENT PowerFactory
Abstract
This paper discusses the modelling of an
HVDC link for a 400 MW offshore wind farm
consisting of DFIG wind turbines. Voltage
source converters (VSC) are used for the
HVDC connection. The paper covers load
flow calculation and time-domain simulation
(RMS and EMT).
Content
Base Model
The following sections will describe the results which can be obtained using the dif-
3.1
Short-Circuit Calculation
In the study case 02 Short Circuit Calculation of the HVDC Offshore Wind Farm
example the short-circuit calculation is presented. Please press the Calculate ShortCircuit button ( ) to execute the shortcircuit calculation.
Since the IEC 60909 standard does not reflect the fault behaviour of modern wind turbines, the DIgSILENT Complete Method is
used to calculate their short-circuit contributions. The quantities Ik00 , Ib , Ith etc. are
calculated, which express the stress on the
grid elements. In this study case, settings
have been selected for the Complete Method
short-circuit calculation which are similar to
those of IEC 60909 (c = 1.1 for max. shortcircuit currents; loads, capacitances of lines,
magnetizing currents of transformers, shunt
elements and filters are ignored in the positive sequence). In addition, settings have
been applied which take the short-circuit
contribution of the wind turbines into account
accurately. Accuracy is achieved by using
current iteration to calculate the transient
short-circuit current Ik0 . In this current iteration the additional reactive currents provided
by the wind turbines are taken into account
precisely, based on the k factor setting and
the max. current of each turbine/converter.
Ib and Ith are calculated on the basis of
Ik00 and Ik0 . Please note that the option
Current Iteration has been activated on the
Advanced Options page of the short-circuit
command dialogue!
3.2
3.3
3.4
HVDC Control
4.1
The composite model of the onshore converter control is based on the frame definition
Frame onshore VSC which is displayed in
Figure 6. Each block represents an element
in PowerFactory . The chopper control with
the two DC valves is marked in red. Besides
the chopper control, there are two more controllers in the composite model. These are
the Main Controller and the Current Controller. All controllers will be described in the
following sections.
4.1.1
Main Controller
4.1.2
Current Controller
4.1.3
Chopper Control
4.2
Offshore Control
The offshore controller has to build the offshore grid voltage. This means the controller
has to keep the frequency and the voltage
magnitude of the AC offshore network at a
constant value. The resulting active and reactive power which flows through the converter cannot be controlled (the converter is
the slack in the offshore system).
4.2.1
The definition of the frame used for the composite model of the offshore controller is
shown in Figure 11. There are measurement devices used for detecting the offshore
AC voltage, the AC current of the converter
and for the DC voltage (positive and negative). There is also a PLL (phase locked
loop) measurement device, but this element
should only be in service for EMT simulations (this is managed in the project via a
Variation).
4.2.2
4.3
References
[1] S. Weigel, B. Weise, M. Poeller:
Control of Offshore Wind Farms with
HVDC Grid Connection, 9th International Workshop on Large-Scale Integration of Wind Power into Power Systems as well as on Transmission Networks for Offshore Wind Power Plants,
Ubertragungsnetzbetreiber
(Network and System Rules of the German
Transmission System Operators), VDN,
Berlin, 2007
HVDC Template
Figure 5: Single line diagram for the HVDC system as modelled in PowerFactory
10
Value
1.15
0.1487
0.001
0.05
12
100
0
1
2
10
0.1
1
0.1
1
1.1
Unit
p.u.
p.u.
s
p.u.
1/s
1/s
s
p.u.
p.u.
p.u.
Description
Max. internal voltage allowed
Series reactor impedance
DC Voltage Filter Time Constant
Gain for Droop Control
Gain of PID Droop-Controller (Q and Vac)
Integral Constant of PID Droop Controller (Q and Vac)
Derivative Constant of PID Droop Controller (Q and Vac)
0 = ctrl. acc. MODE, 1 = ctrl. acc. TC 2007 [3]
Reactive current gain in fault mode
Gain of DC PI Controller
Integral Time Constant of DC PI Controller
Max. reactive current in fault case
Voltage Deviation to enable Fault Mode
0 = voltg. ctrl., 1 = droop, 2 = Q ctrl.
Current Limit
11
12
Value
1.0000
0.0020
-3.0000
3.0000
Unit
p.u.
s
p.u.
p.u.
Description
Proportional Gain for d & q axis
Integral Time for d & q axis
min limit Pm for d & q axis
max limit Pm for d & q axis
Value
1.20
1.10
Unit
p.u.
p.u.
Description
Threshold for Chopper Connection
Threshold for Chopper Disconnection
Value
2.00
0.20
2.00
0.02
1.00
0.005
99.00
0.00
0.03
-0.70
-0.10
0.70
1.10
1.00
Unit
p.u.
s
p.u.
s
p.u.
s
p.u.
p.u.
p.u.
p.u.
p.u.
p.u.
p.u.
1/s
Description
Proportional Gain for Voltage Controller
Integrator Time Const. for Volt. Controller
Proportional Gain for Current Controller
Integrator Time Const. for Cur. Controller
Reference Frequency
Time constant for PT1-Filter
Upper Udc Limit for Frequ. Lifting (high value disables function)
Lower Udc Limit for Frequ. Lifting
Value of Frequ. Lifting
Min Limit Value for Current Limitation
Min Limit for Offshore Voltage
Max Limit Value for Current Limitation
Max Limit for Offshore Voltage
Gradient for Frequ.
13